Table of Contents
Introduction........................................................................................................................................................................................ 4
Definitions............................................................................................................................................................................................ 5
Product Range................................................................................................................................................................................... 8
Product Line Overview............................................................................................................................................................... 11
Product Specifications
Molded Case Circuit Breakers.................................................................................................................................24
Motor Circuit Protectors............................................................................................................................................42
Motor Protection Circuit Breakers........................................................................................................................52
Accessories
Auxiliary & Alarm Contacts......................................................................................................................................55
Shunt Trip...........................................................................................................................................................................58
Undervoltage Release............................................................................................................................................... 60
Motor Operators............................................................................................................................................................62
Residual Current Release Module....................................................................................................................... 64
Time-Current Curves
Motor Circuit Protectors........................................................................................................................................... 66
Thermal Magnetic Molded Case Circuit Breakers......................................................................................76
Electronic Molded Case Circuit Breakers...................................................................................................... 102
Let-Through Energy Curves [I 2t]..........................................................................................................................................116
Peak Let-Through Current Curves.......................................................................................................................................121
Utilization Category
Interrupting medium
Air break
Vacuum break
Gas break
Design
Open case
Moulded (molded) case
Method of controlling the operating mechanism
Dependent manual operation
Independent manual operation
Dependent power operation
Independent power operation
Stored energy operation
Type of overcurrent release
Instantaneous
Definite time delay
Inverse time delay
In reviewing the attributes just listed, it is understandable that
many people are confused about what type of circuit breaker
to use, where to use it, and how to select it properly. In this
section, the focus will be placed on the definition, application
and selection of Molded Case Circuit Breakers (MCCBs) with an
inverse time delay as applied to industrial control panels.
This publication will focus on the application and selection of
MCCBs, Motor Protection Circuit Breakers (MPCBs) and Motor
Circuit Protectors (MCPs). The primary focus will be on products
that are packaged in a molded case design, but much of the
information can be applied to other circuit breakers that are
commonly found in control panels.
Definitions
Each of the product categories we mentioned earlier is
packaged in a molded case and confusion develops because
of the physical similarity of the products.
The Molded Case Circuit Breaker is a specific type of circuit
breaker. NEMA defines circuit breakers as devices designed
to open or close a circuit by nonautomatic means, and
to open the circuit automatically on a predetermined
overcurrent without damage to itself when properly applied
within its rating. The term molded case simply refers to the
construction of the circuit breaker and refers to the fact that the
circuit breaker is an assembled unit in a supporting housing of
an insulating material.
Within the realm of MCCBs, three distinct product variations
exist, each with specific protection properties and uses within
the industrial control panel. The main categories are:
Molded Case Circuit Breakers or Feeder Breakers
MCCBs are intended to provide overcurrent protection for
conductors and equipment by opening automatically before
the current reaches a value and duration that will cause
an excessive or dangerous temperature in conductors or
conductor insulation. Additionally, these devices can serve
as the main disconnecting means for a control panel. This
protection pertains to low level overcurrent, and shortcircuit current. Traditionally these types of circuit breakers are
generically described as thermal magnetic devices, though an
increasing number of these devices are also electronic circuit
breakers which provide the same type of protection, with the
exception that the electronics allow the protection curves to
be customized to the specific application. In the United States,
the National Electrical Code (NEC) defines how this protection
is selected in Sections 240-2, 240-3 and 240-4. In Canada
there are similar references in the Canadian Electric Code,
C22.1-12. For IEC applications, IEC 60204-1 provides guidance
for the construction of industrial control panels.
Motor Protection Circuit Breakers
Application-specific variations of the MCCB, these breakers
combine the short-circuit and isolation functionality of the
MCCB with the motor overcurrent protection of a traditional
overload relay. These devices are traditionally used in twocomponent starter applications, with a contactor to control
a motor load. MPCBs are UL 489 Listed as circuit breakers
and verified as motor overload relays. Allen-Bradley MPCBs
are UL Listed as 100% breakers, allowing utilization of the
full range of motor protection provided. Note: most circuit
breakers applied in North America are 80% rated, meaning
they can only be used continuously at 80% of their thermal
rating. Allen-Bradley MPCBs are 100% rated, allowing
full use of the circuit breakers thermal capacity in motor
protection applications.
Branch Circuits
Motor circuit
protection
devices with
magnetic-only
trip unit
Molded case
circuit breakers
with thermal
magnetic
protection
contactor
overload relay
starter
Resistive loads
(heating elements, lighting, etc.)
10
Time (sec)
1.0
0.1
.01
I
Current (A)
Example of magnetic time vs. current curve.
1E4 s
3 min
Time (sec)
1E3 s
Maximum
Time
100 s
10 s
Time
0.1 s
1E2 s
10 sec
Minimum
Time
2x
5x
0.1 kA
1 kA
10 kA
100 kA
Current
Thermal
Action
1 min
Time
Magnetic
Action
Combining the short-circuit
and overcurrent protection
provides us with a protection
curve that looks like this.
0.01 sec
3x
40x
Long Time Allows the long time between 1.05 and ~1.3 x the
thermal rating to be delayed, similar to how an adjustable relay
changes classes
Short Time Adjustable short time between thermal and
short-circuit
Instantaneous Trip Adjustable instantaneous short-circuit
trip time
Ground Fault Adjustable time and value of ground
fault tripping
Product Range
140G Molded Case Circuit Breaker Thermal Protection
As previously described, MCCBs provide thermal overcurrent protection in addition to short-circuit protection. MCCBs
provide this protection by using mechanical means with heater elements, or by using electronics to detect current flow
and model the associated heat generated by the current.
When electronic MCCBs are applied, the ability to adjust the thermal trip rating to shape the trip curve is available and
the result is that there are fewer trip units required to cover a wider range of current. Note: while a trip unit may have the
capability of protecting the current range, in many cases a rating plug is used to limit the range of adjustability.
The table below illustrates the available thermal magnetic and electronic trip units and adjustment
ranges available with the 140G family of MCCBs.
Amperes
10 15 16 20 24 25 30 32 35 40 45 50 56 60 63 64 70 77 80 87 90 100
T-M
T-M
110
112
120
122
125
140
150
157
160
175
200
210
225
(**)
o
o
o
o
Electronic
Thermal Magnetic
105
o (*)
(*)
Thermal Magnetic
o
o
o
o
o
o
o
o
o
Electronic
Electronic
T-M
N/NS
T-M
M
Amperes
240 250 252 280 300 320 350 400 420 480 560 600 630 800 900 1000 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2400 2500 2600 2700 2800 2900 3000
10
N/NS
4801200 A
8003000 A
Bulletin 140G
globally rated MCCBs
UL 489, EN 60947-2, CE, CCC
Feeder circuits and
disconnects
3- and 4-pole versions
25100 A
40150 A
Bulletin 140MG
globally rated MPCBs
UL 489, EN 60947-2, CE
Branch protection,
2-component starters
3-pole versions
Motor Circuit Protectors
3125 A
1200 A
Bulletin 140MG
globally rated MCPs
UL 489, EN 60947-2, CE
Branch protection,
3-component starters
3-pole versions
* 160 A IEC only
11
22
24
22
24
AX2
21
21
96
98
98
96
AL1
95
After initial alarm contact change of state, the Alarm Contacts (AL)
change state only when one of the above conditions occur. Manual
operation of the breaker to Off does not affect the state of these
contacts. The 140G Alarm contacts are changeover contacts (Form C).
95
96
98
98
96
24
24
22
22
AX2
95
21
AL1
21
12
95
13
Terminal Covers
The terminal shield prevents accidental contact with live parts, they also
provide phase to phase insulation.
Ingress Protection
The table indicates the degrees of protection against intrusion and
accidental contact per IEC 60529 Standard.
Location
IP40**
IP20*
IP40*
IP40
*
**
(&)
G through M frames.
Also with direct or variable depth rotary operator.
After installation.
High terminal covers have a height of 60 mm and are designated with a suffix H in the catalog
number, (i.e. 140G-G-TC3H).
C
B
A
Motor Operators
The operating mechanism enables remote opening and closing of the
circuit breaker and is particularly suitable for use in power supply network
supervisory control systems. It comes complete with a padlock device.
The motor operating mechanism is fitted on the front of the circuit
breaker as an alternative to the front flange or rotary operating mechanism.
Motor-operated circuit breakers are normally used in applications where
switching is done infrequently and generally are not used to replace
contactors that are applied in series with the circuit breaker.
14
Shunt Trip
Shunt trips allow the circuit breaker to be opened using an electric
command (opening release). The shunt trip is housed and fitted in
a slot within the circuit breaker.
Shunt trips are used in applications where a remote signal to open
or isolate a circuit is required.
Undervoltage Release
Undervoltage releases allow the circuit breaker to be opened using a
change in the voltage of the power supply to the circuit breaker terminals.
The undervoltage release is fitted in a slot within the circuit breaker.
Undervoltage releases work when the application voltage is reduced
below 75% of the rating of the release unit voltage rating.
Use of undervoltage releases can protect a system against low voltage,
particularly when running or starting motors, by removing power to the
circuit by opening the circuit breaker in low-voltage situations. In some
applications, the undervoltage release can be used to quickly remove
power to a machine or machines by opening a push button contact,
wired in series with the undervoltage releases.
Rotary Operators
When MCCBs are installed as the main or feeder circuit breaker in an
industrial control panel and a non-flanged enclosure is used, a common
means for operating the circuit breaker is through the use of a rotary
operator mechanism. The use of a rotary operator converts a rotary
motion to a vertical motion that toggles the MCCB. In this situation,
the rotary operator kit would consist of:
External operating handle
Operating shaft
Circuit breaker mounted rotary operating mechanism
Using these kits allows external operation of the circuit breaker with the
capability of turning the circuit breaker on/off, and even resetting the
circuit breaker without having to open the enclosure. Traditionally, these
kits are sold with an operating shaft that allows the customer to use the
kit with enclosures of various depths. The operating handles will also
provide status indication when the circuit breakers trip.
15
NFPA 79 Operators
A NFPA 79-compliant Internal Rotary Operating Handle Kit for
Bulletin 140G Molded Case Circuit Breakers (MCCBs), Bulletin
140MG Motor Circuit Protectors (MCPs), and Bulletin 140MG
Motor Protection Circuit Breakers (MPCBs) is available to address
current requirements of the NFPA 79 standard. The NFPA 79 kits
are available for G-, H-, I-, J-, K-, M- and N-Frame Circuit Breaker
product lines.
Compliance with the current NFPA 79 standard enables
operators to maintain control of the main disconnecting
means when the door is open; an issue for rotary-operated
through-the-door disconnect switches and circuit
breakers alike.
This standard requires that the rotary main disconnecting
means to be operable without the use of accessory tools
or devices (independent of door position) and restates the
requirement for an interlocking provision to prevent the closing
of the disconnecting means while the enclosure door is open,
unless the interlock is operated by a deliberate action. Without
this requirement, rotary operated devices may have a shaft
protruding from the panel when the door is open. If the panel
is powered and it is necessary to turn power off, it is difficult
to de-energize the panel by the operating shaft alone. This
standard is to reduce the possibility of personnel not being
able to turn an energized panel off with the door opened.
16
Phase Barriers
These allow the insulation characteristics between the phases at the
connections to be increased. Phase Barriers provide additional electrical
clearance between each phase when special connections extend past the
circuit breaker housing. They are mounted from the front, even with the
circuit breaker already installed.
Mechanical Accessories
Terminal Lugs
Mechanical Terminal Lugs may be used to terminate line and load wiring
to the MCCB. The 140G product line includes, as standard, the capability
to terminate wiring using customer furnished crimp-on ring lug (ring
tongue) or forked lug termination.
For customers who prefer terminating wiring to Mechanical Terminal Lugs,
the 140G line offers a variety of mechanical terminals lugs to match the
frame and application wiring.
Multiple tap terminal lugs are available for those customers terminating
multiple wires to a MCCB pole, either to line or load connection. Use of a
multi-tap connection can save on panel space, making wiring easier due
to using ( multiple) smaller diameter wire. For applications following the
UL guidelines for panel short-circuit current rating (SCCR), the use of
multiple wire termination on the load size permits the termination to be
rated at the SCCR level of the circuit breaker, which may allow a higher
SCCR than may be available using a separate power distribution block.
17
Padlock Attachments
Padlocking hasps are available for the range of MCCB line. This attachment
allows the user the ability to padlock the MCCB in the off position.
It prevents operation of the circuit breaker when the attachment and
a padlock are in place.
Cold Trip
Hot Trip
Time-Current Curves for 140G-G thermal magnetic Molded Case Circuit Breakers
Neutral Pole
When applying 4 pole MCCB, the neutral pole is rated at 100% for
thermal magnetics, and adjustable 100%, 50% or 0% for electronics.
18
For all 4 pole 140G MCCB and Molded Case Switches the neutral is the left outside
pole, as shown in the illustration.
T1
T2
T3
Motor
Reverse Fed
Bulletin 140G & 140MG
IEC
600Y/347
690
480
480
600Y/347
690
600
600
600
600
600
600
690
690
690
690
J
K
M
N, NS
R
L3 L2 L1
Note: The NEC Article 404.7 states Where these switch or circuit breaker handles are operated
vertically rather than rotationally or horizontally, the up position of the handle shall be the
(on) position. Refer to applicable codes and standards for specific application requirements.
