Roof Extract Fans DV

Ventilation Hoods DLH


Smoke Extract Fans ER

Roof Extract Fans


Ventilation Hoods
Smoke Extract Fans

DV
DLH
ER

Summary .................................................................................................................. Seite


Roof Extract Fans DV
Product review ............................................................................................................................. 3
Summary data sheet .................................................................................................................. 4
General instructions ................................................................................................................... 5
Roof Extract Fan DV 30 ....................................................................................................... 6 - 7
Roof Extract Fan DV 40 ....................................................................................................... 8 - 9
Roof Extract Fan DV 56 ................................................................................................... 10 - 11
Roof Extract Fan DV 71 .................................................................................................. 12 - 13
Roof Extract Fan DV 90 .................................................................................................. 14 - 15
Roof Extract Fan DV 125 ............................................................................................... 16 - 17
Motor protection units ............................................................................................................ 18
Diagrams for control switches / diagrams for isolator switches .................................. 19
Diagrams for isolator switches .............................................................................................. 20
Control unit DigiPro .................................................................................................................. 21
Sample specification ............................................................................................................... 22
Roof Ventilation Hoods DLH
Product review .......................................................................................................................... 24
Dimensions ................................................................................................................................ 24
Pressure drops Intake exhaust .......................................................................................... 24
Dimensions of accessories ..................................................................................................... 25
Smoke Extract Fans ER
Product review .......................................................................................................................... 26
Summary data sheet ............................................................................................................... 27
General instructions ....................................................................................................... 28 - 29
RDM 56/57-25.. Performances / Dimensions ...................................................... 30 - 31
RDM 56/57-35.. Performances / Dimensions ...................................................... 32 - 33
RDM 56/57-45.. Performances / Dimensions ...................................................... 34 - 35
RDM 56/57-56.. Performances / Dimensions ...................................................... 36 - 37
RDM 56/57-71.. Performances / Dimensions ...................................................... 38 - 39
RDM 56/57-90.. Performances / Dimensions ...................................................... 40 - 41
Isolator switches ....................................................................................................................... 42
Dimensions of accessories ..................................................................................................... 43
Sample specification ............................................................................................................... 44

Roof Extract Fans DV

Technical Description

Fan range DV 30
The fans of the range DV 30, for horizontal discharge, are suitable
for discharging slightly polluted but not aggressive air or vapours
from - 20C to app. + 40C. The rectangular casing, made of
galvanised sheet steel, has two opposite mounted discharge outlets
protected from the weather with an aerodynamically shaped grille,
which provide for horizontally directed, swirl-free air discharge.
All roof fans are equipped with an isolator switch ready for
connection.

Fan range DV 40-125


The fans of the range DV 40 - 125, for vertical discharge, are
suitable for discharging slightly polluted but not aggressive air or
vapours from - 20C to app. + 40C. The stylish casing and the base
plate are made of galvanised sheet steel. The centrifugal impeller
with backward curved blades is made of highly resistant aluminium.
The exhaust air, due to the V-casing design, is rejected vertically far
from the roof.
All roof fans are equipped with an isolator switch ready for
connection.

Motors
Well tried and tested integral drive motors are used. Noise-tested,
maintenance-free deep-groove ball bearings give the motor long
life. To avoid overheating, every motor is equipped with thermal
contacts. This thermal protection has to be effective in operation
in order to enable the user to claim for warranty in the case of
break down. Please follow the instructions of the wiring diagram
for connecting the thermal contacts correctly.

Roof Extract Fans DV

Summary data sheet

A full fan line: 36 standardised sizes


Performance range: 445 up to 34 550m/h

Roof
fan
type DV

Voltage
V

Flow
rate
Vmax m/h

30-22-2E
30-22-4E
30-25-2E
30-25-4E

230
230
230
230

Speed
min-1

Max.
absorbed
power kW

Full load
current
A

1step

680
445
1250
800

2370
1400
2020
1390

0,11
0,04
0,16
0,06

0,46
0,17
0,68
0,28

E1-16
E1-16
E1-16
E1-16

40-28-4/4 3x400Y
40-28-4E
230
40-28-6E
230
40-31-4/4 3x400Y
40-31-4E
230
40-31-6E
230

1730/1570
1690
1120
2440/2010
2550
1670

1420/1260
1380
910
1340/1070
1420
920

0,13/0,09
0,16
0,08
0,19/0,13
0,23
0,12

0,40/0,16
0,76
0,34
0,43/0,22
1,2
0,54

56-35-4/4
56-35-4E
56-35-6E
56-40-4/4
56-40-6/6
56-40-4E
56-40-6E
56-45-4/4
56-45-6/6
56-45-4E
56-45-6E

3x400Y
230
230
3x400Y
3x400Y
230
230
3x400Y
3x400Y
230
230

3470/2910
3470
2380
4830/4250
3100/2520
4340
3100
6800/6130
4190/3060
6450
4150

1340/1080
1340
930
1400/1190
890/690
1220
890
1420/1250
860/600
1330
850

0,35/0,22
0,40
0,15
0,58/0,44
0,22/0,13
0,52
0,20
0,95/0,76
0,30/0,17
0,95
0,31

71-50-4/4
71-50-6/6
71-50-4E
71-50-6E
71-56-4/4
71-56-6/6

3x400Y
3x400Y
230
230
3x400Y
3x400Y

9150/7740 1350/1100
6250/5430
930/780
8660
1260
6100
900
12580/9950 1270/960
8990/7790
920/770

Control units*
Sound
Wiring Weight
25steppower
diagram
step
step
less LWA Vmax dB No.
kg
-

E5-1
E5-1
E5-1
E5-1

ES-3
ES-3
ES-3
ES-3

72
64
77
66

507
507
507
507

5,5
5,0
6,5
6,0

D1
DS
E1-16
E1-16 E2-6
D1
DS
E1-16
E1-16 E2-6

D5-1
E5-1
E5-1
D5-1
E5-1
E5-1

ES-3
ES-3
ES-3
ES-3

71/68
70
59
71/66
72
61

515
508
508
515
508
508

23
22
22
23
23
23

0,75/0,39
1,9
0,72
1,35/0,74
0,55/0,23
2,3
0,91
2,30/1,30
0,67/0,32
4,4
1,4

D1
E1-16
E1-16
D1
D1
E1-16
D1
D1
E1-16

DS
DS
DS
DS
DS
-

D5-1
E5-3
E5-1
D5-3
D5-1
E5-3
E5-1
D5-7
D5-1
E5-7
E5-1

ES-3
ES-3
ES-3
ES-3

77/72
77
67
80/77
69/63
77
69
83/80
70/62
82
70

515
508
508
515
515
509
508
515
515
509
508

35
35
35
40
37
40
37
44
44
44
44

1,60/1,05
0,52/0,38
1,45
0,54
2,40/1,46
0,82/0,59

3,20/1,80
1,30/0,69
6,3
2,6
4,30/2,4
2,10/1,1

D1
D1
D1
D1

DS
DS
DS
DS

D5-7
D5-3
E5-7
E5-3
D5-12
D5-7

85/80
75/71
84
75
86/80
78/74

515
515
509
509
516
515

73
64
72
64
82
71

90-63-6/6 3x400Y 12500/10300


90-71-6/6 3x400Y 16850/13640
90-75-6 * 3x400
20000
90-75-8
3x400Y
15000
90-75-6/12 3x400YY/Y 20000/10000

900/700
880/680
870
650
950/480

1,30/0,88
2,50/1,50
3,4
1,6
4,4/0,7

2,9/1,7
5,0/2,8
6,5
3,3
8,7/2,6

D1
D1
D1
-

DS
DS
-

D5-7
D5-12
D5-7
-

81/76
85/79
86
78
88/70

515
516
502
534
551

119
139
140
135
166

125-80-6 * 3x400
125-80-8 3x400

945
660
960/480
940

5,2
2,0
5,5/0,85
8,8

10,2
4,4
11,0/3,3
16,4

D1
-

D5-12
-

90
81
90/72
94

549
537
551
549

215
206
215
238

125-80-6/12 3x400YY/Y

24800
17600
24800/12470

125-90-6 * 3x400Y
* Fan not speed controlled

34550

Roof Extract Fans DV

General instructions

Safety Guards

All roof extract fans are supplied with a discharge-side mesh safety guard in accordance
with DIN EN 294. The inlet side is not fitted with a standard guard, because it is normal
practice to attach other system parts to the side. However, if the unit is installed in such
a way that accidental contact with the impeller is possible, an additional inlet guard has to
be fitted acc. to DIN EN 294! The fans may only be put into operation if all necessary
protection devices are fitted and made effective (see maintenance instructions)! The
safety guards are to be executed acc. to DIN EN 292 1, chapter 3.22 Separating safety
devices and DIN EN 292 2, chapter 4 Technical protection measures.

Safety instructions

Transport, fitting, electrical connection, start up, and maintenance are to be executed
following to the instructions given with the manual and by respecting the actual standards,
guide lines, and safety rules.

Performance data

The performance curves are obtained using an inlet side test chamber in accordance with
DIN 24 163-2 Fans, performance tests, standard test equipment. The performance grids
show the effective pressure increase pfa (Pressure increase obtained from the fan in
free-field conditions) as a function of the flow volume VL.
Reference media density: 1 = 1.15 kg/m. The roof fans comply with the tolerances of
Class 2 of DIN 24 166 Fans, Technical Specifications.

Sound Data

Measurement and evaluation of noise levels are in accordance with DIN 45 635 - 38
Sound measurements on machines; fans. In the technical data the A-weighted sound
power level at maximum flow rate is given.
The computer aided data collection and evaluation enables to obtain highly reliable data
precision. In the curves the emission value of the A-sound-power level LWA is given,
having the same value for intake (LWA3) as for the discharge (LWA8).
For more exact calculations when determining the required attenuation, the sound power
level in the octave bands is important.
LWoct 3/8= LWA + LWrel 3/8
The relative sound power levels for inlet and discharge sides, at various duty points, can be
read from the corresponding tables.

Because conditions in the operating environment are usually far from ideal for
measurement and can vary greatly, a determination of the A-sound-pressure level at any
distance is only possible with great uncertainty.
30
dB

a
b

20
10

m 10

Influence of the back draught damper

LPA LWA L
The diagram on the left side supplies the correction value L in function of the distance
r from the fan centre. Under ideal conditions, with a clear hemisphere of sound
propagation, curve a is valid. However, curve b is recommended for practical estimates.
The calculation of the intake sound-power level is only possible if the exact noise
parameters of the connected room are known (see VDI 2081!).

Due to turbulences generated by the back draught damper the sound data for intake and
discharge may increase by app. 3 dB at discharge when a damper is fitted.
It is recommended to provide a duct section between fan and damper because under this
configuration the indicated pressure drops are applicable.
If the damper is directly fitted to the fan higher pressure losses have to be expected.

Roof Extract Fans DV


Roof
fan
Type DV
30-22-2E
30-22-4E
30-25-2E
30-25-4E

Flow
rate
Vmax m/h
680
445
1250
800

V
230
230
230
230

Speed

Absorbed
power
max kW
0,11
0,04
0,16
0,06

min-1
2370
1400
2020
1390

Control units*
25step
step
E5-1
E5-1
E5-1
E5-1

1step
E1-16
E1-16
E1-16
E1-16

Pa

Sound Wiring Weight


steppower diagram
less LWA Vmax dB No.
kg
ES-3
72
507
5,5
ES-3
64
507
5,0
ES-3
77
507
6,5
ES-3
66
507
6,0

74

DV 30-25-2E 1
DV 30-25-4E 2

78

DV 30-22-2E 1
DV 30-22-4E 2

dB

dB

400

Full load
current
A
0,46
0,17
0,68
0,28

L WA

LW

Pa

Voltage

Performance Data DV 30

500

350

73

300

400

76

250

70

300
1

62

100

2 5
9

50

72

64
0

100

200

300

0
0,05
Flow rate V

400

600

500
0,15

0,1

*
m/h

Available pressure pfa

150

70

Available pressure pfa

200

72

200 67

74

2 63
100

77

66
0

200

400

600

0
0,1
Flow rate V

m/s

*
1200 m/h

1000

800

0,3

0,2

m/s

* Pressure drop in the back draught damper


- Frequency 50 Hz
- Media density1,15 kg/m
Attenuation values
Average
Values
Silencer upstand
ZDS..-0028 16 dB

values in dB at mid frequencies


63 125 250 500 1000 2000 4000 8000 Hz
2

12

18

22

Pressure loss
Pressure loss pA through silencer upstand, at flow rates of
750
900
Silencer upstand
ZDS..-0028
22
30
Intake(LWrel3 = LWoct3 - LWA3 )
Relative sound power level LWrel3 at mid frequencies fm
Duty point 6 3
DV 30-22
0,3 Vmax
9
0,6 Vmax
9
Vmax
7
DV 30-25
0,3 Vmax
9
0,6 Vmax
9
Vmax
7

20

15 dB

1000

m/h

40 Pa

Discharge (LWrel8 = LWoct8 - LWA8 )


