Keypad Prepayment Energy Meter

and Vending System Solution

Shenzhen Inhemeter Co., Ltd.


www.inhemeter.com

Special Declaration
Copyright Inhemeter.All right reserved.
Sustainable product improvement is a policy in Shenzhen Inhemeter Co.,Ltd. Therefore, the
company reserves rights to change product operational details and specification. Contents of
this manual may be changed without notice. No part of the manual will be reproduced or
spread in any form or by any means for any purpose by any person or any other company
without permission in writing from Shenzhen Inhemeter Co., Ltd.
Trademark declaration
and other INHEMETER logos are trademarks of INHEMETER.
Other trademarks or registration trademarks mentioned in this document are possessed by
their respective owners.
VN:EKE201012-1

Index
Chapter1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9

Executive Summary
What Is Keypad Prepayment Energy Meter
Applicable Standards on Keypad Prepayment Meters
STS Certifications Obtained by Inhemeter
Terminology
Technical Features
Categories of Inhe Keypad Prepayment Meter
Security Mechanism of Keypad Prepayment Meter
Basic Function of Products

Chapter2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
2.14
2.15

4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8

16
16
19
20
21
21
21
23
24
26
31
34
38
40
40

Three Phase Keypad Prepayment Energy Meter ............................ 43

Technical Specification
Meter Shape Diagram
Meter Installation Diagram
Meter Installation Diagram
Wiring Diagram

Chapter4

1
2
3
5
7
8
10
12
14

Single Phase Keypad Prepayment Energy Meter ........................... 16

Introduction
Technical Specification
Meter Shape Diagram
Meter Installation Diagram
Terminals
Wiring Diagram
Meter Active Metering Accuracy
Basic Characteristics
Measurement Function
Special Functions
LCD Display
Operation Detail
Communication Port
Safety Regulation
Installation

Chapter3
3.1
3.2
3.3
3.4
3.5

Keypad Prepayment Meter ................................................................. 1

43
45
45
45
46

Split Keypad Prepayment Energy Meter ......................................... 47

Introduction
Customer Interface Unit (CIU)
CIU Technical Parameters
Measurement and Control Unit (MCU)
MCU Technical Parameters
Single Phase Split Keypad Prepayment Meter
Three Phase Split Keypad Prepayment Meter
Three Phase Split Type Measurement Box

47
48
48
49
49
50
51
51

Chapter5

DIN Rail Mounting Split Keypad Prepayment Energy Meter .......... 52

5.1 Introduction
5.2 Three Methods for Communication With MCU
5.3 Three Communication Modes With MCU
5.4 MCU Shape Drawing
5.5 MCU Installation Diagram
5.6 DIN Rail Mounting Diagram
5.7 MCU Terminals
5.8 MCU Typical Wiring Diagram
5.9 Characteristics
5.10 Single phase 2-wire/3-wire split type keypad prepayment energy meter
complying to ANSI
5.11 Single Phase ESKOM Keypad Prepayment Energy Meter
Chapter6
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10

52
53
53
55
55
56
57
58
59
60
60

SMARTVend Anywhere (System) .................................................... 64

Introduction
SMARTvend Characteristic
SMARTvend Structure
SMARTvend Compatibility and Scalability
Diversified Power Vending Module
SMARTvend Functions
Consist of System
Consist of ISVA
Servers Applicable
System Characteristic

64
64
64
65
66
67
67
68
68
69

Chapter7

AMR/AMM of INHEMETER................................................................ 70

Chapter8

Available Types of Keypad Prepayment Energy Meter .................. 72

8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8


Prepayment Energy Meters of Inhemeter


Order List of Single-phase Keypad Meter
Order List of Single-phase Split Type Keypad Meter
Order List of DIN rail-mounting Single-phase Split Keypad Meter
Order List of Single-phase ESKOM Keypad Meter
Order List of Three-phase Keypad Meter
Order List of Three-phase Split Keypad Meter
Order List of Related Software and Accessories
Contact with us

72
74
74
75
75
76
76
77
1

keypad Prepayment Energy Meter and Vending System Solution

Chapter1

Keypad Prepayment Meter

1.1 Executive Summary


With tightened supply of power and resources, energy saving and emission deduction have
become a common trend globally. To follow this global trend, electricity management authority
intends to use and implement prepayment metering system to achieve objectives of energy
saving, meter reading work load reduction and electricity fees collection improvement.
Prepayment metering system consists of Prepayment Electricity Vending Management
System and Prepayment meters.
Prepayment meter is such type of meter with which electricity consumer need to pay in
advance for electricity they consume.
Electricity Consumers can charge the electricity they purchased into meter through some
intermediary, meter will identify and process the data and supply Electricity to consumer
accordingly. When the credit in meter is nearly used up, meter will provide warning to
consumer to remind consumer for charging. when the credit in meter is completely used up,
meter will cut off power supply to realize prepayment (pay in advance, consume later) type
of electricity management.
Application of prepayment meter can successfully solve practical problems which Electricity
Management Authority are facing (such as problematic manual meter reading and hardship in
Electricity Fee collection).
Prepayment meter products developed and manufactured by Shenzhen Inhemeter Co., Ltd.
are of following two types

IC Card Prepayment meter

Keypad Prepayment Meter

Shenzhen Inhemeter Co.,Ltd. | Executive Summary

Keypad Prepayment Energy Meter and Vending System Solution

1.2 What Is Keypad Prepayment Energy Meter


Key-pad Prepayment Energy Meter is a prepayment meter which is using virtual intermediary,
i.e. token, as data exchange media.

Token means a code consists of 20 digits of numbers, such as 2837 5872 3731 6854 3423.
Based on amount paid by the consumer, a unique token will be generated by Vending
Management system. Consumer need to input this token into meter through keypad on meter
to complete credit transfer process. (meter will decode the token within meter as per
communication protocol)

Shenzhen Inhemeter Co.,Ltd. | What Is Keypad Prepayment Energy Meter

keypad prepayment meter and vending system solution

1.3 Applicable Standards on Keypad Prepayment Meters


IEC62055 is the only international standards available for prepayment metering system. The
standard is prepared by Standard Transfer Specification Association (established in 1997) of
South Africa. In 2005, as a result of STSA recommendation, Standard Transfer Specification is
recognized as a international standard, i.e. IEC62055.
IEC62055 series of standards covers payment collection management system, CIS customer
information system, vending management system, data transfer carrier, data exchange
standard, prepayment meter, interface standard and other related contents and all these
established

complete

system

frame

work

for

Prepayment

metering

system.

IEC62055consists of:
EC6205521

standardization structure

IEC6205531 Prepayment meters for Active Energy (Class 1 and 2)


IEC6205541 STS standard data transferring protocolApplication layer data transferring
protocol
IEC6205551

STS standard data transferring protocolPhysical layer data exchange

carriernumeric and magnetic card carrier


EC6205552

STS standard data transferring protocolPhysical layer data exchange

carriercommunication virtual carrier


As all Keypad Prepayment meter follows same standard and are certified for their compatibility
Shenzhen Inhemeter Co.,Ltd. | Applicable Standards on Keypad Prepayment Meters

Keypad Prepayment Energy Meter and Vending System Solution

with STS standard (they also use standardized security module encryption algorithm) ,
therefore all prepayment meters manufactured by different meter manufacturers are
compatible with each others vending systems so long as the vending systems are also STS
certified.
As the only open prepayment metering system standard in the world, STS (Standard Transfer
Standard) has been widely accepted and adopted as prepayment metering system standard in
more than 70 countries. The arrangement of authorized access of STS technology (by STSA)
also assures safety and security of their application by Electricity Utilities.
As only prepayment meter products which obtain STS certification can ensure its compatibility
with other meter manufacturers STS certified prepayment metering system, Keypad
prepayment meter products of Shenzhen Inhemeter Co., Ltd. are also STS certified and the
manufacturers code is 37.
Inhe meters Keypad prepayment metering products also comply with following standards:


IEC 62052-11 2003

General requirement for Electricity measurement equipmentAC

test and test conditions, part 11, measuring equipment




IEC 62053-21 2003 Special requirement on Electricity measurement equipmentAC,


part 21, special requirement on static active electricity meters (class 1 and 2)

SANS 1524-1 2005

National Standard of South Africa for prepayment metersSABS

certification


ESKOM SCSSCAAA9

Prepayment meter technical requirement of ESKOM, South

Africa


ESKOM TRMSCAAP2 Prepayment meter technical requirement of ESKOM, South Africa

BS 5685

British Standard type of wire Connection

DIN 43857

Deutsch Standard type of wire Connection

IEC60529 2001 Meter casing protection class

Shenzhen Inhemeter Co.,Ltd. | Applicable Standards on Keypad Prepayment Meters

keypad prepayment meter and vending system solution

1.4 STS Certifications Obtained by Inhemeter

Shenzhen Inhemeter Co.,Ltd. | STS Certifications Obtained by Inhemeter

Keypad Prepayment Energy Meter and Vending System Solution

Shenzhen Inhemeter Co.,Ltd. | STS Certifications Obtained by Inhemeter

keypad prepayment meter and vending system solution

1.5 Terminology
Shenzhen Inhemeter Co.,Ltd. | Terminology

Keypad Prepayment Energy Meter and Vending System Solution

1.5.1

MCU

MCU (Metering and control unit) for single/three phase integrated/split keypad prepayment
energy meter, installed outdoors, is the main body of meter. Its installation complies with meter
installation requirement and also supports Rs485 communication, infrared communication and
Power Line Carrier Wave Communication (PLC). MCU can have LCD display to display all
measured data such as accumulative kWh reading, history monthly kWh consumption, credit
charged, credit balance, load profile, warning/alarms and other data. Through different
communication means, MCU can also be programmed for it operation parameters or switching
tariffs under stepped multi-tariff arrangement.

1.5.2

CIU

CIU is customer interface unit used for single phase, three-phase split keypad prepaid energy
meter. It is installed indoor, which is convenient for user to learn meter operation parameters
and load pre-purchased energy(credit).

1.6 Technical Features


Main reason for widely acceptance of STS keypad prepayment meters is due to its salient
technical feature of virtual token data transferring system.

1.6.1

Feature of STS


STS is prepayment technology based on virtual token data exchange technology,


which fits development trend of future communication technology.

STS data transfer standard is used to define process of transferring available


credit to electricity meter. it can also be used in water meter, gas meter and other
utility meters.

STS is a secured message system which is used to exchange data between


vending point and meter.

STS is an open and secured transferring standard world wide and use IEC
62055-41 as the only intonation standard for prepayment system.

Encryption key technology provided (classed encryption key which is managed by


Utility themselves).

Every TOKEN, meter, vending point and prepayment metering system is


protected by different levels of security control.

Reliable encryption system, technically reduced possibility of being attacked.

Multi-system structure ensures its timely updating technically.

Products in system has to obtain STS certification.

Transferring process of charging token in the system is secured and reliable.


Even in case of repeated transferring, meter will accept the data only once.
information will be effected only once and only to the meter for which TOEKN is
generated.

Shenzhen Inhemeter Co.,Ltd. | Technical Features

keypad prepayment meter and vending system solution

STS prepayment meter already installed and used by hundreds of Utilities world
wide.

Use of STS ensures the compatibility between meters manufactured by different


manufacturers.

