The relay type NV10P can be typically used in HV, MV and LV distribution systems, on transformers or for
electrical machines.
It can be used for system decoupling, load shedding and loss of main (islanding) protection.
NV10P
PROTECTION RELAY
2xVTs
phase-phase
74TCS
BF
ARF
81O
81U
81R
59Uavg
27
27V1
59
59V2
59N
DDI
NV10P
PROTECTION RELAY
59
27
81O
59V2
81U
27V1
DDI
BF
UEC
59Uavg
27
27V1
59
59V2
59N
59Uavg
81O
81U
81R
BF
74TCS
DDI-OPEN
ARF
ARF
59N
Phase undervoltage
Positive sequence undervoltage
Phase overvoltage
Negative sequence overvoltage
Residual overvoltage
Average overvoltage
Overfrequency
Underfrequency
Frequency rate of change
Circuit breaker failure
Trip circuit supervision
Automatisms concerning the VTs positioning
Automatic reclosure
(opzional for pv plants)
Construction
Firmware updating
Output relays
Six output relays are available (two changeover, three make and
one break contacts); each relay may be individually programmed
as normal state (normally energized, de-energized or pulse) and
reset mode (manual or automatic).
A programmable timer is provided for each relay (minimum pulse
width). The user may program the function of each relay in accordance with a matrix (tripping matrix) structure.
Modular design
Communication
Multiple communication interfaces are implemented:
One RS232 local communication front-end interface for communication with ThySetter setup software
Two back-end interfaces for communication with remote monitoring and control systems by:
- RS485 port - ModBus RTU, IEC 60870-5-103 or DNP3 protocol,
- Ethernet port (RJ45 or optical ber) - ModBus/TCP protocol.
Self diagnostics
In order to extend I/O capability, the NV10 hardware can be customized through external auxiliary modules:
MRI - Output relays and LEDs
MID16 - Binary inputs
MCI - 4...20 mA converters
MPT - Pt100 probe inputs.
Metering
NV10 provides metering values for phase, residual voltages
and frequency, making them available for reading on a display
or to communication interfaces. Voltages are sampled 24 times
per period and the RMS value of the fundamental component is
measured using the DFT (Discrete Fourier Transform) algorithm
and digital ltering. The measured voltages can be displayed
with reference to nominal values or directly expressed in volts.
With DFT the RMS value some harmonic are also measured.
Event storage
Binary inputs
Two binary inputs are available with programmable active state
(active-ON/active-OFF) and programmable timer (active to OFF/
ON or ON/OFF transitions).
Several presettable functions can be associated to each input.
Several useful data are stored for diagnostic purpose; the events
are stored into a non volatile memory.
They are graded from the newest to the older after the Events
reading command (ThySetter) is issued:
Sequence of Event Recorder (SER).
The event recorder runs continuously capturing in circular mode
the last three hundred events upon trigger of binary input/output.
Sequence of Fault Recorder (SFR).
The fault recorder runs continuously capturing in circular
mode the last twenty faults upon trigger of binary input/output
and/or element pickup (start-trip).
Trip counters.
L1
L2
L3
A
MT
Note:
VTs can be placed
upstream (preferably)
or downstream of the DDI
NV10P
PROTECTION RELAY
dn
da
B7
Raf(*)
(*) Antiferrorisonance
UE
B8
B1
UL1
B2
B3
B
DDI
59N
Note:
VTs can be placed upstream (preferably)
or downstream of the DDI
B4
B5
UL2
B6
UL3
81O
81U
59V2
27
27V1
59
BF
ARF
59Uavg
Voltage inputs - V connections VTs and residual voltage acquired with open delta VT
L1
L2
L3
L1
L2
L3
restrictive thresholds
enabled from external signal
N
dn
(*) Antiferrorisonance
NV10P
PROTECTION RELAY
da
NV10P
PROTECTION RELAY
B7
R (*)
B8
UE
59N
B1
B2
B3
B4
B5
B6
B1
U12
81O
81U
B2
B3
59V2
U23
27
27V1
B4
B5
59Uavg
59
U31
B6
BF
U12
81O
81U
59V2
27
27V1
59
U23
U31
BF
ARF
59Uavg
ARF
DDI
DDI
Direct measure of LV phase-to-phase voltages
and residual voltage acquired with open delta VT in MV
Measures
Three phase-to-phase voltages U12, U23, U31
Residual voltage UE
Average value of 3-phase voltages on 10 minutes with updates
every three seconds
Frequency f (measured on phase-to-phase voltages)
Positive sequence voltage U1 (measured on phase-to-phase
voltages) U1=(UL1+e+j120UL2+e-j120UL3)/3
where e-j120=-1/2-j3/2, ej120=-1/2+j3/2.