Relative sound power level LWrel8 at mid frequencies fm

125 250 500 1000 2000 4000 8000

Hz

Duty point

63

125 250

500

1000 2000 4000 8000

Hz

9
7
4

5
4
2

-2
-2
-1

-11
-10
-9

-18
-16
-12

-22
-20
-16

-31
-28
-22

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

-7
-7
-11

-3
-4
-5

0
-2
-4

-3
-3
-4

-6
-6
-5

-7
-7
-7

-14
-13
-12

-24
-23
-21

dB
dB
dB

9
7
4

5
4
2

-2
-2
-1

-11
-10
-9

-18
-16
-12

-22
-20
-16

-31
-28
-22

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

-7
-7
-11

-3
-4
-5

0
-2
-4

-3
-3
-4

-6
-6
-5

-7
-7
-7

-14
-13
-12

-24
-23
-21

dB
dB
dB

Roof Extract Fans DV

Dimensions DV 30
Mains lead

DV 30-22
97

6M6

330

25

ZBU 01-0028-18
Connecting plate

ZDS 20-0028
Silencer upstand
278
245

183

250

ZBS 20-0031
Flat roof
295
245
upstand

97

21
M6
341

DV 30-25

M6
6

410

Mains lead

ZBU 01-0028-22
Connecting plate
229

6M6

6M6

190

M
6

115
765

300
610

213

259

518

518

518

ZBS 23-0031
Flat roof upstand high

ZDS 09-0028-#
Silencer upstand for inclined roof

278
245

278
245

ZKF 01-0180
Intake flexible connection
67

ZKF 13-0225
Intake flexible connection
67

190

183
213
233

229
259
279

150

518

ZBS 09-0031-#
Upstand fr inclined roof

ZKF 01-0180
Mating flange
M
6

278
245

150

150

67

ZKF 13-0225
Mating flange
67

183
213
233

229
259
279

M
6

150

ZBS 11-0031
Soaker sheet (for corrugated roof)

# = inclination up to 45 possible ZLK 01-0180


within 5 steps. Indicate inclination Automatic back draught
with type when ordering
damper
ZBS 09-0031-05 (od. 10, 15,
67
20, 25, 30, 35, 40, 45)
183
213
233

ZLK 03-0225
Automatic back draught
damper
67

229
259
279

M
6

290

920

Roof Extract Fans DV


Roof
Voltage
fan
Type DV
V
40-28-4/4 3x400Y
40-28-4E
230
40-28-6E
230
40-31-4/4 3x400Y
40-31-4E
230
40-31-6E
230

Flow
rate
Vmax m/h
1730/1570
1690
1120
2440/2010
2550
1670

Speed
min-1
1420/1260
1380
910
1340/1070
1420
920

Pa
A

=6

200 6
8

9d

Full load
current
A
0,40/0,16
0,76
0,34
0,43/0,22
1,2
0,54

Sound Wiring Weight


steppower diagram
less LWA Vmax dB No.
kg
71/68
515
23
ES-3
70
508
22
ES-3
59
508
22
71/66
515
23
ES-3
72
508
23
ES-3
61
508
23

DV 40-31-4/4 1 2
DV 40-31-4E 3
DV 40-31-6E 4

240

65

40

400
800
0
0,1
0,2
Flow rate V

1200
0,3

1600

2000

0,4

0,5

72
71

0
0,1
Flow rate V

66

200 400 600 800 1000 1200 1400 1600


m/h
0,5 m/s
0,2
0,3
0,4

62

71

70
68

59

80

69

50

57

70

67

61

61

68

120

65

53

160

3
2

100 5
7

67

62

68

150

200 6
6

64

Control units*
125step step
step
D1
DS
D5-1
E1-16
E5-1
E1-16 E2-6
E5-1
D1
DS
D5-1
E1-16
E5-1
E1-16 E2-6
E5-1

Pa
280 LWA =
72
dB
71

DV 40-28-4/4 1 2
DV 40-28-4E 3
DV 40-28-6E 4

67

Available pressure pfa

Absorbed
power
max kW
0,13/0,09
0,16
0,08
0,19/0,13
0,23
0,12

Available pressure pfa

LW

Performance Data DV 40

2400

0,6

0,7

m/h
m/s

Pressure drop in the back draught damper


- Frequency 50 Hz
- Media density1,15 kg/m
Attenuation values
Average
Values
Discharge silencer
ZDH 20-0250 11 dB
Silencer upstand
ZDS..-0040 16 dB

values in dB at mid frequencies


63 125 250 500 1000 2000 4000 8000 Hz
0

15

22

20

13

14 dB

13

19

23

21

15 dB

Pressure loss
Pressure loss pA through silencer upstand, at flow rates of
1500
2000
3000
Silencer upstand
ZDS..-0040
25
40
100

Intake (LWrel3 = LWoct3 - LWA3 )


Relative sound power level LWrel3 at mid frequencies fm
Duty point
DV 40-28
0,3 Vmax
0,6 Vmax
Vmax
DV 40-31
0,3 Vmax
0,6 Vmax
Vmax

4000

m/h

170

Pa

Discharge (LWrel8 = LWoct8 - LWA8 )


Relative sound power level LWrel3 at mid frequencies fm

63

125 250 500 1000 2000 4000 8000

Hz

Duty point

63

125 250

500

1000 2000 4000 8000

Hz

12
11
4

13
10
11

0
-1
-1

-6
-5
-5

-10
-7
-7

-11
-9
-10

-18
-15
-17

-32
-29
-30

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

5
-4
-9

0
-3
-2

-1
-3
-2

-5
-4
-4

-5
-5
-5

-6
-7
-7

-13
-13
-13

-22
-22
-25

dB
dB
dB

13
8
2

14
13
12

-2
-3
-3

-6
-6
-5

-11
-10
-8

-12
-11
-11

-16
-16
-16

-29
-28
-28

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

3
-5
-10

2
1
1

0
-1
-1

-5
-5
-4

-6
-6
-5

-7
-7
-7

-13
-12
-12

-20
-21
-22

dB
dB
dB

Roof Extract Fans DV


DV 40

Dimensions DV 40
Mains lead

ZDH 20-0250
Discharge silencer

138

410

28
6

M6
6

M6
440
671

12

626

ZBS 20-0040
Flat roof upstand

ZKK 20-0040
Intermediate piece

395
330

ZBU 01-0040-25
Connecting plate
256

M10

6M6

11.5
330
386

400
710

286
618

M
10

ZDS 20-0040
Silencer upstand
378
330

650

270

ZBS 23-0040
Flat roof upstand high

ZKE 11-0250
Intake flexible connection
67

378
330

618

256
286
306

ZDS 09-0040-#
Silencer upstand for inclined roof
378
330

618

535

270

ZBS 09-0040-#
Upstand for inclined roof
378
330

67

150

256
286
306

ZBS 11-0040
Soaker sheet (for corrugated
roof)

67

256
286
306

ZLK 21-0250
Damper with actuator
7

207
185

M
10

319

# = inclination up to 45 possible
within 5 steps. Indicate inclination
with type when ordering ZBS 090031-05 (od. 10, 15, 20, 25, 30, 35,
40, 45)
When using damper ZLK and
upstand silencer ZDS the damper
has to be fitted by using a plate
ZBU below silencer upstand.
When fitting damper to fan an
intermediate piece ZKK must be
added.

ZLK 01-0250
Automatic back draught
damper

180

10

150

340
618

150
M
10

150

ZKF 11-0250
Mating flange

920

256
286
306

Roof Extract Fans DV


Roof
fan
Type DV
56-35-4/4
56-35-4E
56-35-6E
56-40-4/4
56-40-6/6
56-40-4E
56-40-6E
56-45-4/4
56-45-6/6
56-45-4E
56-45-6E

Voltage

Flow
rate
Vmax m/h
3470/2910
3470
2380
4830/4250
3100/2520
4340
3100
6800/6130
4190/3060
6450
4150

V
3x400Y
230
230
3x400Y
3x400Y
230
230
3x400Y
3x400Y
230
230

Speed
min-1
1340/1080
1340
930
1400/1190
890/690
1220
890
1420/1250
860/600
1330
850

Pa
350 L
W

=7

Full load
current
A
0,75/0,39
1,9
0,72
1,35/0,74
0,55/0,23
2,3
0,91
2,30/1,30
0,67/0,32
4,4
1,4

1step
D1
E1-16
E1-16
D1
D1
E1-16
D1
D1
E1-16

Control units*
25step
step
DS
D5-1
E5-3
E5-1
DS
D5-3
DS
D5-1
E5-3
E5-1
DS
D5-7
DS
D5-1
E5-7
E5-1

4d

LW

70

69

64

50

200 67

80

1 2
3 4
5
3

80
79

70

61

77

65

0,6

0,8

4000

m/h
1,2 m/s

1,0

2000
0,6

3000
0,8

70

62

4000
1,0

1,2

5000
1,4

6000 m/h
1,6

values in dB at mid frequencies


63 125 250 500 1000 2000 4000 8000 Hz
0

15

22

20

13

14 dB

12

18

21

20

15 dB

Pressure loss
Pressure loss pA through silencer upstand, at flow rates of
3000
4000
6000
Silencer upstand
ZDS..-0056
25
42
80

83
82
80

Available pressure pfa

Attenuation values
Average
Values
Discharge silencer
ZDH 20-0355 11 dB
Silencer upstand
ZDS..-0056 16 dB

300

0,4

3000

2000
0,4

Pressure drop in the back draught damper


- Frequency 50 Hz
- Media density1,15 kg/m

74

0,2

0,2

76

1000
0

80

63
0

78
400

1000

77

DV 56-45-4/4
DV 56-45-6/6
DV 56-45-4E
DV 56-45-6E

LW
A =8
2 dB
81

56

100

Flow rate V

Pa

56

62

61

Flow rate V

200

5
2

77

1500 2000 2500 3000 3500 m/h


0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 m/s

70
70

69

77

72

67

1000

0,1 0,2

74

Available pressure pfa

100

500

74

75

Available pressure pfa

74

61

1 2
3 4
5
3

77

150

100

dB

300

65

65

500

DV 56-40-4/4
DV 56-40-6/6
DV 56-40-4E
DV 56-40-6E

75

70

200

= 79

400 7
6

Sound Wiring Weight


steppower diagram
less LWA Vmax dB No.
kg
77/72
515
35
ES-3
77
508
35
ES-3
67
508
35
80/77
515
40
69/63
515
37
77
509
40
ES-3
69
508
37
83/80
515
44
70/62
515
44
82
509
44
ES-3
70
508
44

Pa

DV 56-35-4/4 1 2
DV 56-35-4E 1
DV 56-35-6E 3

300
250

Absorbed
power
max kW
0,35/0,22
0,40
0,15
0,58/0,44
0,22/0,13
0,52
0,20
0,95/0,76
0,30/0,17
0,95
0,31

Performance Data DV 56

m/s

8000

m/h

160

Pa

Flow rate V
Intake(LWrel3 = LWoct3 - LWA3 )
Relative sound power level LWrel3 at
Duty point 6 3 125 250 500
DV 56-35
0,3 Vmax
16 12
1
-3
0,6 Vmax
11 11
1
-3
Vmax
8
11
1
-2
DV 56-40
0,3 Vmax
12 12
1
-3
0,6 Vmax
11 11
0
-4
Vmax
7
10
1
-3
DV 56-45
0,3 Vmax
1 2 1 3 -1
-6
0,6 Vmax
5
13
0
-6
Vmax
1
13
0
-5

10

mid frequencies fm
1000 2000 4000 8000

Hz

Discharge (LWrel8 = LWoct8 - LWA8 )


Relative sound power level LWrel8 at mid frequencies fm
Duty point 6 3 125 250
500 1000 2000 4000 8000

Hz

-11
-10
-10

-15
-11
-11

-19
-16
-19

-28
-26
-25

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

4
-3
-6

1
-1
0

-1
-3
-3

-4
-4
-4

-4
-5
-5

-8
-6
-6

-12
-12
-15

-21
-20
-21

dB
dB
dB

-10
-8
-8

-15
-12
-12

-18
-16
-19

-28
-24
-20

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

5
0
-4

2
1
1

0
-1
0

-4
-5
-4

-4
-5
-5

-9
-7
-8

-13
-11
-12

-19
-18
-15

dB
dB
dB

-11
-11
-11

-15
-14
-14

-19
-16
-19

-27
-25
-20

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

5
-2
-6

3
2
2

-1
0
0

-4
-5
-4

-5
-6
-5

-9
-8
-8

-12
-10
-13

-17
-17
-15

dB
dB
dB

Roof Extract Fans DV

Dimensions DV 56
Mains lead

DV 56

ZDH 20-0355
Discharge silencer

192

600

39
5

M8
8

M8
600
881

12

836

ZBS 20-0056
Flat roof upstand

ZKK 20-056
Intermediate piece

555
450

ZBU 01-0056-35
Connecting plate
361

M10

8M8

11.5
450
546

560
870

395
778

M
10

ZDS 20-0056
Silencer upstand
538
450

ZKE 11-0355
Intake flexible connection

430
800

ZBS 23-0056
Flat roof upstand high

89.5

538
450
361
395
421

778

ZDS 09-0056-#
Silencer upstand for inclined roof
778

538
450

ZBS 09-0056-#
Upstand for inclined roof

ZKF 11-0355
Mating flange
89.5

430

538
450

361
395
421

150

150

150

150

ZLK 01-0355
Automatic back draught
damper
236

205

M
10

10

89.5

361
395
421

ZBS 11-0056
Soaker sheet (for corrugated
roof)

M
10

420

# = inclination up to 45 possible
within 5 steps. Indicate inclination
with type when ordering ZBS 09- ZLK 21-0355
0031-05 (od. 10, 15, 20, 25, 30, 35, Automatic back draught
damper
40, 45)
When using damper ZLK and upstand
258
9.5
silencer ZDS the damper has to be
fitted by using a plate ZBU below
silencer upstand.
361
When fitting damper to fan an
395
421
intermediate piece ZKK must be
added.

