Cqi 9 Errata AIAG

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

CQI-9 Special Process: Heat Treat System Assessment, 2nd Edition Errata Sheet

Page

Item #

Original Language (see BOLD)

Corrected Version Language (see highlight)

Section 3.5.5 Initial TUS

17

3.5.5

17

3.5.6

Section 3.5.6 Periodic TUS (For CQI-9,


Section 3.5.6 Periodic TUS (For CQI-9, a
a minimum of once per year periodic TUS
minimum of once per year periodic TUS is
is required)
required)
- Minimum and maximum temperature
Minimum and maximum temperature ranges shall
ranges shall be tested per AMS 2750D.
be tested per AMS 2750D. Exception: If the
Exception: If the operating range of the
operating range of the Qualified Work Zone is equal
Qualified Work Zone is equal to or less than
to or less than 170oC (306oF) then only one
o
o
85 C (153 F) then only one temperature is
temperature is required to be tested. The
required to be tested. The temperature
temperature shall be within the operating range of
shall be within the operating range of the
the Qualified Work Zone.
Qualified Work Zone.

43

A1.9

All hardness test equipment (for each scale


All hardness test equipment (for each scale used)
used) shall be calibrated semi-annually
shall be calibrated annually minimum, and verified
minimum, and verified daily minimum per
daily minimum per the applicable ASTM standard.
the applicable ASTM standard.

48

B1.7

54

C1.3

58

D1.2

62

E1.8

All hardness test equipment (for each scale


All hardness test equipment (for each scale used)
used) shall be calibrated semi-annually
shall be calibrated annually minimum, and verified
minimum, and verified daily minimum per
daily minimum per the applicable ASTM standard.
the applicable ASTM standard.

65

E4.2

Every 2 hours minimum

Section 3.5.5 Initial TUS


Minimum and maximum temperature
Minimum and maximum temperature ranges
ranges shall be tested per AMS 2750D.
shall be tested per AMS 2750D. Exception: If the
Exception: If the operating range of the
operating range of the Qualified Work Zone is
Qualified Work Zone is equal to or less
equal to or less than 170oC (306oF) then only
o
o
than 85 C (153 F) then only one
one temperature is required to be tested. The
temperature is required to be tested. The
temperature shall be within the operating range
temperature shall be within the operating
of the Qualified Work Zone.
range of the Qualified Work Zone.

All hardness test equipment (for each scale


All hardness test equipment (for each scale used)
used) shall be calibrated semi-annually
shall be calibrated annually minimum, and verified
minimum, and verified daily minimum per
daily minimum per the applicable ASTM standard.
the applicable ASTM standard.
All hardness test equipment (for each scale
All hardness test equipment (for each scale used)
used) shall be calibrated semi-annually
shall be calibrated annually minimum, and verified
minimum, and verified daily minimum per
daily minimum per the applicable ASTM standard.
the applicable ASTM standard.
All hardness test equipment (for each scale
All hardness test equipment (for each scale used)
used) shall be calibrated semi-annually
shall be calibrated annually minimum, and verified
minimum, and verified daily minimum per
daily minimum per the applicable ASTM standard.
the applicable ASTM standard.

Every 4 hours minimum

CLARIFICATION TO "GENERAL NOTES FOR AMS 2750D"


PAGES 16 & 17, CQI-09 2nd Edition
General Notes for AMS 2750D
AMS 2750D is referenced in the Pyrometry Section (Section 2.0) of the Process Tables. Heat treat suppliers
are not required to comply to all sections of AMS 2750D. Heat treat suppliers shall comply to the sections
of AMS 2750D that are given below. These sections reference thermocouples, the calibration of
thermocouples and instrumentation, and the procedure for conducting furnace temperature uniformity
surveys (TUS).
Thermocouples and Instrumentation
- Section 3.1 Temperature Sensors (Thermocouples)
- Section 3.2 Instrumentation - Note: Frequency reductions per AMS 2750D are not
allowed by CQI-9
Compliance to the following sections in 3.2, are not required by CQI-9
Section Number
3.2.5.1 & 2
3.2.5.3.1
3.2.5.5

Explanation
Temperature controlling instruments purchased prior to 1 year after
the release of AMS 2750D are exempt of 3.2.5.1 and 3.2.5.2.
One point sensor input is acceptable.
Sensitivity checks during calibration are not required.

CLARIFICATION TO "GENERAL NOTES FOR AMS 2750D"


PAGES 16 & 17, CQI-09 2nd Edition
System Accuracy Test (SAT) Procedure (Section 3.4)
NOTE: Refer to AMS 2750D as directed
-

SAT shall be performed by one of the two methods listed below:


1) Probe Method: The temperature indication of the furnace control instrument connected to the
control sensor (CS) shall be within +/- 5C (or +/- 10F) of the corrected temperature
indication of the test sensor (TS) on a test instrument. This test shall be performed monthly
at a typical operating temperature utilizing the procedures detailed in AMS 2750D Section
3.4.4, System Accuracy Test Procedure.
SAT Frequency:
o
o

Equipment operating at or above 760C (1400F) shall be checked monthly.


Equipment operating below 760C (1400F) shall be checked quarterly.

