Professional Documents
Culture Documents
Chapter - 2 Transformers: 2.1 What Is A Transformer?
Chapter - 2 Transformers: 2.1 What Is A Transformer?
Chapter - 2 Transformers: 2.1 What Is A Transformer?
-2
Chapter
CHAPTER 2
TRANSFORMERS
2.1 What is a Transformer?
A device that transfer energy from one system to another. It can
accept energy at one voltage and deliver it at another voltage. It permits
electrical energy to be generated at relatively low voltages and transmitted
at high voltages and low currents, thus reducing line losses, and to be used
at safe voltages.
Transformer is a device which uses the phenomenon of Mutual
Induction to change the values of alternating voltages and currents. Main
advantages of AC transmission and distribution ease alternating voltage
can be increased or decreased by transformer. Losses are low & efficiency is
high.
Being static they have a long life and very stable . The range in size
from the miniature units used in electronics applications & to large power
size in power station. Principle of operation is the same for each.
2.2 TRANSFORMER CONSTRUCTION
(i)
Core
Transformer is consists of two electrical circuits linked by a common
Page 1 of 23
Chapter
(b)
Circuit symbol
Figure 2.1 Transformer construction
Windings
step
down
Insulation
Chapter
d
dt
volts
- Voltage ratio
N1/N2
if N2 is less than N1 then V2 is less than V1 and then the device is termed as
step down transformer. If N2 is greater than N1 then V2 is greater than V1
and then the device is termed as step up transformer.
when a load is connected across the secondary winding I2 flows. In an
ideal transformer losses are neglected and transformer is considered to be a
100 percent efficient. Hence
Input power = Output power or V1I1= V2I2
Page 3 of 23
Chapter
be the
frequency of the supply. The time for 1 cycle of the alternating flux is the
periodic time T, where T =(1/f ) seconds. The flux rises sinusoidally from zero
to its maximum value in (1/4) cycle, and the time for (1/4) cycle is (1/4f )
seconds. Hence,
the average rate of change of flux =
m
1
4f
= 4 f m Wb/s, and
each turn of
both primary and secondary windings. For a sine wave,
r.m.s. value
Form factor = ___________________ = 1.11
average value
Page 4 of 23
Hence
Chapter
--------
(1)
--------
(2)
Page 5 of 23
Chapter
hence a
Chapter
shown in Fig. 2.4. I0, shown at a phase angle 0 to V1, is the no-load current of
the transformer. The phasor sum of I1 and I0 gives the supply current I1 and
the phase angle between V1 and I1 is shown as 1.
Page 7 of 23
2.7
Chapter
REGULATION OF A TRANSFORMER
Regulation =
E2V 2
E2
X 100%
The fall in voltage, (E2 V2), is caused by the resistance and reactance
of the windings. Typical values of voltage regulation are about 3% in small
transformers and about 1% in large transformers.
2.8
Copper losses are variable and result in a heating of the conductors, due
to the fact that they possess resistance. If R1 and R2 are the primary and
secondary winding resistances then the
Total copper loss =
(b)
I12R1 +I22R2
Iron losses are constant for a given value of frequency and flux density
and are of two types hysteresis loss and eddy current loss.
(i) Hysteresis loss is the heating of the core as a result of the internal
molecular structure reversals which occur as the magnetic flux
alternates. The loss is proportional to the area of the hysteresis loop
and thus low loss nickel iron alloys are used for the core since their
hysteresis loops have small areas.
Page 8 of 23
Chapter
(ii) Eddy current loss is the heating of the core due to e.m.f.s being
induced not only in the transformer windings but also in the core.
These induced e.m.f.s set up circulating currents, called eddy currents.
Owing to the low resistance of the core, eddy currents can be quite
considerable and can cause a large power loss and excessive heating
of the core. Eddy current losses can be reduced by increasing the
resistivity of the core material or, more usually, by laminating the core
(i.e. splitting it into layers or leaves) when very thin layers of insulating
material can be inserted between each pair of laminations. This
increases the resistance of the eddy current
path, and reduces the value of the eddy current.
Transformer efficiency,
=
=1
losses
input power
TRANSFORMER TEST
OPEN CIRCUIT TEST
Page 9 of 23
Chapter
Page 10 of 23
Chapter
cos 0 = W / VI
Magnetizing current
Im = I0 sin 0
Ic = I0 cos 0
Reactance
Resistance
X0 = V1/ Im
R0 = V1/ Ic
(b)
Page 11 of 23
Chapter
Z01 = Vsc / I1
Ro1 = W / I12
X01 = (Z012 R012)
2.10 THREE PHASE TRANSFORMER
Three-phase double-wound transformers are mainly used in power
transmission and are usually of the core type. They basically consist of three
pairs of single phase windings mounted on one core, as shown in Fig. 21.17,
which gives a considerable saving in the amount of iron used. The primary
and secondary windings in Fig. 21.17 are wound on top of each other in the
form of concentric cylinders, similar to that shown in Fig. 21.6(a). The
windings may be with the primary delta-connected and the secondary starconnected, or star-delta, star-star or delta-delta, depending on its use.
