Professional Documents
Culture Documents
Arar LV Cable Sizing Report-07.07.2005
Arar LV Cable Sizing Report-07.07.2005
SHEET i OF i
30421007-3CL00014-P0C
LV CABLE
SIZING REPORT
ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST.MARK'S ROAD
BANGALORE 560001
INDIA
CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O.BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL.00966-1-4633660 : FAX.00966-1-4631150
P0C
07.07.2005
MP
SR
P0B
14.10.2004
MP
SR
P0A
10.09.2004
MP
SR
PREPARED BY
CHECKED BY
275167113.xls
SECTION :cover sheet
CLEARED BY
APPROVED BY
SHEET 1 OF 23
275167113.xls
SECTION :cover sheet
PREPARED BY
CHECKED BY
CLEARED BY
APPROVED BY
SHEET 2 OF 23
CONTENTS
SECTION
DESCRIPTION
1.0
SCOPE
2.0
3.0
GENERAL PARAMETERS
4.0
SIZING CRITERIA
5.0
CONCLUSION
6.0
275167113.xls
SECTION :Index
SHEET 3 OF 23
275167113.xls
SECTION :Index
SHEET 4 OF 23
SCOPE
Scope of this report is to calculate the LV Cable size (600/1000 V Grade) for Arar Power Plant Project
2.0
2.1
2.2
Key One Line Diagram for Arar Plant Drawing No: KA667481 REV P0E
2.3
2.4
3.0
GENERAL PARAMETERS
- Depth of Burried Cables
- Ground Temperature at a depth of 1 meter
- Average Thermal Soil resistivity
- Ambient air Temperature
- Short Circuit current
=
=
=
=
=
1 meter
35 Deg C
2 Deg C -m/w
50 Deg C
65 kA for 1 second
4.0
SIZING CRITERIA
4.1
For all circuit breaker controlled feeders, the Power Cable size shall be selected on the basis of
- Short circuit Rating.
- Current Carrying Capacity.
- Permissible Voltage Drop.
4.2
For all Switch-fuse/MCCB/MCB controlled feeders, the power cable size is selected on the basis of
- Current Carrying Capacity.
- Permissible Voltage Drop.
4.3
I
t
S
K
therefore,
=
=
=
=
0.143 x S
t
Where,
Maximum Allowable conductor Short Circuit Current in Kilo Amps
Duration of Short circuit in seconds
Cross Sectional Area of Current Carrying conductor in Sqmm
Temperature co-efficient of conductor resistance. = 0.143 for copper XLPE
Ix t
0.143
For all circuit breaker controlled feeders,
65 x 1
0.143
454.545
Sqmm
Minimum nearest cable size is 500 Sqmm (Refer SAUDI CABLE COMPANY)
275167113.xls
SECTION :Notes and Sizing Cal
SHEET 5 OF 23
4.4
MCCB/Switchgear-Fuse/MCB controlled outgoing feeders & incoming feeders are sized based on the
full load current and allowable voltage drop.
4.5
4.5.1
Kt
Kp
0.89
0.78
0.7
4.5.2
Ka
Kt x Kp
Ka
0.89 x 0.78
0.6942
Ka
Kt x Kp
Ka
0.89 x 0.70
0.6230
Kt1
1.00
=
=
=
0.86
0.85
0.84
=
=
=
0.92
0.90
0.88
Kt2
Multicore cables.
-up to 16 Sqmm
-from 25 Sqmm to 150 Sqmm
-from 185 Sqmm to 500 Sqmm
Kt2
- Depth of Laying 1m
Single Core
Kp1
0.93
Multicore Cable
Kp1
0.96
Kp2
0.84
275167113.xls
SECTION :Notes and Sizing Cal
SHEET 6 OF 23
Kd
=
=
=
Kd
=
=
=
Kd
=
=
=
Kd
=
=
=
Kd
=
=
=
Multicore cables.
-up to 16 Sqmm
4.3
5.0
=
=
=
=
=
=
Power Factor
Full load Current in A
Length in Km
System Voltage in V
Resistance /Km
Reactance /Km
CONCLUSION
The selected LV cable sizes for each feeder alongwith data regarding feeder designation, load current,
rated current carrying capacity of selected cables under site laying conditions and voltage
drop in each feeder have been calculated and tabulated in ANNEXURE-1 LV CABLE SIZING REPORT
attached.
275167113.xls
SECTION :Notes and Sizing Cal
SHEET 7 OF 23
275167113.xls
SECTION :Notes and Sizing Cal
SHEET 8 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
A.
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
IN AIR
IN DUCT
IN AIR
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
IN DUCT
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
1250
480
1503.52
0.6942
0.5578
3R X 1C X
5R X 1C X
630/Phase +
2R 630/Phase +
3R
X 1C X 630/Neutral X 1C X 630/Neutral
900.00
615.00
624.78
343.05
15
0.0453
0.0938
0.151
547.5
480
0.8
0.85
968.44
0.6942
0.5578
2R X 1C X
630/Phase +
1R X 1C X
630/Neutral
4R X 1C X
630/Phase +
2R
X 1C X 630/Neutral
900.00
615.00
624.78
343.05
75
0.0453
0.0938
0.606
547.5
480
0.8
0.85
968.44
0.6942
0.5578
2R X 1C X
630/Phase +
1R X 1C X
630/Neutral
4R X 1C X
630/Phase +
2R
X 1C X 630/Neutral
900.00
615.00
624.78
343.05
75
0.0453
0.0938
0.606
B.
1250
480
1503.52
0.6942
0.5578
3R X 1C X
5R X 1C X
630/Phase +
2R 630/Phase +
3R
X 1C X 630/Neutral X 1C X 630/Neutral
900.00
615.00
624.78
343.05
15
0.0453
0.0938
0.151
567.5
480
0.8
0.85
1003.82
0.6942
0.5578
2R X 1C X
4R X 1C X
630/Phase +
1R 630/Phase +
2R
X 1C X 630/Neutral X 1C X 630/Neutral
900.00
615.00
624.78
343.05
75
0.0453
0.0938
0.628
567.5
480
0.8
0.85
1003.82
0.6942
0.5578
2R X 1C X
4R X 1C X
630/Phase +
1R 630/Phase +
2R
X 1C X 630/Neutral X 1C X 630/Neutral
900.00
615.00
624.78
343.05
75
0.0453
0.0938
0.628
C.