Negative sequence voltage U2 (measured on phase-to-phase
voltages)
U2 =(UL1+e-j120UL2+e+j120UL3)/3
where e-j120=-1/2-j3/2, ej120=-1/2+j3/2.
Binary inputs
The two binary inputs, in addition to traditional assignments, can
be programmed to:
Acquisition of CB state 52a or 52b (for Breaker Failure protection (BF) and ARF automatic reclosure function for photovoltaic plants)
f<-f> voltage enable, indicating activation by external contact function of 59N external device, or, with inverted logic for
future use contact indicating the presence / absence status of
the communication network).
Remote trip (external command)
PROTECTIVE FUNCTIONS
Undervoltage - 27
Three-phases undervoltage function with OR logic, based on the
RMS value of fundamental component of the three phase-tophase voltages, two denite time thresholds.
Overvoltage - 59
Three-phases overvoltage function with OR logic, based on the
RMS value of fundamental component of the three phase-tophase voltages, two denite time thresholds.
1.1
U>avg
0.9
Um
0.7
0.3
0.1
100
100
200
300
400
500
600 s
Note - The description of 59Uavg element applies to the NV10P devices with
sw version 2.70 and following
Under and over frequency function with frequency measurement on the three phase voltages, two denite time thresholds.
Insensitivity to transient frequency less than or equal to 40 ms.
Operation in the 0,2 Un...1,15 Un input voltage and inhibition for
input voltages lower than 0,2 Un.
The second threshold of each protection is always active.
The rst threshold may be disabled by local control (enable / disable threshold by means of keyboard or communications program).
The rst threshold is enabled / disabled, respectively, in the absence / presence of the integrity of the communication network
(digital input set with inverted logic and f<-f> control enable
function or by means of IEC 61850 communication protocol).
For the trip of the rst threshold of each element one or more of
the following consensus can be enabled:
starting of the second residual overvoltage threshold of 59N
internal protection (ON programming of the f<&UE>>,
f>&UE>> parameter)
starting of the residual overvoltage threshold 59N acquired
from external contact with the binary input programmed as
f<-f> Control (ON programming of the f <& DIGIN, f>
& DIGIN parameter)
loss of communication network from external contact acquired by a binary input programmed as f<-f> Control and
inverted logic (ON programming of the f <& DIGIN, f> &
DIGIN parameter)
starting of the positive sequence element (27V1) (ON programming of the f<&27V1, f>&27V1 parameter)
starting of the negative sequence element (59V2) ((ON programming of the f<&59V2, f>&59V2 parameter)
starting of the undervoltage element (27) (ON programming
of the f<&U<, f>&U< parameter)
loss of communication network from Goose IEC 61850
message (ON programming of the f<&rete61850-KO,
f>&rete61850-KO parameter).
Breaker failure - BF
The starting of the circuit breaker failure protection occurs if both
the following conditions are active:
Start and trip of protective elements internal to the relay
(thresholds trip associated with the breaker failure protection)
or, if enabled, by the trip of external protections associated
with a binary input.
The state of the 52a and 52b auxiliary contacts of the circuit
breaker corresponds to the closed state.