Interrupting Ratings
The maximum amount of fault current supplied by a system can be calculated at
any point in that system. One rule must be followed for applying the correct circuit
breaker. The interrupting rating of the breaker must be equal to or greater than the
amount of fault current that can be delivered at that point in the system where the
breaker is applied. The interrupting rating of the breaker is the maximum amount of
fault current it can safely interrupt without damaging itself. A breakers interrupting
rating always decreases as the voltage increases. Interrupting rating is one of the
most critical factors in the breaker selection process.
Certifications
To provide customers with third-party assurance that Rockwell Automation
MCCBs meet industry standards, our circuit breakers comply with various global
standards. The Bulletin 140G MCCB and 140MG MCP and MPCBs comply with UL,
CSA and IEC standards and as such, are UL Listed, CSA Certified, and CCC Certified.
Other certifications exist for the family of MCCBs. The certification of these products
is an ongoing process and additional ratings and certifications are continually being
pursued. For information about compliance with a particular standard, contact your
local Rockwell Automation sales office or Allen-Bradley distributor.
In each of the product sections, the latest certifications at the time of publication are
listed for the specific product type.
19
17.5 A
7.6 A
7.6 A
32.7 A
20
Example
Branch Circuits
Motor circuit
protection
devices with
magnetic-only
trip unit
Molded case
circuit breakers
with thermal
magnetic
protection
contactor
overload relay
starter
Resistive loads
(heating elements, lighting, etc.)
21
22
Cable Selection
UL Listed circuit breakers rated 125 A or less shall be marked as
being suitable for 60 C (140 F), 75 C (167 F) only or 60/75 C
(140/167 F) wire. All Allen-Bradley breakers rated 125 A or less
are marked for 60/75 C wire. All UL Listed circuit breakers rated
over 125 A are suitable for 75 C conductors. Conductors rated
for higher temperatures may be used, but must not be loaded to
carry more current than the 75 C ampacity of that size conductor
for equipment marked or rated 75 C, or the 60 C ampacity
of that size conductor for equipment marked or rated 60 C.
However, the full 90 C (194 F) ampacity may be used when
applying derating factors, so long as the actual load does not
exceed the lower of the derated ampacity or the 75 C or 60 C
ampacity that applies.
Operation below 0 C
Bulletin 140G MCCBs may be applied in ambient temperatures
(near the MCCB within an enclosure) below 0 C. Applications
below 0 C must consider the possibility of ice forming within
or on the MCCB and interfering with the internal or external
operating mechanisms. All ratings below 0 C are based on the
absence of freezing water or other elements.
Altitude
All Frames
100%
90%
79%
67%
Current Rating
Rated Uninterrupted Current Iu [A]
Altitude
All Frames
98%
93%
90%
Tropicalization
The 140G/MG Circuit breakers are tested in compliance with
IEC Standards, making these devices suitable for hot-humid
conditions defined in IEC 60721-2-1, climatograph 8. These
devices include:
Moldings of glass fiber reinforced synthetic resins
Metallic parts treated for anti-corrosion
Zinc plating protected by a conversion layer
(hexavalent-chromium free) (e.g. RoHS compliant)
Electronic circuits protected for anti-condensation
Electromagnetic Compatibility
The 140G/MG Circuit Breakers electronic trip units and electronic
residual current releases are in compliance with EN 609472 Appendix B and Appendix F and European Directive No.
2004/108/EC regarding EMC electromagnetic compatibility.
Altitude
23
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
[A]
[V]
H-Frame
I-Frame
125/160 o
125/160 o
1000
225
800
800
G2
G3
G6
H2
H3
H6
H0
H15
I2
I3
[kA]
50
65
100
65
100
150
200
200
50
65
[kA]
25
35
65
25
35
65
100
150
25
35
[kA]
10
14
25
10
10
[kA]
[kA]
25
35
[kA]
G-Frame
[kA]
[kA]
[kA]
35
42
50
35
50
50
14
18
25
35
42
35
50
65
75
85
35
50
65
75
85
IEC 60947-2
[kA]
65
85
100
65
85
100
150
200
50
85
[kA]
36
50
70
36
50
70
120
150
30
50
[kA]
36
50
70
36
50
70
120
150
36
50
[kA]
36
50
65
30
36
50
60
70
20
40
[kA]
30
36
50
20
25
30
36
50
13
20
[kA]
22
35
35
10
12
15
18
20
[kA]
10
10
12
15
18
20
[kA]
36
50
70
36
50
70
85
100
36
50
[kA]
[kA]
36 l
50 l
70 l
36
50
70
85
100
36
50
[kA]
[kA]
75% (50)
75%
75%
100%
100%
100%
100%
100%
75%
50%
[kA]
100%
100%
75%
100%
100%
100%
100%
100%
75%
50% (27)
[kA]
100%
75%
50%
100%
100%
100%
100%
100%
75%
50% (27)
[kA]
50%
50%
50%
100%
100%
100%
100%
100%
75%
50%
[kA]
50%
50%
50%
100%
100%
100%
100%
100%
75%
50%
[kA]
50%
50%
50%
100%
100%
100%
100%
100%
75%
50%
[kA]
75%
50%
50%
100%
100%
100%
100%
75%
75%
50%
[kA]
100%
75%
75%
100%
100%
100%
100%
100%
100%
75%
[kA]
[kA]
100%
75%
75%
100%
100%
100%
100%
100%
100%
75%
[kA]
Mechanical Life
[No. of Operations]
25000
25000
25000
240
240
240
[No. of Operations]
8000
8000
8000
[C]
120
120
120
Cu 75 C
Cu 75 C
Al or Cu 75 C
F [C]
104 F [40 C]
104 F [40 C]
104 F [40 C]
Storage Temperature
F [C]
-40...176 F [-40+80 C]
-40...176 F [-40+80 C]
-40...176F [-40+80 C]
Dimensions
3 Pole [mm]
76.2x70x130
90x82.5x130
105x70x150
[Width/Depth/Height]
4 Pole [mm]
101.6x70x130
120x82.5x130
140x70x150
j
k
l
m
n
o
24
Explanation of Interrupting Code - G2 for example: G=G Frame 2= 25 kA@480V. See table for complete ratings.
These ratings have not been tested for the CCC listing.
500V DC 4 Poles in series.
Wire Temperature Ratings is determined by testing the circuit breaker under full load current with the conductors sized for 75 C.
DC rating is applicable for thermal-magnetic trip units only.
IEC version with a 160 A Icu rating.
Visit our website: www.rockwellautomation.com
Publication 140G-TD100B-EN-P
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
J-Frame
K-Frame
M-Frame
N & NS-Frame
R-Frame
250
1000
400
1000
800
1000
1200
1000
2000/2500/3000
J2
J3
J6
J0
K3
K6
K0
K15
K5
K6
K0
N5
N6
N0
65
100
150
200
100
150
200
200
100
200
200
65
100
150
125
25
35
65
100
35
65
100
150
50
65
100
50
65
100
125
14
18
25
35
25
35
65
100
25
35
42
25
50
65
100
35
42
50
85
35
50
65
100
35
50
65
25
35
50
65
20
35
50
130
35
50
65
75
R12
65
85
100
150
85
100
200
200
85
100
200
85
100
200
36
50
70
120
50
70
120
200
50
70
100
50
70
120
80
36
50
70
120
50
70
120
200
50
70
100
50
70
120
80
36
50
65
100
40
65
100
180
45
50
80
50
65
100
80
30
36
50
60
30
50
85
150
35
50
65
40
50
85
40
20
25
45
50
25
40
70
100
25
35
42
30
50
65
40
10
12
15
20
25
40
70
100
22
25
30
30
42
50
40
36
50
70
85
50
70
100
150
50
70
100
36
50
70
85
36
50
70
100
35
50
65
36
50
70
85
25
36
50
70
20
36
50
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
75%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
75%
75%
75%
100%
100%
100%
100%
100%
100%
100%
100%
75%
75%
75%
100%
100%
100%
100%
100%
100%
100%
100%
75%
75%
75%
100%
100%
100%
100%
100%
100%
100%
100%
75%
75%
75%
75%(80 kA) 75% (18 kA) 50% (19 kA) 50% (22.5 kA) 75%(30 kA) 50%(31.5 kA) 50% (37.5 kA)
100%
75%
75%
100%
100%
100%
25000
20000
20000
10000
240
120
120
60
60
2000
4500(2000A) 4000
(2500A) 3000 (3200A)
8000
15000
120
60
60
60
60
Al or Cu 75 C
Al or Cu 75 C
Al or Cu 75 C
Al or Cu 75 C
Al or Cu 75 C
104 F [40 C]
104 F [40 C]
104 F [40 C]
104 F [40 C]
104 F [40 C]
-40...176 F [-40+80 C]
-40...176 F [-40+80 C]
-40...176 F [-40+80 C]
-40...176 F [-40+80 C]
-40...176 F [-40+80 C]
105x82.5x160
140x108.5x205
210x103.5x268
210x154(N)/178(NS)x268
427x282x382
140x82.5x160
185x103.5x205
280x103.5x268
280x154(N)/178(NS)x268
553x282x382
Publication 140G-TD100B-EN-P
25
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
EN 60947-2
Breaking Capacity (50/60 Hz)
220V*
240V
480V
600Y/
347V
50
25
10
65
35
14
100
65
25
100
Icu [kA]
415V
440V*
250V DC
(2-pole in series)
690V
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
65
75
36
100
36
50
85
75
50
75
50
50
75
70
50
65
50
500V DC
(3-pole in series)
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
75
36
100
36
100
50
50
100
50
100
10
50
70
75
70
75
* These ratings have not been tested for the CCC listing.
Watt Loss
Molded Case
Switch
Thermal Magnetic
Rated
Current Watt Loss [W]
Type
In [A]
3 Poles 4 Poles
* IEC only.
26
15
4.0
5.3
16
4.5
6.0
20
5.4
7.2
25
6.0
8.0
30
5.5
7.4
Electrical Specifications
Rated Current
In [A]
Magnetic Trip
Im [A]
UL/CSA
IEC
[A]
125
160
125
(600Y/247V AC)
1500
[A]
125
160
[V]
800
[kV]
[V]
Dimensions (mm)
Plus Terminals
32
6.3
8.4
Height
130
35
6.0
8.0
Width (3-pole)
76.2
40
7.8
10.4
9.0
12.0
Width (4-pole)
101.2
Number of Poles
45
50
11.1
14.8
60
11.7
15.6
63
12.9
17.2
Depth (case)
70
101
600Y/347V
3 and 4
Standards Compliance
Weight (kg)
UL489
Yes
70
11.0
14.7
Yes
80
14.4
19.2
3 Poles
1.1
EN 60947-2
Yes
90
17.0
22.7
100
21.0
28.0
4 Poles
1.4
CCC GB 14048.2
Yes
110
24.9
33.1
125
32.1
42.8
160(*)
25
45.0
60.0
1.2
1.6
50
4.9
6.6
75
11.1
14.8
100
19.8
26.4
125
30.9
41.2
690
Temperature Specification*
Mechanical Endurance
Electrical Life (on-off)
at 120 operations per hour
8000
Mechanical (on-off)
at 240 operations per hour
25,000
-25+70 C
(-13+158 F)
Storage Temperature
-40+70 C
(-40+158 F)
Calibration Temperature
40 C (104 F)
Publication 140G-TD100B-EN-P
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Temperature Performance
140G-G Frame Thermal Magnetic Circuit Breakers
The G frame thermal magnetic circuit breaker is calibrated at 40 C (104 F). For applications at
other temperatures there is a variation in the thermal tripping as indicated below.
T amb [C]
40
50
60
70
In [A]
Max. [A]
Max. [A]
Max. [A]
Max. [A]
15
15
14
13
12
16
16
15
14
13
20
20
19
18
16
25
25
23
22
20
30
30
28
26
24
32
32
30
28
26
40
40
38
35
33
45
45
42
40
37
50
50
47
44
41
60
60
56
52
49
63
63
59
55
51
70
70
66
61
57
80
80
75
70
65
90
90
85
79
73
100
100
94
88
81
110
110
103
96
90
125
125
117
109
102
160*
160*
150*
140*
130*
* IEC only.
North America
IEC
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
15
15
15
15
15
15
15
15
30
30
30
30
30
30
30
30
50
50
50
50
50
50
50
50
70
70
70
70
70
70
70
70
80
80
79
79
80
80
80
80
100
93
84
79
100
100
100
100
125
112
97
79
125
125
125
125
160
160
153
136
Publication 140G-TD100B-EN-P
27
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
EN 60947-2
Breaking Capacity (50/60 Hz)
220V*
240V
480V
600V
65
25
14
100
35
18
Icu [kA]
415V
Ics [% Icu ]
Icu [kA]
65
100
85
100
440V*
Ics [% Icu ]
Icu [kA]
36
100
50
100
250V DC
(2-pole in series)
690V
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
36
100
50
100
10
100
12
100
500V DC
(3-pole in series)
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
36
100
36
100
50
100
50
100
150
65
25
100
100
70
100
65
100
15
100
70
100
70
100
200
100
35
150
100
120
100
100
100
18
75
85
100
85
100
200
150
42
200
100
150
100
150
100
20
75
100
100
100
100
UL/CSA
IEC
160
* These ratings have not been tested for the CCC listing.
