Burner controls for the supervision of 1- or 2-stage gas or gas / oil burners of
small to medium capacity (typically up to 350 kW), with or without fan, in intermittent operation.
The LGB... and this Data Sheet are intended for use by OEMs which integrate the
burner controls in their products!
Use
The LGB... burner controls are used for the startup and supervision of 1- or 2-stage gas
or gas / oil burners in intermittent operation.
Depending on the type of burner control used, the flame is supervised either by an
ionization probe, a blue-flame detector QRC1... for forced draft gas / oil burners, or a
UV detector QRA... (with auxiliary unit AGQ1...A27).
In connection with the respective adapters, the LGB... burner controls replace their
predecessor types LFI7... and LFM1... (also refer to Replacement types under Ordering).
-
CC1N7435en
07.07.2004
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes should be observed!
Do not to open, interfere with or modify the unit!
All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
Before performing any wiring changes in the connection area of the LGB..., completely
isolate the burner control from the mains supply (all-polar disconnection)
Ensure protection against electric shock hazard by providing adequate protection for the
burner controls connection terminals
Fall or shock can adversely affect the safety functions. Such units must not be put into
operation, even if they do not exhibit any damage
Ensure that the relevant national safety regulations are complied with
Always run the ignition cables separate from the unit and other cables while observing
the greatest possible distance
Mounting notes
Installation notes
Example
Legend
V2
M
Z
V1
N
7435a14/0601
V...
M
Z
Fuel valve
Fan motor
Ignition transformer
2/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Locate the high-voltage ignition electrode and the ionization probe such that the ignition
spark cannot arc over to the ionization probe (risk of electrical overloads) and that it
cannot adversely affect the supervision of ionization
With both ionization current and UV supervision, the cable length for flame detection must not exceed 20 m
Insulation resistance
Must be a minimum of 50 M between ionization probe and ground
Soiled detector holders reduce the insulation resistance, thus supporting creepage currents
Prerequisite is not only high-quality heat-resistant insulation of the probes
cable, but also of the ionization probe itself (ceramic holder)
Earth the burner in compliance with the relevant regulations; earthing the boiler
alone does not suffice
The connection diagrams show the burner controls with earthed neutral conductor. In
networks with nonearthed neutral conductor and ionization current supervision, terminal
2 must be connected to the earth conductor via an RC unit (type reference
ARC 4 668 9066 0). It must be made certain that local regulations are complied with
(e.g. protection against electric shock hazard) since AC 230 V / 50 Hz mains voltage
produces peak leakage currents of 2.7 mA
Commissioning notes
a)
b)
c)
Anticipated response
Lockout at the end of TSA
Immediate lockout
Immediate lockout
3/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
LGB21.130A17
LGB21.130A27
LGB21.230A27
LGB21.330A27
LGB21.350A17
LGB21.350A27
LGB21.550A27
LGB22.130A27
LGB22.230B27
LGB22.330A17
LGB22.330A27
LGB22.330A270
LGB32.130A27
LGB32.230A17
LGB32.230A27
LGB32.330A17
LGB32.330A27
LGB32.350A17
LGB32.350A27
LGB41.255A27
LGB41.258A17
LGB41.258A27
89 / 336 EEC
90 / 396 EEC
73 / 23 EEC
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
--x
x
x
--x
x
x
x
--x
x
x
--x
x
x
x
x
-------
Service notes
Each time a unit has been replaced, check to ensure that wiring is in an orderly
state. Make the safety check in accordance with section Commissioning notes
Use KF8872 service adapter for short periods of time only
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with household waste.
Local and currently valid legislation must be observed.
4/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Mechanical design
The housing is made of impact-proof, heat-resistant and flame-retarding plastic.
It is of plug-in design (measuring 91 x 62 x 63 mm, including the base) and engages
audibly in the base.
The housing accommodates the
programming mechanism with the synchronous motor
electronic flame signal amplifier (ionization) with the flame relay and the other
switching devices
lockout reset button with its integrated fault indication lamp
Type summary
The type references given below apply to LGB... burner controls without plug-in base
and without flame detector. For ordering information on plug-in bases and other accessories, refer to Mechanical design, Ordering, Flame supervision ... and Technical data.
