Experiment of Shell & Tube Heat Exchanger
Experiment of Shell & Tube Heat Exchanger
ABSTRACT
The objective of this experiment is to study the function and the
working of shell and tube heat exchanger. For this experiment, countercurrent heat exchanger is used. In counter flow heat exchangers, the two
fluids flow against each other, maintaining a maximum temperature difference
between the hot and cold streams which allows for maximum heat transfer.
Heat transfer and log mean temperature difference (LMTD) are calculated. In
this experiment, we assume negligible heat transfer between the system and
its surroundings, negligible potential or kinetic energy changes, constant
specific heats, and that the fluids are not undergoing any phase change. In
this case, the heat transfer rate across a heat exchanger is usually expressed
in the form Q = mCp T. There were also calculation of Log Mean
Temperature Difference (LMTD) and the formula is :
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
The basic theory in this experiment is Qh=Qc, which the amount of heat
transfer is equal to the amount of heat absorb.
1.2
INTRODUCTION
Heat Exchangers are used to transfer heat from one fluid to another. The shell
and tube exchanger consists of a bundle of tubes with their axes parallel - much in
the manner of soda straws in a carton - but supported at various points by baffles at
right angles to the tube axes, which serve to keep the tubes fixed in space in a
particular configuration, for example, with the axes spaced on equilateral triangles, or
squares, etc. (Kessler & Greenkorn,1999).
Most processes require the heating or cooling of streams to produce a desired
temperature before the stream can be fed to operations. In any heat exchanger there
must be a fluid that requires a change in energy (heating or cooling) and a fluid that
can provide that energy change. One fluid is sent through a pipe on the inside of the
heat exchanger while the other fluid is sent through a pipe on the outside. In this
configuration, no mixing of the hot and cold fluids needs to take place. This is very
convenient for many processes, especially when product purity needs to be ensured.
This arrangement also allows for large quantities of heat to be transferred quickly,
and it is relatively easy to maintain consistent operating conditions.
There are three principle means of achieving heat transfer, conduction,
convection, and radiation. Heat exchangers run on the principles of convective and
conductive heat transfer. Radiation does occur in any process. However, in most
heat exchangers the amount of contribution from radiation is miniscule in comparison
to that of convection and conduction. Conduction occurs as the heat from the hot
fluid passes through the inner pipe wall. To maximize the heat transfer, the innerpipe wall should be thin and very conductive. However, the biggest contribution to
heat transfer is made through convection.
Heat exchangers are typically classified according to flow arrangement. In the
parallel-flow heat exchanger, the hot and cold fluids enter at the same end, flow in
the same direction, and leave at the same end. In the counter-flow arrangement, the
hot and cold fluids enter the heat exchanger at different ends and flow in opposite
directions. Each fluid arrangement leads to different heat rates and the calculations
are different accordingly (Incropera, DeWitt, Bergman & Lavine, 2007
Shell-Side
Inlet
Shell-Side Outlet
Tube-Side Inlet
Tube-Side
Outlet
For this experiment, counter-current heat exchanger is used. In counter flow heat
exchangers, the two fluids flow against each other, maintaining a maximum
temperature difference between the hot and cold streams which allows for maximum
heat transfer. Figure 4 shows how the counter-current heat exchanger works
Figure 4 : The flow of hot & cold water in counter-current heat exchanger
1.3
AIMS
1. To study the function and the working of shell and tube heat exchanger.
2. To calculate heat transfer and heat load with constant FT1.
3. To calculate Log Mean Temperature Difference (LMTD) with constant FT1.
4. To calculate heat transfer and heat load with constant FT2.
5. To calculate Log Mean Temperature Difference (LMTD) with constant FT2.
6. To study the working principle of counter flow heat exchanger.
7. To study the effect of fluid temperature on counter flow heat exchanger
performance.
8. To study the effect of fluid flow rated on heat exchanger performance.
1.4
THEORY
A heat exchanger is a piece of process equipment in which heat exchange
takes place between two fluids that enter and exit at different temperatures. The
primary design objective of the equipment may be either to remove heat from a hot
fluid or to add heat to a cold fluid. Depending upon the relative direction of fluid
motion, shell-and-tube heat exchangers are classified as parallel flow, counter flow,
cross flow.
