Type G
Washdown Nozzle
United States Navy
General
Description
Technical
Data
Approvals
TYCO Type G Nozzles are manufactured
in compliance with NAVSEA Drawing
No. 803-1385828 and have been
qualified to the High Impact Shock
requirements of MIL-S-901C (Navy),
Grade A, Hull Mounted, Class I, Light
Weight Test.
Discharge Coefficient
3.0 gpm/psi1/2 (43,2 lpm/bar1/2)
Water Discharge Pattern
The design of water spray systems
using the Type G Nozzles is to be in
accordance with the applicable standards of the Naval Sea Systems
Command. The approximate water
discharge pattern at the deflector is
125 degrees. The recommended range
of flowing pressure at the nozzle inlet is
20 to 60 psi (1,4 to 4,1 bar).
Thread Connection
1/2 Inch NPT
Nozzle Marking
G-125-.328
Weight
0.3 lbs. (0,14 kg)
Physical Characteristics
The Body of the Type G Nozzle is cast
from aluminum bronze per ASTM B148
(UNS C95300), the Splitter is naval
brass per ASTM B21 (UNS C46400),
the Deflector is silicon bronze per
ASTM B96 (UNS C65500), and the
Pin is bronze per ASTM B159 (UNS
C51000).
Page 1 of 2
APRIL 2015
Installation
TYCO Type G Nozzles must be
installed in compliance with the standards of the Fire Protection Branch of
the Ship Systems Directorate, Naval
Sea Systems Command.
Maintenance
TYCO Type G Nozzles require regularly scheduled inspection and maintenance. For instructions, refer to the
Preventative Maintenance System of
the United States Navy.
TFP820
TFP820
Page 2 of 2
1.69"
(42,9 mm)
PIN
DEFLECTOR
2.43"
(59,4 mm)
SPLITTER
BODY
1/2" NPT
7/16" (11,1 mm)
NOMINAL MAKE-IN
FIGURE 1
TYPE G NOZZLE
ASSEMBLY
Limited
Warranty
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate the full product name, including
description and part number (P/N).
Type G Nozzle
Specify: Bronze Type G Nozzle,
P/N 49-554-1-328
Worldwide
www.tyco-fire.com
Contacts
Technical
Data
Model
BFV-N
Approvals
UL and C-UL Listed
FM Approved
California State Fire Marshall under
Listing No. 7770-1670:101
Materials of Construction:
Body
Disc
Seat Material
Upper Stem
Operator
Friction Loss
The approximate friction loss, based
on the Hazen Williams formula and
expressed in equivalent length of pipe
with C= 120, is as follows. Unless otherwise indicated, the data is based on
friction loss information collected at a
typical flow rate of 15 feet per second.
4.4 feet of 2 inch Sch. 40 pipe for
the 2 inch valve.
6.2 feet of 2-1/2 inch Sch. 40 pipe
for the 2-1/2 inch valve.
7.6 feet of 3 inch Sch. 40 pipe for
the 3 inch valve.
9.2 feet of 4 inch Sch. 40 pipe for
the 4 inch valve.
Page 1 of 4
MARCH 2015
TFP1515
TFP1515
Page 2 of 4
Nominal
Valve
Sizes
Inches
(DN)
2
(50)
2.53
(64,0)
1.68
(43,0)
12.62
(320,5)
2.88
(73,0)
6.48
(164,6)
6.00
(152,4)
5.80
(147,3)
2.12
(53,8)
1.38
(35,1)
5/8
(15,9)
21
(10,0)
2-1/2
(65)
2.90
(74,0)
1.81
(46,0)
13.51
(343,1)
3.25
(83,0)
6.98
(177,3)
6.00
(152,4)
5.80
(147,3)
2.12
(53,8)
2.00
(50,8)
5/8
(15,9)
24
(11,0)
3
(80)
3.17
(81,0)
1.81
(46,0)
13,88
(352,6)
3.38
(86,0)
7.22
(183,4)
6.00
(152,4)
5.80
(147,3)
2.12
(53,8)
2.55
(64,8)
5/8
(15,9)
24
(11,0)
4
(100)
4.17
(106,0)
2.06
(52,0)
15.24
(387,0)
4.00
(160,3)
7.98
(202,7)
6.00
(152,4)
5.80
(147,3)
2.12
(53,8)
2.58
(65,5)
5/8
(15,9)
27
(12,0)
5
(125)
5.17
(131,0)
2.19
(56,0)
16.49
(418,8)
4.75
(121,0)
8.48
(215,4)
6.00
(152,4)
7.80
(198,1)
2.12
(53,8)
4.64
(117,9)
3/4
(19,1)
31
(14,1)
6
(150)
6.17
(157,0)
2.19
(56,0)
17.65
(448,3)
5.25
(133,0)
9.10
(231,1)
6.00
(152,4)
7.80
(198,1)
2.12
(53,8)
5.75
(146,1)
3/4
(19,1)
34
(15,0)
8
(200)
8.17
(208,0)
2.38
(60,0)
20.11
(510,8)
6.50
(165,0)
10.35
(262,9)
10.00
(254,0)
7.90
(200,7)
2.12
(53,8)
7.77
(197,4)
3/4
(19,1)
49
(22,0)
10
(250)
10.17
(258,0)
2.68
(69,0)
23.35
(593,1)
8.00
(203,0)
12.27
(311,7)
11.80
(300,0)
9.50
(241,3)
3.03
(77,0)
9.77
(248,2)
7/8
(22,2)
78
(35,0)
12
(300)
12.17
(309,0)
3.00
(76,0)
26.10
(663,0)
9.25
(235,0)
13.77
(349,8)
11.80
(300,0)
9.50
(241,3)
3.03
(77,0)
11.75
(298,5)
7/8
(22,2)
103
(47,0)
INDICATOR
FLAG
HANDWHEEL
GEAR
OPERATOR
Weight
Lbs.
(kg)
1/2" NPT
CONDUIT
CONNECTION
BODY
C
DISC
J
K
BOLT
DIAMETER
FIGURE 1
MODEL BFV-N WAFER STYLE BUTTERFLY VALVE
NOMINAL DIMENSIONS
Installation
The TYCO Model BFV-N Wafer Style
Butterfly Valves may be installed with
flow in either direction and can be
positioned either horizontally or vertically. They are designed for installation
between the faces of ANSI Class 125
and 150 flanges. The Series BFV-N are
self-sealing between mating flanges;
therefore, they do not require the use
of additional gaskets.
The Model BFV-N may be installed with
any pressure class or schedule of pipe
or tubing no greater than schedule 40
that is listed or approved for fire protection service and installed in accordance
with the manufacturers instructions.
Nominal
Flange Size
ANSI Inches
(DN)
Recommended
Minimum Torque
Ft.-Lbs
(Nm)
2-4
(50 - 100)
20 - 30
(27,1 - 40,7)
5-8
(125 - 200)
33 - 50
(44,7 - 67,8)
10
(250)
53 - 75
(71,8 - 101,7)
12
(300)
80 - 110
(108,4 - 149,1)
TABLE A
RECOMMENDED TORQUES
TFP1515
Page 3 of 4
SUPERVISORY
SWITCH
END OF LINE
RESISTOR
AUXILIARY
SWITCH
GND
SWITCH SHOWN
WITH VALVE
FULL OPEN
PANEL
BLUE
RED
VIOLET
SWITCH SHOWN
WITH VALVE
FULL OPEN
GREEN
ORANGE
YELLOW
YELLOW
ORANGE
CONTACT RATING:
BELL
+
POWER
-
FIGURE 2
MODEL BFV-N BUTTERFLY VALVE
INTERNAL SWITCH WIRING DIAGRAM WITH VALVE IN OPEN POSITION
damage the seat material. Be sure to
center the valve and do not damage
the liner. Relax the separation of the
flanges, install, and hand-tighten all
flange bolts. Slowly open the valve,
checking for free movement of the disc.
If valve opens freely, leave the valve in
the open position, and using a crossdraw sequence, tighten all flange bolts
until the valve is metal-to-metal with
both mating flanges. Recommended
tightening torques are listed in Table A.
Be certain to keep flange faces as parallel as possible during and after tightening bolts or studs. After final tightening,
again check the valve for full opening
and closing.
Care and
Maintenance
The TYCO Model BFV-N Wafer Style
Butterfly Valves must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
control valve for maintenance or inspection work on either the valve or fire
protection system which it controls, permission to shut down the affected fire
protection systems must be obtained
from the proper authorities and all personnel who may be affected by this
decision must be notified.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in accordance with the applicable standards of the National Fire Protection
C
OPEN
B
A
SHUT
FIGURE 3
MODEL BFV-N WAFER STYLE
BUTTERFLY VALVE
OPERATOR ADJUSTMENT
Association (e.g., NFPA 25), in addition to the standards of any authority
having jurisdiction. Contact the installing contractor or product manufacturer
with any questions. Any impairment
must be immediately corrected.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified inspection service.
TFP1515
Page 4 of 4
Limited
Warranty
Ordering
Procedure
Worldwide
www.tyco-fire.com
Contacts
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
Sprinkler
Identification
Numbers
TY3351 Horizontal Sidewall
TY3451 Vertical Sidewall
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
LPCB Certified
NYC Approved
Discharge Coefficient
K=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table C
Recessed Escutcheon: Signal or Pure
White, Jet Black, Chrome Plated, or
Natural Brass
Physical Characteristics
Frame Bronze
Button Brass/Copper
Sealing Assembly. . Beryllium Nickel w/TEFLON
Bulb Glass
Compression Screw Bronze
HSW Deflector Bronze
VSW Deflector Copper
APRIL 2015
TFP161
TFP161
Page 2 of 6
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to activate and water to flow.
Design
Criteria
The TYCO Series TY-B, 5.6 K-factor,
Horizontal and Vertical Sidewall Sprinklers are intended for fire protection
systems designed in accordance with
the standard installation rules recognized by the applicable Listing or Approval agency (for example, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of the FM Loss Prevention Data Sheets). Only the Style 10
Recessed Escutcheon, as applicable,
is to be used for recessed horizontal
installations.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135F (57C) to 3/32
inch (2,4 mm) for the 360F (182C) temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a minimum-to-maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Do not attempt to make-up for insufficient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
Horizontal Sidewall Sprinkler
Installation
The TYCO Series TY-B Recessed Horizontal Sidewall Sprinklers must be installed in accordance with the following
instructions.
Install recessed horizontal sidewall
sprinklers in the horizontal position with
the centerline of waterway perpendicular to the back wall and parallel to the
6*
1-13/16"
(46,0 mm)
CENTERLINE
OF SPRINKLER
WATERWAY
1
1/2" **
NPT
1-1/2"
(38,1 mm)
2-3/16"
(55,6 mm)
is indicated on
Deflector.
Pipe thread
connections per
ISO 7-1 can be
provided on
special request.
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
* Temperature rating
**
WRENCH
FLATS
9/16"
(14,3 mm)
Installation
The TYCO Series TY-B, 5.6 K-factor,
Horizontal and Vertical Sidewall Sprinklers must be installed in accordance
with this section.
DEFLECTOR
HAT
1 - Frame
2 - Button
3 - Sealing
Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector *
STYLE 10
RECESSED
ESCUTCHEON
ESCUTCHEON
PLATE SEATING
SURFACE
2-7/8" DIA.
(73,0 mm)
FIGURE 1
SERIES TY-B HORIZONTAL SIDEWALL (TY3351) SPRINKLER
5.6 K-FACTOR STANDARD RESPONSE
ceiling. The word TOP on the Deflector is to face towards the ceiling.
Step A. After installing the Style 10
Mounting Plate over the sprinkler
threads, hand-tighten the sprinkler into
the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 7
Recessed Sprinkler Wrench (Ref. Figure
5). Apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats
(Ref. Figure 1).
Step C. After the ceiling is installed or
the finish coat is applied, slide on the
Style 10 Closure over the Series TY-B
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFP161
Page 3 of 6
* Temperature
**
rating is
indicated on
Deflector.
ESCUTCHEON
PLATE SEATING
SURFACE
Pipe thread
connections
per ISO 7-1 can
be provided on
special request.
1/2" **
NPT
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
1 - Frame
4 - Bulb
7 - Ejection
2 - Button
5 - Compression Spring
Screw
3 - Sealing
Assembly 6 - Deflector *
ARROW MUST
POINT AWAY
FROM AND BE
PERPENDICULAR
TO THE BACK
WALL SURFACE
FIGURE 4
W-TYPE 6
SPRINKLER WRENCH
6*
FLOW
2-3/16"
(55,6 mm)
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
2-3/16"
(55,6 mm)
WRENCH
RECESS
5
4
2
1-1/2"
(38,1 mm)
WRENCH
FLATS
3
1
SHOWN
PENDENT
SHOWN
UPRIGHT
CROSS
SECTION
FIGURE 2
SERIES TY-B VERTICAL SIDEWALL (TY3451) SPRINKLER
5.6 K-FACTOR, STANDARD RESPONSE
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1-1/4" (31,8 mm)
FIGURE 3
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON, 5.6 K-FACTOR, 1/2 INCH NPT
When installing wax-coated sprinklers
with the adjustable Crescent wrench,
exercise care to prevent damage to the
wax coating on the sprinkler wrench
flats or frame arms and, consequently, exposure of bare metal to the cor-
FIGURE 5
W-TYPE 7 RECESSED
SPRINKLER WRENCH
5/81/4"
(15,96,4 mm)
CLOSURE
SERIES
TY-B
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
NOTICE
Only retouching of the wax coating applied to the wrench flats and frame arms
is permitted, and the retouching is to be
performed only at the time of the initial
sprinkler installation.
The steel rod should be heated only to
the point at which it can begin to melt
the wax, and appropriate precautions
need to be taken when handling the
heated rod in order to prevent the installer from being burned.
TFP161
Page 4 of 6
5.6
1/2
NPT
SPRINKLER
TYPE
HORIZONTAL
SIDEWALL
(TY3351)
Figure 1
RECESSED
HORIZONTAL
SIDEWALL
(TY3351)*
Figure 3
5.6
1/2
NPT
VERTICAL
SIDEWALL
(TY3451)
PENDENT
or
UPRIGHT
Figure 2
TEMPERATURE
RATING
BULB
LIQUID
COLOR NATURAL CHROME
BRASS
PLATED
135F (57C)
Orange
155F (68C)
Red
175F (79C)
Yellow
200F (93C)
Green
286F (141C)
Blue
360F (182C)
Mauve
135F (57C)
Orange
155F (68C)
Red
175F (79C)
Yellow
200F (93C)
Green
135F (57C)
Orange
155F (68C)
Red
175F (79C)
Yellow
200F (93C)
Green
286F (141C)
Blue
360F (182C)
Mauve
1, 2, 3, 4, 9
1, 2, 3, 9
1, 2, 4, 9
1, 2, 9
1, 2, 3, 9
1, 2, 3, 9
1**, 2**, 3**, 9**
N/A
1, 2, 3, 9
4, 5, 6, 7, 8, 9
N/A
5, 6, 7, 9
5, 6, 7, 9
5**, 6**, 7**, 9**
4, 5, 6, 8, 9
N/A
Notes:
1. UL Listed for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector-to-ceiling distance
2. C-UL Listed for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector-to-ceiling distance
3. FM Approved for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector-to-ceiling distance
4. LPCB Approved (Ref. No. 094a & 007k) at a 4 to 6 inch (100 to 150 mm) deflector-to-ceiling distance
5. UL Listed for use in Light and Ordinary Hazard Occupancies
6. C-UL Listed for use in Light and Ordinary Hazard Occupancies
7. FM Approved for use in Light Hazard Occupancies
8. LPCB Approved (Ref. No. 094a & 007k)
9. Approved by the City of New York under MEA 354-01-E
10. Where Polyester Coated, Lead Coated, Wax Coated, and Wax-over-Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion-resistant sprinklers. Where Lead Coated, Wax Coated, and Wax-over-Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as corrosionresistant sprinklers.
* Installed with Style 10 (1/2 NPT) or Style 40 (3/4 NPT) 3/4 Total Adjustment Recessed Escutcheon, as applicable
** 150F (66C) maximum ceiling temperature
*** Frame and deflector only
N/A Not Applicable
TABLE A
SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP161
Page 5 of 6
SPRINKLER FINISH
SPRINKLER
TYPE
NATURAL
BRASS
HORIZONTAL SIDEWALL
(TY3351)
CHROME
PLATED
LEAD
COATED
POLYESTER*
WAX
COATED
WAX-OVER-LEAD
COATED
5.6
1/2
NPT
RECESSED
HORIZONTAL SIDEWALL
(TY3351)
VERTICAL SIDEWALL
(TY3451)
Note:
a. The maximum working pressure of 250 psi (17,2 bar) only applies to UL Listing, C-UL Listing and Approval by the City of New York
* Frame and deflector only
TABLE B
SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS
MAXIMUM WORKING PRESSURE
Care and
Maintenance
Before closing a fire protection system main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection system from the proper authorities and notify all personnel who may be affected
by this action.
