TECHNICAL GUIDE
Description
ASHRAE 90.1 COMPLIANT
R-410A
SERIES 10
J**ZH/ZR/XP
6-1/2 - 12-1/2 TON
60 Hertz
12-1/2 TON
349681-JTG-A-1007
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Component Location
Cooling With Gas Heat
Filter drier
(solid core)
Filter access
Disconnect location
(2 throw-away)
(optional disconnect switch)
Condenser section
Second model
nameplate
inside hinged
access panel
Dual stage
cooling for
maximum
comfort
Belt-drive
blower motor
Power ventor motor
Compressor #2
access (highefficiency
compressor
w/crankcase
heater)
Two-stage gas
heating to maintain
warm, comfortable
temperature
Intelligent control
board for safe and
efficient operation
Compressor #1 access
(high-efficiency compressor
w/crankcase heater)
349681-JTG-A-1007
Heat Pump
Unit control board w/screw
connectors for T-stat wiring
and network connection
Terminal block
for hi-voltage
connection
Disconnect location
(optional disconnect switch)
Filter access
(2 throw-away)
Condenser
section
Second Model
Nameplate Inside
Control Door
Belt-drive
blower
motor
Toolless
Door Latch
Compressor #1 Access
(High-Eff Compressor)
349681-JTG-A-1007
Nomenclature
Product Style
A = Style A
B = Style B
C = Style C
Product Category
SS Drain Pan
Johnson UNT 1126 Controller (N2 protocol), DFS, APS
Johnson Light Commercial Controls System (LCCS) Rtu Controller (Not offered on J**ZR units)
2" Pleated filters
BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)
Product Identifier
Shipping Bag
For valid combinations of the above; see the equipment price pages or
the Unitary Sales Tool program; all combinations are not available
Product Generation
Heat Type and Nominal Heat Capacity
4 = Fourth Generation
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
E09 = 9 KW
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
Installation Options
Airflow
A = Std. Motor
B = Std. Motor/Econo./Barometric Relief (Downflow
Only)
C = Std. Motor/Econo./Power Exhaust (Downflow Only)
D = Std. Motor/Motorized Damper (Downflow Only)
E = Std. Motor/Horizontal Economizer (No Baro.)
F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only)
N = Hi Static Mtr.
P = Hi Static Mtr./Econo./Barometric Relief
(Downflow Only)
Q = Hi Static Mtr./Econo./Power Exhaust
(Downflow Only)
R = Hi Static Mtr./Motorized Damper (Downflow Only)
S = Hi Static Mtr./Horizontal Economizer (No Baro.)
T = Hi Static Mtr./Slab Econo./Power Exhaust
(Downflow Only)
U = Hi Static Mtr./Slab Econo./Barometric Relief
(Downflow only)
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
349681-JTG-A-1007
349681-JTG-A-1007
Flexible Placement All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
To further simplify planning and installation, J**ZH/ZR/XP
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24
on-center joists or between 48 on-center joists.
The drain pan can be rotated to drain to either the front or
the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
Full Perimeter Base Rails The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
Easy Installation Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the unit.
A clearly identified location is provided to mount a field
supplied electrical disconnect switch. Utility connections can
be made quickly and with a minimum amount of field labor.
All units are shipped with 2 throw-away filters installed.
Wide Range of Indoor Airflows All indoor fan motors
are belt-drive type providing maximum flexibility to handle
most airflow requirements. For high static applications,
factory installed alternate indoor fan motors are available.
With the optional indoor fan motor, all units can supply
nominal airflow at a minimum of 1.5 ESP.
Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10year warranty.
349681-JTG-A-1007
Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
Electric Heaters - The electric heaters range from 9kW to
54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to the unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with cover,
on the corner of the unit housing adjacent to the
compressors. The Non-powered option requires the
installer to provide the 120V single-phase power source and
wiring. The Powered option is powered by a stepdown
transformer in the unit. Factory installed option only.
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
Control Options
Johnson Light Commercial System (LCCS) - Provides
rooftop system integration for LCCS single zone, changeover bypass and VAV systems. (Not offered on J**ZR units)
Johnson UNT 1126 Rooftop Controller - N2 protocol
with air proving and dirty filter sensors. Hardware contains
generic application logic; field engineering and/or
modification may be required.
349681-JTG-A-1007
Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
Power Exhaust - This accessory installs in the unit with a
down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a
horizontal flow application.
Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
-60F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
349681-JTG-A-1007
Accessories
Part Number
1RC0470
1RC0471
1RC0472
1BD0408
2TP04520925
2TP04521825
2TP04522425
2TP04523625
2TP04525425
2TP04520946
2TP04521846
2TP04522446
2TP04523646
2TP04525446
2TP04520958
2TP04521858
2TP04522458
2TP04523658
2TP04525458
2TP04540925
2TP04541825
2TP04542425
2TP04543625
2TP04540946
2TP04541846
2TP04542446
2TP04543646
2TP04540958
2TP04541858
2TP04542458
2TP04543658
1FA0413
1FA0414
2MD04702724
2MD04703324
2EE04705424
2EE04705524
2EE04705224
2EE04705624
2PE04703225
2PE04703246
2PE04703258
2EC04700924
1EH0407
1RD0411
1EH0408
1EH0409
2AQ04700424
2AQ04700324
2SD04700424
2MK04700624
1CG0419
1CG0420
1CG0424
1CG0425
1CG0427
1CG0428
Description
Roof Curb, 8" Height
Roof Curb, 14" Height
Roof Curb, Transition (7.5 T through 12.5 T)
Burglar Bars, Downflow
Electric Heat 9kW 230V
Electric Heat 18kW 230V
Electric Heat 24kW 230V
Electric Heat 36kW 230V
Electric Heat 54kW 230V
Electric Heat 9kW 460V
Electric Heat 18kW 460V
Electric Heat 24kW 460V
Electric Heat 36kW 460V
Electric Heat 54kW 460V
Electric Heat 9kW 575V
Electric Heat 18kW 575V
Electric Heat 24kW 575V
Electric Heat 36kW 575V
Electric Heat 54kW 575V
Electric Heat 9kW 230V, 42" Tall Cabinet
Electric Heat 18kW 230V, 42" Tall Cabinet
Electric Heat 24kW 230V, 42" Tall Cabinet
Electric Heat 36kW 230V, 42" Tall Cabinet
Electric Heat 9kW 460V, 42" Tall Cabinet
Electric Heat 18kW 460V, 42" Tall Cabinet
Electric Heat 24kW 460V, 42" Tall Cabinet
Electric Heat 36kW 460V, 42" Tall Cabinet
Electric Heat 9kW 575V, 42" Tall Cabinet
Electric Heat 18kW 575V, 42" Tall Cabinet
Electric Heat 24kW 575V, 42" Tall Cabinet
Electric Heat 36kW 575V, 42" Tall Cabinet
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)
Economizer, Downflow (Incl. Barometric Relief & All Hoods)
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)
"Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet
Power Exhaust, Downflow, 230V (For Units with Economizer only)
Power Exhaust, Downflow, 460V(For Units with Economizer only)
Power Exhaust, Downflow, 580V (For Units with Economizer only)
Dual Enthalpy Control (Use with Single Enthalpy Economizer)
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)
Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)
CO2 Detector Unit Mount
CO2 Detector Space Mount
Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)
Low Limit / Compressor Lockout Kit
Coil Guard (Electric / Electric & HP models), 8-1/2 and 10 Ton
Coil Guard (Gas / Electric models), 8-1/2 and 10 Ton
Coil Guard (Electric / Electric and HP models), 12-1/2 Ton
Coil Guard (Gas / Electric models), 12-1/2 Ton
Coil Guard (Electric / Electric & HP Models), 6-1/2 and 7-1/2 Ton
Coil Guard (Gas / Electric Models), 6-1/2 and 7-1/2 Ton
349681-JTG-A-1007
Accessories (Continued)
Part Number
1HG0411
1HG0415
1GP0405
1NP0442
1HA0442
1HA0443
1FE0412
2BC04700106
2BC04700151
2BC04700154
1FL0402
1FL0423
2DF0401
1FF0410
1FF0411
Description
Hail Guard Kit
Hail Guard Kit, 42" Tall Cabinet
Gas Piping Kit
Propane Conversion Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
Flue Exhaust Extension Kit
Gas Heat Kit, -60 deg F, 230V
Gas Heat Kit, -60 deg F, 460V
Gas Heat Kit, -60 deg F, 575V
Permanent Filter Kit
Permanent Filter Kit, 42" Tall Cabinet
Dirty Filter Switch
Filter Frame Kit, Metal
Metal Filter Frame Kit, 42" Tall Cabinet
Guide Specifications
GENERAL
Units shall be manufactured by Johnson Controls in an ISO
9001 certified facility. Series 10 J**ZH/ZR/XP units are
convertible single packages with a common footprint cabinet
and common roof curb for all 6-1/2 through 12-1/2 ton models.
All units have two compressors with independent R-410a
refrigeration circuits to provide 2 stages of cooling. The units
were designed for light commercial applications and can be
easily installed on a roof curb, slab, or frame. All units are selfcontained and assembled on rigid full perimeter base rails
allowing for 3-way forklift access and overhead rigging. Every
unit is completely charged with R-410a, wired, piped, and
tested at the factory to provide a quick and easy field
installation. All units are convertible between side and down
airflow. Independent economizer designs are used on side and
down discharge applications, as well as all tonnage sizes.
Units are available in the following configurations: cooling only,
cooling with electric heat, cooling with gas heat, heat pump,
and heat pump with electric heat. Electric heaters are available
as factory-installed options or field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec, Gas/
Elec), designed for outdoor installation. They shall have built in
field convertible duct connections for down discharge supply/return
or horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410a refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and ARI test procedures. Units shall
be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of a combination of G60 and
G90 galvanized steel, with exterior surfaces coated with a non-
10
349681-JTG-A-1007
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or
10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
b. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice
expansion devices.
or
thermally
operated
11
349681-JTG-A-1007
STANDARD LIMITED WARRANTIES - Compressor 5 Years,
Heat Exchanger 10 Years, Elect. Heat Elem. 5 Years,
Parts 1 Year
12
349681-JTG-A-1007
NORMAL MODE
"ALTERNATE MODE
When the reheat control board (RCB) detects a need for dehumidification (24VAC) at "HUM" via the field supplied dehumidistat connected to RHTB-1 and RHTB-2 and there is not a call for
cooling, it energizes the hot gas relay (HGR), which energizes
the 3-way valve (SOL 3), the condenser coil valve (SOL 2), and
de-energizes the reheat coil bleed valve (SOL 1). (In the
J12ZR, SOL 2 is only energized when the discharge pressure in
circuit #1 rises above 400 psig and de-energizes SOL 2 after
the discharge pressure falls below 320 psig. Both outdoor fans
of circuit #1 in the J12ZR also disengage to conserve energy.)
The Y1 signal is passed to the unit control board (UCB), which
engages circuit # 1, resulting in circuit #1 reheat mode operation.
When the room thermostat calls for first stage cooling, with or
without a call for dehumidification, the RCB senses a signal
through "Y1", de-energizing the HGR, which de-energizes SOL
3 and SOL 2 and energizes SOL 1, engaging circuit #1, resulting in circuit #1 cooling mode operation.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" & "Y2" and engages circuit
#1 and circuit #2 in cooling mode.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not
operate in the reheat mode, even if there is a call for dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call
for heating.
When the room thermostat calls for first stage cooling while
there is still a call for dehumidification, no operational change is
made. The call for cooling is ignored and the unit continues to
operate with circuit #1 in reheat mode and circuit #2 in cooling
mode.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" and "Y2" and de-energizes
the HGR, which de-energizes SOL 3 and SOL 2, and energizes
SOL 1. Both circuits operate in the cooling mode.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not
operate in the reheat mode, even if there is still a call for dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call
for heating.
All safety devices function as previously described.
13
349681-JTG-A-1007
Reheat Control Board
R
Y1
P4
Y2
K1
G
W1
K2
W2
OCC
K4
K3
COM
P6
P5
P3
HGRR
HGR
MODE
SELECTION
JUMPER
14
HUM
DEHUMIDISTAT
HARNESS
CONNECTION
349681-JTG-A-1007
Physical Data
J06 thru 12 ZH Physical Data
Models
Component
J06ZH
J07ZH
J08ZH
J10ZH
J12ZH
6.5
7.5
8.5
10
12.5
79000
93000
106000
126000
156000
76000
90000
102000
122000
150000
EER
11.4
11.4
11.5
11.5
11.2
SEER
IPLV
12.7
12.4
12.4
12.1
12.7
Nominal CFM
2600
3000
3400
4000
5000
6.67
7.90
8.87
10.61
13.40
R-410a
R-410a
R-410a
R-410a
R-410a
System 1
9-4
8-8
11-8
11-8
19-8
System 2
6-0
8-4
11-0
11-8
19-8
Nominal Tonnage
ARI COOLING PERFORMANCE
Refrigerant type
Refrigerant charge (lb-oz)
10
15
10
15
10
15
15
20
15
20
120
180
120
180
120
180
180
240
180
240
96
144
96
144
96
144
144
192
144
192
80
80
80
80
80
80
80
80
80
80
No. burners
No. stages
20-50
35-65
15-45
30-60
10-40
25-55
20-50
35-65
10-40
25-55
165
165
165
165
215
195
195
160
195
160
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
AFUE %
DIMENSIONS (inches)
Length
89
89
89
89
Width
59
59
59
59
59
Height
42
42
50-3/4
50-3/4
50-3/4
900
920
1135
1135
1400
Scroll
Scroll
Scroll
Scroll
Scroll
119-7/16
COMPRESSORS
Type
Quantity
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
23.8
23.8
29.0
29.0
47.5
Rows
2/1
20
20
20
20
15
3/8
3/8
3/8
3/8
3/8
Split-face
Split-face
Split-face
Split-face
Split-face
13.2
10.6
10.6
13.2
13.2
Rows
15
15
15
15
15
Tube diameter
0.375
0.375
0.375
0.375
0.375
Circuitry Type
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
Refrigerant control
15
349681-JTG-A-1007
J06 thru 12 ZH Physical Data (Continued)
Models
Component
J06ZH
J07ZH
J08ZH
J10ZH
J12ZH
6.5
7.5
8.5
10
12.5
Nominal Tonnage
CONDENSER FAN DATA
Quantity
Fan diameter (Inch)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
No. speeds
Number of motors
1/3
1/3
3/4
3/4
1/3
Motor HP each
RPM
850
850
1110
1110
850
6800
6800
8800
8800
14000
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
1-1/2
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
Quantity - Size
16
4 - 25 x 16 x 2
4 - 25 x 16 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
349681-JTG-A-1007
Component
J06ZR
J07ZR
J08ZR
J10ZR
J12ZR
6.5
7.5
8.5
10
12.5
80000
91000
106000
125000
156000
78000
88000
102000
120000
150000
11.2
11.2
11.2
11.2
11.2
SEER
IPLV
13.0
12.3
12.3
12.3
12.7
Nominal CFM
2600