1250
480
1503.52
0.6942
0.5578
3R X 1C X 630/ph
2R X 1C X 630/N
5R X 1C X 630/ph
3R X 1C X 630/N
900
615
624.78
343.05
100
0.0453
0.0938
1.004
480 V STATION
SWITCHGEAR BUS-1
480 V STATION
SWITCHGEAR BUS-1
480
1000.00
0.6942
0.5578
2R X 1C X 630/ph
1R X 1C X 630/N
3R X 1C X 630/ph
2R X 1C X 630/N
900
615
624.78
343.05
18
0.0453
0.0938
0.200
480 V STATION
SWITCHGEAR BUS-1
480
800.00
0.6942
0.5578
2R X 1C X 500/ph
1R X 1C X 500/N
3R X 1C X 500/ph
2R X 1C X 500/N
779
550
540.78
306.79
110
0.0543
0.0948
1.062
480
0.8
0.85
1000.00
0.6942
0.5578
2R X 1C X 630/ph
1R X 1C X 630/N
3R X 1C X 630/ph
2R X 1C X 630/N
900
615
624.78
343.05
18
0.0543
0.0948
0.217
480
1503.52
0.6942
0.5578
3R X 1C X 630/ph
2R X 1C X 630/N
5R X 1C X 630/ph
3R X 1C X 630/N
900
615
624.78
343.05
145
0.0453
0.0938
1.456
480 V STATION
SWITCHGEAR BUS-2
480 V STATION
SWITCHGEAR BUS-2
480 V STATION
SWITCHGEAR BUS-2
480
0.8
0.85
400.00
0.6330
0.7434
2R x 4C X 185
3R x 4C X 185
496
372
313.97
276.54
490
0.0998
0.0983
4.909
480 V STATION
SWITCHGEAR BUS-2
480
0.8
0.85
800.00
0.6942
0.5578
2R X 1C X 500/ph
1R X 1C X 500/N
3R X 1C X 500/ph
2R X 1C X 500/N
779
550
540.78
306.79
145
0.0543
0.0948
1.400
480 V STATION
SWITCHGEAR BUS-2
480
0.8
0.85
125.00
0.6230
0.7603
4C X 70
4C X 70
220
183
137.06
139.13
150
0.3430
0.0988
2.258
D.
1250
275167113.xls
SECTION :Sizing schedule
SHEET 9 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
480V AC SUBDISTRIBUTION
BOARD BUS-1
277
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
25
3.9300
0.1109
1.159
480V AC SUBDISTRIBUTION
BOARD BUS-1
277
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
25
3.9300
0.1109
1.159
480V AC SUBDISTRIBUTION
BOARD BUS-1
277
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
30
3.9300
0.1109
1.391
480V AC SUBDISTRIBUTION
BOARD BUS-1
480
20.00
0.6230
0.7603
4C X 25
4C X 25
118.0
104
73.51
79.07
20
0.9270
0.1131
0.117
480V AC SUBDISTRIBUTION
BOARD BUS-1
GENERATOR TRANSFORMER
-T607 COOLING FAN MOTOR
POWER SUPPLY
480
32.00
0.6230
0.7772
4C X 16
4C X 16
88
80
54.82
62.18
75
1.4700
0.1068
1.074
480V AC SUBDISTRIBUTION
BOARD BUS-1
480
32.00
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
50
2.3300
0.1111
1.115
480V AC SUBDISTRIBUTION
BOARD BUS-1
480
32.00
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
60
2.3300
0.1111
1.338
480V AC SUBDISTRIBUTION
BOARD BUS-1
480
100.00
0.6230
0.7603
4C X 50
4C X 50
175
149
109.03
113.28
150
0.4940
0.1003
2.465
480V AC SUBDISTRIBUTION
BOARD BUS-1
50
480
0.8
75.18
0.6230
0.7772
4C X 150
4C X 150
363
283
226.15
219.95
75
0.1600
0.0957
0.377
10
480V AC SUBDISTRIBUTION
BOARD BUS-1
28.2
480
0.8
42.40
0.6230
0.7603
3C X 95
3C X 95
272
250
169.46
190.08
25
0.2480
0.0894
0.096
10
480V AC SUBDISTRIBUTION
BOARD BUS-1
120
480
144.34
0.6230
0.7603
4C X 120
4C X 120
316
281
196.87
213.64
10
0.1970
0.0989
0.113
28.2
480
0.8
42.40
0.6230
0.7603
3C X 95
3C X 95
272
250
169.46
190.08
30
0.2480
0.0894
0.116
480
0.8
32.00
0.6230
0.7772
4C X 16
4C X 16
88
80
54.82
62.18
125
1.4700
0.1068
1.790
480
144.34
0.6230
0.7603
4C X 120
4C X 120
316
251
196.87
190.84
10
0.1970
0.0989
0.113
%
STARTING
VOLTAGE
DROP
480V AC SUBDISTRIBUTION
BOARD BUS-2
480V AC SUBDISTRIBUTION
BOARD BUS-2
GENERATOR TRANSFORMER
-T608 COOLING FAN MOTOR
POWER SUPPLY
480V AC SUBDISTRIBUTION
BOARD BUS-2
480V AC SUBDISTRIBUTION
BOARD BUS-2
480
20.00
0.6230
0.7603
4C X 25
4C X 25
118
104
73.51
79.07
20
0.9270
0.1131
0.039
480V AC SUBDISTRIBUTION
BOARD BUS-2
480
32.00
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
60
2.3300
0.1111
1.338
480V AC SUBDISTRIBUTION
BOARD BUS-2
480
32.00
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
60
2.3300
0.1111
1.338
480V AC SUBDISTRIBUTION
BOARD BUS-2
480
100.00
0.6230
0.7603
4C X 50
4C X 50
175
149
109.03
113.28
150
0.4940
0.1003
2.465
480V AC SUBDISTRIBUTION
BOARD BUS-2
277
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
30
5.8800
0.1173
2.068
275167113.xls
SECTION :Sizing schedule
120
SHEET 10 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
480V AC SUBDISTRIBUTION
BOARD BUS-2
277
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
35
5.8800
0.1173
2.413
10
480V AC SUBDISTRIBUTION
BOARD BUS-2
277
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
40
5.8800
0.1173
2.758
11
480V AC SUBDISTRIBUTION
BOARD BUS-2
50
480
0.8
75.18
0.6230
0.7772
4C X 150
4C X 150
363
283
226.15
219.95
75
0.1600
0.0957
0.377
E.