Flame detector
Type reference
Approved in:
tw/s
t1/s
TSA/s
t3n/s
t3/s
t4/s
t9/s
t10/s
6)
ca.
min.
max.
ca.
ca.
ca.
max.
min.
t11/s
t12/s
3)
3)
max.
max.
t20/s
ca.
Burner controls for prepurging with low-fire air volume and control of actuator
Ionization probe (ION)
LGB21.130A27 4)7)
CH, EU, S, SF
2.4
---
---
---
CH, EU, S, SF
15
2.4
---
---
---
38
with AGQ1...A27
LGB21.330A27 5)
CH, EU, H, S, SF
30
2.4
---
---
---
23
LGB21.350A27 5)7)
CH, EU, H, S, SF
30
10
---
---
---
21
LGB21.550A27 5)
AUS, CH, EU
50
10
---
---
---
Burner controls for prepurging with nominal load air volume and control of actuator
Ionization probe (ION)
LGB22.130A27 4)
CH, EU, N, S
2.4
---
12
12
21
or UV detector QRA...
LGB22.230B27 5)
CH, EU, N, S, SF
20
2.4
---
16.5
16.5
with AGQ1...A27
LGB22.330A27 5)7)
30
2.4
---
12
11
LGB22.330A270 5)8)
EU
30
2.4
---
12
11
Blue-flame detector
LGB32.130A27 4)1)
CH, EU
2.4
---
12
12
21
QRC1...
LGB32.230A27 5)1)
CH, EU
20
2.4
---
12
12
LGB32.330A27 5)
CH, EU
30
2.4
---
12
11
LGB32.350A27 5)
CH, EU
30
4.4
10
---
12
EU
18
---
10
---
---
---
10
18
---
10
---
---
---
10
LGB41.255A27
tw
Waiting time
1)
On request
t1
Prepurge time
2)
TSA
3)
t3
Preignition time
4)
t3n
Postignition time
5)
t4
6)
7)
t9
t10
t11
t12
t20
8)
5/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Ordering
Burner control, without plug-in base
Flame detectors
- Ionization probe
- UV- flame detectors QRA2... / QRA10...
- Blue-flame detectors QRC1...
supplied by thirds
refer to Data Sheet N7712
refer to Data Sheet N7716
RC unit
ARC 4 668 9066 0
For the supervision of ionization currents in networks with nonearthed neutral conductor
PTC resistor (AC 230 V)
To burden terminal 3 (mandatory when using burners with no fan
motor connected to terminal 3)
Auxiliary unit for UV supervision
- Cable length 500 mm
- Cable length 300 mm
- Can be fitted under the plug-in base (refer to Dimensions)
AGK25
AGQ1.1A27
AGQ1.2A27
AGK21
Service adapter
- For checking the functioning of the burner controls on the burner plant
- Functional test with signal lamps
- Detector resistance measurement with a jack of 4 mm diameter
KF8872
LFI7...
KF8880
LFM1...
LFM1...-F
KF8853-K
LFI7...
KF8880
LFM1...
KF8862
LFM1...
6/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Technical data
General unit data
LGB...
Mains voltage
Mains frequency
Input current at terminal 12
Current rating
Terminal 3
Mounting position
Weight
Storage
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
DIN EN 60 721-3-1
class 1K3
class 1M2
-20...+60 C
< 95 % r.h.
DIN EN 60 721-3-2
class 2K3
class 2M2
-20...+60 C
< 95 % r.h.
DIN EN 60 721-3-3
class 3K3
class 3M2
-20...+60 C
< 95 % r.h.
Terminals 4, 5 and 7
Terminals 9 and 10
Terminal 12
Cable length terminals 8 and 10
Perm. cable lengths
Detector cable laid separately
Power consumption
Primary fuse
Degree of protection
-
Environmental conditions
7/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Flame supervision
Flame supervision with
ionization probe
The conductivity and rectifying effect of hot flame gases are used for flame supervision.
For that purpose, AC voltage is applied to the heat-resistant ionization probe which
projects into the flame. The current that flows in the presence of a flame (ionization
current) produces the flame signal which is fed to the input of the flame signal amplifier.
