U N D E R F LO O R H E AT I N G
UPONOR CONTROL SYSTEM
WIRED
Upon o r No rd i c T + 4 6 2 2 3 380 00
P O B ox 10 1 F + 4 6 2 2 3 381 01
SE-73 0 6 1 V i rs bo
3. Installation ....................................................................................................................................................... 6
6. Troubleshooting ............................................................................................................................................. 16
Technical constraints
WARNING
Risk of bodily injuries or squeezing. • Keep installation/data cables away from power
Non observance may harm health or cause cables > 50V to avoid interference.
damage to product components. • The electrical circuits of the boiler and the
CAUTION pump must be protected by a maximum
Important note on functionality. Non 6A circuit-breaker.
STOP
observance of this note may cause
malfunctions.
Information
Important operating advice and information.
99
See another page in the manual.
Heating/cooling.
Timer.
4 Underfloor Heating
2. The Uponor Control System
The Uponor Control System is a complete management for 2.2 Uponor Control System components
underfloor heating systems. Comfort, user-friendliness and
temperature control for each individual room of your home
can be combined through the use of thermostats or floor
temperature sensors.
4 Thermostat
Uponor
2 Fastening screws
Thermostat T-37
5 Thermostat for floor sensor
Uponor
2 Fastening screws
Thermostat T-33
6 Thermostat Public
Floor sensor for Thermostat
Uponor
Floor sensor 7 Public T-33 and Thermostat T-37
(option)
Uponor
8 Heating / cooling relay (option)
Relay
Uponor
9 Timer (option)
Mark Description Timer
1 Thermostat T-35
6 Underfloor Heating
3.3 Connections 3.3.2 Connect the actuators to the controller
99
See controller picture in fold-out. There are two non-polarized wires to connect the
thermostat.
12-channel controller
Mark Description
Heating
1 Com
Heating Heating/cooling
2 No timer control
1 Com Com
8 Underfloor Heating
3.3.3.1 Connection without Timer option 3.3.3.2 Connection with Timer option in Heating only mode
Connect thermostat and terminal: (Only 12-channel controller)
Example of an installation wired without Timer: One of the thermostat's two wires will always be
connected to the “Com” quick connector and the
second to one of the remaining three quick
connectors, depending on the mode selected
(non-polarized).
COMF
Thermostat #01 controls the actuator on channels 01a
ECO
and 01b and channels 02a and 02b.
night morning evening night
Thermostat #03 controls the actuator on channel 03 and
controls channel 04.
Thermostat #05 controls the actuator on channel 05 to
channel 11. • "Com" and "Zone 2" (allocate the thermostat to Zone 2):
Thermostat #12 controls channel 12. The corresponding channel will run in Comfort mode
according to the time slots in Zone 2 of the timer.
COMF
ECO
night morning evening night
• "Com" and "No timer": When the system is running in Zone 2 is not used in Heating mode when heating /
Heating mode: cooling is active.
The installation will work in a standard way with the
thermostats regulating each room according to their set
temperatures. One of the thermostat's two wires will always be
When the system is running in Cooling mode: connected to the “Com” quick connector and the
The installation will work in a standard way with the second to one of the remaining three quick
thermostats regulating each room according to their set connectors, depending on the mode selected
temperatures. (non-polarized).
• "Com" and Timer control: When the system is running in
Heating mode:
Example of an installation wired with a timer:
The corresponding channel will run in Comfort mode
according to the time slots in Zone 1 of the timer.
(for settings see timer manual)
COMF
ECO
night morning evening night
Specific
COMF
ECO
night morning evening night
10 Underfloor Heating
3.3.4 Installation of the options 3.3.4.3 Controller heating / cooling input
Different options can be added to the Uponor control system If your installation is equipped with a cooling unit, the Uponor
to enhance its features, optimize your comfort and save control system can be run through a heating / cooling relay.
energy.
The controller heating / cooling input operates with the
WARNING connection of a dry contact.
Mains supply 230VAC 50Hz
The contact's control can be either an additional regulation
Disconnect the 230V mains before installing or
system or a two-position switch.
changing the device wiring.
99
See wiring diagram in the fold-out.
See "3.5 Thermostat option", page 14 for more • The LED is green for Heating / Cooling mode.
99
information on wiring and setting.
See the floor sensor Manual for more information. Heating / Cooling mode is not available for the
6-channel controller.
Example of an installation:
WARNING
See the circulation pump supplier
documentation before performing the
connection.