VTs positioning
0.5
200
t U<def
U< def
U 12, U 23, U 31
(phase-to-phase voltages
measured directly)
t U<def
T
t U<<def
U<< def
t U<<def
T
0
t Uavg>
U> avg
t Uavg>
T
t U>>def
U>> def
t U>>def
T
t f>def
f >> def
t f>def
T
f f>> def
t f<<def
f<< def
f > def
t f>def
f f> def
&
f< def
t f>def
T
t f<def
&
t f<def
T
CB OPEN COMMAND
t f<<def
T
U 2 > def
f>&
U 2 U 2 def
f >&RES
f >&RES
0
U 1 < U 1 def
t UE>>RES
U E >> def
U E (residual voltage
measured directly)
Consenso f<-f>
Consenso f<-f>
P r esen z a Goo se
Remo t e t r ip
Remo t e t r ip
f>&-K
f>&-L
f<&RES
t UE>>RES
0
U E U E >> def
IN 1tOFF
restrictive thresholds enabled
for loss of communication network IN 1tOFF
0
T
f<&RES
0
f<&-K
TRIPPING M ATRIX
(LED+REL AYS)
U 1 < def
f<&-L
f< &
Goose IEC61850
t UE>>def
T
0
Functional diagram for the NV10P protection interface with inductive VTs
NV10P - Flyer- 07 - 2013
NV10P
PROTECTION RELAY
59
27
P1
UL1
P2
59Uavg
81O
59V2
81U
27V1
UL2
UL3
BF
ARF
DDI
UEC
59N
Voltage inputs - V-sensor connections and residual voltage calculated by means of vector sum
V-Sensor
Bottom view
21
Top view
61
D1
C2
M
10
F1
A4
A5
RX
F2
F3
A6
TX
F4
F5
A7
50
Sbarra
C1
A3
10
M
15
10
A1
A2
A8
Vite M10
80.0
A9
B1
A10
A11
B2
B3
A12
A13
A14
A15
A16
A17
A18
A19
A20
A21
B4
B5
L1
B6
B7
B8
L2
L3
A22
E1
M4 screw
Radius 35 mm
RJ45
Pin1
5m
L10085
Max 50 m
Pin:
1 GND
2 GND
3 GND
4 GND
5 VOUT6 VOUT+
7 +VCC
8 -VSS
Measures
Three phase-to-ground voltages UL1, UL2, UL3
Three phase-to-phase voltage U12, U23, U31 (calculated)
U12 =|UL1-UL2|, U23 =|UL2 -UL3|, U31=|UL3 -UL1|
Residual voltage UEC (calculated)
UEC =|UL1+UL2 +UL3|
Average value of 3-phase voltages on 10 minutes with updates
every three seconds
Frequency f (measured on phase-to-phase voltages)
Positive sequence voltage U1 (measured on phase-to-ground
voltages) U1=(UL1+e+j120UL2+e-j120UL3)/3
where e-j120=-1/2-j3/2, ej120=-1/2+j3/2.
Negative sequence voltage U2 (measured on phase-to-ground
voltages)
U2 =(UL1+e-j120UL2+e+j120UL3)/3
where e-j120=-1/2-j3/2, ej120=-1/2+j3/2.
Binary inputs
The two binary inputs, in addition to traditional assignments, can
be programmed to:
Acquisition of CB state 52a or 52b (for Breaker Failure protection (BF) and ARF automatic reclosure function for photovoltaic plants)
f<-f> voltage enable, indicating activation by external contact function of 59N external device, or, with inverted logic for
future use contact indicating the presence / absence status of
the communication network).
Remote trip (external command)
PROTECTIVE FUNCTIONS
Undervoltage - 27
Three-phases undervoltage function with OR logic, based on the
RMS value of fundamental component of the three phase-tophase voltages, two denite time thresholds.
Overvoltage - 59
Three-phases overvoltage function with OR logic, based on the
RMS value of fundamental component of the three phase-tophase voltages, two denite time thresholds.
