Product Guide - RED615
Product Guide - RED615
1MRS756500 H
Contents
1. Description.....................................................................3
2. Standard configurations.................................................3
3. Protection functions......................................................11
4. Application...................................................................11
6. Control.........................................................................15
7. Measurements.............................................................16
8. Fault location................................................................16
9. Disturbance recorder....................................................16
26. Tools...........................................................................55
29. Certificates..................................................................60
14. Self-supervision...........................................................17
30. References..................................................................60
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
Copyright 2014 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
ABB
1. Description
RED615 is a phase-segregated two-end line differential
protection and control IED (intelligent electronic device)
designed for utility and industrial power systems, including
radial, looped and meshed distribution networks with or
without distributed power generation. RED615 is also
designed for the protection of line differential applications
having a transformer within the protection zone. The
RED615s communicate between substations over a fibreoptic link or a galvanic pilot wire connection. RED615 is a
member of ABBs Relion product family and part of its 615
protection and control product series. The 615 series IEDs
are characterized by their compactness and withdrawableunit design. Re-engineered from the ground up, the 615
series has been guided by the IEC 61850 standard for
communication and interoperability of substation automation
equipment.
The IED provides unit type main protection for overhead lines
and cable feeders in distribution networks. The IED also
features current-based protection functions for remote backup for down-stream protection IEDs and local back-up for the
line differential main protection. Further, standard
configurations B and C also include earth-fault protection.
Standard configuration D includes directional overcurrent and
voltage based protection functions.
The IED is adapted for the protection of overhead line and
cable feeders in isolated neutral, resistance earthed,
ABB
1MRS756500 H
Issued: 2014-01-24
Revision: H
compensated (impedance earthed) and solidly earthed
networks. Once the IED has been given the applicationspecific settings, it can directly be put into service.
The 615 series IEDs support a range of communication
protocols including IEC 61850 with GOOSE messaging, IEC
61850-9-2 LE (except in RED615), IEC 60870-5-103,
Modbus and DNP3. Profibus DPV1 communication protocol
is supported by using the protocol converter SPA-ZC 302.
2. Standard configurations
RED615 is available in five alternative standard configurations.
The standard signal configuration can be altered by means of
the signal matrix or the graphical application functionality of
the Protection and Control IED Manager PCM600. Further,
the application configuration functionality of PCM600
supports the creation of multi-layer logic functions utilizing
various logical elements including timers and flip-flops. By
combining protection functions with logic function blocks the
IED configuration can be adapted to user specific application
requirements.
The IED is delivered from the factory with default connections
described in the functional diagrams for binary inputs, binary
outputs, function-to-function connections and alarm LEDs.
The positive measuring direction of directional protection
functions is towards the outgoing feeder.
RED615
1MRS756500 H
PROTECTION
ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization
Master Trip
Lockout relay
94/86
ESC
Clear
R
L
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
3I
I2>
46
3I>
51P-1
I
PHIZ
HIZ
3I>>>
50P/51P
2
3I>>
51P-2
3I>/Io>BF
51BF/51NBF
3I2f>
68
3dI>L
87L
Clear
R
L
CONDITION MONITORING
AND SUPERVISION
Io
PCS
PCS
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3
OPTS
OPTM
MCS 3I
MCS 3I
BST
BST
18
MAP
MAP
ESC
TCS
TCM
Object
Ctrl 2)
Ind 3)
DC
ES
3)
0
0
1
0
0
0
1
0
1
1
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
0
1
0
0
0
1
0
0
0
1
1
0
0
1
1
1
1
1
1
1
1
1
1
1
0
0
0
1
0
0
0
0
1
1
1
0
1
1
1
0
1
1
1
0
1
1
1
1
1
0
0
1
1
0
0
1
0
1
1
1
0
1
1
MEASUREMENT
CB
2)
1
1
1
1
1
1
1
1
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
1)
STANDARD
CONFIGURATION
- I, Io
- Limit value supervision
- Load prole record
- Symmetrical components
1)
Current transformer
Voltage transformer
1)
REMARKS
Optional
function
Calculated
value
3 No. of
instances
Io/Uo
3I
OR Alternative
function to be
dened when
Sum of phase
ordering
currents
RED615
AT REMOTE
END
GUID-78F52211-9D37-4A2F-9527-CD61BDEA68A2 V1 EN
Figure 1.
ABB
0
0
0
0
0
0
0
0
0
1 0
0
0 1 0 1 0 0
1 0
0
Uo
RED615
1MRS756500 H
PROTECTION
ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization
Master Trip
Lockout relay
94/86
ESC
Clear
R
L
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
3I
I2>
46
I2/I1>
46PD
3I>>>
50P/51P
2
3Ith>F
49F
3I>/Io>BF
51BF/51NBF
3I>>
51P-2
3I2f>
68
3Ith>T
49T
ESC
Clear
3I>
51P-1
R
L
CONDITION MONITORING
AND SUPERVISION
CBCM
CBCM
3dI>L
87L
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3
OPTS
OPTM
MCS 3I
MCS 3I
0 1 0 0 0 1 1 0 0 1 1 0 0
Io
BST
BST
Io>>
51N-2
PCS
PCS
Uo
Object
Io>>
67N-2
Io>
67N-1
Yo>
21YN
Io>IEF
67NIEF
Io>HA
51NHA
Po>
32N
OR
Uo>
59G
1
1
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
0
1
0
0
0
1
0
0
0
1
1
0
0
1
1
1
1
1
1
1
1
1
1
1
0
0
0
1
0
0
0
0
1
1
1
0
1
1
1
0
1
1
1
0
1
1
1
1
1
0
0
1
1
0
0
OR
18
MAP
MAP
MEASUREMENT
Ctrl 2)
Ind 3)
CB
DC
ES
1)
2)
3)
0
0
1
0
0
0
1
0
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
TCS
TCM
1
1
1
1
1
1
1
1
PHIZ
HIZ
Io
Io
STANDARD
CONFIGURATION
- I, Io, Uo
- Limit value supervision
- Load prole record
- Symmetrical components
1)
Current transformer
Voltage transformer
1)
OI
79
REMARKS
Optional
function
Calculated
value
3 No. of
instances
Io/Uo
3I
OR Alternative
function to be
dened when
ordering
RED615
AT REMOTE
END
GUID-6AB801FF-A43F-40D6-8D70-D27EF2F402B0 V1 EN
Figure 2.