Page 12 of 23
Chapter
Chapter
transformer. The latter shows that the secondary is actually part of the
primary, the current in the secondary being (I2 I1). Since the current is less
in this section, the cross-sectional area of the winding can be reduced, which
reduces the amount of material necessary. Figure 21.15 shows the circuit
diagram symbol for an auto transformer.
when starting
Page 14 of 23
Chapter
2. ISOLATING TRANSFORMERS
Transformers not only enable current or voltage to be transformed to
some different magnitude but provide a means of isolating electrically one
part of a circuit from another when there is no electrical connection between
primary and secondary windings. An isolating transformer is a 1:1 ratio
transformer with several important applications, including bathroom shaversockets, portable electric tools, model railways, and so on.
Page 15 of 23
Chapter
Chapter
is to have an
approximate e.m.f. per turn of 22V and operate with a maximum flux of
1.25T. Calculate (a) the number of primary and secondary turns, and
(b) the cross-sectional area of the core.
[(a) 150, 5 (b) 792.8 cm2]
PROBLEMS ON REGULATION
9. The open circuit voltage of a transformer is 240V. A tap changing
device is set to operate when the percentage regulation drops below
2.5%. Determine the load voltage at which the mechanism operates.
PROBLEMS ON EFFICIENCY
10.
In a 25KVA, 2000 / 200 V power transformer the iron and full load
Chapter
Chapter
volts
(d) E2 =1.11N2Bm a f
volts
2. A step-up transformer has a turns ratio of 10. If the output current is 5A,
the input
current is:
(a) 50A
(b) 5A
(c) 2.5A
(d) 0.5A
(b) 250
(d) 25
turns
5. A 1 kV/250V transformer has 500 turns on the secondary winding. The
number of turns
on the primary is:
(a) 2000
(b) 125
(c) 1000
(d) 250
windings
Page 19 of 23
Chapter
from occurring
7. The power input to a mains transformer is 200W. If the primary current is
2.5A, the secondary voltage is 2V and assuming no losses in the
transformer, the turns ratio is:
(a) 40:1 step down (b) 40:1 step up
(c) 80:1 step down (d) 80:1 step up
8. A transformer has 800 primary turns and 100 secondary turns. To obtain
40V from the secondary winding the voltage applied to the primary
winding must be:
(a) 5V
(b) 320V
(c) 2.5V
(d) 20V
(a) 81.3kW
(f) 4800
(k) 200W
(b) 800W
(g) 1.3kW
(l) 101.3kW
(c) 97.32%
(h) 98.40%
(d) 80kW
(i) 100kW
(e) 3
(j) 98.28%
(m) 96.38%
(n) 400W
10.
11.
12.
13.
14.
15.
16.
17.
Page 20 of 23
Chapter
(a) In an ideal transformer, the volts per turn are constant for a given
value of primary
voltage
(b) In a single-phase transformer, the hysteresis loss is proportional to
frequency
(c) A transformer whose secondary current is greater than the primary
current is a
step-up transformer
(d) In transformers, eddy current loss is reduced by laminating the core
18.
19.
(c) both eddy current and hysteresis losses (d) the resistance of the
primary and
Secondary
windings
20.
(b) 1 kohm
(d) 1m ohm
Page 21 of 23
Further
problems
on
the
transformer
Chapter
principle
of
operation
1. A transformer has 600 primary turns connectedto a 1.5 kV supply.
Determine the number of secondary turns for a 240V output voltage,
assuming no losses. [96]
2. An ideal transformer with a turns ratio of 2:9 is fed from a 220V supply.
Determine its output voltage. [990V]
3. A transformer has 800 primary turns and 2000 secondary turns. If the
primary voltage
is 160V, determine the secondary voltage assuming an ideal transformer.
[400V]
4. An ideal transformer with a turns ratio of 3:8 has an output voltage of
640V. Determine its input voltage. [240V]
5. An ideal transformer has a turns ratio of 12:1 and is supplied at 192V.
Calculate the
secondary voltage. [16V]
6. A transformer primary winding connected across a 415V supply has 750
turns. Determine how many turns must be wound on the secondary side
if an output of 1.66 kV is required. [3000 turns]
7. An ideal transformer has a turns ratio of 15:1 and is supplied at 180V
when the primary current is 4A. Calculate the secondary voltage and
current. [12V, 60A]
8. A step-down transformer having a turns ratio of 20:1 has a primary
voltage of 4 kV and a load of 10kW. Neglecting losses, calculate the value
of the secondary current. [50A]
9. A transformer has a primary to secondary turns ratio of 1:15. Calculate
the primary
voltage necessary to supply a 240V load. If the load current is 3A
determine the primary current. Neglect any losses. [16V, 45A]
10. A 10 kVA, single-phase transformer has a turns ratio of 12:1 and is
supplied from a
Page 22 of 23
Chapter
2.4 kV supply. Neglecting losses, determine (a) the full load secondary
current, (b) the
minimum value of load resistance which can be connected across the
secondary winding without the kVA rating being exceeded, and (c) the
primary current.
[(a) 50A (b) 4 (c) 4.17A]
11.
Page 23 of 23