920

11

Roof Extract Fans DV


Roof
fan
Type DV
71-50-4/4
71-50-6/6
71-50-4E
71-50-6E
71-56-4/4
71-56-6/6

Voltage

Flow
Speed
rate
Vmax m/h
min-1
9150/7740 1350/1100
6250/5430
930/780
8660
1260
6100
900
12580/9950 1270/960
8990/7790
920/770

V
3x400Y
3x400Y
230
230
3x400Y
3x400Y

Pa
700

WA

82

=8

4d

Absorbed
power
max kW
1,60/1,05
0,52/0,38
1,45
0,54
2,40/1,46
0,82/0,59

DV 71-50-4/4
DV 71-50-6/6
DV 71-50-4E
DV 71-50-6E

Performance Data DV 71
Full load
current
A
3,20/1,80
1,30/0,69
6,3
2,6
4,30/2,4
2,10/1,1

Pa

1 2
3 4
5
6

700

DV 71-56-4/4 1 2
DV 71-56-6/6 3 4

80

500

77

65

67

200

79

68

300

73
72

73

100

83

70

80

69

2
82

73

400 78
Available pressure pfa

74

74

100

m/s

86

m/h

80

1000 2000 3000 4000 5000 6000 7000 8000


0
0,5
2,0
1,0
1,5
Flow rate V

78

85
84

80

75

75

71

74

Available pressure pfa

6d

79

79

79

400

=8

600

500

200

LW

600

300

Control units*
Sound Wiring Weight
25steppower diagram
step
step
less LWA Vmax dB No.
kg
DS
D5-7
85/80
515
73
DS
D5-3
75/71
515
64
E5-7
84
509
72
E5-3
75
509
64
DS
D5-12
86/80
516
82
DS
D5-7
78/74
515
71

1step
D1
D1
D1
D1

2000
4000
6000
8000 10000 12000 m/h
0
0,5
2,5
3,0
2,0
1,5
1,0
m/s
Flow rate V

Pressure drop in the back draught damper


- Frequency 50 Hz
- Media density1,15 kg/m
Attenuation values
Average
Values
Discharge silencer
ZDH 20-0450 11 dB
Silencer upstand
ZDS..-0071 17 dB

values in dB at mid frequencies


63 125 250 500 1000 2000 4000 8000 Hz
0

15

21

20

16

17 dB

13

20

25

22

17 dB

Pressure loss
Pressure loss pA through silencer upstand, at flow rates of
5000
8000
10000
Silencer upstand
ZDS..-0071
25
60
95
Intake(LWrel3 = LWoct3 - LWA3 )
Relative sound power level LWrel3 at mid frequencies fm
Duty point
DV 71-50
0,3 Vmax
0,6 Vmax
Vmax
DV 71-56
0,3 Vmax
0,6 Vmax
Vmax

12

63

12000

m/h

110

Pa

Discharge (LWrel8 = LWoct8 - LWA8 )


Relative sound power level LWrel8 at mid frequencies fm

125 250 500 1000 2000 4000 8000

Hz

Duty point

63

125 250

500

1000 2000 4000 8000

Hz

15
11
7

9
7
6

2
1
1

-3
-3
-3

-9
-8
-8

-13
-11
-11

-14
-12
-12

-19
-15
-12

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

6
1
-2

5
5
4

1
0
1

-4
-5
-3

-5
-6
-6

-9
-8
-10

-12
-10
-12

-18
-16
-14

dB
dB
dB

13
7
4

9
9
9

4
4
3

-3
-4
-3

-9
-8
-8

-14
-12
-12

-15
-14
-14

-22
-18
-15

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

8
-1
-4

5
7
6

0
-1
-1

-4
-4
-3

-5
-5
-5

-9
-8
-9

-13
-11
-14

-19
-18
-16

dB
dB
dB

Roof Extract Fans DV

Dimensions DV 71
Mains lead

DV 71

ZDH 20-0450
Discharge silencer

222

740

48

M8
6

M8
750
1103

14

1016

ZBS 20-0071
Flat roof upstand

ZKK 20-0071
Intermediate piece

705
590

ZBU 01-0071-45
Connecting plate

M12

453

6M8

14
590
700

487

710
1020

988

M
12

ZDS 20-0071
Silencer upstand
688
590

ZKE 11-0450
Intake flexible connection

580

650

ZBS 23-0071
Flat roof upstand high

69.5

688
590

988

453
487
513

ZDS 09-0071-#
Silencer upstand for inclined roof
688
590

988

ZBS 09-0071-#
Upstand for inclined roof

ZKF 11-0450
Mating flange
69.5

580

688
590

453
487
513

150

150

ZLK 01-0450
Automatic back draught
damper
69.5

M
10

12

150

150

453
487
513

M
10

560

# = inclination up to 45 possible
within 5 steps. Indicate inclination
with type when ordering ZBS 09- ZLK 21-0450
0031-05 (od. 10, 15, 20, 25, 30, 35, Damper with actuator
40, 45)
300
When using damper ZLK and upstand
9.5
silencer ZDS the damper has to be
fitted by using a plate ZBU below
silencer upstand.
453
487
When fitting damper to fan an
513
intermediate piece ZKK must be
added.
282

ZBS 11-0071
Soaker sheet (for corrugated
roof)

1400

13

Roof Extract Fans DV


Roof
Voltage
Flow
Speed
fan
rate
Type DV
V
Vmax m/h
min-1
90-63-6/6 3x400Y 12500/10300 900/700
90-71-6/6 3x400Y 16850/13640 880/680
90-75-6 * 3x400
20000
870
90-75-8
3x400Y
15000
650
90-75-6/12 3x400YY/Y 20000/10000 950/480
Pa
LW

Absorbed
power
max kW
1,30/0,88
2,50/1,50
3,4
1,6
4,4/0,7

Performance Data DV 90
Full load
current
A
2,9/1,7
5,0/2,8
6,5
3,3
8,7/2,6

Pa

DV 90-63-6/6 1 2
= 81

Control units*
Sound Wiring Weight
25steppower diagram
step
step
less LWA Vmax dB No.
kg
DS
D5-7
81/76
515
119
DS
D5-12
85/79
516
139
86
502
140
D5-7
78
534
135
88/70
551
166

1step
D1
D1
D1
-

LW

dB

=8

DV 90-71-6/6 1 2

4d

500

400

78

75

74

79

400

300

Available pressure pfa

200

78

200

72

100

73

82

Available pressure pfa

300

69

76

100

Flow rate V

4000

6000

8000

10000
2,5

2,0

1,5

1,0

Pa

m/s

2000 4000 6000 8000 10000 12000 14000


0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0

Flow rate V

m/h
m/s

DV 90-75-6
1
2
DV 90-75-8
DV 90-75-6/12 3 4

LW

=
90

700

12000 m/h

3,0

85

2000
0,5

79

81

76

dB

88

600

drop in the back draught damper


*- Pressure
Frequency 50 Hz

87

500

Attenuation values
Average
Values
Discharge silencer
ZDH 20-0560 11 dB
Silencer upstand
ZDS..-090 15 dB

86
84

300

77

200 72

76

69 4
69

100

1,0

Flow rate V

8000
2,0

12000
3,0

16000
4,0

86

4000
0

20000 m/h
6,0 m/s

5,0

Intake(LWrel3 = LWoct3 - LWA3 )


Relative sound power level LWrel3 at mid frequencies fm
Duty point 6 3 125 250 500 1000 2000 4000 8000
DV 90-63
0,3 Vmax
17
7
3
-4
-8
-12 -14
-21
0,6 Vmax
15
8
3
-4
-8
-11 -14
-20
Vmax
13
8
4
-3
-8
-12 -15
-23
DV 90-71
0,3 Vmax
15
7
3
-4
-6
-11 -13
-20
0,6 Vmax
13
7
3
-4
-7
-11 -12
-19
Vmax
10
7
4
-4
-8
-11 -12
-19
DV 90-75
0,3 Vmax
15
7
3
-4
-6
-11 -13
-20
0,6 Vmax
13
7
3
-4
-7
-11 -12
19
Vmax
10
7
4
-4
-8
-11 -12
-19

14

values in dB at mid frequencies


63 125 250 500 1000 2000 4000 8000 Hz
4

13

17

18

18

17 dB

11

17

21

19

13 dB

Pressure loss
Pressure loss pA through silencer upstand, at flow rates of
10000
15000
20000
Silencer upstand
ZDS..-0090
20
40
80

88

70

78

Available pressure pfa

- Media density1,15 kg/m

80

400

85

30000

m/h

180

Pa

Hz

Discharge (LWrel8 = LWoct8 - LWA8 )


Relative sound power level LWrel8 at mid frequencies fmm
Duty point 6 3 125 250
500 1000 2000 4000 8000

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

9
9
6

7
8
7

-2
-1
-1

-1
-3
-1

-6
-6
-7

-10
-8
-9

-14
-12
-13

-21
-21
-24

dB
dB
dB

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

8
10
7

9
9
9

-3
-3
-2

-2
-3
-2

-7
-6
-7

-9
-9
-9

-13
-12
-13

-18
-18
-19

dB
dB
dB

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

8
9
12

4
2
6

-1
-3
0

-5
-5
-4

-8
-7
-7

-8
-7
-8

-8
-8
-12

-12
-14
-17

dB
dB
dB

Hz

Roof Extract Fans DV


DV 90

Dimensions DV 90
DV 90-63 / DV 90-71

ZDH 20-0560
Discharge silencer

Mains lead

1183

317

DV 90-75

Mains lead

0
M1
8

75
1

M1
8

60
M10
945
1388

317

14

14

1556

ZBS 01-0090
Flat roof upstand

ZBU 01-0090-56
Connecting plate

ZKK 20-0090
Intermediate piece

895
750

569

M12

ZBU 01-0090-71
Connecting plate
8M10

715

8M10

14
750
886

900
1210

605

751

1178

1178

M
12

ZDS 20-0090
Silencer upstand
878
750

ZKE 11-0560
Intake flexible connection

770

900

ZBS 23-0090
Flat roof upstand high

811.5

811.5

878
750

569
605
639

1178

ZDS 09-0090-#
Silencer upstand for inclined roof
878
750

1178

ZBS 09-0090-#
Upstand for inclined roof

ZKE 11-0710
Intake flexible connection

715
751
785

ZKF 11-0710
Mating flange

ZKF 11-0560
Mating flange
811.5

811.5

770

569
605
639

878
750

150

150

10

ZLK 01-0560
Automatic back draught
damper
811.5

ZLK 01-0710
Automatic back draught
damper
811.5

M
12

150

150

715
751
785

569
605
639

10

ZLK 21-0710
Damper with actuator

437

415

11.5

300

720

# = inclination up to 45 possible
within 5 steps. Indicate inclination
with type when ordering ZBS 09- ZLK 21-0560
0031-05 (od. 10, 15, 20, 25, 30, 35, Damper with actuator
40, 45)
When using damper ZLK and upstand
360
11.5
silencer ZDS the damper has to be
fitted by using a plate ZBU below
silencer upstand.
569
When fitting damper to fan an
605
639
intermediate piece ZKK must be
added.