ABB
1
0
1
1
1
0
1
1
0
0
0
0
0
0
0
0
0
1 0
0
0 1 0 1
1 0
0
RED615
1MRS756500 H
PROTECTION
ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization
Master Trip
Lockout relay
94/86
ESC
Clear
R
L
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
3I
I2>
46
I2/I1>
46PD
3I>>>
50P/51P
2
3Ith>F
49F
3I>/Io>BF
51BF/51NBF
3I>>
51P-2
3I2f>
68
3Ith>T
49T
ESC
Clear
3I>
51P-1
R
L
CONDITION MONITORING
AND SUPERVISION
3dI>L
87L
CBCM
CBCM
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3
OPTS
OPTM
MCS 3I
MCS 3I
0 0 0 1 1 0 0 1 1 0 0
Io
BST
BST
Io
Io
Io>>>
50N/51N
Io>
51N-1
Io>>
51N-2
Io>HA
51NHA
PHIZ
HIZ
18
MAP
MAP
PCS
PCS
Object
Ctrl 2)
Ind 3)
DC
ES
3)
0
0
1
0
0
0
1
0
1
1
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
0
1
0
0
0
1
0
0
0
1
1
0
0
1
1
1
1
1
1
1
1
1
1
1
0
0
0
1
0
0
0
0
1
1
1
0
1
1
1
0
1
1
1
0
1
1
1
1
1
0
0
1
1
0
0
1
0
1
1
1
0
1
1
MEASUREMENT
CB
2)
1
1
1
1
1
1
1
1
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
TCS
TCM
1)
STANDARD
CONFIGURATION
- I, Io
- Limit value supervision
- Load prole record
- Symmetrical components
1)
Current transformer
Voltage transformer
1)
OI
79
REMARKS
Optional
function
Calculated
value
3 No. of
instances
Io/Uo
3I
OR Alternative
function to be
dened when
ordering
RED615
AT REMOTE
END
GUID-C4999021-E1FE-4D55-AB91-FC7C6963501B V1 EN
Figure 3.
ABB
0
0
0
0
0
0
0
0
0
1 0
0
0 1 0 1 0 0
1 0
0
1MRS756500 H
UL1UL2UL3
Uo
RED615
PROTECTION
ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization
Master Trip
Lockout relay
94/86
ESC
Clear
R
L
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
3I
I2>
46
I2/I1>
46PD
3I>>>
50P/51P
2
3Ith>F
49F
3Ith>T
49T
3I>/Io>BF
51BF/51NBF
3I>
67-1
3I2f>
68
3I>>
67-2
R
L
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3
Io
3dI>L
87L
3I
Io
PHIZ
HIZ
Clear
CONDITION MONITORING
AND SUPERVISION
1 0 1 0 0 0 1 1 0 0 1 1 0 0
0
Io>>
51N-2
ESC
BST
BST
STANDARD
CONFIGURATION
FUSEF
60
CBCM
CBCM
OPTS
OPTM
PCS
PCS
0
0
1
0
0
0
1
0
1
1
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
0
1
0
0
0
1
0
0
0
1
1
0
0
1
1
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
MCS 3I
MCS 3I
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
1
0
0
0
0
1
1
1
0
1
1
1
0
1
1
1
0
1
1
1
1
1
0
0
1
1
0
0
TCS
TCM
Io
CONTROL AND INDICATION 1)
2
Io
Uo
Io>
67N-1
Yo>
21YN
Io>>
67N-2
Io>IEF
67NIEF
Po>
32N
Io>HA
51NHA
OR
Object
Ind 3)
CB
DC
ES
1)
OR
2)
3)
UL1UL2UL3
2xRTD
1xmA
3U<
27
3U>
59
FLOC
21FL
3I
U2>
47O3
Uo>
59G
U1<
47U+
4
f>/f<,
df/dt
81
18
MAP
MAP
UL1UL2UL3
MEASUREMENT
Ctrl 2)
1)
Current transformer
Voltage transformer 2)
1)
2)
PQM3I
PQM3I
OI
79
PQM3U
PQM3V
PQMU
PQMV
REMARKS
Optional
function
Calculated
value
3 No. of
instances
Io/Uo
OR Alternative
function to be
dened when
ordering
RED615
AT REMOTE
END
GUID-F76822E6-DDB6-44F2-8704-5A5B3035BAFD V1 EN
Figure 4.
ABB
1
0
1
1
1
0
1
1
0
0
0
0
0
0
0
0
0
1 0
0
0 1 0 1
1 0
0
1MRS756500 H
RED615
PROTECTION
ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization
Master Trip
Lockout relay
94/86
ESC
Clear
R
L
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
I2>
46
3I
I2/I1>
46PD
3I>>>
50P/51P
2
3Ith>F
49F
3Ith>T
49T
3I>/Io>BF
51BF/51NBF
3I>
67-1
Clear
R
L
CONDITION MONITORING
AND SUPERVISION
3I2f>
68
3I>>
67-2
ESC
3dI>L
87L
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3
Io
3I
1 0 0 0 1 1 0 0 1 1 0 0
UL1UL2UL3
UL1UL2UL3
Io
Io>
67N-1
BST
BST
Io>>
67N-2
Io
Yo>
21YN
Io>HA
51NHA
Po>
32N
OR
OR
Uo
3
3U<
27
3U>
59
FLOC
21FL
3I
CBCM
CBCM
OPTS
OPTM
PCS
PCS
Object
Io
Io>IEF
67NIEF
FUSEF
60
U2>
47O3
Uo>
59G
U1<
47U+
4
f>/f<,
df/dt
81
18
MAP
MAP
CB
DC
ES
3)
1
1
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
0
1
0
0
0
1
0
0
0
1
1
0
0
1
1
1
1
1
1
1
1
1
1
1
0
0
0
1
0
0
0
0
1
1
1
0
1
1
1
0
1
1
1
0
1
1
1
1
1
0
0
1
1
0
0
1
0
1
1
1
0
1
1
MEASUREMENT
Ind 3)
2)
0
0
1
0
0
0
1
0
TCS
TCM
Ctrl 2)
1)
1
1
1
1
1
1
1
1
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
MCS 3I
MCS 3I
Io>>
51N-2
STANDARD
CONFIGURATION
1)
Current sensor
Voltage sensor
Current transformer
1)
PQM3I
PQM3I
OI
79
PQM3U
PQM3V
PQMU
PQMV
REMARKS
Optional
function
Calculated
value
3 No. of
instances
Io/Uo
OR Alternative
function to be
dened when
ordering
RED615
AT REMOTE
END
GUID-D0C7BD80-3FC0-448D-ACD4-D6123319339C V1 EN
Figure 5.