3000
3400
4000
5000
6.96
7.86
9.11
10.71
13.39
R-410a
R-410a
R-410a
R-410a
R-410a
System 1
9-0
9-12
11-8
12-0
18-8
System 2
5-8
8-8
11-0
10-8
18-8
Nominal Tonnage
ARI COOLING PERFORMANCE
EER
Refrigerant type
Refrigerant charge (lb-oz)
10
15
10
15
10
15
15
20
15
20
120
180
120
180
120
180
180
240
180
240
96
144
96
144
96
144
144
192
144
192
80
80
80
80
80
80
80
80
80
80
No. burners
No. stages
20-50
35-65
15-45
30-60
10-40
25-55
20-50
35-65
10-40
25-55
165
165
165
165
215
195
195
160
195
160
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
AFUE %
DIMENSIONS (inches)
Length
89
89
89
89
Width
59
59
59
59
59
Height
42
42
50-3/4
50-3/4
50-3/4
965
965
1200
1200
1465
Scroll
Scroll
Scroll
Scroll
Scroll
119-7/16
COMPRESSORS
Type
Quantity
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
23.8
23.8
29.0
29.0
47.5
Rows
2/1
20
20
20
20
15
3/8
3/8
3/8
3/8
3/8
Split-face
Split-face
Split-face
Split-face
Split-face
13.2
10.6
10.6
13.2
13.2
Rows
15
15
15
15
15
Tube diameter
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
Refrigerant control
17
349681-JTG-A-1007
J06 thru 12 ZR Physical Data (Continued)
Models
Component
J06ZR
J07ZR
J08ZR
J10ZR
J12ZR
6.5
7.5
8.5
10
12.5
Nominal Tonnage
CONDENSER FAN DATA
Quantity
Fan diameter (Inch)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
No. speeds
Number of motors
1/3
1/3
1/3
1/3
1/3
Motor HP each
RPM
850
850
850
850
850
6800
6800
6800
6800
14000
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
1-1/2
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
Quantity - Size
18
4 - 25 x 16 x 2
4 - 25 x 16 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
349681-JTG-A-1007
Models
J06XP
J07XP
J08XP
J10XP
J12XP
6.5
7.5
8.5
10
12.5
80000
95000
104000
122000
156000
78000
92000
100000
118000
150000
EER
11.0
11.0
11.0
11.0
11.0
SEER
IPLV
12.4
12.4
12.4
12.4
11.9
Nominal CFM
2600
3000
3400
4000
5000
7.10
8.35
9.10
10.70
13.60
R-410a
R-410a
R-410a
R-410a
R-410a
System 1
9-0
9-8
13-8
14-0
16-0
System 2
9-4
9-0
13-0
14-0
16-0
78.0
92.0
94.0
110.0
144.0
6.5 / 3.50
7.6 / 3.50
7.8 / 3.50
9.2 / 3.50
13.2 / 3.20
48.0
55.0
57.0
66.0
90.0
6.2 / 2.30
7.0 / 2.30
7.3 / 2.30
8.3 / 2.30
11.9 / 2.20
Length
89
89
89
89
119-7/16
Width
59
59
59
59
59
Height
42
42
50-3/4
50-3/4
50-3/4
920
920
1135
1135
1400
Scroll
Scroll
Scroll
Scroll
Scroll
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
23.8
23.8
29.0
29.0
47.5
Nominal Tonnage
ARI COOLING PERFORMANCE
Refrigerant type
Refrigerant charge (lb-oz)
HSPF (Btu/Watts-hr)
DIMENSIONS (inches)
20
20
20
20
15
3/8
3/8
3/8
3/8
3/8
Split-face
Split-face
Split-face
Split-face
Split-face
13.2
Circuitry Type
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.6
10.6
13.2
13.2
Rows
15
15
15
15
15
Tube diameter
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
Refrigerant control
19
349681-JTG-A-1007
J06 thru 12 XP Physical Data (Continued)
Models
Component
J06XP
J07XP
J08XP
J10XP
J12XP
6.5
7.5
8.5
10
12.5
Nominal Tonnage
CONDENSER FAN DATA
Quantity
Fan diameter (Inch)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
No. speeds
Number of motors
1/3
1/3
1/3
1/3
1/3
Motor HP each
RPM
850
850
850
850
850
6800
6800
6800
6800
14000
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
1-1/2
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
Quantity - Size
4 - 25 x 16 x 2
4 - 25 x 16 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
4 - 25 x 20 x 2
J06
(6.5)
J07
(7.5)
J08
(8.5)
J10
(10)
J12
(12.5)
20
Model
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
Unit Voltage
Applied Voltage
Outdoor DB Temp
Min
Max
Max (F)
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
349681-JTG-A-1007
Capacity Performance
J06 thru 12 ZH Cooling Capacities
J06ZH (6.5 Ton)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
100.5
91.5
82.5
78.1
104.3
95.0
85.6
81.0
78.6
108.0
98.4
88.7
83.9
81.4
111.8
101.8
91.8
86.8
84.3
104.1
93.8
88.7
86.2
106.3
95.9
90.6
88.1
4.5
4.5
4.4
4.4
4.6
4.5
4.5
4.5
4.5
4.6
4.6
4.5
4.5
4.5
4.6
4.6
4.6
4.5
4.6
4.6
4.6
4.5
4.6
4.6
4.6
4.6
4.6
42.8
53.4
63.9
78.1
46.3
59.4
72.5
81.0
78.6
49.7
65.4
81.1
83.9
81.4
53.2
71.5
89.7
86.8
84.3
76.6
92.8
88.7
86.2
81.7
95.9
90.6
88.1
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
89.1
80.8
72.5
67.9
91.7
83.1
74.6
69.9
72.2
94.2
85.5
76.7
71.8
74.2
96.8
87.8
78.8
73.8
76.3
89.5
80.3
75.2
77.8
91.3
81.9
76.7
79.3
5.9
5.9
5.8
5.8
5.9
5.9
5.8
5.8
5.8
5.9
5.9
5.8
5.8
5.8
5.9
5.9
5.8
5.8
5.8
5.9
5.8
5.8
5.8
5.9
5.8
5.8
5.8
36.5
49.3
62.1
67.9
42.3
55.0
67.7
69.9
72.2
48.2
60.7
73.2
71.8
74.2
54.1
66.4
78.8
73.8
76.3
72.0
80.3
75.2
77.8
77.6
81.9
76.7
79.3
90
39.6
51.3
63.0
73.0
44.3
57.2
70.1
75.4
75.4
49.0
63.1
77.2
77.9
77.8
53.6
68.9
84.2
80.3
80.3
74.3
86.6
82.0
82.0
79.7
88.9
83.7
83.7
31.8
46.5
61.2
62.2
39.9
52.4
64.8
63.9
66.6
48.1
58.2
68.4
65.6
68.4
56.2
64.1
72.0
67.3
70.2
69.4
73.2
68.4
71.4
74.6
74.4
69.5
72.5
65
35.7
38.6
39.5
41.4
42.5
44.3
45.4
44.5
45.1
44.7
44.7
29.1
30.6
30.6
32.1
32.0
33.6
33.5
31.6
33.1
29.6
32.6
21
349681-JTG-A-1007
J06ZH (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
75.4
68.0
60.5
56.4
77.4
69.7
62.1
57.8
61.0
79.3
71.5
63.7
59.3
62.6
81.3
73.3
65.3
60.8
64.1
74.2
66.1
61.5
64.9
75.1
66.9
62.3
65.7
7.9
7.6
7.3
7.2
7.9
7.6
7.3
7.3
7.2
7.9
7.6
7.3
7.3
7.2
8.0
7.6
7.3
7.3
7.3
7.6
7.3
7.3
7.3
7.6
7.3
7.3
7.3
27.1
43.7
60.2
56.4
37.5
49.7
61.9
57.8
61.0
47.9
55.8
63.6
59.3
62.6
58.4
61.8
65.3
60.8
64.1
66.7
66.1
61.5
64.9
71.5
66.9
62.3
65.7
90
27.1
40.8
54.6
50.6
38.3
47.1
55.9
51.8
55.4
49.4
53.3
57.2
53.1
56.7
60.5
59.5
58.5
54.3
58.1
64.0
59.0
54.7
58.5
67.0
59.4
55.1
58.9
65
20.3
20.3
19.8
20.2
19.7
20.2
19.6
17.5
19.2
14.9
18.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
22
349681-JTG-A-1007
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
119.1
107.7
96.3
91.3
123.0
111.2
99.4
94.2
87.2
126.8
114.7
102.5
97.2
89.9
130.7
118.1
105.6
100.1
92.6
120.9
108.1
102.4
94.9
123.6
110.6
104.8
97.1
5.6
5.5
5.3
5.3
5.6
5.5
5.3
5.3
5.3
5.6
5.5
5.3
5.3
5.3
5.6
5.5
5.3
5.3
5.3
5.8
5.6
5.6
5.6
6.1
6.0
5.9
5.9
50.2
63.0
75.8
91.3
55.4
69.1
82.8
94.2
87.2
60.5
75.2
89.9
97.2
89.9
65.6
81.3
96.9
100.1
92.6
86.4
103.7
102.4
94.9
91.5
110.6
104.8
97.1
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
97.7
90.9
84.2
76.5
101.3
94.3
87.3
79.4
80.8
105.0
97.7
90.4
82.2
83.7
108.6
101.1
93.6
85.1
86.6
101.6
94.1
85.6
87.1
102.2
94.6
86.0
87.5
6.9
6.8
6.8
6.7
6.9
6.8
6.8
6.7
6.7
6.9
6.8
6.8
6.7
6.7
6.9
6.9
6.8
6.8
6.8
6.9
6.8
6.8
6.8
6.9
6.8
6.8
6.8
42.9
55.8
68.7
76.5
48.1
62.3
76.6
79.4
80.8
53.3
68.9
84.4
82.2
83.7
58.4
75.4
92.3
85.1
86.6
81.0
93.4
85.6
87.1
86.6
94.6
86.0
87.5
90
46.6
59.4
72.3
83.9
51.7
65.7
79.7
86.8
84.0
56.9
72.0
87.2
89.7
86.8
62.0
78.3
94.6
92.6
89.6
83.7
98.6
94.0
91.0
89.0
102.6
95.4
92.3
37.6
52.9
68.1
72.0
45.3
59.4
73.5
74.2
75.6
53.0
65.9
78.8
76.4
77.9
60.7
72.4
84.2
78.6
80.1
77.8
85.0
79.0
80.6
83.1
85.8
79.5
81.0
65
45.9
48.6
49.0
51.2
51.7
53.9
54.4
54.4
53.1
54.8
51.8
35.3
37.7
38.2
40.1
40.7
42.5
43.2
39.8
40.9
37.1
38.6
23
349681-JTG-A-1007
J07ZH (7.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
88.0
79.6
71.1
67.4
90.0
81.4
72.8
69.0
70.4
92.1
83.3
74.5
70.5
72.0
94.1
85.1
76.1
72.1
73.6
85.6
76.6
72.5
74.0
86.2
77.1
73.0
74.5
8.6
8.5
8.5
8.5
8.6
8.5
8.5
8.5
8.5
8.6
8.5
8.5
8.5
8.5
8.6
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.6
8.5
8.5
8.5
32.3
49.9
67.5
67.4
42.5
56.4
70.4
69.0
70.4
52.7
63.0
73.3
70.5
72.0
63.0
69.5
76.1
72.1
73.6
74.6
76.6
72.5
74.0
79.6
77.1
73.0
74.5
90
29.2
46.9
64.6
62.8
41.4
53.5
65.6
63.8
65.2
53.6
60.1
66.5
64.7
66.1
65.9
66.6
67.4
65.6
67.1
71.4
67.8
66.0
67.5
76.2
68.3
66.5
68.0
65
25.5
26.5
26.3
27.4
27.3
28.4
28.2
25.9
26.6
23.5
24.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
24
349681-JTG-A-1007
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
125.2
116.5
107.7
98.3
130.8
121.6
112.5
102.6
100.7
136.3
126.8
117.2
106.9
105.0
141.9
131.9
121.9
111.2
109.3
135.0
124.8
113.8
111.8
138.1
127.6
116.4
114.4
6.6
6.6
6.6
6.6
6.5
6.5
6.5
6.5
6.5
6.3
6.3
6.3
6.3
6.3
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.3
6.2
57.1
70.4
83.6
98.3
62.2
79.3
96.4
102.6
100.7
67.3
88.2
109.2
106.9
105.0
72.4
97.1
121.9
111.2
109.3
123.1
124.8
113.8
111.8
149.0
127.6
116.4
114.4
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
119.8
108.7
97.7
89.1
123.2
111.8
100.4
91.6
93.5
126.5
114.9
103.2
94.1
96.0
129.9
117.9
105.9
96.6
98.6
120.3
108.0
98.6
100.6
122.6
110.1
100.5
102.5
7.3
7.3
7.3
7.2
7.5
7.5
7.5
7.4
7.4
7.6
7.6
7.6
7.5
7.6
7.8
7.8
7.8
7.7
7.7
7.8
7.8
7.7
7.7
7.8
7.8
7.7
7.7
51.2
67.9
84.6
89.1
60.0
75.8
91.7
91.6
93.5
68.7
83.8
98.8
94.1
96.0
77.5
91.7
105.9
96.6
98.6
99.5
108.0
98.6
100.6
107.2
110.1
100.5
102.5
90
54.2
69.1
84.1
93.7
61.1
77.6
94.1
97.1
97.1
68.0
86.0
104.0
100.5
100.5
74.9
94.4
113.9
103.9
103.9
111.3
116.4
106.2
106.2
128.1
118.9
108.5
108.5
45.1
64.7
84.3
83.4
55.9
72.3
88.7
85.3
87.0
66.7
79.9
93.1
87.2
89.0
77.6
87.6
97.6
89.2
91.0
95.1
99.5
91.0
92.8
102.6
101.5
92.8
94.6
65
47.0
50.5
50.9
54.1
54.5
57.7
58.1
42.8
43.0
27.9
27.9
43.0
45.7
42.3
48.4
44.7
51.0
47.0
45.7
44.6
40.3
42.2
25
349681-JTG-A-1007
J08ZH (8.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
104.5
94.6
84.7
77.6
106.3
96.3
86.2
78.9
80.5
108.2
97.9
87.7
80.3
81.9
110.0
99.6
89.2
81.7
83.3
101.6
91.0
83.3
85.0
103.7
92.9
85.0
86.7
9.5
9.5
9.5
9.5
9.5
9.5
9.6
9.5
9.5
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.7
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
39.0
61.5
83.9
77.6
51.9
68.8
85.7
78.9
80.5
64.8
76.1
87.4
80.3
81.9
77.6
83.4
89.2
81.7
83.3
90.7
91.0
83.3
85.0
97.9
92.9
85.0
86.7
90
38.2
58.2
78.2
71.8
51.4
65.2
79.1
72.6
74.0
64.5
72.3
80.0
73.4
74.9
77.7
79.3
80.8
74.2
75.7
86.3
82.5
75.7
77.2
93.3
84.2
77.3
78.8
65
37.9
40.3
32.4
42.7
34.1
45.1
35.8
35.4
31.5
25.7
27.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
26
349681-JTG-A-1007
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
156.1
144.0
131.9
117.8
160.9
148.4
136.0
121.5
117.2
165.7
152.9
140.0
125.1
120.7
170.5
157.3
144.1
128.7
124.3
161.7
148.1
132.3
127.8
166.1
152.2
136.0
131.3
7.6
7.5
7.4
7.4
7.6
7.5
7.4
7.4
7.3
7.6
7.5
7.4
7.5
7.3
7.6
7.5
7.4
7.5
7.3
7.5
7.4
7.5
7.3
7.5
7.4
7.5
7.3
68.9
85.7
102.5
117.8
75.6
94.6
113.6
121.5
117.2
82.3
103.4
124.6
125.1
120.7
88.9
112.3
135.7
128.7
124.3
120.9
143.9
132.3
127.8
129.6
152.2
136.0
131.3
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
138.8
128.2
117.6
108.7
142.8
131.9
121.0
111.9
109.1
146.8
135.6
124.4
115.0
112.2
150.8
139.3
127.8
118.2
115.3
142.5
130.7
120.8
117.9
145.6
133.6
123.5
120.5
9.4
9.2
9.1
9.0
9.4
9.3
9.1
9.1
9.2
9.5
9.3
9.2
9.1
9.3
9.6
9.4
9.2
9.2
9.3
9.4
9.3
9.2
9.4
9.5
9.3
9.3
9.4
59.1
78.3
97.5
108.7
66.9
87.2
107.6
111.9
109.1
74.6
96.2
117.7
115.0
112.2
82.4
105.1
127.8
118.2
115.3
113.2
130.7
120.8
117.9
121.3
133.6
123.5
120.5
90
64.0
82.0
100.0
113.3
71.2
90.9
110.6
116.7
113.2
78.5
99.8
121.1
120.1
116.5
85.7
108.7
131.7
123.4
119.8
117.1
137.3
126.6
122.8
125.4
142.9
129.8
125.9
53.7
76.1
98.5
104.1
64.1
84.6
105.0
106.0
103.9
74.5
93.0
111.6
107.8
105.7
84.9
101.5
118.1
109.6
107.5
109.5
120.7
112.1
109.9
117.5
123.4
114.5
112.3
65
61.0
64.8
68.5
68.6
72.6
72.4
76.7
72.1
72.3
71.8
68.0
53.0
55.7
55.2
58.4
57.8
61.0
60.5
58.5
57.2
56.0
53.8
27
349681-JTG-A-1007
J10ZH (10 Ton) (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
128.1
117.4
106.8
99.5
128.7
118.0
107.3
100.1
98.8
129.4
118.6
107.9
100.6
99.3
130.1
119.3
108.4
101.1
99.8
121.8
110.8
103.3
101.9
124.4
113.1
105.5
104.1
11.7
11.6
11.5
11.6
11.7
11.6
11.5
11.6
11.6
11.7
11.6
11.5
11.6
11.6
11.8
11.7
11.6
11.6
11.6
11.7
11.6
11.6
11.6
11.7
11.6
11.6
11.6
48.4
73.9
99.5
99.5
61.4
81.9
102.5
100.1
98.8
74.3
89.9
105.4
100.6
99.3
87.3
97.9
108.4
101.1
99.8
105.8
110.8
103.3
101.9
113.6
113.1
105.5
104.1
90
43.0
71.7
100.5
94.9
58.6
79.2
99.9
94.1
93.6
74.2
86.8
99.3
93.3
92.8
89.8
94.3
98.8
92.6
92.0
102.0
100.8
94.5
94.0
109.8
102.9
96.4
95.9
65
49.0
49.5
43.8
50.0
43.8
50.4
43.8
44.0
40.4
37.6
37.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
28
349681-JTG-A-1007
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
187.0
176.3
165.5
149.3
193.7
182.5
171.4
154.5
155.4
200.3
188.8
177.2
159.8
160.7
207.0
195.1
183.1
165.1
166.0
203.6
191.1
172.4
173.3
212.2
199.1
179.6
180.6
9.5
9.5
9.4
9.2
9.6
9.6
9.5
9.3
9.2
9.7
9.7
9.6
9.3
9.3
9.8
9.8
9.7
9.4
9.4
9.7
9.6
9.4
9.3
9.7
9.6
9.4
9.3
73.2
98.5
123.7
149.3
82.5
110.4
138.3
154.5
155.4
91.7
122.3
152.8
159.8
160.7
101.0
134.2
167.3
165.1
166.0
143.3
183.2
172.4
173.3
152.4
199.1
179.6
180.6
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
178.3
163.6
148.9
136.0
183.6
168.4
153.3
140.1
141.1
188.9
173.3
157.7
144.1
145.2
194.1
178.1
162.1
148.1
149.2
183.1
166.6
152.2
153.4
188.0
171.1
156.3
157.5
11.7
11.6
11.5
11.2
11.8
11.7
11.6
11.3
11.3
12.0
11.8
11.7
11.4
11.4
12.1
11.9
11.8
11.5
11.5
11.9
11.8
11.5
11.5
11.9
11.8
11.5
11.5
76.0
98.8
121.6
136.0
83.7
108.6
133.4
140.1
141.1
91.5
118.3
145.2
144.1
145.2
99.2
128.1
157.0
148.1
149.2
138.0
164.0
152.2
153.4
147.8
171.1
156.3
157.5
90
74.6
98.6
122.7
142.6
83.1
109.5
135.8
147.3
148.3
91.6
120.3
149.0
152.0
152.9
100.1
131.1
162.2
156.6
157.6
140.6
173.6
162.3
163.3
150.1
185.1
168.0
169.0
69.9
94.5
119.1
128.6
79.8
104.4
129.0
132.2
132.5
89.7
114.3
138.9
135.8
136.1
99.7
124.2
148.8
139.4
139.7
133.8
154.0
143.0
143.3
143.4
159.1
146.5
146.8
65
78.3
84.0
87.2
89.6
93.2
95.3
99.1
98.5
101.0
101.8
102.8
67.9
72.7
72.8
77.4
77.6
82.2
82.4
81.2
81.5
80.3
80.6
29
349681-JTG-A-1007
J12ZH (12.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
157.3
143.8
130.4
121.2
161.4
147.6
133.8
124.3
123.8
165.5
151.4
137.2
127.5
127.0
169.6
155.1
140.7
130.7
130.2
158.7
143.9
133.7
133.2
162.3
147.2
136.7
136.2
14.5
14.3
14.1
14.0
14.5
14.4
14.2
14.1
14.1
14.6
14.4
14.3
14.1
14.2
14.6
14.5
14.3
14.2
14.2
14.5
14.3
14.2
14.3
14.5
14.4
14.2
14.3
63.8
90.2
116.6
121.2
75.9
100.3
124.6
124.3
123.8
88.0
110.3
132.6
127.5
127.0
100.1
120.4
140.7
130.7
130.2
129.7
143.9
133.7
133.2
139.0
147.2
136.7
136.2
90
56.5
85.9
114.1
113.7
72.0
96.1
120.2
116.5
115.2
87.5
106.3
126.4
119.2
117.9
103.1
116.5
129.9
121.9
120.6
125.5
132.5
124.4
123.1
134.6
135.2
126.9
125.5
65
52.0
56.1
55.1
60.2
59.1
64.2
63.1
62.4
61.1
60.5
59.1
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
30
349681-JTG-A-1007
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
99.9
91.5
83.0
72.4
106.5
97.5
88.5
77.2
78.2
113.1
103.5
93.9
81.9
83.1
119.7
109.5
99.4
86.7
87.9
109.6
99.5
86.8
88.0
109.7
99.6
86.9
88.0
5.1
5.0
5.0
4.9
5.1
5.1
5.1
5.0
5.0
5.2
5.2
5.1
5.1
5.1
5.3
5.2
5.2
5.1
5.2
5.2
5.1
5.1
5.1
5.1
5.1
5.0
5.0
39.3
50.3
61.3
72.4
45.5
57.8
70.1
77.2
78.2
51.6
65.2
78.8
81.9
83.1
57.8
72.7
87.6
86.7
87.9
74.8
91.9
86.8
88.0
76.9
96.1
86.9
88.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