343

ZBS 11-0090
Soaker sheet (for corrugated
roof)

715
751
785

719
751
785

1400

15

Roof Extract Fans DV


Roof
Voltage
fan
Type DV
V
125-80-6 * 3x400
125-80-8 3x400

Flow
rate
Vmax m/h
24800
17600

125-80-6/12 3x400YY/Y

24800/12470

125-90-6 * 3x400Y

34550

Speed
min-1
945
660
960/480
940

Performance Data DV 125

Absorbed
power
max kW
5,2
2,0
5,5/0,85
8,8

Full load
current
A
10,2
4,4
11,0/3,3
16,4

1step
D1
-

Control units*
Sound Wiring Weight
25steppower diagram
step
step
less LWA Vmax dB No.
kg
90
549
215
D5-12
81
537
206
90/72
551
215
94
549
238

* Fan not speed controlled

Pa

LWA = 9

Pa

DV 125-80-6
1
2
DV 125-80-8
DV 125-80-6/12 1 3

1 dB

700

900

LWA = 9

DV 125-90-6 1

4 dB

800

85

600
500

600

400 82

Available pressure pfa

400

87

76
2

91

Available pressure pfa

500

300

300

200 73

67

200

100

15000
4,0

20000

m/h
6,0 m/s

5,0

100

94

90

5000
10000
0
2,0
3,0
1,0
Flow rate V

81

72

88

700

5000 10000 15000 20000 25000 30000 m/h


0
m/s
1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0
Flow rate V

Pressure drop in the back draught damper


- Frequency 50 Hz
- Media density1,15 kg/m
Attenuation values
Average
Values
Discharge silencer
ZDH 20-0710 11 dB
Silencer upstand
ZDS..-0125 16 dB

values in dB at mid frequencies


63 125 250 500 1000 2000 4000 8000 Hz
4

13

17

18

18

17 dB

14

20

25

23

11 dB

Pressure loss
Pressure loss pA through silencer upstand, at flow rates of
17000
20000
25000
30000
Silencer upstand
ZDS..-0125
20
30
40
65
Intake(LWrel3 = LWoct3 - LWA3 )
Relative sound power level LWrel3 at mid frequencies fm
Duty point
DV 125-80
0,3 Vmax
0,6 Vmax
Vmax
DV 125-90
0,3 Vmax
0,6 Vmax
Vmax

16

63

40000

m/h

110

Pa

Discharge (LWrel8 = LWoct8 - LWA8 )


Relative sound power level LWrel8 at mid frequencies fm

125 250 500 1000 2000 4000 8000

Hz

Duty point

63

125 250

500

1000 2000 4000 8000

Hz

15
13
10

7
7
7

3
3
4

-4
-4
-4

-6
-7
-8

-11
-11
-11

-13
-12
-12

-20
-19
-19

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

8
10
7

9
9
9

-3
-3
-2

-2
-3
-2

-7
-6
-7

-9
-9
-9

-13
-12
-13

-18
-18
-19

dB
dB
dB

15
13
10

7
7
7

3
3
4

-4
-4
-4

-6
-7
-8

-11
-11
-11

-13
-12
-12

-20
-19
-19

dB
dB
dB

0,3 Vmax
0,6 Vmax
Vmax

8
10
7

9
9
9

-3
-3
-2

-2
-3
-2

-7
-6
-7

-9
-9
-9

-13
-12
-13

-18
-18
-19

dB
dB
dB

Roof Extract Fans DV

Dimensions DV 125
Mains lead

DV 125

ZDH 20-0710
Discharge silencer

445

1183

75
1

0
M1
8

M10
1270
1769

14

1556

ZBS 20-0125
Flat roof upstand

ZKK 20-0125
Intermediate piece

1205
1050

ZBU 01-0125-71
Connecting plate
715

M12

8M10

14
1050
1235

751

1210
1520

1500

M
12

ZDS 20-0125
Silencer upstand
1226
1050

ZKE 11-0710
Intake flexible connection

1117

ZBS 23-0125
Flat roof upstand high

811.5

1226
1050

1526

715
751
785

ZDS 09-0125-#
Silencer upstand for inclined roof
1226
1050

1526

ZKF 11-0710
Mating flange

1117

ZBS 09-0125-#
Upstand for inclined roof

811.5

1226
1050

715
751
785

150
150

150
150

ZLK 01-0710
Automatic back draught
damper

M
10

811.5

715
751
785

415

300

# = inclination up to 45 possible
within 5 steps. Indicate inclination
with type when ordering ZBS 09- ZLK 21-0710
0031-05 (od. 10, 15, 20, 25, 30, 35, Damper with actuator
40, 45)
When using damper ZLK and upstand
437
silencer ZDS the damper has to be
11.5
fitted by using a plate ZBU below
silencer upstand.
When fitting damper to fan an
719
751
intermediate piece ZKK must be
785
added.

17

Roof Extract Fans DV


Technical Data:

Type

Motor Protection Units


Dimensions:

Main Control
Voltage voltage

Max.
rating

Max.
Current

Weight Protection

Type

D1

400 V

230 V

3 kW

0,9 kg

IP 54

D1

105

170

135

DS

400 V

230 V

4 kW

0,9 kg

IP 54

DS

105

170

135

D5-1

400 V

230 V

1A

4,5 kg

IP 40

D5-1

150

200

175

D5-3

400 V

230 V

2A

7,0 kg

IP 20

D5-3

230

310

185

D5-7

400 V

230 V

4A

9,0 kg

IP 20

D5-7

230

310

185

D5-12

400 V

230 V

7A

19,0 kg

IP 20

D5-12

230

310

185

E5-1

230 V

1,5 A

1,0 kg

IP 40

E5-1

105

170

135

E5-3

230 V

3A

4,0 kg

IP 40

E5-3

150

200

175

Technical Data:

Dimensions:

Type

Voltage

max. Current

Weight

Protection

Type

ES-3

230 V

2,5 A

0,6 kg

IP 44

ES-3

80

65

Technical Data:

Dimensions:

Type

Voltage

max. Current

Weight

Protection

Type

E2-6

230 V

6A

0,15 kg

IP 54

ES-3

80

77

1
2

18

Roof Extract Fans DV

Diagrams for Control Switches


Diagrams for Isolator Switches

Tapping for thermo-contacts T or 11/12 respectively

2-step-switch

2-step-switch DS
For star/delta winding

On/Off Switch D1
For single speed operation

*Remove jumper if room


thermostat is
connected

*Jumper as per motor name plate

Room thermostat

U1

W2

11

V1

U2

PE

W1

V2

12

U1

W2

11

V1

U2

PE

W1

V2

12

0
1
2

12 11 10 9 8 7 6 5 4 3 2 1

U1 V1 W1 W2 U2 V2 TK TK R1 R2 5 PE

230V; 50Hz

L1 N PE

F1
3,15A

F1

3,15A

U1 V1 W1

S1

L1

L2

L3

S1
R2

14

K1
2 4 6 10 8 12

13

0 1
V1

*Brcke entfllt bei


Raumthermostat

R2
K1

L1

L2

L3

Isolator switch
DV-30-2/2e
Isolator switch
DV-40-4/4e

L1
L2
L3
N
PE

5-step-switch
E5-1, E5-3

Fan motor
with thermo-contact
11

W2 U2 V2

12

U1 V1 W1

21 A1

22 A2

Jumper as
per motor
nameplate

to the outside

Fan motor
11 12 CZ2 U1Z1CU2 PE

PE N

L1 R1 R2 PE N VM

PE

11

12 CZ2 U1Z1 CU2

K1

S1

H2

F1

10 12
Control
10 12 Thermo-contacts

8 6
2 6

Step-less controller
ES-3 (phase cutting)

L1
N
PE

PE N L1 L2 L3 TK TK PE U1 V1 W1 R2 R1

2
4

L1
L2
L3
N
PE

5-step-switch
D5-1, D5-3, D5-7, D5-12
L1
L2
L3
N
PE

4
8

2,5A

0 5 4 3 2 1

S1

H1

0 5 4 3 2 1
23
24
7
3
9
5
1
4

5
4
3
2
1

400 V
280 V
230 V
180 V
140 V

1
2
3
4
5

140 V
180 V
230 V
280 V
400 V

T1

0
0

16
13
17
21
15
19

(11)
(12)

1
2

(7)
(3)
(9)
(5)
(1)
(4)

11
9
7
5
3
4

5
4
3
2
1
0

230 V
160 V
145 V
130 V
105 V

L L 1 NN

T1

T2

1
* Remove jumper if room thermostat is connected

*Remove jumper if room thermostat is connected


H1 = Function
H2 = Failure

non-controlled connection
controlled connenction

Phase

Diagrams for isolator switches


Isolator switch ESH 21/23-0030-22
for single-phase AC-motors, with capacitor, thermo-contacts integrated
in the motor winding

Isolator switch ESH 21/23-0030-35 / ESH 21/23-0075-35


for 3-phase motors, 1 speed, with thermo-contact, -connection
Please provide -circuit within
the terminal box!

T
T
L3
L1
L2
HiS
HiS
HiO
HiO
PE

1
3
5
7
9
11
13
15

2
4
6
8
10
12
14
16

Mains isolator switch

white
white
grey
red
orange
black
blue
brown
green-yellow

T
T
V2
U2
W2
W1
V1
U1
PE

L1

brown

black

brown

HiS
HiS
HiO
HiO
PE

Motor
-circuit 400 V

Mains isolator switch


17-09-04

502

blue

blue
green-yellow

Z
U2
U1
PE
Motor

capacitor
17-09-04

507
19

Roof Extract Fans DV

Diagrams for Isolator Switches

Tapping for thermo contacts T or 11/12 respectively


Isolator switch ESH 21/23-0030-22
for single-phase AC-motors, with capacitor, thermo-contacts and
motor winding in serial circuit
white

L1
N
HiS
HiS
HiO

black

blue

T
T
L1
N
HiS
HiS
HiO
HiO
PE

orange

Z2
Z1
U2

brown

U1
green-yellow
PE

PE
Mains isolator switch

Motor

cpacitor

L3
L2
L1
HiS
HiS 21
HiO 23
HiO
PE

2
4
6
8
10
12
14
16
18

white
white
grey
red
orange
black
blue
brown
green-yellow

T
T
V2
U2
W2
W1
V1
U1

22
24

Mains isolator switch


lower speed

T
T

L3
L2
L1
HiS
HiS
HiO
HiO
PE

1
3
5
7
9
11
13
15
17

2
4
6
8
10
12
14
16
18

21
23

22
24

white
white
grey
red
orange
black
blue
brown
green-yellow

Motor Y Mains isolator switch


higher speed

T
T
V2
U2
W2
W1
V1
U1

Motor

515

Isolator switch ESH 21/23-0030-35


for 3-phase motors, 1 speed, Y/-connection, with thermo-contacts

1
3
5
7
9
11

2
4
6
8
10
12

13
15

14
16

Mains Isolator

white
white
grey
red
orange
black
blue
brown
green-yellow

white
white
grey
red
orange
black
blue
brown
green-yellow

T
4
T
6
V2
U2
W2
W1 12
V1 10
U1 8
PE

Motor
Y-Connection 400 V

Motor
Connection 230 V

527

-connection
400V

T
T

20

isolator switch

Motor

=green/yellow

U1-V1-W1 = brown
W2-U2-V2 = blue
T

= white

17-09-04

Motor

capacitor

509

17-09-04

T
T

1
3
5
7
9
11
13
15
17

L3
L1
L2
HiS
HiS 21
HiO 23
HiO
PE

2
4
6
8
10
12
14
16
18
22
24

white
white
grey
red
orange
black
blue
brown
green-yellow

Mains isolator switch


lower speed

T
T
V2
U2
W2
W1
V1
U1

T
T

L3
L1
L2
HiS
HiS
HiO
HiO
PE

1
3
5
7
9
11
13
15
17

2
4
6
8
10
12
14
16
18

21
23

22
24

white
white
grey
red
orange
black
blue
brown
green-yellow

T
T
V2
U2
W2
W1
V1
U1

Motor

Motor Y Mains isolator switch


higher speed

21-09-04

516

T
T
L2
L1
L3
HiS
HiS
HiO
HiO
PE

1
3
5
7
9
11

2
4
6
8
10
12

13
15

14
16

white (grey)
white

T
T

black
blue
brown
green-yellow

W1
V2
V1
U2
U1
W2
PE
Motor
-connection
400V

Mains isolator switch

17-09-04

537

Isolator switch ESH 21/23-0030-65 / ESH 21/23-0075-65


for 3-phase motors, 2 speed, Dahlander circuit Y/YY,
with thermo-contacts

Isolator switch ESH 21/23-0030-35 / ESH 21/23-0075-35


for 3-phase motors, 1 speed, Y/-connection, with thermo-contacts

U1
W2
V1
U2
W1
V2
PE

black
Z1
blue
U2
brown
U1
green-yellow
PE

Isolator switch ESH 21/23-0030-35


for 3-phase motors, 2 speed, -connection, with thermo-contacts

T
T
V2
U2
W2
W1
V1
U1
PE

05-08-02

Mains

14
16

T
T
Z2

Isolator switch ESH 21/23-0030-65 / ESH 21/23-0075-65


for 3-phase motors, 2-speed, Y/-connection, with thermo-contacts

17-09-04

T
T
L2
L1
L3
HiS
HiS
HiO
HiO
PE

13
15

white
white
orange

508

Isolator switch ESH 21/23-0030-65 / ESH 21/23-0075-65


for 3-phase motors, 2-speed, Y/-connection, with thermo-contacts

1
3
5
7
9
11
13
15
17

2
4
6
8
10

Mains isolator switch


17-09-04

T
T

1
3
5
7
9

white

HiO

Isolator switch ESH 21/23-0030-25


for single-phase AC-motors, with capacitor and thermo-contacts

549

T
T

3
5

L3
L1
L2
HiS
HiS
HiO
HiO
PE

13
15
17
22
21
23
24

Mains
lower speed

T
T
L3
L1
L2

HiS
HiS
HiO
HiO
PE

1
3
5
7
9
11
13
15
17

2
4
6
8
10
12
14
16
18

21
23

22
24

Mains isolator switch


higher speed

white
white, pink
blue
blue
blue
brown
brown
brown
green-yellow

T
T
2W
2V
2U
1W
1V
1U
PE

Motor
17-09-04

551

Roof Extract Fans DV

DigiPro Control Unit

The control unit DigiPro is a system for controlling and monitoring a ventilation installation.
DigiPro is fully set and ready for connection.
The smallest unit is equipped with a manual control panel and a second part serving as master
controller.
These components are connected by bus (eBus) in a 2-wire technology.
There up to 32 units can be integrated in the same bus-system (with always one master or group
unit).
2 master units are available for the control and monitoring of exhaust fans and other units
equipped with a 230V or 400V fan motor, 2-speed or continuous speed variation.