GT MCC -GTG#7
1.1
480
0.8
0.65
2.54
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
75
5.8800
0.1173
0.329
1.973
GT MCC -GTG#7
7.5
480
0.8
0.85
13.27
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
75
5.8800
0.1173
1.714
10.285
GT MCC -GTG#7
45
480
0.8
0.93
72.75
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
45
0.6690
0.0973
0.701
4.207
GT MCC -GTG#7
45
480
0.8
0.93
72.75
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
45
0.6690
0.0973
0.701
4.207
GT MCC -GTG#7
45
480
0.8
0.93
72.75
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
50
0.6690
0.1173
0.795
4.769
GT MCC -GTG#7
1.1
480
0.8
0.65
2.54
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
50
5.8800
0.1173
0.219
1.315
GT MCC -GTG#7
1.5
480
0.8
0.65
3.47
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
100
5.8800
0.1044
0.597
3.581
GT MCC -GTG#7
15
480
0.8
0.85
26.53
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
70
1.4200
0.1000
0.802
4.809
GT MCC -GTG#7
30
480
0.8
0.85
53.07
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
50
1.4200
0.1000
1.145
6.870
10 GT MCC -GTG#7
0.3
480
0.8
0.65
0.69
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
60
1.4200
0.1000
0.018
0.108
11
22
480
0.8
0.93
35.57
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
75
1.4200
0.1000
1.151
6.907
12 GT MCC -GTG#7
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
75
1.4200
0.1000
1.570
9.419
13 GT MCC -GTG#7
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
80
1.4200
0.1000
1.675
10.047
14 GT MCC -GTG#7
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
80
1.4200
0.1000
1.675
10.047
15 GT MCC -GTG#7
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
85
1.4200
0.1000
1.779
10.675
16 GT MCC -GTG#7
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
85
1.4200
0.1000
1.779
10.675
17 GT MCC -GTG#7
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
90
1.4200
0.1000
1.884
11.303
18 GT MCC -GTG#7
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
90
1.4200
0.1000
1.884
11.303
19 GT MCC -GTG#7
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
90
1.4200
0.1000
1.884
11.303
20 GT MCC -GTG#7
150
480
0.8
0.93
242.50
0.6230
0.7434
3C X 240
3C X 240
496
372
309.01
276.54
75
0.0998
0.0874
0.868
5.209
21 GT MCC -GTG#7
150
480
0.8
0.93
242.50
0.6230
0.7434
3C X 240
3C X 240
496
372
309.01
276.54
75
0.0998
0.0874
0.868
5.209
22 GT MCC -GTG#7
TURBINE COMPARTMENT
COOLING AIR FAN#1 MOTOR
11
480
0.8
0.85
19.46
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
55
3.9300
0.1109
1.240
7.439
23 GT MCC -GTG#7
TURBINE COMPARTMENT
COOLING AIR FAN#2 MOTOR
11
480
0.8
0.85
19.46
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
55
3.9300
0.1109
1.240
7.439
24 GT MCC -GTG#7
3.7
480
0.8
0.85
6.54
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
60
5.8800
0.1173
0.677
4.059
GT MCC -GTG#7
275167113.xls
SECTION :Sizing schedule
SHEET 11 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
25 GT MCC -GTG#7
3.7
480
0.8
0.85
6.54
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
60
5.8800
0.1173
0.677
4.059
26 GT MCC -GTG#7
ACCESSORY COMPARTMENT
SPACE HEATER
20
480
1.0
0.85
28.30
0.6230
0.7727
3C X 16
3C X 16
88
80
54.82
61.82
75
1.4700
0.1000
0.947
27 GT MCC -GTG#7
ACCESSORY COMPARTMENT
SPACE HEATER
20
480
1.0
0.85
28.30
0.6230
0.7727
3C X 16
3C X 16
88
80
54.82
61.82
75
1.4700
0.1000
0.947
28 GT MCC -GTG#7
6.75
480
1.0
0.85
9.55
0.6230
0.7727
3C X 4
3C X 4
38
37
23.67
28.59
80
5.8800
0.1173
1.316
29 GT MCC -GTG#7
0.5
480
1.0
0.85
0.71
0.6230
0.7727
3C X 4
3C X 4
38
37
23.67
28.59
100
5.8800
0.1173
0.122
30 GT MCC -GTG#7
1.1
480
0.8
0.85
1.95
0.6230
0.7727
3C X 4
3C X 4
38
37
23.67
28.59
100
5.8800
0.1173
0.335
2.011
31 GT MCC -GTG#7
BATTERY CHARGER #1
40
480
0.8
60.14
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
15
0.6690
0.0923
0.192
32 GT MCC -GTG#7
BATTERY CHARGER #2
40
480
0.8
60.14
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
15
0.6690
0.0923
0.192
33 GT MCC -GTG#7
277
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
15
5.8800
0.1173
0.896
34 GT MCC -GTG#7
1.1
480
0.8
0.85
1.95
0.6230
0.7603
3C X 4
3C X 4
38
37
23.67
28.13
100
5.8800
0.1173
0.335
2.011
F.