81.2
75.9
70.7
64.9
87.0
81.4
75.8
69.7
63.0
92.9
87.0
81.0
74.4
67.3
98.8
92.5
86.1
79.1
71.5
90.8
84.5
77.6
70.2
89.1
83.0
76.2
68.9
6.5
6.5
6.4
6.4
6.6
6.5
6.5
6.4
6.5
6.7
6.6
6.6
6.5
6.5
6.7
6.7
6.6
6.6
6.6
6.6
6.6
6.5
6.6
6.6
6.5
6.5
6.5
34.6
45.6
56.7
64.9
40.1
52.5
64.9
69.7
63.0
45.5
59.3
73.2
74.4
67.3
51.0
66.2
81.4
79.1
71.5
68.3
82.2
77.6
70.2
70.4
83.0
76.2
68.9
90
36.9
48.0
59.0
68.7
42.8
55.1
67.5
73.4
70.6
48.6
62.3
76.0
78.1
75.2
54.4
69.5
84.5
82.9
79.7
71.6
87.0
82.2
79.1
73.7
89.5
81.5
78.5
31.0
43.2
55.3
59.4
37.4
49.6
61.8
63.2
61.6
43.8
56.0
68.3
67.0
65.2
50.2
62.5
74.7
70.8
68.9
64.7
74.8
69.7
67.9
66.9
74.8
68.6
66.9
65
39.3
41.9
43.0
44.6
45.8
47.3
48.6
47.7
46.8
48.1
45.1
31.6
33.9
33.2
36.2
35.5
38.5
37.7
37.2
35.9
35.9
34.2
31
349681-JTG-A-1007
J06ZR (6.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
72.6
65.6
58.6
53.8
76.5
69.1
61.8
56.7
60.1
80.4
72.7
64.9
59.6
63.2
84.3
76.2
68.1
62.5
66.3
75.4
67.3
61.8
65.5
74.5
66.6
61.1
64.8
8.1
8.1
8.1
8.0
8.2
8.2
8.2
8.1
8.1
8.4
8.3
8.3
8.2
8.2
8.5
8.4
8.4
8.3
8.3
8.3
8.3
8.2
8.2
8.3
8.2
8.1
8.1
27.5
40.7
54.0
53.8
34.8
46.7
58.7
56.7
60.1
42.1
52.7
63.4
59.6
63.2
49.4
58.8
68.1
62.5
66.3
61.1
67.3
61.8
65.5
63.4
66.6
61.1
64.8
90
24.0
38.3
52.6
48.2
33.0
43.9
54.7
50.2
58.7
42.0
49.4
56.9
52.2
61.2
51.0
55.0
59.1
54.2
63.6
57.5
58.7
53.8
63.2
59.9
58.4
53.5
62.7
65
23.1
24.7
27.6
26.2
29.5
27.7
31.3
24.8
31.2
22.0
31.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
32
349681-JTG-A-1007
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
31.6
32.2
28.5
36.1
36.7
32.6
34.2
40.5
41.2
36.7
38.3
45.0
45.7
40.8
42.5
42.5
43.2
38.5
40.2
40.0
40.6
36.2
37.9
4.5
4.6
4.4
4.3
4.5
4.3
4.4
4.2
4.3
4.2
4.2
4.1
4.2
4.0
4.1
4.0
4.1
4.0
4.0
3.9
4.0
3.9
4.0
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
38.2
38.2
35.5
38.4
38.4
35.7
34.7
38.6
38.6
35.9
34.9
38.8
38.9
36.1
35.1
39.0
39.1
36.3
35.3
39.2
39.3
36.5
35.5
5.7
5.1
5.3
5.5
4.9
5.1
5.1
5.2
4.7
4.9
4.8
5.0
4.4
4.6
4.6
5.2
4.6
4.8
4.8
5.3
4.8
5.0
5.0
65
4.1
10.4
15.6
16.7
25.1
23.1
34.5
26.1
33.3
29.2
32.0
5.3
11.6
14.8
18.0
22.7
24.3
30.7
27.4
30.3
30.5
29.9
33
349681-JTG-A-1007
J06ZR (6.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
34.3
34.2
30.6
35.1
35.0
31.3
31.2
35.9
35.8
32.0
31.9
36.7
36.6
32.7
32.6
37.0
36.9
33.0
32.8
37.2
37.1
33.2
33.1
5.7
5.4
5.0
5.7
5.4
5.0
5.0
5.7
5.4
5.0
5.0
5.7
5.4
5.0
5.0
5.6
5.4
4.9
4.9
5.6
5.3
4.9
4.9
65
2.4
9.5
10.8
16.6
19.2
23.8
27.6
25.0
27.1
26.3
26.6
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
34
349681-JTG-A-1007
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
105.8
98.8
91.9
84.5
111.9
104.5
97.1
89.3
88.6
118.0
110.2
102.4
94.2
93.5
124.1
115.9
107.7
99.0
98.3
115.5
107.3
98.7
98.0
115.1
107.0
98.4
97.6
5.6
5.6
5.5
5.5
5.6
5.6
5.5
5.5
5.5
5.6
5.6
5.5
5.5
5.5
5.6
5.6
5.5
5.5
5.5
5.6
5.5
5.5
5.5
5.6
5.6
5.5
5.5
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
100.0
92.6
85.2
78.6
103.1
95.4
87.8
81.0
80.7
106.2
98.3
90.4
83.4
83.1
109.2
101.2
93.1
85.8
85.6
101.8
93.6
86.4
86.1
102.4
94.2
86.9
86.6
7.1
7.0
6.9
6.8
7.1
7.0
6.9
6.9
6.9
7.2
7.1
7.0
6.9
6.9
7.2
7.1
7.0
6.9
7.0
7.1
7.0
6.9
7.0
7.1
7.0
7.0
7.0
90
42.8
56.0
69.2
81.5
48.5
63.0
77.6
85.1
84.7
54.1
70.0
86.0
88.8
88.3
59.7
77.1
94.4
92.4
91.9
79.1
97.1
92.5
92.0
81.2
99.8
92.6
92.1
35.7
50.5
65.2
72.5
42.3
56.9
71.6
74.5
75.4
48.9
63.4
78.0
76.5
77.4
55.4
69.9
84.4
78.5
79.4
73.3
85.7
79.3
80.2
76.7
87.0
80.2
81.0
65
44.1
46.9
48.8
49.8
51.8
52.7
54.8
55.1
56.0
57.6
57.1
36.7
39.0
39.5
41.2
41.9
43.5
44.2
43.6
44.4
43.8
44.7
35
349681-JTG-A-1007
J07ZR (7.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
87.0
79.6
72.2
66.5
89.0
81.5
74.0
68.1
70.0
91.1
83.4
75.7
69.7
71.6
93.2
85.3
77.4
71.2
73.2
86.6
78.6
72.3
74.4
87.9
79.8
73.4
75.5
8.8
8.7
8.7
8.6
8.9
8.8
8.7
8.6
8.7
8.9
8.8
8.8
8.7
8.7
8.9
8.9
8.8
8.7
8.8
8.9
8.8
8.7
8.8
8.8
8.8
8.7
8.7
31.8
47.8
63.8
66.5
39.5
53.9
68.4
68.1
70.0
47.2
60.0
72.9
69.7
71.6
54.9
66.1
77.4
71.2
73.2
70.2
78.6
72.3
74.4
74.3
79.8
73.4
75.5
90
27.4
45.1
62.5
60.5
36.6
50.9
65.1
61.6
64.6
45.8
56.6
67.8
62.8
65.8
55.1
62.3
69.6
63.9
67.1
67.1
71.1
65.3
68.5
71.8
72.6
66.7
69.9
65
28.9
30.3
30.1
31.7
31.5
33.1
32.9
31.3
32.8
29.5
32.7
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
36
349681-JTG-A-1007
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
38.6
37.9
35.4
43.5
42.8
40.1
41.4
48.5
47.7
44.8
46.1
53.5
52.6
49.5
50.7
50.5
49.6
46.7
47.9
47.6
46.7
43.9
45.2
5.0
4.8
5.6
4.7
4.6
5.3
5.0
4.4
4.3
5.0
4.7
4.1
4.0
4.7
4.4
4.1
4.0
4.7
4.4
4.1
4.0
4.7
4.4
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
45.6
44.8
43.5
45.5
44.7
43.4
41.3
45.4
44.7
43.3
41.2
45.4
44.6
43.2
41.1
45.7
44.9
43.5
41.4
46.0
45.2
43.9
41.7
5.6
5.4
5.2
5.5
5.4
5.1
5.1
5.5
5.3
5.1
5.0
5.4
5.3
5.0
5.0
5.4
5.2
5.0
4.9
5.3
5.2
4.9
4.9
65
4.9
12.5
18.5
20.0
29.7
27.6
41.0
31.4
39.5
35.2
38.0
10.1
16.2
20.6
22.4
28.3
28.6
36.0
32.8
35.7
37.0
35.4
37
349681-JTG-A-1007
J07ZR (7.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
41.4
40.3
37.7
41.9
40.9
38.2
37.3
42.5
41.4
38.8
37.8
43.1
42.0
39.3
38.3
43.6
42.5
39.7
38.8
44.1
43.0
40.2
39.2
6.3
6.0
5.8
6.3
6.0
5.7
5.7
6.2
5.9
5.7
5.7
6.2
5.9
5.6
5.6
6.2
5.9
5.6
5.6
6.1
5.8
5.6
5.6
65
0.0
9.4
10.3
18.8
21.5
28.2
32.6
30.3
32.3
32.4
32.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
38
349681-JTG-A-1007
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
121.9
118.1
114.3
105.8
126.3
122.4
118.4
109.7
107.0
130.7
126.6
122.6
113.5
110.8
135.1
130.9
126.7
117.3
114.5
130.9
126.8
117.4
114.5
131.0
126.8
117.4
114.6
6.4
6.4
6.3
6.2
6.5
6.4
6.4
6.2
6.3
6.5
6.4
6.4
6.3
6.3
6.5
6.5
6.4
6.3
6.4
6.5
6.4
6.3
6.4
6.5
6.5
6.3
6.4
54.3
71.1
87.8
105.8
59.7
79.1
98.4
109.7
107.0
65.1
87.0
108.9
113.5
110.8
70.6
95.0
119.5
117.3
114.5
99.4
123.1
117.4
114.5
103.7
126.8
117.4
114.6
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
115.5
107.5
99.5
91.9
119.5
111.3
103.0
95.2
92.1
123.6
115.1
106.5
98.5
95.2
127.7
118.9
110.1
101.7
98.4
119.8
110.9
102.5
99.2
120.8
111.8
103.3
99.9
8.3
8.1
8.0
7.9
8.3
8.2
8.0
7.9
7.9
8.3
8.2
8.0
7.9
8.0
8.4
8.2
8.1
8.0
8.0
8.3
8.1
8.0
8.0
8.3
8.1
8.0
8.1
50.3
66.9
83.4
91.9
57.6
75.0
92.3
95.2
92.1
64.9
83.1
101.2
98.5
95.2
72.3
91.2
110.1
101.7
98.4
97.1
110.9
102.5
99.2
103.1
111.8
103.3
99.9
90
52.3
69.0
85.6
98.9
58.7
77.0
95.3
102.4
99.6
65.0
85.0
105.1
106.0
103.0
71.4
93.1
114.8
109.5
106.5
98.3
117.0
109.9
106.9
103.4
119.3
110.4
107.3
44.7
63.5
82.4
85.2
54.4
71.5
88.6
88.0
85.8
64.2
79.5
94.9
90.8
88.5
74.0
87.6
101.2
93.6
91.2
93.4
102.0
94.3
92.0
99.2
102.8
95.1
92.7
65
49.8
53.1
54.8
56.5
58.3
59.8
61.8
60.3
59.8
60.8
57.7
40.6
43.1
41.7
45.7
44.1
48.3
46.6
45.9
43.9
43.5
41.2
39
349681-JTG-A-1007
J08ZR (8.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
102.2
93.5
84.8
78.5
105.2
96.2
87.3
80.8
79.6
108.2
99.0
89.8
83.1
81.8
111.2
101.7
92.3
85.4
84.1
102.6
93.0
86.1
84.8
103.4
93.8
86.8
85.5
10.3
10.1
10.0
9.9
10.4
10.2
10.0
9.9
10.0
10.4
10.2
10.0
9.9
10.0
10.4
10.2
10.0
9.9
10.0
10.3
10.1
10.0
10.1
10.3
10.1
10.0
10.1
39.0
60.2
81.3
78.5
51.2
68.1
85.0
80.8
79.6
63.4
76.0
88.6
83.1
81.8
75.7
84.0
92.3
85.4
84.1
89.7
93.0
86.1
84.8
95.4
93.8
86.8
85.5
90
36.2
56.8
77.4
71.8
49.9
64.7
79.4
73.6
73.3
63.7
72.5
81.4
75.4
75.1
77.4
80.4
83.3
77.3
77.0
86.0
84.0
77.9
77.6
91.6
84.7
78.6
78.2
65
28.3
30.1
29.3
31.9
31.0
33.6
32.7
30.5
29.8
27.3
27.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
40
349681-JTG-A-1007
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72.0
74.0
61.6
73.3
75.3
62.6
58.2
74.5
76.7
63.6
59.2
75.7
78.1
64.7
60.2
73.9
76.5
63.0
58.8
72.0
75.0
61.4
57.4
5.0
4.9
5.1
4.9
4.8
5.0
4.7
4.8
4.7
5.0
4.7
4.7
4.6
4.9
4.6
4.7
4.6
4.9
4.6
4.7
4.6
4.9
4.6
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
53.3
49.0
46.3
56.3
51.8
49.0
43.2
59.4
54.6
51.6
45.5
62.4
57.4
54.3
47.9
66.2
60.9
57.6
50.8
70.1
64.5
60.9
53.7
6.1
5.8
5.4
6.0
5.7
5.4
5.3
6.0
5.7
5.4
5.3
6.0
5.7
5.3
5.2
5.9
5.6
5.3
5.2
5.9
5.6
5.3
5.2
65
13.8
21.7
26.0
29.6
35.4
37.5
44.9
42.8
44.7
48.0
44.5
7.7
15.8
18.2
23.9
27.2
32.0
36.2
36.6
36.3
41.2
36.4
41
349681-JTG-A-1007
J08ZR (8.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
42.8
35.4
31.9
50.9
42.1
38.0
29.4
59.1
48.9
44.0
34.1
67.2
55.6
50.1
38.8
68.6
56.7
51.1
39.6
69.9
57.8
52.1
40.4
6.3
6.5
6.2
6.2
6.4
6.1
6.1
6.2
6.4
6.1
6.0
6.2
6.3
6.0
6.0
6.1
6.3
6.0
5.9
6.1
6.3
5.9
5.9
65
0.2
11.2
8.8
22.2
19.0
33.3
29.1
38.3
26.9
43.4
24.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
42
349681-JTG-A-1007
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
145.9
139.2
132.5
114.8
152.7
145.7
138.6
120.2
121.9
159.5
152.1
144.8
125.5
127.3
166.2
158.6
150.9
130.8
132.7
159.9
152.2
131.9
133.8
161.2
153.4
133.0
134.9
7.7
7.5
7.3
7.2
7.7
7.5
7.3
7.2
7.2
7.7
7.5
7.3
7.2
7.2
7.7
7.5
7.3
7.2
7.2
7.5
7.3
7.3
7.3
7.6
7.4
7.4
7.3
59.8
79.5
99.2
114.8
68.3
90.3
112.4
120.2
121.9
76.8
101.2
125.5
125.5
127.3
85.3
112.0
138.7
130.8
132.7
118.5
146.0
131.9
133.8
125.1
153.4
133.0
134.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
134.9
124.1
113.3
101.3
140.7
129.4
118.1
105.6
105.7
146.4
134.6
122.9
109.9
110.1
152.1
139.9
127.7
114.2
114.4
140.8
128.5
114.9
115.1
141.7
129.3
115.6
115.8
9.3
9.2
9.1
9.0
9.4
9.3
9.2
9.1
9.0
9.4
9.3
9.3
9.1
9.1
9.5
9.4
9.3
9.2
9.1
9.4
9.3
9.2
9.1
9.4
9.3
9.2
9.1
58.1
76.1
94.2
101.3
65.3
85.2
105.0
105.6
105.7
72.6
94.2
115.9
109.9
110.1
79.8
103.3
126.7
114.2
114.4
110.0
128.0
114.9
115.1
116.7
129.3
115.6
115.8
90
59.0
77.8
96.7
108.0
66.8
87.8
108.7
112.9
113.8
74.7
97.7
120.7
117.7
118.7
82.6
107.6
132.7
122.5
123.5
114.3
137.0
123.4
124.4
120.9
141.4
124.3
125.3
50.8
71.4
91.9
94.7
60.5
80.3
100.1
98.4
96.9
70.2
89.3
108.4
102.2
100.6
79.9
98.3
116.7
106.0
104.3
104.6
117.2
106.2
104.6
110.9
117.8
106.5
104.8
65
56.3
60.3
63.0
64.2
67.2
68.2
71.5
66.9
69.1
65.7
66.7
47.3
50.0
49.2
52.8
51.9
55.5
54.5
52.6
51.3
49.7
48.0
43
349681-JTG-A-1007
J10ZR (10 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
114.7
105.4
96.1
88.1
118.9
109.3
99.6
91.3
88.0
123.1
113.1
103.1
94.6
91.1
127.3
117.0
106.7
97.8
94.2
116.8
106.4
97.6
94.0
116.5
106.2
97.4
93.9
11.7
11.5
11.4
11.2
11.7
11.6
11.4
11.2
11.5
11.8
11.6
11.5
11.3
11.6
11.8
11.7
11.5
11.3
11.6
11.7
11.5
11.3
11.6
11.7
11.5
11.3
11.6
43.6
66.6
89.6
88.1
55.7
75.5
95.3
91.3
88.0
67.8
84.4
101.0
94.6
91.1
79.9
93.3
106.7
97.8
94.2
99.2
106.4
97.6
94.0
105.2
106.2
97.4
93.9
90
36.1
61.8
87.5
81.5
50.9
70.6
90.4
84.2
79.2
65.7
79.5
93.3
86.9
81.7
80.5
88.3
96.1
89.6
84.2
93.8
95.4
88.9
83.5
99.4
94.7
88.3
82.9
65
35.2
37.3
32.2
39.5
33.9
41.6
35.5
37.6
31.8
33.5
28.1
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
44
349681-JTG-A-1007
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
68.3
71.7
62.7
71.8
75.3
65.9
65.7
75.3
78.9
69.1
68.9
78.9
82.5
72.4
72.1
76.8
80.8
70.6
70.4
74.7
79.0
68.8
68.7
5.0
4.7
5.1
5.2
4.9
5.2
5.0
5.4
5.1
5.4
5.2
5.6
5.3
5.6
5.4
5.6
5.3
5.6
5.4
5.6
5.3
5.6
5.4
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
71.6
63.1
61.7
74.0
65.2
63.7
61.5
76.4
67.3
65.8
63.4
78.7
69.4
67.8
65.4
82.5
72.7
71.0
68.5
86.2
76.0
74.2
71.6
7.3
7.2
6.8
7.1
6.9
6.6
6.4
6.9
6.7
6.4
6.2
6.7
6.5
6.2
6.0
6.7
6.5
6.2
6.0
6.6
6.5
6.2
6.0
65
21.0
27.1
40.5
33.1
49.6
39.2
58.7
43.9
58.1
48.5
57.5
12.5
22.3
28.2
32.1
40.4
41.9
52.7
48.7
53.2
55.6
53.6
45
349681-JTG-A-1007
J10ZR (10 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
59.1
53.8
49.1
62.5
56.9
52.0
50.9
65.9
60.0
54.8
53.7
69.4
63.1
57.7
56.5
70.6
64.3
58.7
57.5
71.9
65.4
59.7
58.5
8.4
8.0
7.6
8.1
7.7
7.4
7.3
7.9
7.5
7.1
7.0
7.6
7.2
6.9
6.8
7.6
7.2
6.9
6.8
7.6
7.2
6.9
6.8
65
1.5
1.2
18.5
22.1
35.6
43.1
39.2
42.7
42.8
42.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
46
349681-JTG-A-1007
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
190.5
180.7
171.0
158.6
199.8
189.6
179.4
166.3
154.4
209.1
198.4
187.7
174.1
161.6
218.4
207.3
196.1
181.8
168.8
211.2
199.9
185.3
172.0
215.2
203.6
188.8
175.3
9.0
9.2
9.3
9.1
9.2
9.3
9.4
9.2
9.2
9.3
9.4
9.6
9.4
9.3
9.4
9.6
9.7
9.5
9.5
9.6
9.7
9.5
9.5
9.5
9.7
9.5
9.4
87.6
111.5
135.4
158.6
94.7
119.8
145.0
166.3
154.4
101.9
128.2
154.5
174.1
161.6
109.0
136.6
164.1
181.8
168.8
148.0
179.4
185.3
172.0
159.4
194.6
188.8
175.3
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
180.0
165.1
150.2
137.5
188.2
172.7
157.1
143.8
139.4
196.5
180.3
164.0
150.1
145.5
204.8
187.8
170.9
156.4
151.6
193.2
175.8
160.9
156.0
198.6
180.7
165.4
160.3
11.9
11.8
11.7
11.5
12.0
11.9
11.7
11.6
11.6
12.0
11.9
11.8
11.6
11.7
12.1
12.0
11.9
11.7
11.7
12.0
11.9
11.7
11.7
12.0
11.9
11.7
11.8
75.6
99.3
123.0
137.5
83.2
109.0
134.8
143.8
139.4
90.7
118.6
146.6
150.1
145.5
98.3
128.3
158.4
156.4
151.6
138.6
169.6
160.9
156.0
148.9
180.7
165.4
160.3
90
81.6
105.4
129.2
148.0
89.0
114.4
139.9
155.1
146.9
96.3
123.4
150.6
162.1
153.5
103.6
132.4
161.2
169.1
160.2
143.3
174.5
173.1
164.0
154.1
187.7
177.1
167.8
71.8
95.1
118.4
127.9
79.5
104.5
129.4
133.5
130.3
87.3
113.9
140.5
139.2
135.7
95.1
123.3
151.6
144.8
141.2
133.3
158.7
148.4
144.7
143.3
165.8
152.0
148.3
65
96.8
101.2
89.1
105.6
92.7
110.0
96.3
109.3
97.8
108.6
99.3
67.8
72.2
69.5
76.6
73.7
81.1
77.9
82.5
79.1
84.0
80.2
47
349681-JTG-A-1007
J12ZR (12.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
156.3
142.6
128.8
118.4
162.8
148.5
134.1
123.3
121.1
169.3
154.4
139.5
128.2
126.0
175.8
160.3
144.9
133.1
130.8
163.7
147.9
135.9
133.5
167.0
150.9
138.6
136.2
14.6
14.5
14.4
14.2
14.7
14.6
14.4
14.3
14.3
14.7
14.6
14.5
14.3
14.4
14.8
14.7
14.5
14.4
14.4
14.7
14.5
14.4
14.4
14.7
14.5
14.4
14.4
67.9
90.8
113.7
118.4
75.9
100.0
124.1
123.3
121.1
83.9
109.2
134.5
128.2
126.0
91.9
118.4
144.9
133.1
130.8
128.0
147.9
135.9
133.5
137.7
150.9
138.6
136.2
90
60.9
86.6
110.3
108.8
72.3
95.5
118.8
113.0
112.0
83.6
104.5
127.2
117.3
116.2
95.0
113.4
131.8
121.5
120.4
122.7
133.9
123.4
122.3
132.0
135.9
125.3
124.2
65
60.4
63.2
53.1
65.9
55.1
68.7
57.0
63.9
57.5
59.0
58.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
48
349681-JTG-A-1007
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
87.0
84.6
82.9
89.0
86.5
84.8
82.2
90.9
88.4
86.6
84.0
92.8
90.3
88.5
85.9
94.1
91.5
89.7
87.1
95.4
92.8
91.0
88.3
7.7
7.3
7.3
7.4
7.1
7.1
7.7
7.2
6.9
6.8
7.4
6.9
6.6
6.6
7.1
7.5
7.1
7.1
7.7
8.0
7.7
7.6
8.3
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
84.8
81.9
78.7
88.8
85.8
82.5
76.1
92.8
89.7
86.2
79.5
96.8
93.6
89.9
83.0
99.3
96.0
92.2
85.1
101.8
98.4
94.6
87.2
8.9
8.7
8.2
8.6
8.3
7.8
8.7
8.2
8.0
7.5
8.3
7.8
7.6
7.1
8.0
8.2
8.0
7.5
8.4
8.6
8.4
7.9
8.8
65
10.9
27.1
31.3
43.3
49.7
59.5
68.2
44.3
50.8
29.0
33.5
18.7
31.5
35.6
44.4
49.7
57.2
63.7
55.9
60.2
54.6
56.8
49
349681-JTG-A-1007
J12ZR (12.5 Ton) Reheat (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
72
67
62
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
83.6
76.2