The owner must assure that the sprinklers are not used for hanging any objects and that the sprinklers are only
cleaned by means of gently dusting with
a feather duster; otherwise, non-operation in the event of a fire or inadvertent
operation may result.
TFP161
Page 6 of 6
P/N57XXXXXXX
TEMPERATURE
RATING
SPRINKLER
FINISH
SIN
578
HORIZONTAL SIDEWALL
TY3351
NATURAL BRASS
135
135F (57C)
575
VERTICAL SIDEWALL
TY3451
155
155F (68C)
175
175F (79C)
200
200F (93C)
WAX COATED
286F (141C) MAX
286
286F (141C)
LEAD COATED
360
360F (182C)
WAX-OVER-LEAD
286F (141C) MAX
000
OPEN***
CHROME PLATED
Notes:
* Eastern Hemisphere sales only
** Available only for 155F (68C) or 200F (93C) temperature
rated sprinklers
*** Available only for horizontal sidewall TY3351 for use in
Deluge Systems (OPEN indicates sprinkler assembly
without glass bulb, button, and sealing assembly)
TABLE C
SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS
PART NUMBER SELECTION
Color
Sprinkler
Temperature Rating
Part Number
Black
135F (57C)
56-065-1-135
Red
155F (68C)
56-065-1-155
Yellow
175F (79C
56-065-1-175
Blue
200F (93C)
286F (141C)
56-065-1-286
TABLE D
SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS
WAX RETOUCHING STICK PART NUMBER SELECTION
Limited
Warranty
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series TY-B (specify SIN),
(specify K-factor), (specify Horizontal or
Vertical Sidewall) Sprinklers with (specify) temperature rating, (specify) finish or
coating, P/N (Refer to Table C)
Recessed Escutcheon
Specify: Style 10 Recessed Escutcheon
with (specify) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Wax Sticks
(for retouching wrench-damaged
wax coating)
Specify: (specify color, below) Colored
Coded Wax Stick for retouching (specify temperature rating) temperature-rated
Series TY-B Sprinklers, P/N (specify)
Note: Each wax stick is suitable for
retouching up to 25 sprinklers.
Note: The wax used for 286F (141C)
sprinklers is the same as for 200F (93C)
sprinklers, and, therefore, the 286F (141C)
sprinkler is limited to the same maximum
ceiling temperature as the 200F (93C)
sprinkler (i.e., 150F [66C]).
Worldwide
www.tyco-fire.com
Contacts
Sprinkler
Identification
Number (SIN)
TY9128
Approvals
UL and C-UL Listed: CMDA
(Standard Response)
FM Approved: CMDA and CMSA
(Quick Response)
NYC Approved under MEA 355-01-E
(Approvals only apply to the service
conditions indicated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1 Inch NPT or ISO 7-R1
Discharge Coefficient
K=25.2 gpm/psi1/2 (362,9 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Maximum Coverage Area
196 ft. (18,2 m)
Finish
Natural Brass
Physical Characteristics
Frame Brass
Deflector Copper
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button Brass
Sealing Assembly. . Beryllium Nickel w/TEFLON
Ejection Spring INCONEL
Deflector Nut Brass
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
Technical
Data
APRIL 2015
TFP213
TFP213
Page 2 of 4
3
TEMPERATURE
RATING
10
2-9/16" DIA.
(65,0 mm)
2
1-
2-
3-
4-
5-
6-
7-
8-
9-
10-
Frame
Deflector
Compression Screw
Hook
Strut
Link Assembly
Button
Gasketed Spring Plate
Ejection Spring
Deflector Nut
3-3/4"
(95,3 mm)
9/16"
(14,3 mm)
NOMINAL
MAKE-IN
6
9
WRENCH
FLATS
7
1
1" NPT *
FIGURE 1
MODEL EC-25 UPRIGHT SPRINKLER, 25.2K
EXTENDED COVERAGE
Operation
The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, allowing the sprinkler to activate and flow water.
Design
Criteria
FM Approval Criteria
FM Loss Prevention Data Sheets
2-0, 3-26, and 8-9
TYCO Model EC-25 Extended Coverage 25.2K Upright Sprinklers (TY9128)
are FM Approved to be utilized in accordance with the following guidelines.
Application
The Model EC-25 Extended Coverage Upright Sprinklers are
FM Approved ceiling-level Storage
Sprinklers for storage occupancy
hazards and other similar high heat
release type fires. When compared with
other FM Approved Storage Sprinklers,
the Model EC-25 Sprinkler provides low
hydraulic demand, the spacing advantages of extended coverage, and the
FM Global obstruction benefits of an
upright sprinkler.
Model EC-25 Sprinklers should be
used in conformance with applicable
FM Global Property Loss Prevention
Data Sheets.
TFP213
Page 3 of 4
Hydraulic Design
To determine the hydraulic design for
the Model EC-25 Sprinkler refer to the
applicable FM Global Property Loss
Prevention Data Sheet.
System Type
Wet pipe systems only
Sprinkler Spacing
The maximum coverage area per
sprinkler is 196 ft. (18,2m). The
minimum coverage area per sprinkler is
100 ft. (9,3 m). The maximum distance
between sprinklers is 14 feet (4,3 m).
The minimum distance between sprinklers is 10 feet (3,05 m).
Note: When a wall or obstruction
makes a minimum spacing of 10 feet
(3,05 m) impossible, consult FM Global
Property Loss Prevention Data Sheet
2.0 for applicable guidelines.
Sprinkler Location
Locate sprinklers with respect to
the ceiling/roof in accordance with
FM Global Property Loss Prevention
Data Sheet 2.0.
Obstructions
Follow the obstruction requirements
as detailed in FM Global Property Loss
Prevention Data Sheet 2.0.
Other Details
All other design details should be in
accordance with FM Global Property
Loss Prevention Data Sheet 2.0 as well
as any other applicable FM Global Data
Sheet.
NFPA 13, Chapter 21
Alternative System Design
(CMSA)
TYCO Model EC-25 Extended Coverage Upright Sprinklers (TY9128) have
successfully undergone large-scale
fire tests at FM Global to comply with
Chapter 21 of NFPA 13, 2013 Edition.
As such, Tables 21.2.2 and 21.3.2 of
NFPA 13 may be utilized for design
options with the Model EC-25 Upright
Sprinklers for providing ceiling-only
protection.
This allows for the protection of Palletized, Solid Piled, Bin Box, Shelf, or
Back-to-Back Shelf Storage as well
as Single, Double, and Multiple Row
Open Rack protection of up to 30 feet
(9,1 m) of Cartoned Unexpanded Group
A Plastic Commodities in a maximum
35 feet (11 m) ceiling condition with
extended spacing up to 196 ft.2 while
maintaining very reasonable flow and
pressure requirements. Pipe sizes as
well as water supply requirements
can now be kept to a minimum when
compared to other design methods for
high piled storage challenges. Refer to
Tables A and B of this data sheet for
specific flow, pressure, and number of
sprinklers to be calculated.
WRENCH
RECESS
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
FIGURE 2
W-TYPE 1
SPRINKLER WRENCH
Installation
TYCO Model EC-25 Extended Coverage 25.2K Upright Sprinklers are to
be installed in accordance with this
section.
Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler using only the
frame arms and the appropriate sprinkler wrench. Do not grip or apply any
force to the fusible Link Assembly.
Damaged sprinklers must be replaced
immediately.
A leak-tight 1 inch NPT sprinkler
joint should be obtained by applying a minimum-to-maximum torque of
20 to 30 lbs.-ft. (26,8 to 40,2 Nm).
Higher levels of torque may distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
Note: Install the Model EC-25 Upright
Sprinkler in the upright position.
Step 1. With pipe thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply any
force to the Link Assembly, and handle
the Model EC-25 Sprinkler only by the
Frame arms.
Step 3. Wrench-tighten the Model
EC-25 Sprinkler using only the W-Type
1 Sprinkler Wrench (Ref. Figure 2) and
by fully engaging (seating) the wrench
on the sprinkler wrench flats.
Step 4. After installation, inspect the
Link Assembly of each Model EC-25
Sprinkler for damage. In particular, verify that the Link Assembly and
Hook are positioned as illustrated in
Figure 1, and that the Link Assembly
has not been bent, creased, or forced
out of its normal position in any way.
Damaged sprinklers must be replaced
immediately.
TFP213
Page 4 of 4
Storage
Arrangement
Commodity
Class
Palletized,
Solid-Piled,
Bin Box,
Shelf, or
Back-to-Back
Shelf Storage
Class I thru
Class IV,
encapsulated
and unencapsulated,
and cartoned
non-expanded
plastics
Max.
Storage
Height
Feet
(m)
Max.
Ceiling/
Roof
Height
Feet
(m)
Type of
System
25
(7,6)
30
(9,1)
Wet
30
(2,1)
14 x 14
(4,3 x 4,3)
250
(950)
30
(9,1)
35
(11)
Wet
40
(2,8)
12 x 12
(3,7 x 3,7)
250
(950)
30
(9,1)
35
(11)
Wet
40
(2,8)
14 x 14
(4,3 x 4,3)
500
(1900)
1.5
Min.
Max.
Hose
Stream
Number Operating Coverage
Area
Allowance
of Design Pressure
Sprinklers
psi
Ft. x Ft.
gpm
(bar)
(m x m)
(lpm)
Water
Supply
Duration
Hours
TABLE A
NFPA 13, CHAPTER 21 ALTERNATIVE SYSTEM DESIGN
PALLETIZED, SOLID-PILED, BIN BOX, SHELF, OR BACK-TO-BACK SHELF STORAGE OF
CLASSES I - IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES
Storage
Arrangement
Commodity
Class
Sprinkler
protection
criteria for
open-frame
rack storage
Class I thru
Class IV,
encapsulated
and unencapsulated,
and cartoned nonexpanded plastics
Max.
Storage
Height
Feet
(m)
Max.
Ceiling/
Roof
Height
Feet
(m)
Type of
System
Number
of Design
Sprinklers
Min.
Operating
Pressure
psi
(bar)
25
(7,6)
30
(9,1)
Wet
30
(2,1)
14 x 14
(4,3 x 4,3)
250
(950)
30
(9,1)
35
(11)
Wet
40
(2,8)
12 x 12
(3,7 x 3,7)
250
(950)
30
(9,1)
35
(11)
Wet
40
(2,8)
14 x 14
(4,3 x 4,3)
500
(1900)
1.5
Max.
Hose
Coverage
Stream
Area
Allowance
Ft. x Ft.
gpm
(m x m)
(lpm)
Water
Supply
Duration
Hours
TABLE B
NFPA 13, CHAPTER 21 ALTERNATIVE SYSTEM DESIGN
OPEN-FRAME RACK (SINGLE, DOUBLE, AND MULTIPLE ROW) STORAGE OF
CLASSES I - IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES
Care and
Maintenance
TYCO Model EC-25 Extended Coverage 25.2K Upright Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
Inspection, testing, and maintenance
must be performed as indicated below
and in accordance with the local
requirements and/or national codes.
Any impairment must be immediately
corrected.
The owner is responsible for the inspection, testing, and maintenance of their
fire protection system and devices in
Sprinkler Assemblies
Specify: Model EC-25 Extended Coverage 25.2K Upright Sprinklers (TY9128),
(specify temperature rating), with
Natural Brass finish, P/N (specify):
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Special Order
Sprinkler Assemblies with
ISO 7-R 1 Thread Connection
Specify: Model EC-25 Extended Coverage 25.2K Upright Sprinklers (TY9128)
with ISO 7-R 1 thread connection,
(specify temperature rating), with
Natural Brass finish, P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-451-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-451-1-214
Sprinkler Wrench
Specify W-Type 1 Sprinkler Wrench,
P/N 56-872-1-025
Contact your local distributor for availability. When placing an order, indicate
the full product description and part
number (P/N).
Worldwide
www.tyco-fire.com
Contacts
Model ESFR-25
25.2 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-25 Pendent Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers having a
nominal K-factor of 25.2 (Ref. Figure 1).
They are suppression-mode sprinklers
that are especially advantageous as a
means of eliminating the use of in-rack
sprinklers when protecting high-piled
storage.
The Model ESFR-25 Sprinklers are primarily used for ceiling-only sprinkler
protection of (but not limited to) the following storage applications:
most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics
uncartoned (exposed) expanded
plastics in accordance with NFPA 13
and FM Global standards
some storage arrangements of rubber tires, roll paper, flammable liquids, aerosols, and automotive
components
For more specific criteria, refer to
Table A as well as the applicable design
standard.
The Model ESFR-25 Pendent Sprinklers provide the system designer
with hydraulic and sprinkler placement options not presently available to
the traditional ESFR sprinklers having
nominal K-factors of 14.0 and 16.8. In
particular, the Model ESFR-25 Sprinkler has been designed to operate at
substantially lower-end head pres-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
Sprinkler
Identification
Number (SIN)
TY9226
TY9226 is a re-designation for Central
SIN 9226, Gem SIN G8441, and Star
SIN S8010.
APRIL 2015
TFP312
TFP312
Page 2 of 4
1
1" NPT
7
Components:
1 - Frame
2 - Deflector
3 - Compression
Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing
Assembly
9 - Ejection Spring
1-13/16"
(46,0 mm)
9/16"
(14,3 mm)
NOMINAL
MAKE-IN
9
6
3-13/16"
(96,8 mm)
5
4
THERMAL
SENSING
ELEMENT
WRENCH
FLATS
3
2
TEMPERATURE
RATING
2" (50,8 mm)
FIGURE 1
MODEL ESFR-25 PENDENT SPRINKLER, 25.2K
EARLY SUPPRESSION, FAST RESPONSE
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
VdS Approved
NYC Approved under MEA 356-01-E
LPCB Certified (Cert. Nos. 094b
and 007l)
CE Certified (Certificate of Conformity
1725-CPD-H0010)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
1 Inch NPT or ISO 7-R 1
Discharge Coefficient
K=25.2 gpm/psi1/2 (362,9 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Finish
Natural Brass
Physical Characteristics
Frame Brass
Deflector Bronze
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button Brass
Sealing Assembly. . Beryllium Nickel w/TEFLON
Ejection Spring INCONEL
Design
Criteria
The following general guidelines provided for the TYCO Model ESFR-25
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
FIGURE 2
W-TYPE 1
SPRINKLER WRENCH
struction (e.g., smooth ceiling, bar
joists, beam and girder, and so forth).
Where the depths of the solid structural members (e.g., beams and stem)
exceed 12 inches (302 mm), install
ESFR Sprinklers in each channel
formed by the structural members.
Ceiling Slope
Maximum 2 inch rise for 12 inch run
(16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)
In some cases, the installation standards permit a greater coverage area.
Minimum Coverage Area
64 ft.2 (5,8 m2) per
NFPA 13 / FM Global 2-0
Maximum Spacing
TFP312
Page 3 of 4
Storage Type
NFPA
FM Global
Refer to NFPA 13
Chapters 16 and 17
Refer to FM Global
2-0 and 8-9
Refer to NFPA 13
Chapters 14 and 15
Refer to FM Global
2-0 and 8-9
Refer to NFPA 13
Chapter 12
Refer to FM Global
2-0, 8-9, and 8-24
Refer to NFPA 13
Chapter 18
Refer to FM Global
2-0 and 8-9
Refer to NFPA 13
Chapter 19
Refer to NFPA 30
Refer to NFPA 13
Chapter 20
N/A
Aerosol Storage
(Refer to the Standard)
Automotive Components in Portable Racks
(Control mode only; refer to the Standard)
N/A Not Applicable
TABLE A
MODEL ESFR-25 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
12 feet (3,7 m) for building heights up to
30 feet (9,1 m)
10 feet (3,1 m) for building heights
greater than 30 feet (9,1 m). In some
cases, installation standards permit a
greater spacing.
Sprinkler Position
Pendent:
Frame arms aligned with pipe
Deflectors parallel with ceiling or roof
System Type
Wet Pipe only
Minimum Spacing
8 feet (2,4 m)
NFPA
Deflector-to-Ceiling Distance
6 to 18 inches (152 to 457 mm)
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.