GT MCC -GTG#8
1.1
480
0.8
0.65
2.54
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
75
5.8800
0.1173
0.329
1.973
GT MCC -GTG#8
7.5
480
0.8
0.85
13.27
0.6230
0.7772
3C X 4
3C X 4
142
125
88.47
97.15
75
5.8800
0.1173
1.714
10.285
GT MCC -GTG#8
45
480
0.8
0.93
72.75
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
55
0.6690
0.0923
0.853
5.116
GT MCC -GTG#8
45
480
0.8
0.93
72.75
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
55
0.6690
0.0923
0.853
5.116
GT MCC -GTG#8
45
480
0.8
0.93
72.75
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
50
0.6690
0.0923
0.775
4.651
GT MCC -GTG#8
1.1
480
0.8
0.65
2.54
0.6230
0.7603
3C X 4
3C X 4
38
37
23.67
28.13
50
5.8800
0.1173
0.219
1.315
GT MCC -GTG#8
1.5
480
0.8
0.65
3.47
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
100
5.8800
0.1173
0.598
3.587
GT MCC -GTG#8
15
480
0.8
0.85
26.53
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
70
1.4700
0.1000
0.828
4.970
GT MCC -GTG#8
30
480
1.0
0.85
42.45
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
50
1.4700
0.1000
0.947
5.680
10 GT MCC -GTG#8
0.3
480
0.8
0.65
0.69
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
60
5.8800
0.1173
0.072
0.430
11
22
480
0.8
0.93
35.57
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
70
1.4700
0.1000
1.110
6.662
12 GT MCC -GTG#8
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
75
1.4700
0.1000
1.622
9.734
13 GT MCC -GTG#8
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
75
1.4700
0.1000
1.622
9.734
14 GT MCC -GTG#8
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
80
1.4700
0.1000
1.731
10.383
15 GT MCC -GTG#8
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
80
1.4700
0.1000
1.731
10.383
16 GT MCC -GTG#8
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
85
1.4700
0.1000
1.839
11.032
GT MCC -GTG#8
275167113.xls
SECTION :Sizing schedule
SHEET 12 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
17 GT MCC -GTG#8
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
85
1.4700
0.1000
1.839
11.032
18 GT MCC -GTG#8
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
90
1.4700
0.1000
1.947
11.681
19 GT MCC -GTG#8
30
480
0.8
0.93
48.50
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
90
1.4700
0.1000
1.947
11.681
20 GT MCC -GTG#8
150
480
0.8
0.93
242.50
0.6230
0.7434
3C X 240
3C X 240
496
372
309.01
276.54
75
0.0998
0.0874
0.868
5.209
21 GT MCC -GTG#8
150
480
0.8
0.85
265.33
0.6230
0.7434
3C X 240
3C X 240
496
372
309.01
276.54
75
0.0998
0.0874
0.950
5.699
22 GT MCC -GTG#8
TURBINE COMPARTMENT
COOLING AIR FAN#1 MOTOR
11
480
0.8
0.85
19.46
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
55
3.9300
0.1109
1.240
7.439
23 GT MCC -GTG#8
TURBINE COMPARTMENT
COOLING AIR FAN#2 MOTOR
11
480
0.8
0.85
19.46
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
55
3.9300
0.1109
1.240
7.439
24 GT MCC -GTG#8
3.7
480
0.8
0.85
6.54
0.6230
0.7772
3C X 6
3C X 6
38
37
23.67
28.76
50
3.9300
0.1109
0.379
2.275
25 GT MCC -GTG#8
3.7
480
0.8
0.85
6.54
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
50
5.8500
0.1173
0.561
3.366
26 GT MCC -GTG#8
6.75
480
1.0
0.85
9.55
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
80
5.8500
0.1173
1.310
27 GT MCC -GTG#8
0.5
480
1.0
0.85
0.71
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
100
5.8500
0.1173
0.121
28 GT MCC -GTG#8
BATTERY CHARGER #1
40
480
0.8
60.14
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
15
0.6690
0.0973
0.193
29 GT MCC -GTG#8
BATTERY CHARGER #2
40
480
0.8
60.14
0.6230
0.7603
3C X 35
3C X 35
142
125
88.47
95.04
15
0.6690
0.0973
0.193
G.
COMPRESSOR DB
AIR COMPRESSOR #1
22
480
0.8
0.93
35.57
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
140
0.4940
0.0934
0.811
4.865
COMPRESSOR DB
AIR COMPRESSOR #2
22
480
0.8
0.93
35.57
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
142
0.4940
0.0934
0.822
4.934
34 COMPRESSOR DB
AIR COMPRESSOR #3
22
480
0.8
0.93
35.57
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
146
0.4940
0.0934
0.846
5.073
1.75
480
0.8
0.93
2.83
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
150
5.8800
0.1173
0.731
4.387
COMPRESSOR DB
AIR DRYER
H.
POWERHOUSE ACDB#7
277
20.00
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
100
2.3300
0.1136
2.790
POWERHOUSE ACDB#7
277
20.00
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
100
2.3300
0.1136
2.790
POWERHOUSE ACDB#7
480
100.00
0.6230
0.7603
4C X 50
4C X 50
175
149
109.03
113.28
160
0.4940
0.1003
2.629
POWERHOUSE ACDB#7
480
100.00
0.6230
0.7603
4C X 50
4C X 50
175
149
109.03
113.28
160
0.4940
0.1003
2.629
POWERHOUSE ACDB#7
277
32.00
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
15
2.3300
0.1111
0.669
POWERHOUSE ACDB#7
277
32.00
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
15
2.3300
0.1111
0.669
POWERHOUSE ACDB#7
1.1
480
0.8
0.93
1.78
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
200
3.9300
0.1109
0.412
2.472
POWERHOUSE ACDB#7
1.1
480
0.8
0.93
1.78
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
220
3.9300
0.1109
0.453
2.720
POWERHOUSE ACDB#7
1.1
480
0.8
0.93
1.78
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
150
3.9300
0.1109
0.309
1.854
275167113.xls
SECTION :Sizing schedule
SHEET 13 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
10 POWERHOUSE ACDB#7
COMPRESSOR DISTRIBUTION
BOARD
11
POWERHOUSE ACDB#7
12 POWERHOUSE ACDB#7
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
45.75
480
0.8
68.79
0.6230
0.7603
3C X 95
3C X 95
272
220
169.46
167.27
20
0.2480
0.0894
0.125
74
480
0.8
111.26
0.6230
0.7603
4C X 150
4C X 150
363
283
226.15
215.16
20
0.1600
0.0957
0.149
480
32.00
0.6230
0.7772
3C X 16
3C X 16
88
80
54.82
62.18
175
1.4300
0.1000
2.809
CEMS SUPPLY
I.