1.1
U>avg
Breaker failure - BF
The starting of the circuit breaker failure protection occurs if both
the following conditions are active:
Start and trip of protective elements internal to the relay
(thresholds trip associated with the breaker failure protection)
or, if enabled, by the trip of external protections associated
with a binary input.
The state of the 52a and 52b auxiliary contacts of the circuit
breaker corresponds to the closed state.
VTs positioning
For static generators only (asynchronous and not self excited),
the VTs may be install downstream of the DDI; the protections
are disabled with DDI open (to avoid that the relay prevent closing of the DDI) the f >>, f<< and UE >> operate time are reduced
for an adjustable time after the closing of the DDI.
0.9
Um
0.7
0.5
0.3
0.1
200
100
100
200
300
400
500
600 s
Optional function.
Note - The description of 59Uavg element applies to the NV10P devices with
sw version 2.70 and following
t U<def
U< def
U 12, U 23, U 31
(phase-to-phase
calculated voltages)
t U<def
T
t U<<def
U<< def
t U<<def
T
0
t Uavg>
U> avg
t Uavg>
T
t U>>def
U>> def
t U>>def
T
t f>def
f >> def
t f>def
T
f f>> def
t f<<def
f<< def
t f<<def
f > def
t f>def
f f> def
&
f< def
t f>def
T
t f<def
&
t f<def
T
U 2 > def
f>&
U 2 U 2 def
f >&RES
f >&RES
0
U 1 < U 1 def
t UE>>RES
U E >> def
U EC
(calculated residual voltage)
Consenso f<-f>
Consenso f<-f>
P r esen z a Goo se
Remo t e t r ip
Remo t e t r ip
f<&RES
0
f<&-K
f<&-L
f< &
IN 1tOFF
0
Goose IEC61850
Functional diagram for the NV10P protection interface with electronic sensors
8
f>&-L
IN 1tOFF
restrictive thresholds enabled
for loss of communication network
f>&-K
f<&RES
t UE>>RES
0
U E C U E >> def
TRIPPING M ATRIX
(LED+REL AYS)
U 1 < def
t UE>>def
T
0
CB OPEN COMMAND
INPUT CIRCUITS
Mechanical data
Insulation tests
Reference standards
High voltage test 50Hz
Impulse voltage withstand (1.2/50 s)
Insulation resistance
EN 60255-5
2 kV 60 s
5 kV
>100 M
EN 61000-4-29
EN 60255-22-1
EN 60255-22-2
EN 60255-22-4
EN 60255-22-6
EN 60255-4-3
EN 61000-4-5
EN 61000-4-8
EN 61000-4-12
EN 61000-4-12
EN 61000-4-16
1 kV-2.5 kV
8 kV
4 kV
10 V
10 V/m
2 kV
1 kA/m
2.5 kV
2 kV
10 V
Emission
100 V
50...130 V selectable by sw
1.3 UER
2 UER
0.5 VA
1.0 V
RJ45 socket
Reference standards
EN 61000-6-4 (ex EN 50081-2)
Conducted emission 0.15...30 MHz
Class A
Radiated emission 30...1000 MHz
Class A
Climatic tests
Reference standards
Mechanical tests
Reference standards
Safety requirements
Reference standards
Pollution degree
Reference voltage
Overvoltage
Pulse voltage
Reference standards
Protection degree:
Front side
Rear side, connection terminals
EN 61010-1
3
250 V
III
5 kV
EN 60529
IP52
IP20
Environmental conditions
Ambient temperature
Storage temperature
Relative humidity
Atmospheric pressure
-25...+70 C
-40...+85 C
10...95 %