In parallel flow, the hot and cold fluids flow in the same direction and
therefore enter the exchanger on the same end and exit the exchanger on the same
end. In counter flow, the two fluids flow in opposite directions and thus enter the
exchanger and exit the exchanger from opposite ends.
Figure 5 : Parallel and counter flow in Shell & Tube Heat Exchanger
The way that a heat exchanger works is hot water and cold water enter the
exchanger, where the process of cold water gaining some heat and the hot water
losing some takes place, before they both exit the exchanger. What is actually
happening is, the hot water is heating either the inside or the outside of the tubes in
the exchanger, depending on where it is flowing, by what is known as convection.
Then the heat is conducted through the tubes to the other side, either the
outside or the inside, where it is then convection back into the cold water raising its
temperature. Convection is a mode of heat transfer that involves motion of some
fluid that either absorbs heat from a source or gives heat to some surrounding.
For a heat exchanger that flows parallel or countercurrent then the coefficient
of heat transfer is called the overall coefficient of heat transfer. It is calculated using
the log mean temperature difference, which is found two different ways, depending
on whether the flow is parallel or counter. A heat exchanger is a device by which
thermal energy is transferred from one fluid to another. The types of heat exchangers
to be tested in this experiment is counter-flow cheat exchanger.
Heat exchangers transfer heat from one working fluid to another. For instance,
steam generators, feed water heaters, re heaters and condensers are all examples
of heat exchangers found in nuclear power systems. The important quantity in heat
exchanger analysis is the total rate of heat transfer between the hot and cold fluid.
Several different expressions for this heat transfer rate can be developed, relating
the heat transfer rate to quantities such as the inlet and outlet fluid temperatures and
the overall heat transfer coefficient. When these expressions are developed, care
must be taken to ensure that the appropriate mean temperature expressions are
used. Several assumptions can be made to simplify these expressions.
We assume negligible heat transfer between the system and its surroundings,
negligible potential or kinetic energy changes, constant specific heats, and that the
fluids are not undergoing any phase change. The basic theory in this experiment is
Qh=Qc, which the amount of heat transfer is equal to the amount of heat absorb. In
this case, the heat transfer rate across a heat exchanger is usually expressed in the
form Q = mCp T.
Qh
Efficiency =
Qc
= mh Cp T
= mc Cp T
QhQc
Qc
x 100
Qh
1.5
APPARATUS
The apparatus for this experiment is the HE158C Tube Heat Exchanger. This
apparatus has a tank with a heater inside to heat water to a specified temperature.
The temperature setting is adjusted at the thermostat on the front panel. Once the
water is heated to the desired temperature it is transferred by a water pump next to
the tank. On the pump there is a knob which varies the pump pressure. When using
a volumetric flow rate above 2 L/min the switch should be set to the highest
pressure. The hot water is pumped through a pipe to an insulated tube for which
heat will be exchanged. The actual heat exchange takes place in the insulated tubing
for which cold water flows concentricity around the hot water tube in two different
flow arrangements. These two arrangements, parallel and counter flow, can be
changed by opening and closing certain valves within the network of hot and cold
water tubing. Each flow arrangement is shown on a diagram located on the front
panel. It is worthwhile to note that the temperature at cold-in changes to temperature
at cold-out when a counter flow arrangement is used. The same situation applies to
the temperature at cold-out, which changes to temperature cold-in for the counter
flow. The other readings remain the same. The flow rates can be adjusted for both
cold and hot water by turning the valve knobs on the right side of the panel.
Thermometers are located at the inlet, exit and middle of the insulated heat
exchanger tubing for both hot and cold water.