Description

Master unit FAE


Master unit FAZ

230V-2,2kW for continuous fan speed control


400V 2,2 kW for 2 speed control

The handling of the unit is simple. The control parameters are set making it ready for connection
and operation.
There is no programming necessary.
If communication with mobile phone is required an ISDN-interface can be added.
In case of operational troubles messages can be mailed to the phone, fax or to a PC, providing a
constant monitoring of the ventilation installation.
Further on a LON-Interface is available for integrating it into a LON-field-bus-system thus
overcoming system limits in a building.
Stylish casing made of cast aluminium; fitted outside fan unit
Integrated isolator switch
Input: 4 x trouble messages
Output: 1 relay connection 230VH, Relay exit potential free, 1 analogue output
Power electronics for motor speed control
Integrated motor temperature monitoring
Address can be set with DIP-switch
Short motor circuit recognition
Radio noise suppression integrated (230V~ execution)
2-wire bus for system integration

Standart functions

universal controller for exhaust units


pre-programmed unit specially set for every application
customised and extendable for growing installations
motor protection by thermo-contacts
several monitoring tasks available including fire detection

In and out tapping


Trouble in
(digital)

Signal in
(analogue)

Command in/out
(digital)

Command continuous
(anal)

Filter control

Free

Damper open/close

Air mix damper (0 to 10V)

Fire detection

Free

Free

Air flow ctrl (KG)

thermo-contact

Technical Data

Protection:
Feed voltage; Rating FAE:
Feed voltage; Rating FAZ:
Sourrounding conditions:
Storage temperature:
Operation altitude:
Wire section for tapping:
Input digital:
Output digital:
Output analogue:
Motor connection to FAE:
motor connection to FAZ:
Feed fuses:
Dimensions L x B x H:

Remark:

IP54
230V~ 10% / 50 Hz / 2,2kW
400V~ 10% / 50 Hz / 2,2kW
Temperature: -20 bis +50C
Air humidity 0 bis 95%
-25 bis + 65C
max. 2000m
max. 2,5mm (coloured plugs coded)
4x 24V=
1x relay 230V~ /2A / AC3
1x 0..10V DC
0-230V~ / 50Hz / max. 11,5A / continuous speed control,
max. 2,2kW for common motor ctrl.
400V~ / 50Hz / max. 3x6,5A / 2-speed control,
max. 2,2kW for common motor control.
10/16 A (not included)
33,7 cm x 21,7 cm x 12,2 cm

Exhaust air management (e.g. under- or over pressure, exhaust air in function of supply air or
parallel operation with supply air) is only possible in connection with a master unit of a supply
air fan. An independent control with DigiPro is not possible.
21

Roof Extract Fans DV

Sample Specification

Roof Extract Fan DV 30

with swirl free horizontally directed discharge, for maximum gas medium temperatures
up to +40C.
Stylish casing and base frame with inlet cone, manufactured from galvanised sheet steel.
Inlet flange in accordance with DIN 24 155- 2.
Discharge outlets protected from the weather with an aerodynamically shaped grille.
Centrifugal impeller with backward curved blades, mounted on the rotor of a variable
speed integral external rotor motor, protected to IP 44.
Motor protection is through direct switching of thermo-contacts in the motor winding,
supplied ready to connect.
Dynamically balanced, installed vibration free, totally maintenance free.

Roof Extract Fan DV 40 - 125

Suitable for maximum gas medium temperatures up to +40C.


Stylish V-shape casing made of galvanized sheet steel.
Base frame made of galvanized sheet steel for being fitted to upstand, large overhung for
implementing roof isolation material.
Inlet flange in accordance with DIN 24 155- 2.
Guard in discharge section. High performance centrifugal impeller with backward curved
blades fitted on the rotor of an integrated motor.
Motor fully maintenance free, vibration free mounted, thermo-contacts for complete
motor protection.
The roof fan is ready for fitting, isolator switch easily accessible under weather cowl.

Fan type
Flow rate
Pressure increase
Temp. of gas medium
Speed
Shaft power
Max. absorbed current
voltage/ frequency
A-Sound power level
Weight
Dimensions

Accessories (at extra cost)

22

DV
V
pfa
t
n
max. P1
max. I
U/f
LWA
G

=
=
=
=
=
=
=
=
=
=
=

...........................
........................... m/h
........................... Pa
........................... C
........................... 1/min
........................... kW
........................... A
........................... V / Hz
........................... dB
........................... kg
........................... mm

Flat roof upstand made of galvanized sheet steel (ZBS 20)


Flat roof upstand high made of galvanized sheet steel (ZBS 23)
Upstand for inclined roof made of aluminium (ZBS 09)
Silencer upstand made of galvanized sheet steel (ZDS 20)
Silencer upstand for inclined roof made of aluminium (ZDS 09)
Discharge silencer ZDH 20 (for DV 40 125)
Soaker sheet for corrugated roof ZBS 11 made of GRP (up tp size 90)
Base plate for tube connection (ZBU 11)
Flexible connection ZKE 11
Mating flange ZKF 11
Back draught damper ZLK
Actuated back draught damper ZLK 21 (sizes DV 40 to 125)
Intermediate piece ZKK 20 (sizes DV 40 to 125)
Inlet guard ZSG 04
Switches and controls

Summary ...................................................................................................................Page
Roof Ventilation Hoods DLH
Product review .......................................................................................................................... 24
Dimensions................................................................................................................................. 24
Pressure drops Intake - exhaust ............................................................................................ 24
Dimensions of accessories ..................................................................................................... 25
Smoke Extract Fans ER
Product review .......................................................................................................................... 26
Summary data sheet ................................................................................................................ 27
Gerneral instructions ...................................................................................................... 28 - 29
RDM 56/57-25.. - Performances / Dimensions ........................................................ 30 / 31
RDM 56/57-35.. - Performances / Dimensions ....................................................... 32 - 33
RDM 56/57-45.. - Performances / Dimensions ....................................................... 34 - 35
RDM 56/57-56.. - Performances / Dimensions ....................................................... 36 - 37
RDM 56/57-71.. - Performances / Dimensions ........................................................ 38 - 39
RDM 56/57-90.. - Performances / Dimensions ....................................................... 40 - 41
Isolator switch ........................................................................................................................... 42
Dimensions of accessories ..................................................................................................... 43
Sample specification ................................................................................................................ 44

23

Roof Ventilation Hoods DLH


Rain protection cowl made of galvanized sheet steel. Base frame with aerodynamic cone
made of galvanized sheet steel.
Roof ventilation hoods are suitable for the use as weather proof ventilation opening in a
roof or as the final element - intake or outlet - in ventilation and exhaust air systems.
The occurring pressure losses are to be checked with the diagrams below.

Description

Dimensions

e
c
a

DLH 40

671

440

440

32

6M6

330

12

286

DLH 56

881

523

600

32

8M8

450

12

395

DLH 71

1103

648

750

32

6M8

590

14

487

DLH 90

1388

822

940

40

8M10

750

14

605

DLH 125

1769

933

1270

65

8M10 1050 14

751

Pressure loss air intake

Pressure loss air discharge

12

90

DL
H

DL
H

56

71
DL
H

Pressure loss pA

DL
H

40
DL
H

12
DL
H

71

56

90
DL
H

DL
H

DL
H

40
DL
H

100

Pressure loss pA

100

1000
Pa

1000
Pa

10

1000
Flow rate V

10000

m/h

10

1000
Flow rate V

10000

m/h

Dimensions accessories
a
b

ZBS 200040
0056
0071
0090
0125
f

a1
d

24

a
395
555
705
895
1205

a1
400
560
710
900
1210

b
330
450
590
750
1050

d
710
870
1020
1210
1520

f
M10
M10
M12
M12
M12

kg
8
10
16
25
34

Roof Ventilation Hoods DLH Dimensions


a
b

b1

ZBS 230040
0056
0071
0090
0125

a
378
538
688
878
1226

b
330
450
590
750
1050

b1
650
800
900
900
900

d1
618
778
988
1178
1526

f
M10
M10
M12
M12
M12

kg
12
14
20
32
40

d1

d11

a
b

ZBS 090040-#
0056-#
0071-#
0090-#
0125-#

a
378
538
688
878
1226

b
330
450
590
750
1050

d11
618
778
988
1178
1526

f
M10
M10
M12
M12
M12

g
250
250
250
250
250

h
150
150
150
150
150

kg
5
6
9
13
18

# = inclination up to 45 possible within 5 steps. Indicate inclination with type when ordering
ZBS 09-0031-05 (od. 10, 15, 20, 25, 30, 35, 40, 45)

b
330
450
450
750

c
200
200
200
200

d
920
920
1400
1400

f
M10
M10
M12
M12

g
1600
1600
2000
2000

h
322
400
560
715

ZBS 110040
0056
0071
0090

DLH
DLH
DLH
DLH
DLH

40
56
71
90
125

ZKE
11-0250
11-0355
11-0450
11-0560
11-0710

DLH
DLH
DLH
DLH
DLH

40
56
71
90
125

ZKF
11-0250
11-0355
11-0450
11-0560
11-0710

DLH
DLH
DLH
DLH
DLH

40
56
71
90
125

ZLK
21-0250
21-0355
21-0450
21-0560
21-0710

zd

a
b
c

zd
a
b
c

d4

a
b
c

a
256
361
453
569
715

a
256
361
453
569
715

a
256
361
453
569
715

b
286
395
487
605
751

b
286
395
487
605
751

b
286
395
487
605
751

c
306
421
513
639
785

c
306
421
513
639
785

c
306
421
513
639
785

d4
88
88
88
88
88

e
240
240
240
240
300

z x d
6 x 7
8 x 9,5
6 x 9,5
8 x 11,5
8 x 11,5

e
25
30
30
35
35

f
185
237
282
343
415

z x d
6 x 7
8 x 9,5
6 x 9,5
8 x 11,5
8 x 11,5

k
207
258
300
360
437

z x d
6 x 7
8 x 9,5
6 x 9,5
8 x 11,5
8 x 11,5
25

Smoke Extract Fans ER


Description

Description

Air discharge vertical and swirl free.


Casing made of aluminium.
Base frame and mechanically stressed parts made of galvanized sheet steel.
Impeller made of steel, welded and coated.
Motor separated from air stream.
Casing side parts removable, centre parts to be swivelled (up to size 7190).
Ready for connection; free cable lead, protected by a steel tube.
Fixing bracket for isolator switch or connection box as a standard.
Isolator switch as an option (loose for fitting on site)
Smoke-extract roof fans of the lines RDM 56 and RDM 57 are provided for eliminating heat
and smoke in case of fire especially in the first phase with usually high smoke content.
They have to keep the escape ways smoke free, reduce damages, and ease fire fighting
actions.
They fulfil the actual requirements for Mechanical Extract Devices (MA)
RDM 56-, +400C - 120 min
The fans of the range RDM 56 do respond to the requirements of the category 1,2, and 3
according to EN 12101-3.
They have been certified by the DIBt with certificate N Z-78.1-26
RDM 57-, +600C - 120min
The fans of the range RDM 57 correspond to the requirements of the category 1,2, 3, and
4 according to EN 12101-3.
They have been certified by the DIBt with certificate N Z-78.1-27
The fans have been tested by the research and test laboratory of the chair for home
improvement and construction techniques at the University of Munich and have
subsequently been certified by the DIBt, Berlin.
Certificates can be provided on request.
The roof extract fans comply with the tolerances of Class 2 of DIN 24 166 Fans, Technical
Specifications.
The smoke extract roof fans are equipped with IEC standard motors B5, protection class IP
55 and heat class F.
Attention!
In case of fire the motor must not be electrically protected. All high temperature and
high current securities have to be bridged, i.e. to be put out of order.