DC rating is applicable for thermal magnetic trip unit only.
Watt Loss
Molded Case
Switch
Electronic
Thermal Magnetic
Type
* IEC only.
28
Rated
Current
In [A]
15
16
20
25
30
32
35
40
50
60
63
70
80
90
100
110
125
160(*)
10
25
60
100
125
25
50
75
100
125
Rated Current
In [A]
Electrical Specifications
Magnetic Trip
Im [A]
125
1500
Dimensions (mm)
Plus Terminals
Height
130
Width (3-pole)
90
Width (4-pole)
120
Depth (case)
82.5
101
[A]
125
[A]
125
[V]
1000
[kV]
[V]
600
690
[V AC]
480
480
160
Number of Poles
3 and 4
Standards Compliance
Weight (kg)
UL489
Yes
3 Poles
1.2
Yes
4 Poles
1.6
EN 60947-2
Yes
CCC GB 14048.2
Yes
Mechanical Endurance
Electrical Life (on-off)
at 120 operations per hour
Mechanical (on-off)
at 240 operations per hour
Temperature Specification*
8000
-25+70 C
(-13+158 F)
Storage Temperature
-40+70 C
(-40+158 F)
Calibration Temperature
40 C (104 F)
25,000
Publication 140G-TD100B-EN-P
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Temperature Performance
140G-H Frame Thermal Magnetic Circuit Breakers
The H frame thermal magnetic circuit breaker is calibrated at 40 C (104 F). For applications at
other temperatures there is a variation in the thermal tripping as indicated below.
T amb [C]
40
50
60
70
In [A]
Max. [A]
Max. [A]
Max. [A]
Max. [A]
15
15
14
13
12
16
16
15
14
13
20
20
19
17
16
25
25
23
22
20
30
30
28
26
24
32
32
30
28
26
40
40
37
35
32
50
50
47
43
40
60
60
56
52
49
63
63
59
55
51
70
70
66
61
57
80
80
75
70
65
90
90
86
78
73
100
100
93
87
81
110
110
103
96
89
125
125
117
109
101
160*
160*
150*
139*
129*
* IEC only.
Electronic Trip Circuit Breakers, Molded Case Switches and Motor Circuit Protectors
The electronic trip circuit breakers do not undergo tripping variations due to ambient temperature.
However, even though ambient temperature does not affect the tripping characteristic, for temperatures
exceeding +40 C it is advisable to reduce the maximum current to prevent terminal overheating.
The same considerations are appropriate for molded case switch and motor circuit protectors.
The tables below show the maximum current to prevent terminal overheating.
North America
IEC
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
15
15
15
15
15
15
15
15
30
30
30
30
30
30
30
30
50
50
50
50
50
50
50
50
70
70
70
70
70
70
70
70
80
80
79
79
80
80
80
80
100
93
84
79
100
100
100
100
125
112
97
79
125
125
125
125
160
160
146
131
Publication 140G-TD100B-EN-P
29
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
EN 60947-2
Breaking Capacity (50/60 Hz)
220V*
240V
480V
600Y/
347V
Icu [kA]
50
25
10
65
35
10
415V
440V*
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
50
75
36
75
85
50
50
50
Icu [kA]
250V DC
(2-pole in series)
690V
500V DC
(3-pole in series)
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
25
75
50
36
100
36
100
40
50
50
50
75
50
75
UL/CSA
IEC
225
* These ratings have not been tested for the CCC listing.
Watt Loss
Thermal Magnetic
Type
30
Rated
Current Watt Loss [W]
In [A]
3 Poles 4 Poles
Electrical Specifications
Rated Current
In [A]
Magnetic Trip
Im [A]
225
2700
[A]
225
[A]
225
60
11.7
15.6
63
12.9
17.2
Dimensions (mm)
[V]
800
Plus Terminals
[kV]
[V]
70
11.0
14.7
80
14.4
19.2
90
13.6
18.1
100
16.8
22.4
110
17.4
23.2
125
19.8
26.4
150
20.8
27.8
160
23.7
31.6
175
30.3
40.4
200
39.6
52.8
225
25
50
75
100
125
150
175
200
43.2
57.6
0.5
2.1
4.8
8.5
13.3
19.2
26.1
34.1
0.7
2.8
6.4
11.4
17.8
25.6
34.8
45.5
225
43.2
57.6
Height
150
Width (3-pole)
105
Width (4-pole)
140
Depth (case)
70
Number of Poles
101
4 Poles
Mechanical (on-off)
at 240 operations per hour
690
3 and 4
UL489
Yes
1.7
Yes
2.1
EN 60947-2
Yes
CCC GB 14048.2
Yes
Mechanical Endurance
Electrical Life (on-off)
at 120 operations per hour
600Y/347V
Standards Compliance
Weight (kg)
3 Poles
225
Temperature Specification*
8000
-25+70 C
(-13+158 F)
Storage Temperature
-40+70 C
(-40+158 F)
Calibration Temperature
40 C (104 F)
25,000
Publication 140G-TD100B-EN-P
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Temperature Performance
140G-I Frame Thermal Magnetic Circuit Breakers
The I frame thermal magnetic circuit breaker is calibrated at 40 C (104 F). For applications at
other temperatures there is a variation in the thermal tripping as indicated below.
T amb [C]
40
50
60
70
In [A]
Max. [A]
Max. [A]
Max. [A]
Max. [A]
60
60
56
52
49
63
63
59
55
51
70
70
66
60
56
80
80
75
69
64
90
90
84
78
72
100
100
93
87
80
110
110
102
95
88
125
125
116
108
100
150
150
140
130
121
160
160
149
139
129
200
200
186
173
161
225
225
210
196
181
North America
IEC
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
100
100
100
100
100
100
100
100
110
110
110
110
110
110
110
110
125
125
125
125
125
125
125
125
150
148
153
142
150
150
150
150
200
181
161
142
200
200
200
200
225
199
175
142
225
225
214
204
Publication 140G-TD100B-EN-P
31
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
EN 60947-2
Breaking Capacity (50/60 Hz)
220V*
600V
Icu [kA]
415V
Ics [% Icu ]
Icu [kA]
65
100
85
100
240V
480V
65
25
14
100
35
18
150
65
25
100
200
100
35
150
440V*
Ics [% Icu ]
Icu [kA]
36
100
50
100
100
70
100
120
250V DC
(2-pole in series)
690V
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
36
100
50
100
10
100
12
100
100
65
100
100
100
15
100
20
500V DC
(3-pole in series)
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
36
100
36
100
50
100
50
100
100
70
100
70
100
100
85
100
85
100
* These ratings have not been tested for the CCC listing.
DC rating is applicable for thermal magnetic trip unit only.
Watt Loss
Electronic
Thermal Magnetic
Type
32
Rated
Current Watt Loss [W]
In [A]
3 Poles 4 Poles
25
8.1
10.7
30
11.6
15.5
32
13.2
17.6
35
13.2
17.6
40
13.5
18.0
50
14.1
18.8
60
14.4
19.2
63
15.9
21.2
70
16.2
21.6
80
16.5
22.0
90
18.0
24.0
100
18.6
24.8
110
20.1
26.8
125
22.2
29.6
150
23.5
31.3
160
26.7
35.6
175
27.3
36.4
200
35.7
47.6
225
39.9
53.1
250
49.2
65.6
40
1.8
2.4
60
3.8
5.1
63
4.2
5.6
100
10.5
14.0
150
23.5
31.4
225
53.0
70.6
250
65.4
87.2
25
0.7
0.9
50
2.6
3.5
75
5.9
7.8
100
10.5
14.0
125
16.4
21.8
150
23.5
31.4
175
32.0
42.7
200
41.9
55.8
225
53.0
70.6
250
65.4
87.2
Electrical Specifications
UL/CSA
IEC
[A]
250
250
[A]
250
250
Dimensions (mm)
[V]
1000
Plus Terminals
[kV]
[V]
600
[V AC]
600
Rated Current
In [A]
Magnetic Trip
Im [A]
250
3000
Height
160
Width (3-pole)
105
Width (4-pole)
140
Depth (case)
82.5
117
Number of Poles
690
600
3 and 4
Standards Compliance
Weight (kg)
3 Poles
2.5
4 Poles
3.5
Mechanical Endurance
Electrical Life (on-off)
at 120 operations per hour
8000
Mechanical (on-off)
at 240 operations per hour
25,000
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
(based on the absence of freezing water or other elements)
-25+70 C
(-13+158 F)
Storage Temperature
-40+70 C
(-40+158 F)
Calibration Temperature
40 C (104 F)
Publication 140G-TD100B-EN-P
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Temperature Performance
140G-J Frame Thermal Magnetic Circuit Breakers
The J frame thermal magnetic circuit breaker is calibrated at 40 C (104 F). For applications at
other temperatures there is a variation in the thermal tripping as indicated below.
T amb [C]
40
50
60
70
In [A]
Max. [A]
Max. [A]
Max. [A]
Max. [A]
25
25
23
21
19
30
30
25
23
20
32
32
27
24
21
35
35
32
30
26
40
40
37
34
30
50
50
46
42
39
60
60
56
51
45
63
63
58
53
48
70
70
65
58
51
80
80
74
66
58
90
90
86
77
68
100
100
95
85
75
110
110
101
92
84
125
125
115
105
95
160
160
150
137
140
175
175
166
153
142
200
200
190
175
160
225
225
208
190
170
250
250
240
230
220
North America
IEC
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
150
150
150
150
150
150
150
150
175
175
164
158
175
175
175
175
200
200
172
158
200
200
200
200
225
225
180
158
225
225
221
213
250
250
222
158
250
250
238
213
Publication 140G-TD100B-EN-P
33
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
240V
2-pole
in series
3-pole
in series
500V DC
600V DC
220V*
Icu [kA]
415V
440V*
500V DC
(3-pole in series)
690V
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
85
100
50
100
40
100
100
70
100
65
120
100
100
100
70
100
70
100
200
100
180
100
80
100
100
100
480V
600V
100
35
25
35
25
150
65
35
50
35
200
100
65
65
50
200
100
200
150
100
100
65
200
100
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
100
25
100
36
100
100
40
100
50
100
* These ratings have not been tested for the CCC listing.
Watt Loss
Thermal
Magnetic
Type
Rated
Watt Loss [W]
Current
In [A]
3 Poles 4 Poles
300
40.8
54.4
Electrical Specifications
Rated Current
In [A]
Magnetic Trip
Im [A]
400
5000
Dimensions (mm)
Plus Terminals
400
Molded Case Switch
and Electronic
300
58.5
31.8
78.0
42.4
Height
205
Width (3-pole)
139.5
Width (4-pole)
186
Depth (case)
103.5
49.5
139
Weight (kg)
3.25
4 Poles
4.15
IEC
[A]
400
400
[A]
400
400
[V]
1000
[kV]
[V]
Number of Poles
600
690
3 and 4
Standards Compliance
66
3 Poles
UL/CSA
Maximum Rated Current (In)
Mechanical Endurance
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
7000
Mechanical (on-off)
at 120 operations per hour
20,000
-25+70 C
(-13+158 F)
Storage Temperature
-40+70 C
(-40+158 F)
Calibration Temperature
40 C (104 F)
34
Publication 140G-TD100B-EN-P
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Temperature Performance
140G-K Frame Thermal Magnetic Circuit Breakers
The K frame thermal magnetic circuit breaker is calibrated at 40 C (104 F). For applications at
other temperatures there is a variation in the thermal tripping as indicated below.
T amb [C]
40
50
60
70
In [A]
Max. [A]
Max. [A]
Max. [A]
Max. [A]
300
300
286
267
247
400
400
380
355
325
North America
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
In [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
300
300
264
228
189
400
400
352
304
252
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
Imax [A]
Imax [A]
Imax [A]
Imax [A]
IEC
In [A]
300
300
300
300
300
400
400
400
400
352
Publication 140G-TD100B-EN-P
35
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
EN 60947-2
220V*
240V
480V
600V
600V DC
415V
Icu [kA]
Ics [% Icu ]
Icu [kA]
500V DC
(3-pole in series)
690V
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
100
50
25
20
85
100
50
100
22
75
16
75
200
65
35
35
100
100
70
100
25
75
36
75
200
100
42
50
200
75
100
75
30
75
50
75
* These ratings have not been tested for the CCC listing.
