KHU-10-YE_-EFE-EA_-000
CLIENT:
PROJECT:
2
1
2012-08-03
2012-07-11
Design
Information and comments
AOX
AOX
DBC
DBC
REV
DATE
DESCRIPTION
EDITED
CHECKED
Domingo
Beato
2012.08.03
13:41:35
+02'00'
MIR
MIR
Ana Martinez-Vara de
Rey
por ausencia
2012.08.03 14:10:22
+02'00'
APPROVED
Project:
Title:
448-10-F-E-01000
KHU-10-YE_-EFE-EA_-000
Purpose of issue:
Design
Prepared:
Reviewed:
Approved:
Issue: 2
Date: 2012-08-03
Alicia Rosa
Lucena
2012.08.03
13:37:25 +02'00'
AOX
DBC
Domingo Beato
2012.08.03
13:42:32 +02'00'
MIR
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is to be used solely for the Project and the purpose for which it is furnished.
It may not be disclosed to others for a different use without the written permission of Empresarios Agrupados Internacional,S.A.
Issue 2
EA No.: 448-10-F-E-01000
Page I
CLASSIFICATION
Contains information for the design of structures, systems or components: Yes
Design verification : Not applicable
Head of OU/Supervisor
Verifier Level 1
No
Level 2
CONTROL OF MODIFICATIONS
Issue
1
2
Modifications
First Issue
As indicated by vertical line in the margin
Paragraphs
Subject
Status
Internal
No. copies/Format
DISTRIBUTION
External
1 pdf
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page i
CONTENTS
Page No.
1.
2.
3.
4.
5.
4.1
4.2
00139289
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
1.
Issue 2
EA No.: 448-10-F-E-01000
Page 1-1
PURPOSE
The purpose of this study is the coordination and setting of the protection relays for
the transformers, cables, busbars, motors and other loads in the 6.6 kV and 415 V
systems.
This study affects all phase and ground overcurrent protection, motor protection and
minimum voltage detection relays.
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
2.
Issue 2
EA No.: 448-10-F-E-01000
Page 2-1
LIST OF DATA
2.1
DATA
2.1.1
6.6 kV System:
-
Is =19.5kA
600A
415 V System:
-
Contribution of transformers:
Contribution through the power centre transformer 10BFT11 and
10BFT12: 42.5 kA
2.1.2
2.1.2.1
Manufacturer:
SIEMENS AG
Rated power
3400 kW
Rated current
340 A
Acceleration time:
Rated voltage:
7 seconds
14 seconds
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-2
18/16seconds
26/29 seconds
Cold:
2.1.2.2
Rated power
315 kW
2.1.3
Transformers Data
2.1.3.1
Power:
15 MVA ONAN
Rated voltage:
15 kV 5% 2.5% / 6.9 kV
Ground
Connection type:
Dyn11
2.1.3.2
Rated power:
Rated voltage:
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
2.1.3.3
Issue 2
EA No.: 448-10-F-E-01000
Page 2-3
Rated power:
2500 kVA
Rated voltage:
Ground:
Rigid to ground
Zcc:
2.1.3.4
Rated power:
200 kVA
Rated voltage:
Connection type:
Dyn1
Ground:
Rigid to ground
2.1.4
Other Data
2.1.4.1
Current Transformers
In MV, all current transformers shall be 5P10 (at In the error is 1% and at 10 In it is
5%), except the following, which is 5P20 (at In the error is 1% and at 20 In it is 5%):
for incoming busbar from auxiliary transformers and coupling between MV busbars.
In LV, all current transformers shall be 5P10 (at In the error is 1% and at 10 In it is
5%).