26

Smoke Extract Fans ER

Summary Data Sheet

A full fan line: 23 standard sizes


Performance range: 3300 up to 57200 m/h
Smoke extract
fan ER

Flow
rate

Available
pressure

Voltage

Speed

Motor
rating

Rated
current

Weight

Isolator
switch

RDM 56/57-

m/h

Pa

1/min

kW

kg

ESH 23

2528-2D-11

3.300

950

230/400 /Y

2845

1.10

4.15/2.40

39

0055-32

2531-4D-10

2.200

270

230/400 /Y

1395

0.55

2.51/1.45

35

0055-32

3535-4D-10

3.370

320

230/400 /Y

1395

0.55

2.51/1.45

44

0055-32

3540-4D-10

4.700

440

230/400 /Y

1395

0.55

2.51/1.45

50

0055-32

3545-4D-13

5.750

570

230/400 /Y

1410

1.1

4.6/2.65

55

0055-32

3545-HD-10

3.700 /1.900

215/50

400 Y/YY

935/425

0.3/0.075

1.0/0.44

55

0075-62

4550-4D-16

9.450

650

230/400 /Y

1420

2.20

8.50/4.90

87

0055-32

4550-HD-14

6.200 /3.000

280/70

400 Y/YY

965/460

0.55/0.12

2.0/0.88

82

0075-62

4556-4D-17

11.400

800

230/400 /Y

1420

3.0

11.1/6.4

100

0055-32

4556-6D-13

7.300

320

230/400 /Y

915

0.75

3.65/2.1

94

0055-32

4556-HD-16

7.300/3.750

320/100

400 Y/YY

940/460

1.1/0.18

2.85/1.09

103

0075-62

5663-6D-16

11.900

470

230/400 /Y

925

1.5

6.75/3.9

181

0055-32

5663-HD-19

11.900/5.900

470/130

400 Y/YY

955/450

1.8/0.45

5.1/2.0

199

0075-62

5671-6D-21

14.500

620

230/400 /Y

950

12.5/7.2

190

0055-32

5671-HD-24

14.500/7.400

620/160

400 Y/YY

965/480

3.3/0.7

6.8/2.5

216

0075-62

7180-6D-24

25.000

780

400/690 /Y

950

5.5

12.8/7.4

288

0075-62

7180-8D-21

18.800

440

230/400 /Y

700

2.2

9.9/5.7

300

0055-32

7180-HD-28

25.000/12.000

780/180

400 Y/YY

975/485

6.2/1.3

12.5/4.1

348

0075-62

7190-6D-28

33.500

980

230/400 /Y

960

9.0

19.4/11.2

297

0110-62

7190-HD-26

33.500/15.800

980/240

400 Y/YY

975/485

9.0/2.0

18.5/6.2

390

0110-62

9090-4D-31

51.900

2000

400/690 /Y

1460

22

41.5/24.1

590

0220-62

9090-ID-34

57.200/38.200

2.200/1.000

400 Y/Y

1470/980

26/9.5

49.0/20.0

640

0300-62

9090-GD-34

57.200/28.800

2.200/590

400 Y/YY

1470/732

28/7.5

52.0/20.5

640

0300-62

27

Smoke Extract Fans ER

Important Remarks

Safety Guards

All roof extract fans are supplied with a discharge-side mesh safety guard in accordance
with DIN EN 294. The inlet side is not fitted with a standard guard, because it is normal
practice to connect other system parts to this end. However, if the unit is installed in
such a way that accidental contact with the impeller is possible, an additional inlet
guard has to be fitted acc. to DIN EN 294! The fans may only be put into operation if
all necessary protection devices are fitted and made effective (see maintenance
instructions)! The safety guards are to be executed acc. to DIN EN 292 1, chapter 3.22
Separating safety devices and DIN EN 292 2, chapter 4 Technical protection measures.

Safety instructions

Transport, fitting, electrical connection, start up, and maintenance are to be executed
following the instructions given in the manual and by respecting the actual standards,
guide lines, and safety rules. Please take care of the special heat protected
cable lead when installing smoke extract fans.

Performance data

The performance curves are obtained using an inlet side test chamber in accordance with
DIN 24 163-2 Fans, performance tests, standard test equipment. The performance grids
show the effective pressure increase pfa (Pressure increase obtained from the fan in
free-field conditions) as a function of the flow volume VL.
Reference media density: 1 = 1.15 kg/m. The roof fans comply with the tolerances of
Class 2 of DIN 24 166 Fans, Technical Specifications.

28

Smoke Extract Fans ER


Sound Data

Important Remarks

Measurement and evaluation of noise levels are in accordance with DIN 45 635 - 38
Sound measurements on machines; fans. In the technical data the A-weighted sound
power level at maximum flow rate is given.
The computer aided data collection and evaluation enables to obtain highly reliable data
precision. In the curves the emission value of the A-sound-power level LWA is given,
having the same value for intake (LWA3) as for the discharge (LWA8).
For more exact calculations when determining the required attenuation, the sound power
level in the octave bands is important.
LWoct 3/8= LWA + LWrel 3/8
The relative sound power levels for inlet and discharge sides, at various duty points, can be
read from the corresponding tables.

Calculation of the sound pressure level Because conditions in the operating environment are usually far from ideal for
measurement and can vary greatly, a determination of the A-sound-pressure level at any
distance is only possible with great uncertainty.
LPA LWA L
The diagram below supplies the correction value L in function of the distance r from
the fan centre. Under ideal conditions, with a clear hemisphere of sound propagation,
curve a is valid. However, curve b is recommended for practical estimates. The
calculation of the intake sound-power level is only possible if the exact noise parameters
of the connected room are known (see VDI 2081!).

30
dB

a
b

20
10

m 10

29

Smoke Extract Fans ER

Technical Data

Smoke extract
fan ER
RDM 56/572528-2D-11

Flow
rate
m/h
3.300

Available
pressure
Pa
950

Voltage

Speed

V
230/400 /Y

2531-4D-10

2.200

270

230/400 /Y

Pa

LW
A=8
8d

RDM 50-2528-2D-11

= Vopt

Rated
current
A
4.15/2.40

Weights

1/min
2845

Motor
rating
kW
1.10

kg
39

Isolator
switch
ESH 23
0055-32

1395

0.55

2.51/1.45

35

0055-32

Pa
280

RDM 50-2531-4D-10

= Vopt

800

LW
A=
72

240

600

dB

200

86

160

500
0

0,1

0,2
Flow rate V

1000
0,3

1500
0,4

2000
0,5

0,6

2500
0,7

3000 m/h
0,8

m/s

Available pressure pfa

200

88

Available pressure pfa

120

87

400

80
40

500
0
0,1
Flow rate V

1000
0,2

0,3

1500
0,4

2000
0,5

m/h

0,6 m/s

In the curves the A-weighted sound power level is LWA (=LWA3 =LWA8) acc. to DIN 45635-38.
Reference media density: 1 = 1.15 kg/m.

Intake
Relative sound power level LWrel3 at octave mid frequencies fm

Discharge
Relative sound power level LWrel3 at octave mid frequencies fm

RDM 56/57-2528; -2531


2-poles
Duty point 6 3 125 250
0.5Vopt 1 6
12
3
Vopt
1
1
6
Vmax
-2
-4
5
4-poles
Duty point 6 3 125 250
0.5Vopt 1 3
12
2
Vopt
9
12
1
Vmax
4
10
1

RDM 56/57-2528; -2531


2-poles
Duty point 6 3 125 250
0.5V opt
-5
0
0
V opt
-8
-6
-1
Vmax
-9
-8
-3
4-poles
Duty point 6 3 125 250
0.5V opt
-2
0
-2
V opt
-5
-0
-2
Vmax
-10
-1
-4

30

500 1000 2000 4000 8000


-4
-13
-17
-20
-27
-3
-12
-14
-15
-24
-3
-12
-16
-15
-19

Hz
dB
dB
dB

500 1000 2000 4000 8000


-3
-10
-14
-19
-27
-3
-10
-13
-18
-27
-2
-10
-13
-15
-23

Hz
dB
dB
dB

500
-2
-3
-2

1000 2000 4000 8000


-5
-8
-12
-19
-6
-8
-9
-17
-6
-8
-8
-15

Hz
dB
dB
dB

500
-3
-3
-3

1000 2000 4000 8000


-5
-8
-13
-21
-5
-7
-13
-21
-5
-6
-12
-19

Hz
dB
dB
dB

Smoke Extract Fans ER

Dimensions

Dimensions

600

RDM 56/57 2528-2D-11


RDM 56/57 2531-4D-10

559
6

28

330

32
440

440

Flat roof upstand

ZBS 03-0040
(600C)

12

6xM6

ZBS 20-0040
For RDM56 only, when connected to duct

395
330

283

283

395
330

400
710

350
710

10

10

6x7

Inlet guard
ZSG 04-0250

130

Flexible connection at intake


ZKE 30-0250 (600C)

67

256
286
306

25

Average attenuation LWA 16 dB

378
330
270

115
650

Robust casing of coated sheet steel. ZDS


32-0400 with removable baffles.

256
286
306

115
618
340

Silencer upstand ZDS 32-0040 (600C)

6x7

M
10

Mating flange
ZKF 11-0250 (600C)

256
286
306

Attenuation in dB at mid frequencies in Hz


63 Hz
3 dB
1000 Hz 19 dB
125 Hz
5 dB
2000 Hz 23 dB
250 Hz
8 dB
4000 Hz 21 dB
500 Hz
13dB
8000 Hz 15 dB
Pressure loss p A through silencer upstand
In Pa, at flow rates in m/h
m/h
Pa
1500
25
2000
40
3000
100
4000
170

31

Smoke Extract Fans ER

Technical Data

Smoke extract
fan ER
RDM 56/573535-4D-10

Flow
rate
m/h
3.370

Available
pressure
Pa
320

Voltage

Speed

V
230/400 /Y

3540-4D-10
3545-4D-13

4.700
5.750

440
570

3545-HD-10

3.700 /1.900

215/50

Pa
300

Rated
current
A
2.51/1.45

Weights

1/min
1395

Motor
rating
kW
0.55

kg
44

Isolator
switch
ESH 23
0055-32

230/400 /Y
230/400 /Y

1395
1410

0.55
1.1

2.51/1.45
4.6/2.65

50
55

0055-32
0055-32

400 Y/YY

935/425

0.3/0.075

1.0/0.44

55

0075-62

Pa

RDM 50-3535-4D-10

= Vopt

LW
A = 74
dB

450
400

250

RDM 50-3540-4D-10
= Vopt

LW
A=
79

dB

350
72

300
200

73

Available pressure pfa

150

100
50

75

500
1000
0
0,1 0,2 0,3
Flow rate V

2500
1500
2000
0,4 0,5 0,6 0,7

Available pressure pfa

250

3000 m/h
0,8
m/s

200
150
100
50
0

1000
0

0,2

2000

3000
0,8

0,6

0,4

m/h

4000

1,2 m/s

1,0

Flow rate V

In the curves the A-weighted sound power level is LWA


(=LWA3 =LWA8) acc. to DIN 45635-38. Reference media
density: 1 = 1.15 kg/m.

Pa

L
W
A=

500

85

RDM 50-3545-4D-13 1
RDM 50-3545-HD-10 2 3
= Vopt

dB
1

400

82

82

72

200

70

100

71

83

72

Available pressure pfa

300

1000
0

2000
0,5

3000

4000

5000

1,0

m/h
1,5 m/s

Flow rate V
Intake
Relative sound power level LWrel3 at octave mid frequencies fm

Discharge
Relative sound power level LWrel3 at octave mid frequencies fm

RDM 56/57-3535; -3540; -3545


4-poles
Duty Point6 3 125 250 500 1000 2000 4000 8000
0.5Vopt 1 3
11
2
-2
-11
-16
-21
-27
Vopt
9
11
1
-2
-11
-16
-20
-24
Vmax
6
9
2
-1
-12
-17
-19
-21
6-poles
Duty Point6 3 125 250 500 1000 2000 4000 8000
0.5Vopt 1 6
10
1
-1
-10
-16
-22
-27
Vopt
14
11
2
-2
-11
-17
-22
-29
Vmax
11
13
3
-1
-12
-17
-21
-29

RDM 56/57-3535; -3540; -3545


4-poles
Duty Point 6 3 125 250 500
0.5V opt
-3
4
-1
-4
V opt
-6
4
-1
-4
Vmax
10
4
-1
-3
6-poles
Duty Point 6 3 125 250 500
0.5V opt
1
6
0
-3
V opt
-1
6
0
-4
Vmax
-1
6
1
-3

32

Hz
dB
dB
dB
Hz
dB
dB
dB

1000 2000 4000 8000


-6
-7
-12
-20
-6
-7
-12
-19
-6
-7
-13
-17

Hz
dB
dB
dB

1000 2000 4000 8000


-6
-9
-16
-25
-6
-9
-15
-25
-6
-8
-13
-25

Hz
dB
dB
dB

Smoke Extract Fans ER

Dimensions

Dimensions

770

RDM 56/57 3535-4D-10


RDM 56/57 3540-4D-10
RDM 56/57 3545-4D-13
RDM 56/57 3540-HD-10

709
5

39

450

32
600

Flat roof upstand

ZBS 03-0056
(600C)

600

12

ZBS 20-0056
For RDM56 only, when connected to duct

555
450

283

283

555
450

510
870

560
870

10

89.5

361
395
421

361
395
421

8x9,5

30

Mating flange
ZKF 11-0355 (600C)

10

Inlet guard
ZSG 04-0355

8x9,5
130

Flexible connection at intake


ZKE 30-0355 (600C)

8xM8

361
395
421

538
450

Average attenuation LWA 16 dB

430

800

115

115

500

10

778
M

Silencer upstand ZDS 32-0056


(600C)
with removable baffles

Attenuation in dB at mid frequencies in Hz


63 Hz
3 dB
1000 Hz 18 dB
125 Hz
5 dB
2000 Hz 21 dB
250 Hz
8 dB
4000 Hz 20 dB
500 Hz
12dB
8000 Hz 15 dB
Pressure loss p A through silencer upstand
In Pa, at flow rates in m/h
m/h
Pa
3000
25
4000
42
6000
80
8000
160

33

Smoke Extract Fans ER

Technical Data

Smoke extract
fan ER
RDM 56/574550-4D-16

Flow
rate
m/h
9.450

Available
pressure
Pa
650

Voltage

Speed

V
230/400 /Y

4550-HD-14
4556-4D-17

6.200 /3.000
11.400

280/70
800

4556-6D-13
4556-HD-16

7.300
7.300/3.750

320
320/100

Pa

LW
A=8
7

600

Rated
current
A
8.50/4.90

Weights

1/min
1420

Motor
rating
kW
2.20

kg
87

Isolator
switch
ESH 23
0055-32

400 Y/YY
230/400 /Y

965/460
1420

0.55/0.12
3.0

2.0/0.88
11.1/6.4

82
100

0075-62
0055-32

230/400 /Y
400 Y/YY

915
940/460

0.75
1.1/0.18

3.65/2.1
2.85/1.09

94
103

0055-32
0075-62

Pa

RDM 50-4550- 4D-16 1


RDM 50-4550-HD-14 2 3
= Vopt

dB
1

500

LW
A=
94
dB

800
700

85

RDM 50-4556-4D-17 1
RDM 50-4556-6D-13 2
RDM 50-4556-HD-16 2 3
= Vopt
1

600
400

90

87

75

74

200

74

100

57

3 56

Flow rate V

4000
1,0

6000

8000
2,0

m/h
m/s

79
200

63

100

3 6
1

2000
0

4000
1,0

91

2000

82

300

80

88

75

57

400

62

Available pressure pfa

300

Available pressure pfa

500

6000

8000
2,0

10000
3,0

m/h
m/s

Flow rate V

In the curves the A-weighted sound power level is LWA


(=LWA3 =LWA8) acc. to DIN 45635-38. Reference media
density: 1 = 1.15 kg/m.