1.6
PROCEDURE
1.7
RESULTS
FI 2
TT 1
TT 2
TT 3
TT 4
DPT 1
DPT 2
(LPM)
(LPM)
(0C)
(0C)
(0C)
(0C)
(mmH2O) (mmH2O)
10
2
43.5
30.4
47.5
49.2
97
18
10
4
39.2
30.1
47.0
49.7
103
23
10
6
36.8
29.5
46.3
49.7
100
65
10
8
35.0
29.9
45.6
48.9
91
130
10
10
34.7
30.5
44.8
48.9
92
190
Table 1 : Counter-current Shell & Tube Heat Exchanger with constant FI 1
FI 2
TT 1
TT 2
TT 3
TT 4
DPT 1
DPT 2
(LPM)
(LPM)
(0C)
(0C)
(0C)
(0C)
(mmH2O) (mmH2O)
2
10
31.9
30.4
37.8
48.7
5
195
4
10
32.5
30.5
42.9
48.8
5
194
6
10
33.4
30.5
44.1
49.1
5
193
8
10
34.3
30.6
44.5
49.7
60
192
10
10
35.0
30.8
45.4
49.8
82
191
Table 2 : Counter-current Shell & Tube Heat Exchanger with constant FI 2
1.8
CALCULATIONS
EXPERIMENT 1 :
1. Calculation On Heat Transfer and heat load (constant FT1) and Calculation of
Log Mean Temperature Difference (LMTD) :
L
min x
= 10.0
1 m3
1000 L
Qh
= mh Cp T
1 min
x 60 s
kg
x 988.18 m 3
J
kg.C
x 4175
(43.5-30.4) C
= 9007.67 W
= 2.0
L
min x
1 m3
1000 L
Qc
= mc Cp T
1 min
60 s
kg
x 995.67 m3
x 4183
J
kg .C
(49.2-47.5) C
= 236.01 W
QhQc
= 9007.67-236.01
= 8771.66 W
Efficiency
Qc
x 100
Qh
236.01
x 100
9007.67
= 2.62 %
( 43.549.2 )(30.447.5)
( 43.549.2)
(30.447.5)
= -10.38C
2. Calculation On Heat Transfer and heat load (constant FT1) and Calculation of
Log Mean Temperature Difference (LMTD) :
= 10.0
L
min x
1m
1000 L
Qh
= mh Cp T
kg
x 988.18 m3
1 min
60 s
x 4175
J
kg .C
x (39.2-
30.1) C
= 6257.24 W
= 4.0
L
min x
1m
1000 L
1 min
60 s
Qc
= mc Cp T
kg
x 995.67 m3
x 4183
J
kg .C
x (49.7-
47.0) C
= 749.67 W
QhQc
Efficiency
749.67
x 100
6257.24
Qc
x 100
Qh
= 11.98 %
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
( 39.249.7 )(30.147.0)
(39.249.7)
(30.147.0)
= -13.45C
3. Calculation On Heat Transfer and heat lost (constant FT1) and Calculation of Log
Mean Temperature Difference (LMTD) :
= 10.0
L
min x
1m
1000 L
Qh
= mh Cp T
kg
x 988.18 m3
1 min
60 s
x 4175
J
kg .C
x (36.8-
29.5) C
= 5019.54 W
= 6.0
L
min x
1m
1000 L
46.3) C
= 1416.06 W
QhQc
1 min
60 s
Qc
= mc Cp T
kg
x 995.67 m3
x 4183
J
kg .C
x (49.7-
= 3603.48 W
Efficiency
1416.06
x 100
5019.54
Qc
x 100
Qh
= 28.21 %
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
( 36.849.7 )( 29.546.3)
(36.849.7)
(29.546.3)
= -14.76C
4. Calculation On Heat Transfer and heat lost (constant FT1) and Calculation of Log
Mean Temperature Difference (LMTD) :
= 10.0
L
min x
1 m3
1000 L
Qh
1 min
60 s
= mh Cp T
kg
x 988.18 m3
29.9) C
= 3506.80 W
Qc
= mc Cp T
x 4175
J
kg .C
x (35.0-
= 8.0
L
min x
1m
1000 L
1 min
60 s
kg
x 995.67 m3
x 4183
J
kg .C
x (48.9-
45.6) C
= 1832.55 W
QhQc
Efficiency
1832.55
x 100
3506.80
Qc
x 100
Qh
= 52.28 %
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
( 35.048.9 )(29.945.6)
(35.048.9)
(29.945.6)
= -14.78C
5. Calculation On Heat Transfer and heat lost (constant FT1) and Calculation of Log
Mean Temperature Difference (LMTD) :
= 10.0
L
min x
1 m3
1000 L
Qh
1 min
60 s
= mh Cp T
kg
x 988.18 m3
x 4175
J
kg .C
x (34.7-
x 4183
J
kg .C
x (48.9-
30.5) C
= 2887.96 W
= 10.0
L
min x
1 m3
1000 L
Qc
1 min
60 s
= mc Cp T
kg
x 995.67 m3
44.8) C
= 2846.01 W
QhQc
Efficiency
2846.01
x 100
2887.96
Qc
x 100
Qh
= 98.75 %
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