The amplifier is designed such that it only responds to the DC current component of the
flame signal, thereby ensuring that a short-circuit between ionization probe and ground
cannot simulate a flame signal (since in that case AC current would flow).
Basically, the flame supervision circuit is insensitive to adverse effects of the ignition
spark.
However, should the disturbing effects of the ignition spark on the ionization current
exceed a certain level, the electrical connections on the primary side of the ignition
transformer must be changed and / or the location of the ionization probe must be
checked.
Ionization current supervision with burner
controls operating on
AC 110 V
Since the ionization current with burner controls operating on AC 110 V is only about
50 % of those operating on AC 230 V, certain applications make it necessary to increase the ionization current with a transformer.
Capacity of transformer: Min. 2 VA
Transforming ratio: Approx. 1.1...1.5
The primary and secondary windings of the transformer must be galvanically separated.
AC 115 V
7435v01/0504
Connection of
transformer
12
LGB2...
ION
AC 115...230 V
8/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
M
sw
QRC1
LGB3...
+
12
7435v02/0601
br
bl
Legend
M
sw
Black wire
br
Brown wire
bl
Blue wire
The QRC1... has been designed specifically for blue-burning flames. Incidence of light
is from the front and laterally. The flame detector is secured by means of a soft plastic
plug. 3-core connection (preamplifier integrated in the detector casing). For the different
types of flame detectors, engineering notes and technical data, refer to Data Sheet
N7716.
Flame supervision with
UV detector QRA... and
AGQ... for LGB21... /
LGB22... / LGB41...
Mains voltage
Mains frequency
Power consumption
Degree of protection
Perm. ambient temperature
In operation
During transport and storage
Perm. length of cable from QRA... to
AGQ1...A27 (use separate cable)
Mounting position
Perm. length of connecting cable from
AGQ1...A27 to LGB...
Weight of AGQ1...A27
AC 240 V
DC 400 V
DC 400 V
DC 300 V
DC 300 V
DC 380 V
DC 380 V
Detector voltage
Load by DC measuring instrument Ri > 10 M
Up to the end of t10 and after controlled shutdown
From the beginning of t1
DC detector signals with UV detector QRA...
Measurement on the QRA...
DC 280 V
DC 280 V
Min. required
Max. possible
200 A
500 A
9/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Flame supervision with UV detector QRA... and auxiliary unit AGQ... for LGB21... / LGB22... / LGB41...
UV detector QRA...
Universal flame detector for use with gas and gas / oil burners. Incidence of light from
the front and laterally, total length 97 mm. Available with normal or, as QRA2M, with
higher sensitivity. Secured with flange and clamp. Also available as a metal encapsulated version in the form of the QRA10... (for details, refer to Data Sheet N7712).
Auxiliary unit
AGQ1...A27
LGB...
12
* 11
(B)
bl rt
sw
sw
bl AGQ1...A27
QRA
br
LGB...
12
* 11
7435a15/0704
Connection diagram
7435a19/0301
Measuring circuit
(B)
GP/SB
R/W
L
(A)
L
N
br
bl rt
sw
QRA
sw
AGQ1...A27
bl
+
-
GP
SB
(A)
(B)
10/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Functions
The function diagrams show the required or permissible input signals to the control
section and to the flame supervision circuit hatched (refer to Connection diagrams).
If these input signals are not present, the burner control will stop the startup sequence to
trigger lockout where required by safety regulations.
Preconditions for
burner startup
Undervoltages
LGB... burner controls are capable of detecting undervoltages. This means that load
relay AR will be deenergized if mains voltage drops below AC 160 V (for nominal AC
220...240 V) or AC 75 V (for nominal AC 100...110 V).
The burner control will automatically make a restart attempt when the supply voltage
returns to a level above AC 160 V and AC 75 V respectively.
Reversed polarity
protection
If the connections of live conductor (terminal 12) and neutral conductor (terminal 2) are
mixed up, the burner control will initiate lockout at the end of TSA.