Utility

can

purchase

products from

any

STS

certified

manufacturer or vending system supplier freely and need not worry security of the
system.

1.6.2

Features of keypad meter




International STS certification

20 digits of virtual token

Support TOU (Time of use) and Stepped tariff function.

Multiple credit balance alarm (local warning, Short message service and email).

Overload disconnection/load control.

Emergency overdraft function and friendly non-disconnection function

Anti-stocking of credit function.

Build-in RS485 or PLC communication module, support remote charging.

When remote charge fails, also support local keypad charging and infrared
communication.

1.6.3

Meter is installed in meter box, consumer can not and need not to touch meter.

Build-in reliable relay, support relay failure detection and warning.

Anti-tamper function.

Consumer consumption history information inquiry.

Easy to adopt split type design.

Strength of Networked Prepayment Management System Based on


STS Standard


AMR system and prepayment management system can be integrated into one
common purpose system.

Based on advanced virtual token data transferring technology of internationally


accepted IEC standard, the system can support multi-means of credit charging
and can be easily integrated in technology newly developed.

Credit charge virtual token can be transferred with IC card, paper note, infrared
communication and PLC communication.

With help of networking technology, meter credit charging becomes as


convenient as mobile phone credit charging. credit charging can be done both
remotely and locally.

No card is required in process so that consumer can be released from headache


of card management.

System security is approved and certified by IEC.


Shenzhen Inhemeter Co.,Ltd. | Technical Features

Keypad Prepayment Energy Meter and Vending System Solution

Automatic report of abnormal behavior of meter, all information can be inquired


via report.

Insufficient credit can be alarmed to consumer via SMS or email.

TOU tariff information and Stepped tariff information can be updated remotely.

Prepayment, consumer data collection and Multi-tariff (TOU/Stepped tariff)


application can be provided at the same time.

1.6.4

Flexible Credit Purchase Means




SMS self serviced credit purchase.

Credit purchase via internet.

Vending station purchase.

Scratch card purchase.

Credit charging via Convenient store POS machine.

Credit purchase via purchase of charging card.

Self-serviced credit purchase via internet banking.

Credit purchase via Call center/special service telephone number.

Credit purchase via ATM

1.7 Categories of Inhe Keypad Prepayment Meter


10

Shenzhen Inhemeter Co.,Ltd. | Categories of Inhe Keypad Prepayment Meter

keypad prepayment meter and vending system solution

Based on phases of consumer




Single phase keypad prepayment meter

Three phase keypad prepayment meter

Based on installation method




Single phase integrated type prepayment meter.

Single phase Split type prepayment meter.

Three phase integrated type prepayment meter.

Three phase Split type prepayment meter.

Based on standards meter comply with




IEC standard complied, BS5685 wiring or DIN43857 wiring Single phase


integrated type prepayment meter,

Single phase Split type prepayment

meter, Three phase integrated type prepayment meter and Three phase
Split type prepayment meter.



ANSI standard complied Single phase Split type prepayment meter


DIN rail installation requirement complied Single phase Split type
prepayment meter

South Africa ESKOM installation requirement complied Single phase keypad


prepayment meter.

Installation diagram of integrated type keypad prepayment meter

Shenzhen Inhemeter Co.,Ltd. | Categories of Inhe Keypad Prepayment Meter

11

Keypad Prepayment Energy Meter and Vending System Solution

Installation diagram of split type keypad prepayment meter

1.8 Security Mechanism of Keypad Prepayment Meter


Keypad prepayment meter use standard classified encryption key encryption technology.
Every token, every meter, every vending station and vending system are protected by different
security key of different security class. The reliable encryption key system can effectively
minimize opportunity of being attacked.


KMCKey Management Center, management authority who are managing


encryption keys of various Utilities, Supply Groups and meter manufacturers and it
is a neutral third party.

Meter manufacturermeter manufacturer must become member of STSA,


manufacturers ID is assigned by STSA, otherwise their product will not be able to
work with system.

Utility Supply Groupevery prepayment system which is using STS technology


must apply for SGC (Supply group code).

STSAStandard Transfer Specification Association, responsible for managing


membership application issues.

Encryption key card manufacturermanufacturer of vending system encryption


key cardthe card is used to encrypt data of power vending and is the main part for
system security.

CMMSecurity module manufacturer

POSpoint of sales

1.8.1


Vending System Encryption Key


VDDKVending Default Keydefault vending key to meter manufacturer at the
time of application. This key is unique for each meter manufacturer and is issued
by KMC. With this VDDK, manufacturer can generate factory defult key of their

12

Shenzhen Inhemeter Co.,Ltd. | Security Mechanism of Keypad Prepayment Meter

keypad prepayment meter and vending system solution

meter product, i.e. DDTK.




1.8.2


VUDKVending Unique Key, with VUDK unique vending key can be generated.

Prepayment Meter Encryption Key


DITKInitialization keyopen encryption key of meter manufacturers, used in
meter manufacturing process and repairing process, managed by meter
manufacturer.

DDTKDefault keyused in the process delivering meter from manufacturer to


SGC. This key is generated from unique manufacturers vending key (VDDK)
assigned to each meter manufacturer by KMC and is loaded into meter when meter
is in ex-work/ready for delivery status. This DDTK can only be changed with POS
provided by the manufacturer of the meter (the party who owns the unique VDDK)
and the key is defaultly generated by vending encryption card together with KMF
supplied by KMC.

DUTKUnique keyused in meter daily operation, credit purchase and credit


loading. DUK, when used together with vending key AUDK, is used to encrypt or
de-encrypt meter application function, i.e. encrypt or de-encrypt STS code
transferring function. After accept the meter products from meter manufacturer,
Utility need to replace DDTK with DUTK.

1.8.3


Security Principle of Encryption Key


Generation of all keys are centrally controlled. Security of the keys of all SGCs are
assigned and ensured by KMC. Utility need not to invest resources in managing
Shenzhen Inhemeter Co.,Ltd. | Security Mechanism of Keypad Prepayment Meter

13

Keypad Prepayment Energy Meter and Vending System Solution

generation and security of keys. Generation and transferring process of all kinds of
keys (irrespective Vending system key or meter key) are all performed in encrypted
status, therefore. in any case, the contents of the key itself can not be interpreted
directly.


All the data are transferred in form of encrypted contents to prevent these contents
from being interpreted. Following principles of security and practical, the key is so
designed to facilitate operation and control of meter after the security requirement
is satisfied.

All the meters have unique key. With the help of above mentioned key
management flow, we can understand the distributed and related relation among
key, meter serial No., key version No., tariff index No., SGC and key type. these
relations ensured that one unique encryption key to one meter and as there is no
root encryption key present in vending system, security of the system will not be
threatened from root key side.

Security arrangement facilitate the building of vending system as it can be used in


both PC version of vending system and networked vending system which is
operating in internet environment and with banking system.

By using public key in meter manufacturing process and private key in meters
working status, as well as controlling meter working status key with SM which is
actively generating working status key with file provided by KMF, the system not
only successfully separated the security in meter manufacturing process and the
security in meter working status, but also successfully separated the meter
manufacturer and Utility. System security and safety is completely assured.

1.8.4


Security Certification
Product certified has already obtained certification from highest international
security certification authority.

Systems Security is as safe as Banking system, certified by NIST (National


Institute of Standards and Technology) and FIPS (Federal Information Processing
Standards)which is also the certifying authority for banking system security
systems.

STS system have used several encryption algorithms including DES3DES and
STA.

In the process of transferring encryption keys, 3DES encryption algorithms has


been used.

Generation of charge token adopts STA special encryption algorithm, which is


similar to DES encryption algorithm. the interchange table of each manufacturer is
also allocated and controlled by STSA.

1.9 Basic Function of Products


Keypad prepayment meter products series of Inhemeter is a new generation of products which
adopt advanced technology of measurement, control and communication. They can provide
14

Shenzhen Inhemeter Co.,Ltd. | Basic Function of Products

keypad prepayment meter and vending system solution

not only accurate measurement of energy, but also reliable control on electricity charge
collection. Inhemeters keypad prepayment meter products (including single and three phase
keypad prepayment meter, MCU CIU etc.) have following basic functions:



20 digits TOEKN complies with STS specification.


Measurement, calculation and storage of active energy, Reactive energy (for three
phase meter), apparent energy and related parameters (voltage, current, frequency,
demand, power).

TOU (time of usage) function provided: support programmable tariff scheme.

Historic data storage function provided: last 12 months data stored.

Event record functioncan record event such as terminal cover open, meter cover
open, power loss, phase loss, tariff change, meter date/time calibration, MD reset,
battery replacement and external magnetic influence.

Anti-tamper function providedcan detect and record tamper behaviors such as


reverse current and circuit bypass.

Load control function provided, for different types of consumers, different load
control threshold can be programmed to control their consumption.

Visible/audible Low credit balance (in energy units/in monetary units) warning
signal provided, pre-warning and warning threshold credit balance level
programmable.

Overdraft electricity switch provided.

Minimum charity electricity consumption (basic electricity use) function provided.

Disconnection disable function at night (or predefined periods), in holidays and


weekends provided

Peak hour load control facility provided.

IP54 protection provided for outdoor use MCU and IP51 protection provided for
indoor use CIU.

Large size, wide visible angle, wide working temperature range LCD screen with
backlight

Display items programmable

Braille characters and key stroke tone provided on keypad

Load threshold programmable

15 years life

STS certified

KEMA certified

Shenzhen Inhemeter Co.,Ltd. | Basic Function of Products

15

Keypad Prepayment Energy Meter and Vending System Solution

Chapter2

Single Phase Keypad Prepayment Energy Meter

2.1 Introduction
INHEMETER Single Phase Keypad Prepayment Energy Meter is for residential or commercial
use. It has been certified with STS (Standard Transfer Specification) regulation, and can
accept 20 digits STS code inputting. Adopts IEC62053, IEC62055 and IEC62056 standard,
and its design and production comply with ISO9001 standard.
Meter circuit design, structure design, choice of components and materials are made
according to allowable greater environment tolerance for reliable guarantee of lasting and
stable operation of meter. Metering components take shield protection measures in structure
design, which can resist interference of external DC and AC magnetic field, over-voltage and
high frequency electromagnetism field. Energy meter is with good electromagnetism
compatibility. These designs guarantee metering reliability and lasting stability, other
influences can be neglected and metering is highly reliable. Therefore, this meter do not need
to be calibrated during its whole life period.
Meter cover is made of fire retardant, flame resistant
and heat deformation resistant polycarbonate material.
The material is recyclable and friendly to environment.
Meter cover is double insulated and compliance with
IP54(IEC60529). Meter terminal is made of brass
material, and plated with nickel as tropical climate
energy meter. Terminal cover can be either short type
or extendable type, and fastened by a sealing screw.
Meanwhile, it can record events of opening terminal
cover after installation. Meter wiring complies with
DIN43857 and BS5685 standards.
The Meter can measure single phase two wire active AC electricity with frequency of 50Hz or
60Hz.