( 34.748.9 )(30.544.8)
(34.748.9)
(30.544.8)
= -14.25C
EXPERIMENT 2 :
1. Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
Mean Temperature Difference (LMTD) :
= 2.0
L
min x
1m
1000 L
Qh
kg
x 988.18 m3
1 min
60 s
= mh Cp T
x 4175
J
kg .C
x (31.9-
30.4) C
= 206.28 W
= 10.0
L
min x
1 m3
1000 L
Qc
1 min
60 s
= mc Cp T
kg
x 995.67 m3
x 4183
J
kg .C
x (48.7-
37.8) C
= 7566.21 W
QhQc
Efficiency
7566.21
x 100
206.28
Qc
x 100
Qh
= 3667.93 %
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
( 31.948.7 )( 30.437.8)
(31.948.7)
(30.437.8)
= -11.46C
2. Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
Mean Temperature Difference (LMTD) :
= 4.0
L
min x
1 m3
1000 L
Qh
kg
x 988.18 m3
1 min
60 s
= mh Cp T
x 4175
J
kg .C
x (32.9-
30.5) C
= 660.10 W
= 10.0
L
min x
1m
1000 L
42.9) C
= 4095.47 W
QhQc
Qc
1 min
60 s
= mc Cp T
kg
x 995.67 m3
x 4183
J
kg .C
x (48.8-
Efficiency
Qc
x 100
Qh
4095.47
x 100
660.10
= 620.43 %
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
( 32.948.8 )(30.542.9)
(32.948.8)
(30.542.9)
= -14.08C
3. Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
Mean Temperature Difference (LMTD) :
= 6.0
L
min x
1 m3
1000 L
1 min
60 s
Qh
= mh Cp T
kg
x 988.18 m3
30.5) C
= 1196.44 W
Qc
= mc Cp T
x 4175
J
kg .C
x (33.4-
= 10.0
L
min x
1m
1000 L
1 min
60 s
kg
x 995.67 m3
x 4183
J
kg .C
x (49.1-
44.1) C
= 3470.74 W
QhQc
Efficiency
3470.74
x 100
1196.44
Qc
x 100
Qh
= 290.09 %
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
( 33.449.1 )(30.544.1)
(33.449.1)
(30.544.1)
= -14.62C
4. Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
Mean Temperature Difference (LMTD) :
= 8.0
L
min x
1 m3
1000 L
Qh
kg
x 988.18 m3
1 min
60 s
= mh Cp T
x 4175
J
kg .C
x (34.3-
30.6) C
= 2035.32 W
= 10.0
L
min x
1 m3
1000 L
Qc
1 min
60 s
= mc Cp T
kg
x 995.67 m3
x 4183
J
kg .C
x (49.7-
44.5) C
= 3609.57 W
QhQc
Efficiency
3609.57
x 100
2035.32
Qc
x 100
Qh
= 177.35 %
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
( 34.349.7 )(30.644.5)
(34.349.7)
(30.644.5)
= -14.63C
5. Calculation On Heat Transfer and heat lost (constant FT2) and Calculation of Log
Mean Temperature Difference (LMTD) :
= 10.0
L
min x
1m
1000 L
Qh
1 min
60 s
= mh Cp T
kg
x 988.18 m3
x 4175
J
kg .C
x (35.0-
x 4183
J
kg .C
x (49.8-
30.8) C
= 2887.95 W
= 10.0
L
min x
1 m3
1000 L
Qc
1 min
60 s
= mc Cp T
kg
x 995.67 m3
45.4) C
= 3054.25 W
QhQc
= 2887.95-3054.25 = -166.3 W
Efficiency
3054.25
x 100
2887.95
Qc
x 100
Qh
= 105.76 %
LMTD, TLM = [( Th,in Tc,out) (Th,out Tc,in)] / ln[( Th,in Tc,out) /( Th,out - Tc,in)]
( 35.049.8 )(30.845.4 )
(35.049.8)
(30.845.4)
= -14.70C
+ 2887.95
= 2971.1
1.9
DISCUSSIONS
In this experiment of shell and tube heat exchanger particular apparatus,
water is used as both the hot and cold fluid. The purpose of this heat exchanger is
to cool a hot stream. Cooling water flows through the outer pipe (the shell), and hot
water flows through the inner pipe on the inside. Heat transfer occurs in both
directions; the hot water is cooled, and the cooling water is heated. This
arrangement is called a shell-and-tube heat exchanger. There are many other
forms of heat exchangers; most notably, the double-pipe heat exchanger.
