Professional Documents
Culture Documents
Fire Barrier Brochure
Fire Barrier Brochure
Fire Barrier Brochure
com
Insulating
Our
World
400C
Lorry Fire
1000C
1200C
1400C
FireBarrier 135 is a refractory cement fire protection material specially developed for the high temperatures developed
in tunnel fires. It can be applied by spraying or cast into sheets.
High strength
FireBarrier 135 has high adhesion strength
typically 8 times its weight, allowing fixings
to be attached directly to it.
Like concrete, strength increases over
time. Adhesion has been verified in use
and in independent laboratory tests.
Ease of installation
FireBarrier is easy to install with virtually no wastage due to spray rebound. It is installed in one single layer with quick dry times.
It can be installed onto concrete or metal substrates using standard
spray equipment (Putzmeister M11 or PFT G4/G5).
Temp. at
Interface of
concrete &
FB135 after
135 mins (C)
Temp. of
Steel
reinforcement
bars after
120 mins (C)
Temp. of
concrete
cold face
after
120 mins (C)
CSI DC02/016/F02
120
B35
HCM
150mm
28mm
289
123
50
CSI DC02/006/F02
120
B35
HCM
150mm
32mm
282
122
39
TNO 2005-CVB-R-0024
120
B50
HCM
200mm
28mm
345
135
56
TNO 2005-CVB-R-0024
120
B50
HCM
200mm
35mm
275
118
35
TNO 98-CVB-R-1182
120
B35
RWS
150mm
38mm
334
209
Not Measured
TNO 98-CVB-R-1182
120
B35
RWS
150mm
51mm
136
113
Not Measured
SINTEF 22NOO8,02,C
134
B70
RWS
400mm
49mm
167
N/A
18
SINTEF 22NOO8,02,C
125
B76
RWS
400mm
57mm
113
N/A
18
CSI DC02/006/F05
240
B35
ISO834
150mm
28mm
348
189
55
CSTB France1
132
B30
HCM
180mm
28mm
334
148
43
SP Sweden
120
C35/45
RWS
600
36mm
230
285
852
652
Not Measured
RS06-186 A
P80 1874
1 Tested as a floor with fire above to simulate the floor of an escape passage
2 Reinforcing rods placed 75mm from concrete lining surface
Temperature (C)
400
350
300
250
200
150
100
50
0
38mm
49mm
51mm
57mm
Concrete Thickness
65mm
Protection of ventilation
shafts/escape shafts
Protection of cables,
pipes and other
essential services
Protection of refuges
and fire escapes
Requirements: Fire protection of main concrete tunnel structure 2 hours RWS fire curve
Application:
Volume:
Project:
Requirement:
Fire Protection of escape refuges, 2 hours HCM and 4 hours ISO fire curves
Application:
Volume:
Project:
Requirements: Immersed road tunnel 2 hours RWS fire protection with fire testing required on
large pre-stressed roof sections. Washable surface, high adhesion strength
Application:
FireBarrier 135 in one single layer 36mm thick. Custom designed fore rated
expansion joint seal system between segments
Volume:
Project:
Requirements: Escape passage located under roof of ventilation shaft. Fire protection
required for the floor of the ventilation shaft to prevent fire spread to
escape way underneath. 2 hours protection required against HCM high-rise
hydrocarbon fire
Application:
Project:
Requirements: Fire protection of tunnel roof, ventilation ducts and escape passage, 2 hours
HCM fire curve, 4 hours ISO curve
Application:
28mm in one single layer for concrete exposed to HCM curve for 120 minutes.
12mm in one single layer for concrete exposed to ISO 834 curve for 2 hours.
35mm for steel sections exposed to HCM fire curse for 2 hours
Volume:
1350C
1050kg
Installed density
1550kg/m3
1180kg/m33
Dry density
1100kg/m3
3.0 MPa
9.0 MPa
40 MPa
Water to mix
50%
>4.9 MPa
>4.6 MPa
(after 7 days)
0.7 MPa
(after 28 days)
1.1 MPa
Modulus of elasticity
(after setting)
4.05 MPa
(after 28 days)
4.05 MPa
0.267 W/m.K
200C
0.194 W/m.K
500C
0.169 W/m.K
at 50C
704 kj/kg.K
at 100C
806 kj/kg.K
at 500C
678 kj/kg.K
Chemical composition
Si02
28.2%
AI203
43.5%
Ca0 Total
24.4%
Fe203
1.5%
Ti02
0.8%
1.6%
The values given here in are typical values obtained in accordance with excepted test methods and we are subject to normal manufacturing
variations. They are supplied as a technical service and are subject to change without notice. Therefore, the data contained here in should not be
used for specification purposes.
www.kemwellthermal.com
Roma Road, Tyseley, Birmingham, West Midlands, B11 2JH
Email: enquiries@kemwellthermal.com
Insulating
Our
World