70.5
85.8
78.2
72.3
69.0
88.0
80.2
74.2
70.8
90.1
82.2
76.0
72.6
96.1
87.6
81.0
77.3
102.0
93.0
86.0
82.1
9.7
9.2
8.7
9.9
9.3
8.8
9.3
10.0
9.4
8.9
9.5
10.1
9.5
9.0
9.6
10.3
9.6
9.1
9.7
10.4
9.8
9.2
9.8
65
39.6
41.3
49.8
43.0
52.8
44.7
55.8
65.5
71.5
81.7
79.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
50
349681-JTG-A-1007
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
101.5
92.3
83.1
76.7
105.5
95.9
86.3
79.8
78.2
109.5
99.6
89.6
82.8
81.2
113.6
103.2
92.9
85.8
84.2
105.5
95.0
87.7
86.1
107.8
97.0
89.7
87.9
4.7
4.8
4.9
4.8
4.8
4.8
4.9
4.8
4.8
4.8
4.9
4.9
4.8
4.9
4.8
4.9
5.0
4.9
4.9
4.9
4.9
4.8
4.9
4.8
4.9
4.8
4.8
41.0
52.5
64.0
76.7
45.8
58.9
72.0
79.8
78.2
50.6
65.3
79.9
82.8
81.2
55.4
71.7
87.9
85.8
84.2
76.3
92.5
87.7
86.1
80.9
97.0
89.7
87.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
84.3
77.8
71.3
65.2
88.0
81.2
74.4
68.0
68.8
91.7
84.6
77.5
70.8
71.7
95.3
88.0
80.6
73.7
74.6
90.2
82.6
75.5
76.5
92.4
84.7
77.4
78.3
6.6
6.5
6.4
6.4
6.6
6.4
6.3
6.4
6.4
6.5
6.4
6.3
6.3
6.3
6.5
6.3
6.2
6.3
6.3
6.4
6.3
6.3
6.3
6.4
6.3
6.3
6.3
37.4
48.6
59.9
65.2
42.5
54.7
66.8
68.0
68.8
47.7
60.7
73.7
70.8
71.7
52.9
66.7
80.6
73.7
74.6
71.4
82.6
75.5
76.5
76.1
84.7
77.4
78.3
90
39.2
50.6
62.0
71.0
44.2
56.8
69.4
73.9
73.5
49.2
63.0
76.8
76.8
76.5
54.1
69.2
84.3
79.8
79.4
73.8
87.6
81.6
81.3
78.5
90.9
83.5
83.1
33.1
46.3
59.6
59.9
40.2
52.2
64.1
62.1
64.4
47.4
58.0
68.6
64.3
66.7
54.5
63.8
73.1
66.6
69.0
68.3
74.6
68.0
70.5
72.7
76.2
69.4
72.0
65
37.3
40.2
41.8
43.0
44.8
45.8
47.8
46.3
47.1
46.8
46.4
29.7
31.4
33.5
33.1
35.4
34.8
37.3
33.9
36.4
32.9
35.5
51
349681-JTG-A-1007
J06XP (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
72.6
66.3
60.1
54.6
74.7
68.3
61.9
56.2
60.0
76.9
70.3
63.7
57.8
61.8
79.0
72.3
65.5
59.4
63.5
73.5
66.6
60.4
64.5
74.7
67.7
61.4
65.6
8.1
8.1
8.0
8.0
8.1
8.0
8.0
7.9
8.0
8.1
8.0
8.0
7.9
8.0
8.0
8.0
7.9
7.9
8.0
8.0
8.0
7.9
8.0
8.1
8.0
8.0
8.0
28.9
44.0
59.2
54.6
38.0
49.6
61.3
56.2
60.0
47.1
55.3
63.4
57.8
61.8
56.2
60.9
65.5
59.4
63.5
65.1
66.6
60.4
64.5
69.4
67.7
61.4
65.6
90
29.0
41.7
54.5
49.3
38.6
47.1
55.7
50.3
55.6
48.2
52.5
56.8
51.3
56.8
57.8
57.9
58.0
52.3
57.9
62.0
58.6
52.9
58.6
65.8
59.2
53.4
59.2
65
18.5
19.4
24.1
20.3
25.5
21.2
26.8
19.4
25.1
17.7
23.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
52
349681-JTG-A-1007
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
117.7
108.9
100.0
94.6
122.0
112.8
103.6
98.0
94.3
126.2
116.7
107.2
101.4
97.6
130.4
120.6
110.7
104.7
100.8
122.0
112.1
106.0
102.1
123.5
113.4
107.2
103.3
5.8
5.7
5.7
5.6
5.8
5.7
5.7
5.6
5.6
5.8
5.8
5.7
5.6
5.6
5.8
5.8
5.7
5.6
5.6
5.8
5.7
5.6
5.7
5.8
5.7
5.7
5.7
48.9
63.3
77.7
94.6
54.1
69.7
85.4
98.0
94.3
59.3
76.2
93.0
101.4
97.6
64.5
82.6
100.7
104.7
100.8
87.6
107.1
106.0
102.1
92.5
113.4
107.2
103.3
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
104.4
95.9
87.4
79.8
107.4
98.7
89.9
82.1
81.9
110.4
101.4
92.4
84.4
84.2
113.4
104.1
94.9
86.7
86.5
104.6
95.3
87.0
86.8
105.0
95.7
87.4
87.2
7.4
7.3
7.2
7.2
7.4
7.3
7.3
7.2
7.2
7.4
7.4
7.3
7.2
7.2
7.5
7.4
7.3
7.2
7.2
7.4
7.3
7.3
7.3
7.4
7.3
7.3
7.3
43.3
57.2
71.0
79.8
47.9
63.0
78.1
82.1
81.9
52.6
68.9
85.2
84.4
84.2
57.3
74.8
92.2
86.7
86.5
80.2
94.0
87.0
86.8
85.7
95.7
87.4
87.2
90
46.1
60.2
74.4
87.2
51.0
66.4
81.7
90.1
88.1
55.9
72.5
89.1
92.9
90.9
60.9
78.7
96.5
95.7
93.7
83.9
100.5
96.5
94.4
89.1
104.6
97.3
95.2
37.8
53.5
69.2
74.7
43.9
59.2
74.5
76.5
76.1
50.1
64.9
79.8
78.2
77.9
56.2
70.6
85.1
80.0
79.6
75.6
85.8
80.1
79.7
80.6
86.6
80.1
79.8
65
46.1
48.6
51.8
51.1
54.6
53.6
57.4
54.6
55.5
55.7
53.6
38.5
40.7
42.1
42.9
44.4
45.1
46.7
42.5
43.1
39.9
39.5
53
349681-JTG-A-1007
J07XP (7.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
88.3
81.1
74.0
69.6
89.8
82.6
75.3
70.8
70.3
91.4
84.0
76.6
72.0
71.5
92.9
85.4
77.9
73.3
72.7
85.2
77.7
73.1
72.6
85.0
77.5
72.9
72.4
9.2
9.1
9.1
9.0
9.3
9.2
9.1
9.1
9.1
9.3
9.2
9.1
9.1
9.1
9.3
9.2
9.2
9.1
9.1
9.2
9.2
9.1
9.1
9.3
9.2
9.1
9.1
32.2
49.8
67.3
69.6
39.9
55.3
70.8
70.8
70.3
47.5
60.9
74.3
72.0
71.5
55.1
66.5
77.9
73.3
72.7
71.0
77.7
73.1
72.6
75.5
77.5
72.9
72.4
90
26.0
46.1
65.7
64.5
35.8
51.5
67.2
65.2
64.5
45.6
56.9
68.7
65.9
65.2
55.4
62.4
69.3
66.5
65.9
66.4
68.9
66.1
65.4
70.4
68.4
65.6
65.0
65
30.4
32.3
31.8
34.2
33.7
36.1
35.6
31.8
31.2
27.5
26.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
54
349681-JTG-A-1007
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
120.9
113.7
106.4
96.7
126.2
118.6
110.9
100.9
100.3
131.4
123.5
115.5
105.1
104.4
136.7
128.4
120.1
109.3
108.6
132.2
123.6
112.5
111.8
136.0
127.2
115.7
115.0
6.2
6.1
6.0
5.9
6.2
6.1
6.0
6.0
5.9
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.3
6.2
6.1
6.1
58.3
69.9
81.4
96.7
62.1
78.1
94.1
100.9
100.3
65.9
86.3
106.8
105.1
104.4
69.7
94.6
119.5
109.3
108.6
101.6
123.3
112.5
111.8
108.6
127.2
115.7
115.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
116.2
105.1
94.0
87.9
120.4
108.9
97.4
91.1
91.1
124.5
112.6
100.7
94.2
94.2
128.7
116.4
104.1
97.4
97.4
118.8
106.3
99.4
99.4
121.3
108.4
101.4
101.4
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.7
7.7
7.9
7.9
7.8
7.7
7.7
7.9
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
46.9
64.7
82.5
87.9
56.5
73.1
89.7
91.1
91.1
66.1
81.5
96.9
94.2
94.2
75.7
89.9
104.1
97.4
97.4
96.9
106.3
99.4
99.4
103.9
108.4
101.4
101.4
90
52.6
67.3
82.0
92.3
59.3
75.6
91.9
96.0
95.7
66.0
83.9
101.8
99.6
99.3
72.7
92.2
111.8
103.3
103.0
99.2
114.8
105.9
105.6
106.2
117.8
108.6
108.2
44.1
62.6
81.1
80.7
56.2
71.1
86.0
83.5
85.1
68.4
79.7
91.0
86.4
88.0
80.5
88.3
96.0
89.2
90.9
95.4
97.8
90.9
92.6
102.5
99.7
92.6
94.4
65
45.9
49.7
50.3
53.5
54.2
57.3
58.1
57.1
57.3
56.8
56.5
38.3
41.8
38.1
45.2
41.1
48.7
44.1
43.5
42.1
38.4
40.1
55
349681-JTG-A-1007
J08XP (8.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
98.9
89.2
79.6
73.4
102.3
92.4
82.4
76.0
79.1
105.8
95.5
85.1
78.5
81.8
109.2
98.6
87.9
81.1
84.4
100.3
89.4
82.5
85.9
101.9
90.9
83.9
87.3
10.0
9.9
9.8
9.7
10.0
9.9
9.8
9.8
9.8
10.1
10.0
9.9
9.8
9.8
10.1
10.0
9.9
9.8
9.9
10.0
9.9
9.9
9.9
10.1
10.0
9.9
9.9
41.2
60.4
79.6
73.4
55.9
69.1
82.4
76.0
79.1
70.7
77.9
85.1
78.5
81.8
85.4
86.6
87.9
81.1
84.4
93.9
89.4
82.5
85.9
101.1
90.9
83.9
87.3
90
44.1
58.2
72.4
66.2
59.4
67.2
74.9
68.5
73.1
74.8
76.1
77.3
70.7
75.6
90.2
85.0
79.8
73.0
78.0
91.0
81.0
74.0
79.1
92.3
82.1
75.1
80.3
65
32.0
35.2
25.5
38.5
27.7
41.7
29.8
30.0
26.6
18.3
23.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
56
349681-JTG-A-1007
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
132.6
125.0
117.5
105.6
142.4
134.2
126.1
113.4
111.1
152.2
143.4
134.6
121.2
118.8
162.0
152.6
143.2
128.9
126.4
153.5
144.1
129.7
127.1
154.4
145.0
130.4
127.9
6.7
6.9
7.0
6.6
6.8
7.0
7.1
6.7
6.9
6.9
7.1
7.2
6.8
7.0
7.0
7.2
7.3
6.9
7.1
7.0
7.2
6.8
7.0
6.9
7.1
6.6
6.8
57.3
74.4
91.5
105.6
64.4
86.2
108.1
113.4
111.1
71.5
98.1
124.6
121.2
118.8
78.6
109.9
141.1
128.9
126.4
115.1
143.0
129.7
127.1
120.3
145.0
130.4
127.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
129.5
118.6
107.8
101.0
134.9
123.6
112.3
105.3
104.0
140.4
128.6
116.9
109.6
108.2
145.8
133.6
121.4
113.8
112.5
136.1
123.6
115.9
114.5
138.5
125.9
118.0
116.6
9.2
9.1
9.0
9.0
9.2
9.1
9.1
9.0
9.0
9.3
9.2
9.1
9.0
9.1
9.3
9.2
9.1
9.0
9.1
9.2
9.1
9.0
9.1
9.2
9.1
9.0
9.1
54.8
75.0
95.2
101.0
64.6
84.3
103.9
105.3
104.0
74.3
93.5
112.7
109.6
108.2
84.1
102.7
121.4
113.8
112.5
109.7
123.6
115.9
114.5
116.6
125.9
118.0
116.6
90
56.1
74.7
93.4
103.3
64.5
85.2
106.0
109.3
107.6
72.9
95.8
118.6
115.4
113.5
81.3
106.3
131.3
121.4
119.4
112.4
133.3
122.8
120.8
118.5
135.4
124.2
122.2
49.5
71.4
93.2
93.0
63.4
81.3
99.2
96.7
95.6
77.3
91.3
105.2
100.4
99.2
91.2
101.2
111.2
104.0
102.8
107.3
112.9
105.6
104.4
113.4
114.5
107.1
105.9
65
56.6
59.9
60.5
63.1
63.8
66.4
67.2
66.7
66.1
67.0
65.0
41.0
43.4
43.9
45.9
46.4
48.4
49.0
48.0
47.6
47.5
46.3
57
349681-JTG-A-1007
J10XP (10 Ton) (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
111.3
101.2
91.1
85.0
115.3
104.9
94.4
88.1
87.1
119.4
108.5
97.7
91.2
90.1
123.4
112.2
101.0
94.2
93.2
113.4
102.1
95.3
94.2
114.6
103.2
96.3
95.2
11.5
11.4
11.3
11.2
11.6
11.5
11.4
11.3
11.4
11.7
11.6
11.5
11.4
11.5
11.8
11.7
11.6
11.5
11.5
11.7
11.6
11.5
11.5
11.6
11.5
11.4
11.5
44.2
67.7
91.1
85.0
62.3
78.4
94.4
88.1
87.1
80.3
89.0
97.7
91.2
90.1
98.4
99.7
101.0
94.2
93.2
105.0
102.1
95.3
94.2
110.3
103.2
96.3
95.2
90
45.2
64.0
82.8
77.0
65.3
75.4
85.5
79.5
78.6
85.4
86.8
88.1
82.0
81.1
105.5
98.2
90.8
84.4
83.6
102.1
91.4
84.9
84.0
102.7
91.9
85.4
84.5
65
25.1
24.9
26.1
24.8
26.1
24.6
26.1
23.7
23.9
22.7
21.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
58
349681-JTG-A-1007
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
163.7
158.9
154.2
145.0
169.7
164.7
159.8
150.3
147.7
175.7
170.5
165.4
155.6
152.9
181.6
176.3
171.0
160.9
158.1
180.7
175.3
164.9
162.0
185.0
179.5
168.8
165.9
9.7
9.5
9.4
9.3
9.7
9.5
9.4
9.3
9.4
9.7
9.5
9.4
9.3
9.4
9.7
9.5
9.4
9.3
9.4
9.6
9.5
9.4
9.4
9.6
9.5
9.4
9.4
70.7
95.0
119.4
145.0
77.1
103.5
129.9
150.3
147.7
83.5
112.0
140.4
155.6
152.9
89.9
120.4
150.9
160.9
158.1
125.2
159.2
164.9
162.0
129.9
167.4
168.8
165.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
155.1
148.5
141.8
133.3
160.4
153.5
146.6
137.8
135.3
165.6
158.5
151.4
142.3
139.8
170.8
163.5
156.2
146.8
144.2
167.7
160.2
150.5
147.9
171.8
164.1
154.2
151.5
11.6
11.5
11.4
11.3
11.6
11.6
11.5
11.3
11.4
11.7
11.7
11.6
11.4
11.5
11.8
11.7
11.7
11.5
11.5
11.7
11.6
11.5
11.5
11.7
11.6
11.5
11.5
64.1
89.6
115.1
133.3
71.2
99.2
127.1
137.8
135.3
78.4
108.8
139.2
142.3
139.8
85.5
118.4
151.3
146.8
144.2
125.0
157.7
150.5
147.9
131.6
164.1
154.2
151.5
90
67.4
92.3
117.2
139.1
74.2
101.3
128.5
144.0
141.5
80.9
110.4
139.8
148.9
146.3
87.7
119.4
151.1
153.8
151.2
125.1
158.4
157.7
154.9
130.7
165.8
161.5
158.7
58.0
86.8
115.6
126.1
67.7
96.2
124.8
130.1
128.0
77.3
105.7
134.0
134.1
131.9
86.9
115.1
143.2
138.1
135.9
122.1
148.3
141.7
139.4
129.1
153.3
145.4
143.0
65
78.2
84.3
86.4
90.4
92.6
96.4
98.9
101.4
101.2
106.4
103.6
64.8
69.3
70.2
73.8
74.8
78.4
79.4
81.1
80.5
83.9
81.6
59
349681-JTG-A-1007
J12XP (12.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
139.5
131.8
124.1
118.9
143.6
135.7
127.8
122.4
120.6
147.7
139.6
131.5
125.9
124.1
151.8
143.5
135.1
129.4
127.6
147.4
138.8
133.0
131.0
151.3
142.5
136.5
134.5
14.4
14.2
14.1
14.0
14.4
14.3
14.1
14.0
14.1
14.5
14.3
14.1
14.1
14.1
14.5
14.3
14.2
14.1
14.1
14.4
14.2
14.1
14.1
14.4
14.2
14.2
14.2
52.0
84.1
116.1
118.9
64.1
93.3
122.5
122.4
120.6
76.2
102.5
128.8
125.9
124.1
88.3
111.7
135.1
129.4
127.6
119.1
138.8
133.0
131.0
126.5
142.5
136.5
134.5
90
47.4
81.4
115.3
111.7
62.4
90.4
118.4
114.7
113.3
77.3
99.4
121.5
117.8
116.3
92.2
108.4
124.6
120.8
119.2
116.2
128.1
124.2
122.6
123.9
131.7
127.6
126.0
65
49.2
51.8
54.6
54.4
57.4
57.0
60.2
59.0
59.8
61.0
59.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
60
349681-JTG-A-1007
Model
70
80
55
J06
(6.5)
XP
2600
70
80
55
3250
70
80
55
2250
70
80
55
J07
(7.5)
XP
3000
70
80
55
3750
70
80
55
2550
70
80
55
J08
(8.5)
XP
3400
70
80
55
4250
70
80
Capacity1 &
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
10
20
30
40
50
60
18.7
4.8
13.9
5.6
11.6
6.4
21.8
4.2
16.9
5.0
14.7
5.8
22.9
3.9
18.1
4.7
15.8
5.5
19.0
5.0
14.7
6.1
11.6
6.9
22.0
4.4
17.7
5.4
14.5
6.2
21.7
4.0
17.4
5.0
14.3
5.8
9.4
4.9
12.2
6.1
11.1
6.9
14.9
4.3
17.7
5.6
16.6
6.4
17.2
4.0
20.0
5.2
18.9
6.1
29.2
4.9
24.4
5.7
22.1
6.5
32.3
4.3
27.4
5.1
25.2
6.0
33.5
4.0
28.6
4.9
26.3
5.6
31.5
5.2
27.2
6.3
24.1
7.1
34.4
4.6
30.2
5.6
27.0
6.4
34.2
4.2
29.9
5.2
26.8
6.1
22.3
5.1
25.1
6.3
24.0
7.1
27.8
4.5
30.6
5.8
29.4
6.6
30.1
4.2
32.9
5.4
31.8
6.3
39.8
5.1
35.0
5.9
32.6
6.7
42.9
4.5
37.9
5.3
35.8
6.1
44.0
4.2
39.2
5.0
36.9
5.8
43.9
5.4
39.7
6.5
36.5
7.3
46.9
4.8
42.6
5.8
39.4
6.7
46.6
4.4
42.3
5.4
39.2
6.3
35.1
5.3
37.9
6.5
36.8
7.3
40.6
4.7
43.4
6.0
42.3
6.8
42.9
4.4
45.7
5.6
44.6
6.5
50.3
5.2
45.5
6.0
43.2
6.8
53.4
4.6
48.5
5.4
46.3
6.3
54.6
4.3
49.7
5.2
47.4
6.0
56.4
5.6
52.1
6.7
49.0
7.5
59.3
5.0
55.1
6.0
51.9
6.9
59.1
4.6
54.8
5.6
51.7
6.5
48.0
5.5
50.8
6.7
49.7
7.5
53.5
4.9
56.3
6.2
55.1
7.0
55.8
4.6
58.6
5.9
57.5
6.7
60.9
5.4
56.0
6.2
53.7
7.0
64.0
4.8
59.0
5.6
56.8
6.4
65.1
4.5
60.3
5.3
58.0
6.1
68.8
5.9
64.6
6.9
61.5
7.7
71.8
5.2
67.5
6.3
64.4
7.1
71.5
4.8
67.3
5.8
64.1
6.7
60.8
5.7
63.7
6.9
62.5
7.7
66.3
5.2
69.1
6.4
68.0
7.2
68.6
4.8
71.4
6.1
70.3
6.9
71.4
5.5
66.6
6.3
64.3
7.1
74.5
4.9
69.6
5.7
67.4
6.6
75.6
4.6
70.8
5.5
68.5
6.3
81.3
6.1
77.0
7.1
73.9
7.9
84.2
5.4
80.0
6.5
76.8
7.3
84.0
5.0
79.7
6.0
76.6
6.9
73.7
5.9
76.5
7.1
75.4
7.9
79.2
5.4
82.0
6.6
80.8
7.4
81.5
5.0
84.3
6.3
83.2
7.1
81.9
5.7
77.1
6.5
74.8
7.3
85.1
5.1
80.1
5.9
77.9
6.7
86.2
4.8
81.4
5.6
79.0
6.4
93.8
6.3
89.5
7.3
86.4
8.1
96.7
5.6
92.5
6.7
89.3
7.5
96.5
5.2
92.2
6.3
89.1
7.1
86.5
6.1
89.4
7.3
88.2
8.2
92.0
5.6
94.8
6.8
93.7
7.6
94.3
5.2
97.1
6.5
96.0
7.3
92.5
5.8
87.7
6.7
85.3
7.4
95.6
5.2
90.7
6.0
88.5
6.9
96.7
4.9
91.9
5.8
89.6
6.6
106.2
6.5
101.9
7.5
98.8
8.4
109.2
5.8
104.9
6.9
101.7
7.7
108.9
5.4
104.6
6.5
101.5
7.3
99.4
6.3
102.2
7.5
101.1
8.4
104.9
5.8
107.7
7.0
106.6
7.8
107.2
5.4
110.0
6.7
108.9
7.5
61
349681-JTG-A-1007
J06 thru 12 XP (Continued)
Size
(Tons)
Model
70
80
55
J10
(10)
XP
4000
70
80
55
5000
70
80
55
3750
70
80
55
J12
(12.5)
XP
5000
70
80
55
6250
70
80
Capacity1 &
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
10
20
30
40
50
60
14.5
5.9
11.2
7.0
7.8
7.9
24.6
5.5
21.2
6.7
17.9
7.6
21.2
5.0
17.8
6.2
14.4
7.0
26.2
8.0
22.8
9.5
19.5
10.7
34.3
7.2
30.9
8.7
27.6
9.9
36.3
6.8
32.9
8.3
29.6
9.5
29.4
6.0
26.0
7.2
22.7
8.1
39.5
5.7
36.1
6.8
32.8
7.7
36.0
5.2
32.6
6.3
29.3
7.2
45.3
8.4
41.9
9.9
38.7
11.1
53.4
7.6
50.1
9.1
46.7
10.3
55.5
7.2
52.0
8.7
48.8
9.9
44.3
6.2
40.9
7.4
37.6
8.3
54.3
5.8
51.0
7.0
47.6
7.9
50.9
5.3
47.5
6.5
44.2
7.4
64.5
8.8
61.0
10.3
57.8
11.5
72.6
8.0
69.2
9.5
65.8
10.7
74.6
7.6
71.1
9.1
67.9
10.3
59.1
6.4
55.7
7.5
52.4
8.4
69.2
6.0
65.8
7.2
62.5
8.1
65.8
5.5
62.4
6.6
59.0
7.5
83.6
9.2
80.2
10.7
76.9
11.9
91.7
8.4
88.3
9.9
85.0
11.1
93.7
8.0
90.3
9.5
87.0
10.7
74.0
6.5
70.6
7.7
67.3
8.6
84.1
6.2
80.7
7.3
77.4
8.2
80.6
5.6
77.2
6.8
73.9
7.7
102.7
9.6
99.3
11.1
96.1
12.3
110.8
8.8
107.5
10.3
104.1
11.5
112.8
8.4
109.4
9.9
106.2
11.1
88.9
6.7
85.5
7.9
82.1
8.8
98.9
6.3
95.5
7.5
92.2
8.4
95.5
5.8
92.1
7.0
88.8
7.9
121.9
10.0
118.4
11.5
115.2
12.7
130.0
9.2
126.6
10.7
123.2
11.9
132.0
8.8
128.5
10.3
125.3
11.5
103.7
6.9
100.3
8.0
97.0
8.9
113.8
6.5
110.4
7.6
107.1
8.5
110.3
6.0
107.0
7.1
103.6
8.0
141.0
10.4
137.6
11.9
134.3
13.1
149.1
9.6
145.7
11.1
142.4
12.3
151.1
9.2
147.7
10.7
144.4
11.9
118.6
7.0
115.2
8.2
111.9
9.1
128.7
6.6
125.3
7.8
122.0
8.7
125.2
6.1
121.8
7.3
118.5
8.2
160.1
10.8
156.7
12.3
153.5
13.5
168.2
10.0
164.8
11.5
161.5
12.7
170.2
9.6
166.8
11.1
163.6
12.3
1. These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh = 3.415 x
kW.
