Plan Mark Up
Plan Mark Up
Plan Mark Up
DATE:
1500030
29/01/2015
Reviewed by:
PETER C. DUNKIN
(Director) MIFireE, FNZFBI
Key summary
The building has been designed as being under one
title
Building to be installed with a Type 5 fire alarm system
Install emergency lighting in stairway
Illuminated exits at the bottom of the stairs and final exits
from the restaurant and laundromat
Stairways to be constructed as Accessible stairs
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
TITLE:
1500030
29/01/2015
Occupant Load Plan
NOTES:
Occupant Loads
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
34
2
14
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
TITLE:
1500030
29/01/2015
Occupant Load Plan
NOTES:
14
Occupant Loads
30
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
TITLE:
1500030
29/01/2015
Occupant Load Plan
NOTES:
30
Occupant Loads
60
60
60
60
60
60
60
60
60
120
120
120
120
120
120
120
120
60
60
60
60
60
60
60
60
60
120
120
120
120
120
120
120
120
120
120
120
120
120
120
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
1500030
29/01/2015
TITLE:
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
NOTES:
120
60
120
60
60 minute fire rated walls are achieved by GBTL 60 (1 layer 13mm Fyreline Gib to each
side of the framing)
Engineers calculations may be required to verify that the walls required to provide a fire
rating are designed for stability under fire conditions for a minimum of 120 minutes for the
external fire rated walls and 60 minutes for the internal fire rated walls
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
120
120
120
120
120
120
120
120
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
120
120
REFERENCE NUMBER:
DATE:
1500030
29/01/2015
TITLE:
60
120
60
120
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
120
60
60
60
60
60
60
60
60
60
60
60
120
60
120
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
120
120
120
120
120
120
120
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
NOTES:
120
120
120
120
120
120
60
60
60
60
60
60
120
120
60
60
60
60
60
60
120
60
60
60
60
60
60
120
120
120
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
NOTES:
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
Engineers calculations may be required to verify that the walls required to provide a fire
rating are designed for stability under fire conditions for a minimum of 120 minutes for the
external fire rated walls and 60 minutes for the internal fire rated walls
120
120
120
60
60
60
29/01/2015
60
60
60
120
60
60
60
60
60
DATE:
1500030
TITLE:
60
120
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
120
120
60
120
60
120
60
60
120
PLEASE PRINT IN C O L O U R
60
60
60
120
60
60
120
60
60
120
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
120
120
120
120
120
120
120
ER
ER
D.E.O.P 21m
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
PLEASE PRINT IN C O L O U R
ER
ER
ER
ER
ER
ER
ER
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
TITLE:
Exits Signs
ER
ER
ER
ER
29/01/2015
1500030
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
NOTES:
All escape routes shall have signs complying with NZBC F8.
Install illuminated EXIT signs to cover the escape routes and over the final exit doors.
-Design and installation of the illuminated signs is to be in accordance with AS
2293.1:2005.
-Install an emergency lighting system to comply with NZBC F6 Visibility in Escape Routes
as there are changes in level
-For routes not designated as accessible and used by <50 people, the escape routes
must have a minimum width of 700 mm for horizontal travel
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
D.E.O.P 24m
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
D.E.O.P 24m
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
TITLE:
Exits Signs
ER
ER
ER
ER
29/01/2015
1500030
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
NOTES:
All escape routes shall have signs complying with NZBC F8.
Install illuminated EXIT signs to cover the escape routes and over the final exit doors.
-Design and installation of the illuminated signs is to be in accordance with AS
2293.1:2005.
-Install an emergency lighting system to comply with NZBC F6 Visibility in Escape Routes
as there are changes in level
-For routes not designated as accessible and used by <50 people, the escape routes
must have a minimum width of 700 mm for horizontal travel
ER
ER
ER
ER
ER
ER
ER
ER
D.E.O.P 15m
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
D.E.O.P 23m
ER
ER
ER
ER
ER
ER
ER
ER
ER
D.E.O.P 20m
T.O.P 31m
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
TITLE:
Exits Signs
ER
ER
ER
ER
29/01/2015
1500030
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
NOTES:
All escape routes shall have signs complying with NZBC F8.
Install illuminated EXIT signs to cover the escape routes and over the final exit doors.
-Design and installation of the illuminated signs is to be in accordance with AS
2293.1:2005.
-Install an emergency lighting system to comply with NZBC F6 Visibility in Escape Routes
as there are changes in level
-For routes not designated as accessible and used by <50 people, the escape routes
must have a minimum width of 700 mm for horizontal travel
ER
ER
ER
ER
ER
ER
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
29/01/2015
TITLE:
1500030
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
NOTES:
Surface finishes:
4.17.8 Suspended flexible fabrics
When tested to AS 1530 Part 2:
-Suspended flexible fabrics shall have a flammability index of no greater than 12.
-When used as underlay to roofing or exterior cladding that is exposed to view the
flammability index shall be no greater than 5.
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
29/01/2015
TITLE:
1500030
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
NOTES:
Surface finishes:
4.17.8 Suspended flexible fabrics
When tested to AS 1530 Part 2:
-Suspended flexible fabrics shall have a flammability index of no greater than 12.
-When used as underlay to roofing or exterior cladding that is exposed to view the
flammability index shall be no greater than 5.
PLEASE PRINT IN C O L O U R
PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:
DATE:
TITLE:
29/01/2015
1500030
PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.
NOTES:
Wall and ceiling linings
Surface finishes:
= 1S
Critical radiant flux (floor
coverings) = 2.2 kW/sqm 4.17.8 Suspended flexible fabrics
When tested to AS 1530 Part 2:
Wall and ceiling linings
-Suspended flexible fabrics shall have a flammability index of no greater than 12.
= 2S
Critical radiant flux (floor
-When used as underlay to roofing or exterior cladding that is exposed to view the
coverings) = 2.2 kW/sqm
flammability index shall be no greater than 5.