Startup sequence
AC
Startup sequence
TSA
tw
Waiting time
During the waiting time, air pressure switch LP and flame relay FR are
tested for correct contact positions.
t1
Prepurge time
Purging the combustion chamber and the secondary heating surfaces:
Required with low-fire air volumes when using the LGB21... and with nominal
load air volumes when using the LGB22... / LGB32...
Type summary and the Function and sequence diagrams show the socalled prepurge time t1 during which air pressure switch LP must indicate that the required air pressure is available.
The effective prepurge time t1 comprises interval end tw through t3.
t3
Preignition time
During t3 and up to the end of TSA, flame relay FR is forced to close.
On completion of t3, the release of fuel is triggered at terminal 4 or at terminal 11 of the LGB41...
11/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
t3n
Postignition time
Ignition time during TSA
Just before reaching the end of TSA, ignition transformer Z will be
switched off.
This means that t3n is somewhat shorter than TSA.
This is necessary in order to give the forcedly closed flame relay FR sufficient time to drop out if there is no flame.
t4
Interval
LGB21... / LGB41...: Time to the release of the second fuel valve BV2
LGB22... / LGB32...: On completion of t4, the heat source is controlled
depending on the load (release of load controller LR)
t9
t10
t11
t12
B B
CD
Shutdown by R
The burner is immediately shut down and the programming mechanism is
ready for a new start.
12/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Control sequence in
the event of fault
In principle, whenever lockout occurs, the fuel supply will immediately be shut down. If
that takes place between startup and preignition, which is not indicated by a symbol,
the usual cause is air pressure switch LP shutting down, or a premature, faulty flame
signal.
After a mains failure or in the event of undervoltage:
Premature flame signal from the start of t1:
Contacts of air pressure switch LP have
welded during tw:
No air pressure signal:
Air pressure failure on completion of t10:
Burner does not ignite:
Flame is lost during operation:
Lockout
After lockout, the LGB... will remain locked (lockout cannot be changed).
This state will also be maintained in the event of mains voltage failure.
IIII
Release of fuel
Lockout since there is no flame signal on completion of the first safety time
Lockout since there is no flame signal on completion of the second safety time
(LGB41...)
zzzz
Partial load or nominal load operation (or return to the operating position)
13/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Connection diagrams
LGB21...
Flame supervision
QRA...
A
GP/SB
R/W
B B
12
12
t1
tw
t10
10
11
GP/SB
Dbr1
bv1
bv2
ION
LP
11
t3
Z
BV1
AL
HS
BV1
LP
BV2
EK2
TSA
FS
Si
BV2
L
N
7435a09/0704
t4
7435f01/1299
LGB2...
LKP
t1
Application examples
LR
NL
SA
IV
KL
BV1
IV
IV
III
III
Zu
operation!
II
12
10
11
(*)
Dbr1
EK2
LP
AL
12
10
11
EK2
Z
BV1
(*)
BV1
BV2
SB
IV
a2
II
I
MS
SA
a b
L
b
a b
RV
K1
C3
V
C31
II
a b
I
MS
a b
LK
a b
R32
* Note:
R1
b
LK
SA
SQN3...121...
III
IV
N
a1
K2
A
a3
LR
BV2
HS
III
a
7435a01/0704
Si
ION
R/W
b2
b1
Si
LP
LR
SB
1
GP
R/W
AL
GP
HS
9
Dbr1
ION
7435a02/0704
14/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
12
10
11
LP
ION
EK2
GP
AL
BV1
LR
R/W
BV2
SB
HS
6
LKP
Si
NL
b2
a1
c1
IV
III
Zu II
a2
b1
II
III
IV
TSA
t4
7435a03/0704
t1
IV
III
KL
11
6
AGK25
7435a04/0398
3
HS AGK25
11
GP/SB
R/W
L
L
N
11
br bl rt
AGQ1 sw
sw
bl
7435a06/0704
QRA
+
-
Legend
LP
7435a16/1299
bl
Blue wire
br
Brown wire
rt
Red wire
sw Black wire
15/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Flame supervision
Air damper control for prepurging with nominal load air volume.
QRA...
LGB32...: With blue-flame detector QRC1...
B B
Nur LGB22...