70...110 kPa
Certifications
Product standard for measuring relays
CE conformity
EMC Directive
Low Voltage Directive
Type tests
EN 50263
89/336/EEC
73/23/EEC
IEC 60255-6
COMMUNICATION INTERFACES
Local PC RS232
19200 bps
Network:
1200...57600 bps
RS485
100 Mbps
Ethernet 100BaseT
Protocol
ModBus RTU/IEC 60870-5-103/DNP3, TCP/IP
20/3 kV
1.8
Binary inputs
Quantity
Type
Max permissible voltage
Max consumption, energized
2
dry inputs
19...265 Vac/19...300 Vdc
3 mA
OUTPUT CIRCUITS
Output relays K1...K6
Quantity
6
changeover (SPDT, type C)
Type of contacts K1, K2
make (SPST-NO, type A)
Type of contacts K3, K4, K5
break (SPST-NC, type B)
Type of contacts K6
Nominal current
8A
Nominal voltage/max switching voltage
250 Vac/400 Vac
Breaking capacity:
50 W
Direct current (L/R = 40 ms)
1250 VA
Alternating current ( = 0,4)
Make
1000 W/VA
Short duration current (0,5 s)
30 A
LEDs
Quantity
ON/fail (green)
Start (yellow)
Trip (red)
Allocatable (red)
8
1
1
1
5
GENERAL SETTINGS
Rated values
Relay nominal frequency (f n)
50, 60 Hz
Relay nominal voltage (Un)
50...130 V or 200...520 V
Relay nominal voltage phase-to-ground (En )[1]
En = Un/3
Relay residual nominal voltage (direct measure) (UEn) 50...130 V
Relay residual nominal voltage (calculated) (UECN)=Un 3 50...130 V
Line VT primary nominal voltage (Unp)
50 V..500 kV
Residual primary nominal voltage (phase-to-phase) 3 (UEnp)
50 V...500 kV
Note [1] Electronic sensor version only
0.000...0.500 s
PROTECTIVE FUNCTIONS
Undervoltage - 27 (inductive VTs)
Common conguration:
27 Operating logic (Logic27)
AND/OR
U< Element
U< Curve type (U<Curve)
DEFINITE
INVERSE [1]
Denite time
27 First threshold denite time (U <def)
U<def Operating time (t U<def )
Inverse time
27 First threshold inverse time (U <inv)
U<inv Operating time (t U<inv)
U<< Element
Denite time
27 Second threshold denite time (U <<def)
U<<def Operating time (t U<<def )
0.05...1.10 U n
0.03...100.0 s
0.05...1.10 U n
0.10...100.0 s
0.05...1.10 U n
0.03...100.0 s
DEFINITE
INVERSE [1]
Denite time
59 First threshold denite time (U >def)
U>def Operating time (t U> def )
Inverse time
59 First threshold inverse time (U >inv)
U>inv Operating time (t U>inv)
0.50...1.50 U n
0.10...100.0 s
U>> Element
Denite time
59 Second threshold denite time (U >>def)
U>>def Operating time (t U>> def )
0.50...1.50 U n
0.03...100.0 s
0.50...1.50 U n
0.03...100.0 s
Denite time
59 First threshold denite time (U >def)
U>def Operating time (t U> def )
Inverse time
59 First threshold inverse time (U >inv)
U>inv Operating time (t U>inv)
0.50...1.50 U n /E n
0.10...100.0 s
0.05...1.10 U n /E n
0.03...100.0 s
U>> Element
Denite time
59 Second threshold denite time (U >>def)
U>>def Operating time (t U>> def )
0.50...1.50 U n /E n
0.03...100.0 s
0.05...1.10 U n /E n
0.10...100.0 s
Common conguration:
Voltage measurement type for 27 (Utype27) [1]
27 Operating logic (Logic27)
U ph-ph /U ph-n
AND/OR
U< Element
U< Curve type (U<Curve)
DEFINITE
INVERSE [2]
U<< Element
Denite time
27 Second threshold denite time (U <<def)
0.05...1.10 U n /E n
U<<def Operating time (t U<<def )
0.03...100.0 s
Note [1] - With U ph-ph setting all threshold are in p.u. U n
With U ph-n setting all threshold are in p.u. E n
Note [2] - The mathematical formula for INVERSE curves is:
t = 0.75 t U<inv / [1-(U/U <inv)] where:
t = trip time (in seconds)
t U< inv = operating time setting (in seconds)
U = input voltage
U<inv = threshold
U> Element
U> Curve type (U>Curve)
U> Element
U> Curve type (U>Curve)
U1< Element
27V1 First threshold denite time (U 1<def)
27V1 Operating time (t U1<def )
AND/OR
Common conguration:
Voltage measurement type for 59 (Utype59) [1]
59 Operating logic (Logic59)
Denite time
27 First threshold denite time (U <def)
U<def Operating time (t U<def )
Inverse time
27 First threshold inverse time (U <inv)
U<inv Operating time (t U<inv)
Common conguration:
59 Operating logic (Logic59)
0.05...1.10 E n
0.07...100.0 s
0.50...1.50 U n /E n
0.03...100.0 s
AND/OR
0.50...1.50 U n
0...1000 s
Note [1] - based on the average value of the three phase-to-phase voltages on
10 minutes with refresh every 3 seconds.
10
U E > Element
U E > Curve type (U E >Curve)
DEFINITE
INVERSE [1]
0.00...100.0 s
U E >> Element
U E>> Reset time delay (t UE>>RES)
59N Second threshold denite time (U E >>def)
U E>>def Operating time (t UE >>def)
U E>>def reduced operating time (t cUE>>def)
t cUE>>def activation time (t atcUE >>def)
0.01...0.70 U En
0.07...100.0 s
0.01...0.50 U En
0.10...100.0 s
0.00...100.0 s
0.01...0.70 U En
0.07...100.0 s
0.07...10.00 s
1...60 s
U E > Element
U E > Curve type (U E >Curve)
DEFINITE
INVERSE [1]
0.00...100.0 s
U E >> Element
U E>> Reset time delay (t UE>>RES)
59N Second threshold denite time (U E >>def)
U E>>def Operating time (t UE >>def)
U E>>def reduced operating time (t cUE>>def)
t cUE>>def activation time (t atcUE >>def)
0.01...0.70 U En
0.07...100.0 s
0.01...0.50 U En
0.10...100.0 s
0.00...100.0 s
0.01...0.70 U En
0.07...100.0 s
0.07...10.00 s
1...60 s
0.01...0.50 Un
0.07...100.0 s
0.01...0.50 En
0.07...100.0 s
Underfrequency - 81U
f< Element
Denite time
81U First threshold denite time (f<def)
0.800...1.000 fn
f<def Operating time (t f<def )
0.05...100.0 s
Voltage control
f< Control enable (f<&)
ON/OFF
f< Controlled by UE>> start (f<&UE>>)
ON/OFF
f< Controlled by binary input (f<&DIGIN)
ON/OFF
f< Controlled by 27V1 start (f<&27V1)
ON/OFF
f< Controlled by 59V2 start (f<&59V2)
ON/OFF
f< Controlled by U< start (f<&U<)
ON/OFF
f< Controlled by 61850 no link (f<&rete61850-KO)
ON/OFF
f<& Reset time delay (f<&RES)
0.00...200.0 s
f<< Element
Denite time
81U Second threshold denite time (f<<def)