POWERHOUSE ACDB#8
45
480
0.8
0.93
72.75
0.6230
0.7603
4C X 95
4C X 95
272
250
169.46
190.08
150
0.2480
0.0963
1.009
6.053
POWERHOUSE ACDB#8
55
480
0.8
0.93
88.92
0.6230
0.7603
4C X 95
4C X 95
272
250
169.46
190.08
100
0.2480
0.0963
0.822
4.932
POWERHOUSE ACDB#8
480
200.00
0.6230
0.7434
3C X 185
3C X 185
418
321
260.41
238.63
220
0.1290
0.0889
2.485
POWERHOUSE ACDB#8
480
100.00
0.6230
0.7603
4C X 50
4C X 50
175
149
109.03
113.28
100
0.4940
0.1003
1.643
POWERHOUSE ACDB#8
480
32.00
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
15
2.3300
0.1044
0.334
POWERHOUSE ACDB#8
480
32.00
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
15
2.3300
0.1044
0.334
POWERHOUSE ACDB#8
1.1.
480
0.8
0.93
1.78
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
200
3.9300
0.1109
0.412
2.475
POWERHOUSE ACDB#8
1.1
480
0.8
0.93
1.78
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
200
3.9300
0.1109
0.412
2.472
POWERHOUSE ACDB#8
74
480
0.8
111.26
0.6230
0.7603
4C X 150
4C X 150
363
283
226.15
215.16
20
0.1600
0.0921
0.147
J.
32
480
0.8
0.93
51.73
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
50
0.4940
0.0934
0.421
2.527
32
480
0.8
0.93
51.73
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
55
0.4940
0.0934
0.463
2.780
32
480
0.8
0.93
51.73
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
145
0.4940
0.0934
1.221
7.329
32
480
0.8
0.93
51.73
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
145
0.4940
0.0934
1.221
7.329
480
0.8
0.93
1.62
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
50
3.9300
0.1109
0.094
0.562
480
0.8
0.93
1.62
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
55
3.9300
0.1109
0.103
0.618
480
0.8
0.93
1.62
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
155
3.9300
0.1109
0.290
1.742
480
0.8
0.93
1.62
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
155
3.9300
0.1109
0.290
1.742
480
0.8
0.93
3.23
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
150
3.9300
0.1109
0.562
3.371
10
480
0.8
0.93
3.23
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
155
3.9300
0.1109
0.581
3.484
11
480
0.8
0.93
3.23
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
160
3.9300
0.1109
0.599
3.596
12
480
0.8
0.93
3.23
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
165
3.9300
0.1109
0.618
3.708
275167113.xls
SECTION :Sizing schedule
SHEET 14 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
32
480
0.8
0.93
51.73
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
50
0.4940
0.0934
0.421
2.527
32
480
0.8
0.93
51.73
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
55
0.4940
0.0934
0.463
2.780
32
480
0.8
0.93
51.73
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
145
0.4940
0.0934
1.221
7.329
32
480
0.8
0.93
51.73
0.6230
0.7603
3C X 50
3C X 50
175
149
109.03
113.28
145
0.4940
0.0934
1.221
7.329
480
0.8
0.93
1.62
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
50
3.9300
0.1109
0.094
0.562
480
0.8
0.93
1.62
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
55
3.9300
0.1109
0.103
0.618
480
0.8
0.93
1.62
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
155
3.9300
0.1109
0.290
1.742
480
0.8
0.93
1.62
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
155
3.9300
0.1109
0.290
1.742
480
0.8
0.93
3.23
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
150
3.9300
0.1109
0.562
3.371
10
480
0.8
0.93
3.23
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
155
3.9300
0.1109
0.581
3.484
11
480
0.8
0.93
3.23
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
160
3.9300
0.1109
0.599
3.596
12
480
0.8
0.93
3.23
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
165
3.9300
0.1109
0.618
3.708
277
20.00
0.6230
0.7772
3CX 6
3CX 6
48
46
29.90
35.75
15
3.9300
0.1109
0.695
277
20.00
0.6230
0.7772
3CX 6
3CX 6
48
46
29.90
35.75
15
3.9300
0.1109
0.695
277
20.00
0.6230
0.7772
3CX 6
3CX 6
48
46
29.90
35.75
20
3.9300
0.1109
0.927
480
100.00
0.6230
0.7603
4C X 50
4C X 50
175
149
109.03
113.28
60
0.4940
0.1003
0.986
480
100.00
0.6230
0.7603
4C X 50
4C X 50
175
149
109.03
113.28
140
0.4940
0.1003
2.300
480
100.00
0.6230
0.7603
4C X 50
4C X 50
175
149
109.03
113.28
175
0.4940
0.1003
2.876
15
480
0.8
0.93
24.25
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
85
2.3300
0.1044
1.433
8.598
15
480
0.8
0.93
24.25
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
90
2.3300
0.1044
1.517
9.104
1.5
480
0.8
0.93
2.43
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
100
3.9300
0.1109
0.281
1.686
1.5
480
0.8
0.93
2.43
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
230
3.9300
0.1109
0.646
3.877
11
480
20.00
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
150
2.3300
0.1136
2.092
480
20.00
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
200
2.3300
0.1136
2.789
480
20.00
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
120
2.3300
0.1136
1.673
480
20.00
0.6230
0.7772
3C X 10
3C X 10
67
62
41.74
48.19
200
2.3300
0.1136
2.789
275167113.xls
SECTION :Sizing schedule
SHEET 15 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
UPS DB
0.672
120
0.8
7.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
125
3.9300
0.1109
UPS DB
0.096
120
0.8
1.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
125
3.9300
0.1109
UPS DB
0.096
120
0.8
1.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
125
3.9300
0.1109
UPS DB
0.672
120
0.8
7.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
190
3.9300
0.1109
UPS DB
0.096
120
0.8
1.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
190
3.9300
0.1109
UPS DB
0.096
120
0.8
1.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
190
3.9300
0.1109
UPS DB
0.672
120
0.8
7.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
285
3.9300
0.1109
UPS DB
0.096
120
0.8
1.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
285
3.9300
0.1109
UPS DB
0.672
120
0.8
7.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
290
3.9300
0.1109
10 UPS DB
0.096
120
0.8
1.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
290
3.9300
0.1109
11
0.225
120
0.8
2.34
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
285
3.9300
0.1109
12 UPS DB
0.225
120
0.8
2.34
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
295
3.9300
0.1109
13 UPS DB
SOER PANEL
0.5
120
0.8
5.21
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
295
3.9300
0.1109
14 UPS DB
MASTERCLOCK
0.1
120
0.8
1.04
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
285
3.9300
0.1109
15 UPS DB
0.5
120
0.8
5.21
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
285
3.9300
0.1109
UPS DB
N.