GP/SB
R/W
LGB22... / LGB32...
12
12
3
Nocke I
10
11
ION
GP/
SB
LR
LP
LK
W
M
t11
t10
t1
t12
LP
t3
Z
BV1
11
HS
0 I
L
N
t4
Nur LGB32...
2
AL
3 1
7 10
Si
tw
1
sw
SA
br
QRC1...
BV1
12
bl
2
EK2
7435a10/0704
LR
5
TSA
LGB22.../32...
LKP
t1
FS
LR
NL
SA
7435f02/0700
BV1/2
KL
III
Zu
Application examples
III
t
II
LGB22...
10
EK2
GP
11
ION
LP
AL
12
10
GP
7435a20/0704
R1
Si
b1
b2
L
A
a2
a1
III
R3
C3
III
R1
L
K2
K1
LK
II
10
2)
R3
B
N
ION
LR
HS
0
LP
SB
HS
0
BV1
Si
*
1
11
BV1
LR
BV2
N
EK2
SB
AL
S1)
R/W
7435a08/0704
12
R2
1)
C1
RV
MS
RV
II
SQN3...151... or SQN3...251...
* Note:
SA
LK
16/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
LGB22...
12
10
R/W
11
LP
12
10
11
R/W
ION
LP
EK2
ION
EK2
LR
GP
AL
LR
GP
AL
BV1
BV1
BV2
BV2
SB
SB
4
a1
HS
I
b2
Si
0 I
N
NL
II
III
IV
7435a17/0704
III
KL
III
t1
TSA
II
III
IV
2
t4
GP/SB
R/W
L
L
N
6
AGK25
7435a04/0398
11
br bl rt
AGQ1 sw
sw
bl
7435a06/0704
QRA
+
-
Legend
GP/SB
R/W
L
N
LGB22... / LGB32...
11
Zu II
a2
b1
IV
Single-wire control
a1
I
IV
a2
b1
b2
c1
LKP
Si
HS
3
HS AGK25
11
bl
Blue wire
br
Brown wire
rt
Red wire
sw Black wire
LP
7435a16/1299
Legend
TSA
t1
Prepurge time
t4
AL
Alarm
LR
Load controller
BV...
Fuel valve
Fan motor
EK2
NL
Nominal load
ION
Ionization probe
GP
SB
HS
Mains isolator
Si
Primary fuse
KL
Low-fire
Limit thermostat
LKP
Ignition transformer
LP
17/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
B B
tw
GP/SB
R/W
D
12
t3
7
Z
TSA
BV1
4
t4
ZV1
11
t9
5
BV2
FS
1
7435f03/0301
10
11
Dbr2
GP/
SB
12
Dbr1
bv1
zv1
GP/SB
R/W
L
L
N
bv2
W
AL
R
EK2
BV2
BV1
ZV1
HS
ION
br bl rt
AGQ1 sw
sw
bl
7435a21/0704
QRA
Si
+
-
L
N
7435a11/0704
ION
ION1
ZR
7435s02/0504
7435s01/0504
ION2
HR
BV1
Legend
A
B B
C
HR
BV2
BV2
ZV1
Startup (switching on by R)
Interval for establishment of flame
Operating position of burner or release of the second stage
by load controllerLR
Shutdown by R
tw
Waiting time
TSA
t3
t4
t9
AL
BV...
bv...
Dbr1
Dbr2
EK2
ION
FS
GP
HR
HS
M
QRA...
R
SB
Si
W
Z
ZR
ZV1
zv1
Alarm
Fuel valve
Auxiliary switch in the fuel valves (for checking the fully
closed position)
Wire link
Wire link, required when contact bv or zv1 is missing
Remote reset button
Ionization probe
Flame signal
Gas pressure switch
Main burner
Mains isolator
(Auxiliary) fan motor
Blue-flame detector
bl
Blue
br
Brown
rt
Red
sw
Black
Control thermostat or pressurestat
Safety limit thermostat
Primary fuse
Limit thermostat
Ignition transformer
Pilot burner
Pilot gas valve
Auxiliary switch in the pilot gas valve
18/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
GP/
SB
12
br
L N
Legend
0 I
b
AS
1)
ar
ba
I
a
BR
LP
6 11
b
IV
fr
a
AR
V
a
FR
b
IX
a b
VI
b a
VII
b
a b a b
II VIII
EK1
L1
2 10
AL EK2
BV1
BV2
ION
Dbr1
7435i01/0504
MS
b
I a
tw
t10
II
b
IV a
t1
t3
TSA
t4
t20
b
V a
b
VI a
b
VII a
Alarm
AR
AS
Unit fuse
BR
BV...