2.1.4.2
Feeders consumption
Electrical heater
200 kW
45 kW
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
2.1.4.3
Issue 2
EA No.: 448-10-F-E-01000
Page 2-4
Diesel Generator
1250 kVA
Rated voltage:
415 V
Power factor:
0.8
2.1.5
2.1.5.1
1 to 6250 A
(0.4 1.3) x IN
1 to 6250 A
Phase sensor:
1 or 5 A
220 V to 250 kV
0 to 100%
50 to 300%
1 to 120 min
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-5
5 to 600 min
0 2.25 4.5 9
50% Ib Is 500% Ib
Tripping curve:
Definite time:
0.1 IN Is 24 IN (A)
Time dependent:
Definite time:
Time dependent:
Curve:
Definite, IDMT
Definite time:
10% Ib Is 500% Ib
IDMT:
10% Ib Is 50% Ib
Definite time:
IDMT:
0.1 1 sec
Tripping curve:
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-6
2A rating: 0.2A to 2A
20A rating: 2A to 20A
Definite time:
Time dependent:
For Iso< 0.4Ino, the minimum time delaty is 300ms. If a shorter time delay
is needed, use the CT+ CSH30.
1 6 hours
1 60
1 Nt
0 90 mn
Set point:
Time delay:
50 ms to 300 sec
Note:
2.1.5.2
Functions that are not specified are not used in this project.
Phase and ground protection relay type SEPAM series 60 from
Schneider Electric
Medium voltage busbars supply lines and Medium Voltage couplings (S60), MV
switchgear 10BBA11/10BBA12 Synchronization (MCS025).
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-7
1 to 6250 A
(0.2 1.3) x IN
1 to 6250 A
Phase sensor:
1 or 5 A
220 V to 250 kV
Tripping curve:
Definite time:
0.05 IN Is 24 IN (A)
Time dependent:
Definite time:
Time dependent:
Tripping curve:
Definite time:
Time dependent:
Definite time:
Time dependent:
Set point:
Time delay:
50 ms to 300 sec
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-8
Uns sync1:
Uns sync2 :
Synchro-check setpoints
Others settings:
Note:
0,05 a 0,5 Hz
Lead time:
0 a 0,5 s
Dead1 OR Dead2
Functions that are not specified are not used in this project.
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
2.1.5.3
Issue 2
EA No.: 448-10-F-E-01000
Page 2-9
Functions:
-
RATED
CURRENT
Instant Unit
Time Unit
5A
0.5 60 A
1A
STEPS
CURRENT
0.5 12 A
0.1 A
0.25 15 A
0.25 3 A
0.01 A
0.25 A
0.05 3 A
0.05 1 A
0.01 A
0.1 A
0.02 1.5 A
0.02 0.3 A
0.01 A
0.01 A
0.004 0.035 A
0.004 0.02 A
0.001 A
Earth
0.01 A
0.005 0.1 A
0.005 0.03 A
0.001 A
Earth
Precision:
-
Measurement:
5%
Defined times:
5% or 0.03 seconds
2.1.5.4
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-10
Functions:
-
(51N)
RATED
CURRENT
Instant Unit
Time Unit
5A
0.5 60 A
1A
STEPS
CURRENT
0.5 12 A
0.1 A
0.25 15 A
0.25 3 A
0.01 A
0.25 A
0.05 3 A
0.05 1 A
0.01 A
0.1 A
0.02 1.5 A
0.02 0.3 A
0.01 A
Precision:
-
Measurement:
5%
Defined times:
5% or 0.03 seconds
2.1.5.5
Low voltage: 415 V Station boards (10BFA11/12) incomings and coupling and
essential distribution board (10BMA11/12) coupling.
Curves: Inverse, very inverse and extremely inverse, etc., as per IEEE
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-11
Function 51PH, 51PL, 51N and 51G phase and earth time overcurrent:
-
Function 50PH, 50PL, 50N and 50G instantaneous phase and earth
over-current.