ABB
0
0
0
0
0
0
0
0
0
1 0
0
0 1 0 1 0 0
1 0
0
1MRS756500 H
Std. conf.
Line differential protection with directional earth-fault protection, CB condition monitoring and CB control
Line differential protection with non-directional earth-fault protection, CB condition monitoring and CB control
Line differential protection, directional overcurrent and directional earth-fault protection, phase-voltage and frequency based
protection and measurement functions, CB condition monitoring, CB control and fault locator (optional)
Line differential protection with directional overcurrent and directional earth-fault protection, phase-voltage and frequency
based protection and measurement functions, CB condition monitoring, CB control, sensor inputs for phase currents and
phase voltages and fault locator (optional)
ABB
1MRS756500 H
IEC 61850
PHLPTOC
PHHPTOC
PHIPTOC
DPHLPDOC
DPHHPDOC
EFLPTOC
2 2)
EFHPTOC
1 2)
EFIPTOC
2 2)3)
2 4)5)
Protection1)
1 2)
2)3)
DEFLPDEF
DEFHPDEF
1 2)3)
1 2)3)
1 4)5)
EFPADM
(3) 2)3)6)
(3) 2)3)6)
(3) 2)5)6)
WPWDE
(3) 2)3)6)
(3) 2)3)6)
(3) 2)5)6)
6)
INTRPTEF
HAEFPTOC
EFHPTOC
NSPTOC
PDNSPTOC
ROVPTOV
7)8)
(1)
6)8)
1
(1)
6)8)
1 4)
2
7)8)
(1)
6)8)
1 5)8)
(1) 6)8)
1 4)
1 4)
2
3 7)
3 5)
PHPTUV
PHPTOV
PSPTUV
NSPTOV
Frequency protection
FRPFRQ
T1PTTR
T2PTTR
BSTGGIO
CCBRBRF
1 9)
INRPHAR
Master trip
TRPPTRC
MAPGAPC
18
18
18
18
18
Fault locator
SCEFRFLO
(1)
(1)
LNPLDF
PHIZ
3 3)
Power quality
Current total demand distortion
Voltage total harmonic distortion
Voltage variation
CMHAI
(1) 11)
(1) 11)
VMHAI
(1)
11)
(1) 11)
(1)
11)
(1) 11)
PHQVVR
Control
Circuit-breaker control
CBXCBR
Disconnector control
DCXSWI
ESXSWI
DCSXSWI
ESSXSWI
Autoreclosing
DARREC
(1)
(1)
(1)
(1)
Condition monitoring
Circuit-breaker condition monitoring
SSCBR
TCSSCBR
CCRDIF
SEQRFUF
PCSRTPC
10
ABB
1MRS756500 H
IEC 61850
MDSOPT
Disturbance recorder
RDRE
LDPMSTA
CMMXU
CSMSQI
RESCMMXU
VMMXU
RESVMMXU
VSMSQI
PEMMXU
RTD/mA measurement
XRGGIO130
Frequency measurement
FMMXU
Measurement
(1)
1
The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.
Io selectable by parameter, Io measured as default
"Uo measured" is always used.
Io selectable by parameter, "Io calculated" as default
"Uo calculated" is always used.
One of the following can be ordered as an option: admittance-based E/F, wattmetric-based E/F or harmonics-based E/F. The option is an addition to the existing E/F of the original
configuration. The optional E/F has also a predefined configuration in the IED. The optional E/F can be set on or off.
7)
Uo selectable by parameter, Uo measured as default
8)
"Io measured" is always used.
9)
"Io calculated" is always used.
10) Multi-purpose protection is used, for example, for RTD/mA-based protection or analog GOOSE.
11) Power quality option includes current total demand distortion, voltage total harmonic distortion and voltage variation.
3. Protection functions
The IED offers two-stage phase-segregated line differential
protection, phase overcurrent protection, negative phasesequence overcurrent protection and circuit breaker failure
protection. Depending on the standard configuration chosen,
the basic functionality can be extended by thermal overload
protection, non-directional or directional overcurrent
protection, directional or non-directional earth-fault
protection, sensitive earth-fault protection, phase
discontinuity protection, transient/intermittent earth-fault
protection, residual overvoltage protection, phase-voltage
and frequency based protection and three-pole multi-shot
auto-reclose functions for overhead line feeders. For standard
configuration B, D and E, admittance-based, wattmetricbased or harmonics-based earth-fault protection is offered as
an option in addition to the directional earth-fault protection.
The line differential protection function includes a stabilized
low stage and an instantaneous high stage. The stabilized low
stage provides sensitive differential protection and remains
stable during, for example, current transformer saturation
conditions. The low-stage operation can be restrained using
second harmonic detection if an out-of-zone power
transformer is to be energized. The instantaneous high stage
offers less sensitive differential protection but enables fast
operation during high fault currents. If there is an in-zone
transformer in the protection zone, then the vector group is
ABB
1MRS756500 H
Protection
communication
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
ESC
IL2 0 A
Clear
3I
3I
R
L
I
O
I
RED615
ESC
Clear
R
L
I
RED615
Std. conf.
Std. conf.
ANSI
IEC
ANSI
IEC
46
I2>
46
I2>
50P/51P
3I>>>
50P/51P
3I>>>
51BF/51NBF
3I>/Io>BF
51BF/51NBF
3I>/Io>BF
51P-1/51P-2
3I>/3I>>
51P-1/51P-2
3I>/3I>>
87L
3I>
87L
3I>
BST
BST
BST
BST
MCS 3I
MCS 3I
MCS 3I
MCS 3I
GUID-28763BDA-8E54-4716-9CDD-F2A208E79E25 V1 EN
Figure 6.
Line differential protection for an interconnecting feeder between two primary distribution substations using standard
configuration A
12
ABB
1MRS756500 H
3U
Uo
3I
ESC
RED615
D
Std. conf.
A
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
ANSI
IEC
46
I2>
47O-/59
U2>/3U>
47U+/27
U1</3U<
50P/51P
3I>>>
51BF/51NBF
3I>/Io>BF
67N-1/67N-2
Io>/Io>>
87L
3I>
BST
BST
MCS 3I
MCS 3I
Clear
R
L
Io
Protection
communication
Io
RED615
3I
B/C
Std. conf.