Specific
Application
Listing (UL)
TYCO Model ESFR-25 Pendent Sprinklers are listed by Underwriters Laboratories (UL) for Specific Applications
with a ceiling height greater than
45 ft. (13,7 m) up to and including 48 ft. (14,6 m), and a storage
arrangement up to and including
43 ft. (13,1 m), the following guideline are provided for the TYCO Model
ESFR-25 Pendent Sprinklers:
Operation
The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.
TFP312
Page 4 of 4
Installation
TYCO Model ESFR-25 Early Suppression, Fast Response 25.2K Pendent
Sprinklers must be installed in accordance with this section.
General Instructions
Damage to the fusible Link Assembly during installation can be avoided
by handling the sprinkler by the frame
arms only (i.e., do not apply pressure
to the fusible Link Assembly), and by
using the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
A leak-tight 1 inch NPT sprinkler
joint should be obtained by applying a minimum-to-maximum torque of
20 to 30 lbs.-ft. (26,8 to 40,2 Nm).
Higher levels of torque can distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
Note: Install the Model ESFR-25
Pendent Sprinkler in the pendent position (Ref. Figure 2).
Step 1. With pipe thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply pressure to the Link Assembly, and handle
the Model ESFR-25 Pendent Sprinkler
only by the Frame arms.
Step 2. Wrench-tighten the Model
ESFR-25 Pendent Sprinkler using only
the W-Type 1 Sprinkler Wrench (Ref.
Figure 2) and by fully engaging (seating)
the wrench on the sprinkler wrench
flats (Ref. Figure 1).
Step 4. After installation, inspect the
Link Assembly of each Model ESFR-25
Pendent Sprinkler for damage. In particular, verify that the Link Assembly
and Hook are positioned as illustrated
in Figure 1, and that the Link Assembly is not bent, creased, or forced out
of normal position in any way. Replace
damaged sprinklers.
Care and
Maintenance
TYCO Model ESFR-25 Early Suppression, Fast Response 25.2K Pendent
Sprinklers must be maintained and serviced in accordance with this section.
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-25 Early Suppression, Fast Response 25.2K
Pendent Sprinklers (TY9226), (specify
temperature rating), with Natural Brass
finish, P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-441-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-441-1-214
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connection
Specify: Model ESFR-25, Early Suppression, Fast Response 25.2K
Pendent Sprinklers (TY9226) with
ISO 7-1 thread connection, (specify
temperature rating), with Natural Brass
finish, P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-442-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-442-1-214
Sprinkler Wrench
Specify: W-Type 1 Sprinkler Wrench,
P/N 56-872-1-025
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Worldwide
www.tyco-fire.com
Contacts
Model ESFR-17
16.8 K-factor Upright Sprinkler
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-17 Upright Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers having a
nominal K-factor of 16.8 (Ref. Figure 1).
They are suppression mode sprinklers
that are especially advantageous as a
means of eliminating in-rack sprinklers
when protecting high-piled storage.
Model ESFR-17 Sprinklers are primarily
used for ceiling-only sprinkler protection of (but not limited to) the following
storage applications:
most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics
cartoned, expanded plastics
some storage arrangements of
rubber tires and roll paper
For more specific criteria, refer to Table
A in this technical data sheet as well as
the applicable design standard.
The Model ESFR-17 Upright Sprinklers provide the system designer with
an upright option to the traditional
pendent ESFR Sprinklers. With a K-factor of 16.8, Model ESFR-17 Sprinklers
provide system designers with hydraulic and sprinkler placement options not
presently available to traditional ESFR
Sprinklers having a K-factor of 14.0. In
particular, the Model ESFR-17 Upright
Sprinklers are designed to operate at
substantially lower-end head pressures
compared to ESFR Sprinklers with 14.0
K-factors. This feature offers flexibility
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
when sizing system piping and positioning the system piping with respect
to the ceiling.
Applications for the TYCO ESFR Sprinklers are expanding beyond currently
recognized installation standards. For
information on research fire tests that
may be acceptable to an authority
having jurisdiction, contact Tyco Fire
Protection Products (TFPP) Technical
Services.
NOTICE
The Model ESFR-17 Upright Sprinklers
described herein must be installed and
maintained in compliance with this document, as well as with the applicable
standards of the National Fire Protection Association (NFPA), in addition to
the standards of any authorities having
jurisdiction (e.g., FM Global). Failure to
do so may impair the performance of
these devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
In all cases, the appropriate NFPA or
FM Global installation standard must
be referenced to ensure applicability and to obtain complete installation guidelines. The general guidelines
in this data sheet are not intended to
provide complete installation criteria.
Sprinkler
Identification
Number (SIN)
TY7126
APRIL 2015
Technical
Data
Approvals
FM Approved
CE Certified (Certificate of Conformity
1725-CPD-H0012)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 Inch NPT or ISO 7-R 3/4
Discharge Coefficient
K=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Finish
Natural Brass
Physical Characteristics
Frame Brass
Deflector Copper
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button Brass
Sealing Assembly. . Beryllium Nickel w/TEFLON
Ejection Spring INCONEL
Deflector Nut Brass
TFP316
TFP316
Page 2 of 4
2-9/16" DIA.
(65,0 mm)
TEMPERATURE
RATING
10
Components:
1 - Frame
2 - Deflector
3 - Compression
Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing
Assembly
9 - Ejection Spring
10 - Deflector Nut
2
3
WRENCH
FLATS
THERMAL
SENSING
ELEMENT
3-5/8"
(92,1 mm)
5
6
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
1-5/8"
(41,3 mm)
3/4" NPT
FIGURE 1
MODEL ESFR-17 UPRIGHT SPRINKLER, 16.8K
EARLY SUPPRESSION, FAST RESPONSE
Design
Criteria
The following general guidelines provided for the TYCO Model ESFR-17
Upright Sprinklers may be used for
quick reference.
The National Fire Protection Association (NFPA) and FM Global (FM Approvals) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines provided by NFPA and FM Global may
differ; consequently, the appropriate
standard must be used for a given
installation.
In all cases, the appropriate NFPA or
FM Global installation standard must
be referenced to ensure applicability and to obtain complete installation
guidelines, since the following general
guidelines are not intended to provide
complete installation criteria.
In addition to this technical data sheet,
the following data sheets describe
other TYCO ESFR Sprinklers:
TFP312
Model ESFR-25 (TY9226)
K=25.2 Pendent Sprinkler
TFP315
Model ESFR-17 (TY7226)
K=16.8 Pendent Sprinkler
TFP318
Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler
System Type
Wet Pipe
Roof Construction
Unobstructed or obstructed construction (e.g., smooth ceiling, bar joists,
beam and girder, and so forth)
Where the depths of the solid structural members (e.g., beams and stem)
exceed 12 inches (302 mm), install
ESFR Sprinklers in each channel
formed by the structural members.
Ceiling Slope
Maximum 2 inch rise for 12 inch run
(16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.
Obstructions below Upright ESFR
Sprinklers, Including Branchlines
Per the requirements of FM, obstructions below upright ESFR Sprinklers
can be ignored as follows
open-web bar joists or trusses
having chords no more than 4
inches (102 mm) wide
bridging or wind bracing no more
than 4 inches (102 mm) wide
Maximum Spacing
12 feet (3,7 m) for building heights
up to 30 feet (9,1 m)
Operation
The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.
TFP316
Page 3 of 4
Storage Type
NFPA
FM Global
Refer to NFPA 13
Chapters 16 and 17
Refer to NFPA 13
Chapters 14 and 15
Refer to NFPA 13
Chapter 12
Refer to NFPA 13
Chapter 18
Refer to Chapter 13
Chapter 19
Refer to FM 8-21
N/A
Refer to FM 7-29
Aerosol Storage
(Refer to the standard)
N/A
N/A
N/A
N/A
TABLE A
MODEL ESFR-17 UPRIGHT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Installation
TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Upright
Sprinklers must be installed in accordance with this section.
General Instructions
Avoid damage to the fusible Link
Assembly during installation by using
the Frame arms only to handle the
sprinkler (i.e., do not apply pressure
to the fusible Link Assembly) and by
using the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
A leak-tight 3/4 inch NPT sprinkler
joint should be obtained by applying a minimum-to-maximum torque of
10 to 20 lbs.-ft. (13,4 to 26,8 Nm).
Higher levels of torque can distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
WRENCH
RECESS
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
FIGURE 2
W-TYPE 21
SPRINKLER WRENCH
TFP316
Page 4 of 4
Care and
Maintenance
Limited
Warranty
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-17 Early Suppression, Fast Response 16.8K Upright
Sprinklers (TY7126), (specify temperature rating), with Natural Brass finish,
P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-447-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-447-1-214
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connection
Specify: Model ESFR-17 Early Suppression, Fast Response 16.8K Upright
Sprinklers (TY7126) with ISO 7-1 thread
connection, (specify temperature
rating), with Natural Brass finish, P/N
(specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-448-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-448-1-214
Sprinkler Wrench
Specify: W-Type 21 Sprinkler Wrench,
P/N 56-001-0-686
Worldwide
www.tyco-fire.com
Contacts
Model ESFR-17
16.8 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-17 Pendent Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers having a
nominal K-factor of 16.8 (Ref. Figures
1 and 2). They are suppression mode
sprinklers that are especially advantageous as a means of eliminating in-rack
sprinklers when protecting high-piled
storage.
Model ESFR-17 Pendent Sprinklers are
primarily used for ceiling-only sprinkler
protection of (but not limited to) the following storage applications:
most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics
cartoned, expanded plastics
uncartoned, unexpanded plastics
uncartoned, expanded plastics
some storage arrangements of
rubber tires, roll paper, and aerosols
For more specific criteria, refer to Table
1 in this technical data sheet as well as
the applicable design standard.
The Model ESFR-17 Pendent Sprinklers provide the system designer
with hydraulic and sprinkler placement options not presently available
to traditional ESFR Sprinklers having
a nominal K-factor of 14.0. In particular, Model ESFR-17 Pendent Sprinklers
are designed to operate at substantially lower-end head pressures, as
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
Sprinkler
Identification
Number (SIN)
Technical
Data
Approvals
UL Listed
C-UL Listed
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 Inch NPT or ISO 7-R 3/4
Discharge Coefficient
K=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Finish
Natural Brass
Physical Characteristics
Frame Brass
Deflector Bronze
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button. . . . . . . . . . . . . . . . . . . . Phosphor Bronze
Sealing Assembly. . Beryllium Nickel w/TEFLON
TY7223
APRIL 2015
TFP317
TFP317
Page 2 of 4
Components:
1 - Frame
2 - Deflector *
3 - Compression Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing Assembly
* Temperature rating is indicated
on Deflector.
** ISO 7-R 3/4 pipe thread can be
provided on special request.
1
3/4" **
NPT
7
1-1/2"
(38,1 mm)
8
6
1/2"
2-3/8"
(12,7 mm)
(60,3 mm)
NOMINAL
MAKE-IN
4
5
3
2*
WRENCH
FLATS
THERMAL
SENSING
ELEMENT
FIGURE 1
MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 165F (74C)
EARLY SUPPRESSION, FAST RESPONSE
Components:
1 - Frame
2 - Deflector *
3 - Compression Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing Assembly
* Temperature rating is indicated
on Deflector.
** ISO 7-R 3/4 pipe thread can be
provided on special request.
1
3/4" **
NPT
7
1-1/2"
(38,1 mm)
8
6
1/2"
2-3/8"
(12,7 mm)
(60,3 mm)
NOMINAL
MAKE-IN
4
5
3
2*
WRENCH
FLATS
THERMAL
SENSING
ELEMENT
FIGURE 2
MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 212F (100C)
EARLY SUPPRESSION, FAST RESPONSE
Design
Criteria
The following general guidelines provided for the TYCO Model ESFR-17
Pendent Sprinklers can be used for a
quick reference.
The National Fire Protection Association (NFPA) and FM Global (FM Approvals) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines provided by NFPA and FM Global may
differ. Consequently, the appropriate standard must be used for a given
installation.
In all cases, the appropriate NFPA or
FM Global installation standard must
be referenced to ensure applicability and to obtain complete installation guidelines. The following general
guidelines are not intended to provide
complete installation criteria.
System Type
Wet Pipe
Roof Construction
Unobstructed or obstructed construction (e.g., smooth ceiling, bar joists,
beam and girder, etc.).
Where the depths of the solid structural members (e.g., beams and stem)
exceed 12 in. (302 mm), install ESFR
Sprinklers in each channel formed by
the structural members.
Ceiling Slope
Maximum 2 inch rise for 12 inch run
(16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)
In some cases, the installation standards permit a greater coverage area.
Minimum Coverage Area
64 ft.2 (5,8 m2) per NFPA 13
Maximum Spacing
12 feet (3,7 m) for building heights up to
30 feet (9,1 m)
10 feet (3,1 m) for building heights
greater than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA 13
Deflector-to-Ceiling Distance
6 to 14 inches (152 to 356 mm)
FM Global 2-0
Consult FM Global and/or FM Global
guidelines for allowable deflector-toceiling distances as well as thermal
sensing element-to-ceiling criteria.
Operation
The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.
TFP317
Page 3 of 4
Storage Type
NFPA
Refer to NFPA 13
Chapters 16 & 17
Refer to NFPA 13
Chapters 14 & 15
Refer to NFPA 13
Chapter 12
Refer to NFPA 13
Chapter 18
Refer to NFPA 13
Chapter 19
Refer to NFPA 30
Aerosol Storage
(Refer to the standard)
Automotive Components in Portable Racks
(Control mode only; refer to the standard)
N/A
TABLE 1
MODEL ESFR-17 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
WRENCH
RECESS
FIGURE 3
W-TYPE 2
SPRINKLER WRENCH
WRENCH
FLATS
Installation
"FITTING SIDE"
TOWARD SPRINKLER
FITTING
WRENCH
RECESS
SOCKET
ACCEPTS
1/2" DRIVE
HEX
ACCEPTS
1" WRENCH
FIGURE 4
W-TYPE 30
SPRINKLER WRENCH
TFP317
Page 4 of 4
Care and
Maintenance
Limited
Warranty
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).
Special Order
Sprinkler Assemblies with
ISO 7-R 3/4 Thread Connection
Specify: Model ESFR-17 Early Suppression, Fast Response 16.8K Pendent
Sprinklers (TY7223) with ISO 7-R 3/4
thread connection, (specify temperature rating), with Natural Brass finish,
P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-456-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-456-1-214
Sprinkler Wrench
Specify: W-Type 2 Sprinkler Wrench,
P/N 56-872-1-001
Specify: W-Type 30 Sprinkler Wrench,
P/N 56-001-0-688
Worldwide
www.tyco-fire.com
Contacts
Model ESFR-1
14.0 K-Factor Pendent Sprinkler
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-1 Pendent Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers having
a nominal K-factor of 14.0. They are
suppression-mode sprinklers that are
especially advantageous as a means of
eliminating the use of in-rack sprinklers
when protecting high-piled storage.
Model ESFR-1 Sprinklers are primarily
designed for protection of the following
storage arrangements:
most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics
some storage arrangements of
rubber tires, roll paper, flammable
liquids
For more specific criteria, refer to
Table A as well as the applicable design
standard.
Applications for the TYCO ESFR Sprinklers are expanding beyond currently
recognized installation standards. For
information on research fire tests (with
flammable liquids and aerosols, for
example) that may be acceptable to an
authority having jurisdiction, contact
the Tyco Fire Protection Products
(TFPP) Technical Services.
NOTICE
The Model ESFR-1 Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition
to the standards of any other authorities
having jurisdiction (e.g., FM Global).
Failure to do so may impair the performance of these devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
In all cases, the appropriate NFPA,
FM Global installation standard, or
other applicable standard, must be
referenced to ensure applicability and
to obtain complete installation guidelines. The general guidelines in this
data sheet are not intended to provide
complete installation criteria.
Sprinkler
Identification
Number (SIN)
TY6226
TY6226 is a re-designation for Central
SIN C6226, Gem SIN G8440, and Star
SIN S8000.