-
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-12
Dead/live levels for line and bus: 0.00 to 300.00 in steps of 0.01 V
Maximum voltage difference: 2.00 to 300.00 V in steps of 0.01 V
Maximum angle difference: 2.0 to 80.0 in steps of 0.1
Maximum frequency slip: 10 to 5000 mHz in steps of 10 mHz
Synchronism time: 0.01 to 600.00 s in steps of 0.015
Angle accuracy: 2
2.1.5.6
Four poles
400-630-800-2000 A
1-0.95-0.9-0.85-0.8-0.75-0.7-0.65-0.6-
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-13
10%
Accuracy (current):
Accuracy (current):
10%
Accuracy (current):
15%
2.1.5.7
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Page 2-14
EA No.: 448-10-F-E-01000
Issue 2
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
EA No.: 448-10-F-E-01000
Page 2-15
Unit number:
-
Issue 2
2.1.5.8
2.1.5.8.1
80-125-100-160-250 A
(0.625-1) In in 16 steps
Pick-up band:
1.05-1.2x Ir
(2-13) Ir in 10 steps
Pick-up band:
Im 20%Im
2.1.5.8.2
Thermal protection:
(0.8-1) In
Pick-up band:
1.05-1.3 x Ir
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 2-16
Magnetic protection:
-
(5-10) In
Pick-up band:
Im 20%Im
2.1.5.9
2.1.5.10
(10BFA11/12)
and
Essential
distribution
boards
Start voltage:
-
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
3.
Issue 2
EA No.: 448-10-F-E-01000
Page 3-1
HYPOTHESIS
3.1
The minimum inverse time margin for the maximum fault current
between electronic relays in the MV system shall be greater than or equal to 250 ms.
Time corresponding to breaker ...........................................
65 ms
85 ms
50 ms
50 ms
Total .................................................
250 ms
3.2
In order to ensure an adequate level of selectiveness, the precision of
the various relays and of the current transformers is taken into account.
3.3
The symmetrical current supplied to the Gas booster compressor shortcircuit taken into consideration for protection purposes is 20% higher than the locked
rotor current of the Gas booster compressor.
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.
Issue 2
EA No.: 448-10-F-E-01000
Page 4-1
RESULTS
4.1
4.1.1
KKS
10EKH10/20AP001
Service
Gas booster
compressor
Transform. ratio
T.I.
Phase
Ground
630/1
5P10
CSH200
Rated
Base Sensor
phase
current rating
current
Ib
INO
IN
630
391
Termal overload
Unit
(***)
Es2 Es0 T1
T2
100
126
21
Excessive
starting time and
locked rotor unit
K
Is
2.25 200
F (50/51)-1
Phase overcurrent
Unit
(setting A)
Phase overcurrent
Unit
(setting B)
Negative
sequence/unbalance
Unit
ST
LT
Curve
ISF1A
TF1B
Curve
ISi
TF1
20
DT
3635
Inst
11.5
DT
40
0.5
SIT
391
Curve ISO
DT
TO
P Nt Nh Nc Ta
15 0.1 1
LEGEND:
The phase sensors will be set at 1 A
ISF1A
Is
ISF1B
Ib
ST
TF1A
INO
LT
TF1B
Es0
Curve
ISI
Es2
T1
T2
(***)
IN
TFI
Iso
To
The alarm set point, ES1, must be disabled or inhibitted (setting: 300%)
Nt
NC
Nh
Ta
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 4-2
Note 1
Note 2
Note 3
Timer hold curve and Timer hold delay settings must remain in definite time and 0 miliseconds respectively, in phase overcurrent and earth fault units
Note 4
Note 5
Delay for locked rotor on start (LTS) setting must be disabled or inhibitted (setting: 300 sec), in excessive starting time and locked rotor unit
Note 6
As an explanation: Groups of settings A and B must be always active when using SEPAM M20
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.1.2
Issue 2
EA No.: 448-10-F-E-01000
Page 4-3
Service
Toroidal
Transformer
ratio
(In/1)
Rated
current
40/1
1A
0.25
(Inst)
LEGEND
I n:
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.1.3
Issue 2
EA No.: 448-10-F-E-01000
Page 4-4
KKS
10MBJ10
10BFT11/12
10XGA20AP001
Service
Transform.
Ratio
T.I.