A
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
ESC
Clear
ANSI
IEC
R
L
46
I2>
49F/49T
3Ith>F/3Ith>T
50P/51P
3I>>>
51BF/51NBF
3I>/Io>BF
51N
Io>
87L
3I>
BST
BST
MCS 3I
MCS 3I
GUID-3084D6C6-6067-4827-AA10-DAC1A772077C V1 EN
Figure 7.
RED615
A
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
3I
ESC
Clear
R
L
3U
Io
Protection
communication
Std. conf.
ANSI
IEC
46
I2>
47O-/59
U2>/3U>
47U+/27
U1</3U<
50P/51P
3I>>>
51BF/51NBF
3I>/Io>BF
67N-1/67N-2
Io>/Io>>
87L
3I>
BST
BST
Io
RED615
E
Std. conf.
3U
3I
A
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
I
O
ESC
ANSI
IEC
46
I2>
47O-/59
U2>/3U>
47U+/27
U1</3U<
50P/51P
3I>>>
51BF/51NBF
3I>/Io>BF
67N-1/67N-2
Io>/Io>>
87L
3I>
BST
BST
Clear
R
L
GUID-6802EC2A-DC22-44E6-8BD2-DF7DCEAAEBA0 V1 EN
Figure 8.
ABB
13
1MRS756500 H
protection zone. The standard configuration E has been preconfigured especially for ABB switchgears, for example,
UniGear Digital. The use of this configuration is not restricted
for this purpose only.
The 615 series IEDs offer native support for the IEC 61850
standard also including binary and analog horizontal GOOSE
messaging. In addition, process bus with sampled values of
analog phase voltages is supported. Compared to traditional
hard-wired, inter-device signaling, peer-to-peer
communication over a switched Ethernet LAN offers an
advanced and versatile platform for power system protection.
Among the distinctive features of the protection system
approach, enabled by the full implementation of the IEC
61850 substation automation standard, are fast
communication capability, continuous supervision of the
integrity of the protection and communication system, and an
inherent flexibility regarding reconfiguration and upgrades.
At substation level, COM600 uses the data content of the baylevel IEDs to enhance substation level functionality. COM600
features a Web browser-based HMI, which provides a
Version
System 800xA
5.1 or later
14
ABB
1MRS756500 H
ABB
MicroSCADA Pro/
System 800xA
COM600
Web HMI
Ethernet switch
PCM600
IEC 61850
COM600
Web HMI
Ethernet switch
PCM600
IEC 61850
GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V1 EN
Figure 9.
ABB power system example using Relion IEDs, Grid Automation controller COM600 and MicroSCADA Pro/System 800xA
6. Control
RED615 integrates functionality for the control of a circuit
breaker via the front panel HMI or by means of remote
controls. In addition to the circuit-breaker control the IED
features two control blocks which are intended for motoroperated control of disconnectors or circuit breaker truck and
for their position indications. Further, the IED offers one
control block which is intended for motor-operated control of
one earthing switch control and its position indication.
Two physical binary inputs and two physical binary outputs
are needed in the IED for each controllable primary device
taken into use. Depending on the chosen standard
configuration of the IED the number of unused binary inputs
and binary outputs varies. Further, some standard
configurations also offer optional hardware modules that
increase the number of available binary inputs and outputs.
In case the amount of available binary inputs and/or outputs
of the chosen standard configuration is not sufficient, the
following alternatives are recommended:
ABB
1MRS756500 H
ABB
ABB
1MRS756500 H
17
1MRS756500 H
RED615
RED615
GUID-8CE71CC9-F0EA-4BE9-B693-173CAEA9FA58 V2 EN
Figure 10.
RED615
RED615
RPW600
modem
RPW600
modem
GUID-12C57326-6CB9-4FA9-B9F4-3D8F21015DCF V2 EN
Figure 11.
ABB
1MRS756500 H
Analog channels
5-6
7-8
CT
VT
Combi
sensor
BI
BO
RTD
mA
AD
12
4 PO + 6 SO
AF
18
4 PO + 9 SO
AC
11
4 PO + 6 SO
AE
17
4 PO + 9 SO
AD
12
4 PO + 6 SO
AF
18
4 PO + 9 SO
FE / FF
AD
12
4 PO + 6 SO
AE / AF
AG
16
4 PO + 6 SO
DA
AH
4 PO + 6 SO
AC
AA / AB
AC
D
E
ABB
Binary channels
19
Client A
1MRS756500 H
Client B
Network A
Network B
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN
Figure 12.
1MRS756500 H
Ethernet
Serial
100BASE-TX RJ-45
RS-232/RS-485
Fibre-optic ST
IEC 61850-8-1
MODBUS RTU/ASCII
MODBUS TCP/IP
DNP3 (serial)
DNP3 TCP/IP
IEC 60870-5-103
= Supported
ABB
21
1MRS756500 H
Value
Width
frame
177 mm
case
164 mm
frame
177 mm (4U)
case
160 mm
Height
Depth
Weight
complete IED
4.1 kg
2.1 kg
Type 1
Type 2
50 ms at Un
Fuse type
T4A/250 V
Value
Rated frequency
50/60 Hz
Current inputs
Rated current, In
1/5 A1)
4A
20 A
For 1 s
100 A
500 A
Half-wave value
250 A
1250 A
Input impedance
<100 m
<20 m
Rated voltage
60...210 V AC
Voltage inputs
Voltage withstand:
1)
22
Continuous
240 V AC
For 10 s
360 V AC
<0.05 VA
ABB
1MRS756500 H
Value
Operating range
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
16...176 V DC
Reaction time
<3 ms
Value
Rated voltage
250 V AC/DC
5A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
Value
Rated voltage
250 V AC/DC
5A
10 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
ABB
23
1MRS756500 H
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
Value
Rated voltage
250 V AC/DC
6A
15 A
30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC
5 A/3 A/1 A
Start
1 ms
Reset
Protocol
Cable
Front
TCP/IP protocol
10 MBits/s
Fibre type
Wave length
Max. distance
LC
MM 62.5/125 or 50/125 m
1300 nm
2 km
< 8 dB
LC
SM 9/125 m2)
1300 nm
20 km
< 8 dB
1)
2)
Value
B004, B0051)
Isolation
500V 1 min
Modulation
Unmodulated
Logic level
5 V TTL
Current consumption
<4 mA
Power consumption
<20 mW
1)
24
ABB
1MRS756500 H
Value
Front side
IP 54
IP 20
Value
-25...+55C (continuous)
-40...+70C (<16h)1)2)
Relative humidity
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
Up to 2000 m
-40...+85C
1)
2)
ABB