Fuel valve
Dbr1
Wire link
EK...
FR
Flame relay
GP
HS
Mains isolator
ION
Ionization probe
L1
LP
Fan motor
MS
Synchronous motor
SB
Ignition transformer
7435f04/0801
b
a
AL
b
VIII a
I...IX
Cam switches
tw
Waiting time
TSA
t1
Prepurge time
t3
Preignition time
t4
t10
t20
b
IX a
b
AR a
1)
2)
exceed 1.6 k
b
FR a
T = 81 s (40,5 s 2) )
19/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
a br
GP/
SB
12
L N
Legend
0 I
b
AS
1)
III
b
LP
a
6 11
b
IV
fr
a b
V
VI
b
a
b a
AR
7435i02/0704
ar
a
FR
I
a
IX
a b
VII
a
BR
a b a b
II VIII
MS
EK1 L1
2 10
4
BV1
AL EK2
7
Z
BV2
Nur LGB22...
AL
Alarm
AR
AS
Unit fuse
BR
BV...
Fuel valve
EK...
FR
Flame relay
GP
HS
Mains isolator
ION
Ionization probe
L1
LP
Fan motor
MS
Synchronous motor
SB
Ignition transformer
Nur LGB32...
1
1
sw
ION
br
QRC1...
12
bl
2
B
7435f05/1299
b
I a
b
II a
b
III a
tw
t11 + t10
t1
t12
b
IV a
I...IX
Cam switches
tw
Waiting time
TSA
t1
Prepurge time
b
V a
b
VI a
4
t3
b
VII a
TSA t4
t20
b
VIII a
b
IX a
b
AR a
t3
Preignition time
t4
t10
t11
t12
t20
b
FR a
T = 81 s
1)
20/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
HS
a br
GP/
SB
12
0 I
AL
b
AS
I
a
ar
a
b
3
1)
III
VI
b a
VII
IX
a
L1
IV
8
AL
EK2
6
Dbr2
2 10
a
11
9 1
7
Dbr1
ZV1
BV1
BV2
ION
Ib
a
7435i03/0504
MS
EK1
Unit fuse
BR
BV...
Fuel valve
Dbr1
Wire link
Dbr2
EK...
BR
a
b a
II VIII b
AS
is missing
b
a
Alarm
AR
FR
fr
a
AR
Legend
Flame relay
GP
HR
Main burner
HS
Mains isolator
ION
Ionization probe
L1
Fan motor
MS
Synchronous motor
SB
Ignition transformer
ZR
Pilot burner
ZV1
II b
a
FR
III b
a
6
t9
IV b
a
tw
11
tw
t3 TSA
t4
t20
Vb
a
VI b
a
VII b
a
Waiting time
TSA
t3
Preignition time
t4
t9
t20
VIII b
a
IX b
a
5
7435f06/0301
AR b
a
FR b
a
T = 40,5 s
ION
HR
BV1
Cam switches
1)
ION1
ZR
7435s02/0504
7435s01/0504
ION2
I...IX
1.6 k
HR
BV2
BV2
ZV1
21/22
Siemens Building Technologies
HVAC Products
CC1N7435en
07.07.2004
Dimensions
Dimensions in mm
22
7435m03/0704
53,5
5,5
LGB...
41,5
62,5
47
88
91
xxxxxxxxxx
Type
27,5
Auxiliary unit
AGQ1...A27
Dimension
reference
90,5
AGQ1.1A27
500
19
AGQ1.2A27
300
34
60
69
13
22/22
Siemens Building Technologies
HVAC Products
65,6
18
220
5,4
5,4
B 6
7435m01/0301
CC1N7435en
07.07.2004