AC PANEL-INTERNAL TO
PEECC GTG#7
230
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
75
3.9300
0.1109
4.188
AC PANEL-INTERNAL TO
PEECC GTG#7
TURBINE/COMPRESSOR WASH
WATER INJ.SOL.VALVE 20TW 1-3
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
40
5.8800
0.1173
3.321
AC PANEL-INTERNAL TO
PEECC GTG#7
CRANKING MOTOR
HEATER(23CR-1)
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
30
5.8800
0.1173
2.491
AC PANEL-INTERNAL TO
PEECC GTG#7
COMPARTMENT LIGHTING(DF)
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
20
5.8800
0.1173
1.661
AC PANEL-INTERNAL TO
PEECC GTG#7
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
40
5.8800
0.1173
3.321
AC PANEL-INTERNAL TO
PEECC GTG#7
230
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
60
3.9300
0.1109
3.350
AC PANEL-INTERNAL TO
PEECC GTG#7
INLET COMPARTMENT
(LIGHTS,RECEPTCLES,34TF1,88MH)
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
20
5.8800
0.1173
1.661
AC PANEL-INTERNAL TO
PEECC GTG#7
230
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
50
3.9300
0.1109
2.792
AC PANEL-INTERNAL TO
PEECC GTG#7
230
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
50
3.9300
0.1109
2.792
AC PANEL-INTERNAL TO
PEECC GTG#8
275167113.xls
SECTION :Sizing schedule
230
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
75
3.9300
0.1109
4.188
SHEET 16 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
AC PANEL-INTERNAL TO
PEECC GTG#8
TURBINE/COMPRESSOR WASH
WATER INJ.SOL.VALVE 20TW 1-3
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
40
5.8800
0.1173
3.321
AC PANEL-INTERNAL TO
PEECC GTG#8
CRANKING MOTOR
HEATER(23CR-1)
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
30
5.8800
0.1173
2.491
AC PANEL-INTERNAL TO
PEECC GTG#8
COMPARTMENT LIGHTING(DF)
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
20
5.8800
0.1173
1.661
AC PANEL-INTERNAL TO
PEECC GTG#8
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
40
5.8800
0.1173
3.321
AC PANEL-INTERNAL TO
PEECC GTG#8
230
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
60
3.9300
0.1109
3.350
AC PANEL-INTERNAL TO
PEECC GTG#8
INLET COMPARTMENT
(LIGHTS,RECEPTCLES,34TF1,88MH)
230
20.00
0.6230
0.7772
3C X 4
3C X 4
38
37
23.67
28.76
20
5.8800
0.1173
1.661
AC PANEL-INTERNAL TO
PEECC GTG#8
230
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
50
3.9300
0.1109
2.792
AC PANEL-INTERNAL TO
PEECC GTG#8
230
20.00
0.6230
0.7772
3C X 6
3C X 6
48
46
29.90
35.75
50
3.9300
0.1109
2.792
MLDB-BUS-1
SLDB-1(MAIN SWITCHGEAR
BLDG) (Load in kVA)
35
480
42.10
0.6230
0.7603
4C X 25
4C X 25
118
104
73.51
79.07
30
0.9270
0.1072
0.367
MLDB-BUS-1
25
480
30.07
0.6230
0.7603
4C X 35
4C X 35
142
125
88.47
95.04
140
0.6690
0.0973
0.902
MLDB-BUS-1
60
480
72.17
0.6230
0.7603
4C X 95
4C X 95
272
250
169.46
190.08
490
0.2480
0.0963
3.269
MLDB-BUS-2
SLDB-1(MAIN SWITCHGEAR
BLDG) (Load in kVA)
35
480
42.10
0.6230
0.7603
4C X 25
4C X 25
118
104
73.51
79.07
30
0.9270
0.1072
0.367
MLDB-BUS-2
25
480
30.07
0.6230
0.7603
4C X 35
4C X 35
142
125
88.47
95.04
140
0.6690
0.0973
0.902
MLDB-BUS-2
60
480
72.17
0.6230
0.7603
4C X 95
4C X 95
272
250
169.46
190.08
490
0.2480
0.0963
3.269
SLDB-1
0.736
127
0.8
7.24
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
40
5.8800
0.1593
SLDB-1
0.8
127
0.8
7.87
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
70
5.8800
0.1593
4.166
SLDB-1
TRAFO/PERIPHERAL LIGHTING
0.58
220
0.8
3.30
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
110
5.8800
0.1593
SLDB-1
1.5
220
0.8
4.92
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
60
5.8800
0.1237
SLDB-1
1.5
220
0.8
4.92
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
70
5.8800
0.1237
SLDB-1
1.5
220
0.8
4.92
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
90
5.8800
0.1237
SLDB-1
220
0.8
9.84
0.6230
0.7772
4C X 16
4C X 16
88
80
54.82
62.18
500
1.4700
0.1068
SLDB-1
220
0.8
9.84
0.6230
0.7772
4C X 16
4C X 16
88
80
54.82
62.18
500
1.4700
0.1068
SLDB-1
0.736
127
0.8
7.24
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
60
5.8800
0.1593
10 SLDB-1
SWITCHGEAR TOOM
0.436
480
0.8
--
0.66
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
60
5.8800
0.1593
11
BUILDING ENTRANCES/STAIRE
CASES /STREET LIGHTING
0.436
127
0.8
4.29
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
200
2.3300
0.1111
SLDB-1
275167113.xls
SECTION :Sizing schedule
SHEET 17 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
12 SLDB-1
13 SLDB-1
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
220
0.8
9.84
0.6230
0.7772
4C X 16
4C X 16
88
80
54.82
62.18
500
1.4700
0.1068
1.5
220
0.8
4.92
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
100
2.3300
0.1111
SLDB2
SLDB2
0.32
127
0.8
3.15
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
40
5.8800
0.1593
0.952
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
95
5.8800
0.1593
SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
95
5.8800
0.1593
SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
95
5.8800
0.1593
SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
95
5.8800
0.1593
SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
150
5.8800
0.1593
SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
150
5.8800
0.1593
--
SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
150
5.8800
0.1593
SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
150
5.8800
0.1593
10 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
150
5.8800
0.1593
11
SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
150
5.8800
0.1593
12 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
150
5.8800
0.1593
13 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
170
5.8800
0.1593
14 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
170
5.8800
0.1593