Degradation in MTBF and HMI performance outside the temperature range of -25...+55 C
For IEDs with an LC communication interface the maximum operating temperature is +70 C
25
1MRS756500 H
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
Common mode
2.5 kV
Differential mode
2.5 kV
Reference
IEC 61000-4-18
IEC 60255-22-1, class III
2.5 kV
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
Contact discharge
8 kV
Air discharge
15 kV
IEC 61000-4-6
IEC 60255-22-6, class III
10 V/m (rms)
f = 80...2700 MHz
IEC 61000-4-3
IEC 60255-22-3, class III
10 V/m
f = 900 MHz
ENV 50204
IEC 60255-22-3, class III
20 V/m (rms)
f = 80...1000 MHz
IEEE C37.90.2-2004
All ports
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
4 kV
IEC 61000-4-5
IEC 60255-22-5
Communication
1 kV, line-to-earth
Other ports
4 kV, line-to-earth
2 kV, line-to-line
IEC 61000-4-8
Continuous
1...3 s
300 A/m
1000 A/m
1000 A/m
6.4/16 s
IEC 61000-4-10
2s
100 A/m
1 MHz
400 transients/s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
26
IEC 61000-4-9
IEC 61000-4-11
ABB
1MRS756500 H
Reference
IEC 61000-4-16
IEC 60255-22-7, class A
Common mode
300 V rms
Differential mode
150 V rms
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
Emission tests
IEC 61000-4-16
EN 55011, class A
IEC 60255-25
Conducted
0.15...0.50 MHz
0.5...30 MHz
Radiated
30...230 MHz
230...1000 MHz
Reference
Dielectric tests
>100 M, 500 V DC
<0.1 , 4 A, 60 s
IEC 60255-27
Description
Reference
Requirement
Class 2
Class 2
Seismic test
IEC 60255-21-3
Class 2
ABB
27
1MRS756500 H
Reference
96 h at +55C
16 h at +70C1)
IEC 60068-2-2
96 h at -25C
16 h at -40C
IEC 60068-2-1
IEC 60068-2-30
5 cycles (3 h + 3 h)
at -25C...+55C
IEC60068-2-14
Storage test
96 h at -40C
96 h at +85C
IEC 60068-2-1
IEC 60068-2-2
1)
For IEDs with an LC communication interface the maximum operating temperature is +70 o C
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2005)
EN 60255-1 (2009)
Reference
EMC directive
2004/108/EC
Standard
EN 50263 (2000)
EN 60255-26 (2007)
28
ABB
1MRS756500 H
Protection functions
Table 27. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Value
Operation accuracy
PHHPTOC
and
PHIPTOC
Typical
Maximum
16 ms
19 ms
23 ms
11 ms
12 ms
14 ms
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
2)
3)
4)
ABB
Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Includes the delay of the heavy-duty output contact
Valid for FPHLPTOC
29
1MRS756500 H
Function
Value (Range)
Step
Start Value
PHLPTOC
0.05...5.00 In
0.01
PHHPTOC
0.10...40.00 In
0.01
PHIPTOC
1.00...40.00 In
0.01
PHLPTOC
0.05...15.00
0.01
PHHPTOC
0.05...15.00
0.01
PHLPTOC
40...200000 ms
10
PHHPTOC
40...200000 ms
10
PHIPTOC
20...200000 ms
10
PHLPTOC
PHHPTOC
PHIPTOC
Definite time
Time multiplier
1)
30
ABB
1MRS756500 H
Value
Operation accuracy
Current:
1.5% of the set value or 0.002 In
Voltage:
1.5% of the set value or 0.002 Un
Phase angle: 2
DPHHPDOC
Current:
1.5% of the set value or 0.002 In
(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Voltage:
1.5% of the set value or 0.002 Un
Phase angle: 2
Start
time1)2)
IFault = 2.0 set Start value
Minimum
Typical
Maximum
39 ms
43 ms
47 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
Measurement mode and Pol quantity = default, current before fault = 0.0 I n, voltage before fault = 1.0 U n, f n = 50 Hz, fault current in one phase with nominal frequency injected from
2)
3)
4)
Function
Value (Range)
Step
Start value
DPHLPDOC
0.05...5.00 In
0.01
DPHHPDOC
0.10...40.00 In
0.01
Time multiplier
DPHxPDOC
0.05...15.00
0.01
DPHxPDOC
40...200000 ms
10
Directional mode
DPHxPDOC
1 = Non-directional
2 = Forward
3 = Reverse
Characteristic angle
DPHxPDOC
-179...180
DPHLPDOC
DPHHPDOC
1)
ABB
31
1MRS756500 H
Value
Operation accuracy
EFHPTOC
and
EFIPTOC
Typical
Maximum
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
1)
2)
3)
Measurement mode = default (depends on stage), current before fault = 0.0 I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 2.5 I n , Start value multiples in range of 1.5...20
Function
Value (Range)
Step
Start value
EFLPTOC
0.010...5.000 In
0.005
EFHPTOC
0.10...40.00 In
0.01
EFIPTOC
1.00...40.00 In
0.01
EFLPTOC
0.05...15.00
0.01
EFHPTOC
0.05...15.00
0.01
EFLPTOC
40...200000 ms
10
EFHPTOC
40...200000 ms
10
EFIPTOC
20...200000 ms
10
EFLPTOC
EFHPTOC
EFIPTOC
Definite time
Time multiplier
1)
32
ABB
1MRS756500 H
Value
Operation accuracy
Current:
1.5% of the set value or 0.002 In
Voltage
1.5% of the set value or 0.002 Un
Phase angle:
2
DEFHPDEF
Current:
1.5% of the set value or 0.002 In
(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Voltage:
1.5% of the set value or 0.002 Un
Phase angle:
2
Minimum
Typical
Maximum
42 ms
46 ms
49 ms
58 ms
62 ms
66 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
1)
Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 I n , f n = 50 Hz, earth-fault current
2)
3)
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 2.5 I n, Start value multiples in range of 1.5...20
ABB
33
1MRS756500 H
Function
Value (Range)
Step
Start Value
DEFLPDEF
0.010...5.000 In
0.005
DEFHPDEF
0.10...40.00 In
0.01
Directional mode
1 = Non-directional
2 = Forward
3 = Reverse
Time multiplier
DEFLPDEF
0.05...15.00
0.01
DEFHPDEF
0.05...15.00
0.01
DEFLPDEF
60...200000 ms
10
DEFHPDEF
40...200000 ms
10
DEFLPDEF
DEFHPDEF
1 = Phase angle
2 = IoSin
3 = IoCos
4 = Phase angle 80
5 = Phase angle 88
Operation mode
1)
Value
Operation accuracy1)
At the frequency f = fn
1.0% or 0.01 mS
(In range of 0.5...100 mS)
Start time2)
Minimum
Typical
Maximum
56 ms
60 ms
64 ms
Reset time
40 ms
Suppression of harmonics
1)
2)
34
Uo = 1.0 Un
Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.
