Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Uniswitch

Medium Voltage Cubicle


Circuit Breaker Cubicle (CBC)
Uniswitch is an air insulated (AIS), metal
enclosed, switchgear cubicle design of
the next generation developed through
continous innovation and vision to meet
the changing market needs.

Switchgear for electricity distribution application such as:


Secondary Substations, Manufacturing, Shopping centres,
Airport, Small/Medium size Power Plants, Building, etc.

CBC

SF6 CB HD4/S

CBC-W

Vacuum CB VD4/S

Rated Voltage (kV)


Circuit Breaker Cubicle, fixed or withdrawable

The Circuit Breaker cubicle, type CBC & CBC-W is designed


for control and protection of distribution lines, network,
motor, transformer, capacitor banks, etc. The cubicle can be
equipped with a Vacuum or SF6 Gas Circuit Breaker. The
breaker is rail mounted and fixed or withdrawable type. To
achieve the disconnecting function a 3-position Load Break
Switch with an earthing switch is mounted between busbars
and the breaker.
The door is mechanically interlocked with the Load Break
Switch earthing position to provide personal safety. The
cubicle is designed to be equipped with CT and VT.

Unit

12

24

Basic Insulation Level (BIL)

kV

75

125

AC Withstand Voltage

kV

28

50

Rated Frequency

Hz

50/60

50/60

- Busbar

630/1250

630/1250

- Feeder

630

630

kA/1s

25

20

kA

65

50

IP3X

IP3X

+40

+40

+35

+35

-5

-5

1000

1000

Rated Current

Rated Short time withstand current


Rated Peak withstand current
Degree of Protection Enclosure
Ambient Temperature
- Maximum Value

oC

- Maximum Value of 24 h - mean


- Minimum Value
Altitude above sea level

(m)

Basic Equipment :
3 Position Load Break Switch
Operating mechanism with mechanical position indication
Neon indicator
Interlocking unit
Enclosure of busbar compartment
Busbars
Earthing Bar
Integrated low voltage compartment for secondary
components
Earthing Switch
Enclosure of cable compartment
Cable entry with cable support
Anti condensation heater
Standard Relay Protection
Functionality
Over-current
Earth-fault
Thermal overload for cables
Phase discontinuity protection
Circuit Breaker Failure Protection
Trip Lockout Function

ANSI

REF610

Arc-protection

Cubicle Dimension

CBC

Painting
Standard RAL 7032

Depth of Trenches for CBC


Cabling throught trenches with single core or three core
cables
Cable Dimention (mm2)

Bending radius (mm)

depth of trench (mm)

50/51

35

370

400

50N/51N

50

370

400

49

70

400

430

46

95

440

470

62BF

120

470

500

86

150

500

550

180

540

670

79

240

590

730

50/50NL

Trip Circuit Supervision


Auto-reclose for 1...3 shots

Optional Accessories :
Voltage Transformer
Auxiliary contacts (2NO+2NC)
Motor Operation device
Relay Protection
Plug in LV Connection for CBC
Metering
Surge arrester

CBC-W

Width (mm)

750

750

Depth (mm)

1155

1155

Height (mm)

1635/1885

1635/1885

Approximate Weight
(kg)

420

430

Test and Certificates


Type test according to IEC 62271-200 and certificated by
SATS
Routine test IEC 62271-200
Quality certificate ISO 9001
Environmental certificate ISO 14001

Informasi lebih lanjut hubungi:


PT. ABB Sakti Industri
Corporate Office Sales & Engineering
15th floor, World Trade Center I
Jl. Jend. Sudirman Kav. 29-31
Jakarta 12920, Indonesia
Phone : +62 21 2551 5555
Fax
: +62 21 2551 5566
Uniswitch Factory
Jl. Gajah Tunggal Km. 1,0
Tangerang 15136, Indonesia
Phone : +62 21 2559 5555
Fax
: +62 21 2559 5566
www.abb.com