15 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
170
5.8800
0.1593
16 SLDB2
GENERATOR TRANSFORMER -7
YARD LIGHTING/PERIPHARAL
LIGHTING
1.65
220
0.8
5.41
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
150
5.8800
0.1237
17 SLDB2
220
0.8
9.84
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
100
5.8800
0.1237
18 SLDB2
220
0.8
9.84
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
125
5.8800
0.1237
19 SLDB2
220
0.8
9.84
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
160
5.8800
0.1237
20 SLDB2
220
0.8
6.56
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
270
2.3300
0.1111
21 SLDB2
SMOKE STACK/AVATION
WARNING LIGHTS
220
0.8
3.28
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
150
2.3300
0.1111
22 SLDB2
0.32
127
0.8
3.15
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
100
5.8800
0.1593
23 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
180
5.8800
0.1593
24 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
180
5.8800
0.1593
25 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
180
5.8800
0.1593
275167113.xls
SECTION :Sizing schedule
SHEET 18 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
26 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
300
5.8800
0.1593
27 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
300
5.8800
0.1593
28 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
300
5.8800
0.1593
29 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
300
5.8800
0.1593
30 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
300
5.8800
0.1593
31 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
300
5.8800
0.1593
32 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
350
5.8800
0.1593
33 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
350
5.8800
0.1593
34 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
350
5.8800
0.1593
35 SLDB2
127
0.8
9.84
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
350
5.8800
0.1593
36 SLDB2
GENERATOR TRANSFORMER -8
YARD LIGHTING/PERIPHARAL
LIGHTING
1.65
220
0.8
5.41
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
100
5.8800
0.1237
37 SLDB2
220
0.8
9.84
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
200
5.8800
0.1237
38 SLDB2
220
0.8
9.84
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
225
5.8800
0.1237
39 SLDB2
220
0.8
9.84
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
250
5.8800
0.1237
40 SLDB2
220
0.8
6.56
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
350
2.3300
0.1111
41 SLDB2
SMOKE STACK/AVATION
WARNING LIGHTS
220
0.8
3.28
0.6230
0.7772
4C X 10
4C X 10
67
62
41.74
48.19
250
2.3300
0.1111
SLDB3
ATTENDANT ROOM
LIGHTING/EXIT LIGHTS
SLDB3
0.16
127
0.8
1.57
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
30
5.8800
0.1593
SLDB3
0.24
220
0.8
0.79
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
120
5.8800
0.1593
SLDB3
220
0.8
13.12
0.6230
0.7772
4C X 10
4C X 10
67.00
62.00
41.74
48.19
200
2.3300
0.1111
SLDB3
0.5
220
0.8
1.64
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
30
5.8800
0.1237
SLDB3
0.5
220
0.8
1.64
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
20
5.8800
0.1237
SLDB3
0.32
127
0.8
3.15
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
270
5.8800
0.1593
SLDB3
0.32
127
0.8
3.15
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
300
5.8800
0.1593
--
SLDB3
0.32
127
0.8
3.15
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
320
5.8800
0.1593
10 SLDB3
0.16
127
0.8
1.57
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
400
5.8800
0.1593
11
0.5
220
0.8
1.64
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
280
5.8800
0.1237
0.5
220
0.8
1.64
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
400
5.8800
0.1237
SLDB3
12 SLDB3
275167113.xls
SECTION :Sizing schedule
0.24
127
0.8
2.36
0.6942
0.6718
1C X 4
1C X 4
38
37
26.38
24.86
50
5.8800
0.1593
SHEET 19 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
NO. OF
PHASES
kW
VOLTAGE
POWER
FACTOR
EFFICIENCY
VOLTS
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
13 SLDB3
220
0.8
13.12
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
100
5.8800
0.1237
14 SLDB3
220
0.8
13.12
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
250
5.8800
0.1237
15 SLDB3
220
0.8
13.12
0.6230
0.7772
4C X 4
4C X 4
38
37
23.67
28.76
250
5.8800
0.1237
44.00
0.6942
0.6718
1C X 25
1C X 25
145
137
100.66
92.04
50
0.9270
3.263
DC MCC-GTG#7
5.5
125
DC MCC-GTG#7
2.5
125
20.00
0.6942
0.6718
1C X 16
1C X 16
88
80
61.09
53.74
50
1.4664
2.346
DC MCC-GTG#8
5.5
125
44.00
0.6942
0.6718
1C X 25
1C X 25
145
137
100.66
92.04
50
0.9270
3.263
DC MCC-GTG#8
2.5
125
20.00
0.6942
0.6718
1C X 16
1C X 16
88
80
61.09
53.74
50
1.4664
2.346
125
15.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
15
5.8782
2.116
125
15.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
25
5.8782
3.527
125
30.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
15
5.8782
4.232
125
30.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
15
5.8782
4.232
125
20.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
20
5.8782
3.762
10
125
20.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
20
5.8782
3.762
11
125
30.00
0.6942
0.6718
1C X 10
1C X 10
82
83
56.92
55.76
90
2.3334
12
125
20.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
15
5.8782
2.822
13
125
15.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
15
5.8800
2.117
14
125
15.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
25
5.8782
3.527
15
125
30.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
15
5.8782
4.232
16
125
30.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
15
5.8782
4.232
17
125
20.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
20
5.8782
3.762
18
125