f<<def Operating time (t f<<def )
f<<def reduced operating time (t cf<<def)
t cf<<def activation time (t atc<<def)
0.800...1.000 fn
0.05...100.0 s
0.07...10.00 s
1...60 s
f<<< Element
Denite time
81U Third threshold denite time (f<<<def)
f<<<def Operating time (t f<<<def )
0.800...1.000 fn
0.05...100.0 s
f<<<< Element
Denite time
81U Fourth threshold denite time (f<<<<def)
f<<<<def Operating time (t f<<<<def )
0.800...1.000 fn
0.05...100.0 s
Overfrequency - 81O
f> Element
Denite time
81O First threshold denite time (f>def)
1.000....1.200 fn
f>def Operating time (t f> def )
0.05...100.0 s
Voltage control
f> Control enable (f<&)
ON/OFF
f> Controlled by UE>> start (f>&UE>>)
ON/OFF
f> Controlled by binary input (f>&DIGIN)
ON/OFF
f> Controlled by 27V1 start (f>&27V1)
ON/OFF
f> Controlled by 59V2 start (f>&59V2)
ON/OFF
f> Controlled by U< start (f>&U<)
ON/OFF
f> Controlled by 61850 no link (f>&rete61850-KO)
ON/OFF
f>& Reset time delay (f>&RES)
0.00...200.0 s
f>> Element>
Denite time
81O Second threshold denite time (f>>def)
f>>def Operating time (t f>> def )
f>>def reduced operating time (t cf>>def)
t cf>>def activation time (t atcf >>def)
1.000....1.200 fn
0.05...100.0 s
0.07...10.00 s
1...60 s
Denite time
59V2 First threshold denite time (U2 >def)
U2>def Operating time (t U2> def )
df> Element
Module/Positive/Negative
Operating mode (df >mode)
Denite time
81R First threshold denite time (df > def)
0.1...10.0 Hz/s
df > def Operating time (tdf > def)
0.00...100.0 s
df>> Element
Operating mode (df >>mode)
Module/Positive/Negative
Denite time
81R Second threshold denite time (df >> def)
0.1...10.0 Hz/s
df >> def Operating time (tdf >> def)
0.00...100.0 s
df>>> Element
Operating mode (df >>>mode)
Module/Positive/Negative
Denite time
81R Third threshold denite time (df >>> def)
0.1...10.0 Hz/s
df >>> def Operating time (tdf >>> def)
0.00...100.0 s
11
df>>>> Element
Operating mode (df >>>>mode)
Module/Positive/Negative
Denite time
81R Fourth threshold denite time (df >>>> def)
0.1...10.0 Hz/s
df >>>> def Operating time (tdf >>>> def)
0.00...100.0 s
Breaker failure - BF
BF Time delay (t BF)
0.06...10.00 s
0...10000
0.05...1.00 s
f
U L1, U L 2 , U L 3
UE
Calculated:
Phase-to-phase voltages
U 12 , U 23 , U 31
Calculated residual voltage
U EC
Maximum voltage between U L1-U L 2 -U L 3
U Lmax
Average voltage between U L1-U L 2 -U L 3
UL
Average voltage between U 12 , U 23 , U 31
U Lavg
Positive sequence voltage
U1
Negative sequence voltage
U2
Third harmonic residual voltage
U E-3rd
Frequency rate of change
df/dt
Averages:
Voltage averages (refresh 3 s)
U L1avg , U L 2avg , U L 3avg
Maximum voltage between U L1avg , U L 2avg , U L 3avg U Lavgmax
COMTRADE
depending on setting [1]
circular
24 samples per cycle
Trigger setup:
Pre-trigger time
Post-trigger time
Trigger from inputs