F(50/51)-1
Rated
phase
current
IN
Sensor
rating
INO
Phase overcurrent
Unit
(setting A)
F(50/51)-2
Phase overcurrent
Unit
(setting B)
Earth fault
Unit
Phase overcurrent
Unit
(setting A)
Phase
Ground
Curve
ISF1A
TF1A
Curve
ISF1B
TF1B
Curve
ISF2A
TF2A
Curve
ISO
TO
Start up transformers
750/1
CSH200
750
SIT
722
DT
4619
0.1
DT
5280
inst
DT
10
Inst
300/1
CSH200
300
EIT
302
DT
1312
1.35
DT
4667
inst
DT
10
inst
60/1
CSH200
60
EIT
44
3.5
DT
455
inst
--
--
--
DT
10
inst
LEGEND:
The phase sensors will be set at 1 A
IN
ISF1A
ISF1B
ISF2A
TF1A
TF1B
TF2A
Iso
TO
INO
Curve
Note 1
Note 2
Note 3
Note 4
Note 5
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.1.4
Issue 2
EA No.: 448-10-F-E-01000
Page 4-5
Service
MV/LV station
transformers Neutral
1000/1
DT
3A
1.3 sec
LEGEND
I n:
Delay type:
Ie>>:
tIe>>:
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.1.5
4.1.5.1
Phase protection
Transform.
Ratio
T.I.
Service
Phase
1600/1
1600/1
1600/1
Issue 2
EA No.: 448-10-F-E-01000
Page 4-6
Rated
Rated
phase residual
current current
IN
INO
Ground
3CT+CSH30 1600
3CT+CSH30 1600
3CT+CSH30 1600
1600
1600
1600
F(50/51)-1
F(50N/51N)-1*
LEGEND:
IN
INO
Curve
Note 1
TF1
TF2
TF3
TO1
Note 2
Note 3
Timer hold curve and Timer hold delay settings must remain in definite time and 0 miliseconds respectively, in
phase overcurrent unit.and in earth fault unit
Note 4*
Harmonic 2 restraint setting must be enabled in earth fault unit for coupling 10BBA11/12 Busbars, Incoming to busbars 10BBA12 from Auxilary Transformers and Incoming to busbars
10BBA11 from Unit Auxilary Transformers
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 4-7
4.1.6
4.1.6.1
FUNCTION
RANGE
SETTING
Unsync1
110V
Unsync2
110V
dUs
3% Unsync1 to 30%Unsync1
5%
dfs
0.05 - 0.5 Hz
0.1 Hz
5 to 50
15
90%
20%
Voltage checking
On /off
On
dPhis
4.1.6.2
FUNCTION
RANGE
SETTING
Unsync1
110V (phase-phase
conection)
110V
Unsync2
110V (phase-phase
conection)
110V
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
FUNCTION
Issue 2
EA No.: 448-10-F-E-01000
Page 4-8
RANGE
SETTING
dUs
3% Unsync1 to
30%Unsync1
5%
dfs
0.05 - 0.5 Hz
0.1 Hz
5 to 50
15
70% Unsync1 to
110%Unsync1
90%
10% Unsync1 to
70%Unsync1
20%
Voltage checking
On /off
On
Dead1 OR Dead2
dPhis
4.1.7
4.1.7.1
VOLTAGE
TRANSFORMATION
(Vnp // Uns/3)
6600/3 // 110/3
(connection phase-toneutral)
Tripping
curve
TIME DELAY
(ms)
70% Vnp
Definite
50
Vnp:
Uns:
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.1.7.2
Issue 2
EA No.: 448-10-F-E-01000
Page 4-9
Relay type SEPAM series 60 (S60 for incoming from Unit Auxiliary
transformer 10BBT10 and Auxiliary transformer)
VOLTAGE
TRANSFORMATION
(Vnp // Uns/3)
6600/3 // 110/3
(connection phase-toneutral)
Tripping curve
TIME DELAY
(ms)
90% Vnp
Definite
50
FUNCTION
IDENTIFICATION
DELAY
27T2
2 seconds
Transfer initiation
27T1
2.1 seconds
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 4-10
4.2
4.2.1
Earth Protection
Instantaneous
Overcurrnet
(50PH)
Transf.
Ratio
CT (A)
Ts (s)
Curve
Ii
Ti (s)
4000/1
2.8
IEC C
3.5
1.1
4000/1
0.7
3.1
IEC C
2.8
2000/1
0.72
1.85
IEC B
2000/1
0.98
IEC B
SERVICE
Transf.