2.2 Technical Specification


ModelDDZ1513
Description
Technical standard

Specification
IEC 62052-11 2003
IEC 62053-21 2003
IEC 62055-31 2005
IEC 62055-41 2007
SANS 1524-1 2005

16

Shenzhen Inhemeter Co.,Ltd. | Introduction

keypad prepayment meter and vending system solution

ESKOM SCSSCAAA9
Meter Type

Single-phase two wire direct access type meter


Forward and reverse active electrical power are all included

Active energy computation

in forward active electrical power


Reverse

active

electrical

power

can

be

computed

separately.
Anti-tamper function

Double circuit measurement to prevent tempering

(Optional)
STS manufacturer code

37

STS certificate code

STS-154

Rated operating voltage (Un)

220V (230V/240V)

Frequency

50Hz5Hz . 60Hz5Hz

Accuracy active

1.0

Nominal Current Ib

5A/10A

Starting current

20mA

Max. working current

30A,60A

/ 80A ,100A

Max. computation current

90A

/120A

Meter constant

1600imp/kWh

Instant over current

2500A

Power impulse output mode

LED

Working voltage range

240V +20%

2.0

220V -30%
Max. tolerant over voltage

415V

(48 hours)

Meter condition remains normal after test

Current

5(30)A

Display and indication port

Large LCD screen with wide angle120, anti-ultraviolet

5(60)A

function and wide temperature range. 8 Digits display,


IEC62056 display code encoding, visualized symbol,
balance energy (credit) bar indication, alarm/tip LED
indication, LCD screen with backlit instruction, user-friendly.
Character dimensionheight*width: 12X4.5mm
Power failure display function(optional)
Keypad

12-key keypad, with keypad tone & Braille signs.


Sound alarm and symbol indication of wrong keypad
inputting
Every key can be used for over 50000 times

Power consumption

Voltage circuits <2.0w / <10VA


Current circuit power < 0.2 VA

@230V

Shenzhen Inhemeter Co.,Ltd. | Technical Specification

17

Keypad Prepayment Energy Meter and Vending System Solution

Working environment

Operation temperature

-25+75

range
Storage and transport

-40+80

temperature range
Humidity requirement

Max. temperature is 55, relative humidity range: 095%

Lightning protection

Built-in varistor protection

Communication port

1. Infrared communication
2. RS - 485 or RS - 232 (optional)
3. PLC
Meter reading interface: comply with ESKOM
SCSSCAAA9

Communication protocol

IEC62056-21 mode C
Baud rate: 2400bps

CIU Communication port

CIU communication port (2 wire communication port) can be

(option)

adopted.

In

this

case,

meter

becomes

measuring/controlling component, with addition of one CIU


component it will become a split type keypad prepayment
meter.
Real-time clock (optional)

Crystal timing real-time clock


Crystal frequency: 32.768 kHz
Clock accuracy (support temperature compensation) :
5ppm
Within reference temperature (23) and working voltage
range: clock accuracy 0.5s/d
Within working temperature range (-25 +75 ) and
under AC power supply or back-up power supply mode:
clock accuracy1.0s/d

Real-time clock backup

1. columnar battery:

power (option)

1200mAh

3.6 V lithium-ion battery capacity

Sustain clock for more than 10 years during power failure.


2.super charged capacitor
Sustain clock for more than 36 hours during power failure.

18

Shenzhen Inhemeter Co.,Ltd. | Technical Specification

keypad prepayment meter and vending system solution

2.3 Meter Shape Diagram


2.3.1

Short terminal Cover


unit: mm

2.3.2

Extended terminal Cover


unit: mm
Transparent extended terminal cover optional

Shenzhen Inhemeter Co.,Ltd. | Meter Shape Diagram

19

Keypad Prepayment Energy Meter and Vending System Solution

2.4 Meter Installation Diagram


Short terminal cover
unit: mm

Pothook has two holes of which the distance is 10mm.

Optional transparent extended terminal cover

20

Shenzhen Inhemeter Co.,Ltd. | Meter Installation Diagram

keypad prepayment meter and vending system solution

2.5 Terminals
Unit: mm

Characteristics: pressure plate wiring mode is suitable for wires of different materials and diameters, and
it will not break the wire.

2.6 Wiring Diagram

2.7 Meter Active Metering Accuracy


Error limit of DDZ1513 meter, Class 1, active
Load Value

Power factor

Error limit percentage


IEC62053-21 standard

Inhemeter Standard

0.02IbI< 0.05 Ib

1.5

1.0

0.05IbI< 0.10 Ib

1.5

1.0

0.10IbIImax

1.0

0.6

Shenzhen Inhemeter Co.,Ltd. | Terminals

21

Keypad Prepayment Energy Meter and Vending System Solution

0.02IbI< 0.1Ib
0.1IbI< 0.2Ib
0.2IbIImax

0.5 lag

1.5

1.0

0.8 lead

1.5

1.0

0.5 lag

1.5

1.0

0.8 lead

1.5

1.0

0.5 lag

1.0

0.6

0.8 lead

1.0

0.6

Inhemeter single phase two wire energy meter active error range diagram

COS=1 active error range

COS=0.5

22

active error range

Shenzhen Inhemeter Co.,Ltd. | Meter Active Metering Accuracy

keypad prepayment meter and vending system solution

2.8 Basic Characteristics


1

Energy meter cover

Impulse indicator light

3
4
5

Phase voltage indicator


Energy meter case
Photovoltaic (infrared) communication

interface
6

12-key keypad

Meter seals ( 1 on the left and the

other on the right)

2.8.1

Terminal cover (short and extended)

Terminal cover seal

10

Meter Panel

11

Energy meter unique serial No

12

LCD display

13

Alarm indicator light

Impulse Indicator Light (Red LED)

Flash frequency of the red LED impulse light indicates instantaneous power load. The more
quickly it flashes, the higher the load is. Meanwhile, it can also be regarded as standard power
impulse output so as to check the accuracy of measurement.
Meter impulse constant is 1600imp/kWh, which means red LED flashes 1600 times when 1
kWh is used.

2.8.2

Phase Voltage Indicator Light (Green LED)

The green LED light indicates phase voltage (power grid is on). When the meter is connected
to power grid which is under normal power supply condition, the meter is in working status, the
green LED indicator light is on. When power is off or meter is not in working status, the green
LED indicator light is off.

2.8.3

Alarm Status Indicator Light (Yellow LED)

The yellow LED light is the indication of meter abnormal status or alarm status. If the yellow
Shenzhen Inhemeter Co.,Ltd. | Basic Characteristics

23

Keypad Prepayment Energy Meter and Vending System Solution

LED light flashes or lights permanently, proper operation need to be carried out to solve the
problem otherwise it may influence energy consumption.
The yellow LED indicator light flashes: it means meter is in alarm status, for example balance
energy is less than alarm amount, power load exceeds limit, or meter is in abnormal status.
Proper action should be carried out according to information indicated on LCD display,
otherwise meter may cut off the power.
The yellow LED indicator lights permanently: it means power is cut off because balance
energy is zero, power load exceeds limit, or meter is in abnormal consumption status. Proper
action should be carried out according to information indicated on LCD display, for example,
recharge credit, reduce load, stop abnormal consumption.

2.8.4

Photoelectrical (infrared) Communication Port

The photoelectrical (infrared) communication port can be connected to portable device (HHU,
laptop, etc.) through a communication cable to read data from meter or set parameter for
meter. Communication protocol is compliance with model C in IEC62056-21.

2.8.5

12-key Keypad

The meter has a non-inductive, non-touch, silicon 12-key keypad, keypad is equipped with key
tone and Braille symbol. Token input and other actions can be operated on the keypad.
0-9 are 10 digits keys, which are used for inputting TOKEN code and short code. The other
two special keys are red
A.

delete key and blue

enter key.

After inputting TOKEN code or short code, press Enter. If code is correct, purchased
kWh or credit will be entered into the meter and the meter will display corresponding
data item. Otherwise there will be alarm and corresponding wrong code indication on
LCD display.

B.

Press Enter key without inputting any code, scroll display data item can be checked
manually.

2.9 Measurement Function


2.9.1

Active Power Measurement

The meter can measure and save single phase two wire active energy. Measurement unit is
kWh. Measurement record is default as zero in factory. When accumulated active power
measurement reaches 999999.99kWh, the power record will return to zero again
automatically.


Both forward and reverse consumption will be added to active accumulated power.
Reverse consumption can be measured separately (optional).

Measure/display total active accumulated energy

Record and check(or download) daily (24 hours, 00:00---24:00) active energy of
recent 7 days.

Record and check(or download) monthly total active energy of recent 3 months

24

Shenzhen Inhemeter Co.,Ltd. | Measurement Function

keypad prepayment meter and vending system solution

Record and download monthly total active energy of last 12 months

Active accuracy class: 1

Active energy display method: 6+2 6 integrals and 2 decimals (factory default setting),
programmable setting is 7+1, 8+0 display modes.

Double-loop anti tempering measurement function(optional function) double-circuit


anti tempering measurement available. Real time comparing of phase and neutral
current, and always measure the circuit with larger current.

2.9.2

Maximum Demand Measurement

DDZ1513 single phase keypad prepayment energy meter can measure, analyze and record
maximum demand, date and time of maximum demand within billing period.


Billing period is 1 month. The starting date of billing period is settable. setting range
is 1st-27th.

Demand measurement method is slide method. The slide is 1 minute, and cycle is 15
minutes.

Measure/display maximum demand, date/time of maximum demand within current


month

Record and check(or download) monthly maximum demand, date/time of maximum


demand of last 3 months

Record and download monthly maximum demand, date/time of maximum demand of


last 12 months

2.9.3


Electrical Parameters Measurement


Phase voltage measurement/display: 3 integrals,2 decimals, unit is V, accuracy is
1%

Current measurement/display: 3 integrals,2 decimals, unit is A, accuracy is 1%

Power measurement/display: 2 integrals,3 decimals, unit is kW, accuracy is 1%

Apparent power measurement/display (optional function):

It is programmable to choose

active power or apparent power measurement/display. If programmed to apparent power


measurement, display and load control, the display item (006) will display apparent power (2
integrals, 3 decimals, unit is kVA, accuracy is 1%). Load control will be changed from active
power (kW) threshold to apparent power (kVA) threshold, and display item (089) will display
active power (2 integrals, 3 decimals, unit is KW, accuracy is 1%).
Note: Except for power measurement (active power, reactive power, apparent power), error percentage
of other parameter is calculated as follows:
Measurement error percentage (%) =

meter measurement amount-actual amount


100%
reference value measured

Definition of measured reference value:


Voltage is meter rated voltage. voltage measurement range is 0.6Um--1.2Um
Current is meter maximum current, current measurement range is 0.05Ib--IMAX

Shenzhen Inhemeter Co.,Ltd. | Measurement Function

25

Keypad Prepayment Energy Meter and Vending System Solution

2.10

Special Functions

2.10.1 Load Breaking Function


The built-in latching relay can control the load according to balance credit, tempering status
and load status. When power is off, built-in relay will disconnect to cut off power supply. When
power is on (power grid is restored to supply power), meter will analyze the record. If it is
normal (balance credit is not zero, and meter is not under tempering, overload or any other
abnormal condition), built-in relay will reconnect to supply power, otherwise (balance credit is
zero, or meter is under tempering, overload or any other abnormal condition), built-in relay will
remain disconnected to cut off load power supply.
Note: When phase voltage is lower than operating voltage range70%Un or 176V AC,the
relay will not react. When phase voltage is higher than operating voltage range70%Un or
176V AC, meter will drive the relay to complete working status transformation.
Relay condition instruction on LCD display:

built-in relay is connected, user load is on.

built-in relay is disconnected, user load is off.