62
349681-JTG-A-1007
Airflow Performance
J06 thru 12 ZH Side Duct Application
J06ZH (6.5 Ton) Side Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
0.62
0.75
0.90
1.06
1.24
1.43
1.65
1.88
2.12
929
954
982
1013
1047
1084
1123
1165
1208
0.78
0.92
1.06
1.22
1.40
1.60
1.81
2.04
2.29
1095
1119
1147
1178
1212
1249
1288
-
1.20
1.33
1.48
1.64
1.82
2.02
2.23
-
1150
1175
1203
1234
1268
1304
-
1.59
1.72
1.87
2.03
2.21
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
897
925
956
990
1027
1066
1107
1151
1197
1245
0.75
0.90
1.06
1.24
1.43
1.65
1.88
2.12
2.39
2.67
954
982
1013
1047
1084
1123
1165
1208
1254
1302
1.20
1.35
1.51
1.69
1.89
2.10
2.33
2.58
2.84
3.12
1119
1147
1178
1212
1249
1288
1330
1374
1419
1467
1.72
1.87
2.03
2.21
2.40
2.62
2.85
3.10
3.36
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
755
765
776
787
800
814
829
846
864
884
906
0.73
0.83
0.94
1.04
1.16
1.28
1.43
1.59
1.76
1.96
2.17
893
904
914
925
938
952
967
984
1002
1022
1044
1.27
1.38
1.48
1.58
1.70
1.83
1.97
2.13
2.31
2.50
2.72
937
947
957
969
981
995
1010
1027
1046
1066
1087
1.44
1.55
1.65
1.76
1.87
2.00
2.14
2.30
2.48
2.67
2.89
1.96
2.07
2.17
2.27
2.39
2.52
2.66
2.82
3.00
3.19
3.41
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
63
349681-JTG-A-1007
0.94
1.04
1.16
1.28
1.43
1.59
1.76
1.96
2.17
2.41
2.66
2.93
3.22
824
835
847
861
877
893
912
932
953
976
1001
1027
1055
1.12
1.23
1.34
1.47
1.61
1.77
1.95
2.15
2.36
2.59
2.85
3.12
3.41
957
969
981
995
1010
1027
1046
1066
1087
1110
1135
-
2.17
2.27
2.39
2.52
2.66
2.82
3.00
3.19
3.41
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.88
1.02
1.18
1.36
1.55
1.77
2.00
2.25
2.52
2.81
3.12
3.45
3.80
4.16
4.54
4.94
861
877
893
912
932
953
976
1001
1027
1055
1084
1115
1147
1181
1216
1252
1.47
1.61
1.77
1.95
2.15
2.36
2.59
2.85
3.12
3.41
3.72
4.05
4.39
4.75
5.13
5.53
907
923
939
958
978
999
1022
1047
1073
1101
1130
1161
1193
1227
1262
1298
1.65
1.79
1.95
2.13
2.33
2.54
2.77
3.03
3.30
3.59
3.90
4.23
4.57
4.93
5.31
5.71
952
967
984
1002
1022
1044
1067
1092
1118
1146
1175
1206
1238
1271
1306
-
1079
1094
1111
1129
1149
1171
1194
1219
1245
1273
1302
1333
1365
1398
-
2.34
2.48
2.64
2.82
3.02
3.23
3.46
3.72
3.99
4.28
4.59
4.91
5.26
5.62
-
1119
1135
1152
1170
1190
1211
1235
1259
1285
1313
1343
1373
1405
-
2.52
2.66
2.82
3.00
3.19
3.41
3.64
3.89
4.16
4.45
4.76
5.09
5.44
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
64
349681-JTG-A-1007
924
952
986
1027
1071
1119
1171
1225
-
1.05
1.19
1.34
1.52
1.72
1.94
2.18
-
1147
1175
1210
1250
1294
1343
-
1384
1412
1447
1487
-
1.69
1.83
1.98
2.16
-
1469
1497
1532
-
1.89
2.03
2.18
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
952
986
1027
1071
1119
1171
1225
1282
1341
1401
1.19
1.34
1.52
1.72
1.94
2.18
2.45
2.73
3.04
3.37
1.65
1.81
1.98
2.18
2.40
2.65
2.91
3.20
-
1412
1447
1487
1532
1580
1632
1686
1742
-
1.83
1.98
2.16
2.36
2.58
2.82
3.09
3.37
-
1497
1532
1572
1617
1665
1717
1771
-
2.03
2.18
2.36
2.56
2.78
3.02
3.29
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
791
808
828
850
875
903
934
967
1002
1041
1082
0.88
0.99
1.11
1.26
1.42
1.60
1.81
2.04
2.29
2.56
2.86
841
858
878
900
925
953
983
1017
1052
1091
1132
1.01
1.12
1.25
1.39
1.55
1.74
1.94
2.17
2.42
2.69
2.99
1.14
1.25
1.37
1.52
1.68
1.86
2.07
2.30
2.55
2.82
3.12
936
953
973
995
1020
1048
1078
1112
1147
1186
1227
1.27
981
1.39 1025
1.37
999
1.49 1043
1.50 1018 1.62 1063
1.64 1041 1.76 1085
1.80 1066 1.92 1110
1.99 1093 2.11 1138
2.19 1124 2.32 1168
2.42 1157 2.54 1201
2.67 1193 2.80 1237
2.95 1231 3.07 1275
3.24 1272 3.36
3 HP & Field Supplied Drive
1.51
1.62
1.74
1.88
2.05
2.23
2.44
2.67
2.92
3.19
-
1069
1086
1106
1128
1153
1181
1212
1245
1280
1319
-
1.63
1.74
1.86
2.00
2.17
2.35
2.56
2.79
3.04
3.31
-
1111
1129
1149
1171
1196
1224
1254
1287
1323
1362
-
1.75
1.86
1.99
2.13
2.29
2.48
2.68
2.91
3.16
3.43
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
65
349681-JTG-A-1007
828
850
875
903
934
967
1002
1041
1082
1125
-
1.11
1.26
1.42
1.60
1.81
2.04
2.29
2.56
2.86
3.17
-
1.86
2.00
2.17
2.35
2.56
2.79
3.04
3.31
-
1149
1171
1196
1224
1254
1287
1323
1362
-
1.99
2.13
2.29
2.48
2.68
2.91
3.16
3.43
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
903
934
967
1002
1041
1082
1125
1171
1219
1269
1321
1376
1433
-
1.60
1.81
2.04
2.29
2.56
2.86
3.17
3.50
3.86
4.23
4.62
5.03
5.46
-
953
983
1017
1052
1091
1132
1175
1221
1269
1319
1371
1426
1483
-
1093
1124
1157
1193
1231
1272
1315
1361
1409
1459
1512
1566
-
2.11
2.32
2.54
2.80
3.07
3.36
3.67
4.01
4.36
4.74
5.13
5.54
-
1138
1168
1201
1237
1275
1316
1360
1405
1453
1504
1556
1611
-
2.48
2.68
2.91
3.16
3.43
3.73
4.04
4.38
4.73
5.10
5.50
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
66
349681-JTG-A-1007
0.73
0.85
1.00
1.15
1.33
1.52
1.73
1.95
2.20
951
977
1006
1039
1076
1115
1157
1201
-
0.88
1.00
1.14
1.30
1.47
1.67
1.88
2.10
-
1112
1138
1168
1201
1237
1276
1318
-
1.59
1.72
1.86
2.02
2.19
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
921
951
984
1020
1059
1101
1145
1192
1241
1292
0.85
1.00
1.15
1.33
1.52
1.73
1.95
2.20
2.46
2.74
1085
1114
1147
1183
1222
1264
1309
1355
1404
1455
1.26
1.40
1.56
1.73
1.92
2.13
2.36
2.60
2.86
3.14
1304
1333
1366
1402
1442
1483
1528
1574
1623
-
1.72
1.86
2.02
2.19
2.38
2.59
2.82
3.06
3.32
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
0.67
0.76
0.86
0.96
1.08
1.21
1.35
1.51
1.69
1.89
2.11
783
793
805
817
831
846
862
881
901
923
947
0.84
0.94
1.04
1.14
1.25
1.38
1.53
1.69
1.87
2.07
2.29
829
840
851
863
877
892
909
927
948
970
993
1.01
1.11
1.20
1.31
1.42
1.55
1.69
1.86
2.04
2.23
2.45
874
885
896
908
922
937
954
972
992
1014
1038
918
928
939
952
965
980
997
1016
1036
1058
1082
1.32
1.42
1.52
1.62
1.74
1.86
2.01
2.17
2.35
2.55
2.77
960
970
981
994
1007
1023
1039
1058
1078
1100
1124
1.48
1.57
1.67
1.78
1.89
2.02
2.16
2.32
2.50
2.70
2.92
1081
1091
1103
1115
1128
1144
1160
1179
1199
1221
1245
1.94
2.04
2.13
2.24
2.35
2.48
2.62
2.79
2.97
3.16
3.38
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
67
349681-JTG-A-1007
805
817
831
846
862
881
901
923
947
972
1000
1029
1059
1.04
1.14
1.25
1.38
1.53
1.69
1.87
2.07
2.29
2.52
2.78
3.06
3.35
851
863
877
892
909
927
948
970
993
1019
1046
1075
-
1.52
1.62
1.74
1.86
2.01
2.17
2.35
2.55
2.77
3.01
3.26
-
2.13
2.24
2.35
2.48
2.62
2.79
2.97
3.16
3.38
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
1.38
1.53
1.69
1.87
2.07
2.29
2.52
2.78
3.06
3.35
3.67
4.00
4.35
4.72
5.11
5.51
892
909
927
948
970
993
1019
1046
1075
1106
1138
1172
1207
1244
1283
1323
1.55
1.69
1.86
2.04
2.23
2.45
2.69
2.95
3.23
3.52
3.84
4.17
4.52
4.89
5.28
5.68
937
954
972
992
1014
1038
1064
1091
1120
1151
1183
1217
1252
1289
1328
-
1.71
1.85
2.02
2.20
2.39
2.61
2.85
3.11
3.39
3.68
4.00
4.33
4.68
5.05
5.44
-
1064
1080
1099
1119
1141
1165
1190
1218
1247
1277
1310
1344
1379
1416
-
2.17
2.31
2.48
2.66
2.86
3.07
3.31
3.57
3.85
4.14
4.46
4.79
5.14
5.51
-
1104
1121
1139
1159
1181
1205
1231
1258
1287
1318
1350
1384
1419
1456
-
2.32
2.47
2.63
2.81
3.01
3.23
3.47
3.72
4.00
4.29
4.61
4.94
5.29
5.66
-
1144
1160
1179
1199
1221
1245
1270
1298
1327
1357
1390
1424
1459
-
2.48
2.62
2.79
2.97
3.16
3.38
3.62
3.88
4.16
4.45
4.77
5.10
5.45
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
68
349681-JTG-A-1007
946
975
1012
1055
1102
1154
1208
1266
-
1.11
1.24
1.39
1.57
1.76
1.98
2.22
-
1315
1344
1381
1424
1471
-
1.52
1.66
1.81
1.98
2.17
-
1395
1424
1461
1503
-
1.68
1.81
1.96
2.14
-
1477
1507
1543
-
1.86
1.99
2.14
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
0.78
0.93
1.10
1.30
1.51
1.75
2.02
2.30
2.60
2.93
975
1012
1055
1102
1154
1208
1266
1326
1389
1453
0.95
1.10
1.27
1.47
1.69
1.92
2.19
2.47
2.77
3.10
1047
1084
1126
1174
1225
1280
1338
1398
1461
1525
1.10
1.25
1.43
1.62
1.84
2.08
2.34
2.62
2.93
3.25
1.51
1.66
1.84
2.03
2.25
2.49
2.75
3.03
3.33
-
1344
1381
1424
1471
1523
1578
1636
1696
-
1.66
1.81
1.98
2.17
2.39
2.63
2.89
3.17
-
1424
1461
1503
1551
1602
1657
1715
1775
-
1.81
1.96
2.14
2.33
2.55
2.79
3.05
3.33
-
1507
1543
1586
1634
1685
1740
1798
-
1.99
2.14
2.31
2.51
2.73
2.96
3.23
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
818
837
858
882
910
940
973
1009
1048
1090
1135
0.98
1.08
1.20
1.35
1.51
1.69
1.90
2.13
2.38
2.66
2.95
867
886
907
931
958
989
1022
1058
1097
1139
1184
1.09
1.20
1.32
1.46
1.63
1.81
2.02
2.25
2.50
2.78
3.07
1.21
1.31
1.44
1.58
1.74
1.93
2.13
2.36
2.61
2.89
3.18
960
1.32 1004 1.43
978
1.42 1022 1.53
1000 1.55 1044 1.65
1024 1.69 1068 1.80
1051 1.85 1095 1.96
1081 2.04 1125 2.14
1114 2.24 1158 2.35
1150 2.47 1195 2.58
1190 2.72 1234 2.83
1231 3.00 1276 3.11
1276 3.29 1320 3.40
3 HP & Field Supplied Drive
1047
1066
1087
1111
1138
1168
1202
1238
1277
1319
-
1.53
1.64
1.76
1.90
2.07
2.25
2.46
2.69
2.94
3.21
-
1089
1108
1129
1153
1181
1211
1244
1280
1319
1361
-
1.64
1.75
1.87
2.01
2.17
2.36
2.57
2.80
3.05
3.32
-
1131
1150
1171
1195
1222
1252
1286
1322
1361
1403
-
1.75
1.86
1.98
2.12
2.28
2.47
2.68
2.91
3.16
3.43
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
69
349681-JTG-A-1007
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
858
882
910
940
973
1009
1048
1090
1135
1182
-
1.20
1.35
1.51
1.69
1.90
2.13
2.38
2.66
2.95
3.27
-
907
931
958
989
1022
1058
1097
1139
1184
1231
-
1.32
1.46
1.63
1.81
2.02
2.25
2.50
2.78
3.07
3.39
-
1044
1068
1095
1125
1158
1195
1234
1276
1320
-
1.65
1.80
1.96
2.14
2.35
2.58
2.83
3.11
3.40
-
1087
1111
1138
1168
1202
1238
1277
1319
-
1.76
1.90
2.07
2.25
2.46
2.69
2.94
3.21
-
1129
1153
1181
1211
1244
1280
1319
1361
-
1.87
2.01
2.17
2.36
2.57
2.80
3.05
3.32
-
1171
1195
1222
1252
1286
1322
1361
1403
-
1.98
2.12
2.28
2.47
2.68
2.91
3.16
3.43
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
1.57
1.78
2.01
2.26
2.53
2.83
3.15
3.48
3.84
4.22
4.61
5.03
5.46
-
940
973
1009
1048
1090
1135
1182
1232
1285
1340
1398
1457
1519
-
1.69
1.90
2.13
2.38
2.66
2.95
3.27
3.61
3.96
4.34
4.74
5.15
5.58
-
989
1022
1058
1097
1139
1184
1231
1281
1334
1389
1446
1506
1568
-
1.81
2.02
2.25
2.50
2.78
3.07
3.39
3.72
4.08
4.46
4.85
5.27
5.70
-
2.14
2.35
2.58
2.83
3.11
3.40
3.72
4.06
4.41
4.79
5.19
5.60
-
1168
1202
1238
1277
1319
1364
1411
1461
1514
1569
1626
1686
-
2.25
2.46
2.69
2.94
3.21
3.51
3.83
4.16
4.52
4.90
5.29
5.71
-
1211
1244
1280
1319
1361
1406
1453
1503
1556
1611
1669
-
2.36
2.57
2.80
3.05
3.32
3.62
3.93
4.27
4.63
5.01
5.40
-
1252
1286
1322
1361
1403
1447
1495
1545
1598
1653
1710
-
2.47
2.68
2.91
3.16
3.43
3.73
4.05
4.38
4.74
5.12
5.51
-
1. Blower performance includes gas heat exchangers and 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
70
349681-JTG-A-1007
0.63
0.76
0.91
1.08
1.26
1.46
1.68
1.92
2.18
929
955
985
1018
1054
1093
1135
1179
-
0.79
0.92
1.07
1.24
1.42
1.63
1.85
2.09
-
1094
1120
1150
1183
1220
1259
1301
-
1.20
1.34
1.48
1.65
1.84
2.04
2.26
-
1150
1176
1206
1239
1275
1315
-
1.59
1.72
1.87
2.04
2.22
-
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
898
928
961
998
1037
1079
1123
1169
1218
1268
0.76
0.91
1.08
1.26
1.46
1.68
1.92
2.18
2.45
2.74
955
985
1018
1054
1093
1135
1179
1226
1274
1324
1.21
1.36
1.52
1.71
1.91
2.13
2.37
2.63
2.90
3.19
1120
1150
1183
1220
1259
1301
1345
1391
1440
1490
1.72
1.87
2.04
2.22
2.43
2.65
2.89
3.14
3.42
-
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
734
741
748
756
765
774
785
798
811
826
842
0.65
0.74
0.82
0.92
1.02
1.13
1.25
1.39
1.55
1.72
1.92
783
790
797
805
813
823
834
846
860
874
890
1.21
1.30
1.39
1.48
1.58
1.69
1.82
1.96
2.12
2.29
2.48
921
928
936
943
952
962
973
985
999
1013
1029
1.39
1.48
1.57
1.66
1.76
1.87
2.00
2.14
2.29
2.47
2.66
966
972
980
987
996
1006
1017
1029
1043
1057
1073
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
71
349681-JTG-A-1007
0.82
0.92
1.02
1.13
1.25
1.39
1.55
1.72
1.92
2.13
2.35
2.60
2.86
797
805
813
823
834
846
860
874
890
908
926
946
967
1.02
1.11
1.21
1.32
1.45
1.59
1.75
1.92
2.11
2.32
2.55
2.79
3.06
844
852
861
871
882
894
907
922
938
955
974
993
1014
1.57
1.66
1.76
1.87
2.00
2.14
2.29
2.47
2.66
2.87
3.10
3.34
-
980
987
996
1006
1017
1029
1043
1057
1073
1091
1109
-
1.74
1.83
1.93
2.05
2.17
2.31
2.47
2.64
2.83
3.04
3.27
-
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.71
0.84
0.98
1.14
1.31
1.50
1.71
1.94
2.19
2.45
2.73
3.03
3.34
3.67
4.02
4.39
724
735
747
761
776
792
809
827
847
868
890
914
938
964
990
1018
1.51
1.63
1.78
1.93
2.11
2.30
2.51
2.74
2.98
3.25
3.53
3.82
4.14
4.47
4.82
5.18
917
928
940
953
968
984
1001
1020
1040
1061
1083
1106
1131
1156
1183
1211
1.69
1.82
1.96
2.12
2.29
2.48
2.69
2.92
3.16
3.43
3.71
4.01
4.32
4.65
5.00
5.36
962
973
985
999
1013
1029
1046
1065
1085
1106
1128
1151
1176
1201
1228
1256
2.39
2.52
2.66
2.81
2.99
3.18
3.39
3.62
3.86
4.13
4.41
4.70
5.02
5.35
5.70
-
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
72
349681-JTG-A-1007
923
953
990
1033
1081
1132
1187
1245
-
1.05
1.19
1.35
1.53
1.74
1.97
2.22
-
1147
1177
1214
1257
1305
1356
-
1385
1414
1451
1495
-
1.68
1.82
1.98
2.17
-
1469
1499
1536
-
1.88
2.02
2.18
-
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
953
990
1033
1081
1132
1187
1245
1305
1367
1430
1.19
1.35
1.53
1.74
1.97
2.22
2.49
2.79
3.11
3.45
1.65
1.81
1.99
2.20
2.43
2.68
2.96
3.25
-
1414
1451
1495
1542
1594
1649
1706
1766
-
1.82
1.98
2.17
2.37
2.60
2.85
3.13
3.43
-
1499
1536
1579
1627
1679
1734
1791
-
2.02
2.18
2.36
2.57
2.80
3.05
3.33
-
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
770
784
801
819
841
864
890
918
948
981
1016
0.83
0.93
1.04
1.17
1.33
1.50
1.69
1.91
2.14
2.40
2.68
918
933
949
968
989
1012
1038
1066
1097
1130
1164
1.22
1.32
1.44
1.57
1.72
1.89
2.09
2.30
2.54
2.80
3.07
1098
1112
1129
1148
1169
1192
1218
1246
1276
1309
-
1.71
1.81
1.92
2.06
2.21
2.38
2.58
2.79
3.03
3.28
-
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
73
349681-JTG-A-1007
801
819
841
864
890
918
948
981
1016
1053
1092
-
1.04
1.17
1.33
1.50
1.69
1.91
2.14
2.40
2.68
2.98
3.29
-
1.80
1.94
2.09
2.26
2.45
2.67
2.91
3.16
3.44
-
1129
1148
1169
1192
1218
1246
1276
1309
-
1.92
2.06
2.21
2.38
2.58
2.79
3.03
3.28
-
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
1.50
1.69
1.91
2.14
2.40
2.68
2.98
3.29
3.63
3.98
4.35
4.74
5.15
5.57
915
941
969
999
1032
1067
1104
1143
1184
1228
1273
1319
1368
1418
1.64
1.83
2.04
2.28
2.54
2.81
3.11
3.43
3.76
4.12
4.49
4.88
5.29
5.71
964
990
1018
1049
1082
1117
1154
1193
1234
1277
1322
1369
1418
-
2.02
2.21
2.43
2.66
2.92
3.20
3.49
3.81
4.15
4.50
4.87
5.26
5.67
-
1104
1130
1158
1189
1222
1256
1294
1333
1374
1417
1462
1509
-
2.14
2.33
2.55
2.78
3.04
3.32
3.62
3.93
4.27
4.62
5.00
5.38
-
1. Blower performance includes 2 filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
74
349681-JTG-A-1007
RPM Selection
Size
(Tons)
J06
(6.5)
Model
ZH
J07
(7.5)
ZH
J08
(8.5)
ZH
J10
(10)
ZH
J12
(12.5)
ZH
J06
(6.5)
ZR
J07
(7.5)
ZR
J08
(8.5)
ZR
J10
(10)
ZR
J12
(12.5)
ZR
J06
(6.5)
XP
J07
(7.5)
XP
J08
(8.5)
XP
J10
(10)
XP
J12
(12.5)
XP
HP
1.5
2
1.5
3
2
3
2
3
3
5
1.5
2
1.5
3
2
3
2
3
3
5
1.5
2
1.5
3
2
3
2
3
3
5
Max
BHP
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
Motor
Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower
Sheave
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
6 Turns
Open
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
5 Turns
Open
897
1039
897
1088
735
880
785
880
880
1095
897
1039
897
1088
735
880
785
880
880
1095
897
1039
897
1088
735
880
785
880
880
1095
4 Turns
Open
945
1094
945
1147
775
928
821
928
928
1136
945
1094
945
1147
775
928
821
928
928
1136
945
1094
945
1147
775
928
821
928
928
1136
3 Turns
Open
991
1150
991
1205
815
972
858
972
972
1175
991
1150
991
1205
815
972
858
972
972
1175
991
1150
991
1205
815
972
858
972
972
1175
2 Turns
Open
1035
1207
1035
1265
851
1016
901
1016
1016
1216
1035
1207
1035
1265
851
1016
901
1016
1016
1216
1035
1207
1035
1265
851
1016
901
1016
1016
1216
1 Turn
Open
1079
1256
1079
1312
889
1067
940
1067
1067
1272
1079
1256
1079
1312
889
1067
940
1067
1067
1272
1079
1256
1079
1312
889
1067
940
1067
1067
1272
Fully
Closed
1126
1308
1126
1365
930
1110
980
1110
1110
N/A
1126
1308
1126
1365
930
1110
980
1110
1110
N/A
1126
1308
1126
1365
930
1110
980
1110
1110
N/A
75
349681-JTG-A-1007
Model
J06 (6.5)
J07 (7.5)
ZH/ZR/XP1
J08 (8.5)
J10 (10)
J12 (12.5)
ZH/ZR/XP1
CFM
Cooling Only1
Economizer2 3
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.00
-0.01
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
-0.09
-0.09
-0.10
-0.11
0.06
0.07
0.08
0.09
0.11
0.12
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.52
0.56
0.60
0.07
0.09
0.11
0.13
0.16
0.18
0.20
0.22
0.24
0.27
0.29
0.31
0.30
0.35
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
09
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
18
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
36
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
54
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
1. Add these values to the available static resistance in the respective Blower Performance Tables. J**XP units do not require cooling only
adjustments.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
76
349681-JTG-A-1007
Drive Selection
1.