Ratio
CT (A)
Tst (s)
Curve
4000/1
0.66
1.1
Definite
time
0.95
4000/1
0.62
0.95
Definite
time
2.25
0.49
2000/1
0.49
Definite
time
2.9
0.64
2000/1
1.25
0.64
Definite
time
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 4-11
LEGEND
Is:
Ts:
Curve:
Ii:
Ti:
Ist:
Tst:
Curve:
Note:
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.2.2
Issue 2
EA No.: 448-10-F-E-01000
Page 4-12
KKS
Service
In
(A)
Settings
LT
ST
GF
Ie
Ir
LTD Band
Im
STDB Band*
If
GFDB Band**
10BFA11GS210
400
1 xIn (400A)
1x Ie (400A)
C-5
4xIr
1 xIn
10BFA11GS220
10BJA11 MCC++
800
1 xIn (800A)
0.75x Ie (600A)
C-10
4xIr+
1 xIn+
10BFA11GS310
10BJA13 MCC++
800
1 xIn (800A)
0.65x Ie (520A)
C-15
4xIr
1 xIn
10BFA12GS210
10BJA12 MCC++
800
1 xIn (800A)
0.75x Ie (600A)
C-10
4xIr+
1 xIn+
10BFA12GS220
10BJA14 MCC++
800
1 xIn (800A)
0.75x Ie (600A)
C-10
4xIr+
1 xIn+
10BFA12GS410
10BJA15 MCC+++
800
1 xIn (800A)
0.5x Ie (400A)
C-15
4xIr
1 xIn
10BFA12GS420
10BJA16 MCC+++
800
1 xIn (800A)
0.65x Ie (520A)
C-10
4xIr
1 xIn
LEGEND
Ie
Ir
Im
If
*
**
Note 1:
Note 2:
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.2.3
Issue 2
EA No.: 448-10-F-E-01000
Page 4-13
KKS
Service
In
(A)
Settings
LT
ST
GF
Ie
Ir
LTD Band
Im
STDB Band*
If
GFDB Band**
10BFA11GS320
10BMA11++
2000
1xIn (2000A)
0.9x Ie (1800A)
C-7
3.5xIr
15
1 xIn
13
10BFA12GS310
10BMA12++
2000
1xIn (2000A)
0.9x Ie (1800A)
C-7
3.5xIr
15
1 xIn
13
10BFA11GS410
Electrical heater+++
400
1xIn (400A)
0.8x Ie (320A)
C-3
2.5xIr
0.2 xIn
10BFA11GS420
Turbine crane+++
400
0.55x Ie (99A)
C-22
11xIr
0.2 xIn
1 xIn (800A)
0.5x Ie (400A)
C-15 5.5xIr
1 xIn
11BTL10
10BFA12GS320
400
0.95xIn(380)
0.75x Ie (285A)
C-15 9.5xIr
10
0.2 xIn
400
0.95xIn(380)
0.75x Ie (285A)
C-15 9.5xIr
10
0.2 xIn
LEGEND
Ie
Ir
Im
If
**
Note:
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.2.4
Issue 2
EA No.: 448-10-F-E-01000
Page 4-14
Normal and emergency lighting transformer 10BNT10 and 10BLT10 neutral protection 50G1: GE relay MIF II N
Settings
Current transformer
600/1
Pickup value
Type of curve
DELAY
(s)
3.8
Definite time
0.35
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.2.5
Issue 2
EA No.: 448-10-F-E-01000
Page 4-15
Note: for setting of thermal and magnetic relay of the motors fed from 10BMA11/12, see section 4.2.8.