Watt Loss
Thermal Magnetic
Type
Rated
Watt Loss [W]
Current
In [A]
3 Poles 4 Poles
600
90.0
120.0
Electrical Specifications
Rated Current
In [A]
Magnetic Trip
Im [A]
800
10,000
Dimensions (mm)
Plus Terminals
630 (*)
800
* IEC only
91.8
93.0
122.4
124.0
Height
268
Width (3-pole)
210
Width (4-pole)
280
Depth (case)
600
86.4
115.2
630 (*)
90.0
120.0
800
96.0
128.0
IEC
800
[A]
800
[A]
800
[V]
1000
[kV]
[V]
Number of Poles
103.5
UL/CSA
159
800
600
690
3 and 4
Standards Compliance
Weight (kg)
3 Poles
12.1
4 Poles
15.1
Mechanical Endurance
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
7000 (630 A)
5000 (800 A)
Mechanical (on-off)
at 120 operations per hour
20,000
-25+70 C
(-13+158 F)
Storage Temperature
-40+70 C
(-40+158 F)
Calibration Temperature
40 C (104 F)
36
Publication 140G-TD100B-EN-P
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Temperature Performance
140G-M Frame Thermal Magnetic Circuit Breakers
The M frame thermal magnetic circuit breaker is calibrated at 40 C (104 F). For applications at
other temperatures there is a variation in the thermal tripping as indicated below.
T amb [C]
40
50
60
70
In [A]
Max. [A]
Max. [A]
Max. [A]
Max. [A]
600
600
552
514
476
630*
630
580
540
500
800
800
740
670
610
* IEC only.
North America
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
In [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
600
600
528
456
378
800
800
704
608
504
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
In [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
630
630
630
598.5
567
800
800
800
760
720
IEC
Publication 140G-TD100B-EN-P
37
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Interrupting Rating/Breaking Capacity Electronic Circuit Breakers (See page 25 for additional voltages breaking capacities)
Interrupting Rating (50/60 Hz),
UL 489/CSA C22.2-5, No. 5 [kA]
240V
480V
600V
Icu [kA]
415V
500V
690V
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
65
50
25
85
85
50
50
50
50
40
40
30
30
100
65
50
100
100
70
70
65
65
50
50
42
32
150
100
65
200
200
120
120
100
100
85
64
50
38
1200
4 Poles
252.0
336.0
Magnetic Trip
Im [A]
1200
20,000
Dimensions (mm)
Electrical Specifications
UL/CSA
IEC
1200
[A]
1200
[A]
1200
[V]
1000
[kV]
[V]
1200
600
Number of Poles
690
3 and 4
Standards Compliance
Plus Terminals
Height
268
Width (3-pole)
210
Width (4-pole)
280
Depth (case)
125
225
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
Weight (kg)
N 3/4 Poles
9.7/12.5
NS 3/4 Poles
11/14
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
40 C (104 F)
Mechanical Endurance
Electrical Life (on-off)
at 60 operations per hour
2000
Mechanical (on-off)
at 60 operations per hour
10,000
38
440V
Publication 140G-TD100B-EN-P
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Temperature Performance
140G-N/NS Frame Electronic Trip Circuit Breakers, Molded Case Switches and
Motor Circuit Protectors
The N/NS frame electronic trip circuit breakers do not undergo tripping variations due to
ambient temperature. However, even though ambient temperature does not affect the tripping
characteristic, for temperatures exceeding +40 C it is advisable to reduce the maximum current to
prevent terminal overheating.
The same considerations are appropriate for molded case switch and motor circuit protectors.
The tables below show the maximum current to prevent terminal overheating.
North America
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
In [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
1200
1200
1056
815
756
IEC
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
In [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
1250
1250
1250
1118
980
Publication 140G-TD100B-EN-P
39
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Interrupting Rating/Breaking Capacity Electronic Circuit Breakers (See page 25 for additional voltages breaking capacities)
Interrupting Rating (50/60 Hz),
UL 489/CSA C22.2-5, No. 5 [kA]
415V
440V
500V
690V
240V
480V
600V
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
125
125
100
130
97.5
80
60
80
60
40
40
40
40
3 Poles
4 Poles
2000
138
184
2500
219
292
3000
351
468
Magnetic Trip
Im [A]
2500
40,000
Electrical Specifications
UL/CSA
IEC
[A]
3000
3000
[A]
3000
3000
[V]
1000
[kV]
12
[V]
600
Number of Poles
690
3 and 4
Standards Compliance
Dimensions (mm)
UL489
Yes
Plus Terminals
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Height
382
Width (3-pole)
428
Width (4-pole)
554
Depth (case)
231
284
Temperature Specification*
Ambient Operating Temperature Range
Weight (kg)
3 Pole
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
73
40 C (104 F)
Mechanical Endurance
Electrical Life (on-off)
at 60 operations per hour
4500 (2000 A)
4000 (3000 A)
Mechanical (on-off)
at 60 operations per hour
15,000
40
Publication 140G-TD100B-EN-P
Bulletin 140G
Product Specifications
Molded Case Circuit Breakers
Temperature Performance
140G-R Frame Electronic Trip Circuit Breakers and Molded Case Switches
The R frame electronic trip circuit breakers do not undergo tripping variations due to ambient
temperature. However, even though ambient temperature does not affect the tripping
characteristic, for temperatures exceeding +40 C it is advisable to reduce the maximum setting for
external thermal protection against overloads per the following.
The same considerations are appropriate for molded case switches, except instead of a current
adjustment, the table should be used to reflect the maximum current at the specific temperature.
The tables below show the maximum adjustment at which the threshold I1 of the overcurrent
protection (L) must be set according to the ambient temperature.
North America
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
In [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
2000
2000
1760
1520
1260
2500
2500
2200
1900
1575
3000
3000
2640
2280
1890
IEC
40 C (104 F)
50 C (122 F)
60 C (140 F)
70 C (158 F)
In [A]
Imax [A]
Imax [A]
Imax [A]
Imax [A]
2000
2000
2000
1826
1633
2500
2500
2500
2283
2042
3000
3000
3000
2800
2613
Publication 140G-TD100B-EN-P
41
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
G-Frame
H-Frame
I-Frame
125
125
225
[A]
Poles
Instantaneous Trip Settings
[A]
3125
3...125
100150
[V]
800
1000
800
UL 489 Instantaneous Trip Circuit Breaker (Magnetic Only) Max SCCR. Combination Controller Rating k
480V AC
[kA]
65
65
35
600/347V AC
[kA]
25
10
600V AC
[kA]
25
[kA]
65 n
100 o
85
400-415V AC
[kA]
36 n
70 o
50
440V AC j
[kA]
36 n
65 o
40
500V AC
[kA]
30 n
50 o
30
525V AC
[kA]
22 n
30 o
20
690V AC
[kA]
6 n
15 o
[kA]
36 n
36 o
50
[kA]
36 o
50
[kA]
75% n
100% o
50%
400-415V AC
[kA]
100% n
100% o
50% (27)
440V AC j
[kA]
50% n
100% o
50% (27)
500V AC
[kA]
50% n
100% o
50%
525V AC
[kA]
50% n
100% o
50%
690V AC
[kA]
75% n
100% o
50%
[kA]
100% n
100% o
75%
[kA]
100% o
75%
25000
Mechanical Life
Electrical Life @ 415V (AC)
[No. of Operations]
25000
25000
240
240
240
[No. of Operations]
8000
8000
8000
120
120
120
Cu 75 C
Al or Cu 75 C
Al or Cu 75 C
F [C]
104 F [40 C]
104 F [40 C]
104 F [40 C]
Operating Temperature
F [C]
-13+158 F [-25+70 C]
-13+158 F [-25+70 C]
-13+158 F [-25+70 C]
Storage Temperature
F [C]
-40...158 F [-40+70 C]
-40...158 F [-40+70 C]
-40...158 F [-40+70 C]
[mm]
76.2x70x130
90x82.5x130
105x70x150
[inches]
3x2.76x5.12
3.54x3.25x5.12
4.13x2.76x5.9
2.4 [1.1]
2.6 [1.2]
3.7 [1.7]
Dimensions
[Width/Depth/Height]
Weight (approximate)
lb [kg]
j These ratings have not been tested for the CCC listing.
k The Short Circuit value is based on a combined of MCP, motor contactor and overload relay as a UL60497-4-1 Type D Combination Motor Controller.
Refer to the AB Global Short Circuit Current Ratings Tables, or contact your local Allen Bradley Representative.
l Adjustable between 110x motor FLA. Value based on 1200A rating plug.
m Wire temperature Rating is determined by testing the Motor Circuit Protector under full load current with the conductors sized for 75 C.
3A7A, G Frame
42
230V
415V
440V
500525V
690V
250V DC
Icu [kA]
Ics [kA]
100%
100%
100%
100%
100%
100%
Publication 140G-TD100B-EN-P
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
J-Frame
K-Frame
M-Frame
N-Frame
250
400
800
1200
150250
1200 l
1000
1000
1000
1000
65
65
65
25
35
35
100
100
100
100
70
70
70
70
65
65
50
65
50
50
50
50
45
40
25
42
15
40
25
42
70
70
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
75%
75%
100%
100%
75%
75%
100%
100%
25000
20000
20000
10000
240
120
120
60
8000
7000
5000
2000
120
60
60
60
Al or Cu 75 C
Al or Cu 75 C
Al or Cu 75 C
Al or Cu 75 C
104 F [40 C]
104 F [40 C]
104 F [40 C]
104 F [40 C]
-13+158 F [-25+70 C]
-13+158 F [-25+70 C]
-13+158 F [-25+70 C]
-13+158 F [-25+70 C]
-40...158 F [-40+70 C]
-40...158 F [-40+70 C]
-40...158 F [-40+70 C]
-40...158 F [-40+70 C]
105x82.5x160
140x108.5x205
210x103.5x268
210x154x268
4.13x3.25x6.3
5.51x4.27x8.07
8.27x4.07x10.55
8.27x6.06x10.55
5.5 [2.5]
7.2 [3.25]
21 [9.5]
21.4 [9.7]
3A7A, H Frame
230V
415V
440V
500525V
690V
250V DC
500V DC
Icu [kA]
Ics [kA]
100%
100%
100%
100%
100%
100%
100%
Publication 140G-TD100B-EN-P
43
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
230V AC
460V AC
575V AC
40
100
125
IEC kW Rating
@ 50 Hz
230V AC
400/415V AC
690V AC
22
45
110
Dimensions (mm)
Electrical Specifications
Plus Terminals
Maximum
Height
130
Width (3-pole)
76.2
[A]
125
[kV]
800
[kV]
Depth (case)
70
101
Mechanical Endurance
8000
Mechanical (on-off)
at 240 operations per hour
25,000
Watt Loss
44
Rated Current
In [A]
4.2
9.9
15
3.3
30
6.9
50
9.3
70
15.9
80
15.9
100
19.8
125
30.9
[A]
125
8
UL/CSA [60 Hz]
600Y/347V
690
[V]
Number of Poles
Standards Compliance
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
Ambient Operating Temperature Range
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
40 C (104 F)
* For use at temperatures other than 40 C (104 F), see the Temperature Performance information
on page 27.
Publication 140G-TD100B-EN-P
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
230V AC
460V AC
575V AC
40
100
125
IEC kW Rating
@ 50 Hz
230V AC
400/415V AC
690V AC
22
45
110
Dimensions (mm)
Electrical Specifications
Plus Terminals
Maximum
Height
130
Width (3-pole)
90
[A]
125
[kV]
1000
[kV]
Depth (case)
82.5
101
Mechanical Endurance
8000
Mechanical (on-off)
at 240 operations per hour
25,000
Watt Loss
125
8
UL/CSA [60 Hz]
[A]
[V]
[V AC]
600
690
480
480
Number of Poles
Standards Compliance
Rated Current
In [A]
UL489
Yes
Yes
11.1
EN 60947-2
Yes
27.9
CCC GB 14048.2
Yes
15
19.2
30
11.4
50
15
70
16.5
-25+70 C (-13+158 F)
80
20.4
Storage Temperature
-40+70 C (-40+158 F)
100
24.3
Calibration Temperature
125
42
Publication 140G-TD100B-EN-P
Temperature Specification*
40 C (104 F)
* For use at temperatures other than 40 C (104 F), see the Temperature Performance information
on page 29.
45
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
230V AC
460V AC
575V AC
50
100
125
IEC kW Rating
@ 50 Hz
230V AC
400/415V AC
690V AC
22
45
90
Dimensions (mm)
Electrical Specifications
Plus Terminals
Maximum
Height
150
Width (3-pole)
105
Depth (case)
70
[A]
225
101
[kV]
800
[kV]
Mechanical Endurance
8000
Mechanical (on-off)
at 240 operations per hour
25,000
Watt Loss
Rated Current
In [A]
100
13.5
110
9.9
125
12.3
150
19.5
[A]
225
8
UL/CSA [60 Hz]
600Y/347V
690
[V]
Number of Poles
Standards Compliance
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
Ambient Operating Temperature Range
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
40 C (104 F)
* For use at temperatures other than 40 C (104 F), see the Temperature Performance information
on page 31.
46
Publication 140G-TD100B-EN-P
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
230V AC
460V AC
575V AC
100
200
250
IEC kW Rating
@ 50 Hz
230V AC
400/415V AC
690V AC
55
90
160
Dimensions (mm)
Electrical Specifications
Plus Terminals
Maximum
Height
160
Width (3-pole)
105
Depth (case)
82.5
[A]
250
117
[kV]
1000
[kV]
Mechanical Endurance
8000
Mechanical (on-off)
at 240 operations per hour
25,000
Watt Loss
250
8
UL/CSA [60 Hz]
[A]
[V]
[V AC]
600
690
600
600
Number of Poles
Standards Compliance
Rated Current
In [A]
150
UL489
Yes
Yes
23.4
EN 60947-2
Yes
175
27.3
CCC GB 14048.2
Yes
200
35.7
225
39.9
250
49.2
Temperature Specification*
Ambient Operating Temperature Range
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
40 C (104 F)
* For use at temperatures other than 40 C (104 F), see the Temperature Performance information
on page 33.
