To measure the 3- power in a balanced circuit, the method or main apparatus used here are 2
CTs and one Wattmeter. The details of the apparatus required for this measurement are as
follow:
1. Wattmeter 600V, 10A, UPF -> 1 no.
2. Ammeter (0-10)A MI -> 1 no.
3. Voltmeter (0-600)V MI -> 1 no.
4. Current Transformer (CT) 5/5A -> 2 no.
In this method the power absorbed in a 3- balanced circuit is measured using a single wattmeter
in conjunction with 2 CTs. Usually 2-Wattmeter method is used measure the 3- power for both
balanced and unbalanced load, but method like this requires only one wattmeter. The CTs used
for this method should be of 1:1 ratio.
The primaries are connected in series with the 2 phases. The secondaries are connected to the
current coil of wattmeter such that the difference in the two phase currents will flow through the
current coil. The wattmeter pressure coil is connected between the same two phases.
Any wattmeter measures the product of
Voltage across pressure coil
http://www.tech-wonders.com/2010/10/measurement-of-3-phase-power-using-2.html
1/3
5/15/2015
The circuit is assumed to be connected in star, for delta connection also the procedure is valid and
the wattmeter reads directly total power absorbed.
Procedure
1. Give the connections as per the circuit diagram.
2. Apply 415 V, 3-, 50Hz supply closing the TPST switch.
3. Vary the load in suitable steps.
4. At each load note down the wattmeter readings.
5. Tabulate the results. Expected example tabulated results are as follows:
S.No
VL
(Volts)
IL
(Amps)
Wattmeter Reading
(Watts)
Calculated (1.732VL I L
Cos)
1.
415
2.4
480 x 4 = 1920
1725.12
2.
415
600 x 4 = 2400
2156.2
Sharing is Fun!
Previous
Next
Leave a Reply
Your email address will not be published. Required fields are marked *
Name *
Email *
http://www.tech-wonders.com/2010/10/measurement-of-3-phase-power-using-2.html
2/3
5/15/2015
Website
Comment
Post Comment
Link List
Tech-Wonders.com Priv acy Policy
Tech-Wonders.com Disclaimer
http://www.tech-wonders.com/2010/10/measurement-of-3-phase-power-using-2.html
3/3