Trigger from outputs
Communication
0.05...1.00 s
0.05...60.00 s
IN1, IN2...INx
K1...K6...K10
ThySetter
f
U L1, U L 2 , U L 3
U E, U EC
U1
U2
df /dt
K1...K6...K10
IN1, IN2...INx
Oscillography (DFR)
12
BF (K2)
L1
L2
L3
A
Note:
VTs can be placed
upstream (preferably)
or downstream of the DDI
NV10P
+UAUX
A3
A4
A5
dn
K1
da
B7
Raf(*)
(*) antiferrorisonance
B8
UE
K3
A6
BF - Breaker failure
A7
A8
A9
K4
A10
K5
A11
A12
K6
A13
B1
B2
B3
Note:
VTs can be placed upstream (preferably)
or downstream of the DDI
UL1
B4
B5
UL2
B6
UL3
VOLTAGE INPUTS
OUTPUT RELAYS
K2
A
TRIP - NV10P
Self test
A14
DI
BA+
F1
F2
F3
F4
F5
ETHERNET
D1
THYBUS
-UAUX
E1
A19
A21
A22
IN1
BINARY INPUTS
A20
IN2
BF (K2)
A1
A2
UAUX
RS232
FRONT PANEL
G~
NV10P-schCEI016-MT.ai
V connections VTs or direct measure of LV phase-to-phase voltages and residual voltage acquired with open delta VT in MV
NV10P - Flyer- 07 - 2013
13
Connection diagram example for active users (photovoltaic plant with low voltage interface) with reclosing function
BF (K2)
L1
L2
L3
A
NV10P
+UAUX
K1
A3
A4
A5
K2
A6
A7 BF - Breaker Failure
A8
dn
da
Raf(*)
B8
UE
B1
DI
UL1
B4
B5
UL2
B6
UL3
K6
A14
IN1
+UAUX
Reclose blocking
-UAUX
A21
A22
IN2
ETHERNET
A20
D1
E1
A2
Digital input and output relays connections for automatic reclosing function (ARF)
Phase-phase input voltages with direct connection to the LV side (UR = 400 V versions)
NV10P - Flyer- 07 - 2013
UAUX
RS232
FRONT PANEL
A1
F1
F2
F3
F4
F5
THYBUS
A19
INGRESSI DIGITALI
-UAUX
BF (K2)
BA+
Enable reclosing
command
Close command
K5
-UAUX
-UAUX
14
A11
Enable
reclosing
command
Trip - NV10P
A10 +UAUX
K4
Close command
52b
A9
K3
RS485
+UAUX
B2
B3
RELE FINALI
B7
VOLTAGE INPUTS
Connection diagram example for active users with V-Sensor voltage sensors
L1
L2
L3
NV10P
OUTPUT RELAYS
A3
P1
P2
K1
A4
A5
K2
A6
A7
A8
K3
A9
K4
A10
K5
A11
A12
K6
A13
A14
F1
RS485
F2
F3
BF4
A+
F5
A21
A22
A1
A2
ETHERNET
IN2
FRONT PANEL
UAUX
Voltage inputs - V-sensor connections and residual voltage calculated by means of vector sum
15
E1
IN1
RS232
A20
BINARY INPUTS
A19
D1
THYBUS
DDI
DIMENSIONS
FRONT VIEW
REAR VIEW
120
107
101
D1
D1
A1
A2
4.5
C1
A3
A4
A5
RX
A6
TX
A7
ON
START
START
C3
A4
A5
RX
F3
F4
A6
F5
A7
TX
F2
A9
A10
A11
B2
B3
A10
A11
B4
B6
A12
A13
A14
B7
B8
A15
A16
B5
C5
C6
A15
A16
A17
A17
A18
A18
A19
A20
A19
A20
C7
C8
A21
A21
A22
A22
F4
F5
B2
B3
B4
B5
L1
B6
B7
B8
L2
L3
E1
FLUSH MOUNTING
(inductive VT inputs)
PROJECTING MOUNTING
F2
F3
B1
E1
FLUSH MOUNTING
F1
A8
C4
B1
A12
A13
A14
TRIP
A3
F1
A9
31
TRIP
149
171
80
177
A8
ON
A1
A2
C2
FLUSH MOUNTING
(electronic sensor inputs)
SIDE VIEW
275
212.5
205
30
4.5
170
30
25 15
FLUSH MOUNTING
PROJECTING MOUNTING
(Separate operator panel)
SEPARATE
OPERATOR PANEL
RACK MOUNTING
PROJECTING MOUNTING
(Stand alone)
ON
START
ON
TRIP
START
TRIP
102.5 0.3
70
ON
START
ON
TRIP
START
161
154
177 (4U)
101.6
482.6
465
TRIP