Note: If LCD indicated relay status does not match actual situation, it is possibly a malfunction,
please inform management department for servicing.

2.10.2 Zero Balance Cut off Function


When balance credit is zero built-in relay will cut off load power supply immediately to perform
power breaking function in prepaid meter.
Note: Overdraft, life-line load supply and evening (or specified time) and holidays guarantee will be
considered as exceptions. Under these exceptions load will not be cut off even when balance credit is
zero, but meter will record consumption as negative value, and the value can be deducted from next
recharge amount.

2.10.3 Overdraft Function


The meter supports overdraft function. When overdraft threshold setting (short code 022) is
not zero, the meter can perform overdraft function and overdraft amount is the amount set by
overdraft threshold (short code 022). The overdraft threshold is shown as: 6 integers and 2
decimals, unit of kWh. (default inactivated)

2.10.4 Life-line Load Supply Function


The meter supports Life-line load supply function. Under this function, when balance credit is
zero and user load is lower than life-line load, power supply will not be cut off. But if user load
is higher than life-line load, it will be regarded as overload consumption and the power will be
cut off.
When the life-line load threshold (short code 091) is not zero, the function is activated. The
threshold is shown as: 2 integers and 3 decimals, unit of kWh or KVA. (Default inactivated)
26

Shenzhen Inhemeter Co.,Ltd. | Special Functions

keypad prepayment meter and vending system solution

2.10.5 Evening(or Special Time) Guarantee Function


The meter supports evening (or special time) guarantee function. Setting can be made as that
power can not be cut off during evening (or special time). (Optional Function).

2.10.6 Holiday Guarantee Function


The meter supports holiday guarantee function. Setting can be made as that power can not be
cut off during holiday. (Optional Function).

2.10.7 Load Control Function


Load control function of DDZ1513 single phase keypad prepaid meter accords with the special
provisions of load control algorithm in SCSSCAAA9 item 7.7.2 in Eskom regulations. The
meter has load control function.
Note: Load control function is not for power load security protection. Generally load control is used for
restricting the average load upper limit in specified region (mainly for power grid security, wire losses
reduction, power lines load limit, etc).

2.10.8 Automatic Restoration Mode after Overload Power Off Delay


This function default activated. If user power load is higher than load threshold (short code
015), the meter will sound the alarm and yellow LED flashes. If user power load is higher than
load threshold and this situation lasts for 45 seconds, built-in relay will cut off power supply at
the 45th second and automatically reconnect to restore power supply after 150 seconds of
power off delay. If user power load is still higher than load threshold, above process will be
repeated. If continuous overload trip lasts 5 times within 30 minutes, the automatic
reconnection will be delayed to 45 minutes later. The user can not manually restore power
supply during the delay.
The restoration time after 5 times overload trip within 30 minutes can be set. The minimum set time is
5 minutes. factory default set time is 45 minutes.
Overload meter sound and light warning and LCD display status indicator:

The meter is locked. The relay will reconnect automatically after locking. If locking time is deducted by
every second then remaining of locking time is displayed as unit of seconds, for example 150 seconds. If
deducted by every minute then remaining locking time is displayed as units of minute. When recovery
time is decreased to zero, the relay will reconnect.

2.10.9 Relay Manual Reconnect


Shenzhen Inhemeter Co.,Ltd. | Special Functions

27

Keypad Prepayment Energy Meter and Vending System Solution

This is a Optional function. If user power load is higher than load threshold (short code 015),
the meter will sound the alarm and yellow LED flashes. If user power load is higher than load
threshold and this situation lasts for 45 seconds, built-in relay will cut off power supply at the
45th second. The user need to manually press blue enter

button on keypad to

reconnect relay after 150 seconds of power off delay. If power load is still higher than threshold,
above process will be repeated. If continuous overload trip lasts 5 times within 30 minutes, the
meter will restore power supply after the delay of 45 minutes. The user can not manually
restore power supply during the delay.

2.10.10 Load Threshold for Special Peak Time


This is a Optional function.
In order to guarantee life-line power supply, the meter accepts peak time special threshold for
the selected users.

2.10.11 Built-in Relay Disconnected When Power is off


Optional function, default activated.
This personalized optional function enables built-in relay to disconnect when the meter power
is cut off. When power is on (power grid is restored to supply power), meter will analyze the
record. If it is normal (balance credit is not zero, and meter is not under tempering, overload or
any other abnormal condition), built-in relay will reconnect to supply power, otherwise (balance
credit is zero, or meter is under tempering, overload or any other abnormal condition) built-in
relay will remain disconnected to cut off load power supply.
This function is used for anti-tempering, for example: cutting off power supply circuit when
neutral line is switched off (meter power is cut off).

2.10.12 Built-in Relay Disconnect When Terminal Cover is opened


Optional function, default activated
This personalized optional function enables built-in relay to disconnect when terminal cover is
opened. For restoration of power supply, the user need to apply for specific TOKEN from utility
or power selling station, and correctly input this specific TOKEN code into the meter to have
built-in relay reconnect.
This feature is used for anti-tempering, for example: trying to open terminal cover for
tempering.

2.10.13 Pre-warning and Warning Function When Balance Credit is short


This feature reminds user that balance credit is short and they need to recharge in time.
Besides, this function enables users to set threshold, sound alarm and balance bar by
themselves

2.10.14 Pre-warning Function


When balance credit is less than pre-warning threshold (short code 016), sound alarm and

28

Shenzhen Inhemeter Co.,Ltd. | Special Functions

keypad prepayment meter and vending system solution

LED indicator will be activated.

Will flash alternately and

will have three

bars remain only. User should recharge the meter in time. Power pre-warning threshold
amount and function can be set by inputting code: 4547 8xxxavailable set amount is
0kWh~999kWh.

2.10.15 Warning Function


When balance amount is equal or less than pre-warning threshold (short code 017), the meter
will sound the alarm and yellow LED light will keep flashing. Built-in relay will be disconnected
to cut off power supply, and user should recharge in time.
and

will flash alternately

will have two bars remain only. User need to press blue enter button on keypad

to reconnect power. Power warning threshold can be set by inputting code: 4547 9xxx
available set amount is 0kWh~999kWh.
Note: Power warning threshold amount must be less than pre-warning threshold amount. The
warning function will be shut off if power warning threshold amount or pre-warning threshold
amount is zero.

2.10.16 Balance Credit Bar Indication Function


The bar

on LCD display will visually indicate available balance amount. This is

similar to battery power bar indication on mobile phone. Details can be found in the following
section.

2.10.17 Anti-over Credit Function


The meter can be set with maximum credit limit (short code 021). When credit exceeds limit,
the recharging TOKEN will be rejected even if it is valid. Recharge operation will work only
when the sum of balance credit and recharge credit is less or equal to credit limit.

2.10.18 Number of Balance Days Indication Function


Optional function.
The meter can estimate how many days remaining credit will last. Details is displayed in
available time (short code 012), display unit is: dd:hh (day: hour), maximum indicative time is
99 days 24 hours.
Detailed arithmetic is made according to remaining credit and maximum demand. Calculation
will be made by maximum demand last month if the demand is zero this month and by load
threshold if maximum demand is zero last month.

2.10.19 History Data Transfer and Event Record Function


Optional function.
The meter can save monthly history measurement data for latest 12 months. Date and time of
Shenzhen Inhemeter Co.,Ltd. | Special Functions

29

Keypad Prepayment Energy Meter and Vending System Solution

month summary are configurable and is default as 24:00 of end day of the month.


Total kWh consumption accumulated

Total kWh consumption of current summary cycle

Monthly maximum demand with date & time of happening.

The meter can save daily kWh consumption (00:00----24:00) of latest 7 days.

2.10.20 Event Recording Function


The meter can record 50 events with date & time of happening. The events include:


Tempering record clearance

Key modified event

Balance credit clearance

Overload power failure

Battery failure event

System clock calibration event

2.10.21 Special Events Recording Function


The meter can record start time and end time of following special events.


Opening of terminal cover


When terminal cover is opened, the integrated relay will disconnect to cut off the power.
The indicator light will be turned on, and one time of terminal cover opening event will
be recorded.
Status A: on LCD

flashes,

and

are shown, which means terminal

cover is opened, and is still under opening status.


Status B: on LCD

lights permanently,

and

are shown, which means

terminal cover was opened, but is closed now.


How to operate: After terminal cover is opened users need to apply to electricity utility for
reconnection of load. Electricity utility can check the event and issue a specific TOKEN. Users
enter the TOKEN to the meter to clear out temper record and reconnect the load.
Note: In order to avoid unnecessary re-records of terminal cover openings, reopen of terminal
cover will be record only when it happens 1 minute after the closing of last opening. And reopens
within 1 minute of last closing will be ignored.
Note: The meter records latest 5 times of terminal opens only.

Power failure event


Power failure and re-supply will be both record as events with date & time of
happening.
Note: The meter records latest 5 times of power failure events only.

30

Reverse power event

Shenzhen Inhemeter Co.,Ltd. | Special Functions

keypad prepayment meter and vending system solution

The meter will record reverse power event and turn on alarm light. On LCD
flashes alternately.


Bypass tempering event


The meter will record bypass tempering and short circuit events, and turn on alarm
light. On LCD

flashes alternately.

For following events, the meter can record latest 5 events with not only the date and
time of happening, but also related event data.


Recharge event (including recharging token code, TID code, recharge amount, time of
recharge)

 Zero balance credit (including overdraft) event

2.11

LCD Display

DDZ1513 single phase keypad prepayment energy meter equipped with LCD display with
large screen, wide angle (120), wide temperature range and UV protection function. The
digit display is 8 bits (6 integrals and 2 decimals, or 7 integrals and 1 decimal, or 8 integrals
only). IEC62056 display code encoding, visualized reminding symbols, balance credit bar
indication, alarm/tip LED indication. LCD display is with backlight.
Digit size (height*width): 12X4.5mm
Power failure display function(optional)

Graphic symbol

Instructions
1.
2.

Code display area, support OIBS encoding display


Current tariff indication (in case of multi tariff
prepayment meter)

Balance credit (kWh, amount of money) indication bar


Smiley Face :Meter in Good Condition
Smile & Sad face
Relay status indication

Sad Face Meter in Bad Condition


1.

connect

2.

disconnect

Shenzhen Inhemeter Co.,Ltd. | Special Functions

31

Keypad Prepayment Energy Meter and Vending System Solution

Measurement unit
kWh: Active energy unit
kW: Active power unit
V: Voltage unit
A: Current unit
kVA: Apparent power unit
Unit of credit is amount of money.
coins symbol
Data area to indicate:
1.

Measurement data and TOKEN code

2.

Date: YY-MM-DD (year-month-date)

3.

Time: HH-MM-SS (hour-minute-second)

Three phase prepayment meter phase voltage


indication (not valid for single phase meter)
Lighting symbol: to instruct power grid condition. Can be
ignored if there is a power indication light.
1.

On power grid supply is under normal condition

2.

Off power grid failure, power supplied by backup


battery.

Warning symbol: to indicate opening of terminal cover.


1.

On: terminal cover was opened and now it is


closed.

2.