Approvals
UL and C-UL Listed
FM Approved
VdS Approved
NYC Approved under MEA 356-01-E
LPCB Approved (Cert. Nos. 094b and
007l)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 Inch NPT
Discharge Coefficient
K=14.0 gpm/psi1/2 (201,6 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Finish
Natural Brass
Physical Characteristics
Frame Brass
Deflector Bronze
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button Brass
Ejection Spring INCONEL
Sealing Assembly. . Beryllium Nickel w/TEFLON
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
Technical
Data
MARCH 2015
TFP318
TFP318
Page 2 of 4
Components:
1 - Frame
2 - Deflector
3 - Compression
Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing
Assembly
9 - Ejection Spring
3/4" NPT
7
8
1-1/2"
(38,1 mm)
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
9
6
3-9/16"
(90,5 mm)
THERMAL
SENSING
ELEMENT
5
WRENCH
FLATS
4
3
2
1-7/8"
(47,6 mm)
TEMPERATURE
RATING
FIGURE 1
MODEL ESFR-1 PENDENT SPRINKLER, 14.0K
EARLY SUPPRESSION, FAST RESPONSE
Design
Criteria
The following general guidelines provided for the TYCO ESFR-1 Sprinklers
can be used for quick reference.
NOTICE
The National Fire Protection Association (NFPA) and FM Global (FM Approvals) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines provided by NFPA and FM may differ; consequently, the appropriate standard
must be used for a given installation.
In all cases, the appropriate NFPA or
FM installation standard must be referenced to assure applicability and to
obtain complete installation guidelines,
since the following general guidelines
are not intended to provide complete
installation criteria.
In addition to this technical data sheet,
the following data sheets describe
other TYCO ESFR Sprinklers:
TFP312
Model ESFR-25 (TY9226)
K=25.2 Pendent Sprinkler
TFP315
Model ESFR-17 (TY7226)
K=16.8 Pendent Sprinkler
TFP316
Model ESFR-17 (TY7126)
K=16.8 Upright Sprinkler
System Type
Wet Pipe
Operation
Roof Construction
Unobstructed or obstructed construction (e.g., smooth ceiling, bar joists,
beam and girder, and so forth)
The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.
Where the depths of solid structural members (beams and stem, for
example) exceed 12 inches (302 mm),
install ESFR Sprinklers in each channel
formed by the structural members.
Ceiling Slope
Maximum 2-inch rise for 12-inch run
(16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)
In some cases, the installation standards permit a greater coverage area.
Minimum Coverage Area
64 ft.2 (5,8 m2) per
NFPA 13 / FM Global 2-0
Maximum Spacing
12 feet (3,7 m) for building heights up to
30 feet (9,1 m)
10 feet (3,1 m) for building heights
greater than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA
Deflector-to-Ceiling Distance
6 to 14 inches (152 to 356 mm)
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.
TFP318
Page 3 of 4
Storage Type
NFPA
FM Global
Refer to NFPA 13
Chapters 16 and 17
Refer to FM Global
2-0 and 8-9
Refer to NFPA 13
Chapters 14 and 15
Refer to FM Global
2-0 and 8-9
Refer to NFPA 13
Chapter 12
Refer to FM Global
2-0, 8-9, and 8-24
Refer to NFPA 13
Chapter 18
Refer to FM Global
2-0 and 8-9
Refer to NFPA 13
Chapter 19
Refer to FM Global
8-21
Refer to NFPA 30
Refer to FM Global
7-29
Refer to FM Global
7-31
N/A
N/A
Aerosol Storage
(Refer to the standard)
Automotive Components in Portable Racks
(Control mode only; refer to the standard)
N/A Not Applicable
TABLE A
MODEL ESFR-1 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Installation
TYCO Model ESFR-1 Early Suppression, Fast Response 14.0K Pendent
Sprinklers must be installed in accordance with this section.
NOTICE
Damage to the fusible Link Assembly during installation can be avoided
by handling the sprinkler by the frame
arms only (i.e., do not apply pressure
to the fusible Link Assembly), and by
using the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
FIGURE 2
W-TYPE 2
SPRINKLER WRENCH
TFP318
Page 4 of 4
Care and
Maintenance
Limited
Warranty
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-14 Early Suppression, Fast Response 14.0K
Pendent Sprinklers (TY6226), (specify
temperature rating), with Natural Brass
finish, P/N (specify):
Sprinkler Wrench
Specify: W-Type 2 Sprinkler Wrench,
P/N 56-872-1-001
Worldwide
Contacts
www.tyco-fire.com
Model ESFR-17
16.8 K-factor Dry Type Pendent Sprinklers
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-17 Dry Type
Pendent Sprinklers are Early Suppression, Fast Response (ESFR) sprinklers
having a nominal K-factor of 16.8.
They are suppression mode sprinklers
that are especially advantageous as a
means of eliminating in-rack sprinklers
when protecting high-piled box-in-box
refrigerated storage areas.
The Model ESFR-17 Dry Type Pendent
Sprinkler is FM Approved and has
successfully undergone full-scale fire
testing at FM Global, when used in conformance with applicable FM Global
Property Loss Prevention Data Sheets.
The Model ESFR-17 Dry Type Sprinkler consists of an ESFR sprinkler permanently secured to a sprinkler drop
featuring an inlet with both grooved
and threaded connections. The drop
between the inlet and sprinkler remains
dry until the sprinkler operates, allowing for a pendent sprinkler installation on a wet pipe sprinkler system
where the dry drop and sprinkler are
located in an area subjected to freezing
temperatures.
The Model ESFR-17 Dry Type Sprinklers are primarily used for ceiling only
sprinkler protection (i.e., no need for
in-rack sprinklers) and used to protect
solid piled, palletized, and rack storage
that is subject to freezing temperatures.
The water supply is provided from a
wet pipe system located outside of the
refrigerated storage area. The Model
ESFR-17 Dry Type Sprinklers feature
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
MARCH 2015
Sprinkler
Identification
Number (SIN)
TY7229
TFP320
TFP320
Page 2 of 8
GROOVED
COUPLING
GASKET
SEALING
SURFACE
1-1/4" NPT
OR ISO 7-R 1-1/4
PIPE THREADED
CONNECTION
2" (DN50)
GROOVED
CONNECTION
THREADED
AND GROOVED
INLET
INLET
WRENCH
HEX
TABLE A
DIM. C
TABLE A
DIM. A
CASING
TABLE A
DIM. B
FRAME
WRENCH
FLATS
LINK
ASSEMBLY
CENTERLINE
OF THERMAL
SENSING
ELEMENT
HOOK
FIGURE 1
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER (TY7229)
36 Inch
(914 mm)
Sprinkler
30 Inch
(762 mm)
Sprinkler
23 Inch
(584 mm)
Sprinkler
Dimension A
37.5 in.
(952,5 mm)
31.3 in.
(795 mm)
24.3 in.
(617 mm)
Dimension B
36.2
(919,5 mm)
30.0
(762 mm)
23.0
(584 mm)
Dimension C
33.9
(861 mm)
27.7
(704 mm)
20.7
(526 mm)
TABLE A
SPRINKLER LENGTHS
Sprinkler
Type
Temperature
Rating
Laboratory Listings
and Approvals
Pendent
K=16.8 (TY7229)
165F (74C)
1, 2
212F (100C)
Notes:
1. UL Listed
2. FM Approved
TABLE B
LABORATORY LISTINGS AND APPROVALS
Design
Criteria
FRAME
DEFLECTOR
Approvals
UL Listed
FM Approved
BUTTON
WITH VENT
HOLES
STRUT
Technical
Data
TFP320
Page 3 of 8
Storage Type
NFPA
FM Global
Refer to NFPA 13
Chapters 16 and 17
Refer to FM Global
2-0 and 8-9
Refer to NFPA 13
Chapters 14 and 15
Refer to FM Global
2-0 and 8-9
Refer to NFPA 13
Chapter 12
Refer to FM Global
2-0, 8-9, and 8-24
Refer to NFPA 13
Chapter 18
Refer to FM Global
2-0 and 8-3
Refer to NFPA 13
Chapter 19
Refer to NFPA 30
Refer to 30B
N/A
N/A
Aerosol Storage
(Refer to the standard)
Automotive Components in Portable Racks
(Control mode only; refer to the standard)
N/A = Not Applicable
TABLE C
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Maximum Spacing
12 feet (3,7 m) for ceiling heights up to
30 feet (9,1 m)
10 feet (3,1 m) for ceiling heights greater
than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA
Deflector-to-Ceiling Distance
6 to 14 inches (152 to 356 mm)
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.
Sprinkler Threaded Fittings
1-1/4 inch NPT Model ESFR-17 Dry
Type Sprinklers are to be installed in
the 1-1/4 inch NPT outlet or run of the
following fittings:
malleable or ductile iron threaded
tee fittings that meet the dimensional requirements of ANSI B16.3
(Class 150)
cast iron threaded tee fittings that
meet the dimensional requirements
of ANSI B16.4 (Class 125)
NOTICE
Do not install Model ESFR-17 Dry Type
Sprinkler into any other type fitting connection without first consulting TFPP
Technical Services. Failure to use the
appropriate fitting may result in insufficient engagement of the inlet pipe
threads with consequent leakage.
Exposure Length
When using Model ESFR-17 Dry Type
Sprinklers to protect areas subject to
freezing temperatures, use Figures
2 and 3, and Table D to determine a
sprinklers appropriate exposed barrel
length to prevent water from freezing in
the connection pipes due to conduction. The exposed barrel length measurement must be taken from the face
of the sprinkler fitting to the exterior
surface of the structure or insulation
that is exposed to the heated area.
Do not attempt to add additional insulation around the barrel in the heated
area as a method to minimize condensation. This will reduce the calculated
exposure length.
TFP320
Page 4 of 8
1" (25,4 mm) NOMINAL
END OF
SPRINKLER
INLET
EXPOSED
BARREL
LENGTH
(REFER TO
TABLE D
AND DESIGN
CRITERIA)
FACE OF
SPRINKLER
FITTING
HEATED
AREA
EXTERIOR
SURFACE OF
CEILING
DIM. A
TABLE A
THREADED
FITTING
(REFER TO
DESIGN
CRITERIA)
INSULATING
SEAL
ASSEMBLIES
DIM. B
TABLE A
CEILING
DEPTH
INTERIOR
SURFACE OF
CEILING
PROTECTED
AREA
CLEARANCE
HOLE
2-1/2" to 3"
(65 to 75 mm)
DIA.
FIGURE 2
THREADED FITTING INSTALLATION
1-3/8"
(35 mm)
SYSTEM
PIPE
END OF
SPRINKLER
INLET
EXPOSED
BARREL
LENGTH
(REFER TO
TABLE D
AND DESIGN
CRITERIA)
FACE OF
SPRINKLER
FITTING
HEATED
AREA
EXTERIOR
SURFACE OF
CEILING
DIM. A
TABLE A
GROOVED
FITTING AND
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA)
INSULATING
SEAL
ASSEMBLIES
CEILING
DEPTH
Exposed Barrel
Ambient
Temperature(b)(c)
SYSTEM
PIPE
INTERIOR
SURFACE OF
CEILING
PROTECTED
AREA
CLEARANCE
HOLE
2-1/2" to 3"
(65 to 75 mm)
DIA.
FIGURE 3
GROOVED CONNECTION INSTALLATION
Ambient
Temp. of
Protected
Area(a)
40F
(4C)
40F
(4C)
30F
(-1C)
20F
(-7C)
4
(101,6)
10F
(-12C)
8
(203)
1
(25,4)
0F
(-18C)
12
(305)
3
(76)
-10F
(-23C)
14
(356)
4
(101,6)
1
(25,4)
-20F
(-29C)
14
(356)
6
(152)
3
(76)
-30F
(-34C)
16
(406)
8
(203)
4
(101,6)
-40F
(-40C)
18
(457)
8
(203)
4
(101,6)
-50F
(-46C)
20
(508)
10
(254)
6
(152)
-60F
(-51C)
20
(508)
10
(254)
6
(152)
50F
(10C)
60F
(16C)
Minimum Exposed
Barrel Length
Inches
(mm)
Notes:
a. The area below the ceiling is referred to as the
protected area. Ambient temperature is the temperature at the discharge end of the sprinkler.
For protected area temperatures that range
between the listed temperatures, use the next
cooler temperature.
b. Lengths are inclusive of wind velocities up to 30
mph (48,3 km/h) and assume a minimum 40F
(4C) in heated area.
c. Minimum exposed barrel length when Insulating
Seal Assembly is installed on exterior surface of
ceiling:
Threaded Fitting Installation 5 in. (125 mm)
(Ref. Figure 2)
Grooved Fitting Installation 4-1/2 in. (114
mm) (Ref. Figure 3)
TABLE D
MINIMUM EXPOSED
BARREL LENGTH REQUIRED
PER AMBIENT TEMPERATURE
DIM. B
TABLE A
TFP320
Page 5 of 8
GROOVED
TEE
MODEL ESFR-17
SPRINKLER
WELDED
GROOVED OUTLET
GROOVED
DROP NIPPLE
GROOVED RIGID OR
FLEXIBLE COUPLING
(REFER TO DESIGN
CRITERIA)
FIGURE 4
TYPICAL GROOVED CONNECTION
OPTIONS
THREADED
SPRINKLER
FITTING
SELF
TAPPING
SCREWS
W-TYPE 26
WRENCH
"INLET
SIDE"
SYSTEM
PIPE
WRENCH
JAW
APPLY WRENCH
JAW TO INLET
WRENCH HEX
SPRINKLER
FITTING
CLEARANCE
HOLE
W-TYPE 26
WRENCH
"FRAME
ARMS"
REFERENCE
MARKS
INDICATE
RELATIVE
SPRINKLER
FRAME ARM
ORIENTATION
BELOW
CEILING
"FITTING
SIDE"
"SPRINKLER
SIDE"
WRENCH
JAW
APPLY
WRENCH
JAW TO
FRAME
WRENCH
FLATS
FRAME
ARM
WRENCH
FRAME ARM
CLEARANCE
RECESS
"FITTING SIDE"
TOWARD
SPRINKLER
FITTING
W-TYPE 26
WRENCH
"SPRINKLER
SIDE" TOWARD
SPRINKLER
DEFLECTOR
SPRINKLER
DEFLECTOR
FIGURE 5
W-TYPE 26
SPRINKLER WRENCH
CEILING
SPRINKLER
FRAME
ARMS
FIGURE 6
SPRINKLER FRAME ARMS
ORIENTATION MARK
ORIENT
HOUSING
SLOT 180
OPPOSED
TO INSERT
SLOT
HOUSING
INSERT
INSULATION
RING
CLEARANCE
HOLE
ORIENT
INSULATION
RING SPLIT
BETWEEN
HOUSING
SLOT AND
SCREW
FIGURE 7
INSULATING SEAL ASSEMBLY
INSTALLATION
TFP320
Page 6 of 8
Clearance Space
In accordance with Section 8.4.9.2
of the 2010 edition of NFPA 13, when
protecting insulated freezer structures
with dry type sprinklers, the clearance
hole around the sprinkler barrel of
the Dry Type Sprinkler and the clearance hole must be sealed. Sealing is
accomplished by use of the Insulating
Seal Assemblies (Ref. Figure 7). Failure
to use the Insulating Seal Assemblies
will increase the potential for the formation of condensation on the sprinkler and subsequent ice build-up on
or around the sprinkler can occur that
might damage the dry type sprinkler
and/or prevent proper operation in a
fire situation.
FM Global 2-0
Consult FM Global and/or FM Global
guidelines for allowable vertical distance from ceiling to centerline of
thermal sensing element.
Replace with the new sprinkler following the installation instructions in this
section.
Operation
Installation
TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Pendent
Sprinklers must be installed in accordance with this section.
General Instructions
Avoid damage to the fusible Link
Assembly during installation by using
only the Casing to handle the sprinkler (i.e., do not apply pressure to the
fusible Link Assembly), and by using
the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
Model ESFR-17 Dry Type Sprinklers
must only be installed in fittings/connections that meet the requirements
of the Design Criteria section. Refer
to the Design Criteria section for other
important requirements regarding
piping design, exposure length, and the
sealing of the clearance space around
the sprinkler casing.
If a sprinkler using a threaded connection (vs. grooved connection) requires
replacement, remove the sprinkler
using only the W-Type 26 Sprinkler
Wrench. Fully engage the wrench on
the inlet wrench hex (Ref. Figure 5).
Threaded Connection
Instructions
A leak-tight 1-1/4 inch NPT sprinkler
joint should be obtained by applying a
minimum-to-maximum torque of 45 to
65 lbs.-ft. (61 to 88 Nm). Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Note: Install the Model ESFR-17 Dry
Type Pendent Sprinkler in the pendent
position (Ref. Figure 5) by carefully
raising the pendent sprinkler through
the clearance hole. The deflector of the
pendent sprinkler is to be parallel to the
ceiling.
Step 1. Apply a non-hardening pipe
thread sealant such as TEFLON to the
male 1-1/4 inch NPT inlet threads.