12 Underfloor Heating
3.4 Thermostats 3.4.2 Mounting and wiring the thermostats
The Uponor Control System may be controlled with three
types of thermostats. 3.4.2.1 Location of a thermostat
3.5.1 Introduction
Thermostat Public T-33 and Thermostat T-37 allow a floor
sensor to be fitted to the system. The temperatures thus
measured ensure a more efficient management of the
system.
99
See: "3.3.3 Controller wiring", page: 8
14 Underfloor Heating
4. Finishing the installation 5. System maintenance
5.1 Controller current limitation
To avoid risk of current overload, the controller uses a
protection system:
The Power LED of the controller is lit up. The actuators are activated if there is demand for heating or cooling.
underfloor heating
system)
*: To find out if a problem is caused by the supply system or the control system. Check the temperatures of the flow and
return pipes for the loop(s) corresponding to the room. Loosen the corresponding actuator(s) from the manifold. If the loop
temperature starts to rise after a short while (a few minutes for the flow and longer for the return pipe, depending on the
floor type), the problem is most likely caused by the room control system. If the temperature remains the same, the
problem is in the system (hydraulic).
16 Underfloor Heating
12-CHANNEL CONTROLLER
Technical data
General
■ IP: IP20
Thermostat
■ CE marking:
■ Voltage: 6 V to 12 V
Controller
■ CE marking:
■ Pump relay output: 230VAC +10%/-15%, 250VA max. Only Dry contact
Run the thermostat cable in the clamp and tighten the screw to block
6 them
#1
Wiring diagram
Floor sensor
Yes 24V
Relay
No 230V
Yes
Pump
No
Yes
Timer
No
2 Underfloor Heating
UPONOR
U N D E R F LO O R H E AT I N G
UPONOR CONTROL SYSTEM
WIRED
Upon o r No rd i c T + 4 6 2 2 3 380 00
P O B ox 10 1 F + 4 6 2 2 3 381 01
SE-73 0 6 1 V i rs bo
3. Thermostat ...................................................................................................................................................... 7
Information
Important operating advice and information.
99
See another page in the manual.
4 Underfloor Heating
2. The Uponor Control System
The Uponor Control System is a complete management for
underfloor heating systems. Comfort, user-friendliness and
temperature control for each individual room of your home 1 Thermostat T-35 wired
can be combined through the use of thermostats or floor
temperature sensors.
Thermostat T-35 is easy to use.
Temperature settings are be adjusted with a
2.1 Overview of the system
dial.
The Uponor Control System consists of thermostats, a
The dial must be removed to set min/max on
controller and actuators. The controller manages the
the thermostat.
operation of the actuator when the thermostats detect a
The 21°C position is marked.
demand for heating or cooling.
Principle of operation:
As soon as the temperature measured at the thermostat is
lower than the desired set temperature, it sends this
information to the controller, which opens the actuators for
this room. Once the set temperature is reached, fresh
information is sent and the actuators are closed.
6 Underfloor Heating
3. Thermostat
Thermostat Public T-33
Thermostat T-35 and Thermostat T-37 Thermostat T-35 and Thermostat T-37
The blue and red cam set the lower and upper
ranges from which the set temperature is allowed to
deviate.
Example:
8 Underfloor Heating
3.3 Floor sensor settings 4. System maintenance
If your system includes a floor sensor, a potentiometer fitted
on the Thermostat Public T-33 and Thermostat T-37 allows Checks on your system components regularly to optimize
you to adjust the minimum or maximum temperature performance. This system requires no maintenance.
settings for the floor.
Automatic exercise function:
The floor sensor can be used for maximum or minimum
limitation of the floor temperature, regardless of the room The system is fitted with an automatic exercise function. Set
temperature. every 6 days +/- 24 hours, this function consists of a test-run
For example, the maximum limitation will protect a sensitive designed to prevent the pump and actuators from seizing up,
floor covering from exposure to too high temperature when when they have not been activated since the last test.
there is a high heat demand. The minimum limitation can
keep a tiled floor warm even when there is a no general
demand for heat supply to the room. Use a dry soft cloth to clean the Control System
STOP
and all it's components. Do not use any detergent.
The Power LED of the controller is lit up. The actuators are
activated if there is demand for heating or cooling.
WARNING
Note that some actions, e.g. actions involving 230V,
wiring, etc., are to be performed by a qualified
person.
WARNING
Risk of electric shocks. Disconnect the controller
from the mains prior to any intervention.
• Installation report.
10 Underfloor Heating
5.2 List of possible failures and solutions
12 Underfloor Heating