2.
3.
Using the operating point determined from steps 1 & 2, locate this point on the appropriate supply air blower performance table.
(Linear interpolation may be necessary.)
4.
Noting the RPM and BHP from step 3, locate the appropriate model and drive on the RPM selection table.
5.
Review the BHP compared to the motor options available. Select the appropriate motor.
6.
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
7.
Example
1.
19000 CFM
2.
5.4 iwg
3.
Using the supply air blower performance table below, the following data point was located: 1150 RPM & 36 BHP.
4.
Using the RPM selection table below, Size X and Model Y is found.
5.
36 BHP exceeds the maximum continuous BHP rating of the 30 HP motor. The 40 HP motor is required.
6.
1150 RPM is within the range of the 30 & 40 HP drives, but step 5 requires the 40 HP motor.
7.
Using the 40 HP motor and drive, 5.5 turns open will achieve 1150 RPM.
10.00
12.00
14.00
16.00
950
1000
1050
1100
22.00
24.00
26.00
28.00
1000
1050
1100
1150
34.00
36.00
38.00
40.00
1150
1200
1250
1300
46.00
48.00
50.00
52.00
Model
HP
30
40
Max
BHP
34.50
46.00
Motor
Sheave
1VL51
1VL63
Blower
Sheave
BK99
BK67
6 Turns
Open
1000
1125
5 Turns
Open
1025
1175
4 Turns
Open
1045
1250
3 Turns
Open
1060
1325
2 Turns
Open
1110
1400
1 Turn
Open
1150
1475
Fully
Closed
N/A
N/A
77
349681-JTG-A-1007
0
1.060
1.039
1.019
1.000
0.982
0.964
0.946
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
Altitude (Ft.)
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
1.100
1.050
Correction Factor
1.000
Sea Level
0.950
1000 ft
0.900
2000 ft
0.850
3000 ft
0.800
5000 ft
0.750
6000 ft
7000 ft
4000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40
50
60
70
80
90
100
78
349681-JTG-A-1007
Size
(Tons)
Model
J06
(6.5)
J07
(7.5)
J08
(8.5)
J10
(10)
J12
(12.5)
Heat Size
Cooling
10
15
10
15
10
15
15
20
15
20
ZH/ZR
ZH/ZR
ZH/ZR
ZH/ZR
ZH/ZR
Heating
Min
1950
1950
2250
2250
2550
2550
3000
3000
3750
3750
Max
3250
3250
3750
3750
4250
4250
5000
5000
6250
6250
Min
1950
1950
2250
2250
2550
2550
3000
3000
3750
3750
Max
3250
3250
3750
3750
4250
4250
5000
5000
6250
6250
9
1950
1950
1950
2250
2250
2250
2550
2550
2550
-
Model
Voltage
J06
(6.5)
ZH/ZR/XP
J07
(7.5)
ZH/ZR/XP
J08
(8.5)
ZH/ZR/XP
J10
(10)
ZH/ZR/XP
J12
(12.5)
ZH/ZR/XP
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
54
3500
3000
3500
4000
3750
3750
Motor
Model
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
ZH/ZR/XP
HP
RPM
Eff.
SF
Frame
1-1/2
2
1-1/2
3
2
3
2
3
3
5
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.87
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
56
56
56
56
56
56
56
56
56
184T
Motor Sheave
Datum Dia.
Bore (in.)
(in.)
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
4.3 - 5.3
1-1/8
Model
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
Datum Dia.
Bore (in.)
(in.)
7.0
1
6.0
1
7.0
1
5.7
1
8.5
1
7.0
1
8.0
1
7.0
1
7.0
1
6.7
1
Model
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Voltage
2PE04703225
2PE04703246
2PE04703258
208/230-1-60
460-1-60
575-1-60
HP
3/4
3/4
3/4
Motor
RPM1
1075
1075
1050
QTY
1
1
1
LRA
7.8
3.4
2.9
Motor
FLA
5
2.2
1.5
MCA
6.3
2.8
1.9
Fuse Size
10
5
4
CFM @
0.1 ESP
3800
3800
3800
79
349681-JTG-A-1007
kW Capacity Multipliers1
Applied
208
230
460
575
240
480
600
0.75
0.92
0.92
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Sound Performance
Indoor Sound Power Levels
Size
(Tons)
J06
(6.5)
J07
(7.5)
J08
(8.5)
J10
(10)
J12
(12.5)
Model
CFM
ESP
(IWG)
Blower
RPM
BHP
Sound Rating1
dB (A)
63
8000
ZH/ZR/XP
2600
0.6
812
1.14
74
71
73
73
71
69
65
65
60
ZH/ZR/XP
3000
0.6
854
1.47
77
74
76
76
74
72
68
68
63
ZH/ZR/XP
3400
0.6
872
1.65
80
77
79
79
77
75
71
71
66
ZH/ZR/XP
4000
0.6
959
2.29
83
80
82
82
80
78
74
74
69
ZH/ZR/XP
5000
0.6
1132
3.74
87
84
86
86
84
82
78
78
73
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
Model
Sound Rating1
dB (A)
125
8000
ZH
83
88.0
82.5
81.5
78.0
73.0
69.0
62.0
ZH
83
89.5
83.5
82.0
78.0
72.5
68.0
60.5
ZH
90
93.5
92.5
88.0
84.5
79.0
74.5
68.0
ZH
90
94.0
92.0
88.5
84.5
80.0
75.5
68.5
ZH
84
90.0
84.5
81.5
77.5
72.0
68.5
61.5
ZR/XP
83
88.0
82.5
81.5
78.0
73.0
69.0
62.0
ZR/XP
83
89.5
83.5
82.0
78.0
72.5
68.0
60.5
ZR/XP
83
89.0
84.5
81.5
78.0
72.5
68.5
70.5
ZR/XP
83
89.5
83.5
81.0
78.0
72.0
68.5
70.5
ZR/XP
84
90.0
84.5
81.5
77.5
72.0
68.5
61.5
80
349681-JTG-A-1007
Electrical Data
J06 thru 12 ZH Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
12.8
95.0
20.0
1.5
6.2
5.5
0.0
230
12.8
95.0
20.0
1.5
6.2
5.5
0.0
460
6.4
45.0
10.0
0.8
3.1
2.2
0.0
575
5.4
38.0
8.5
0.6
2.4
1.8
0.0
208
1.5
6.2
5.5
0.0
230
1.5
6.2
5.5
0.0
460
7.7
50.0
12.0
0.8
3.1
2.2
0.0
575
6.4
40.0
10.0
0.6
2.4
1.8
0.0
208
3.5
8.2
5.5
0.0
230
3.5
8.2
5.5
0.0
460
8.3
60.0
13.0
1.6
4.1
2.2
0.0
575
6.7
40.0
10.5
1.3
3.6
1.8
0.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
38.0
38.0
54.6
70.2
96.2
38.0
38.0
61.9
79.9
110.0
19.1
19.1
30.9
40.0
55.0
15.8
15.8
24.7
31.9
43.9
42.3
42.3
54.6
70.2
96.2
42.3
42.3
61.9
79.9
110.0
22.0
22.0
30.9
40.0
55.0
18.0
18.0
24.7
31.9
43.9
51.2
51.2
57.1
72.7
98.7
51.2
51.2
64.4
82.4
112.5
26.0
26.0
32.2
41.2
56.2
21.3
21.3
26.2
33.4
45.4
43.5
43.5
61.5
77.1
103.1
43.5
43.5
68.8
86.8
116.9
21.3
21.3
33.7
42.7
57.7
17.6
17.6
26.9
34.1
46.1
47.8
47.8
61.5
77.1
103.1
47.8
47.8
68.8
86.8
116.9
24.2
24.2
33.7
42.7
57.7
19.8
19.8
26.9
34.1
46.1
56.7
56.7
64.0
79.6
105.6
56.7
56.7
71.3
89.3
119.4
28.2
28.2
34.9
44.0
59.0
23.1
23.1
28.4
35.6
47.6
81
349681-JTG-A-1007
J06 thru 12 ZH Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
3.5
8.2
5.5
0.0
230
3.5
8.2
5.5
0.0
460
9.6
70.0
15.0
1.6
4.1
2.2
0.0
575
7.4
53.0
11.5
1.3
3.6
1.8
0.0
208
1.5
10.9
5.5
0.0
230
1.5
10.9
5.5
0.0
460
11.8
75.0
16.5
0.8
5.3
2.2
0.0
575
8.6
54.0
12.0
0.6
4.1
1.8
0.0
J10
(10)
J12
(12.5)
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
55.5
57.1
72.7
98.7
151.1
55.5
64.4
82.4
112.5
140.2
28.9
32.2
41.2
56.2
70.1
22.9
26.2
33.4
45.4
56.5
73.2
73.2
76.1
102.1
154.5
73.2
73.2
85.8
115.9
143.5
35.1
35.1
42.7
57.7
71.6
25.9
26.8
34.0
46.0
57.1
61.0
64.0
79.6
105.6
158.0
61.0
71.3
89.3
119.4
147.0
31.1
34.9
44.0
59.0
72.8
24.7
28.4
35.6
47.6
58.7
78.7
78.7
83.0
109.0
161.4
78.7
78.7
92.7
122.7
150.4
37.3
37.3
45.5
60.5
74.3
27.7
29.0
36.2
48.3
59.3
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
82
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
12.8
95.0
20.0
1.5
8.2
5.5
0.0
230
12.8
95.0
20.0
1.5
8.2
5.5
0.0
460
6.4
45.0
10.0
0.8
4.1
2.2
0.0
575
5.4
38.0
8.5
0.6
3.6
1.8
0.0
208
1.5
10.9
5.5
0.0
230
1.5
10.9
5.5
0.0
460
7.7
50.0
12.0
0.8
5.3
2.2
0.0
575
6.4
40.0
10.0
0.6
4.1
1.8
0.0
208
3.5
10.9
5.5
0.0
230
3.5
10.9
5.5
0.0
460
8.3
60.0
13.0
1.6
5.3
2.2
0.0
575
6.7
40.0
10.5
1.3
4.1
1.8
0.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
40.0
40.0
57.1
72.7
98.7
40.0
40.0
64.4
82.4
112.5
20.1
20.1
32.2
41.2
56.2
17.0
17.0
26.2
33.4
45.4
47.0
47.0
60.5
76.1
102.1
47.0
47.0
67.8
85.8
115.9
24.2
24.2
33.7
42.7
57.7
19.7
19.7
26.8
34.0
46.0
53.9
53.9
60.5
76.1
102.1
53.9
53.9
67.8
85.8
115.9
27.2
27.2
33.7
42.7
57.7
21.8
21.8
26.8
34.0
46.0
45.5
45.5
64.0
79.6
105.6
45.5
45.5
71.3
89.3
119.4
22.3
22.3
34.9
44.0
59.0
18.8
18.8
28.4
35.6
47.6
52.5
52.5
67.3
83.0
109.0
52.5
52.5
74.6
92.7
122.7
26.4
26.4
36.4
45.5
60.5
21.5
21.5
29.0
36.2
48.3
59.4
59.4
67.3
83.0
109.0
59.4
59.4
74.6
92.7
122.7
29.4
29.4
36.4
45.5
60.5
23.6
23.6
29.0
36.2
48.3
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
50
50
50
60
70
80
80
100
110
50
50
50
50
70
80
90
90
125
125
25
25
25
25
35
35
45
45
60
60
20
20
20
20
30
30
35
40
50
50
60
60
60
60
70
70
80
90
110
110
60
60
60
60
70
80
90
100
125
125
30
30
30
30
35
40
45
50
60
70
25
25
25
25
30
30
35
40
50
50
60
70
60
70
70
70
80
90
110
110
60
70
60
70
70
80
90
100
125
125
35
35
35
35
35
40
45
50
60
70
25
30
25
30
30
30
35
40
50
50
83
349681-JTG-A-1007
J06 thru 12 ZH Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
3.5
10.9
5.5
0.0
230
3.5
10.9
5.5
0.0
460
9.6
70.0
15.0
1.6
5.3
2.2
0.0
575
7.4
53.0
11.5
1.3
4.1
1.8
0.0
208
1.5
16.1
5.5
0.0
230
1.5
16.1
5.5
0.0
460
11.8
75.0
16.5
0.8
8.1
2.2
0.0
575
8.6
54.0
12.0
0.6
6.0
1.8
0.0
J10
(10)
J12
(12.5)
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
58.2
60.5
76.1
102.1
154.5
58.2
67.8
85.8
115.9
143.5
30.1
33.7
42.7
57.7
71.6
23.4
26.8
34.0
46.0
57.1
78.4
78.4
82.6
108.6
161.0
78.4
78.4
92.3
122.4
150.0
37.9
37.9
46.2
61.2
75.1
27.8
29.2
36.4
48.4
59.5
63.7
67.3
83.0
109.0
161.4
63.7
74.6
92.7
122.7
150.4
32.3
36.4
45.5
60.5
74.3
25.2
29.0
36.2
48.3
59.3
83.9
83.9
89.5
115.5
167.9
83.9
83.9
99.2
129.2
156.9
40.1
40.1
49.0
64.0
77.8
29.6
31.4
38.6
50.6
61.7
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
70
80
80
90
110
110
175
175
70
80
70
80
90
100
125
125
175
175
35
40
35
40
45
50
60
70
80
80
30
30
30
30
35
40
50
50
70
70
100
100
100
100
100
100
110
125
175
175
100
100
100
100
100
100
125
150
175
175
45
50
45
50
50
50
70
70
90
90
35
35
35
35
40
40
50
60
70
70
84
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
12.8
95.0
20.0
1.5
6.2
5.5
10.0
230
12.8
95.0
20.0
1.5
6.2
5.5
10.0
460
6.4
45.0
10.0
0.8
3.1
2.2
5.0
575
5.4
38.0
8.5
0.6
2.4
1.8
4.0
208
1.5
6.2
5.5
10.0
230
1.5
6.2
5.5
10.0
460
7.7
50.0
12.0
0.8
3.1
2.2
5.0
575
6.4
40.0
10.0
0.6
2.4
1.8
4.0
208
3.5
8.2
5.5
10.0
230
3.5
8.2
5.5
10.0
460
8.3
60.0
13.0
1.6
4.1
2.2
5.0
575
6.7
40.0
10.5
1.3
3.6
1.8
4.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
48.0
48.0
67.1
82.7
108.7
48.0
48.0
74.4
92.4
122.5
24.1
24.1
37.2
46.2
61.2
19.8
19.8
29.7
36.9
48.9
52.3
52.3
67.1
82.7
108.7
52.3
52.3
74.4
92.4
122.5
27.0
27.0
37.2
46.2
61.2
22.0
22.0
29.7
36.9
48.9
61.2
61.2
69.6
85.2
111.2
61.2
61.2
76.9
94.9
125.0
31.0
31.0
38.4
47.5
62.5
25.3
25.3
31.2
38.4
50.4
53.5
53.5
74.0
89.6
115.6
53.5
54.2
81.3
99.3
129.4
26.3
26.4
39.9
49.0
64.0
21.6
21.6
31.9
39.1
51.1
57.8
57.8
74.0
89.6
115.6
57.8
57.8
81.3
99.3
129.4
29.2
29.2
39.9
49.0
64.0
23.8
23.8
31.9
39.1
51.1
66.7
66.7
76.5
92.1
118.1
66.7
66.7
83.8
101.8
131.9
33.2
33.2
41.2
50.2
65.2
27.1
27.1
33.4
40.6
52.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
60
60
60
70
80
90
90
110
125
60
60
60
60
80
90
100
100
125
150
30
30
30
30
40
40
50
50
70
70
25
25
25
25
30
35
40
40
50
60
60
70
60
70
70
80
90
90
110
125
60
70
60
70
80
90
100
100
125
150
30
35
30
35
40
40
50
50
70
70
25
30
25
30
30
35
40
40
50
60
70
80
70
80
70
80
90
100
125
125
70
80
70
80
80
90
100
110
125
150
35
40
35
40
40
45
50
60
70
70
30
30
30
30
35
35
40
45
60
60
85
349681-JTG-A-1007
J06 thru 12 ZH Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
3.5
8.2
5.5
10.0
230
3.5
8.2
5.5
10.0
460
9.6
70.0
15.0
1.6
4.1
2.2
5.0
575
7.4
53.0
11.5
1.3
3.6
1.8
4.0
208
1.5
10.9
5.5
10.0
230
1.5
10.9
5.5
10.0
460
11.8
75.0
16.5
0.8
5.3
2.2
5.0
575
8.6
54.0
12.0
0.6
4.1
1.8
4.0
J10
(10)
J12
(12.5)
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
65.5
69.6
85.2
111.2
163.6
65.5
76.9
94.9
125.0
152.7
33.9
38.4
47.5
62.5
76.3
26.9
31.2
38.4
50.4
61.5
83.2
83.2
88.6
114.6
167.0
83.2
83.2
98.3
128.4
156.0
40.1
40.1
49.0
64.0
77.8
29.9
31.8
39.0
51.0
62.1
71.0
76.5
92.1
118.1
170.5
71.0
83.8
101.8
131.9
159.5
36.1
41.2
50.2
65.2
79.1
28.7
33.4
40.6
52.6
63.7
88.7
88.7
95.5
121.5
173.9
88.7
88.7
105.2
135.2
162.9
42.3
42.7
51.7
66.7
80.6
31.7
34.0
41.2
53.3
64.3
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
80
80
80
80
90
100
125
125
175
175
80
80
80
90
100
110
125
150
175
175
40
45
40
45
50
60
70
70
90
90
30
35
35
35
40
45
60
60
70
70
100
110
100
110
100
110
125
125
175
175
100
110
100
110
100
110
150
150
175
175
50
50
50
50
50
60
70
70
90
90
35
40
35
40
40
45
60
60
70
70
86
349681-JTG-A-1007
J06 thru 12 ZH Hi Static Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
12.8
95.0
20.0
1.5
8.2
5.5
10.0
230
12.8
95.0
20.0
1.5
8.2
5.5
10.0
460
6.4
45.0
10.0
0.8
4.1
2.2
5.0
575
5.4
38.0
8.5
0.6
3.6
1.8
4.0
208
1.5
10.9
5.5
10.0
230
1.5
10.9
5.5
10.0
460
7.7
50.0
12.0
0.8
5.3
2.2
5.0
575
6.4
40.0
10.0
0.6
4.1
1.8
4.0
208
3.5
10.9
5.5
10.0
230
3.5
10.9
5.5
10.0
460
8.3
60.0
13.0
1.6
5.3
2.2
5.0
575
6.7
40.0
10.5
1.3
4.1
1.8
4.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
50.0
50.0
69.6
85.2
111.2
50.0
50.0
76.9
94.9
125.0
25.1
25.1
38.4
47.5
62.5
21.0
21.0
31.2
38.4
50.4
57.0
57.0
73.0
88.6
114.6
57.0
57.0
80.3
98.3
128.4
29.2
29.2
39.9
49.0
64.0
23.7
23.7
31.8
39.0
51.0
63.9
63.9
73.0
88.6
114.6
63.9
63.9
80.3
98.3
128.4
32.2
32.2
39.9
49.0
64.0
25.8
25.8
31.8
39.0
51.0
55.5
55.5
76.5
92.1
118.1
55.5
56.7
83.8
101.8
131.9
27.3
27.7
41.2
50.2
65.2
22.8
22.8
33.4
40.6
52.6
62.5
62.5
79.8
95.5
121.5
62.5
62.5
87.1
105.2
135.2
31.4
31.4
42.7
51.7
66.7
25.5
25.5
34.0
41.2
53.3
69.4
69.4
79.8
95.5
121.5
69.4
69.4
87.1
105.2
135.2
34.4
34.4
42.7
51.7
66.7
27.6
27.6
34.0
41.2
53.3
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
60
60
60
70
80
90
100
125
125
60
60
60
60
80
90
100
110
125
150
30
30
30
30
40
45
50
60
70
70
25
25
25
25
35
35
40
45
60
60
70
70
70
70
80
80
90
100
125
125
70
70
70
70
90
90
100
110
150
150
35
35
35
35
40
45
50
60
70
70
30
30