ABB
1MRS756500 H
Function
Value (Range)
Step
EFPADM
0.01...2.00 Un
0.01
Directional mode
EFPADM
1 = Non-directional
2 = Forward
3 = Reverse
Operation mode
EFPADM
1 = Yo
2 = Go
3 = Bo
4 = Yo, Go
5 = Yo, Bo
6 = Go, Bo
7 = Yo, Go, Bo
EFPADM
60...200000 ms
10
Circle radius
EFPADM
0.05...500.00 mS
0.01
Circle conductance
EFPADM
-500.00...500.00 mS
0.01
Circle susceptance
EFPADM
-500.00...500.00 mS
0.01
Conductance forward
EFPADM
-500.00...500.00 mS
0.01
Conductance reverse
EFPADM
-500.00...500.00 mS
0.01
EFPADM
-30...30
Susceptance forward
EFPADM
-500.00...500.00 mS
0.01
Susceptance reverse
EFPADM
-500.00...500.00 mS
0.01
EFPADM
-30...30
Value
Operation accuracy
Typically 63 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Suppression of harmonics
1)
Io varied during the test. Uo = 1.0 U n = phase to earth voltage during earth-fault in compensated or un-earthed network. The residual power value before fault = 0.0 pu, f n = 50 Hz,
2)
ABB
35
1MRS756500 H
Function
Value (Range)
Step
Directional mode
WPWDE
2 = Forward
3 = Reverse
WPWDE
0.010...5.000 In
0.001
WPWDE
0.010...1.000 Un
0.001
WPWDE
0.003...1.000 Pn
0.001
Reference power
WPWDE
0.050...1.000 Pn
0.001
Characteristic angle
WPWDE
-179...180
Time multiplier
WPWDE
0.05...2.00
0.01
WPWDE
WPWDE
60...200000 ms
10
WPWDE
0.010...1.000 In
0.001
WPWDE
0.01...1.00 Un
0.01
Value
Suppression of harmonics
Function
Value (Range)
Step
Directional mode
INTRPTEF
1=Non-directional
2=Forward
3=Reverse
INTRPTEF
40...1200000 ms
10
INTRPTEF
0.01...0.50 x Un
0.01
Operation mode
INTRPTEF
1=Intermittent EF
2=Transient EF
INTRPTEF
2...20
INTRPTEF
0.01...1.00 x In
0.01
36
ABB
1MRS756500 H
Value
Operation accuracy
Typically 77 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Suppression of harmonics
-50 dB at f = fn
-3 dB at f = 13 fn
1)
Fundamental frequency current = 1.0 I n. Harmonics current before fault = 0.0 I n , harmonics fault current 2.0 Start value . Results based on statistical distribution of 1000
2)
3)
measurement.
Includes the delay of the signal output contact
Maximum Start value = 2.5 I n, Start value multiples in range of 2...20
Function
Value (Range)
Step
Start value
HAEFPTOC
0.05...5.00 In
0.01
Time multiplier
HAEFPTOC
0.05...15.00
0.01
HAEFPTOC
100...200000 ms
10
HAEFPTOC
100...200000 ms
10
HAEFPTOC
Value
Operation accuracy
Minimum
Typical
Maximum
23 ms
15 ms
26 ms
18 ms
28 ms
20ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
Negative sequence current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2)
3)
ABB
37
1MRS756500 H
Function
Value (Range)
Step
Start value
NSPTOC
0.01...5.00 In
0.01
Time multiplier
NSPTOC
0.05...15.00
0.01
NSPTOC
40...200000 ms
10
NSPTOC
1)
Value
Operation accuracy
Start time
<70 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
Function
Value (Range)
Step
PDNSPTOC
10...100%
PDNSPTOC
100...30000 ms
PDNSPTOC
0.05...0.30 In
0.01
I1)
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set Start value
Minimum
Typical
Maximum
48 ms
51 ms
54 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
Residual voltage before fault = 0.0 U n, f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
2)
measurements
Includes the delay of the signal output contact
38
ABB
1MRS756500 H
Function
Value (Range)
Step
Start value
ROVPTOV
0.010...1.000 Un
0.001
ROVPTOV
40...300000 ms
Value
Operation accuracy
Start time1)2)
UFault = 0.9 set Start value
Minimum
Typical
Maximum
62 ms
66 ms
70 ms
Reset time
Typically 40 ms
Reset ratio
Retardation time
<35 ms
Suppression of harmonics
1)
2)
3)
Start value = 1.0 Un, Voltage before fault = 1.1 U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
Function
Value (Range)
Step
Start value
PHPTUV
0.05...1.20 Un
0.01
Time multiplier
PHPTUV
0.05...15.00
0.01
PHPTUV
60...300000 ms
10
PHPTUV
1)
ABB
39
1MRS756500 H
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set Start value
Minimum
Typical
Maximum
23 ms
27 ms
31 ms
Reset time
Typically 40 ms
Reset ratio
Retardation time
<35 ms
Suppression of harmonics
1)
2)
3)
Start value = 1.0 Un, Voltage before fault = 0.9 U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 1.20 U n, Start value multiples in range of 1.10... 2.00
Function
Value (Range)
Step
Start value
PHPTOV
0.05...1.60 Un
0.01
Time multiplier
PHPTOV
0.05...15.00
0.01
PHPTOV
40...300000 ms
10
PHPTOV
type1)
Value
Operation accuracy
Start time1)2)
UFault = 0.99 set Start value
UFault = 0.9 set Start value
Minimum
Typical
Maximum
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time
Typically 40 ms
Reset ratio
Retardation time
<35 ms
Suppression of harmonics
1)
2)
40
Start value = 1.0 Un, Positive sequence voltage before fault = 1.1 U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
ABB
1MRS756500 H
Function
Value (Range)
Step
Start value
PSPTUV
0.010...1.200 Un
0.001
PSPTUV
40...120000 ms
10
PSPTUV
0.01...1.0 Un
0.01
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set Start value