TFP320
Page 7 of 8
Care and
Maintenance
Limited
Warranty
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-17 Dry Type Early
Suppression, Fast Response 16.8K
Pendent Sprinklers (TY7229) with
two (2) Insulating Sealing Assemblies,
P/N (specify):
36 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . 614411360
212F (100C) . . . . . . . . . . . . . . . . . . 614421360
30 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . 614411300
212F (100C) . . . . . . . . . . . . . . . . . . 614421300
23 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . 614411230
212F (100C) . . . . . . . . . . . . . . . . . . 614421230
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connections
Specify: Model ESFR-17 Dry Type
Early Suppression, Fast Response
16.8K Pendent Sprinkler (TY7229) with
ISO 7-1 thread connection and two (2)
Insulating Sealing Assemblies, (specify
temperature rating), P/N (specify):
36 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . I614411360
212F (100C) . . . . . . . . . . . . . . . . . . I614421360
30 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . I614411300
212F (100C) . . . . . . . . . . . . . . . . . . I614421300
23 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . I614411230
212F (100C) . . . . . . . . . . . . . . . . . . I614421230
Sprinkler Wrench
Specify: W-Type 26 Sprinkler Wrench,
P/N 563411001
Insulating Seal Assembly Kit
Each Insulating Seal Assembly kit consists of one (1) Insulation Ring, one (1)
Insert, one (1) Housing, and two (2)
Screws.
Specify: Insulating Sealing Assembly,
P/N 911061500
TFP320
Page 8 of 8
Worldwide
www.tyco-fire.com
Contacts
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 6
MARCH 2015
Sprinkler
Identification
Number (SIN)
TY2234
Technical
Data
Approvals
UL Listed
(for use with wet pipe and dry pipe systems)
C-UL Listed
(for use only with wet pipe systems)
Certified to all requirements of
NSF/ANSI 61
(Refer to the Design Criteria section for details on these approvals.)
Discharge Coefficient
Temperature Rating
Finishes
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Button. . . . . . . . . . . . . . . . . . . . . . . Copper
Sealing Assembly. . . . . . . Beryllium Nickel
w/TEFLON
Bulb (3 mm) Glass
Compression Screw Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . Bronze
TFP400
TFP400
Page 2 of 6
Components:
1 - Frame
2 - Button
3 - Sealing Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector *
1/2"
NPT
rating is
indicated on
Deflector.
2-7/8" DIA.
(73,0 mm)
1
2
2-1/4"
(57,2 mm)
3
4
* Temperature
ESCUTCHEON
PLATE SEATING
SURFACE
1-5/8"
(41,3 mm)
STYLE 20
RECESSED
ESCUTCHEON
WRENCH
FLATS
6*
CROSS SECTION
PENDENT
RECESSED PENDENT
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
7/161/8"
(11,13,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
WRENCH RECESS
(END "A" USED
FOR TY2234)
FIGURE 3
W-TYPE 6
SPRINKLER WRENCH
MOUNTING
SURFACE
CLOSURE
1/8"
(3,2 mm)
TY2234
WRENCH
RECESS
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE
RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The TYCO RAPID RESPONSE Series
LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers are UL
and C-UL Listed for installation in
accordance with this section.
Residential Sprinkler
Design Guide
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturers recommendations that may be
acceptable to the local authority having
jurisdiction.
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
System Types
Per the UL Listing, wet pipe and dry
pipe systems may be utilized. Per the
C-UL Listing, only wet pipe systems
may be utilized.
Refer to Technical Data Sheet TFP485
for the use of residential sprinklers in
residential dry pipe systems.
Ceiling Types
Smooth flat horizontal, or beamed, or
sloped, in accordance with the 2013
Edition of NFPA 13D, 13R, or 13, as
applicable.
TFP400
Page 3 of 6
Hydraulic Design
(NFPA 13D and 13R)
For systems designed to NFPA 13D
or NFPA 13R, the minimum required
sprinkler flow rates are given in
Tables A and B as a function of temperature rating and the maximum
allowable coverage areas. The
sprinkler flow rate is the minimum
required discharge from each of the
total number of design sprinklers as
specified in NFPA 13D or NFPA 13R.
The number of design sprinklers
specified in NFPA 13D and 13R for wet
pipe systems is to be applied when
designing dry pipe systems.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required discharge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Table A or
B as a function of temperature
rating and the maximum allowable
coverage area.
A minimum discharge of 0.1 gpm/ft2
over the design area comprised
of the four most hydraulically
demanding sprinklers for actual
coverage areas protected by the
four sprinklers.
The number of design sprinklers specified in NFPA 13 for wet pipe systems is
to be applied when designing dry pipe
systems.
Dry Pipe System Water Delivery
When using the Series LFII Residential
Sprinklers (TY2234) in dry pipe sprinkler systems, the time for water delivery must not exceed 15 seconds for the
most remote operating sprinkler.
Obstruction to
Water Distribution
Sprinklers are to be located in accordance with the obstruction rules of
NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as with
the obstruction criteria described within
the Technical Data Sheet TFP490.
Operational Sensitivity
Sprinklers are to be installed with a
deflector-to-ceiling distance of 1-1/4 to
4 inches.
Sprinkler Spacing
The minimum spacing between sprinklers is 8 feet (2,4 m). The maximum
spacing between sprinklers cannot
exceed the length of the coverage area
(Table A or B) being hydraulically calculated (e.g., maximum 12 feet for a
12 ft. x 12 ft. coverage area, or 20 feet
for a 20 ft. x 20 ft. coverage area).
Installation
TYCO RAPID RESPONSE Series
LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a minimum-to-maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutcheon Plate by under- or over- tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
TFP400
Page 4 of 6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure (2)(3)
Maximum Ordinary Temperature Rating Intermediate Temperature Rating
Coverage
155F (68C)
175F (79C)
Area (1)
Flow
Pressure
Flow
Pressure
Ft. x Ft.
(m x m)
gpm
psi
gpm
psi
(l/min)
(bar)
(l/min)
(bar)
12 x 12
(3,7 x 3,7)
13
(49,2)
7.0
(0,48)
13
(49,2)
7.0
(0,48)
14 x 14
(4,3 x 4,3)
13
(49,2)
7.0
(0,48)
13
(49,2)
7.0
(0,48)
16 x 16
(4,9 x 4,9)
13
(49,2)
7.0
(0,48)
13
(49,2)
7.0
(0,48)
18 x 18
(5,5 x 5,5)
17
(64,3)
12.0
(0,83)
17
(64,3)
12.0
(0,83)
20 x 20
(6,1 x 6,1)
20
(75,7)
16.7
(1,15)
20
(75,7)
16.7
(1,15)
Deflector to
Ceiling
Installation
Type
Minimum
Spacing
Ft.
(m)
Smooth
Ceilings
1-1/4 to
4 inches
Recessed
using Style 20
Beamed
or
Ceilings per Escutcheon
non-recessed
NFPA 13D
per NFPA 13D,
or 13R
13R, or 13
1-1/4 to 1-3/4
inches below
bottom of
beam.
8
(2,4)
Notes:
1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design
criteria are stated.
2. Requirement is based on minimum flow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal
K-factor. Refer to Hydraulic Design under the Design Criteria section.
3. For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEM
Minimum Flow and Residual Pressure (2)(3)
Maximum
Coverage Ordinary Temperature Rating Intermediate Temperature Rating
Area (1)
155F (68C)
175F (79C)
Ft. x Ft.
Flow
Pressure
Flow
Pressure
(m x m)
gpm
psi
gpm
psi
(l/min)
(bar)
(l/min)
(bar)
12 x 12
(3,7 x 3,7)
13
(49,2)
7.0
(0,48)
13
(49,2)
7.0
(0,48)
14 x 14
(4,3 x 4,3)
14
(53,0)
8.2
(0,57)
14
(53,0)
8.2
(0,57)
16 x 16
(4,9 x 4,9)
15
(56,8)
9.4
(0,65)
15
(56,8)
9.4
(0,65)
18 x 18
(5,5 x 5,5)
18
(68,1)
13.5
(0,93)
18
(68,1)
13.5
(0,93)
20 x 20
(6,1 x 6,1)
21
(79,5)
18.4
(1,27)
21
(79,5)
18.4
(1,27)
Deflector to
Ceiling
Smooth
Ceilings
1-1/4 to 4
inches
Beamed
Ceilings
per NFPA 13D
or 13R
1-1/4 to 1-3/4
inches below
bottom of
beam.
Installation
Type
Minimum
Spacing
Ft.
(m)
Recessed
using Style 20
Escutcheon or
non-recessed
per NFPA 13D,
13R, or 13
8
(2,4)
Notes:
1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design
criteria are stated.
2. Requirement is based on minimum flow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal
K-factor. Refer to Hydraulic Design under the Design Criteria section.
3. For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used.
TABLE B
DRY PIPE SYSTEM
SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
TFP400
Page 5 of 6
Care and
Maintenance
Limited
Warranty
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Series LFII 4.9K Residential
Pendent Sprinkler (TY2234), (specify
temperature rating), with (specify) finish,
P/N (specify):
155F (68C)
Natural Brass . . . . . . . . . . . . . P/N 51-201-1-155
Pure White (RAL 9010)* . . . . . . P/N 51-201-3-155
Signal White (RAL 9003) . . . . . P/N 51-201-4-155
Chrome Plated . . . . . . . . . . . . P/N 51-201-9-155
175F (79C)
Natural Brass . . . . . . . . . . . . . P/N 51-201-1-175
Pure White (RAL 9010)* . . . . . . P/N 51-201-3-175
Signal White (RAL 9003) . . . . . P/N 51-201-4-175
Chrome Plated . . . . . . . . . . . . P/N 51-201-9-175
* Eastern Hemisphere sales only
Recessed Escutcheon
Specify: Style 20 Recessed Escutcheon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrenches
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
TFP400
Page 6 of 6
Worldwide
www.tyco-fire.com
Contacts
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers (SINs)
The flush design is made aesthetically appealing by concealing the deflector and other operating parts behind
the link assembly. The RAVEN Studio
Sprinklers, with a heat sensitive solder
type release element, are Listed as
quick response sprinklers.
NOTICE
RAVEN Studio Sprinklers described
herein must be installed and maintained in compliance with this document and with the applicable standards
of the National Fire Protection Association (NFPA), in addition to the standards
of any authorities having jurisdiction.
Failure to do so may impair the performance of these devices.
Standard Coverage
TY1281 Pendent
TY1381 Horizontal Sidewall
Extended Coverage
TY1282 Pendent
TY1382 Horizontal Sidewall
Technical
Data
Approvals
UL and C-UL Listed
Maximum Working Pressure
175 psi (12,1 bar)
Thread Connection
Adapter: 1/2 NPT x ISO 228 G3/8
Sprinkler: ISO 228 G3/8
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 16
Discharge Coefficient
K=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
Temperature Rating
165F (74C)
Finishes
Sprinkler: White, Grey, or Custom
Color
Physical Characteristics
Body Brass
Deflector Assembly Bronze
Sealing Assembly . . Beryllium Nickel w/TEFLON
Link Assembly Copper
Thread Adapter Brass
Escutcheon . . . . . . . . . Carbon or Stainless Steel
MARCH 2015
TFP658
TFP658
Page 2 of 16
Application
Pendent
Horizontal
Sidewall
Coverage
SIN
Standard
TY1281
Extended
TY1282
Standard
TY1381
Extended
TY1382
DUST
CAP
Dust Cap
Color
A
Inches
(mm)
Red
1-7/8
(48)
Green
2-13/16
(56)
INSTALLATION 1
LIP
BODY
NOTES:
1. USE LIP OF PAINTED SPRINKLER BODY, NOT BRASS
SHOULDER, AS INSTALLATION SURFACE,
REF. FIGURES 11 OR 12 AND INSTALLATION
PROCEDURE STEPS 8 OR G
LINK
ASSEMBLY
SPRINKLER
WRENCHING
NOTCHES
ENCLOSED
DEFLECTOR
(HORIZONTAL
SIDEWALL
SHOWN)
EXPOSED
BRASS
SHOULDER 1
FACTORY
PAINTED
AREA 1
A
SIDE VIEW
1-3/8" DIA.
(35 mm)
LINK VIEW
FIGURE 1
RAVEN STUDIO SPRINKLERS
ASSEMBLY
B
BASE
FLANGE
Dimensions
Inches
(mm)
Dim.
A
Dia.
C
PRONGS
Escutcheon
Style
J
3
(76)
4
(101)
7/16
(11)
C
Dia.
CLEARANCE
HOLE
FIGURE 2
RAVEN STUDIO SPRINKLERS
ESCUTCHEONS
2
(51)
Min.
Max.
2-1/2
(63)
3-1/2
(88)
TFP658
Page 3 of 16
1/2" NPT
TAPERED
THREADS
Fitting
Type
ISO
228 G3/8"
PARALLEL
THREADS
90 Elbow
WRENCH HEX,
1" (25 mm)
ACROSS FLATS
7/16"
(11 mm)
NOMINAL
MAKE-IN
Tee
A
Nominal
Pipe Size
Inches
DN
B
Outlet
Thread
ISO 228
Inches
1
DN25
G3/8
Dimensions
Inches
(mm)
C
1-5/8
(41)
13/16
(21)
13/16
(21)
3/4
(19)
1-3/4
(44)
1-5/8
(41)
13/16
(21)
N/A
11/16
(17)
1-13/16
(46)
NOTES:
COMMON THREAD
ADAPTER FEATURES
3/4"
(19 mm)
SHORT
1"
(25 mm)
A
X
STANDARD
B
E
1-1/2"
(38 mm)
90 ELBOW
D
MEDIUM
A
X
C
B
2"
(50 mm)
C
X
A
LONG
FIGURE 3
RAVEN STUDIO SPRINKLERS
THREAD ADAPTERS
TEE
FIGURE 4
RAVEN STUDIO SPRINKLERS
CPVC SPRINKLER ADAPTER FITTINGS
TFP658
Page 4 of 16
A
Inches
(mm)
Thread
Adapter
Size
Thread
Adapter
Length
Inches
(mm)
Min.
Max.
Min.
Max.
Short
3/4
(19)
1-1/4
(32)
1-3/4
(44)
1-1/2
(38)
2
(51)
5/16
(8)
Standard
1
(25)
1-1/2
(38)
2
(51)
1-3/4
(44
2-1/4
(57)
9/16
(14)
Medium
1-1/2
(38)
2
(51)
2-1/2
(64)
2-1/4
(57)
2-3/4
(70)
1-1/16
(27)
Long
2
(50)
2-1/2
(64)
3
(64)
2-3/4
(70)
3-1/4
(83)
1-9/16
(40)
B
Nominal
Inches
(mm)
Horizontal
Sidewall
Pendent
NOTES:
1. SPRINKLER FITTING AND WATERWAY CENTERLINE
MUST BE PERPENDICULAR TO ESCUTCHEON
MOUNTING SURFACE
2. MINIMUM THREAD ENGAGEMENT APPROX.
3/16" (5 mm) = 3 FULL REVOLUTIONS AFTER INITIAL
ENGAGEMENT OF SPRINKLER INLET THREADS WITH
THREAD ADAPTER OUTLET THREADS
3. THREAD ADAPTER NOT APPLICABLE WHEN
INSTALLING SPRINKLER DIRECTLY IN ISO 228 G3/8"
OUTLET THREADS OF CPVC SPRINKLER ADAPTER
FITTING (REF. FIGURES 4 AND 6)
A
7/16"
(11 mm)
NOMINAL
MAKE-IN
FACE OF
THREAD
ADAPTER
CEILING
OR WALL
COVERING
MATERIAL
FACE OF
SPRINKLER
FITTING
CLEARANCE
HOLE
CEILING
OR WALL
ESCUTCHEON
MOUNTING
SURFACE
SPRINKLER
FITTING AND
WATERWAY
CENETRLINE 1
SPRINKLER
FITTING 3
THREAD
ADAPTER 3
3/16" (5 mm)
MINIMUM THREAD
ENGAGEMENT 2
SPRINKLER
BODY ENGAGED
BY ESCUTCHEON
PRONGS
STYLE J OR K
ESCUTCHEON
FACE OF
FRAMING
MEMBER
FIGURE 5
RAVEN STUDIO SPRINKLERS
PENDENT AND HORIZONTAL SIDEWALL INSTALLATION CRITERIA
TFP658
Page 5 of 16
Fitting
Type
Fitting
Size
Inches x ISO 228
Outlet Threads
90 Elbow
1 x G3/8
Tee
1 x 1 x G3/8
A
Inches
(mm)
Horizontal
Sidewall
Pendent
Min.