Flashing: terminal cover is opened and remains


open.

Battery: to indicate battery status.


1.

On: battery down, a new battery is needed

2.

Off: battery is normal

2.11.1 LCD Data Display Instruction


When meter is powered on, there will be 2 seconds of self
examination during which LCD is showed full screen (as picture).
After self examination meter will start auto-scroll display. Items,
sequence and time of auto-scroll display can be configured.

Normal working condition: built-in relay is connected, meter has certain amount of credits, kWh
32

Shenzhen Inhemeter Co.,Ltd. | Special Functions

keypad prepayment meter and vending system solution

consumption is displayed.
Meters measurement and records can be checked by following three methods:


Auto-scroll display: LCD auto-scroll displays according to configured items, sequence


and time. Display duration of each item can be programmed within 3~99 seconds. At
most 10 items can be programmed in auto-scroll display (programmed by BCS)

Manual scroll display: press blue ENTER key manually to scroll display according to
configured items, sequence and time. Display duration of each item can be
programmed within 3~99 seconds. At most 20 items can be programmed in manual
scroll display (programmed by BCS). Manual scroll items will be displayed after
auto-scroll items, which means manual scroll items are: auto-scroll items + manual
scroll items (programmed by BCS).

Short code display: Specific item can be checked by inputting 3 digits of short code.
Display duration of each item is same with manual scroll display. LCD will return to
auto-scroll display after short code display.

2.11.2 Balance Credit bar

4 bars

3 bars

2 bars

1 bar

Empty / flashing

Shape of balance credit bar depends on comparing result with warning and pre-warning
thresholds (kWh/amount).


Balance credit pre-warning threshold,4 bars appear. see diagram .

Pre-warning thresholdBalance credit Warning threshold) + (pre-warning threshold


warning threshold) / 2
3 bars appear, user should consider purchasing credit. see diagram .

Warning threshold (short code 017) + (pre-warning threshold warning threshold) / 2


Balance credit Warning threshold
2 bars appear, user should consider purchasing credit. see diagram .

Warning threshold Balance credit 1/2 Warning threshold


1 bar appears, user should purchase credit. see diagram .

1/2 Warning threshold Balance credit 0


Bar is empty, user need to purchase credit immediately. see diagram

Balance credit = 0
Bar is empty and frame flashes, relay disconnects and power is off (except for
over-draft, night/holidays). see diagram

Shape of balance credit bar depends on real balance (optional function)


Diagram means balance credit is not less than 500kWh
Diagram means balance credit is not less than 100kWh
Shenzhen Inhemeter Co.,Ltd. | Special Functions

33

Keypad Prepayment Energy Meter and Vending System Solution

Diagram means balance credit is not less than 50kWh


Diagram means balance credit is not less than 10kWh
Diagram means balance credit is zero


Bar diagram can be used for power load indication (optional function),
Diagram means power load is higher than 100% of load threshold
Diagram means power load is higher than 75% of load threshold
Diagram means power load is higher than 50% of load threshold
Diagram means power load is higher than 25% of load threshold

Bar diagram can be used for estimated days of credit running out indication (optional
function),
Diagram means estimated days of credit running out are more than 30 days
Diagram means estimated days of credit running out are 15 days
Diagram means estimated days of credit running out are 10 days
Diagram means estimated days of credit running out are 5 days

2.11.3 Smile Face and Sad Face Symbol


Smile face and sad face indicate that meter operation is correct/incorrect. Alternating of
smile/sad faces means alarm.
It means the meter is in good condition, user is allowed to use electricity
Smile face

Operation is correct, input TOKEN code is right, the meter recharge is


normal.
Relay is disconnected, meter is in abnormal condition and user cannot

Sad face

use electricity.
Operation incorrect, input TOKEN code is wrong and the meter
recharge is abnormal.

2.12

Operation Detail

Via 12-keys keypad users can input TOKEN code, passwords, short codes, and data codes
and TIKEN codes.
When digits are input via keypad, they will be displayed on LCD and move from the right to the
left. Every four digits will be separated by a dash. At the same time, number of digits will be
display on left top corner of the screen. While keyboard operation, all symbols not related to
inputting code will not be displayed. Below picture shows inputting procedure - 10 digits have
been entered.
Every digit enter will be accompanied with a key tone beep.
Red

to delete wrong digit. Every pressing can delete one digit from the right side of

screen.
Inputting interval of every two digits should not be more than 30 seconds, otherwise inputted
digits will be ignored and meter will return to normal display status.
34

Shenzhen Inhemeter Co.,Ltd. | Operation Detail

keypad prepayment meter and vending system solution

2.12.1 TOKEN Input through Keypad




Complete TOKEN code


After inputting 20 digits TOKEN code and pressing ENTER button,
LCD display will indicate Accept if this TOKEN code is correct.

Keypad will be locked for 5 seconds for TOKEN processing

Sound notification

Smile face

Display the credit recharged of this time

Display current available kWh/credit (balance credit + recharged credit) in 5 seconds

Balance credit bar changed accordingly.

Incomplete TOKEN code


If no digit is input continuously within 30 seconds while inputting TOKEN code, TOKEN input
is overtime.

Inputted TOKEN codes disappear from LCD display

Display of balance kWh/credit

Duplicated TOKEN code


Once a TOKEN code is accepted and processed by the meter, it
will be rejected if input this code again. Meter LCD display will
indicate Used.

Keypad will be locked for 5 seconds and indicate Used

Sound notification

Sad face

Overdue TOKEN code


If TOKEN code is older than the oldest TOKEN code in meter, it
will be regarded as overdue and rejected by the meter. Meter
LCD display will indicate Old.
Shenzhen Inhemeter Co.,Ltd. | Operation Detail

35

Keypad Prepayment Energy Meter and Vending System Solution

Keypad will be locked for 5 seconds and indicate Used

Sound notification

Sad face

Correct but over-credit TOKEN code


A correct TOKEN code will be rejected if balance credit (after recharged) will be more than
credit limit and LCD display will indicate Over Crd

Keypad will be locked for 5 seconds and indicate Over Crd

Sound notification

Smile face

Wrong TOKEN code


Meter will reject TOKEN codes that of wrong numbers, wrong
meter ID, wrong keys or random codes. LCD display will indicate
Reject-1.


Indicating Reject-1

Sound notification

Sad face

Note: Meter allows 3 times of false and retry when input one TOKEN. After 3 times TOKEN decoding
will be locked for a while, during which LCD indicates Reject-1 and PRd-Loc (period locked, for
example Loc-028 means period lock remains 28 seconds). Period locked will increase while times of
failure increases. But it will return to default when correct TOKEN is input after locking. This function will
prevent temper of random codes.

2.12.2 Operation of Inputting Transfer Key


Meter transfer key need to be modified when install & re-install meter, vending station changes,
management software password changes or just for security purpose. Vending station and
meter must use same vending key and transfer keys, otherwise TOKEN from vending station
will not be accepted by the meter.
To change the transfer key, operator need to enter two groups of TOKEN (1st group of key
modify TOKEN and 2nd group of key modify TOKEN). Either group of TOKEN can be input
first, but inputting of both groups of TOKEN must be finished within 5 minutes otherwise the
procedure has to be restart again.
After inputting one group of TOKEN (accepted by meter correctly), the meter will indicate as
followings:
The 2nd group of key modify TOKEN is input and accepted,
please input the 1st group now.
The 1st group of key modify TOKEN is input and accepted,
please input the 2nd group now.

2.12.3 Special Functions TOKEN


The meter has several special functions such as tempering clearance and reconnect, records
clearance and overload configuration, etc. These special functions can be achieved through
36

Shenzhen Inhemeter Co.,Ltd. | Operation Detail

keypad prepayment meter and vending system solution

unique TOKEN which is generated by vending system.




Tempering clearance TOKEN

If the power is cut off because of terminal cover open, user has to go to apply for
tempering clearance TOKEN from Management Center. After inputting the TOKEN,
the meter will reconnect to power supply.
Note: While inputting tempering clearance TOKEN, other events logged in the
recorder will be cleared as well.


Load threshold TOKEN

Load threshold can be changed by inputting load threshold TOKEN. If existing load
threshold is too low to meet users need, the user can apply to Management Center
for modifying load threshold. If applying is accepted, the Management Center will
generate a load threshold TOKEN. Meter load threshold will be revised by inputting
the load threshold TOKEN.


Balance clearance TOKEN

If meter needs to be replaced or repaired, or user needs to be changed, operator can


record the balance and then input a balance clearance TOKEN to clear the balance
credit. At the moment relay will open and power supply will be cut off.

2.12.4 Special TOKEN


Following special TOKEN codes are to support extended functions of keypad prepayment
energy meter.


Pre-warning threshold TOKEN

Pre-warning threshold can be configured by user-self: 4547 8xxx, the threshold can
be set between 0kWh~999kWh. There will be no pre-warning if set to zero.


Warning threshold TOKEN

Warning threshold can be configured by user-self: 4547 9xxx, the threshold can be
set between 0kWh~999kWh. There will be no warning if set to zero.

2.12.5 Test TOKEN (not Specific Meter TOKEN)


Some TOKEN codes are related to function test (not specific meters). Once these test TOKEN
codes are accepted, meter will start corresponding test.
Functions

TOKEN

Change the status of relay

0000 0000 0001 5099 7584

HMI test, which includes turning on all the LEDs,


displaying all segments on the LCD, and activating
the buzzer
Display the total units counter

0000 0000 0001 6777 4880


0000 0000 0002 0132 8896

Display the key revision number and key type

1844 6744 0738 4377 2416

Display the tariff index

3689 3488 1475 5332 2496

Display the power limit level

0000 0000 0012 0797 4400


Shenzhen Inhemeter Co.,Ltd. | Operation Detail

37

Keypad Prepayment Energy Meter and Vending System Solution

Display the tamper state

0000 0000 0022 8172 8512

Display the instantaneous power

0000 0000 0044 2920 8064

Display the software version number

0000 0000 0087 2419 5840

Test all the above functions (tests run sequentially)

5649 3153 7254 5031 3471

When test all functions (sequence of tests as per the list above), each item will take 2.5
seconds. While individual item test will take 5 seconds. The meter will return to normal
operation mode after test.
Retrieval of measuring data, computing data, recording data, setup parameter
and status, etc.
If short code is not exist, the data item is empty.

2.13

Communication Port

The meter has communication ports of photoelectric (infrared), RS485/232, ESKOM credit
reader port and twin cable communication port to CIU.

2.13.1 Photoelectric (Infrared) Communication Port


Through Photoelectric(infrared) communication (as picture below) data such as kWh used,
maximum demand, consumption history of past 12 months, monthly maximum demand of past
12 months with date and time, daily consumption of latest 7 days and events record etc can be
retrieved. And meter configuration can be realized if keys are given.

Notice: Its suggested that configuration should be done according to users requirement before meters
leave factory.

Accessories below can be provided if required:


38

Shenzhen Inhemeter Co.,Ltd. | Communication Port

keypad prepayment meter and vending system solution

Accessory Name
Photoelectric communication cable

Instruction
Cable for communication between photoelectric port
and CMRI/HHU.

HHU TP900

Photoelectric hand held unit (HHU), HHU

Psion Teklogix 7525 / 7527S

multi-charger. communication cable between HHU and

CMRICMRI1010/CMRI1006

BCS (basic computer station), and operation system.

