Plan Mark Up

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

REFERENCE NUMBER:

DATE:

1500030

29/01/2015

These drawings support the fire design and are to be


read in conjunction with the fire report. They do not show
all of the required fire safety systems & features and are
not construction drawings.

Reviewed by:

PETER C. DUNKIN
(Director) MIFireE, FNZFBI

Key summary
The building has been designed as being under one
title
Building to be installed with a Type 5 fire alarm system
Install emergency lighting in stairway
Illuminated exits at the bottom of the stairs and final exits
from the restaurant and laundromat
Stairways to be constructed as Accessible stairs

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:
TITLE:

1500030

29/01/2015
Occupant Load Plan

NOTES:

Occupant Loads

Bulk store = 100sqm/ person


Office space = 10sqm/ person

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

34
2
14

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:
TITLE:

1500030

29/01/2015
Occupant Load Plan

These drawings support the fire design and are to


be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:

14

Occupant Loads

Sleeping spaces = 2 people sleeping per room


Restaurant = Fixed number of seating
Kitchen = 10sqm/person
Laundromat = 3.5sqm/person

30

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:
TITLE:

1500030

29/01/2015
Occupant Load Plan

These drawings support the fire design and are to


be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:

30

Occupant Loads

Sleeping spaces = 2 people sleeping per room

60
60

60

60

60

60

60
60

60

120

120

120

120

120

120

120

120

60

60

60

60

60

60

60

60

60

120

120

120

120

120

Maintain 1200mm wide safe path


to the outside of the building

120

120

120

120

120

120

120

120

120

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:

1500030

29/01/2015

TITLE:

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:
120
60

120
60

120/120/1200 FRR walls.

120 minute fire rated walls.

60/60/60 FRR walls.

60 minute fire rated walls are achieved by GBTL 60 (1 layer 13mm Fyreline Gib to each
side of the framing)

60/60/60 FRR midfloor.


-/60/30sm FRR

Engineers calculations may be required to verify that the walls required to provide a fire
rating are designed for stability under fire conditions for a minimum of 120 minutes for the
external fire rated walls and 60 minutes for the internal fire rated walls

60
60

60

60

60

60

60

60
60

60

60

60

60

60

60

60

60

60

60

60

60

120

120

120

120

120

120

120

120

60

60

60

60

60

60

60

60
60

60

60

60

60

60

60
60

120

120

REFERENCE NUMBER:
DATE:

1500030

29/01/2015

TITLE:

60

120
60

120/120/1200 FRR walls.


60/60/60 FRR walls.
60/60/60 FRR midfloor.

-/60/30sm FRR midfloor.


-/60/60sm FRR midfloor.

120

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

120

60

60

60

60

60

60

60
60

60

60

60

120

60

120

60

60

60

60

60

60

60
60
60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60
60

60

60

60

60

60

60

120

120

120

120

120

120

120

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:

120 minute fire rated walls.


60 minute fire rated walls are achieved by GBTL 60 (1 layer 13mm Fyreline Gib to each
side of the framing)
Engineers calculations may be required to verify that the walls required to provide a fire
rating are designed for stability under fire conditions for a minimum of 120 minutes for the
external fire rated walls and 60 minutes for the internal fire rated walls

120

120

120

120

120

120

-/60/60sm FRR midfloor.

60
60
60

60

60

60
120

120

60

60

60

60

60
60
120

60

60

60

60

60
60
120

120

120

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:

120 minute fire rated walls.


60 minute fire rated walls are achieved by GBTL 60 (1 layer 13mm Fyreline Gib to each
side of the framing)

-/60/30sm FRR midfloor.

60

60
60

60
60

60
60

60
60
60
60
60

60

60
60

60

60

60
60

60
60
60
60
60

60

60
60

60
60

60
60
60
60

60

60

60

120/120/1200 FRR walls.


60/60/60 FRR walls.

60

Engineers calculations may be required to verify that the walls required to provide a fire
rating are designed for stability under fire conditions for a minimum of 120 minutes for the
external fire rated walls and 60 minutes for the internal fire rated walls

120

120

120

60

60

60
29/01/2015

60

60

60

120
60

60

60

60

60

DATE:

1500030

TITLE:

60

120

PLEASE PRINT IN C O L O U R
REFERENCE NUMBER:

120

120

60

120

60

120

60

60
120

PLEASE PRINT IN C O L O U R

60

60

60

120

60

60

120

60

60

120

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60

60
60

60

60

60

60

60

60

60

60

60

Kitchenette area can not be in the


safe path. 60 minute fire separation
is to be maintained

120

120

120

120

120

120

120

ER

ER

D.E.O.P 21m

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER
ER

ER

ER

PLEASE PRINT IN C O L O U R

ER

ER

ER

ER

ER

ER

ER

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:
TITLE:

Exits Signs
ER

ER

ER

ER

Escape route (DEOP)


Escape route (TOP)

29/01/2015

1500030

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:

All escape routes shall have signs complying with NZBC F8.
Install illuminated EXIT signs to cover the escape routes and over the final exit doors.
-Design and installation of the illuminated signs is to be in accordance with AS
2293.1:2005.
-Install an emergency lighting system to comply with NZBC F6 Visibility in Escape Routes
as there are changes in level
-For routes not designated as accessible and used by <50 people, the escape routes
must have a minimum width of 700 mm for horizontal travel

ER

ER
ER
ER
ER
ER

ER

ER
ER
ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

D.E.O.P 24m

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

D.E.O.P 24m

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:
TITLE:

Exits Signs
ER

ER

ER

ER

Escape route (DEOP)


Escape route (TOP)

29/01/2015

1500030

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:

All escape routes shall have signs complying with NZBC F8.
Install illuminated EXIT signs to cover the escape routes and over the final exit doors.
-Design and installation of the illuminated signs is to be in accordance with AS
2293.1:2005.
-Install an emergency lighting system to comply with NZBC F6 Visibility in Escape Routes
as there are changes in level
-For routes not designated as accessible and used by <50 people, the escape routes
must have a minimum width of 700 mm for horizontal travel

ER

ER

ER

ER

ER

ER

ER

ER

D.E.O.P 15m

ER
ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER
ER

ER

ER
ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER
ER

ER

ER

ER

ER

ER

ER

ER

ER
ER

D.E.O.P 23m

ER
ER
ER

ER

ER

ER

ER

ER

ER

D.E.O.P 20m
T.O.P 31m

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:
TITLE:

Exits Signs
ER

ER

ER

ER

Escape route (DEOP)


Escape route (TOP)

29/01/2015

1500030

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:

All escape routes shall have signs complying with NZBC F8.
Install illuminated EXIT signs to cover the escape routes and over the final exit doors.
-Design and installation of the illuminated signs is to be in accordance with AS
2293.1:2005.
-Install an emergency lighting system to comply with NZBC F6 Visibility in Escape Routes
as there are changes in level
-For routes not designated as accessible and used by <50 people, the escape routes
must have a minimum width of 700 mm for horizontal travel

ER

ER

ER

ER

ER

ER

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:

29/01/2015

TITLE:

Wall and ceiling linings


= 1S
Critical radiant flux (floor
coverings) = 2.2 kW/sqm
Wall and ceiling linings
=3
Critical radiant flux (floor
coverings) = 1.2 kW/sqm

1500030

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:

Surface finishes:
4.17.8 Suspended flexible fabrics
When tested to AS 1530 Part 2:
-Suspended flexible fabrics shall have a flammability index of no greater than 12.
-When used as underlay to roofing or exterior cladding that is exposed to view the
flammability index shall be no greater than 5.

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:

29/01/2015

TITLE:

Wall and ceiling linings


= 1S
Critical radiant flux (floor
coverings) = 2.2 kW/sqm
Wall and ceiling linings
= 2S
Critical radiant flux (floor
coverings) = 1.2 kW/sqm

1500030

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:

Surface finishes:
4.17.8 Suspended flexible fabrics
When tested to AS 1530 Part 2:
-Suspended flexible fabrics shall have a flammability index of no greater than 12.
-When used as underlay to roofing or exterior cladding that is exposed to view the
flammability index shall be no greater than 5.

PLEASE PRINT IN C O L O U R

PLEASE PRINT IN C O L O U R

REFERENCE NUMBER:
DATE:
TITLE:

29/01/2015

1500030

PLEASE PRINT IN C O L O U R
These drawings support the fire design and are to
be read in conjunction with the fire report. They do
not show all of the required fire safety systems &
features and are not construction drawings.

NOTES:
Wall and ceiling linings
Surface finishes:
= 1S
Critical radiant flux (floor
coverings) = 2.2 kW/sqm 4.17.8 Suspended flexible fabrics
When tested to AS 1530 Part 2:
Wall and ceiling linings
-Suspended flexible fabrics shall have a flammability index of no greater than 12.
= 2S
Critical radiant flux (floor
-When used as underlay to roofing or exterior cladding that is exposed to view the
coverings) = 2.2 kW/sqm
flammability index shall be no greater than 5.