Max.
Min.
Max.
7/8
(22)
1-1/4
(32)
1-1/8
(29)
1-1/2
(38)
NOTES:
1. SPRINKLER FITTING AND WATERWAY CENTERLINE
MUST BE PERPENDICULAR TO ESCUTCHEON
MOUNTING SURFACE
2. MINIMUM THREAD ENGAGEMENT APPROX.
7/32" (6 mm) = 4 FULL REVOLUTIONS AFTER INITIAL
ENGAGEMENT OF SPRINKLER INLET THREADS WITH
ADAPTER FITTING OUTLET THREADS
CPVC
PIPE FROM
SYSTEM
FACE OF
SPRINKLER
FITTING
A
CEILING
OR WALL
COVERING
MATERIAL
CEILING
OR WALL
ESCUTCHEON
MOUNTING
SURFACE
CLEARANCE
HOLE
CPVC SPRINKLER
ADAPTER FITTING
WITH ISO 228 G3/8"
OUTLET THREADS
(REF. FIGURE 4)
7/32" (6 mm)
MINIMUM THREAD
ENGAGEMENT 2
SPRINKLER
FITTING AND
WATERWAY
CENETRLINE 1
SPRINKLER
BODY ENGAGED
BY ESCUTCHEON
PRONGS
STYLE J OR K
ESCUTCHEON
FACE OF
FRAMING
MEMBER
FIGURE 6
RAVEN STUDIO SPRINKLERS
PENDENT AND HORIZONTAL SIDEWALL
LOW-PROFILE CPVC ADAPTER FITTING INSTALLATION CRITERIA
TFP658
Page 6 of 16
CAP PRONGS
UNIQUELY SPACED TO
ENGAGE SPRINKLER
WRENCHING NOTCHES
"UP" INDICATES
TOP OF HORIZONTAL
SIDEWALL SPRINKLER
DEFLECTOR
CAP IS FOR
SINGLE-USE ONLY
DO NOT RE-USE
AFTER PAINTING
CAP FLAT
ACCOMMODATES
LEVEL IF NECESSARY
FOR HORIZONTAL
SIDEWALL SPRINKLER
INSTALLATION
RAVEN STUDIO
SPRINKLER
FINGER
GRIP
CENTER
MARKING
POINT
FIGURE 7
RAVEN STUDIO SPRINKLERS
PAINT CAP APPLICATION
WRENCH PRONGS
UNIQUELY SPACED TO
ENGAGE SPRINKLER
WRENCHING NOTCHES
USE WRENCH
FOR SPRINKLER
INSTALLATION
AND REMOVAL
"UP" INDICATES
TOP OF HORIZONTAL
SIDEWALL SPRINKLER
DEFLECTOR
WRENCH FLAT
ACCOMMODATES
LEVEL IF NECESSARY
FOR HORIZONTAL
SIDEWALL SPRINKLER
INSTALLATION
RAVEN STUDIO
SPRINKLER
SOCKET ACCEPTS
1/2" DRIVE
FIGURE 8
RAVEN STUDIO SPRINKLERS
W-TYPE 25 WRENCH APPLICATION
TFP658
Page 7 of 16
NOTES:
STEEL
PIPE FROM
SYSTEM
LOCTITE 243
SEALANT
BOTTLE
SPRINKLER
INLET
THREADS
FIGURE 9
RAVEN STUDIO SPRINKLERS
LOCTITE 243 SEALANT APPLICATION STEEL PIPE SYSTEM INSTALLATIONS
NOTES:
CPVC
PIPE FROM
SYSTEM
PERMABOND LH056
SEALANT
APPLICATOR
CPVC SPRINKLER
HEAD ADAPTER FITTING,
ISO 228 G3/8" THREAD
SPRINKLER
INLET
THREADS
FIGURE 10
RAVEN STUDIO SPRINKLERS
PERMABOND LH056 SEALANT APPLICATION CPVC PIPE SYSTEM INSTALLATIONS
TFP658
Page 8 of 16
SPRINKLER
FITTING WITH
THREAD
ADAPTER
BASE
CLEARANCE
HOLE
CEILING OR WALL
ESCUTCHEON
MOUNTING
SURFACE
FINISHED
SURFACE
INSTALLATION
TOOL
SPRINKLER
BODY STOP
CPVC SPRINKLER
ADAPTER FITTING
WITH ISO 228 G3/8"
OUTLET THREADS
FINISHED
SURFACE
INSTALLATION
TOOL
FIGURE 11
RAVEN STUDIO SPRINKLERS
FINISHED SURFACE INSTALLATION TOOL APPLICATION
ROUGH-IN
INSTALLATION TOOL
LIP OF SPRINKLER BODY,
NOT BRASS SHOULDER,
FLUSH AGAINST SPRINKLER
BODY STOP SURFACE
RAVEN STUDIO SPRINKLER
WITH PAINT CAP OR
W-TYPE 25 WRENCH
WIDE BASE OF
BEAM FLUSH
AGAINST FACE
OF FRAMING
MEMBERS
CARRIAGE
SPRINKLER
FITTING WITH
THREAD
ADAPTER
CPVC SPRINKLER
ADAPTER FITTING
WITH ISO 228 G3/8"
OUTLET THREADS
ADJUST TO
ALIGN EDGE
OF GAUGE
WITH MARKING
ON IMPERIAL
OR METRIC
SCALE TO SUIT
TOTAL COVERING
MATERIAL
THICKNESS
METRIC SCALE
(0 to 40 mm)
GAUGE LOCK
HANDLE
GAUGE
ADJUST TO
SUIT FRAMING
SPACING AND
FITTING
LOCATION
LOCK
UNLOCK
IMPERIAL SCALE
(0 to 1-1/2")
FIGURE 12
RAVEN STUDIO SPRINKLERS
ROUGH-IN INSTALLATION TOOL APPLICATION
FACE OF
WALL OR
CEILING
FRAMING
MEMBER
TFP658
Page 9 of 16
NOTES:
1. INSPECT WRENCHING NOTCH POSITIONS AFTER
ESCUTCHEON INSTALLATION TO VERIFY PROPER
HORIZONTAL SIDEWALL SPRINKLER DEFLECTOR
ORIENTATION
FACE OF
FINISHED
CEILING
SPRINKLER
FITTING
RAVEN
STUDIO
HORIZONTAL
SIDEWALL
SPRINKLER
FARTHEST-SPACED
WRENCHING NOTCH
SPRINKLER
FITTING AND
WATERWAY
CENTERLINE
THREAD
ADAPTER
STYLE J OR K
ESCUTCHEON
ESCUTCHEON
MOUNTING
SURFACE
CLOSEST-SPACED
WRENCHING NOTCHES
FIGURE 13
RAVEN STUDIO SPRINKLERS
HORIZONTAL SIDEWALL INSTALLATION CRITERIA
NOTES:
1. REFERENCE DIMENSION D = TOTAL CEILING
OR WALL COVERING MATERIAL THICKNESS
(DRYWALL, PLYWOOD, ETC. PLUS TAPE,
PLASTER, ETC.)
D
REF.
CEILING OR WALL
ESCUTCHEON
MOUNTING
SURFACE
CLEARANCE
HOLE
PLASTER,
TAPE, ETC.
CEILING
OR WALL
COVERING
MATERIAL
FIGURE 14
RAVEN STUDIO SPRINKLERS
TOTAL CEILING AND WALL COVERING MATERIAL THICKNESS
ENCLOSED
HORIZONTAL
SIDEWALL
DEFLECTOR
TFP658
Page 10 of 16
5.6K Extended Coverage Pendent (TY1282)
Response
Rating
Coverage Area
Ft. x Ft. (m x m)
Minimum
Flow(a)
gpm (lpm)
Minimum
Pressure(b)
psi (bar)
Deflector-to-Ceiling
Distance
Sprinkler
Temperature Rating
F (C)
Minimum
Spacing
Ft. (m)
Quick
16 x 16 (4,9 x 4,9)
26 (98)
21.6 (1,49)
Flush Mounted
165 (74)
8 (2,4)
Coverage Area
Ft. x Ft. (m x m)
Minimum
Flow(a)
gpm (lpm)
Minimum
Pressure(b)
psi (bar)
Deflector-to-Ceiling
Distance(c)
Inches (mm)
Sprinkler
Temperature Rating
F (C)
Lateral
Minimum
Spacing(d)
Ft. (m)
Quick
16 x 16 (4,9 x 4,9)
26 (98)
21.6 (1,49)
4 to 12 (100 to 300)
165 (74)
8 (2,4)
Notes:
a. Requirement is based on minimum flow in gpm (lpm) from each sprinkler.
b. Indicated residual pressures are based on the nominal K-factor.
c. Centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figure 15).
d. Minimum spacing is for lateral distance between sprinklers located along a single wall; otherwise, adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.
TABLE A
RAVEN STUDIO SPRINKLERS
UL AND C-UL LISTING EXTENDED COVERAGE AREAS for LIGHT HAZARDS AND FLOW RATE CRITERIA
Design
Criteria
Standard Coverage Criteria
RAVEN Studio 5.6K Pendent and Horizontal Sidewall Sprinklers (TY1281 and
TY1381) are intended for use in light
hazard or ordinary hazard applications as defined by NFPA 13, utilizing
the density/area method for hydraulically calculated systems, and with
fire protection systems designed in
accordance with the standard installation rules recognized by the applicable listing or approval agency
(e.g., UL Listing is based on NFPA 13
requirements).
RAVEN Studio Horizontal Sidewall
Sprinklers (TY1381) must be installed
with a deflector-to-ceiling distance of 4
to 12 inches (100 to 300 mm). To meet
this requirement, the centerline of the
sprinkler waterway must be located
4-7/16 to 12-7/16 inches (112,7 to 315,9
mm) below the ceiling (Ref. Figures 13
and 15).
Extended Coverage Criteria
RAVEN Studio 5.6K Pendent and Horizontal Sidewall Sprinklers (TY1282 and
TY1382) must be installed in accordance with the flow rate criteria provided in Table A. They must be installed
and utilized in light hazard occupancies
only under smooth, flat, horizontal ceilings as outlined in the applicable installation standard recognized by the listing
or approval agency (e.g., UL Listing is
based on NFPA 13 requirements).
RAVEN Extended Coverage, Horizontal
Sidewall Sprinklers (TY1382) must be
installed with a deflector-to-ceiling distance of 4 to 12 inches (100 to 300 mm).
To meet this requirement, the centerline of the sprinkler waterway must be
located 4-7/16 to 12-7/16 inches (112,7
Operation
Water is prevented from flowing from
the RAVEN Studio Sprinkler by means
of a sealing assembly held in place
by operating parts secured by a link
assembly. The link assembly is comprised of two link halves soldered
together with an eutectic solder that
melts when exposed to heat. When
the link reaches its rated temperature,
the link halves separate and release
the operating parts and sealing assembly, allowing the deflector assembly to
extend from the body and water to flow
from the sprinkler.
Care and
Maintenance
TYCO RAVEN Studio Sprinklers 5.6K
Pendent and Horizontal Sidewall
(HSW) Quick Response, Standard and
Extended Coverage must be maintained and serviced in accordance with
this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities and
notify all personnel who may be affected by this action.
Service inspections should be made
on a regular basis to detect possible
damage or alterations to the sprinkler and escutcheon. Inspections
should include making certain that the
escutcheon is held fast to the mounting surface. Damaged or altered sprinklers are to be replaced immediately
TFP658
Page 11 of 16
RAVEN STUDIO
SPRINKLER
ESCUTCHEON
MOUNTING
SURFACE
ESCUTCHEON
9/16"
(14 mm)
SPRINKLER
DEFLECTOR ASSEMBLY
IN OPERATED POSITION
PENDENT
FACE OF
FINISHED CEILING
11/16"
(17 mm)
4" (102 mm)
TO
12" (305 mm)
TOP OF
DEFLECTOR
7/16"
(11 mm)
CENTERLINE
OF SPRINKLER
WATERWAY
RAVEN STUDIO
SPRINKLER
SPRINKLER
DEFLECTOR ASSEMBLY
IN OPERATED POSITION
ESCUTCHEON
ESCUTCHEON
MOUNTING
SURFACE
HORIZONTAL SIDEWALL
FIGURE 15
RAVEN STUDIO SPRINKLERS
OPERATED CONDITION
TFP658
Page 12 of 16
Installation
In finished surface construction, TYCO Raven Studio 5.6 K-factor Pendent and
Horizontal Sidewall Sprinklers must be installed in accordance with this section.
Preferred Method:
Finished Surface Procedure
Step 1
Step 2
Step 3
C
A
Step 4
Step 5
Step 6
TFP658
Page 13 of 16
Step 7
Step 8
Step 10
Step 11
Step 9
Step 12
TFP658
Page 14 of 16
Installation
In rough-in construction, TYCO Raven Studio 5.6 K-factor Pendent and Horizontal
Sidewall Sprinklers must be installed in accordance with this section.
Alternate Method:
Rough-in Procedure
Step A
Step B
Step C
A-D
Step E
Step F
TFP658
Page 15 of 16
Step G
Step H
Step J
Step K
Step L
Step M
TFP658
Page 16 of 16
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product description and Part
Number (P/N).
Note: Order all components separately.
A complete assembly consists of sprinkler, escutcheon, thread adapter and
inlet thread sealant. Order installation
tools and accessories as needed.
Sprinklers
Specify: RAVEN Studio 5.6K Sprinkler, (specifiy) SIN, (specify) coverage,
(specify) orientation, (specify) finish,
P/N (specify):
Standard Coverage
TY1281 Pendent
White . . . . . . . . . . . . . . . . . . . . . . . 50-310-4-165
Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-310-9-165
Custom Color . . . . . . . . . . . . . . . . 50-310-X-165
TY1381 Horizontal Sidewall
White . . . . . . . . . . . . . . . . . . . . . . . 50-312-4-165
Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-312-9-165
Custom Color . . . . . . . . . . . . . . . . 50-312-X-165
Extended Coverage
TY1282 Pendent
White . . . . . . . . . . . . . . . . . . . . . . . 50-311-4-165
Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-311-9-165
Custom Color . . . . . . . . . . . . . . . . . 50-311-X-165
TY1382 Horizontal Sidewall
White . . . . . . . . . . . . . . . . . . . . . . . 50-318-4-165
Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-318-9-165
Custom Color . . . . . . . . . . . . . . . . 50-313-X-165
Style J Escutcheons
(3 Inch Diameter)
Specify: RAVEN Studio Sprinkler
Escutcheon, Style J, 3 inch diameter,
(specify) material, (specify) finish, P/N
(specify):
Carbon Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-306-4-010
Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-306-7-010
Chrome . . . . . . . . . . . . . . . . . . . . . 56-306-9-010
Primed White . . . . . . . . . . . . . . . . . 56-306-0-004
Primed Grey . . . . . . . . . . . . . . . . . 56-306-0-007
Custom Color . . . . . . . . . . . . . . . . 56-306-X-010
Stainless Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-307-4-010
Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-307-7-010
Electropolish* . . . . . . . . . . . . . . . . 56-307-9-010
Primed White . . . . . . . . . . . . . . . . . 56-307-0-004
Primed Grey . . . . . . . . . . . . . . . . . 56-307-0-007
Custom Color . . . . . . . . . . . . . . . . 56-307-X-010
* Chrome-coated appearance
Style K Escutcheons
(4 Inch Diameter)
Specify: RAVEN Studio Sprinkler
Escutcheon, Style K, 4 inch diameter,
(specify) material, (specify) finish, P/N
(specify):
Carbon Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-308-4-010
Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-308-7-010
Chrome . . . . . . . . . . . . . . . . . . . . . 56-308-9-010
Primed White . . . . . . . . . . . . . . . . . 56-308-0-004
Primed Grey . . . . . . . . . . . . . . . . . 56-308-0-007
Custom Color . . . . . . . . . . . . . . . . 56-308-X-010
Stainless Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-309-4-010
Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-309-7-010
Electropolish* . . . . . . . . . . . . . . . . 56-309-9-010
Primed White . . . . . . . . . . . . . . . . . 56-309-0-004
Primed Grey . . . . . . . . . . . . . . . . . 56-309-0-007
Custom Color . . . . . . . . . . . . . . . . 56-309-X-010
* Chrome-coated appearance
Thread Adapters
Specify: RAVEN Studio Sprinkler
Thread Adapter, Brass, (specify) size,
P/N (specify):
Short 3/4 (19 mm) . . . . . . . . . . . . 91-310-0-075
Standard 1 (25 mm) . . . . . . . . . . . 91-310-0-100
Medium 1-1/2 (38 mm) 91-310-0-150
Long 2 (50 mm) . . . . . . . . . . . . . . 91-310-0-200
Paint Cap
Specify: RAVEN Studio Sprinkler Paint
Cap, P/N 56-100-0-354
Sprinkler Wrench
Specify: W-Type 25 Sprinkler Wrench,
P/N 56-314-1-001
Worldwide
www.tyco-fire.com
Contacts
Sprinkler
Identification
Numbers (SINs)
TY363
TY3630 (LPCB Approved only)
Technical
Data
Approvals
UL and C-UL Listed
VdS Approved
LPCB Approved (TY3630 only)
Sprinklers with Polyester Finish are UL
and C-UL Listed as Corrosion-Resistant Sprinklers.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
Temperature Ratings
135F (57C)
155F (68C)
175F (79C)
200F (93C)
286F (141C)
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor, Conventional Sprinklers, Quick
Response are intended for fire protection systems designed in accordance
with the standard installation rules recognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on NFPA 13 requirements). The
Series TY-FRB Conventional Sprinklers
are only for non-recessed applications.