UFault = 2.0 set Start value
Minimum
Typical
Maximum
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
Negative-sequence voltage before fault = 0.0 U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
2)
Function
Value (Range)
Step
Start value
NSPTOV
0.010...1.000 Un
0.001
NSPTOV
40...120000 ms
Characteristic
Operation accuracy
Start time
f>/f<
10 mHz
df/dt
f>/f<
<80 ms
df/dt
<120 ms
Reset time
<150 ms
ABB
41
1MRS756500 H
Function
Value (Range)
Step
Operation mode
FRPFRQ
1 = Freq<
2 = Freq>
3 = df/dt
4 = Freq< + df/dt
5 = Freq> + df/dt
6 = Freq< OR df/dt
7 = Freq> OR df/dt
FRPFRQ
0.9000...1.2000 fn
0.0001
FRPFRQ
0.8000...1.1000 fn
0.0001
FRPFRQ
-0.200...0.200 fn/s
0.005
Operate Tm Freq
FRPFRQ
80...200000 ms
10
Operate Tm df/dt
FRPFRQ
120...200000 ms
10
Value
Operation accuracy
Function
Value (Range)
Step
T1PTTR
-50...100C
T1PTTR
1...5
Current reference
T1PTTR
0.05...4.00 In
0.01
T1PTTR
0.0...200.0C
0.1
T1PTTR
60...60000 s
Maximum temperature
(temperature level for operate)
T1PTTR
20.0...200.0C
0.1
T1PTTR
20.0...150.0C
0.1
Reclose temperature
(Temperature for reset of block
reclose after operate)
T1PTTR
20.0...150.0C
0.1
T1PTTR
-50.0...100.0C
0.1
42
ABB
1MRS756500 H
Value
Operation accuracy
Table 62. Thermal overload for protection, two time constants (T2PTTR) main settings
Parameter
Function
Value (Range)
Step
Temperature rise
T2PTTR
0.0...200.0oC
0.1
Max temperature
T2PTTR
0.0...200.0oC
0.1
Operate temperature
T2PTTR
80.0...120.0 %
0.1
Weighting factor p
T2PTTR
0.00...1.00
0.01
T2PTTR
6...60000 s
Current reference
T2PTTR
0.05...4.00 x In
0.01
Operation
T2PTTR
Off
On
Characteristic
Signalling delay
<5 ms
<10 ms
Value
Operation accuracy
Retardation time
<20 ms
ABB
43
1MRS756500 H
Function
Value (Range)
Step
CCBRBRF
0.05...1.00 In
0.05
CCBRBRF
0.05...1.00 In
0.05
CCBRBRF
1 = Current
2 = Breaker status
3 = Both
CCBRBRF
1 = Off
2 = Without check
3 = Current check
Retrip time
CCBRBRF
0...60000 ms
10
CB failure delay
CCBRBRF
0...60000 ms
10
CB fault delay
CCBRBRF
0...60000 ms
10
Value
Operation accuracy
At the frequency f = fn
Current measurement:
1.5% of the set value or 0.002 In
Ratio I2f/I1f measurement:
5.0% of the set value
Reset time
+35 ms / -0 ms
Reset ratio
Typically 0.96
+35 ms / -0 ms
Function
Value (Range)
Step
INRPHAR
5...100%
INRPHAR
20...60000 ms
Value
Operation accuracy
Function
Value (Range)
Step
Start value
MAPGAPC
-10000.0...10000.0
0.1
MAPGAPC
0...200000 ms
100
Operation mode
MAPGAPC
Over
Under
44
ABB
1MRS756500 H
Value
Measurement accuracy
At the frequency f = fn
Impedance:
2.5% or 0.25
Distance:
2.5% or 0.16 km/0.1 mile
XC0F_CALC:
2.5% or 50
IFLT_PER_ILD:
5% or 0.05
Function
Value (Range)
Step
SCEFRFLO
1.0...10000.00
0.1
Ph leakage Ris
SCEFRFLO
20...1000000
Ph capacitive React
SCEFRFLO
10...1000000
R1 line section A
SCEFRFLO
0.000...1000.000 /pu
0.001
X1 line section A
SCEFRFLO
0.000...1000.000 /pu
0.001
R0 line section A
SCEFRFLO
0.000...1000.000 /pu
0.001
X0 line section A
SCEFRFLO
0.000...1000.000 /pu
0.001
SCEFRFLO
0.000...1000.000 pu
0.001
Value
Operation accuracy 1)
2)3)
Low stage
High stage
Minimum
Typical
Maximum
22 ms
25 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
<40 ms
1)
2)
3)
With the symmetrical communication channel (as when using dedicated fiber optic).
Without additional delay in the communication channel (as when using dedicated fiber optic).
Including the delay of the output contact. When differential current = 2 High operate value and f n = 50 Hz with galvanic pilot wire link + 5 ms.
4)
ABB
45
1MRS756500 H
Values (Range)
Unit
Description
200...4000
% In
10...200
% In
45...200000
ms
Time multiplier
0.05...15.00
10...50
CT ratio correction
0.200...5.000
Function
Value (Range)
Step
Security Level
PHIZ
1...10
System type
PHIZ
1=Grounded
2=Ungrounded
46
ABB
1MRS756500 H
Value (Range)
ABB
47
1MRS756500 H
Value
Operation accuracy
Reset ratio
48
ABB
1MRS756500 H
Control functions
Table 77. Autoreclosing (DARREC)
Characteristic
Value
ABB
49
1MRS756500 H
Supervision functions
Table 78. Current circuit supervision (CCRDIF)
Characteristic
Value
Operate time1)
<30 ms
1)
Function
Value (Range)
Step
Start value
CCRDIF
0.05...0.20 x In
0.01
CCRDIF
1.00...5.00 x In
0.01
Value
NPS function
Delta function
1)
<33 ms
<18 ms
<30 ms
<24 ms
Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Value
0.5%
1)
50
ABB
1MRS756500 H
Measurement functions
Table 82. Three-phase current measurement (CMMXU)
Characteristic
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
ABB
51
1MRS756500 H
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
10 mHz
(in measurement range 35...75 Hz)
52
ABB
1MRS756500 H
IECA070904 V3 EN
Figure 13.
apart from the default single line diagram. The SLD view can
also be accessed using the Web browser-based user
interface. The default SLD can be modified according to user
requirements by using the Graphical Display Editor in
PCM600. The user can create up to 10 SLD pages.