INHE AMI2010

INHEMETER Smart Power Management System


Software

For detailed introduction of INHE AMI2010, refer to introduction manual.


Standard: IEC 62056-21 (replacement of IEC 61107).

2.13.2 RS232/RS485 Communication Port (Optional)


RS232 communication port is prepared for AMR purpose in future.

2.13.3 Credit Reader Interface (Eskom Port) - Optional


Meter has credit reader interface (ESKOM port). It complies with ESKOM specification
SCSSCAAA9 and the reader interface is on PCB board of the meter. User can insert the probe
through hole on meter case to read credit. When this port is not used, plastic seal should be
inserted into the hole to prevent insects.
Notice: For security of operator and meter, power MUST be cut off during operation through the Credit
Reader Interface.
Shenzhen Inhemeter Co.,Ltd. | Communication Port

39

Keypad Prepayment Energy Meter and Vending System Solution

2.13.4 Twin Cable Communication Port


Optional port. In case of split type keypad prepayment meter, the meter will work as
measurement control unit (MCU)
MCU twin cable communication port is used for connection to user display unit (CIU).The
communication port does not have polarity, and it adopts twin cable port to connect
measurement control unit (MCU) and user display unit (CIU).
Notice: Maximum communication distance between MCU and CIU is 130 meters. But the distance will
be affected by resistance (max 40 ohm) as well.

2.13.5 Auxiliary Terminal Wiring Diagram


Communication port & test port for impulse output

2.14

Safety Regulation

The meter can be installed outdoor, indoor or in meter box. And its keypad, LCD, cover and
case are safe and insulated. But wiring security must be considered during installation incase
wires or terminals are left exposed.

2.15

Installation
 Before installation, please make sure the appearance, seals, utility inspection notice
are complete. Meter should be installed on solid & fire resistant wall. Recommend
height is 1.4m~1.7m.

40

Shenzhen Inhemeter Co.,Ltd. | Safety Regulation

keypad prepayment meter and vending system solution

 Wiring method should follow diagram printed in terminal cover. Copper wire/terminal
is recommended.
 Insert wires by loosing the screws on terminal. Screws need to be fasten properly to
make sure security and good contact.
 Close the terminal cover after wiring and seal the cover with sealing screw from
utility.
 Fasten the wires tightly and always tidy them gently. Keep the meter clean from dust
and water etc.
 Turn on the power supply and check meters working condition. Record data if it
works properly. Otherwise need re-check the installation and connection.
 Handle with care to prevent dropping and bumping during installation.
 Pay attention to operator and meter security during installation.
Notice: the meter adopts double circuits measurement method (anti-temper) which will measure both
phase and neutral lines and computing with the one of larger current only. Operator should make sure
the wiring and connection are correct during installation, so as to avoid repeated computations. Diagrams
of wiring are as follows:

Correct Installation

Shenzhen Inhemeter Co.,Ltd. | Installation

41

Keypad Prepayment Energy Meter and Vending System Solution

Incorrect Installation
Neutral line of B1,C1 and C2 are incorrect.
Error 1: Neutral incorrect. Extra kWh record. A=A+B1
Error 2: Neutral incorrect. Extra kWh record. C=C+C1+C2
Error 3: Neutral incorrect. Extra kWh record. C1= C1+C2
Correct: B, B1 and C2

42

Shenzhen Inhemeter Co.,Ltd. | Installation

keypad prepayment meter and vending system solution

Chapter3

Three Phase Keypad Prepayment Energy Meter

3.1 Technical Specification

DTZ1513 three-phase keypad prepayment energy meter is to measure 50Hz or 60Hz


three-phase 4-wire directly connected AC active electricity energy (reactive electricity energy),
the dimension is as follows:
Description

Specification

Technical standard

IEC 62052-11 2003


IEC 62053-21 2003
IEC 62053-23 2003
IEC 62055-31 2005
IEC 62055-41 2007
IEC 62055-51 2007
SANS 1524-1 2005
ESKOM SCSSCAAA9

Meter Type

Three-phase 4-wire directly connected meter


Forward and reverse active electrical power are all included in

Active energy computation

forward active electrical power


Reverse active electrical power can be computed separately.
Shenzhen Inhemeter Co.,Ltd. | Technical Specification

43

Keypad Prepayment Energy Meter and Vending System Solution

Reactive energy

Quadrant reactive power energy computation

computation(optional)

Can compute reactive input and reactive output respectively

STS manufacturer code

37

Rated operating voltage (Un)

3X230V/400V (3X220V/380V 3X240V/415V)

Frequency

50Hz5Hz . 60Hz5Hz

Active computation accuracy

1.0

/ 2.0

Reactive computation

2.0

/3.0

Nominal Current
Ib

5A

/10A

Max. computation current

80A

/80A.100A

Starting current

20mA

Meter constant

400imp/kWh

Display and indication port

Large LCD screen with wide angle120, anti-ultraviolet function

accuracy

40mA

and wide temperature range. 8 Digits display, IEC62056 display


code encoding, visualized symbol, balance energy (credit) bar
indication, alarm/tip LED indication, LCD screen with backlit
instruction, user-friendly.
Character dimension( height*width): 12X4.5mm
12-key keypad, with keypad tone & Braille signs.

Keypad

Sound alarm and symbol indication of wrong keypad inputting


Every key can be used for over 50000 times
Power consumption

Voltage circuit power: <2.0W

or <10VA@230V

Current circuit power: < 0.2 VA


Communication port

1.

Infrared communication

2.

RS - 485 or RS - 232 (optional)

3.

PLC

Meter reading interface: comply with ESKOM SCSSCAAA9


Communication protocol

IEC62056-21 mode C
Baud rate: 2400bps

CIU Communication port

CIU communication port (2 wire communication port) can be


adopted. In this case, meter becomes a measuring/controlling

(option)

component, with addition of one CIU component it will become a split


type keypad prepayment meter.
Real-time clock (optional)

Crystal timing real-time clock


Crystal frequency: 32.768 kHz
Clock accuracy (support temperature compensation) : 5ppm
Within reference temperature (23) and working voltage range:
clock accuracy 0.5s/d
Within working temperature range (-25+75) and under AC
power supply or back-up power supply mode: clock accuracy1.0s/d

Real-time clock backup power


44

1: columnar battery:

3.6 V lithium-ion battery capacity 1200mAh

Shenzhen Inhemeter Co.,Ltd. | Technical Specification

keypad prepayment meter and vending system solution

(option)

Sustain clock for more than 10 years during power failure.


2: super charged capacitor
Sustain clock for more than 36 hours during power failure.

3.2 Meter Shape Diagram


unit: mm
Transparent extended terminal cover optional

3.3 Meter Installation Diagram

unit: mm

3.4 Meter Installation Diagram


Shenzhen Inhemeter Co.,Ltd. | Meter Shape Diagram

45

Keypad Prepayment Energy Meter and Vending System Solution

Characteristics: pressure plate wiring mode is suitable for wires of different materials and diameters, and
it will not break the wire.

3.5 Wiring Diagram

46

Shenzhen Inhemeter Co.,Ltd. | Wiring Diagram

keypad prepayment meter and vending system solution

Chapter4

Split Keypad Prepayment Energy Meter

4.1 Introduction
INHEMETER Split Keypad Prepayment Energy Meter is civil or commercial used single-phase
multi-components keypad prepayment energy meter compliance with STS (Standard Transfer
Specification) regulation, which can accept 20 digits STS code inputting and pass STS test
certification. It includes two components:
INHEMETER split keypad prepayment energy meter adopt international IEC62053, IEC62055
and IEC62056 standard, and the design and production comply with ISO9001 standard.
Meter circuit design, structure design, choice of components and materials are made
according to allowable greater environment tolerance for reliable guarantee of lasting and
stable operation of meter. Metering components take shield protection measures in structure
design, which can resist interference of external DC and AC magnetic field, over-voltage and
high frequency electromagnetism field. Energy meter is with good electromagnetism
compatibility. These designs guarantee metering reliability and lasting stability, other
influences can be neglected and metering is highly reliable. Therefore, this meter does not
need to be calibrated during its whole life period.
Meter cover is made of fire retardant, flame resistant and heat deformation resistant
polycarbonate material. It can be recycled after the end of its life cycle to save environment.
MCU cover is double insulated and compliance with dust and watch protection standard IP54
(IEC60529). MCU terminal is made of brass material, and plated with nickel as tropical climate
energy meter. MCU terminal cover can be short or extended, and fastened by a sealing screw.
Meanwhile, it can record events of opening terminal cover after installation. MCU wiring
complies with DIN43857 and BS5685 standards.
Split keypad prepaid energy meter operation diagram:

Shenzhen Inhemeter Co.,Ltd. | Introduction

47

Keypad Prepayment Energy Meter and Vending System Solution

4.2 Customer Interface Unit (CIU)


CIU is customer interface unit used for single phase, three-phase split keypad prepaid energy
meter. It is installed indoor, which is convenient for user to learn meter operation parameters
and load pre-purchased energy (credit).
CIU model for single, three phase split keypad prepaid energy meter is DDS1513-CIU
DDZ1513-CIU-CABLE

Two core communication cable(including RS485 / RS232)

DDZ1513-CIU-PLC

PLC(Power line wave-carrier communication)

DDZ1513-CIU-RF

Low power wireless communication

4.3 CIU Technical Parameters


4.3.1 Two Core Communication Cable
DDZ1513-CIU-CABLE
Technical parameter classification

Technical parameter value

Communication types

Two core communication cable, insulation, step less,


half-duplex

Supply mode

12DC got from MCU30mA

Communication distance

130 meters (maximum linear resistor 40 ohm),

Keyboard

12-key keyboard, keyboard tip sound , error indication of


keyboard inputting., with Braille signs

Cable specification

2.5 mm2

Dimension

160mm(L) 87.6mm(W) 41.2mm(H)

4.3.2 PLC Power Line Wave-carrier Communication


DDZ1513-CIU-PLC
Technical parameter classification

Technical parameter value

Communication types

Power line wave-carrier communication, stepless, half-duplex

Supply mode

Frequency AC/ battery (supply power at AC failure, optional)

Communication distance

200 meters

48

Shenzhen Inhemeter Co.,Ltd. | Customer Interface Unit (CIU)

keypad prepayment meter and vending system solution

Keyboard

12-key keyboard, keyboard tip sound , error indication of


keyboard inputting., with Braille signs

Cable specification

2.5 mm2

Dimension

160mm(L) 87.6mm(W) 41.2mm(H)

4.3.3 RF Low Power Wireless Communication


DDZ1513-CIU-RF
Technical parameter classification

Technical parameter value

Communication types

Adopt international general ISM (industry, science and


medicine) / SRD (short distance ) frequency band, low power
consumption, exemption frequency application of wireless
communication mode to realize wireless communication
between CIU and MCU
Frequency band (choose and confirm central frequency
according to regulations from different countries or regions)
300-400-348MHZ, 464MHz, 800-928MHz

Supply mode

Frequency AC and battery without (AC)

Communication distance

100m open areas


50m (with obstacles)

Keyboard

12-key keyboard, keyboard tip sound , error indication of


keyboard inputting., with Braille signs

Cable specification

2.5 mm2

Dimension

160mm(L) 87.6mm(W) 41.2mm(H)

4.4 Measurement and Control Unit (MCU)


MCU: Measurement and Control Unit
Metering and control unit for single phase split keypad prepaid energy meter, installed
outdoors.
Three communication modes with MCU:
DDZ1513-CIU-CABLE

Two core communication cable

DDZ1513-CIU-PLC

Power line wave-carrier communication

DDZ1513-CIU-RF

Low power wireless communication

4.5 MCU Technical Parameters


Description

Specification
Single-phase two wire direct access type meter

Meter Type

Three-phase 4-wire directly connected energy meter.