Publication 140G-TD100B-EN-P
47
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
230V AC
460V AC
575V AC
100
250
300
IEC kW Rating
@ 50 Hz
230V AC
400/415V AC
690V AC
90
160
250
Dimensions (mm)
Electrical Specifications
Plus Terminals
Maximum
Height
205
Width (3-pole)
139.5
Depth (case)
103.5
[A]
400
[kV]
1000
[kV]
139
Mechanical Endurance
7000
Mechanical (on-off)
at 120 operations per hour
20,000
Watt Loss
Rated Current
In [A]
300
31.8
400
49.5
[A]
400
8
UL/CSA [60 Hz]
600
690
[V]
Number of Poles
Standards Compliance
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
Ambient Operating Temperature Range
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
40 C (104 F)
* For use at temperatures other than 40 C (104 F), see the Temperature Performance information
on page 35.
48
Publication 140G-TD100B-EN-P
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
230V AC
460V AC
575V AC
200
400
500
IEC kW Rating
@ 50 Hz
230V AC
400/415V AC
690V AC
160
250
500
Dimensions (mm)
Electrical Specifications
Plus Terminals
Maximum
Height
268
Width (3-pole)
210
[A]
800
[kV]
1000
[kV]
Depth (case)
103.5
159
Mechanical Endurance
Electrical Life (on-off)
at 60 operations per hour
7000 (630 A)
5000 (800 A)
Mechanical (on-off)
at 120 operations per hour
20,000
Watt Loss
Rated Current
In [A]
600
86.4
800
96.0
[A]
800
8
UL/CSA [60 Hz]
600
690
[V]
Number of Poles
Standards Compliance
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
Ambient Operating Temperature Range
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
40 C (104 F)
* For use at temperatures other than 40 C (104 F), see the Temperature Performance information
on page 37.
Publication 140G-TD100B-EN-P
49
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
230V AC
460V AC
575V AC
300
600
700
IEC kW Rating
@ 50 Hz
230V AC
400/415V AC
690V AC
200
250
710
Dimensions (mm)
Electrical Specifications
Plus Terminals
Maximum
Height
268
Width (3-pole)
210
Depth (case)
125
[A]
1200
225
[kV]
1000
[kV]
Mechanical Endurance
2000
Mechanical (on-off)
at 60 operations per hour
10,000
Watt Loss
Rated Current
In [A]
1200
252.0
[A]
1200
8
UL/CSA [60 Hz]
600
690
[V]
Number of Poles
Standards Compliance
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
Ambient Operating Temperature Range
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
40 C (104 F)
* For use at temperatures other than 40 C (104 F), see the Temperature Performance information
on page 39.
50
Publication 140G-TD100B-EN-P
Bulletin 140MG
Product Specifications
Motor Circuit Protectors
Publication 140G-TD100B-EN-P
51
Bulletin 140MG
Product Specifications
Motor Protection Circuit Breakers
H-Frame
J-Frame
[A]
100
150
[V]
1000
1000
H8
J8
[kA]
150
150
[kA]
65
65
[kA]
25
25
[kA]
100
100
[kA]
70
70
IEC 60947-2
[kA]
70
70
[kA]
65
65
[kA]
15
45
[kA]
15
45
[kA]
15
15
[kA]
100%
100%
[kA]
100%
100%
[kA]
100%
100%
[kA]
100%
100%
[kA]
100%
100%
[kA]
100%
100%
[kA]
100%
100%
[No. of Operations]
25000
25000
240
240
[No. of Operations]
8000
8000
120
120
Mechanical Life
Cu 75 C
Al or Cu 75 C
F [C]
104 F [40 C]
104 F [40 C]
Operational Temperature
F [C]
-13+158 F [-25+70 C]
-13+158 F [-25+70 C]
Storage Temperature
F [C]
-40...158 F [-40+70 C]
-40...158 F [-40+70 C]
[mm]
90x82.5x130
105x82.5x160
3.54x3.25x5.12
4.13x3.25x6.3
2.6 [1.2]
5.5 [2.5]
Dimensions
[Width/Depth/Height]
Weight (approximate)
[C]
[inches]
lb [kg]
j Explanation of Interrupting Code H8 for example: H=H Frame & 8=65 kA@480V. See table for complete ratings.
k These ratings have not been tested for the CCC listing.
l Wire temperature Rating is determined by testing the Motor Circuit Protector under full load current with the conductors sized for 75 C.
52
Publication 140G-TD100B-EN-P
Bulletin 140MG
Product Specifications
Motor Protection Circuit Breakers
EN 60947-2
Breaking Capacity (50/60 Hz)
220V*
415V
440V*
250V DC
(2-pole in series)
690V
500V DC
(3-pole in series)
240V
480V
600V
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
150
65
25
100
100
70
100
65
100
15
100
70
100
70
100
* These ratings have not been tested for the CCC listing.
Dimensions (mm)
Electrical Specifications
Plus Terminals
Maximum
Height
130
Width (3-pole)
90
82.5
[A]
100
101
[kV]
1000
[kV]
[V]
Depth (case)
Depth (op handle)
Mechanical Endurance
Electrical Life (on-off)
at 120 operations per hour
Mechanical (on-off)
at 240 operations per hour
8000
25,000
Watt Loss
[A]
[V AC]
100
600
690
480
480
Number of Poles
Standards Compliance
Rated Current
In [A]
10
0.3
25
2.4
60
4.5
100
12.6
UL489
Yes
Yes
EN 60947-2
Yes
CCC GB 14048.2
Yes
Temperature Specification*
Ambient Operating Temperature Range
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
40 C (104 F)
* For use at temperatures other than 40 C (104 F), see the Temperature Performance information
on page 29.
Publication 140G-TD100B-EN-P
53
Bulletin 140MG
Product Specifications
Motor Protection Circuit Breakers
Interrupting Rating/Breaking Capacity Motor Protection Circuit Breaker (See page 52 for additional voltages breaking capacities)
Interrupting Rating
(50/60 Hz), UL 489/CSA
C22.2-5, No. 5-02 [kA]
EN 60947-2
Breaking Capacity (50/60 Hz)
220V*
415V
440V*
250V DC
(2-pole in series)
690V
500V DC
(3-pole in series)
240V
480V
600V
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
Icu [kA]
Ics [% Icu ]
150
65
25
100
100
70
100
65
100
15
100
70
100
70
100
* These ratings have not been tested for the CCC listing.
Dimensions (mm)
Electrical Specifications
Plus Terminals
Maximum
Height
160
Width (3-pole)
105
Depth (case)
82.5
[A]
250
117
[kV]
1000
[kV]
[V]
Mechanical Endurance
Electrical Life (on-off)
at 120 operations per hour
Mechanical (on-off)
at 240 operations per hour
[A]
250
8000
Maximum Reverse Fed Voltage
25,000
Watt Loss
[V AC]
600
690
600
600
Number of Poles
Standards Compliance
Rated Current
In [A]
40
UL489
Yes
Yes
1.8
EN 60947-2
Yes
60
3.8
CCC GB 14048.2
Yes
63
4.2
100
10.5
150
23.5
Temperature Specification*
Ambient Operating Temperature Range
-25+70 C (-13+158 F)
Storage Temperature
-40+70 C (-40+158 F)
Calibration Temperature
40 C (104 F)
* For use at temperatures other than 40 C (104 F), see the Temperature Performance information
on page 33.
54
Publication 140G-TD100B-EN-P
Bulletin 140MG
Accessories
Auxiliary & Alarm Contacts
AL1 Auxiliary
Test Button
Position of the Contacts when the Circuit Breaker Trip Unit has
TRIPPED. This can occur from fault current of thermal overload
or via the Test Button on the center pole of TM trip units.
Publication 140G-TD100B-EN-P
55
Bulletin 140G
Accessories
Auxiliary & Alarm Contacts
140G Family
Frame
Order
Code Catalog Number G H
140G-G-EA1R1A
140G-K-EA1R1A
Rated
Voltage
Ue [V] AWG mm2
Description
X O O
250V
20
0.5
O O O O X X
250V
20
0.5
140G-H-EA1R1ZB O X O X O O
400V
17
1m
(39 in.)
12 A @ 250V AC
3 A @ 400V AC
0.5 A @ 125V DC
0.3 A @ 250V DC
10 A @ 125V AC
10 A @ 250V AC
140G-K-EA1R1B
O O O O X X
400V
17
1m
(39 in.)
12 A @ 250V AC
3 A @ 400V AC
0.5 A @ 125V DC
0.3 A @ 250V DC
12 A @ 125V AC
12 A @ 250V AC
140G-N-EA1R1B
X
O O O O O O (N only)
O
400V
17
1m
(39 in.)
12 A @ 250V AC
3 A @ 400V AC
0.5 A @ 125V DC
0.3 A @ 250V DC
12 A @ 125V AC
12 A @ 250V AC
140G-G-EA1R1J
Aux - Form C
O ((1)
(1) AL - Form C
24V
20
0.5
1m
(39 in.)
140G-N-EA1R1J
X
O O O O O O (N only)
O
24V
20
0.5
1m
(39 in.)
AA
AB
AJ
N, NS
K M
Wire Size
X O O
UL Rating
5 A @ 125V AC
3 A @ 250V AC
5 A @ 125V AC
6 A @ 250V AC
5 A @ 24V DC
0.5 A @ 110V DC
5 A @ 125V AC
0.3 A @ 250V DC
3 A @ 250V AC
(min. 0.03 A DC)
5 A @ 24V DC
0.5 A @ 110V DC
5 A @ 125V AC
0.3 A @ 250V DC
3 A @ 250V AC
(min. 0.03 A DC)
5 A @ 24V DC
0.5 A @ 110V DC
5 A @ 125V AC
0.3 A @ 250V DC
6 A @ 250V AC
(min. 0.03 A DC)
Max. 0.1 A @ 24V DC
Min. 0.01 A @ 5V DC min.
X O O
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
140G-H-EA3R1A O X
X O O
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
140G-K-EA3R1A
O O O O X X
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
140G-H-EA3R1J
O X
X O O
24V
20
0.5
1m
(39 in.)
140G-K-EA3R1J
O O O O X X
24V
20
0.5
1m
(39 in.)
DA
140G-H-EA1TA
O X O X O O
AL - Form C
O (1) TU
(Thermal)
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
DJ
140G-H-EA1TJ
O X O X O O
AL - Form C
O (1) TU
(Thermal)
24V
20
0.5
1m
(39 in.)
140G-H-EA2B
O X O X O O
400V
17
1m
(39 in.)
12 A @ 250V AC
3 A @ 400V AC
0.5 A @ 125V DC
0.3 A @ 250V DC
12 A @ 125V AC
12 A @ 250V AC
140G-K-EA2B
O O O O X X
400V
17
1m
(39 in.)
12 A @ 250V AC
3 A @ 400V AC
0.5 A @ 125V DC
0.3 A @ 250V DC
10 A @ 125V AC
10 A @ 250V AC
KA
140G-G-EA1A
X O O
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
0.5 A @ 110V DC
0.3 A @ 250V DC
(min. 0.03 A DC)
5 A @ 125V AC
3 A @ 250V AC
TA
140G-G-EA1AU
X O O
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
5 A @ 24V DC
0.5 A @ 110V DC
0.3 A @ 250V DC
(min. 0.03 A DC)
140G-G-EA1J
X O O
24V
20
0.5
1m
(39 in.)
BA
140G-G-EA2R1A X
CA
CJ
5 A @ 125V AC
3 A @ 250V AC
FB
56
Publication 140G-TD100B-EN-P
Bulletin 140G
Accessories
Auxiliary & Alarm Contacts
Application Ratings
140G Family
Frame
Order
Code Catalog Number
G H
Wire Size
N,
K M NS R
IEC Rating
Rated
Voltage
Wire
Ue [V] AWG mm2 Length
Description
Rated
Operational
Current
(AC)
Rated
Operational
Current
(DC)
5 A @ 24V DC
0.5 A @ 110V DC
0.3 A @ 250V DC
(min. 0.03 A DC)
5 A @ 24V DC
0.5 A @ 110V DC
0.3 A @ 250V DC
(min. 0.03 A DC)
5 A @ 125V AC
3 A @ 250V AC
UL Rating
140G-H-EA2R2TA O X O X
O O
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
140G-H-EA3R2A
O X O X
O O
Aux - Form C
O (3)
(2) AL - Form C
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
140G-N-EA1TA
O O O O O O
(1) AL - Form C
(Thermal)
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
0.5 A @ 110V DC
0.3 A @ 250V DC
(min. 0.03 A DC)
140G-N-EA2B
O O O O O O
400V
17
1m
(39 in.)
12 A @ 250V AC
3 A @ 400V AC
0.5 A @ 125V DC
0.3 A @ 250V DC
12 A @ 125V AC
12 A @ 250V AC
140G-N-EA2J
O O O O O O
24V
20
0.5
1m
(39 in.)