30
30
35
35
40
45
60
60
70
80
70
80
80
80
90
100
125
125
70
80
70
80
90
90
100
110
150
150
40
40
40
40
40
45
50
60
70
70
30
30
30
30
35
35
40
45
60
60
87
349681-JTG-A-1007
J06 thru 12 ZH Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
3.5
10.9
5.5
10.0
230
3.5
10.9
5.5
10.0
460
9.6
70.0
15.0
1.6
5.3
2.2
5.0
575
7.4
53.0
11.5
1.3
4.1
1.8
4.0
208
1.5
16.1
5.5
10.0
230
1.5
16.1
5.5
10.0
460
11.8
75.0
16.5
0.8
8.1
2.2
5.0
575
8.6
54.0
12.0
0.6
6.0
1.8
4.0
J10
(10)
J12
(12.5)
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
68.2
73.0
88.6
114.6
167.0
68.2
80.3
98.3
128.4
156.0
35.1
39.9
49.0
64.0
77.8
27.4
31.8
39.0
51.0
62.1
88.4
88.4
95.1
121.1
173.5
88.4
88.4
104.8
134.9
162.5
42.9
43.4
52.5
67.5
81.3
31.8
34.2
41.4
53.4
64.5
73.7
79.8
95.5
121.5
173.9
73.7
87.1
105.2
135.2
162.9
37.3
42.7
51.7
66.7
80.6
29.2
34.0
41.2
53.3
64.3
93.9
93.9
102.0
128.0
180.4
93.9
93.9
111.7
141.7
169.4
45.1
46.2
55.2
70.2
84.1
33.6
36.4
43.6
55.6
66.7
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
80
90
80
90
90
100
125
125
175
175
80
90
90
90
100
110
150
150
175
175
40
45
40
45
50
60
70
70
90
90
30
35
35
35
40
45
60
60
70
70
110
110
110
110
110
110
125
150
175
200
110
110
110
110
110
125
150
150
175
175
50
50
50
50
60
60
70
80
90
90
40
40
40
40
45
45
60
60
70
70
88
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
6.2
5.5
0.0
230
14.1
95.0
22.0
1.5
6.2
5.5
0.0
460
6.4
45.0
10.0
0.8
3.1
2.2
0.0
575
5.4
38.0
8.5
0.6
2.4
1.8
0.0
208
1.5
6.2
5.5
0.0
230
1.5
6.2
5.5
0.0
460
7.7
50.0
12.0
0.8
3.1
2.2
0.0
575
6.4
40.0
10.0
0.6
2.4
1.8
0.0
208
1.5
8.2
5.5
0.0
230
1.5
8.2
5.5
0.0
460
8.3
60.0
13.0
0.8
4.1
2.2
0.0
575
6.7
40.0
10.5
0.6
3.6
1.8
0.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
40.9
40.9
54.6
70.2
96.2
40.9
40.9
61.9
79.9
110.0
19.1
19.1
30.9
40.0
55.0
15.8
15.8
24.7
31.9
43.9
42.3
42.3
54.6
70.2
96.2
42.3
42.3
61.9
79.9
110.0
22.0
22.0
30.9
40.0
55.0
18.0
18.0
24.7
31.9
43.9
47.2
47.2
57.1
72.7
98.7
47.2
47.2
64.4
82.4
112.5
24.4
24.4
32.2
41.2
56.2
19.9
19.9
26.2
33.4
45.4
46.4
46.4
61.5
77.1
103.1
46.4
46.4
68.8
86.8
116.9
21.3
21.3
33.7
42.7
57.7
17.6
17.6
26.9
34.1
46.1
47.8
47.8
61.5
77.1
103.1
47.8
47.8
68.8
86.8
116.9
24.2
24.2
33.7
42.7
57.7
19.8
19.8
26.9
34.1
46.1
52.7
52.7
64.0
79.6
105.6
52.7
52.7
71.3
89.3
119.4
26.6
26.6
34.9
44.0
59.0
21.7
21.7
28.4
35.6
47.6
89
349681-JTG-A-1007
J06 thru 12 ZR Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
1.5
8.2
5.5
0.0
230
1.5
8.2
5.5
0.0
460
9.6
70.0
15.0
0.8
4.1
2.2
0.0
575
7.4
53.0
11.5
0.6
3.6
1.8
0.0
208
1.5
10.9
5.5
0.0
230
1.5
10.9
5.5
0.0
460
12.2
87.0
19.0
0.8
5.3
2.2
0.0
575
8.7
62.0
13.5
0.6
4.1
1.8
0.0
J10
(10)
J12
(12.5)
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.5
57.1
72.7
98.7
151.1
51.5
64.4
82.4
112.5
140.2
27.3
32.2
41.2
56.2
70.1
21.5
26.2
33.4
45.4
56.5
68.9
68.9
76.1
102.1
154.5
68.9
68.9
85.8
115.9
143.5
36.0
36.0
42.7
57.7
71.6
26.1
26.8
34.0
46.0
57.1
57.0
64.0
79.6
105.6
158.0
57.0
71.3
89.3
119.4
147.0
29.5
34.9
44.0
59.0
72.8
23.3
28.4
35.6
47.6
58.7
74.4
74.4
83.0
109.0
161.4
74.4
74.6
92.7
122.7
150.4
38.2
38.2
45.5
60.5
74.3
27.9
29.0
36.2
48.3
59.3
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
90
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
8.2
5.5
0.0
230
14.1
95.0
22.0
1.5
8.2
5.5
0.0
460
6.4
45.0
10.0
0.8
4.1
2.2
0.0
575
5.4
38.0
8.5
0.6
3.6
1.8
0.0
208
1.5
10.9
5.5
0.0
230
1.5
10.9
5.5
0.0
460
7.7
50.0
12.0
0.8
5.3
2.2
0.0
575
6.4
40.0
10.0
0.6
4.1
1.8
0.0
208
1.5
10.9
5.5
0.0
230
1.5
10.9
5.5
0.0
460
8.3
60.0
13.0
0.8
5.3
2.2
0.0
575
6.7
40.0
10.5
0.6
4.1
1.8
0.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
42.9
42.9
57.1
72.7
98.7
42.9
42.9
64.4
82.4
112.5
20.1
20.1
32.2
41.2
56.2
17.0
17.0
26.2
33.4
45.4
47.0
47.0
60.5
76.1
102.1
47.0
47.0
67.8
85.8
115.9
24.2
24.2
33.7
42.7
57.7
19.7
19.7
26.8
34.0
46.0
49.9
49.9
60.5
76.1
102.1
49.9
49.9
67.8
85.8
115.9
25.6
25.6
33.7
42.7
57.7
20.4
20.4
26.8
34.0
46.0
48.4
48.4
64.0
79.6
105.6
48.4
48.4
71.3
89.3
119.4
22.3
22.3
34.9
44.0
59.0
18.8
18.8
28.4
35.6
47.6
52.5
52.5
67.3
83.0
109.0
52.5
52.5
74.6
92.7
122.7
26.4
26.4
36.4
45.5
60.5
21.5
21.5
29.0
36.2
48.3
55.4
55.4
67.3
83.0
109.0
55.4
55.4
74.6
92.7
122.7
27.8
27.8
36.4
45.5
60.5
22.2
22.2
29.0
36.2
48.3
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
60
50
60
60
70
80
80
100
110
50
60
50
60
70
80
90
90
125
125
25
25
25
25
35
35
45
45
60
60
20
20
20
20
30
30
35
40
50
50
60
60
60
60
70
70
80
90
110
110
60
60
60
60
70
80
90
100
125
125
30
30
30
30
35
40
45
50
60
70
25
25
25
25
30
30
35
40
50
50
60
70
60
70
70
70
80
90
110
110
60
70
60
70
70
80
90
100
125
125
30
35
30
35
35
40
45
50
60
70
25
25
25
25
30
30
35
40
50
50
91
349681-JTG-A-1007
J06 thru 12 ZR Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
1.5
10.9
5.5
0.0
230
1.5
10.9
5.5
0.0
460
9.6
70.0
15.0
0.8
5.3
2.2
0.0
575
7.4
53.0
11.5
0.6
4.1
1.8
0.0
208
1.5
16.1
5.5
0.0
230
1.5
16.1
5.5
0.0
460
12.2
87.0
19.0
0.8
8.1
2.2
0.0
575
8.7
62.0
13.5
0.6
6.0
1.8
0.0
J10
(10)
J12
(12.5)
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
54.2
60.5
76.1
102.1
154.5
54.2
67.8
85.8
115.9
143.5
28.5
33.7
42.7
57.7
71.6
22.0
26.8
34.0
46.0
57.1
74.1
74.1
82.6
108.6
161.0
74.1
74.3
92.3
122.4
150.0
38.8
38.8
46.2
61.2
75.1
28.0
29.2
36.4
48.4
59.5
59.7
67.3
83.0
109.0
161.4
59.7
74.6
92.7
122.7
150.4
30.7
36.4
45.5
60.5
74.3
23.8
29.0
36.2
48.3
59.3
79.6
79.6
89.5
115.5
167.9
79.6
81.1
99.2
129.2
156.9
41.0
41.0
49.0
64.0
77.8
29.8
31.4
38.6
50.6
61.7
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
70
70
70
80
90
110
110
175
175
70
70
70
80
90
100
125
125
175
175
35
40
35
40
45
50
60
70
80
80
25
30
30
30
35
40
50
50
70
70
90
100
90
100
90
100
110
125
175
175
90
100
90
100
100
100
125
150
175
175
50
50
50
50
50
50
70
70
90
90
35
35
35
35
40
40
50
60
70
70
92
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
6.2
5.5
10.0
230
14.1
95.0
22.0
1.5
6.2
5.5
10.0
460
6.4
45.0
10.0
0.8
3.1
2.2
5.0
575
5.4
38.0
8.5
0.6
2.4
1.8
4.0
208
1.5
6.2
5.5
10.0
230
1.5
6.2
5.5
10.0
460
7.7
50.0
12.0
0.8
3.1
2.2
5.0
575
6.4
40.0
10.0
0.6
2.4
1.8
4.0
208
1.5
8.2
5.5
10.0
230
1.5
8.2
5.5
10.0
460
8.3
60.0
13.0
0.8
4.1
2.2
5.0
575
6.7
40.0
10.5
0.6
3.6
1.8
4.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
50.9
50.9
67.1
82.7
108.7
50.9
50.9
74.4
92.4
122.5
24.1
24.1
37.2
46.2
61.2
19.8
19.8
29.7
36.9
48.9
52.3
52.3
67.1
82.7
108.7
52.3
52.3
74.4
92.4
122.5
27.0
27.0
37.2
46.2
61.2
22.0
22.0
29.7
36.9
48.9
57.2
57.2
69.6
85.2
111.2
57.2
57.2
76.9
94.9
125.0
29.4
29.4
38.4
47.5
62.5
23.9
23.9
31.2
38.4
50.4
56.4
56.4
74.0
89.6
115.6
56.4
56.4
81.3
99.3
129.4
26.3
26.4
39.9
49.0
64.0
21.6
21.6
31.9
39.1
51.1
57.8
57.8
74.0
89.6
115.6
57.8
57.8
81.3
99.3
129.4
29.2
29.2
39.9
49.0
64.0
23.8
23.8
31.9
39.1
51.1
62.7
62.7
76.5
92.1
118.1
62.7
62.7
83.8
101.8
131.9
31.6
31.6
41.2
50.2
65.2
25.7
25.7
33.4
40.6
52.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
60
70
70
80
90
90
110
125
60
70
60
70
80
90
100
100
125
150
30
30
30
30
40
40
50
50
70
70
25
25
25
25
30
35
40
40
50
60
60
70
60
70
70
80
90
90
110
125
60
70
60
70
80
90
100
100
125
150
30
35
30
35
40
40
50
50
70
70
25
30
25
30
30
35
40
40
50
60
70
70
70
70
70
80
90
100
125
125
70
70
70
70
80
90
100
110
125
150
35
35
35
35
40
45
50
60
70
70
30
30
30
30
35
35
40
45
60
60
93
349681-JTG-A-1007
J06 thru 12 ZR Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
1.5
8.2
5.5
10.0
230
1.5
8.2
5.5
10.0
460
9.6
70.0
15.0
0.8
4.1
2.2
5.0
575
7.4
53.0
11.5
0.6
3.6
1.8
4.0
208
1.5
10.9
5.5
10.0
230
1.5
10.9
5.5
10.0
460
12.2
87.0
19.0
0.8
5.3
2.2
5.0
575
8.7
62.0
13.5
0.6
4.1
1.8
4.0
J10
(10)
J12
(12.5)
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
61.5
69.6
85.2
111.2
163.6
61.5
76.9
94.9
125.0
152.7
32.3
38.4
47.5
62.5
76.3
25.5
31.2
38.4
50.4
61.5
78.9
78.9
88.6
114.6
167.0
78.9
80.3
98.3
128.4
156.0
41.0
41.0
49.0
64.0
77.8
30.1
31.8
39.0
51.0
62.1
67.0
76.5
92.1
118.1
170.5
67.0
83.8
101.8
131.9
159.5
34.5
41.2
50.2
65.2
79.1
27.3
33.4
40.6
52.6
63.7
84.4
84.4
95.5
121.5
173.9
84.4
87.1
105.2
135.2
162.9
43.2
43.2
51.7
66.7
80.6
31.9
34.0
41.2
53.3
64.3
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
70
80
90
100
125
125
175
175
70
80
80
90
100
110
125
150
175
175
40
40
40
45
50
60
70
70
90
90
30
30
35
35
40
45
60
60
70
70
100
100
100
100
100
100
125
125
175
175
100
100
100
100
100
110
150
150
175
175
50
50
50
50
50
60
70
70
90
90
35
40
35
40
40
45
60
60
70
70
94
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
8.2
5.5
10.0
230
14.1
95.0
22.0
1.5
8.2
5.5
10.0
460
6.4
45.0
10.0
0.8
4.1
2.2
5.0
575
5.4
38.0
8.5
0.6
3.6
1.8
4.0
208
1.5
10.9
5.5
10.0
230
1.5
10.9
5.5
10.0
460
7.7
50.0
12.0
0.8
5.3
2.2
5.0
575
6.4
40.0
10.0
0.6
4.1
1.8
4.0
208
1.5
10.9
5.5
10.0
230
1.5
10.9
5.5
10.0
460
8.3
60.0
13.0
0.8
5.3
2.2
5.0
575
6.7
40.0
10.5
0.6
4.1
1.8
4.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
52.9
52.9
69.6
85.2
111.2
52.9
52.9
76.9
94.9
125.0
25.1
25.1
38.4
47.5
62.5
21.0
21.0
31.2
38.4
50.4
57.0
57.0
73.0
88.6
114.6
57.0
57.0
80.3
98.3
128.4
29.2
29.2
39.9
49.0
64.0
23.7
23.7
31.8
39.0
51.0
59.9
59.9
73.0
88.6
114.6
59.9
59.9
80.3
98.3
128.4
30.6
30.6
39.9
49.0
64.0
24.4
24.4
31.8
39.0
51.0
58.4
58.4
76.5
92.1
118.1
58.4
58.4
83.8
101.8
131.9
27.3
27.7
41.2
50.2
65.2
22.8
22.8
33.4
40.6
52.6
62.5
62.5
79.8
95.5
121.5
62.5
62.5
87.1
105.2
135.2
31.4
31.4
42.7
51.7
66.7
25.5
25.5
34.0
41.2
53.3
65.4
65.4
79.8
95.5
121.5
65.4
65.4
87.1
105.2
135.2
32.8
32.8
42.7
51.7
66.7
26.2
26.2
34.0
41.2
53.3
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
60
70
70
80
90
100
125
125
60
70
60
70
80
90
100
110
125
150
30
30
30
30
40
45
50
60
70
70
25
25
25
25
35
35
40
45
60
60
70
70
70
70
80
80
90
100
125
125
70
70
70
70
90
90
100
110
150
150
35
35
35
35
40
45
50
60
70
70
30
30
30
30
35
35
40
45
60
60
70
80
70
80
80
80
90
100
125
125
70
80
70
80
90
90
100
110
150
150
35
40
35
40
40
45
50
60
70
70
30
30
30
30
35
35
40
45
60
60
95
349681-JTG-A-1007
J06 thru 12 ZR Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
1.5
10.9
5.5
10.0
230
1.5
10.9
5.5
10.0
460
9.6
70.0
15.0
0.8
5.3
2.2
5.0
575
7.4
53.0
11.5
0.6
4.1
1.8
4.0
208
1.5
16.1
5.5
10.0
230
1.5
16.1
5.5
10.0
460
12.2
87.0
19.0
0.8
8.1
2.2
5.0
575
8.7
62.0
13.5
0.6
6.0
1.8
4.0
J10
(10)
J12
(12.5)
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
64.2
73.0
88.6
114.6
167.0
64.2
80.3
98.3
128.4
156.0
33.5
39.9
49.0
64.0
77.8
26.0
31.8
39.0
51.0
62.1
84.1
84.1
95.1
121.1
173.5
84.1
86.8
104.8
134.9
162.5
43.8
43.8
52.5
67.5
81.3
32.0
34.2
41.4
53.4
64.5
69.7
79.8
95.5
121.5
173.9
69.7
87.1
105.2
135.2
162.9
35.7
42.7
51.7
66.7
80.6
27.8
34.0
41.2
53.3
64.3
89.6
89.6
102.0
128.0
180.4
89.6
93.6
111.7
141.7
169.4
46.0
46.2
55.2
70.2
84.1
33.8
36.4
43.6
55.6
66.7
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
80
80
80
80
90
100
125
125
175
175
80
80
90
90
100
110
150
150
175
175
40
45
40
45
50
60
70
70
90
90
30
35
35
35
40
45
60
60
70
70
100
110
100
110
100
110
125
150
175
200
100
110
100
110
110
125
150
150
175
175
50
50
50
50
60
60
70
80
90
90
40
40
40
40
45
45
60
60
70
70
96
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
6.2
5.5
0.0
230
14.1
95.0
22.0
1.5
6.2
5.5
0.0
460
6.4
45.0
10.0
0.8
3.1
2.2
0.0
575
5.4
38.0
8.5
0.6
2.4
1.8
0.0
208
15.6
83.1
21.4
1.5
6.2
5.5
0.0
230
15.6
83.1
21.4
1.5
6.2
5.5
0.0
460
6.9
41.0
9.7
0.8
3.1
2.2
0.0
575
5.4
33.0
7.5
0.6
2.4
1.8
0.0
208
1.5
8.2
5.5
0.0
230
1.5
8.2
5.5
0.0
460
8.7
60.0
13.5
0.8
4.1
2.2
0.0
575
6.7
42.0
10.5
0.6
3.6
1.8
0.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
40.9
64.5
87.8
103.4
129.4
40.9
68.0
95.1
113.1
143.2
19.1
32.6
46.2
55.2
70.2
15.8
26.6
37.4
44.6
56.6
44.3
67.9
91.1
106.8
132.8
44.3
71.4
98.4
116.5
146.5
20.2
33.8
47.3
56.3
71.3
15.8
26.6
37.4
44.6
56.6
48.8
72.4
95.6
111.2
137.3
48.8
75.8
102.9
120.9
151.0
25.3
38.8
52.3
61.4
76.4
19.9
30.7
41.5
48.7
60.8
46.4
70.0
93.3
108.9
134.9
46.4
73.5
100.6
118.6
148.7
21.3
34.8
48.4
57.4
72.4
17.6
28.4
39.2
46.4
58.4
49.8
73.4
96.6
112.3
138.3
49.8
76.9
103.9
122.0
152.0
22.4
36.0
49.5
58.5
73.5
17.6
28.4
39.2
46.4
58.4
54.3
77.9
101.1
116.7
142.8
54.3
81.3
108.4
126.4
156.5
27.5
41.0
54.5
63.6
78.6
21.7
32.5
43.3
50.5
62.6
97
349681-JTG-A-1007
J06 thru 12 XP Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
1.5
8.2
5.5
0.0
230
1.5
8.2
5.5
0.0
460
9.6
70.0
15.0
0.8
4.1
2.2
0.0
575
7.4
53.0
11.5
0.6
3.6
1.8
0.0
208
1.5
10.9
5.5
0.0
230
1.5
10.9
5.5
0.0
460
12.2
87.0
19.0
0.8
5.3
2.2
0.0
575
8.7
62.0
13.5
0.6
4.1
1.8
0.0
J10
(10)
J12
(12.5)
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.5
98.3
113.9
140.0
151.1
51.5
105.6
123.6
153.7
153.7
27.3
54.4
63.4
78.4
78.4
21.5
43.1
50.3
62.3
62.3
68.9
115.7
131.3
157.4
157.4
68.9
123.0
141.0
171.1
171.1
36.0
63.0
72.0
87.1
87.1
26.1
47.7
54.9
67.0
67.0
57.0
103.8
119.4
145.5
158.0
57.0
111.1
129.1
159.2
159.2
29.5
56.6
65.6
80.6
80.6
23.3
44.9
52.1
64.1
64.1
74.4
121.2
136.8
162.9
162.9
74.4
128.5
146.5
176.6
176.6
38.2
65.2
74.2
89.3
89.3