In this arrangement, a cold fluid flows through a pipe in the center of the
apparatus and is heated by a hot fluid on the outside of that pipe. The hot water used
in the shell-and-tube heat exchanger is produced by means of a double-pipe heat
exchanger. The discharge from the shell of the shell-and-tube heat exchanger is
circulated through the inner pipe of the double pipe heat exchanger. Low-pressure
steam condenses on the outside of the pipe, heating the water before it enters the
tubes of the shell-and-tube heat exchanger.
For this experiment, counter-current heat exchanger is used. In counter flow
heat exchangers, the two fluids flow against each other, maintaining a maximum
temperature difference between the hot and cold streams which allows for maximum
heat transfer.
In this experiment we are able to determine the value of heat load (Qh and
Qc) besides to calculate the LMTD. We assume negligible heat transfer between the
system and its surroundings, negligible potential or kinetic energy changes, constant
specific heats, and that the fluids are not undergoing any phase change. In this
case, the heat transfer rate across a heat exchanger is usually expressed in the form
Q = mCp T.
Qh
= mh Cp T
Qc
= mc Cp T
Efficiency =
QhQc
Qc
x 100
Qh
The basic theory in this experiment is Qh=Qc, which the amount of heat
transfer is equal to the amount of heat absorb. In this experiment, the value of Q h is
not the exact value as Qc because of some errors occur during this experiment. For
example, heat loss to the surroundings. Presently, the heat exchanger has no
insulation and the ambient room temperature has a large effect on the results
obtained in this experiment and the reading affects the calculations too.
1.10
CONCLUSION
The heat exchanger apparatus follows the basic laws of thermodynamics and
this can be shown experimentally. From the other experiments that hold flow rates
constant or vary the flow rates, it is clear that the First Law of Thermodynamics and
conservation of energy applies to the heat exchanger apparatus. The basic theory in
this experiment is Qh=Qc, which the amount of heat transfer is equal to the amount
of heat absorb. Although the value of Qh obtained in this experiment is slightly
different with Qc, this might due to some errors occur during this experiment and the
recommendations were made to improve this experiment.
1.11
RECOMMENDATIONS
For this experiment of shell and tube heat exchanger, it is recommended that
the heat exchanger be well insulated in order to reduce the heat loss to the
surroundings. Presently, the heat exchanger has no insulation and the ambient room
temperature has a large effect on the results obtained in this experiment.
Apart from that, the flowrate measure during this experiment must be taken
accurately. The eyes must be perpendicular to the scale of the flow meter so that the
readings will be more accurate.
During the experiment, it is recommended that the readings such as FT1,
FT2, DPT1, DPT2 and temperature must be taken when the system is stabilized and
reach its steady state. If the readings were taken when the system are not in
stabilized condition, error might be occur. Then this will affect the readings and also
the calculations.
Next, to improve the system of shell and tube heat exchanger, it is
recommended that the shell and tube heat exchanger have alert sign or alarm that
can give a sign to the engineer who handles the equipment to take the readings at
the correct time in order to get accurate readings. So that, this would help in
reducing the inaccuracy of the measurements in the future.
Lastly, the water to the tube side should be the first and last flow rate to be
turned on. The steam should be turned on only after the water is flowing through the
tube side and the water should be turned on only after the steam has been turned on
so that the tube and shell heat exchanger can operates more effectively.
1.12
REFERENCES
1) Kessler, D.P., Greenkorn, R.A. (1999). Momentum, Heat, and Mass Transfer
Fundamentals, New York : Marcel Dekker Inc., pp (768-828).
2) Holman, J.P. (1981), Heat Transfer, 5th Edition, New York : McGraw Hill, pp (437467).
3) http://www.ejbowman.co.uk/products/ShellandTubeHeatExchangers.html retrieved
on 4.4.2015.
4) http://www.alfalaval.com/about-us/our-company/key-technologies/heattransfer/shell-and-tube-heat-exchangers/pages/shell-and-tube-heat-exchanger.aspx
retrieved on 4.4.2015.
5) http://www.thermopedia.com/content/1121/ retrieved on 4.4.2015
6) McCabe, W.L., Smith, J.C., Marriott, P. (1985), Unit Operations of Chemical
Engineering, 4th Edition, McGraw-Hill.