Forward and reverse active electrical power are all included
Active energy computation

in forward active electrical power


Reverse active electrical power can be computed

Shenzhen Inhemeter Co.,Ltd. | Measurement and Control Unit (MCU)

49

Keypad Prepayment Energy Meter and Vending System Solution

separately.
Anti-tamper function

Double circuit measurement to prevent tempering

(Optional)
STS manufacturer code

37

STS certificate code

STS-154

Rated operating voltage (Un)

Single Phase:220V (230V/240V)


(3X220V/380V

Three Phase: 3X230V/400V


3X240V/415V)
Frequency

50Hz5Hz . 60Hz5Hz

Accuracy active

Single Phase:Class1.0

Class2.0

Three Phase: Class1.0

Class2.0

Nominal Current
Ib

5A/10A

Starting current

20mA

Max. working current

30A,60A

Max. computation current

90A

Meter constant

Single phase:1600imp/kWh

/ 80A ,100A
120A

Three phase:400 imp/kWh


Working voltage range

Single phase:240V +20%


Three phase: 380-30%

220V -30%
415+20%

4.6 Single Phase Split Keypad Prepayment Meter

DDZ1513-MCU-BS:MCU without keyboard

DDZ1513-MCU-KBS:MCU with keyboard and

and display component

display component

Split keypad meter with IC Card

50

Shenzhen Inhemeter Co.,Ltd. | Single Phase Split Keypad Prepayment Meter

keypad prepayment meter and vending system solution

4.7 Three Phase Split Keypad Prepayment Meter


Three-phase split keypad prepayment meter: DTZ1513-MCU-BS/DTZ1513-MCU-BSK
DTZ1513-MCU-BS is a MCU unit without LCD screen and keyboard interface.
DTZ1513-MCU-BSK is a MCU with LCD screen and keyboard interface.

DDZ1513-CIU
DTZ1513-MCU-KBS
Measurement and Control Unit Customer Interface Unit

DDZ1513-CIU
DTZ1513-MCU-BS
Measurement and Control Unit Customer Interface Unit

4.8 Three Phase Split Type Measurement Box

DTZ1513-MCU-BOX
Measurement and Control Unit

DDZ1513-CIU
Customer Interface Unit

The CT ratios are as follows:


200/5A

300/5A

500/5A

800/5A

1200/5A

There are circuit breakers in the measurement box.

Shenzhen Inhemeter Co.,Ltd. | Three Phase Split Keypad Prepayment Meter

51

Keypad Prepayment Energy Meter and Vending System Solution

Chapter5

DIN Rail Mounting Split Keypad Prepayment


Energy Meter

5.1 Introduction
DIN rail mounted Single Phase Split Keypad Prepayment Energy Meter is civil or commercial
used single-phase multi-components keypad prepayment energy meter compliance with STS
(Standard Transfer Specification) regulation, which can accept 20 digits STS code inputting
and pass STS test certification. It includes two components:
A: MCUMeasurement and Control Unit. Split keypad prepayment energy meter MCU unit can
be installed outdoor, or in centralized meter box or on telegraph pole.
B: CIU: Customer Interface Unit. Split keypad prepayment energy meter CIU unit is installed
indoor, which is convenient for user to learn meter operation parameters and load
pre-purchased energy (credit). Inhemeter DIN rail mounted single phase split keypad
prepayment energy meter adopt international IEC62053, IEC62055 and IEC62056 standard,
and the design and production comply with ISO9001 standard.
DDZ1513-MCU-DIN is MCU without display component
DDZ1513-MCU-DIN-LCDS is MCU with display component

Meter circuit design, structure design, choice of components and materials are made
according to allowable greater environment tolerance for reliable guarantee of lasting and
stable operation of meter. Metering components take shield protection measures in structure
design, which can resist interference of external DC and AC magnetic field, over-voltage and
high frequency electromagnetism field. Energy meter is with good electromagnetism
compatibility. These designs guarantee metering reliability and lasting stability, other
influences can be neglected and metering is highly reliable. Therefore, this meter does not
need to be calibrated during its whole life period.
Meter cover is made of fire retardant, flame resistant and heat deformation resistant
polycarbonate material. It can be recycled after the end of its life cycle to save environment.
MCU cover is double insulated and compliance with dust and watch protection standard IP54
(IEC60529). MCU terminal is made of brass material, and plated with nickel as tropical climate
energy meter. MCU mounting complies with DIN VDE 0611-1 and EN60947-7-1 standards.
52

Shenzhen Inhemeter Co.,Ltd. | Introduction

keypad prepayment meter and vending system solution

DIN rail mounted single phase split keypad prepaid energy meter operation diagram:

5.2 Three Methods for Communication With MCU




DDZ1513-CIU-CABLE

Two core communication cable

DDZ1513-CIU-PLC

Power line wave-carrier communication

DDZ1513-CIU-RF

Low power wireless communication

MCU of DIN rail mounted single phase split keypad prepaid energy meter is installed outdoors.
Generally it can be installed in special metering box by fixing on DIN rail without mounting
screws.

5.3 Three Communication Modes With MCU


DDZ1513-CIU-CABLE

Two core communication cable

Shenzhen Inhemeter Co.,Ltd. | Three Methods for Communication With MCU

53

Keypad Prepayment Energy Meter and Vending System Solution

DDS1513-CIU-PLC

Power line wave-carrier communication

DDS1513-CIU-RF

Low power wireless communication

DDZ1513-MCU-DIN : MCU without display component


DDZ1513-MCU-DIN-LCD : MCU with display component

54

Shenzhen Inhemeter Co.,Ltd. | Three Communication Modes With MCU

keypad prepayment meter and vending system solution

5.4 MCU Shape Drawing


Unit: mm

5.5 MCU

Installation Diagram

Unit: mm

Shenzhen Inhemeter Co.,Ltd. | MCU Shape Drawing

55

Keypad Prepayment Energy Meter and Vending System Solution

5.6 DIN Rail Mounting Diagram


Unit: mm

56

Shenzhen Inhemeter Co.,Ltd. | DIN Rail Mounting Diagram

keypad prepayment meter and vending system solution

5.7 MCU Terminals


Unit: mm

Shenzhen Inhemeter Co.,Ltd. | MCU Terminals

57

Keypad Prepayment Energy Meter and Vending System Solution

5.8 MCU Typical Wiring Diagram

58

Shenzhen Inhemeter Co.,Ltd. | MCU Typical Wiring Diagram

keypad prepayment meter and vending system solution

5.9 Characteristics
MCU unit without display components

Meter top terminal

Meter data reading port

CIU communication cable port

Meter bottom terminal

Meter MCU unique serial number

MCU and CIU communication status


indicator light

Meter impulse indicator light

Meter alarm status indicator light

Photoelectric communication port

MCU unit with display components


1 Meter top terminal
2 Meter data reading port
3 LCD display screen
4 CIU communication cable port
5 Meter bottom terminal
6 Meter MCU unique serial number
7 MCU and CIU communication status indicator light
8 Meter impulse indicator light
9 Meter alarm status indicator light
10 Photoelectric(infrared) communication port

Shenzhen Inhemeter Co.,Ltd. | Characteristics

59

Keypad Prepayment Energy Meter and Vending System Solution

5.10

Single phase 2-wire/3-wire split type keypad prepayment energy


meter complying to ANSI

5.11

Single Phase ESKOM Keypad Prepayment Energy Meter

DDZ1513-ESKOM-ESKOM is a single-phase keypad prepayment energy meter complying to


STS(Standard Transfer Specification) protocol and South African ESKOM SCSSCAAA9
back-mounting(socket mounting), can enter 20-bit STS code, certified by STS Association.

60

Shenzhen Inhemeter Co.,Ltd. | Single phase 2-wire/3-wire split type keypad prepayment energy
meter complying to ANSI

keypad prepayment meter and vending system solution

5.11.1 Outline of the mete


Unit: mm
Including the mounting base:

Excluding the mounting base:

Shenzhen Inhemeter Co.,Ltd. | Single Phase ESKOM Keypad Prepayment Energy Meter

61

Keypad Prepayment Energy Meter and Vending System Solution

Mounting base of the meter:

Mounting base of the meter:

62

Shenzhen Inhemeter Co.,Ltd. | Single Phase ESKOM Keypad Prepayment Energy Meter

keypad prepayment meter and vending system solution

Wiring of the mounting base:

Shenzhen Inhemeter Co.,Ltd. | Single Phase ESKOM Keypad Prepayment Energy Meter

63

Keypad Prepayment Energy Meter and Vending System Solution

Chapter6

SMARTVend Anywhere (System)

6.1 Introduction
SMARTvend: Inhemeter smart network power vending management system(Smart Vending
Anywhere) is introduced after years of experience of developing IC prepayment energy meter,
keypad prepayment energy meter, SMS prepayment energy meter power vending
management system and after-payment power vending management mode. It uses B/S and
C/S mixing network construction and network data is under centralized management. Value
added service, various power vending, 7*24 power vending anywhere can be realized by
co-operation with the bank, the network companies, etc. It is mainly used to manage energy
charge collection of utilities, companies, schools and etc, and plays important role in automatic
collection of energy charges and load control. Smart Vending Anywhere SystemSVASbrings
convenience, efficiency and security for users and thus simplifies the complexity of
management, reduces cost and improves revenue collection.

6.2 SMARTvend Characteristic




Network based system structure and operation mode

Multi-method Billing and compatible with various billing solution

Various power vending methods available, i.e. vending through internet, ATM,
agent, scratch card.

Multi-station or single station management for vending points. Vending points can
be centralized for control and vending authorization.

Support all STS certified meter and IC card prepayment meter as well.

Abundant graphic statistic and analysis report forms.

Multi-level management mode and digital certificate authentication system to


ensure system security.

Users are given rights according to position which can be done to each control point
of each module.

Built-in third party data exchange port and can communicate with external
marketing and automatic meter reading system.

Desktop user-defined

6.3 SMARTvend Structure


Servers Applicable:


Database Server: used for storage of business data.

Web Server: used for providing HTTP service to connect vending points of utility
company, and connection for bank payment collection, internet power vending,
vending agency, etc.

64

Shenzhen Inhemeter Co.,Ltd. | Introduction

keypad prepayment meter and vending system solution

Data

Exchange Server: maintain multilayer system data exchange and data

exchange with different suppliers.




Affair Server: for affair data processing and encryption, etc.

Management Terminal: for system comprehensive maintenance and report forms


analysis.

Notice: Abovementioned server application can be grouped according to customer demand and
development condition. all service function operated in one server is supported as well.

Other Systems:



Power marketing and its business system.


Telecommunication port: payment collection port provided by bank for ATM
automatic and internet power vending.