Example of Probe Method


Control Sensor
Over-Temp Sensor

Control Instrument

Part or Raw
Material
1500
1501

Lead Wire

Chart Recorder

Over Temp Test Sensor


Furnace Wall
Protection

Test Instrument

Furnace
Work Zone

B
Note: The test sensor can be a
resident thermocouple, refer to
AMS 2750 D section 3.4.4.2.1

EXAMPLE OF SYSTEM ACCURACY TEST (SAT)


CONTROL
INSTRUMENT
TEMPERATURE
INDICATION
(A)
o

900 C
(1652oF)

TEST
INSTRUMENT
TEMPERATURE
INDICATION
(B)
o

901.5 C
(1655oF)

TEST SENSOR
CORRECTION
FACTOR
(C)
o

-0.5 C
(-1.0oF)

TEST
INSTRUMENT
CORRECTION
FACTOR
(D)
o

+0.1 C
(+0.2oF)

TRUE TEST
TEMPERATURE

SAT
DIFFERENCE

(E)=(B)+(C)+(D)

(A) (E)
-1.1oC
(-2.2oF)

901.1 C
(1654.2oF)

CLARIFICATION TO "GENERAL NOTES FOR AMS 2750D"


PAGES 16 & 17, CQI-09 2nd Edition
2) Comparative Method: The relationship between the control system (sensor, leadwire, control
instrument) and any other permanently installed monitoring system such as over temperature
control system (sensor, leadwire, over temp instrument) or a load monitoring system (sensor,
leadwire, recording instrument) etc. at the time of the most recent conforming instrument
calibration test shall be established. This established relationship shall not differ by more
than +/-1C (or +/-2F) when checked weekly at a typical operating temperature.

Example of Comparative
Method
Control Instrument

Control Sensor
Over-Temp Sensor
Part or Raw
Material

1500
1501

Chart Recorder
Furnace
Work Zone
Over Temp
Protection

Furnace Wall

Other permanently installed thermocouple


(If utilized)

Note: It is strongly recommended that


the comparative check be performed at or near the original temperature
temperature

Any actions to correct a failing reading or validate a test result shall be documented.
Control Sensors (CS) failing to meet the requirements of SAT method 1 shall be changed. A
new TUS is not required unless the position of the control sensor changes. If new
thermocouple(s) are required in Test method 2, a new relationship must be established.

Thermocouple Replacement Schedule:


o
o
o
o

Base metal sensors (e.g. Type K, N, J, E) thermocouples shall be changed when needed
or annually at a minimum for equipment operating at or above 760C (1400F).
Base metal sensors (e.g. Type K, N, J, E) thermocouples shall be changed when needed
or every two years at a minimum for equipment operating below 760C (1400F).
Noble metal sensors (e.g. Type R and S) thermocouples shall be changed when needed
or every two years at a minimum for equipment operating at or above 760C (1400F).
Note: A new TUS is not required for any thermocouple replacement unless the position
of the control sensor(CS) is changed (CS)

CLARIFICATION TO "GENERAL NOTES FOR AMS 2750D"


PAGES 16 & 17, CQI-09 2nd Edition

Furnace Temperature Uniformity Survey (TUS)


o Section 3.5.2
Multiple Qualified Operating Temperature Ranges
o Section 3.5.3
Furnace Modifications
o Section 3.5.4
Furnace Repairs
o Section 3.5.5
Initial TUS

Section 3.5.6

o
o
o
o
o

o
o
o
o

Periodic TUS (For CQI-9, a minimum of once per year periodic


TUS is required)

Minimum and maximum temperature ranges shall be tested per AMS 2750D.
Exception: If the operating range of the Qualified Work Zone is equal to or less
than 170oC (306oF) then only one temperature is required to be tested. The
temperature shall be within the operating range of the Qualified Work Zone.

Section 3.5.8
Furnace Parameters During TUS
Section 3.5.9
Furnace Temperature at Insertion of TUS Sensors (Thermocouples)
Section 3.5.10 Load Condition
Section 3.5.11 Furnace Atmosphere During TUS
Section 3.5.13 Batch Furnaces, Salt Baths, Controlled Temperature Liquid Baths, and
Fluidized Bed Furnaces EXCEPT:

o
o

Minimum and maximum temperature ranges shall be tested per AMS 2750D.
Exception: If the operating range of the Qualified Work Zone is equal to or less
than 170oC (306oF) then only one temperature is required to be tested. The
temperature shall be within the operating range of the Qualified Work Zone.

3.5.13.3.2: CQI-9 requires that data from the TUS sensors is automatically
recorded.

Section 3.5.14 Continuous and Semi-Continuous Furnaces


Section 3.5.15 Alternative Testing Methods for Continuous and Semi-Continuous
Furnaces or Furnaces with Retorts or Muffles
Section 3.5.16 Temperature Uniformity Survey Sensor Failures
Section 3.5.18 Relocation of Hot or Cold Recording Sensors for Class A or C
Instrumentation
Section 3.5.20 Temperature Uniformity Survey Instrumentation
Section 3.5.21 Temperature Uniformity Survey Report

You might also like