Intake
Relative sound power level LWrel3 at octave mid frequencies fm

Discharge
Relative sound power level LWrel3 at octave mid frequencies fm

RDM 56/57-4550; - 4556


4-poles
Duty point 6 3 125 250
0.5Vopt 1 4
10
1
Vopt
9
12
0
Vmax
3
9
1
6-poles
Duty point 6 3 125 250
0.5Vopt 1 5
11
1
Vopt
11
13
-1
Vmax
7
15
3

RDM 56/57-4550; -4556


4-poles
Duty point 6 3 125 250
0.5V opt
1
5
0
V opt
-4
8
-1
Vmax
-8
8
-2
6-poles
Duty point 6 3 125 250
0.5V opt
2
4
1
V opt
0
4
0
Vmax
-4
6
1

34

500 1000 2000 4000 8000


-2
-11
-14
-15
-22
-3
-11
-15
-15
-21
-2
-12
-16
-16
-12

Hz
dB
dB
dB

500 1000 2000 4000 8000


-2
-11
-15
-16
-23
-4
-12
-16
-17
-25
-1
-10
-14
-12
-21

Hz
dB
dB
dB

500
-4
-5
-4

1000 2000 4000 8000


-5
-9
-13
-20
-6
-9
-12
-19
-6
-9
-15
-12

Hz
dB
dB
dB

500
-4
-4
-3

1000 2000 4000 8000


-5
-7
-13
-22
-6
-8
-13
-22
-6
-8
-12
-22

Hz
dB
dB
dB

Smoke Extract Fans ER

Dimensions

Dimensions

985

RDM 56/57 4550-4D-16


RDM 56/57 4550-HD-14
RDM 56/57 4556-4D-17
RDM 56/57 4556-6D-13
RDM 56/57 4556-HD-16

794
7
48

590

32
750

Flat roof upstand

ZBS 03-0071
(600C)

750

14

ZBS 20-0071
For RDM56 only , when connected to duct

705
590

283

283

705
590

660
1020

710
1020

12

12

Inlet guard
ZSG 04-0450

6x9,5

130

Flexible connection at intake


ZKE 30-0450 (600C)

69.5

453
487
513

453
487
513

6x9,5

30

Mating flange
ZKF 11-0450 (600C)

6xM8

453
487
513

Average attenuation LWA 17 dB

688
590
580

900

115

115

650

12

988

Silencer upstand ZDS 32-0071


(600C)

Attenuation in dB at mid frequencies in Hz


63 Hz
3 dB
1000 Hz 20 dB
125 Hz
5 dB
2000 Hz 25 dB
250 Hz
9 dB
4000 Hz 22 dB
500 Hz
13dB
8000 Hz 17 dB
Pressure loss p A through silencer upstand
In Pa, at flow rates in m/h
m/h
Pa
5000
25
8000
60
10000
95
12000
110

35

Smoke Extract Fans ER

Technical Data

Smoke extract
fan ER
RDM 56/575663-6D-16

Flow
rate
m/h
11.900

Available
pressure
Pa
470

Voltage

Speed

V
230/400 /Y

5663-HD-19
5671-6D-21

11.900/5.900
14.500

470/130
620

5671-HD-24

14.500/7.400

620/160

Pa
450

LW
A=
8

3d

Rated
current
A
6.75/3.9

Weights

1/min
925

Motor
rating
kW
1.5

kg
181

Isolator
switch
ESH 23
0055-32

400 Y/YY
230/400 /Y

955/450
950

1.8/0.45
3

5.1/2.0
12.5/7.2

199
190

0075-62
0055-32

400 Y/YY

965/480

3.3/0.7

6.8/2.5

216

0075-62

Pa

RDM 50-5663-6D-16 1
RDM 50-5663-HD-19 1 2
= Vopt

400

600

350

RDM 50-5671-6D-21 1
RDM 50-5671-HD-24 1 2
= Vopt

LW
A=
89
dB
1

500

81

88

300

400

Available pressure pfa

200
150

65
100

63

50
83

65

Available pressure pfa

250

2000
0
Flow rate V

4000
1,0

6000

8000

10000

2,0

3,0

m/h
m/h

300
200

71

69

100

88

70
0

2000

4000

6000

0
1,0
Flow rate V

8000
2,0

10000 12000

m/h

3,0

m/s

In the curves the A-weighted sound power level is LWA


(=LWA3 =LWA8) acc. to DIN 45635-38. Reference media
density: 1 = 1.15 kg/m.

Intake
Relative sound power level LWrel3 at octave mid frequencies fm

Discharge
Relative sound power level LWrel3 at octave mid frequencies fm

RDM 56/57-5663; -5671


6-poles
Duty point 6 3 125 250
0.5Vopt 1 4
11
1
Vopt
11
12
-1
Vmax
7
13
1

RDM 56/57-5663; -5671


6-poles
Duty point 6 3 125 250
0.5V opt
2
3
0
V opt
1
3
-1
Vmax
-3
4
-1

36

500 1000 2000 4000 8000


-2
-9
-14
-16
-23
-4
-10
-15
-16
-22
-2
-9
-13
-10
-15

Hz
dB
dB
dB

500
-3
-4
-4

1000 2000 4000 8000


-5
-8
-13
-21
-5
-8
-12
-19
-6
-8
-11
-16

Hz
dB
dB
dB

Smoke Extract Fans ER

Dimensions

Dimensions

1225

RDM 56/57 5663-6D-16


RDM 56/57 5663-HD-19
RDM 56/57 5671-6D-21
RDM 56/57 5671-HD-24

1004
5
60

750

40
940

Flat roof upstand

ZBS 03-0090
(600C)

940

14

ZBS 20-0090
For RDM56 only , when connected to duct

895
750

283

283

895
750

850
D1210

900
1210

12

811.5

569
605
639

569
605
639

8x11,5

35

Mating flange
ZKF 11-0560 (600C)

12

Inlet guard
ZSG 04-0560

8x11,5

130

Flexible connection at intake


ZKE 30-0560 (600C)

8xM10

569
605
639

Average attenuation LWA 15 dB

115

878
750

115

900

770

840

12

1178

Silencer upstand ZDS 32-0090


(600C)

Attenuation in dB at mid frequencies in Hz


63 Hz
2 dB
1000 Hz 17 dB
125 Hz
5 dB
2000 Hz 21 dB
250 Hz
8 dB
4000 Hz 19 dB
500 Hz
11dB
8000 Hz 13 dB
Pressure loss p A through silencer upstand
In Pa, at flow rates in m/h
m/h
Pa
10000
20
15000
40
20000
80
30000
180

37

Smoke Extract Fans ER

Technical Data

Smoke extract
fan ER
RDM 56/577180-6D-24

Flow
rate
m/h
25.000

Available
pressure
Pa
780

Voltage

Speed

V
400/690 /Y

7180-8D-21
7180-HD-28

18.800
25.000/12.000

440
780/180

7190-6D-28
7190-HD-26

33.500
33.500/15.800

980
980/240

Pa
800

LW
A=
92

700

Rated
current
A
12.8/7.4

Weights

1/min
950

Motor
rating
kW
5.5

kg
288

Isolator
switch
ESH 23
0075-62

230/400 /Y
400 Y/YY

700
975/485

2.2
6.2/1.3

9.9/5.7
12.5/4.1

300
348

0055-32
0075-62

230/400 /Y
400 Y/YY

960
975/485

9.0
9.0/2.0

19.4/11.2
18.5/6.2

297
390

0110-62
0110-62

Pa

RDM 50-7180-6D-24 1
RDM 50-7180-8D-21 2
RDM 50-7180-HD-28 1 3
= Vopt

dB

900

500

500

Available pressure pfa

400

90

82

300

83

3 7
0

93

Available pressure pfa

93

600

84

100

700
89

73

RDM 50-7190-6D-28 1
RDM 50-7190-HD-26 1 2
= Vopt

800

200

4d

600

400

LW
A=
9

300

77

200

75

100

10000

1
2
Flow rate V

15000
4

20000
6

25000

m/h

m/s

77
0

5000
0

10000 15000

1
2
Flow rate V

94

5000
0

91

84

72

20000
5

25000
7

30000 m/h
8

9 m/s

In the curves the A-weighted sound power level is LWA


(=LWA3 =LWA8) acc. to DIN 45635-38. Reference media
density: 1 = 1.15 kg/m.

Intake
Relative sound power level LWrel3 at octave mid frequencies fm

Discharge
Relative sound power level LWrel3 at octave mid frequencies fm

RDM 56/57-7180; -7190


6-poles
Duty point 6 3 125 250
0.5Vopt 1 5
11
1
Vopt
11
13
-1
Vmax
7
14
3
8-poles
Duty point 6 3 125 250
0.5Vopt 1 5
5
1
Vopt
15
4
0
Vmax
15
3
1

RDM 56/57-7180; -7190


6-poles
Duty point 6 3 125 250
0.5V opt
2
4
1
V opt
1
4
0
Vmax
-3
4
0
8-poles
Duty point 6 3 125 250
0.5V opt
3
1
-1
V opt
3
0
-2
Vmax
3
2
0

38

500 1000 2000 4000 8000


-2
-10
-14
-16
-23
-4
-11
-15
-17
-23
-1
-10
-13
-12
-19

Hz
dB
dB
dB

500 1000 2000 4000 8000


-2
-8
-14
-17
-24
-3
-7
-13
-15
-24
-3
-9
-14
-13
-25

Hz
dB
dB
dB

500
-4
-4
-3

1000 2000 4000 8000


-5
-8
-13
-21
-6
-8
-13
-21
-6
-8
-12
-20

Hz
dB
dB
dB

500
-3
-3
-3

1000 2000 4000 8000


-6
-8
-15
-23
-5
-8
-14
-23
-6
-9
-10
-23

Hz
dB
dB
dB

Smoke Extract Fans ER

Dimensions

Dimensions

1625

RDM 56/57 7180-6D-24


RDM 56/57 7180-8D-21
RDM 56/57 7180-HD-28
RDM 56/57 7190-6D-28
RDM 56/57 7190-HD-26

1304
1
75

1050

65
1270

Flat roof upstand

ZBS 03-0125
(600C)

1270

14

ZBS 20-0125
For RDM56 only , when connected to duct

1205
1050

283

283

1205
1050

1160
1520

1210
1520

12

12

Inlet guard
ZSG 04-0710

8x11,5

130

Flexible connection at intake


ZKE 30-0710 (600C)

811.5

715
751
785

715
751
785

8x11,5

35

Mating flange
ZKF 11-0710 (600C)

8xM10

715
751
785

Average attenuation LWA 16 dB

115

1226
1050

115

900

1117

1190

12

1526

Silencer upstand ZDS 32-0125


(600C)

Attenuation in dB at mid frequencies in Hz


63 Hz
3 dB
1000 Hz 20 dB
125 Hz
6 dB
2000 Hz 25 dB
250 Hz
8 dB
4000 Hz 23 dB
500 Hz
14dB
8000 Hz 11 dB
Pressure loss p A through silencer upstand
In Pa, at flow rates in m/h
m/h
Pa
17000
20
20000
30
25000
40
30000
65
40000
11 0

39

Smoke Extract Fans ER

Technical Data

Smoke extract
fan ER
RDM 56/579090-4D-31

Flow
rate
m/h
51.900

Available
pressure
Pa
2000

Voltage

Speed

V
400/690 /Y

9090-ID-34
9090-GD-34

57.200/38.200
57.200/28.800

2.200/1.000
2.200/590

400 Y/Y
400 Y/YY

Pa
2200

LW
A=
11
1d

10

2000

9
1800

Rated
current
A
41.5/24.1

Weights

1/min
1460

Motor
rating
kW
22

kg
590

Isolator
switch
ESH 23
0220-62

1470/980
1470/732

26/9.5
28/7.5

49.0/20.0
52.0/20.5

640
640

0300-62
0300-62

RDM 50-9090-4D-31 2
RDM 50-9090-ID-34 1 3
RDM 50-9090-GD-34 1 4
= Vopt

B
1

1600
1400

10
10 9
7

1200

101

800
600

94

400

0
11
8
10

99

10

4 92

93
94
10000

0
2,5
Flow rate V

20000
5

30000
7,5

10

40000
10

50000

12,5

1
11

200

10

Available pressure pfa

1000

m/h
m/s

In the curves the A-weighted sound power level is LWA


(=LWA3 =LWA8) acc. to DIN 45635-38. Reference media
density: 1 = 1.15 kg/m.