Finishes
Sprinkler: Refer to Table A.
Physical Characteristics
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
FEBRUARY 2015
TFP667
TFP667
Page 2 of 4
Components: * Temperature
rating is indicated
1 - Frame
on Deflector.
2 - Button
3 - Sealing
6*
Assembly
4 - Bulb
5
5 - Compression
Screw
4
6 - Deflector *
ESCUTCHEON PLATE
SEATING SURFACE
2"
(50,8 mm)
** Pipe thread
1-3/8"
(34,9 mm)
3
connections per
ISO 7-1 can be
1
provided on
special request.
CROSS SECTION
SHOWN UPRIGHT
WRENCH
FLATS
SHOWN
PENDENT
FIGURE 1
SERIES TY-FRB CONVENTIONAL SPRINKLERS (TY363 & TY3630)
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation
The TYCO Series TY-FRB, 5.6 K-factor, Conventional Sprinklers, Quick
Response must be installed in accordance with this section.
General Instructions
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135F (57C) to 3/32
inch (2,4 mm) for the 286F (141C) temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to
14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Step 1. With pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 2).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the wrench flats.
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor, Conventional Sprinklers, Quick
Response must be maintained and serviced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb. (Refer to Installation Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to
the standards of any other authorities
WRENCH RECESS
(USE ONLY
END "A")
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
having jurisdiction. Contact the installing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.
TFP667
Page 3 of 4
P/N*77XXXXXXX
SPRINKLER
FINISH
SIN
TEMPERATURE
RATINGS
373
5.6K CONVENTIONAL
TY363
NATURAL
BRASS
135
135F (57C)
373
5.6K CONVENTIONAL
TY3630**
155
155F (68C)
175
175F (79C)
CHROME
PLATED
200
200F (93C)
286
286F (141C)
Notes:
* Use suffix I for ISO 7-1 connection (e.g., 77-373-4-175-I)
** LPCB Approved Series TY-B Conventional Sprinkler assemblies only: Use suffix L for LPCB Approved assemblies (e.g., 77-373-4-175-L or 77-373-4-175-IL for LPCB
Approved and ISO 7-1 connection)
*** Eastern Hemisphere sales only
TABLE A
PART NUMBER SELECTION
SERIES TY-FRB CONVENTIONAL SPRINKLERS
Limited
Warranty
Ordering
Procedure
TFP667
Page 4 of 4
Worldwide
Contacts
www.tyco-fire.com
Technical
Data
Approvals
UL Listed
FM Approved
VdS Approved
LPCB Approved
Page 1 of 8
APRIL 2015
TFP720
TFP720
Page 2 of 8
BRANCHLINE FITTING OUTLET
ISO 7-R 1 or
ISO 7-R 1-1/4
PIPE THREADED
END
FLEXIBLE HOSE
WITH SLIP NUTS:
25 mm ID UNBRAIDED
25 mm ID BRAIDED
25 mm ID BRAIDED - FM
28 mm ID BRAIDED
28 mm ID BRAIDED - FM
25 or 28 mm ID
HOSE THREADED
END
INLET
NIPPLE
SUPPORT
BAR
BAR
FIXING
CLAMP WITH
BUTTERFLY
BOLTS
25 or 28 mm ID
HOSE THREADED
SPRINKLER REDUCER
(STRAIGHT SHOWN)
SEE FIGURE 2
FOR DETAILS
REDUCER
BRACKET WITH
BUTTERFLY
BOLTS
SCREW
DROP-IN
CEILING PANEL
CEILING
GRID
T-BAR
TYPICAL SPRINKLER
ASSEMBLY
600 mm
BRANCHLINE
FITTING
(NOT INCLUDED)
INLET
NIPPLE
SYSTEM
BRANCHLINE
FLEXIBLE HOSE
WITH SLIP NUTS:
25 mm ID UNBRAIDED
25 mm ID BRAIDED
25 mm ID BRAIDED - FM
28 mm ID BRAIDED
28 mm ID BRAIDED - FM
ISO 7-R 1 or
ISO 7-R 1-1/4
THREADED
FITTING
OUTLET
SPRINKLER
REDUCER
(SEE FIGURE 2)
HOSE
THREADED
SLIP NUT
BAR
FIXING
CLAMP WITH
BUTTERFLY
BOLTS
SUPPORT
BAR
REDUCER
BRACKET WITH
BUTTERFLY
BOLTS
CEILING
GRID
T-BAR
DROP-IN
CEILING
PANEL
SPRINKLER INSTALLED
IN ACCORDANCE WITH
MANUFACTURER'S
INSTRUCTIONS
FIGURE 1
FASTFLEX FLEXIBLE SPRINKLER HOSE
TFP720
Page 3 of 8
INLET
NIPPLE
L1
700
1000
1200
1500
1800
2000
2500
2700
3100
3700
L2
SLIP
NUT
FLEXIBLE
HOSE
BRANCHLINE
FITTING
NOMINAL LENGTH mm
L1
L2
L2
(YN or YB)
(YN)
(YB)
MODEL
SIZE
HOSE
TERMINATION
FERRULE
580
880
1080
1380
1680
1880
2380
2580
2980
3580
390
690
890
1190
1490
1690
2190
2390
2790
3390
370
670
870
1380
1470
1670
2170
2370
2770
3370
SPRINKLER
REDUCER
HOSE ASSEMBLIES
25 or 28 mm ID
MALE HOSE
THREADED
INLET
125 mm
WRENCH
AND BRACKET
FLATS
WRENCH
AND BRACKET
FLATS
120 mm
25 or 28 mm ID
MALE HOSE
THREADED
INLET
125 mm
STRAIGHT
WRENCH
AND BRACKET
FLATS
140 mm
45 DEGREE
133 mm
SPRINKLER REDUCERS
50 mm
25 or 28 mm ID
MALE HOSE
THREADED
INLET
90 mm
BAR FIXING CLAMPS
FIGURE 2
FASTFLEX FLEXIBLE SPRINKLER HOSE
NOMINAL DIMENSIONS
TFP720
Page 4 of 8
Up to 700
Yes
Yes
Yes
Up to 1200
No
Yes
Yes
Up to 3700
No
No
Yes
For compensation of pressure loss, the nominal
assembly length is to be multiplied by 12. The resulting
length will provide pressure drop in equivalent length
DN20 (26,9 x 2,3 mm) seamless metal tube per DIN
2448.
Number of
90 Bends
Equivalent Length* of
DN25 Sch. 40 Pipe at
C=120 in Meters
700
8,9
1000
13,5
1200
11,9
1500
18,7
1800
24,7
2000
20,7
2500
21,7
2700
24,2
3100
25,9
3700
3
30,3
* Add 2,3 meters when using a 45 or 90 sprinkler
reducer.
TFP720
Page 5 of 8
FM - Design Criteria
UL - Design Criteria
6,7
3,0
3/4
8,5
4,9
1/2
9,8
4,9
3/4
11,6
7,0
1/2
12,5
6,1
3/4
14,6
7,6
1/2
14,9
7,0
3/4
16,5
8,5
18,3
7,9
20,4
9,8
20,4
10,1
22,6
11,6
700
1000
1200
1500
1/2
1800
3/4
* Information in this column indicates the maximum number of allowable bends and that hoses are installed with at least one bend.
TFP720
Page 6 of 8
Model
Type
Assembly
Length in
Millimeters
LPCB
VdS
FM
UL*
APSAD**
50 and 90 mm
Bar Fixing
Clamp
50 and 90 mm
Bar Fixing
Clamp
50 and 90 mm
Bar Fixing
Clamp
50 mm
Bar Fixing
Clamp
50 and 90 mm
Bar Fixing
Clamp
Sprinkler
Reducer Type
Sprinkler
Reducer Type
Sprinkler
Reducer Type
Sprinkler
Reducer Type
Sprinkler
Reducer Type
45
90
45
90
45
90
45
90
YN25-700
Un-braided
700
YN25-1000
Un-braided
1000
YN25-1200
Un-braided
1200
YN25-1500
Un-braided
1500
YN25-1800
Un-braided
1800
YN25-2000
Un-braided
2000
YN25-2500
Un-braided
2500
YN25-2700
Un-braided
2700
YN25-3100
Un-braided
3100
YN25-3700
Un-braided
3700
YB25-700
Braided
700
YB25-1000
Braided
1000
YB25-1200
Braided
1200
YB25-1500
Braided
1500
YB25-1800
Braided
1800
YB25-2000
Braided
2000
YB25-2500
Braided
2500
YB25-700
Braided-FM
700
YB25-1000
Braided-FM
1000
YB25-1200
Braided-FM
1200
YB25-1500
Braided-FM
1500
YB25-1800
Braided-FM
1800
YB28-700
Braided
700
YB28-1000
Braided
1000
YB28-1200
Braided
1200
YB28-1500
Braided
1500
YB28-1800
Braided
1800
YB28-2000
Braided
2000
YB28-2500
Braided
2500
YB28-700
Braided - FM
700
YB28-1000
Braided - FM
1000
YB28-1200
Braided - FM
1200
YB28-1500
Braided - FM
1500
YB28-1800
Braided - FM
1800
45
90
TABLE A
FASTFLEX SPRINKLER HOSE ASSEMBLY
MODELS, ASSEMBLY LENGTHS, AND APPROVALS
TFP720
Page 7 of 8
BRANCHLINE
FITTING
OUTLET
INLET
NIPPLE
ISO 7-R 1
OR ISO 7-R 1 1/4
THREADED END
PERMITTED
NOT PERMITTED
SLIP
NUT
FLEXIBLE
HOSE TO
SPRINKLER
MACHINE HOSE
THREADED
END
NOT PERMITTED
FIGURE 3
FASTFLEX FLEXIBLE SPRINKLER HOSE
INSTALLATION GUIDANCE
Installation
The TYCO FASTFLEX Flexible Sprinkler Hose as shown in Figure 1, must
be installed in accordance with this
section.
NOTICE
Flexible Hoses are intended only to
connect sprinklers directly to system
piping (Ref. Figure 1). Flexible Hoses
cannot be joined together to form
longer hoses. Joining Flexible Hoses
together creates an assembly with
unknown performance that has not
been accounted for in system calculations or safe product performance.
Step 1. Review the Design Criteria
section that applies to the Approval
agency recognized by the authority
having jurisdiction, as well as Figure 3
that provides installation guidance.
Step 2. Determine the approximate
place where the sprinkler will be
located. The Support Bar is 700 mm
long and shall be mounted on the
600 mm width of the ceiling grid. The
sprinkler should be located as close as
possible to the center of the distance
between ceiling grid T-bars.
Step 3. Slide the Reducer Bracket
onto the Support Bar. Loosely attach
the Reducer Bracket and the two Bar
Fixing Clamps on the Support Bar and
place the Bar Fixing Clamps such that
the Support Bar crosses the location
where the sprinkler will be located.
Step 4. Attach one end of the Flexible Hose onto the sprinkler reducer.
Applying the wrench to the Slip Nut,
and not to the Flexible Hose, tighten to
a maximum torque of 35 Nm.
TFP720
Page 8 of 8
MINIMUM
RADIUS
INDICATOR
MRI55
YN25
FLEXIBLE
HOSE
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N).
Flexible Hose Assembly
The FASTFLE X Flexible Hose
Assembly includes Flexible Hose,
ISO 7-R 1 x Hose Thread Inlet Nipple,
1/2" NPT x Hose Thread Straight Sprinkler Reducer, Reducer Bracket, Bar
Fixing Clamps, and Support Bar.
Note: Refer to Table A for Model, Type,
Length, Bar Fixing Clamp options, and
Approval details.
FIGURE 4
MINIMUM RADIUS INDICATOR
MRI55
Care and
Maintenance
The TYCO FASTFLEX Flexible Sprinkler
Hose must be maintained and serviced
in accordance with this section.
Before closing a fire protection system
control valve for inspection or maintenance work on the fire protection
system that it controls, permission to
shut down the effected fire protection
system must first be obtained from
the proper authorities and all personnel who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for monitoring proprietary and/or central station
alarms.
The owner is responsible for the inspection, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Inlet Nipple
Specify: (25 mm or 28 mm) hose thread
FASTFLEX Inlet Nipple with (ISO 7-R 1
or ISO 7-R 1 1/4) inlet thread connection, P/N (specify):
25 mm Hose Thread
ISO 7-R 1. . . . . . . . . . . . . . . . . . . HOSENIP25
ISO 7-R 1 1/4. . . . . . . . . . . . . . . HOSENIP25R
28 mm Hose Thread
ISO 7-R 1 HOSENIP28
ISO 7-R 1 1/4 HOSENIP28R
Sprinkler Reducer
Specify: (Straight, 45 Degree, or 90
Degree) for (25 mm or 28 mm hose
threads) FASTFLEX Sprinkler Reducer
with (ISO 7-Rc 3/8, 1/2 inch NPT, or 3/4
inch NPT) outlet thread connection,
P/N (specify):
Straight
25 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . . . PBR120
1/2 inch NPT . . . . . . . . . . . . . . . . . . . . RBR120
3/4 inch NPT . . . . . . . . . . . . . . . . . . . . SBR120
28 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . PBR28120
1/2 inch NPT . . . . . . . . . . . . . . . . . . RBR28120
3/4 inch NPT . . . . . . . . . . . . . . . . . . SBR28120
45 Degree
25 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . . PBAR45
1/2 inch NPT . . . . . . . . . . . . . . . . . . . RBAR45
3/4 inch NPT . . . . . . . . . . . . . . . . . . . SBAR45
28 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . PB28AR45
1/2 inch NPT . . . . . . . . . . . . . . . . . RB28AR45
3/4 inch NPT . . . . . . . . . . . . . . . . . SB28AR45
90 Degree
25 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . . PBAR90
1/2 inch NPT . . . . . . . . . . . . . . . . . . . RBAR90
3/4 inch NPT . . . . . . . . . . . . . . . . . . . SBAR90
28 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . PB28AR90
1/2 inch NPT . . . . . . . . . . . . . . . . . RB28AR90
3/4 inch NPT . . . . . . . . . . . . . . . . . SB28AR90
Worldwide
www.tyco-fire.com
Contacts
FASTFLEX
Model FB Flexible Braided Hose
General
Description
Technical
Data
Approvals
VdS Approved
Page 1 of 6
Design Criteria
The TYCO FASTFLEX Model FB Flexible Braided Hose is VdS Listed and
used with pendent sprinklers. The following paragraph provides the design
criteria unique to VdS Approval listing.
VdS Listing Design Criteria
Wet-pipe systems only
Minimum bend radius of 55 mm
Maximum service pressure of 16
bar
Pendent sprinklers with nominal
K57, K80, or K115
Maximum ambient temperature of
107C
MARCH 2015
TFP730
TFP730
Page 2 of 6
INTEGRATED
KNURLED AND
MALE THREADED
SWIVEL INLET
NIPPLE
BRAIDED
JACKET
FLEXIBLE
HOSE
BRANCHLINE
FITTING
(NOT INCLUDED)
SYSTEM
BRANCHLINE
BRANCHLINE
FITTING
ISO 7-R 1
THREADED
OUTLET
INTEGRATED
HEX SPRINKLER
REDUCER
600 mm
REDUCER
BRACKET WITH
SOCKET HEAD
SCREW
END BRACKET
WITH WING
SCREW, HEX
SCREW AND
LOCK WASHER
CEILING
GRID
T-BAR
DROP-IN
CEILING
PANEL
SUPPORT
BAR
SPRINKLER INSTALLED
IN ACCORDANCE WITH
MANUFACTURER'S
INSTRUCTIONS
FIGURE 1
FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE
ASSEMBLY AND TYPICAL INSTALLATION
Installation
T-Bar Bracket Application
The TYCO FASTFLEX Model FB
Flexible Braided Hose, as shown in
Figure 1, must be installed in accordance with this section.