4.2.5.1
Circuit Breaker/
Relay type
Service
FE 250A SMR1
FE 250A SMR1
Settings
In
(A)
LT
ST
Ir
Im
250
0.85xIn=212.5
9xIr
160
0.75xIn=120
6xIr
LEGEND
Ir
Im
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.2.5.2
Issue 2
EA No.: 448-10-F-E-01000
Page 4-16
Circuit Breaker/
Relay type
Service
FE 160A LTMD
FE 160A LTMD
Settings
In
(A)
Thermal Ir
Magnetic Im
Ir
Im
By-pass tranformer
125
0.9xIn=112.5
10 xIn=1250
160
0.9xIn=144
5 xIn=800
LEGEND
Ir
Im
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 4-17
4.2.6
4.2.6.1
Input mode
415/3/ 110/3
(connection phase-neutral)
Phase-to-ground
57
U:
T:
4.2.6.2
START VOLTAGE
(V)
DELAY
(S)
44.5
IDENTIFICATION
DELAY
27T1
3 seconds
Motor trip
27T2
2 seconds
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.2.6.3
Issue 2
EA No.: 448-10-F-E-01000
Page 4-18
TIMED UNIT
START VOLTAGE
(V)
DELAY
(S)
44.5
415/3 // 110/3*
IDENTIFICATION
DELAY
27T1
4 seconds
TRANSFER INITIATION
4.2.7
4.2.7.1
RANGE
STEP
SETTING
0 300 V
0.01 V
50 V
2 300 V
0.01 V
6.4 V
2 80
0.1
15
0.01 600 s
0.01 s
2s
10 - 5000 MHZ
10 MHZ
100 MHZ
NONE, DL-DB
LL-DB, DL-LB
--
LL DB
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
4.2.7.2
Issue 2
EA No.: 448-10-F-E-01000
Page 4-19
RANGE
STEP
SETTING
0 300 V
0.01 V
88 V
2 300 V
0.01 V
11 V
2 80
0.1
15
0.01 600 s
0.01 s
2s
10 - 5000 MHZ
10 MHZ
100 MHZ
NONE, DL-DB
LL-DB, DL-LB
--
LL DB
DL LB
4.2.7.3
4.2.7.3.1
RANGE
STEP
SETTING
50/60 HZ
N.A.
50
0-1
FREQUENCY
1-1
2-90 V
0.5 V
6.5
1-2
2-60
15
1-3
10-500 MHZ
10 MHZ
100
1-4
0.1-99.0 s
0.1 s
1-5
0.1-99.0 s
0.1 s
10
2-1
OFF-ON
N.A.
ON
2-2
VOLTAGE SUPERVISION
VOLTAGE
10-180 V
1V
57
3-1
40-245 V
1V
50 *
3-2
10-180 V
1V
30 *
THRESHOLD
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page 4-20
SETTING NAME
RANGE
STEP
SETTING
3-3
40-245 V
1V
50 *
3-4
10-180 V
1V
30 *
4-1
OFF-ON
N.A.
ON
4-2
OFF-ON
N.A.
OFF
4-3
OFF-ON
N.A.
ON
4-4
OFF-ON
N.A.
ON
5-1
CONFIGURATION
OUTPUT
OF
1ST
AUXILIARY
SEE TABLE 2
N.A.
5-2
CONFIGURATION
OUTPUT
OF
2ND
AUXILIARY
SEE TABLE 2
N.A.
Default values
4.2.8
The thermal tap at 1.15 times the motor rated current is selected.
The magnetic element is set to 6.5 x 1.5 x 1.1 = 11 times the motor rated
current.
where:
6.5:
The ratio between the motor start current and the rated current
1.5:
Asymmetrical component
1.1:
Relay tolerance
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
5.
Issue 2
EA No.: 448-10-F-E-01000
Page 5-1
REFERENCE DOCUMENTS
5.1
5.2
5.3
5.4
5.5
5.6
5.7
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
APPENDIX A
COORDINATION CURVES
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page A-i
CONTENTS
Pag.
1.
2.
1.2
2.2
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page A-1
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page A-2
Aux
transformers
(by others)
1000
Unit
Auxiliary
Transf.
R2
R1
R4
10BBA11
R5
R7
R3
10BBA12
R6
Gas Booster
Electric Fire
Compressor
Station
pump
Start up transformer
Isolation
Highest
Transf.
transformer
motor
100
R7
R5
Gas Booster
Compressor
Station
transformer
Isolation
Transf.
R7
R2
10
Time (s)
R6
R1
R5
R3
R4
1
0,1
Icc phase to
ground in MV
system (600A)
0,01
1
10
100
1000
Current (A)
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page A-3
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page A-4
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page A-5
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page
Issue 2
EA No.: 448-10-F-E-01000
Page A-6
This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page