27.9
49.5
56.7
68.8
68.8
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
98
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
8.2
5.5
0.0
230
14.1
95.0
22.0
1.5
8.2
5.5
0.0
460
6.4
45.0
10.0
0.8
4.1
2.2
0.0
575
5.4
38.0
8.5
0.6
3.6
1.8
0.0
208
15.6
83.1
21.4
1.5
10.9
5.5
0.0
230
15.6
83.1
21.4
1.5
10.9
5.5
0.0
460
6.9
41.0
9.7
0.8
5.3
2.2
0.0
575
5.4
33.0
7.5
0.6
4.1
1.8
0.0
208
1.5
10.9
5.5
0.0
230
1.5
10.9
5.5
0.0
460
8.7
60.0
13.5
0.8
5.3
2.2
0.0
575
6.7
42.0
10.5
0.6
4.1
1.8
0.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
42.9
66.5
89.8
105.4
131.4
42.9
70.0
97.1
115.1
145.2
20.1
33.6
47.2
56.2
71.2
17.0
27.8
38.6
45.8
57.8
49.0
72.6
95.8
111.5
137.5
49.0
76.1
103.1
121.2
151.2
22.4
36.0
49.5
58.5
73.5
17.5
28.3
39.1
46.3
58.3
51.5
75.1
98.3
113.9
140.0
51.5
78.5
105.6
123.6
153.7
26.5
40.0
53.5
62.6
77.6
20.4
31.2
42.0
49.2
61.3
48.4
72.0
95.3
110.9
136.9
48.4
75.5
102.6
120.6
150.7
22.3
35.8
49.4
58.4
73.4
18.8
29.6
40.4
47.6
59.6
54.5
78.1
101.3
117.0
143.0
54.5
81.6
108.6
126.7
156.7
24.6
38.2
51.7
60.7
75.7
19.3
30.1
40.9
48.1
60.1
57.0
80.6
103.8
119.4
145.5
57.0
84.0
111.1
129.1
159.2
28.7
42.2
55.7
64.8
79.8
22.2
33.0
43.8
51.0
63.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
60
70
80
90
100
110
125
150
150
50
60
70
80
100
110
125
125
150
175
25
25
35
40
50
50
60
60
80
80
20
20
30
30
40
45
50
50
60
60
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
110
125
150
175
175
25
30
40
40
50
60
60
70
80
80
20
20
30
35
40
45
50
50
60
70
60
70
80
90
100
110
125
125
150
150
60
70
80
90
110
125
125
150
175
175
35
35
45
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
99
349681-JTG-A-1007
J06 thru 12 XP Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
1.5
10.9
5.5
0.0
230
1.5
10.9
5.5
0.0
460
9.6
70.0
15.0
0.8
5.3
2.2
0.0
575
7.4
53.0
11.5
0.6
4.1
1.8
0.0
208
1.5
16.1
5.5
0.0
230
1.5
16.1
5.5
0.0
460
12.2
87.0
19.0
0.8
8.1
2.2
0.0
575
8.7
62.0
13.5
0.6
6.0
1.8
0.0
J10
(10)
J12
(12.5)
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
54.2
101.0
116.6
142.7
154.5
54.2
108.3
126.3
156.4
156.4
28.5
55.6
64.6
79.6
79.6
22.0
43.6
50.8
62.8
62.8
74.1
120.9
136.5
162.6
162.6
74.1
128.2
146.2
176.3
176.3
38.8
65.8
74.8
89.9
89.9
28.0
49.6
56.8
68.9
68.9
59.7
106.5
122.1
148.2
161.4
59.7
113.8
131.8
161.9
161.9
30.7
57.8
66.8
81.8
81.8
23.8
45.4
52.6
64.6
64.6
79.6
126.4
142.0
168.1
168.1
79.6
133.7
151.7
181.8
181.8
41.0
68.0
77.0
92.1
92.1
29.8
51.4
58.6
70.7
70.7
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
70
110
110
125
125
150
150
175
175
70
70
110
125
150
150
175
175
175
175
35
40
60
60
70
70
80
90
80
90
25
30
45
50
60
60
70
70
70
70
90
100
125
150
150
150
175
175
175
175
90
100
150
150
150
175
200
200
200
200
50
50
70
70
80
80
90
100
90
100
35
35
50
60
60
60
70
80
70
80
100
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
6.2
5.5
10.0
230
14.1
95.0
22.0
1.5
6.2
5.5
10.0
460
6.4
45.0
10.0
0.8
3.1
2.2
5.0
575
5.4
38.0
8.5
0.6
2.4
1.8
4.0
208
15.6
83.1
21.4
1.5
6.2
5.5
10.0
230
15.6
83.1
21.4
1.5
6.2
5.5
10.0
460
6.9
41.0
9.7
0.8
3.1
2.2
5.0
575
5.4
33.0
7.5
0.6
2.4
1.8
4.0
208
1.5
8.2
5.5
10.0
230
1.5
8.2
5.5
10.0
460
8.7
60.0
13.5
0.8
4.1
2.2
5.0
575
6.7
42.0
10.5
0.6
3.6
1.8
4.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
50.9
74.5
97.8
113.4
139.4
50.9
78.0
105.1
123.1
153.2
24.1
37.6
51.2
60.2
75.2
19.8
30.6
41.4
48.6
60.6
54.3
77.9
101.1
116.8
142.8
54.3
81.4
108.4
126.5
156.5
25.2
38.8
52.3
61.3
76.3
19.8
30.6
41.4
48.6
60.6
58.8
82.4
105.6
121.2
147.3
58.8
85.8
112.9
130.9
161.0
30.3
43.8
57.3
66.4
81.4
23.9
34.7
45.5
52.7
64.8
56.4
80.0
103.3
118.9
144.9
56.4
83.5
110.6
128.6
158.7
26.3
39.8
53.4
62.4
77.4
21.6
32.4
43.2
50.4
62.4
59.8
83.4
106.6
122.3
148.3
59.8
86.9
113.9
132.0
162.0
27.4
41.0
54.5
63.5
78.5
21.6
32.4
43.2
50.4
62.4
64.3
87.9
111.1
126.7
152.8
64.3
91.3
118.4
136.4
166.5
32.5
46.0
59.5
68.6
83.6
25.7
36.5
47.3
54.5
66.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
125
125
150
175
175
30
30
40
40
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
60
70
80
90
110
110
125
125
150
150
60
70
90
90
110
125
150
150
175
175
30
30
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
70
80
90
90
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
35
40
45
50
60
60
70
70
90
90
30
30
35
40
50
50
60
60
70
70
101
349681-JTG-A-1007
J06 thru 12 XP Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
1.5
8.2
5.5
10.0
230
1.5
8.2
5.5
10.0
460
9.6
70.0
15.0
0.8
4.1
2.2
5.0
575
7.4
53.0
11.5
0.6
3.6
1.8
4.0
208
1.5
10.9
5.5
10.0
230
1.5
10.9
5.5
10.0
460
12.2
87.0
19.0
0.8
5.3
2.2
5.0
575
8.7
62.0
13.5
0.6
4.1
1.8
4.0
J10
(10)
J12
(12.5)
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
61.5
108.3
123.9
150.0
163.6
61.5
115.6
133.6
163.7
163.7
32.3
59.4
68.4
83.4
83.4
25.5
47.1
54.3
66.3
66.3
78.9
125.7
141.3
167.4
167.4
78.9
133.0
151.0
181.1
181.1
41.0
68.0
77.0
92.1
92.1
30.1
51.7
58.9
71.0
71.0
67.0
113.8
129.4
155.5
170.5
67.0
121.1
139.1
169.2
169.2
34.5
61.6
70.6
85.6
85.6
27.3
48.9
56.1
68.1
68.1
84.4
131.2
146.8
172.9
173.9
84.4
138.5
156.5
186.6
186.6
43.2
70.2
79.2
94.3
94.3
31.9
53.5
60.7
72.8
72.8
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
110
125
125
150
150
175
175
175
70
80
125
125
150
150
175
175
175
175
40
40
60
70
70
80
90
90
90
90
30
30
50
50
60
60
70
70
70
70
100
100
150
150
150
150
175
175
175
175
100
100
150
150
175
175
200
200
200
200
50
50
70
80
80
80
100
100
100
100
35
40
60
60
60
70
80
80
80
80
102
349681-JTG-A-1007
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
14.1
95.0
22.0
1.5
8.2
5.5
10.0
230
14.1
95.0
22.0
1.5
8.2
5.5
10.0
460
6.4
45.0
10.0
0.8
4.1
2.2
5.0
575
5.4
38.0
8.5
0.6
3.6
1.8
4.0
208
15.6
83.1
21.4
1.5
10.9
5.5
10.0
230
15.6
83.1
21.4
1.5
10.9
5.5
10.0
460
6.9
41.0
9.7
0.8
5.3
2.2
5.0
575
5.4
33.0
7.5
0.6
4.1
1.8
4.0
208
1.5
10.9
5.5
10.0
230
1.5
10.9
5.5
10.0
460
8.7
60.0
13.5
0.8
5.3
2.2
5.0
575
6.7
42.0
10.5
0.6
4.1
1.8
4.0
J06
(6.5)
J07
(7.5)
J08
(8.5)
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
52.9
76.5
99.8
115.4
141.4
52.9
80.0
107.1
125.1
155.2
25.1
38.6
52.2
61.2
76.2
21.0
31.8
42.6
49.8
61.8
59.0
82.6
105.8
121.5
147.5
59.0
86.1
113.1
131.2
161.2
27.4
41.0
54.5
63.5
78.5
21.5
32.3
43.1
50.3
62.3
61.5
85.1
108.3
123.9
150.0
61.5
88.5
115.6
133.6
163.7
31.5
45.0
58.5
67.6
82.6
24.4
35.2
46.0
53.2
65.3
58.4
82.0
105.3
120.9
146.9
58.4
85.5
112.6
130.6
160.7
27.3
40.8
54.4
63.4
78.4
22.8
33.6
44.4
51.6
63.6
64.5
88.1
111.3
127.0
153.0
64.5
91.6
118.6
136.7
166.7
29.6
43.2
56.7
65.7
80.7
23.3
34.1
44.9
52.1
64.1
67.0
90.6
113.8
129.4
155.5
67.0
94.0
121.1
139.1
169.2
33.7
47.2
60.7
69.8
84.8
26.2
37.0
47.8
55.0
67.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
18.9
37.5
50.0
70.8
22.6
45.2
60.2
85.3
11.3
22.6
30.1
42.7
9.0
18.1
24.1
34.1
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
80
90
100
110
125
125
150
150
60
70
80
90
110
125
150
150
175
175
30
30
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
70
80
90
90
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
30
35
45
45
60
60
70
70
80
90
25
25
35
35
45
45
60
60
70
70
70
80
90
100
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
40
40
50
50
60
70
70
70
90
90
30
30
40
40
50
50
60
60
70
70
103
349681-JTG-A-1007
J06 thru 12 XP Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
1.5
10.9
5.5
10.0
230
1.5
10.9
5.5
10.0
460
9.6
70.0
15.0
0.8
5.3
2.2
5.0
575
7.4
53.0
11.5
0.6
4.1
1.8
4.0
208
1.5
16.1
5.5
10.0
230
1.5
16.1
5.5
10.0
460
12.2
87.0
19.0
0.8
8.1
2.2
5.0
575
8.7
62.0
13.5
0.6
6.0
1.8
4.0
J10
(10)
J12
(12.5)
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
64.2
111.0
126.6
152.7
167.0
64.2
118.3
136.3
166.4
166.4
33.5
60.6
69.6
84.6
84.6
26.0
47.6
54.8
66.8
66.8
84.1
130.9
146.5
172.6
173.5
84.1
138.2
156.2
186.3
186.3
43.8
70.8
79.8
94.9
94.9
32.0
53.6
60.8
72.9
72.9
69.7
116.5
132.1
158.2
173.9
69.7
123.8
141.8
171.9
171.9
35.7
62.8
71.8
86.8
86.8
27.8
49.4
56.6
68.6
68.6
89.6
136.4
152.0
178.1
180.4
89.6
143.7
161.7
191.8
191.8
46.0
73.0
82.0
97.1
97.1
33.8
55.4
62.6
74.7
74.7
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
37.5
50.0
70.8
112.7
45.2
60.2
85.3
135.6
22.6
30.1
42.7
67.8
18.1
24.1
34.1
54.2
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
80
80
125
125
150
150
175
175
175
175
80
80
125
125
150
150
175
175
175
175
40
45
70
70
70
80
90
90
90
90
30
35
50
50
60
60
70
70
70
70
100
110
150
150
150
175
175
200
175
200
100
110
150
150
175
175
200
200
200
200
50
50
80
80
80
90
100
100
100
100
40
40
60
60
70
70
80
80
80
80
104
349681-JTG-A-1007
105
349681-JTG-A-1007
Typical J06 thru 10 ZH/ZR Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
106
349681-JTG-A-1007
Typical J06 thru 10 ZH/ZR Cooling Unit with/without Electric Heat Wiring Diagram
107
349681-JTG-A-1007
Typical J12ZH/ZR Cooling Unit with Gas Heat 230 Volt Wiring Diagram
108
349681-JTG-A-1007
Typical J12ZH/ZR Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
109
349681-JTG-A-1007
Typical J12ZH/ZR Cooling Unit with/without Electric Heat Wiring Diagram
110
349681-JTG-A-1007
Typical J06 thru 10 ZR Reheat Wiring Diagram
111
349681-JTG-A-1007
Typical J12ZR Reheat Wiring Diagram
112
349681-JTG-A-1007
113
349681-JTG-A-1007
Typical J12XP Heat Pump with/without Electric Heat Wiring Diagram
114
349681-JTG-A-1007
FRONT
FRONT
LEFT
LEFT
C
E
F
FRONT
LEFT
Weight (lbs.)
Center of Gravity
Size
Model
Shipping Operating
X
Y
(Tons)
J06
ZH
905
900
38
23
(6.5)
J07
ZH
925
920
38
23
(7.5)
J08
ZH
1140
1135
38
25.5
(8.5)
J10
ZH
1140
1135
38
25.5
(10)
J12
ZH
1405
1400
51
25.5
(12.5)
J06
ZR
970
965
38
23
(6.5)
J07
ZR
970
965
38
23
(7.5)
J08
ZR
1205
1200
38
25.5
(8.5)
J10
ZR
1205
1200
38
25.5
(10)
J12
ZR
1470
1465
51
25.5
(12.5)
J06
XP
925
920
38
23
(6.5)
J07
XP
925
920
38
23
(7.5)
J08
XP
1140
1135
38
25.5
(8.5)
J10
XP
1140
1135
38
25.5
(10)
J12
XP
1405
1400
51
25.5
(12.5)
201
150
234
315
141
115
95
149
180
221
206
153
240
322
144
117
97
152
184
225
281
209
275
369
197
160
133
175
211
259
281
209
275
369
197
160
133
175
211
259
258
347
456
339
164
198
243
319
260
216
216
161
251
337
151
123
102
160
193
236
216
161
251
337
151
123
102
160
193
236
297
221
291
390
208
170
141
185
223
274
297
221
291
390
208
170
141
185
223
274
270
363
477
355
172
207
254
334
272
226
206
153
240
322
144
117
97
152
184
225
206
153
240
322
144
117
97
152
184
225
281
209
275
369
197
160
133
175
211
259
281
209
275
369
197
160
133
175
211
259
258
347
456
339
164
198
243
319
260
216
115
349681-JTG-A-1007
Weight (lbs.)
Shipping
Operating
90
85
155
150
80
80
110
110
J12ZH/ZR/XP
116
349681-JTG-A-1007
A
42
42
50 3/4
50 3/4
50 3/4
J06
J07
J08
J10
J12
Detail A
B
89
89
89
89
119 1/2
Base
Pan
17-13/16
E
15 3/16
15 3/16
17 3/16
17 3/16
17 3/16
F
6 3/16
6 3/16
6 3/16
6 3/16
6 3/16
Detail B
5-1/4
Dimension (in.)
C
D
22 1/8
18 3/16
22 1/8
18 3/16
30 3/16
24 3/16
30 3/16
24 3/16
30 3/16
24 3/16
5-3/8
Distance (in.)
72
36
36
Direction
Right
Left
Bottom2
Distance (in.)
12
36
0
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
117
349681-JTG-A-1007
J06 thru 12 ZH/ZR/XP Unit Electrical Entry
Convenience Outlet
Power Entry 7/8
FRONT
Dot Plugs
Return
Air
Supply
Air
D
B
2-31/32
5-5/32
C
31-11/16
118
349681-JTG-A-1007
J12ZH/ZR/XP Unit Side Duct Openings
Dot Plugs
18-1/4
D
B
5-5/32
2-7/8
C
31-5/8
A
27 3/4
27 3/4
28 1/4
28 1/4
28 1/4
Dimension (in.)
B
C
12 1/16
27 1/2
12 1/16
27 1/2
18 1/16
28 1/4
18 1/16
28 1/4
18 1/16
28 1/4
D
16
16
18 1/4
18 1/4
18 1/4
30-3/8
4-5/16
119
349681-JTG-A-1007
RIGHT
80-5/8
20
SUPPLY
20
RETURN
2 TYP.
30
INSULATED DECK UNDER
COMPRESSOR SECTION
50-1/2
FRONT
8 or 14
50-1/2
30-1/2
23 4
80-5/8
26
RETURN
SUPPLY
10
76-5/8
94
FRONT
120
59-1/4
64-1/4
RIGHT
349681-JTG-A-1007
J06 thru 12 ZH/ZR/XP Economizer Assembly
58 1/4
88 1/4
39 1/2
or
47 1/2
Outside Air
Intake Hood
35 3/4
26
25 3/4
26
30 1/4
121
349681-JTG-A-1007
Economizer Options
Economizer Usage
Application
Cabinet Height
Description
Model
Bottom Return
All
2EE04705424
Side Return
All
2EE047055241
42"
2EE047056242
50"
2EE047052242
2EE04705424
Fresh Air Hood
2EE04705424
2EE04705424
2EE04705424
Fresh Air Damper Return Air Damper
Barometric Relief Damper
2EE04705424
Barometric Relief Hood
2EE04705424
Fresh Air Hood
122
2EE04705424
2EE04705424
Fresh Air Damper Return Air Damper
2PE047032XX
Power Exhaust
2EE04705424
Barometric Relief Damper
2EE04705424
Barometric Relief Hood
349681-JTG-A-1007
Field Installed Horizontal Economizer W/Power Exhaust
2EE04705524
Return Air Damper
Field Installed
Duct Work
2EE04705524
Fresh Air Damper
2PE047032XX
Power Exhaust
1EH0408
Barometric
Relief Damper
1EH0408
Barometric
Relief Hood
2EE04705524
Fresh Air Hood
1EH0409
Fresh Air Hood
2EE04705X24
Slab Economizer
2PE047032XX
Power Exhaust
1EH0409 Barometric
Relief Damper
1EH0409 Barometric
Relief Hood
123
1EH0409
Fresh Air Hood
Field Installed
Duct Work
2EE04705X24
Slab Economizer
1EH0409
Barometric Relief Hood
1EH0409
Barometric Relief Damper
2PE047032XX
Power Exhaust
349681-JTG-A-1007
Supersedes: Nothing