NOTICE
TYCO Model FB Flexible Braided Hoses
are intended only to connect sprinklers
directly to system piping (Ref. Figure
1). Model FB Flexible Braided Hoses
cannot be joined together to form
longer hoses. Joining flexible hoses
together creates an assembly with
unknown performance that has not
been accounted for in system calculations or safe product performance.
TFP730
Page 3 of 6
RBF38T
GYPSUM END
BRACKET WITH
WING SCREW
SUPPORT BAR
GYPSUM CEILING
U-PROFILE SUPPORT
CHANNEL
FIGURE 2
FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE
GYPSUM CEILING INSTALLATION DETAIL
kler is properly located in accordance
with the manufacturers instructions.
If not in the proper location, adjust its
position as necessary.
Step 9. Once the sprinkler is in the
proper location, torque all hardware as
follows:
NOTE: The End Brackets Wing Screws
must be tightened before tightening the
Reducer Bracket to the Support Bar.
End Bracket
Hex Screws . . . . . . . . . . 4,5 Nm (min)
End Bracket
Wing Screws . . . . . . . . . 4,5 to 5,7 Nm
Reducer Bracket
Fastener . . . . . . . . . . . . . 2,3 Nm (min)
Installation
Gypsum End Bracket Application
THE TYCO FASTFLEX Model FB Flexible Braided Hose gypsum ceiling
installation, using the Gypsum End
Bracket RBF38T as shown in Figure 2,
must be installed in accordance with
this section.
NOTICE
TYCO Model FB Flexible Braided Hoses
are intended only to connect sprinklers
directly to system piping (Ref. Figure
1). Model FB Flexible Braided Hoses
cannot be joined together to form
longer hoses. Joining flexible hoses
together creates an assembly with
unknown performance that has not
been accounted for in system calculations or safe product performance.
Step 1. Review the Design Criteria
section that applies to the approval
agency recognized by the authority
having jurisdiction, as well as Figure 4
that provides Installation Guidance.
TFP730
Page 4 of 6
Model
Type
L
Nominal
Length
Maximum
Number of
Bends
FB25-700
Braided
700 mm
FB25-1000
Braided
1000 mm
FB25-1200
Braided
1200 mm
FB25-1500
Braided
1500 mm
FB25-2000
Braided
2000 mm
L
ISO 7-R 1
SWIVEL
INLET
NIPPLE
INNER
FLEXIBLE
HOSE
OUTER
BRAIDED
JACKET
STRAIGHT
SPRINKLER
REDUCER
1/2" NPT
or
3/4" NPT
L
ISO 7-R 1
SWIVEL
INLET
NIPPLE
INNER
FLEXIBLE
HOSE
OUTER
BRAIDED
JACKET
90
SPRINKLER
REDUCER
1/2" NPT
or
3/4" NPT
FIGURE 3
FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE ASSEMBLY
NOMINAL DIMENSIONS
Care and
Maintenance
The TYCO FASTFLEX Model FB Flexible Braided Hose must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
control valve for inspection or maintenance work on the fire protection
system that it controls, permission to
shut down the effected fire protection
system must first be obtained from
the proper authorities and all personnel who may be affected by this action
must be notified.
Inspection, testing, and maintenance
must be performed as indicated below
and in accordance with the local
requirements and/or national codes.
Any impairment must be immediately
corrected.
The owner is responsible for the inspection, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for monitoring proprietary and/or central station
alarms.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.
180 mm
TFP730
Page 5 of 6
PERMITTED
PERMITTED
NOT PERMITTED
NOT PERMITTED
Route the Model FB Flexible Braided Hose to permit the water to drain back into the branchline or through the
sprinkler reducer.
FIGURE 4
FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE
INSTALLATION GUIDANCE
Limited
Warranty
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N).
Flexible Hose Assembly*
*T he FASTFLEX Model FB Flexible
Braided Hose Assemblies includes the
following items:
- Flexible Braided Hose
- Inlet Nipple, ISO 7-R 1
- Sprinkler Reducer, 1/2" or 3/4" NPT,
Straight or Angled
- Reducer Bracket
- End Brackets
- Support Bar
Specify: FASTFLEX Model FB Flexible Braided Hose Model (specify,
Ref. Figure 3), (specified) length, and
(specify size, 50 or 90 mm) Bar Fixing
Clamps, P/N (specify):
With 1/2 inch Straight Reducer:
700 . . . . . . . . . . . . . . . . . . . . . . . . . .
1000 . . . . . . . . . . . . . . . . . . . . . . . . .
1200 . . . . . . . . . . . . . . . . . . . . . . . . .
1500 . . . . . . . . . . . . . . . . . . . . . . . . .
2000 . . . . . . . . . . . . . . . . . . . . . . . . .
FBS1250700
FBS1251000
FBS1251200
FBS1251500
FBS1252000
FBA1250700
FBA1251000
FBA1251200
FBA1251500
FBA1252000
End Bracket
Specify: FASTFLEX End Bracket,
P/N FENDBRA
Gypsum End Bracket
Specify: Gypsum End
P/N RBF38T
Bracket,
Support Bar
Specify: FASTFLEX Support Bar,
(specify) length, P/N (specify):
700 . . . . . . . . . . . . . . . . . . . . . . . . FSUPBAR0700
1000 . . . . . . . . . . . . . . . . . . . . . . . FSUPBAR1000
1300 . . . . . . . . . . . . . . . . . . . . . . . FSUPBAR1300
Reducer Bracket
Specify: FASTFLEX Reducer Bracket,
(specify) size, P/N (specify):
1/2". . . . . . . . . . . . . . . . . . . . . . . . . FREDBRA050
3/4" . . . . . . . . . . . . . . . . . . . . . . . . . FREDBRA075
TFP730
Page 6 of 6
Worldwide
www.tyco-fire.com
Contacts
Page 1 of 6
Type MV-R
Type MV-T
The owner is responsible for maintaining their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
FEBRUARY 2015
TFP809
TFP809
Page 2 of 6
47,6 mm
(1-7/8")
MV ORIFICE SIZE
AND REVERSE
ACTION CODE R
INDICATED ON
FRAME ARM
DEFLECTOR
55,6 mm
(2-3/16")
K-FACTOR AND
APPROVAL AGENCY
INDICATED ON
FRAME ARM
FRAME
65,1 mm
(2-9/16")
WRENCHING
AREA
1/2" NPT
SPLITTER
17,5 mm*
(11/16")
ORIFICE *
INSERT
STRAINER *
WITH NOMINAL
3,2 mm (1/8") DIA.
HOLES
* NOZZLES HAVING
ORIFICES SMALLER
THAN 9,5 mm (0.37")
DIAMETER INCLUDE
ORIFICE INSERT AND
STRAINER
11,1 mm (7/16")
NOMINAL MAKE-IN
FIGURE 1
TYPE MV-R REVERSE ACTION NOZZLE
ASSEMBLY AND NOMINAL DIMENSIONS
47,6 mm
(1-7/8")
MV ORIFICE
SIZE AND
TANK TOP CODE T
INDICATED ON
FRAME ARM
DEFLECTOR
55,6 mm
(2-3/16")
K-FACTOR AND
APPROVAL AGENCY
INDICATED ON
FRAME ARM
FRAME
65,1 mm
(2-9/16")
ORIFICE *
INSERT
WRENCHING
AREA
1/2" NPT
SPLITTER
17,5 mm*
(11/16")
STRAINER *
WITH NOMINAL
3,2 mm (1/8") DIA.
HOLES
* NOZZLES HAVING
ORIFICES SMALLER
THAN 9,5 mm (0.37")
DIAMETER INCLUDE
ORIFICE INSERT AND
STRAINER
11,1 mm (7/16")
NOMINAL MAKE-IN
FIGURE 2
TYPE MV-T TANK TOP
ASSEMBLY AND NOMINAL DIMENSIONS
Technical
Data
Approvals
MV-R, UL Listed and FM Approved
(refer to Table A)
MV-T, UL Listed and FM Approved
(refer to Table B)
Physical Characteristics
Type MV-R and MV-T Nozzles are comprised of components constructed
from: Stainless Steel, Brass & Leaded
Gunmetal LG2, Titanium, Aluminium
Bronze, SMO254, or Zeron 100.
TFP809
Page 3 of 6
Orifice
Size
Minimum
Diameter
mm
(Inches)
MV10R
5,15 (0.20)
K-factor
LPM/bar1/2
GPM/psi1/2
17,3
1.2
MV12R
5,40 (0.21)
18,7
1.3
MV15R
6,35 (0.25)
25,9
1.8
MV18R
6,80 (0.27)
28,8
2.0
MV19R
7,15 (0.28)
31,7
2.2
MV21R
7,70 (0.30)
36,0
2.5
MV25R
8,35 (0.33)
41,8
2.9
MV26R
8,80 (0.34)
44,6
3.1
MV30R
9,00 (0.35)
49,0
3.4
MV34R
9,60 (0.38)
59,0
4.1
MV47R
11,20 (0.44)
79,2
5.5
MV57R
12,60 (0.50)
100,8
7.0
Stainless
Steel
Brass
Titanium
Aluminium
Bronze
SMO254
Zeron 100
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
NOTES:
1. UL Listed
2. FM Approved
TABLE A
TYPE MV-R REVERSE ACTION NOZZLE
ORIFICE SIZES, DISCHARGE COEFFICIENTS, MATERIALS OF CONSTRUCTION, AND
LABORATORY LISTINGS AND APPROVALS
Orifice
Size
Minimum
Diameter
mm
(Inches)
MV10T
5,15 (0.20)
K-factor
LPM/bar1/2
GPM/psi1/2
17,3
1.2
1.3
MV12T
5,40 (0.21)
18,7
MV15T
6,35 (0.25)
25,9
1.8
MV18T
6,80 (0.27)
28,8
2.0
MV19T
7,15 (0.28)
31,7
2.2
MV21T
7,70 (0.30)
36,0
2.5
MV25T
8,35 (0.33)
41,8
2.9
MV26T
8,80 (0.34)
44,6
3.1
MV30T
9,00 (0.35)
49,0
3.4
MV34T
9,60 (0.38)
59,0
4.1
MV47T
11,20 (0.44)
79,2
5.5
MV57T
12,60 (0.50)
100,8
7.0
Stainless
Steel
Brass
Titanium
Aluminium
Bronze
SMO254
Zeron 100
NOTES:
1. UL Listed
TABLE B
TYPE MV-T TANK TOP NOZZLE
ORIFICE SIZES, DISCHARGE COEFFICIENTS, MATERIALS OF CONSTRUCTION, AND
LABORATORY LISTINGS AND APPROVALS
0,25
0,50
2
0,75
TFP809
Page 4 of 6
1,75
0
0,25
0,50
2
0,75
GRAPH A
TYPE MV-R REVERSE ACTION NOZZLE
SPRAY PROFILE
GRAPH B
TYPE MV-T TANK TOP NOZZLE
SPRAY PROFILE
Design
Criteria
Nozzle Placement
Where direct impingement of water
spray onto all of the protected surface
is required by the authority having jurisdiction, Type MV-R and MV-R Nozzles
are to be spaced and directed so that
their spray patterns will completely
cover the protected surface with the
minimum required average density.
Both MV-R and MV-T nozzles must be
installed at a maximum effective distance of 0,75 m (2.5 ft.) from the protected surface.
Type MV-R nozzles can be oriented at
any angle on pipe sprigs (refer to Figure
3).
Type MV-T nozzles must be oriented in
the upright position on pipe sprigs (refer
to Figure 4).
Spray Patterns
Spray patterns for MV-R and MV-T
nozzles are shown in Graphs A and B
and apply to discharge pressures of 1,4
(20 psi). Though the Maximum Working
Pressure is 12,1 bar (175 psi), discharge
pressures in excess of 4,1 bar (60 psi)
Installation
The Tyco Type MV-R and MV-T Nozzles
must be installed in accordance with
this section.
General Instructions
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a minimum-to-maximum torque of 9,5 to 19,0
Nm (7 to 14 ft.-lbs.). Higher levels of
torque can distort the nozzle Inlet with
consequent impairment of the nozzle.
Step 1. With pipe-thread sealant
applied to the pipe threads, handtighten the nozzle into the nozzle fitting.
Step 2. With reference to Figures 1 and
2, apply an appropriate size adjustable
Crescent wrench to the wrenching area
and tighten the nozzle into the nozzle
fitting.
TFP809
Page 5 of 6
Frequent visual inspections are recommended to be initially performed
for nozzles installed in potentially corrosive atmospheres to verify the integrity of the materials of construction and
finish as they may be affected by the
corrosive conditions present for a given
installation. Thereafter, annual inspections per NFPA 25 are required.
WATER
DISCHARGE
PIPE
SPRIG
Water spray fixed systems to fire protection service require regularly scheduled care and maintenance by trained
personnel.
TYPE MV-R
REVERSE ACTION
NOZZLE
(ORIENT AT
ANY ANGLE)
SUPPLY
PIPE
PROTECTED
SURFACE
FIGURE 3
TYPE MV-R REVERSE ACTION NOZZLE
TYPICAL INSTALLATION
TYPE MV-T
TANK TOP NOZZLE
(ORIENT UPRIGHT
ONLY)
WATER
DISCHARGE
PIPE
SPRIG
SUPPLY
PIPE
PROTECTED
SURFACE
FIGURE 4
TYPE MV-T TANK TOP NOZZLE
TYPICAL INSTALLATION
Care and
Maintenance
The Tyco Type MV-R and MV-T Nozzles
must be maintained and serviced in
accordance with this section.
Before closing a fire protection system
main control valve for maintenance work
on the fire protection system that it controls, obtain permission to shut down
the affected fire protection system from
the proper authorities and notify all per-
TFP809
Page 6 of 6
Material
Orifice
Size
Stainless
Steel
Brass &
Leaded
Gunmetal
LG2
Titanium
Aluminium
Bronze
SMO254
Zeron 100
28480Z
MV10R
28480
28383
28480T
28383AB
28480SMO
MV12R
28481
28384
28481T
28384AB
28481SMO
28481Z
MV15R
28482
28385
28482T
28385AB
28482SMO
28482Z
MV18R
28483
28386
28483T
28386AB
28483SMO
28483Z
MV19R
28484
28387
28484T
28387AB
28484SMO
28484Z
MV21R
28485
28388
28485T
28388AB
28485SMO
28485Z
MV25R
28486
28389
28486T
28389AB
28486SMO
28486Z
MV26R
28487
28390
28487T
28390AB
28487SMO
28487Z
MV30R
28488
28391
28488T
28391AB
28488SMO
28488Z
MV34R
28489
28392
28489T
28392AB
28489SMO
28489Z
MV47R
28490
28393
28490T
28393AB
28490SMO
28490Z
MV57R
28491
28394
28491T
28394AB
28491SMO
28491Z
TABLE C
TYPE MV-R REVERSE ACTION NOZZLE
PART NUMBERS
Material
Stainless
Steel
Brass &
Leaded
Gunmetal
LG2
Titanium
Aluminium
Bronze
SMO254
Zeron 100
MV10T
28492
28285
28492T
28285AB
28492SMO
28492Z
MV12T
28493
28281
28493T
28281AB
28493SMO
28493Z
MV15T
28494
28282
28494T
28282AB
28494SMO
28494Z
Orifice
Size
MV18T
28495
28283
28495T
28283AB
28495SMO
28495Z
MV19T
28496
28286
28496T
28286AB
28496SMO
28496Z
MV21T
28497
28287
28497T
28287AB
28497SMO
28497Z
MV25T
28498
28288
28498T
28288AB
28498SMO
28498Z
MV26T
28499
28289
28499T
28289AB
28499SMO
28499Z
MV30T
28500
28290
28500T
28290AB
28500SMO
28500Z
MV34T
28501
28291
28501T
28291AB
28501SMO
28501Z
MV47T
28502
28292
28502T
28292AB
28502SMO
28502Z
MV57T
28503
28293
28503T
28293AB
28503SMO
28503Z
TABLE D
TYPE MV-T TANK TOP NOZZLE
PART NUMBERS
Limited
Warranty
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).