20.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
20
5.8782
3.762
19
125
30.00
0.6942
0.6718
1C X 10
1C X 10
82
83
56.92
55.76
90
2.3334
20
125
20.00
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
15
5.8782
2.822
BATTERY BANK-1
125
335.82
0.6942
0.6718
1C X 630
1C X 630
1184
752
821.93
505.19
15
0.0361
0.291
275167113.xls
SECTION :Sizing schedule
SHEET 20 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
kW
NO. OF
PHASES
VOLTAGE
VOLTS
POWER
FACTOR
EFFICIENCY
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
BATTERY MONITORING
PANEL-1
125
335.82
0.6942
0.6718
1C X 630
1C X 630
1184
752
821.93
505.19
35
0.0361
0.679
BATTERY CHARGER-1
125
154.00
0.6942
0.6718
1C X 120
1C X 120
409
327
283.93
219.68
15
0.1951
0.721
BATTERY BANK-2
125
335.82
0.6942
0.6718
1C X 630
1C X 630
1184
752
821.93
505.19
15
0.0361
0.291
BATTERY MONITORING
PANEL-2
125
335.82
0.6942
0.6718
1C X 630
1C X 630
1184
752
821.93
505.19
35
0.0361
0.679
BATTERY CHARGER-2
125
154.00
0.6942
0.6718
1C X 120
1C X 120
409
327
283.93
219.68
15
0.1951
0.721
%
STARTING
VOLTAGE
DROP
125V DC MAIN
DISTRIBUTION BOARD-I
4.16 KV SWITCHGEAR
0.72
125
5.76
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
25
3.9273
0.905
125V DC MAIN
DISTRIBUTION BOARD-I
0.804
125
6.43
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
30
3.9273
1.213
125V DC MAIN
DISTRIBUTION BOARD-I
0.452
125
3.62
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
80
3.9273
1.818
125V DC MAIN
DISTRIBUTION BOARD-I
2.53
125
20.24
0.6942
0.6718
1C X 95
1C X 95
344
286
238.80
192.13
300
0.2461
2.391
125V DC MAIN
DISTRIBUTION BOARD-I
125
63.00
0.6942
0.6718
1C X 25
1C X 25
145
137
100.66
92.04
30
0.9270
2.803
125V DC MAIN
DISTRIBUTION BOARD-I
125
63.00
0.6942
0.6718
1C X 95
1C X 95
344
286
238.80
192.13
10
0.2461
0.248
125V DC MAIN
DISTRIBUTION BOARD-II
0.452
125
3.62
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
110
3.9273
2.499
125V DC MAIN
DISTRIBUTION BOARD-II
2.53
125
20.24
0.6942
0.6718
1C X 95
1C X 95
344
286
238.80
192.13
300
0.2461
2.391
125V DC MAIN
DISTRIBUTION BOARD-II
125
63.00
0.6942
0.6718
1C X 25
1C X 25
145
137
100.66
92.04
30
0.9270
2.803
0.375
125
3.00
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
30
0.9270
0.133
0.078
125
0.62
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
25
0.9270
0.023
0.5
125
4.00
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
40
0.9270
0.237
0.5
125
4.00
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
50
0.9270
0.297
0.145
125
1.16
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
25
0.9270
0.043
0.145
125
1.16
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
25
0.9270
0.043
275167113.xls
SECTION :Sizing schedule
SHEET 21 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
125V DC MAIN
DISTRIBUTION BOARD-I
kW
NO. OF
PHASES
VOLTAGE
VOLTS
POWER
FACTOR
EFFICIENCY
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
0.134
125
1.07
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
25
0.9270
0.040
0.5
125
4.00
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
30
0.9270
0.178
0.155
125
1.24
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
30
0.9270
0.055
%
STARTING
VOLTAGE
DROP
0.375
125
3.00
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
30
0.9270
0.133
0.078
125
0.62
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
25
0.9270
0.023
0.5
125
4.00
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
40
0.9270
0.237
0.5
125
4.00
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
50
0.9270
0.297
0.145
125
1.16
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
25
0.9270
0.043
0.134
125
1.07
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
25
0.9270
0.040
0.134
125
1.07
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
30
0.9270
0.048
0.155
125
1.24
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
30
0.9270
0.055
0.5
125
4.00
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
30
0.9270
0.178
125
32.00
0.6942
0.6718
1C X 50
1C X 50
218
195
151.34
131.00
200
0.4935
5.053
125
3.20
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
80
5.8782
125
32.00
0.6942
0.6718
1C X 50
1C X 50
218
195
151.34
131.00
350
0.4935
125
32.00
0.6942
0.6718
1C X 50
1C X 50
218
195
151.34
131.00
150
0.4935
3.790
0.4
125
3.20
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
80
5.8782
0.4
125V DC SUB-SUB
DISTRIBUTION BOARD-I
0.48
125
3.84
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
140
5.8782
125V DC SUB-SUB
DISTRIBUTION BOARD-I
0.48
125
3.84
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
140
5.8782
275167113.xls
SECTION :Sizing schedule
SHEET 22 OF 23
SL
NO.
FEEDER DESCRIPTION
FROM
LOAD
TO
kW
NO. OF
PHASES
VOLTAGE
VOLTS
POWER
FACTOR
EFFICIENCY
FULL
LOAD
CURRENT
IFL
DERATING FACTOR
AMPS
CURRENT CARRYING
CAPACITY OF CABLE
SQMM
CURRENT CARRYING
CAPACITY OF CABLE
AFTER DERATING
AMPS
AMPS
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
IN AIR
IN DUCT
AC
LENGTH OF CONDUCTOR
CABLE
RESISTANCE,
R AT 90 0C
REACTANCE
X OF CABLE
%
RUNNING
VOLTAGE
DROP
METERS
OHMS/KM
OHMS/KM
%
STARTING
VOLTAGE
DROP
125V DC SUB-SUB
DISTRIBUTION BOARD-II
0.48
125
3.84
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
100
5.8782
125V DC SUB-SUB
DISTRIBUTION BOARD-II
0.48
125
3.84
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
100
5.8782
125V DC SUB-SUB
DISTRIBUTION BOARD-II
0.48
125
3.84
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
180
5.8782
125V DC SUB-SUB
DISTRIBUTION BOARD-III
0.48
125
3.84
0.6942
0.6718
1C X 6
1C X 6
60
63
41.65
42.32
300
5.0111
125V DC SUB-SUB
DISTRIBUTION BOARD-III
UNLOADING PUMP/ATTANDENT
ROOM DC LIGHTING'
0.18
125
1.44
0.6942
0.6718
1C X 4
1C X 4
47
50
32.63
33.59
150
5.8782
275167113.xls