Other System port: payment collection through agents like network company,
telecommunication company or scratch card.

6.4 SMARTvend Compatibility and Scalability


SMARTvend SVAS adopts unified power vending and revenue collection method, compatible
with various IC prepayment energy meters, STS keypad prepayment energy meter, SMS
Shenzhen Inhemeter Co.,Ltd. | SMARTvend Compatibility and Scalability

65

Keypad Prepayment Energy Meter and Vending System Solution

prepayment energy meter researched by Inhemeter, as well as STS keypad energy meter
made by different manufacturers. Meanwhile, it makes SMARTvend SVAS compatible with
prepayment energy meter with different type and different protocol, prepayment water meter,
prepayment hot water meter and gas meter by system third party extended interface base.

6.5 Diversified Power Vending Module


SMARTvend SVAS provides various vending modes in order to bring convenience and
efficiency to users and reduce workload of vending personnel.


ATM: Users purchase electricity from ATM self-help equipment. Recharge will be
made by connecting with bank system after safety certificate. ATM will read the
card and print digit code.

PC recharge: Users enter online network vending website to purchase electricity(IC


card reader is needed for operation for IC prepayment energy meter). After paying
and confirming the payment on internet, vending management center will make
safety authentication and give vending instruction for printing digit code.

POS, PDA recharge: Users enter network vending website by internet with
handhold computer for recharge (It can not recharge for IC prepayment energy
meter).

Agent vending: Banks or other agent vendors authorized by the utility provide
vending business for users.

Recharge hall: Integrated petty charges recharge hall provide electricity vending
business.

66

Shenzhen Inhemeter Co.,Ltd. | Diversified Power Vending Module

keypad prepayment meter and vending system solution

Vending hall: Power supply system provides internal vending network.

Scratch card: Telecom companies use their value added service to transfer the
recharge payment and give recharge instruction (It can not recharge for IC
prepayment energy meter).

SMS: Telecom companies use their value added service to transfer the recharge
payment, and after successful recharge transferring, recharge can be made by
SMS. It is applicable for SMS prepayment energy meter and STS keypad
prepayment energy meter (It can not recharge for IC prepayment energy meter).

6.6 SMARTvend Functions


SMARTvend SVAS has three versions: standard version, professional version and enterprise
version. Different version system contains different functions and supports different meter type.
Customers can choose according to their actual business requirement.
SMARTvend SVAS has following function modules:
1 Daily business processing module
Customer data maintenance, power consumption contact signing and canceling, petty
charge collection, power vending, meter exchange, card complement, card data
maintenance, and complementally bill printing.
2 Power vending network management module:
Contact signing or canceling of vending network, vending terminal management, vending
network reconciliation, vending network permission, commission payment, etc
3 Tempering module
Customer power off/power recovery, tempering charge collection, handling charge
collection of power off made by customers, etc
4 Charge collection module
Petty charge collection, capacitance increase charge collection, meter freezing charge
collection
5 Reports outputting module
Account opening integrated report, vending integrated report, consumption integrated
report, tempering integrated report, vending network integrated report, charges integrated
report, etc daily report outputting, consumption and vending and other analyses report
outputting
6 System management module
Company information management, department management, role permission
management, user management, electricity price management, system operation data
management, data management, data maintenance, data exchange management, etc,
7 Assistance module: online assistance display

6.7 Consist of System


Inhemeter

keypad

prepaid

power

vending

management

system

(Smart

Vending

Shenzhen Inhemeter Co.,Ltd. | SMARTvend Functions

67

Keypad Prepayment Energy Meter and Vending System Solution

Anywhere)uses B/S and the C/S mixing network construction and network data is under
centralized management. Value added service and various power vending can be realized by
co-operation with the bank, the network companies, etc. INHEMETER Smart Vending
Anywhere (ISVA) brings convenience, efficiency and security for users and thus simplifies the
complexity of management, reduces cost and improves revenue collection.

6.8 Consist of ISVA


1.
2.
3.
4.
5.
6.

Smart Vending Anywhere (System)


Database Software (Used by ISVA)
Computer Installed with ISVA
Power Vending Encryption Module
TOKEN Code Printer, card reader or barcode reader
Handheld Meter Reading Device (optional)

6.9 Servers Applicable




Database Server: used for storage of business data.

Web Server: used for providing HTTP service to connect vending points of utility
company, and connection for bank payment collection, internet power vending,
vending agency, etc.

Data

Exchange

Server: maintain multilayer system

and data exchange

data exchange

with different suppliers.

Affair Server: for affair data processing and encryption, etc.

Management Terminal: for system comprehensive maintenance and report forms


analysis.
Notice: abovementioned server application can be grouped according to
customer demand and development condition. all service function operated in one
server is supported as well.
Other Systems:

Power marketing and its business system.

Telecommunication port: payment collection port provided by bank for ATM


automatic and internet power vending.

Other System port: payment collection through agents like network company,
telecommunication company or scratch card.

68

Shenzhen Inhemeter Co.,Ltd. | Consist of ISVA

keypad prepayment meter and vending system solution

6.10

System Characteristic


Network based system structure and operation mode

Multi-method Billing and compatible with various billing solution

Various power vending methods available, i.e. vending through internet, ATM,
agent, scratch card.

Multi-station or single station management for vending points. Vending points can
be centralized for control and vending authorization.

Support all STS certified meter and IC card prepayment meter as well.

Abundant graphic statistic and analysis report forms.

Multi-level management mode and digital certificate authentication system to


ensure system security.

Users are given rights according to position which can be done to each control
point of each module.

Built-in third party data exchange port and can communicate with external
marketing and automatic meter reading system.

Desktop user-defined

MultiStatio

Single Station

Shenzhen Inhemeter Co.,Ltd. | System Characteristic

69

Keypad Prepayment Energy Meter and Vending System Solution

Chapter7

AMR/AMM of INHEMETER

The Public Basic Energy/Resources Information Acquisition & Control Management System
(AMR/AMM) of INHEMETER Instrument Co., Ltd is a comprehensive AMR/AMM solution
which contains local data acquisition of electricity/water/gas meters, data transmission by
remote communications, data storage in system master station, data analysis and marketing
management. It provides energy/resources consumption data and control & management
methods to the public utilities of electricity, water and gas during their business applications, in
order to achieve rational resources distribution, reduce energy loss, improve energy/resources
utilization efficiency, save resources and protect environment, and maximize the social
benefits ultimately.

The Public Basic Energy/Resources Information Acquisition & Control Management System
(AMR/AMM) can effectively promote the utilities to realize their standardization and scientific
management in measurement, meter reading, control and charging mode etc. It can provide
accurate, real-time and reliable date from the source of users energy/resources consumption,
reflect customer demand quickly and enhance the utilities service level and their fast response
ability to market changes. In order to fulfill social responsibilities and respond to the energy
saving policies of Government, this system provides a strong technical support to implement
time-of-use tariff & stepped tariff of electricity/water/gas and adjust electricity/water/gas price
70

Shenzhen Inhemeter Co.,Ltd. | System Characteristic

keypad prepayment meter and vending system solution

timely and effectively based on the changes in market of energy/resources supply and
demand.
The Public Basic Energy/Resources Information Acquisition& Control Management System
(AMR/AMM) of INHEMETER Instrument Co., Ltd is divided into the following three parts based
on

its

physical

structure:

System

Master

Station,

Communication

Channel,

and

Acquisition/Control Equipments of Utility Meters.


System master station can be built with united or separate network based on different needs
and different places. If its network is connected to public communication channel or other
system, the firewall should be adopted for security isolation and to ensure information security
of the system. The physical structure of System Master Station network mainly consists of
database servers, disk arrays, application servers, front servers, interface servers,
workstations, GPS clock, firewall, and relative network equipments etc. The scale of system
master station depends on the quantity of utility meter users, data acquisition and control
points in the system as well as the number of concurrent workstations.
Communication Channels are remote communication channels between System Master
Stations and terminals, which mainly includes special optic fiber channel, GSM/GPRS/CDMA
public wireless networks, PSTN public cable network channel and the special communication
networks built by utilities etc.

Acquisition/Control Equipments of Utility Meters are the metering data acquisition terminals
and utility meters installed in the measurement/control sites of public basic energy/resources.
For the power industry, it includes mainly metering data acquisition terminals in power
plant/substation, special transformer acquisition terminals, public transformer acquisition
terminals, remote communication multi-function meters, data concentrators in low-voltage
transformer district as well as all the single-phase/three-phase watt-hour meters with function
of short-range communication. For water/gas industry, it includes mainly concentrators,
collectors as well as all the water/gas meters

With function of short-range communication. Short-range communication mode can be


selected as power line carrier (PLC), RS-485, M-bus, Zigbee, wireless (RF) and so on.
Shenzhen Inhemeter Co.,Ltd. | System Characteristic

71

Keypad Prepayment Energy Meter and Vending System Solution

Chapter8 Available Types of Keypad Prepayment Energy Meter

8.1 Prepayment Energy Meters of Inhemeter

72

Shenzhen Inhemeter Co.,Ltd. | Prepayment Energy Meters of Inhemeter

keypad prepayment meter and vending system solution

Shenzhen Inhemeter Co.,Ltd. | Prepayment Energy Meters of Inhemeter

73

Keypad Prepayment Energy Meter and Vending System Solution

8.2 Order List of Single-phase Keypad Meter

8.3 Order List of Single-phase Split Type Keypad Meter

74

Shenzhen Inhemeter Co.,Ltd. | Order List of Single-phase Keypad Meter

keypad prepayment meter and vending system solution

8.4 Order List of DIN rail-mounting Single-phase Split Keypad Meter

8.5 Order List of Single-phase ESKOM Keypad Meter

Shenzhen Inhemeter Co.,Ltd. | Order List of DIN rail-mounting Single-phase Split Keypad Meter

75

Keypad Prepayment Energy Meter and Vending System Solution

8.6 Order List of Three-phase Keypad Meter

8.7 Order List of Three-phase Split Keypad Meter

76

Shenzhen Inhemeter Co.,Ltd. | Order List of Three-phase Keypad Meter

keypad prepayment meter and vending system solution

8.8 Order List of Related Software and Accessories


No.

Model

Name

Unit

diagram

Prepayment power
1

SMARTvend

vending management
system for IC card and

set

Keypad
Hand Held Unit
(HHU)
PSION TEKLOGIX
WORKABOUT PRO3
7527C-G2
2

(including meter

set

reading software)
Huaxia
PDA-2
(including meter

set

reading software)
Optical
3

communication

pcs

cable
TP-USB-IEC
Security Module

TSM210-USB
Magnetic card reader
YD-626

set

set

Bill printer
Desktop thermal
printer

SRP150

set

6
Desktop multi-stylus
printer
Portable printer
7

SRP270

set

SPP-R200BG
(with leather case and

set

battery

Shenzhen Inhemeter Co.,Ltd. | Order List of Related Software and Accessories

77

Contact with us

78

Shenzhen Inhemeter Co.,Ltd. | Contact with us

enzhen INHEMETER Co.,Ltd.


Add: 7/F,Science & Industry Park Building,
Science & Industry Park,Nanshan District,
Shenzhen,China.
P.C.:518057
Tel: +86-755-26616686
Fax: +86-755-26616689
Web: www.inhemeter.com
E-mail: marketing@inhemeter.com