Yes
140G-R-EA1TA
O O O O O O
(1) AL - Form C
(Thermal)
250V
6 A @ 250V AC (#)
0.5 A @ 110V DC
0.3 A @ 250V DC
(min. 0.03 A DC)
140G-R-EA4A
O O O O O O
400V
12 A @ 250V AC
3 A @ 400V AC
0.5 A @ 125V DC
0.3 A @ 250V DC
15 A @ 125V AC
15 A @ 250V AC
140G-R-EA4J
O O O O O O
24V
Yes
140G-G-EAB1B
Quantity 2
Each (1) N.C.
Early Break
400 V
17
1m
(39 in.)
12 A @ 250V AC
3 A @ 400V AC
0.5 A @ 125V DC
0.3 A @ 250V DC
12 A @ 125V AC
12 A @ 250V AC
Quantity 2
Each (1) N.O.
Early Make
400 V
17
1m
(39 in.)
12 A @ 250V AC
3 A @ 400V AC
0.5 A @ 125V DC
0.3 A @ 250V DC
12 A @ 125V AC
12 A @ 250V AC
Quantity 2
Each (1) N.O.
Early Make
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
0.5 A @ 110V DC
0.3 A @ 250V DC
(min. 0.03 A DC)
Quantity 2
Each (1) N.O.
Early Make
250V
20
0.5
1m
(39 in.) 6 A @ 250V AC (#)
0.5 A @ 110V DC
0.3 A @ 250V DC
(min. 0.03 A DC)
O O
140G-G-EAM1B
O O
140G-K-EAM1A
140G-M-EAM1A
O
**
**
5 A @ 125V AC
3 A @ 250V AC
For use with 140G-G-RMB, -RMY,-RMX 140G-H-RMB, -RMY, RMX handle mechanisms.
250V AC/DC
Class of use
AC
DC
DC-12
0.5 A
DC-14
0.05 A
6A
AC-15
5A
6A
0.3 A
AC-13
6A
AC-14, DC-14
5A
0.03 A
AC-15
4A
Publication 140G-TD100B-EN-P
57
Bulletin 140G
Accessories
Shunt Trip
Order
Code Catalog Number
Rated Voltage
Ue [V]
140G-G-SNR
12V DC
SJ
140G-G-SNJ
2430V AC/DC
SK
140G-G-SNKY
4860V AC/DC
SD
140G-G-SND
110127V AC
110125V DC
SA
140G-G-SNA
220240V AC
220250V DC
SB
140G-G-SNB
380440V AC
SC
140G-G-SNC
480525V AC
Wire Length
Size
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
1m
1 mm2
17 AWG
Shunt Open
Release
8.4
13.2
50
16.8
33
50
50
33.6
66
60
60
77
139 AC
137 DC
50
50
154
278 AC
274 DC
50
50
266
484
55
336
577
55
8.4
13.2
50
16.8
33
50
50
33.6
66
60
60
77
139 AC
137 DC
50
50
154
278 AC
274 DC
50
50
266
484
55
336
577
55
Opening Time
[ms] *
15
140G Frames K, M
140G-K-SNR
12V DC
SJ
140G-K-SNJ
2430V AC/DC
SK
140G-K-SNKY
4860V AC/DC
SD
140G-K-SND
110127V AC
110125V DC
SA
140G-K-SNA
220240V AC
220250V DC
SB
140G-K-SNB
380440V AC
SC
140G-K-SNC
480525V AC
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
1m
1 mm2
17 AWG
Shunt Open
Release
15
All wired with 600V (UL/CSA) insulated wire. No voltage derating required.
* The time it takes to signal the coil and open the power contacts with no load. Under load conditions add 25 ms.
58
Publication 140G-TD100B-EN-P
Bulletin 140G
Accessories
Shunt Trip
Application Ratings
Order
Code
Catalog Number
Rated Voltage
Ue [V]
Wire Length
Size
1m
0.5 mm2
20 AWG
SJ
140G-N-SNJ
24V AC/DC
SK
140G-N-SNKY
48V AC/DC
SD
140G-N-SND
110120V AC/DC
SA
140G-N-SNA
220240V AC/DC
SB
140G-N-SNB
380400V AC
RJ
140G-NS-SNCJ
24V AC/DC
RK
140G-NS-SNCKY
48V AC/DC
RD
140G-NS-SNCD
110120V AC/DC
RA
140G-NS-SNCA
220240V AC/DC
RB
140G-NS-SNCB
380400V AC
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
Shunt Open
Release
Shunt Close
Release
16.8
26.4
300
33.6
52.8
300
300
77
132
300
300
154
264
300
300
266
440
300
20.4
26.4
300
300
40.8
52.8
300
300
93.5
126.5
300
300
187
196.5
300
300
323
440
300
16.8
26.4
200
33.6
52.8
200
200
77
132
200
200
154
264
200
200
266
440
200
20.4
26.4
200
40.8
52.8
200
200
93.5
126.5
200
200
187
196.5
200
200
323
440
200
Opening Time
[ms]
20
80
140G Frame R
SJ
140G-R-SNJ
24V AC/DC
SK
140G-R-SNKY
48V AC/DC
SD
140G-R-SND
110120V AC/DC
SA
140G-R-SNA
220240V AC/DC
SB
140G-R-SNB
380400V AC/DC
RJ
140G-R-SNCJ
24V AC/DC
RK
140G-R-SNCKY
48V AC/DC
RD
140G-R-SNCD
110120V AC/DC
RA
140G-R-SNCA
220240V AC/DC
RB
140G-R-SNCB
380400V AC/DC
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
Shunt Open
Release
Shunt Close
Release
60
80
All wired with 600V (UL/CSA) insulated wire. No voltage derating required.
Publication 140G-TD100B-EN-P
59
Bulletin 140G
Accessories
Undervoltage Release
Undervoltage Release
Application Ratings
Order
Code
Catalog Number
Rated Voltage
Ue [V]
UJ
140G-G-UVJ
2430V AC/DC
UR
140G-G-UVR
48V AC/DC
140G-G-UVKY
60V AC/DC
UD
140G-G-UVD
110127V AC
110125V DC
UA
140G-G-UVA
220240V AC
220250V DC
UB
140G-G-UVB
380440V AC
UC
140G-G-UVC
480525V AC
Wire Length
Size
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
1m
1 mm2
17 AWG
Electrical Specifications
UVR Power Absorbed During
Normal Operation
Pickup Voltage
Max. [V]
AC [VA]
DC [W]
8.4
21
25.5
1.5
1.5
16.8
33.6
40.8
21
42
51
38.5
88.9 AC
87.5 DC
108 AC
106 DC
77
154 AC
175 DC
208 AC
212.5 DC
2.5
2.5
133
308
374
168
367.5
446
Opening
Time
15
140G Frames K, M
UJ
140G-K-UVJ
2430V AC/DC
UR
140G-K-UVR
48V AC/DC
140G-K-UVKY
60V AC/DC
UD
140G-K-UVD
110127V AC
110125V DC
UA
140G-K-UVA
220240V AC
220250V DC
UB
140G-K-UVB
380440V AC
UC
140G-K-UVC
480525V AC
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
1m
1 mm2
17 AWG
8.4
21
25.5
1.5
1.5
16.8
33.6
40.8
21
42
51
38.5
88.9 AC
87.5 DC
108 AC
106 DC
77
154 AC
175 DC
208 AC
212.5 DC
2.5
2.5
133
308
374
168
367.5
446
All wired with 600V (UL/CSA) insulated wire. No voltage derating required.
60
Publication 140G-TD100B-EN-P
25
Bulletin 140G
Accessories
Undervoltage Release
Application Ratings
Order
Code
Rated Voltage
Ue [V]
Catalog Number
UJ
140G-N-UVJ
24V AC/DC
140G-N-UVKY
60V AC/DC
UD
140G-N-UVD
110120V AC/DC
UA
140G-N-UVA
220240V AC/DC
UB
140G-N-UVB
380400V AC
UC
140G-N-UVC
415440V AC
Wire Length
Size
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
1m
1 mm2
17 AWG
Electrical Specifications
UVR Power Absorbed During
Normal Operation
Pickup Voltage
Max. [V]
AC [VA]
DC [W]
8.4
21
25.5
21
42
51
38.5
88.9 AC
87.5 DC
108 AC
106 DC
77
154 AC
175 DC
208 AC
212.5 DC
133
308
374
168
367.5
446
8.4
21
25.5
21
42
51
38.5
88.9 AC
87.5 DC
108 AC
106 DC
77
154 AC
175 DC
208 AC
212.5 DC
133
308
374
168
367.5
446
Opening
Time
20
140G Frame R
UJ
140G-R-UVJ
24V AC/DC
140G-R-UVKY
60V AC/DC
UD
140G-R-UVD
110120V AC/DC
UA
140G-R-UVA
220240V AC/DC
UB
140G-R-UVB
380400V AC
UC
140G-R-UVC
415440V AC
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
1m
0.5 mm2
20 AWG
30
All wired with 600V (UL/CSA) insulated wire. No voltage derating required.
Publication 140G-TD100B-EN-P
61
Bulletin 140G
Accessories
Motor Operators
Motor Operators
Application Ratings
140G Family
Frame
Catalog Number
Rated Voltage
Ue [V]
140G-G-EOPJ
140G-H-EOPJ
O X O X
X O X O
4860 V DC
O X O X
X O X O
110125 V AC/DC
O X O X
140G-G-EOPA
140G-H-EOPA
X O X O
220250 V AC/DC
O X O X
140G-G-EOPB
140G-H-EOPB
X O X O
380440 V AC
O X O X
140G-G-EOPC
140G-H-EOPC
X O X O
140G-G-EOPD
140G-H-EOPD
24 V DC
140G-G-EOPKY
140G-H-EOPKY
G H
X O X O
480525 V AC
O X O X
Wire
Length
Size
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
1m
1 mm2
17 AWG
Catalog Number
140G-K-EOPJ
24 V DC
140G-M-EOPJ
140G-K-EOPKY
4860 V DC
140G-M-EOPKY
140G-K-EOPD
110125 V AC/DC
140G-M-EOPD
140G-K-EOPA
220250 V AC/DC
140G-M-EOPA
140G-K-EOPB
380 V AC
140G-M-EOPB
Opening
Time [s]
Closing
Time [s]
Inrush
Min. Control
Power
Impulse Time
Resetting (opening and AC DC
Time [s] closing) [ms] [VA] [W]
UVR Power
Absorbed During
Normal Operation
AC
DC
[VA]
[W]
20.4
26.4
0.1
0.1
150
500
350
350
40.8
66
0.1
0.1
150
500
350
106.3
137
0.1
0.1
150
500
500
350
350
212.6
275
0.1
0.1
150
500
500
350
350
374
484
0.1
0.1
150
500
350
Operating
Voltage
Min. Max.
[V]
[V]
Frame
Rated Voltage
Ue [V]
Operating
Voltage
Min. Max.
[V]
[V]
Opening
Time [s]
Closing
Time [s]
Inrush
Min. Control
Power
Impulse Time
Resetting (opening and AC DC
Time [s] closing) [ms] [VA] [W]
UVR Power
Absorbed During
Normal Operation
AC
DC
[VA]
[W]
20.4
26.4
1.5
< 0.1
100
300
150
20.4
26.4
< 0.1
100
300
150
40.8
66
1.5
< 0.1
100
300
150
40.8
66
< 0.1
100
300
150
1m
0.5 mm2
20 AWG
106.3
137
1.5
< 0.1
100
300
300
150
150
106.3
137
< 0.1
100
300
300
150
150
1m
0.5 mm2
20 AWG
212.6
275
1.5
< 0.1
100
300
300
150
150
212.6
275
< 0.1
100
300
300
150
150
374
484
1.5
< 0.1
100
300
150
374
484
< 0.1
100
300
150
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
All wired with 600V (UL/CSA) insulated wire. No voltage derating required.
62
Publication 140G-TD100B-EN-P
Bulletin 140G
Accessories
Motor Operators
Motor Operators
Application Ratings
140G Family
Frame
Catalog Number
Wire
Spring Charging
Rated Voltage
Length
Motor
Ue [V]
N
NS
Size
1m
140G-NS-SCMJ
2430 V AC/DC
O
X
0.5 mm2
20 AWG
1m
140G-NS-SCMKY 4860 V AC/DC
O
X
0.5 mm2
20 AWG
1m
140G-NS-SCMD
100130 V AC/DC
O
X
0.5 mm2
20 AWG
1m
140G-NS-SCMA
220250 V AC/DC
O
X
0.5 mm2
20 AWG
1m
140G-NS-SCMB
380415 V AC
O
X
1 mm2
17 AWG
Frame
Rated Voltage
Ue [V]
140G-R-SCMJ
2430 V AC/DC
140G-R-SCMKY
4860 V AC/DC
140G-R-SCMD
100130 V AC/DC
140G-R-SCMA
220250 V AC/DC
Catalog Number
Wire
Length
Size
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
0.5 mm2
20 AWG
1m
1 mm2
17 AWG
33
8 - 10
400
400
40.8
66
8 - 10
400
400
106.3
143
8 - 10
400
400
212.6
275
8 - 10
400
400
323
456
8 - 10
400
Operating Voltage
Min.