Intake
Relative sound power level LWrel3 at octave mid frequencies fm

Discharge
Relative sound power level LWrel3 at octave mid frequencies fm

RDM 56/57-9090
4-poles
Duty point 6 3 125
0.5Vopt 1 5
11
Vopt
11
13
Vmax
7
14
6-poles
Duty point 6 3 125
0.5Vopt 1 5
11
Vopt
11
13
Vmax
7
14

RDM 56/57-9090
4-poles
Duty point 6 3 125
0.5V opt
2
4
V opt
1
4
Vmax
-3
4
6-poles
Duty point 6 3 125
0.5V opt
2
4
V opt
1
4
Vmax
-3
4

40

250
1
-1
3

500 1000 2000 4000 8000


-2
-10
-14
-16
-23
-4
-11
-15
-17
-23
-1
-10
-13
-12
-19

Hz
dB
dB
dB

250
1
-1
3

500 1000 2000 4000 8000


-2
-10
-14
-16
-23
-4
-11
-15
-17
-23
-1
-10
-13
-12
-19

Hz
dB
dB
dB

250
1
0
0

500
-4
-4
-3

1000 2000 4000 8000


-5
-8
-13
-21
-6
-8
-13
-21
-6
-8
-12
-20

Hz
dB
dB
dB

250
1
0
0

500
-4
-4
-3

1000 2000 4000 8000


-5
-8
-13
-21
-6
-8
-13
-21
-6
-8
-12
-20

Hz
dB
dB
dB

Smoke Extract Fans ER

Dimensions

Dimensions

1800

RDM 56/57 9090-4D-31


RDM 56/57 9090-ID-34
RDM 56/57 9090-GD-34

1275
4
93

1050

65
1276

Flat roof upstand

ZBS 33-0125 (600C)


for RDM 57
1205
1050

1276

14

ZBS 31-0125 (400C)


for RDM 56

283

283

1205
1050

1160
1520

1160
1520

12

12

12x11,5

130

Flexible connection at intake


ZKE 33-0900 (600C)

12xM10

Mating flange
ZKF 11-0900 (600C)

12x11,5

35

898
934
968

898
934
968

Inlet guard
ZSG 04-0900

1211.5
898
934
968

41

Smoke Extract Fans ER


Isolator switch ESH 23-0055-32 for
ER 2528-2D-11, ER 2531-4D-10
ER 3535-4D-10, ER 3540-4D-10, ER 3545-4D-13
ER 4550-ED-16, ER 4556-4D-17, ER 4556-6D-13
ER 5663-6D-16, ER 5671-6D-21
ER 7180-8D-21

Isolator switch ESH 23-0220-62 for


ER 990-4D-31

Isolator switch ESH 21/23-0220-62


for 3-phase motors, 1 speed, Y/-connection

Isolator switch ESH 21/23-0055-32


1 speed, Y/-connection

KL

L3

1L1

L1

1L2

L2

1L3

HiS

Isolator switches

W2 U2 V2

KL

KL KL U1 V1 W1
1T1 black
1T2 blue
1T3 brown
green /yellow

KL

KL

W2

U2

1L1
1L2

V2

KL KL U1 V1 W1
1T1 black
1T2 blue
1T3 brown
green /yellow

L1
L2
HiS

HiS

13

14

HiS

HiO

21

22

HiO

HiO
HiO

PE

PE

517

Isolator switch ESH 23-0110-62 for


ER 7190-HD-26, ER 7190-6D-28

1L1
1L2

HiO
HiO

2L1
2L2
2L3
14
13

L3
L1
L2
HiS

21

HiS
HiO

22

HiO

PE
Mains Y

2L1
2L2

1T1 grey
1T2 red
1T3 white
2T1 black
2T2 blue

2L3

2T3 brown

13

14

21

22

42

13

14

21

22

W2 U2 V2
U1 V1 W1

HiS
HiO

22

HiO

green /yellow

PE

green /yellow

Mains

Mains Y

L3
L1
L2

W2 U2 V2
U1 V1 W1

Motor Y/

isolator switch

isolator switch

Motor Y/

543

L3
L1
L2

HiS
HiS
HiO
HiO
PE
Mains
higher speed

1L1 1T1 white


1L2 1T2 grey
1L3 1T3 red
2L1 2T1 black
2L2 2T2 blue
2L3 2T3 brown
13
21

KL
KL

HiS
HiS
HiO
HiO
PE

518

2L1
2L2
2L3
14
13
21
22

Mains

L3
L1
L2

HiS
HiS
HiO
HiO
PE

1L1 1T1 2W
1L2 1T2 2V
1L3 1T3 2U
2L1 2T1 1W
2L2 2T2 1V
2L3 2T3 1U
13
21

KL
KL

2U 2V 2W
1U 1V 1W

14
22
green /yellow

Mains isolator switch

Motor Y/YY

544

Isolator switch ESH 23-0300-62 for


ER 9090-ID-34

Isolator switch ESH 21/23-0075-62


2 speeds, Dahlander connection Y/YY

Mains
lower speed

2L3

21

KL

Isolator switch ESH 23-0075-62 for


ER 3545-HD-10,
ER 4550-HD-14, ER 4556-HD-16
ER 5663-HD-19, ER 5671-HD-24
ER 7180-6D-24, ER 7180-HD-28

L3 2L1
L1 2L2
L2 2L3
HiS 14
HiS 13
HiO 21
HiO 22
PE

2T1 W1
2T2 V1
2T3 U1

KL

KL
KL

green / yellow

PE
Mains

L1
L2
HiS

Isolator switch ESH 21/23-0300-62

1L1
1L2
1L3

1L3
L1
L2
HiS
HiS

14
13

2L1
2L2

L3

KL

Isolator switch ESH 23-0300-62 for


ER 9090-GD-34

Isolator switch ESH 21/23-0110-62


1 speed, Y/-connection

L3

2L3

Motor Y

Mains isolator switch

1L3

1L3
2L1
2L2

L3

1T1 V2
1T2 U2
1T3 W2

1L1
1L2

KL

KL
KL

KL
KL

KL
KL

L3
L1
L2

1L1
1L2
1L3

2U 2V 2W
1U 1V 1W

14
22
green /yellow

isolator switch

Isolator switch ESH 21/23-0300-62


for 3-phase motors, 2 speed, separate windingsY/Y

Motor Y/YY

519

HiS
HiS
HiO
HIO
PE

14
13
21
22

Mains
lower speed

L3
L1
L2
HiS
HiS
HiO
HIO
PE

1L1
1L2
1L3
2L1
2L2
2L3
13
21

KL
KL

1T1 2W
1T2 2V
1T3 2U
2T1 1W
2T2 1V
2T3 1U

KL
KL

2U 2V 2W
1U 1V 1W

14
22

Mains isolator switch


higher speed

green /yellow
Motor

545

Smoke Extract Fans ER


Isolator switch ESH 23
D
C

ESH 23
0055-32
0075-62
0110-62
0220-62
0300-62

A
85
100
100
145
200

B
120
190
190
250
300

C
90
93
93
107
172

D
107
110
110
124
222

Dimensions Accessories

Execution
Clear grey plastic casing (ESH 23-0300-62 in sheet steel) for fitting on the wall. Protection IP 66.
Black handle for positions 0" and I. Cover coupling with integrated locking device.
Clear tapping arrangement. Every switch is equipped with a wiring diagram.
Function
The isolator switch is installed for isolating the smoke extract fan from the mains safely on site
in case of checking, cleaning, or maintenance works. So accidents by uncontrolled switching on
can be avoided and service operations will be eased.
Every isolator switch is provided with potential free contacts (1 open, 1 closed)

Execution
Robust coated sheet steel casing, protection IP 66, (when cooling fan and air filter IP 43) are
integrated. Surrounding temperature up to +40C.
Signals and buttons arranged on the front door.
Function
The switch panel will fulfil the following task in case of fire:
bridge the motor protection
start the fan into highest possible speed (e.g. 2 speed motor)
The switch panel is made for reaction to a signal coming from the optical smoke detector EBS 02.
A button is provided for manual start from the panel.

Optical smoke detector EBS 02

80

The optical smoke detector recognizes early smouldering as well as open fire with smoke generation.
It is working following the principle of scattered light. Light emitter end sensor are placed in the
sample chamber in a way that the emitter beam cannot directly hit the sensor. Only the light
scattered by smoke (Tyndall-effect) reaches the sensor and generates an electrical signal. The
electronic evaluation system of EBS 02 controls the smoke measuring chamber additionally with
regard to if dust deposit may false the signal. Strong dirt accumulation or a failure in function
are optically shown by EBS 02. A long range alarm threshold value check assures that a sufficiently
wide opening between basic signal and alarm signal will be maintained, until the maximum dirt
accumulation is reached. The alarm threshold signal is set acc. to EN 54-7. An additional
temperature sensor generates an alarm when a temperature above 70C is reached. A relay
contact will inside opens at alarm or current failure.
Execution
The smoke detector is of protection class IP 42acc. to DIN VDE 0470 and equipped with a LED
light signalising operational readiness.
The smoke detector EBS 02 may exclusively be connected to the electronic switch panel EBG.

Mounting plate for optical smoke


detector ZES 01

Fitting base for simple surface mounting of the optical smoke detector EBS 02. Designed for dry
rooms and for the maximum cable diameter of 9 mm. Weight app. 45 g.

33

Smoke detector switch panel EBG


(on request)

Cable max. 9 mm.


Cable passage by breaking out.
Cable max. 9 mm.

33

59,5

33

80

4,5
3,7

Manual switch ESH 31

125

The manual switch ESH 31 is made for starting the smoke extract installation by hand. The actual
state of operation is indicated.
Execution
The manual switch ESH 31 is made for being surface mounted. The casing made of plastic has an
orange colour. Protection class IP 20.
The unit is equipped with 2 buttons, switching voltage 24V, switching current 1A.

38

43

Sample specification Smoke Extract fans ER


Item.

Pcs.

Single price

Total price

RDM 56-2528 ./. 9090, suitable for maximum temperatures up to 400 C - 120 minutes.
RDM 57-2528 ./. 9090, suitable for maximum temperatures up to 600 C - 120 minutes.
Smoke extract fan
Air discharge vertical and swirl free. Tested and certified acc. to EN 12101-3 and certified by DIBt
under the codes Z-78.1-26/Z-78.1-27.
Stylish and fully closed casing made of aluminium.
Feed cable from the front and protected by a tube.
Fixing bracket for isolator switch or connection box to be fixed at the base frame.
Base frame for upstand fitting with wide overhung for integrating isolating material on roof.
Discharge to be protected against weather by integrated back draught dampers closing at standstill
of the fan.
Centrifugal impeller with backward curved blades made of steel, welded and coated.
All mechanically stressed parts made of galvanized sheet steel, motor separated from air stream
and cooled by outside air. Motor cabinet additionally thermally isolated.
The roof fans comply with the tolerances of Class 2 of DIN 24 166 Fans, Technical Specifications.

Fan type

................................................................

Flow rate

........................................................................... m3/h

Pressure increase

........................................................................... Pa

Temp. of gas medium

........................................................................... C

Speed

........................................................................... 1/min

Motor rating

........................................................................... kW

Voltage/frequency

........................................................................... V/Hz

A-Sound power level

........................................................................... dB

Weight

........................................................................... kg

Dimensions

........................................................................... mm

Accessories (at extra cost)


Flat roof upstand ZBS
Flat roof upstand ZBS 20 (only RDM 56, for duct connection, up to size 7190)
Silencer upstand ZDS 32 (up to size 7190)
Flexible Connection ZKE
Mating flange ZKF
Isolator switch
Smoke detector switch panel (on request)
Optical smoke detector
Mounting plate for smoke detector

Wolf GmbH, Postfach 1380, D-84048 Mainburg, Tel.: 087 51 / 74-0, Fax: 087 51 / 74-1600, Internet: www.wolf-heiztechnik.de

44
Part no.: 48 00 135

07/06
GB
subject to modifications

Manual switch