Max.
[V]
[V]
Inrush Power
Inrush Time
[s]
Charging
Time [s]
AC [VA]
DC [W]
20.4
33
0.2
4-5
500
500
40.8
66
0.2
4-5
500
500
106.3
143
0.2
4-5
500
500
212.6
275
0.2
4-5
500
500
All wired with 600V (UL/CSA) insulated wire. No voltage derating required.
Publication 140G-TD100B-EN-P
63
Bulletin 140G
Accessories
Residual Current Release Module
140G-G-ELP* k
140G-H-ELP* l
85690
85690
85690
85690
415690
4566
4566
4566
4566
4566
50-60
50-60
50-60
50-60
50-60
85690
85690
85690
85690
415690
160 A Max.
160 A Max.
250 A Max.
250 A Max.
400 A Max.
140G-J-ELP* l
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
0.1-0.2-0.3-0.5-1-2-3
0.1-0.2-0.3-0.5-1-2-3
0.1-0.2-0.3-0.5-1-2-3
0.1-0.2-0.3-0.5-1-2-3
0.1-0.2-0.3-0.5-1-2-3
<5 W at 690V AC
<5 W at 690V AC
<5 W at 690V AC
<5 W at 690V AC
<10 W at 690V AC
Power Consumption
64
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-G......................................................................................................................................................... 66
Bulletin 140MG-H..........................................................................................................................................................67
Bulletin 140MG-I............................................................................................................................................................69
Bulletin 140MG-J............................................................................................................................................................70
Bulletin 140MG-K...........................................................................................................................................................71
Bulletin 140MG-M.........................................................................................................................................................72
Bulletin 140MG-N..........................................................................................................................................................73
Bulletin 140MG-H8E....................................................................................................................................................74
Bulletin 140MG-J8E.......................................................................................................................................................75
Thermal Magnetic Molded Case Circuit Protectors
Bulletin 140G-G..............................................................................................................................................................76
Bulletin 140G-H..............................................................................................................................................................82
Bulletin 140G-I.................................................................................................................................................................89
Bulletin 140G-J................................................................................................................................................................92
Bulletin 140G-K...............................................................................................................................................................98
Bulletin 140G-M............................................................................................................................................................ 99
Electronic Molded Case Circuit Protectors
Bulletin 140G-H........................................................................................................................................................... 102
Bulletin 140G-J.............................................................................................................................................................104
Bulletin 140G-K............................................................................................................................................................106
Bulletin 140G-M..........................................................................................................................................................108
Bulletin 140G-N, -NS..................................................................................................................................................110
Bulletin 140G-R.............................................................................................................................................................114
Let-Through Energy Curves
I 2t @ 240V.........................................................................................................................................................................116
I 2t @ 415V.........................................................................................................................................................................117
I 2t @ 480V.........................................................................................................................................................................118
I 2t @ 600V.........................................................................................................................................................................119
I 2t @ 690V........................................................................................................................................................................ 120
Peak Let-Through Current Curves
Peak, kA @ 240V...........................................................................................................................................................121
Peak, kA @ 415V........................................................................................................................................................... 122
Peak, kA @ 480V.......................................................................................................................................................... 123
Peak, kA @ 600V...........................................................................................................................................................124
Peak, kA @ 690V.......................................................................................................................................................... 125
Publication 140G-TD100B-EN-P
65
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-G
Maximum Current: 3125 A
A
12
28
45
90
150
210
240
300
375
B
15
34
60
120
200
280
320
400
500
C
17
40
75
150
250
350
400
500
625
D
20
46
90
180
300
420
480
600
750
E
23
53
105
210
350
490
560
700
875
F
25
59
120
240
400
560
640
800
1000
G
28
65
135
270
450
630
720
900
1125
H
30
71
150
300
500
700
800
1000
1250
I
33
77
165
330
550
770
880
1100
1375
B
400
C
500
D
600
E
700
F
800
G
900
H
1000
Note: Motor circuit protectors are for use only in combination controllers.
For DC applications, pick-up settings are approximately 40% higher.
66
Publication 140G-TD100B-EN-P
I
1100
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-H
Maximum Current: 3100 A
A
12
28
45
90
150
210
240
300
B
15
34
60
120
200
280
320
400
C
17
40
75
150
250
350
400
500
D
20
46
90
180
300
420
480
600
E
23
53
105
210
350
490
560
700
F
25
59
120
240
400
560
640
800
G
28
65
135
270
450
630
720
900
H
30
71
150
300
500
700
800
1000
I
33
77
165
330
550
770
880
1100
B
400
C
500
D
600
E
700
F
800
G
900
H
1000
I
1100
Note: Motor circuit protectors are for use only in combination controllers.
For DC applications, pick-up settings are approximately 40% higher.
Publication 140G-TD100B-EN-P
67
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-H
Maximum Current: 125 A
B
703
C
781
D
859
E
938
F
1016
G
1094
H
1172
I
1250
Note: Motor circuit protectors are for use only in combination controllers.
For DC applications, pick-up settings are approximately 40% higher.
68
Publication 140G-TD100B-EN-P
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-I
Maximum Current: 100150 A
A
600
660
750
900
B
675
743
844
1013
C
750
825
938
1125
D
825
908
1031
1238
E
900
990
1125
1350
F
975
1073
1219
1463
G
1050
1155
1313
1575
H
1125
1238
1406
1688
I
1200
1320
1500
1800
B
675
C
750
D
825
E
900
F
975
G
1050
H
1125
I
1200
Note: Motor circuit protectors are for use only in combination controllers.
For DC applications, pick-up settings are approximately 40% higher.
Publication 140G-TD100B-EN-P
69
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-J
Maximum Current: 150250 A
A
750
875
1000
1125
1250
B
844
984
1125
1266
1406
C
938
1094
1250
1406
1563
D
1031
1203
1375
1547
1719
E
1125
1313
1500
1688
1875
F
1219
1422
1625
1828
2031
G
1313
1531
1750
1969
2188
H
1406
1641
1875
2109
2344
I
1500
1750
2000
2250
2500
B
844
C
938
D
1031
E
1125
F
1219
G
1313
H
I
1406 1500
Note: Motor circuit protectors are for use only in combination controllers.
For DC applications, pick-up settings are approximately 40% higher.
70
Publication 140G-TD100B-EN-P
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-K
Maximum Current: 300 A, 400 A
Note: Motor circuit protectors are for use only in combination controllers.
For DC applications, pick-up settings are approximately 40% higher.
Publication 140G-TD100B-EN-P
71
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-M
Maximum Current: 600 A, 800 A
Note: Motor circuit protectors are for use only in combination controllers.
For high fault current levels an additional fixed instantaneous override is
provided at 9.6 kA.
72
Publication 140G-TD100B-EN-P
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-N
Maximum Current: 1200 A
Note: Motor circuit protectors are for use only in combination controllers.
For high fault current levels an additional fixed instantaneous override is
provided at 22 kA.
Publication 140G-TD100B-EN-P
73
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-H8E
Available Current Sensors: 25 A, 60 A, 100 A
74
Publication 140G-TD100B-EN-P
Bulletin 140MG
Time-Current Curves
Motor Circuit Protectors
Bulletin 140MG-J8E
Available Current Sensors: 40 A, 60 A, 100 A, 150 A
Publication 140G-TD100B-EN-P
75
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-G
Maximum Current: 1530 A
76
Rated Current
In [A]
Magnetic Trip
Im [A]
1530
500
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-G
Maximum Current: 32 A
Publication 140G-TD100B-EN-P
77
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-G
Maximum Current: 3550 A
78
Rated Current
In [A]
Magnetic Trip
Im [A]
3550
500
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-G
Maximum Current: 60100 A
Rated Current
In [A]
Magnetic Trip
Im [A]
60
600
63
630
70
700
80
800
90
900
100
1000
Publication 140G-TD100B-EN-P
79
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-G
Maximum Current: 125 A
80
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-G
Maximum Current: 160 A
Publication 140G-TD100B-EN-P
81
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-H
Maximum Current: 1530 A
82
Rated Current
In [A]
Magnetic Trip
Im [A]
1530
400
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-H
Maximum Current: 32 A
Publication 140G-TD100B-EN-P
83
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-H
Maximum Current: 3550 A
84
Rated Current
In [A]
Magnetic Trip
Im [A]
35
400
40
400
50
500
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-H
Maximum Current: 6070 A
Rated Current
In [A]
Magnetic Trip
Im [A]
60
600
63
630
70
700
Publication 140G-TD100B-EN-P
85
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-H
Maximum Current: 80100 A
86
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-H
Maximum Current: 110125 A
Publication 140G-TD100B-EN-P
87
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-H
Maximum Current: 160 A
88
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-I
Maximum Current: 60100 A
Publication 140G-TD100B-EN-P
89
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-I
Maximum Current: 100150 A
90
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-I
Maximum Current: 160225 A
Publication 140G-TD100B-EN-P
91
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-J
Maximum Current: 2550 A
92
Rated Current
In [A]
Magnetic Trip
Im [A]
2540
400
50
500
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-J
Maximum Current: 6070 A
Rated Current
In [A]
Magnetic Trip
Im [A]
60
600
Publication 140G-TD100B-EN-P
63
630
70
700
93
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-J
Maximum Current: 80100 A
t [s]
10000
1 HOUR
1000
10 MIN
100
1 MIN
10
0.1
0.01
0.1
10
100
Current in Multiples of In
94
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-J
Maximum Current: 110150 A
Publication 140G-TD100B-EN-P
95
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-J
Maximum Current: 160225 A
96
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-J
Maximum Current: 250 A
Publication 140G-TD100B-EN-P
97
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-K
Maximum Current: 300 A, 400 A
98
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-M
Maximum Current: 600 A
Publication 140G-TD100B-EN-P
99
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Bulletin 140G-M
Maximum Current: 800 A
100
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Thermal Magnetic Molded Case Circuit Breakers
Publication 140G-TD100B-EN-P
101
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Bulletin 140G-H
Available Sensors (In): 25 A, 60 A, 100 A, 125 A
Electronic Trip Unit. Long Delay Response, Short Delay with I 2t Response, and Instantaneous Curve
Tolerance Values
Protection
Trip Threshold
Trip Time
20%
S
I
Others
10%
15%
20%
20%
60 ms
Notes:
1. Curve accuracy applies from -20 C to +55 C (-4 F to +131 F) ambient temperature. For possible continuous
ampere derating for ambient temperature above 40 C (104 F), consult your local Rockwell Automation sales office
or Allen-Bradley distributor.
2. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
3. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of
the current.
4. For high fault current levels an additional fixed instantaneous hardware override is provided at 2.2 kA.
102
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Bulletin 140G-H
Tolerance Values
I4 [In]
140G-H
In [A]
0.2
0.25
0.45
0.55
0.75
0.8
25
60
100
125
160*
5
12
20
25
32
6.25
15
25
31.3
40
11.3
27
45
56.3
72
13.8
33
55
68.8
88
18.8
45
75
93.8
120
20
48
80
100
128
25
60
100
125
160
Protection
G
Trip Threshold
10%
Trip Time
20%
103
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Bulletin 140G-J
Available Sensors (In): 40 A, 60 A, 100 A, 150 A, 250 A
Electronic Trip Unit. Long Delay Response, Short Delay with I 2t Response, and Instantaneous Curve
Tolerance Values
Protection
Trip Threshold
Trip Time
20%
S
I
Others
10%
15%
20%
20%
60 ms
Notes:
1. Curve accuracy applies from -20 C to +55 C (-4 F to +131 F) ambient temperature. For possible continuous
ampere derating for ambient temperature above 40 C (104 F), consult your local Rockwell Automation sales
office or Allen-Bradley distributor.
2. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
3. Total clearing times shown include the response times of the trip unit, the breaker opening, and the
interruption of the current.
4. For high fault current levels an additional fixed instantaneous hardware override is provided at 3 kA.
104
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Bulletin 140G-J
Example:
In = 100 A
I4 = 100 x (0.2 + 0.25) = 45 A
t4 = 0.2 s @ I > I4
I4 [In]
140G-J
In [A]
0.2
0.25
0.45
0.55
0.75
0.8
40
60
100
150
250
8
12
20
30
50
10
15
25
37.5
62.5
18
27
45
67.5
113
22
33
55
82.5
138
30
45
75
113
188
32
48
80
120
200
40
60
100
150
250
Tolerance Values
Protection
G
Trip Threshold
10%
Trip Time
20%
Publication 140G-TD100B-EN-P
105
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Bulletin 140G-K
Available Sensors (In): 300 A, 400 A
Electronic Trip Unit. Long Delay Response, Short Delay with I 2t Response, and Instantaneous Curve
Example:
In = 300 A
I3 = 300 x (1.5 + 3) = 1350 A
I3 [In]
In [A]
1.5
300
400
450
600
2.5
750 900
1000 1200
4.5
5.5
6.5
7.5
9.5
10.5
Tolerance Values
Protection
Trip Threshold
Trip Time
20%
S
I
Others
10%
1 5%
20%
20%
60 ms
12
1200 1350 1500 1650 1950 2100 2250 2400 2700 2850 3150 3600
1600 1800 2000 2200 2600 2800 3000 3200 3600 3800 4200 4800
Notes:
1. Curve accuracy applies from -20 C to +55 C (-4 F to +131 F) ambient temperature. For possible continuous ampere derating for
ambient temperature above 40 C (104 F), consult your local Rockwell Automation sales office or Allen-Bradley distributor.
2. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
3. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current.
4. For high fault current levels an additional fixed instantaneous hardware override is provided at 5 kA.
106
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Bulletin 140G-K
Example:
In = 100 A
I4 = 100 x (0.2 + 0.25) = 45 A
t4 = 0.2 s
I4 [In]
In [A]
0.2
0.25
0.45
0.55
0.75
0.8
300
400
60
80
75
100
135
180
165
220
225
300
240
320
300
400
Tolerance Values
Protection
G
Trip Threshold
10%
Trip Time
20%
Publication 140G-TD100B-EN-P
107
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Bulletin 140G-M
Available Sensors (In): 600 A, 800 A
Electronic Trip Unit. Long Delay Response, Short Delay with I 2t Response, and Instantaneous Curve
Tolerance Values
Example:
In = 600 A
I3 = 600 x (1.5 + 3) = 2700 A
Protection
Trip Threshold
Trip Time
20%
S
I
Others
10%
15%
20%
20%
60 ms
Notes:
1. Curve accuracy applies from -20 C to +55 C (-4 F to +131 F) ambient temperature. For possible continuous ampere derating for
ambient temperature above 40 C (104 F), consult your local Rockwell Automation sales office or Allen-Bradley distributor.
2. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
3. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current.
4. For high fault current levels an additional fixed instantaneous hardware override is provided at 9.6 kA.
108
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Bulletin 140G-M
Available Sensors (In): 600 A, 800 A
Tolerance Values
Protection
G
Trip Threshold
10%
Trip Time
20%
Example:
In = 600 A
I4 = 600 x (0.2 + 0.25) = 270 A
t4 = 0.2 s
Publication 140G-TD100B-EN-P
109
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
LSI
Protection
Disable
L
(t=k/I2)
Trip Threshold
Trip Time
I1=0.4-0.44-0.48-0.521 x In
10% If 6 x In
S
(t=k)
I2=0.6-0.8-1.2-1.8-2.4-3-3.6-4.2-5-5.86.6-7.4-8.2-9-10 x In
with I > I2
t2=0.1-0.25-0.5-0.8 s
7% If 6 x In
10% If > 6 x In
S
(t=k/I2)
I2=0.6-0.8-1.2-1.8-2.4-3-3.6-4.2-5-5.86.6-7.4-8.2-9-10 x In
I=10 x In
t2=0.1-0.25-0.5-0.8 s
7% If 6 x In
10% If > 6 x In
15% If 6 x In
20% If > 6 x In
I
(t=k)
I3=1.5-2.5-3-4-4.5-5-5.5-6.5-7-7.5-8-9 30 ms
9.5-10.5-12 x In
10%
Notes:
1. The minimum value of this trip is 1 s regardless of curve type (self-protection)
2. These tolerances apply under the following conditions:
- self-powered relay at full power (without start-up)
- presence of auxiliary power supply
- two-phase or three-phase power supply
- preset trip time 100 ms
Trip Threshold
Trip Time
20%
S
I
Others
10%
15%
20%
20%
60 ms
3. Curve accuracy applies from -20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult
Rockwell Automation.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
5. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current.
6. For high fault current levels an additional fixed instantaneous hardware override is provided at 22 kA.
110
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Publication 140G-TD100B-EN-P
111
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
LSIG
Protection
Disable
L
(t=k/I2)
Trip Threshold
Trip Time
I1=0.4-0.425-0.45-0.475-0.5-1 x In
10% If 6 x In
S
(t=k)
I2=0.6-0.8-1.2-1.8-2.4-3-3.6-4.2-5-5.86.6-7.4-8.2-9-10 x In
with I > I2
t2=0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8 s
7% If 6 x In
10% If > 6 x In
S
(t=k/I2)
I2=0.6-0.8-1.2-1.8-2.4-3-3.6-4.2-5-5.86.6-7.4-8.2-9-10 x In
t2=0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8 s
@ 10 In
7% If 6 x In
10% If > 6 x In
15% If 6 x In
20% If > 6 x In
I
(t=k)
30 ms
10%
I3=1.5-2-3-4-5-6-7-8-9-10-11-12-1314-15 x In
Notes:
1. The minimum value of this trip is 1 s regardless of curve type (self-protection)
2. These tolerances apply under the following conditions:
- self-powered relay at full power (without start-up)
- presence of auxiliary power supply
- two-phase or three-phase power supply
- preset trip time 100 ms
Trip Threshold
Trip Time
20%
S
I
Others
10%
15%
20%
20%
60 ms
3. Curve accuracy applies from -20 C to +55 C ambient. For possible continuous ampere derating for ambient above 40 C, consult
Rockwell Automation.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
5. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current.
6. For high fault current levels an additional fixed instantaneous hardware override is provided at 22 kA.
112
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Protection
G
(t=k)
G
(t=k/I2)
Disable
4
Trip Threshold
Trip Time
I4=0.2-0.3-0.4-0.6-0.8-0.9-1 x In
with I > I4
t4=0.1-0.2-0.4-0.8 s
7%
I4=0.2-0.3-0.4-0.6-0.8-0.9-1 x In
t4=0.1 @ 4.47 I4
t4=0.2 @ 3.16 I4
t4=0.4 @ 2.24 I4
t4=0.8 @ 1.58 I4
7%
15%
Trip Threshold
10%
20%
Trip Time
20%
Publication 140G-TD100B-EN-P
113
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Bulletin 140G-R
Available Sensors (In): 2000 A, 2500 A, 3000 A
Electronic Trip Unit. Long Delay Response, Short Delay with I 2t Response, and Instantaneous Curve
Protection
L
(t=k/I2)
Disable
Trip Threshold
Trip Time
I1=0.4-0.425-0.45-0.475-0.5-1 x In
I2=0.6-0.8-1.2-1.8-2.4-3-3.6-4.2-5-5.86.6-7.4-8.2-9-10 x In
with I > I2
t2=0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8 s
S
(t=k)
S
(t=k/I2)
I
(t=k)
I3=1.5-2-3-4-5-6-7-8-9-10-11-12-1314-15 x In
G
(t=k)
G
(t=k/I2)
I2=0.6-0.8-1.2-1.8-2.4-3-3.6-4.2-5-5.86.6-7.4-8.2-9-10 x In
7% If 6 x In
10% If > 6 x In
t2=0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8 s
@ 10 In
7% If 6 x In
10% If > 6 x In
30 ms
10%
I4=0.2-0.3-0.4-0.6-0.8-0.9-1 x In
with I > I4
t4=0.1-0.2-0.4-0.8 s
7%
I4=0.2-0.3-0.4-0.6-0.8-0.9-1 x In
t4=0.1 @ 4.47 I4
t4=0.4 @ 2.24 I4
3. Curve accuracy applies from -20 C to +55 C (-4 F to +131 F) ambient temperature. For possible continuous
ampere derating for ambient temperature above 40 C (104 F), consult your local Rockwell Automation
sales office or Allen-Bradley distributor.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
10% If 6 x In
The best of:
10% or 40 ms
15% If 6 x In
20% If > 6 x In
t4=0.2 @ 3.16 I4
7%
t4=0.8 @ 1.58 I4
Notes:
15%
Trip Time
20%
20%
60 ms
20%
5. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current.
6. For high fault current levels an additional fixed instantaneous hardware override is provided at 40 kA.
114
Publication 140G-TD100B-EN-P
Bulletin 140G
Time-Current Curves
Electronic Molded Case Circuit Breakers
Publication 140G-TD100B-EN-P
115
Bulletin 140G
Bulletin 140G
I 2t Let-Through Energy Curve @ 240V
1,000,000,000
I2t (A2s)
100,000,000
10,000,000
M
K
1,000,000
J
G
100,000
10
100
1000
116
Publication 140G-TD100B-EN-P
Bulletin 140G
Bulletin 140G
I 2t Let-Through Energy Curve @ 415V
1,000,000,000
100,000,000
I2t (A2s)
N
M
10,000,000
K
I
G
1,000,000
J
H
100,000
10,000
1
10
100
1000
Publication 140G-TD100B-EN-P
117
Bulletin 140G
Bulletin 140G
I 2t Let-Through Energy Curve @ 480V
1,000,000,000
100,000,000
I2t (A2s)
N
M
10,000,000
K
G
1,000,000
J
H
100,000
10
100
1000
118
Publication 140G-TD100B-EN-P
Bulletin 140G
Bulletin 140G
I 2t Let-Through Energy Curve @ 600V
1,000,000,000
R
100,000,000
I2t (A2s)
N
M
10,000,000
K
G
1,000,000
J
H
100,000
10
100
1000
Publication 140G-TD100B-EN-P
119
Bulletin 140G
Bulletin 140G
I 2t Let-Through Energy Curve @ 690V
1,000,000,000
R
100,000,000
I2t (A2s)
N
M
10,000,000
1,000,000
J
H
100,000
10,000
1
10
100
120
Publication 140G-TD100B-EN-P
Bulletin 140G
Bulletin 140G
Peak Let-Through Current, kA @ 240V
1000 kA
N
100 kA
Ip [kA]
K
J
G
10 kA
1 kA
10
100
1000
Publication 140G-TD100B-EN-P
121
Bulletin 140G
Bulletin 140G
Peak Let-Through Current, kA @ 415V
1000 kA
R
N
100 kA
Ip [kA]
K
I
J
H
10 kA
1 kA
10
100
1000
122
Publication 140G-TD100B-EN-P
Bulletin 140G
Bulletin 140G
Peak Let-Through Current, kA @ 480V
1000 kA
R
N
100 kA
Ip [kA]
J
H
G
10 kA
1 kA
10
100
1000
Publication 140G-TD100B-EN-P
123
Bulletin 140G
Bulletin 140G
Peak Let-Through Current, kA @ 600V
1000 kA
R
N
100 kA
Ip [kA]
M
J
K
H
10 kA
1 kA
10
100
1000
124
Publication 140G-TD100B-EN-P
Bulletin 140G
Bulletin 140G
Peak Let-Through Current, kA @ 690V
1000 kA
R
100 kA
Ip [kA]
M
K
J
I
10 kA
1 kA
H
G
10
100
Publication 140G-TD100B-EN-P
125
Selection and
Application Tools
Diagrams
Accessories
08
22
24
96
96
96
98
98
21
95
95
95
21
05
Only Lug)
21
95
E
F
12
12
22
22
14
14
AX1
24
32
AX2
34
96
98
98
98
24
96
32
24
24
AX2
34
22
22
14
14
AX1
96
12
12
24
AL1
96
(Copper
22
TU AL
98
Terminals
08
AL1
21
ate
Approxim
-G-TLC14
, 140G
-G-TLC13
140G
06
AX2
uit
ame
A, G-Fr
e Circ
125
d Cas
Molde Dimensions
Cat. Nos.
98
06
24
96
rs
Breake
05
22
24
140G
98
A
22
AX2
Bulletin
AX3
AL1
21
34
34
22
32
32
24
24
96
22
AX2
95
31
96
98
98
18
16
16
21
31
Rotary
Operating
06
08
32
34
34
42
24
AX2
AX3
42
05
44
44
14
AX1
15
22
24
14
32
12
22
le
Hand
AX4
-G-RMB
140G
TU AL
A
11
21
41
Detail
31
g: See
Drillin
21
Cat. No.
12
ed
tion provid
protec
with IP40 ction
al coversable conne
t
Direc
ed termin multi-c
Requir al lugs for
-G-RMY
Termin
or 140G
95
05
31
21
15
95
95
15
11
21
31
AL2
TU AL
15
95
31
21
18
AX3
AL2
AL1
11
95
16
18
98
98
AL1
06
11
G
96
AX3
08
11
21
95
34
16
32
AX2
31
95
21
24
24
12
22
22
14
14
AX1
32
12
64 Term
-MTL
34
TL63,
-G-M
140G
96
inal (Mult
als
termin
Cat. No.
18
11
inal Lug)
le Term
i-Cab
Front
21
11
AL1
11
CAD drawings in a
range of formats
31
41
Min. door
n radius
49
rotatio
d case
on molde
nism
handle ed
ing mecha rotary
operat with direct barriers provid
te
handle
ing phase
Rotarydrilling templa
insulat
Door ed 25 mm
Requir
circuit
breake
69
alogs
m/cat
ab.co
-P
te: www.
1A-EN
websi
-SG00
Visit our
ation 140G
Public
Local Distributor
Visit our website to find your local Distributor.
www.rockwellautomation.com/distributor
Rockwell Automation, Inc. (NYSE:ROK), the worlds largest company dedicated to industrial automation, makes its customers
more productive and the world more sustainable. Throughout the world, our flagship Allen-Bradley and Rockwell Software
product brands are recognized for innovation and excellence.
Allen-Bradley, LISTEN. THINK. SOLVE. and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Copyright 2015 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.