The local HMI includes a push button (L/R) for local/remote
operation of the IED. When the IED is in the local mode, the
IED can be operated only by using the local front panel user
interface. When the IED is in the remote mode, the IED can
execute commands sent from a remote location. The IED
supports the remote selection of local/remote mode via a
binary input. This feature facilitates, for example, the use of
an external switch at the substation to ensure that all IEDs are
in the local mode during maintenance work and that the
circuit breakers cannot be operated remotely from the
network control center.
IECA070901 V3 EN
Small display
Figure 14.
Large display
20
8 or more
1)
10
20
8 or more
1)
ABB
53
1MRS756500 H
Mounting methods:
Flush mounting
Semi-flush mounting
Semi-flush mounting in a 25 tilt
Rack mounting
Wall mounting
Mounting to a 19" equipment frame
Mounting with a RTXP 18 test switch to a 19" rack
190
6
18
164
177
230
177
177
160
160
25
1 53
48
IECA070900 V4 EN
Figure 15.
98
IECA070903 V4 EN
Flush mounting
Figure 16.
133
IECA070902 V4 EN
Semi-flush mounting
54
107
103
Figure 17.
measuring IED unit and vice versa, i.e. the IED cases are
assigned to a certain type of IED plug-in unit.
24. Selection and ordering data
Use the ABB Library to access the selection and ordering
information and to generate the order number.
ABB
1MRS756500 H
Order number
Pilot Wire communication package including two Pilot Wire modems: RPW600AM (master) and RPW600AF
(follower)
RPW600AMF
Diagnostics kit including the RPW-diagnostic tool, a diagnostic cable and a CD with necessary drivers and
information
RPW600ADP
3.0 meter LC-LC single-mode fibre-optic patch cable for connecting one Pilot Wire modem to the RED615
IED1)
1MRS120547-3
1)
Please note that two patch cables are required for connecting the Pilot Wire communication package (RPW600AMF).
Order number
1MRS050696
1MRS050697
1MRS050831
1MRS050694
1MRS050695
Mounting bracket for one IED with test switch RTXP in 4U Combiflex (RHGT 19 variant C)
2RCA022642P0001
2RCA022643P0001
19 rack mounting kit for one IED and one RTXP18 test switch (the test switch is not included in the delivery)
2RCA021952A0003
19 rack mounting kit for one IED and one RTXP24 test switch (the test switch is not included in the delivery)
2RCA022561A0003
Replacement kit for a Strmberg SP_J40 series relay (cut-out in the center of the installation plate)
2RCA027871A0001
Replacement kit for a Strmberg SP_J40 series relay (cut-out on the left or the right of the installation plate)
2RCA027874A0001
2RCA027880A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (one cut-out)
2RCA027894A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (two cut-outs)
2RCA027897A0001
2RCA027881A0001
2RCA027882A0001
2RCA027885A0001
26. Tools
The IED is delivered as a pre-configured unit. The default
parameter setting values can be changed from the front-panel
user interface, the Web browser-based user interface (Web
HMI) or the PCM600 tool in combination with the IED-specific
connectivity package.
The Protection and Control IED Manager PCM600 offers
extensive IED configuration functions such as IED signal
configuration, application configuration, graphical display
configuration including single line diagram configuration, and
IEC 61850 communication configuration including horizontal
GOOSE communication.
ABB
1MRS756500 H
Version
PCM600
2.6 or later
5.0
Web HMI
PCM600
Signal monitoring
Application configuration
Event viewing
Online monitoring
= Supported
56
download and Web HMI uses TLS encryption with 128 bit
key length protecting data in transit according FTPS and
HTTPS standards.
ABB
1MRS756500 H
GUID-FBFA9940-E37D-4C32-A083-0367AAEDE267 V2 EN
Figure 18.
ABB
57
1MRS756500 H
GUID-A05D9233-4377-48D7-9F00-4218F0E7D4DC V2 EN
Figure 19.
58
ABB
1MRS756500 H
RED615
X100
X120
1
BI 1
U aux
-
BI 2
IRF
BI 3
1
2
3
4
5
PO1
BI 4
6
7
1/5A
8
9
N
1/5A
10
11
N
1/5A
12
N
1/5A
14
6
7
2)
IL1
PO2
8
9
10
IL2
IL3
SO1
11
12
13
Io
SO2
X130
1
BI 1
2
3
5
BI 4
11
12
14
15
16
14
16
17
15
19
18
20
22
PO4
13
TCS1
BI 3
10
PO3
BI 2
6)
TCS2
60 210V
U1
N
60 210V
U2
N
60 210V
N
60 210V
18
U3
Uo
X110
X110
1
3
5
16
15
17
SO2
BI 3
19
18
20
BI 4
7
8
SO3
22
21
23
BI 5
SO4
24
BI 6
10
11
BI 7
12
BI 8
13
X1
LAN
X2
LAN
RX
TX
SO1
BI 2
X12
14
BI 1
X5
1
2
3
4
5
6
7
8
9
24
not in use
N
60 210V
17
21
23
1) 3)
1) 3)
1) 4)
GND
GNDC
IRIG-B IRIG-B +
AGND
B/- / TX
A/+
B/A/+ / RX
1) 5)
1) Optional
2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
3) 100BaseFx / LC or 100BaseTx / RJ-45
4) RS-485 serial bus
5) Fibre Optic (ST) Serial Bus
6) AIM0006 (5U+4BI)
Alternative Module AIM0003 (5U+2RTD+1mA)
X16
Line Differential Protection Communication
GUID-EE704FD2-E4A7-4745-B84D-95033D4DC5AA V1 EN
Figure 20.
ABB
59
1MRS756500 H
RED615
X100
X130
1
0,2/1A
U aux
Io
IRF
X131
4
IL1
5
7
8
9
10
U2
4
5
PO2
IL2
6
7
X132
4
PO1
U1
SO1
X133
4
11
12
13
IL3
5
7
SO2
U3
PO3
TCS1
X110
PO4
BI 1
TCS2
14
16
17
15
19
18
20
22
21
23
24
BI 2
4
5
X110
BI 3
14
SO1
BI 4
7
8
BI 5
22
21
23
BI 7
12
SO4
BI 8
13
X1
LAN
X2
LAN
RX
TX
19
18
20
SO3
11
X12
SO2
BI 6
10
X5
1
2
3
4
5
6
7
8
9
16
15
17
24
1) 3)
1) 3)
1) 4)
GND
GNDC
IRIG-B IRIG-B +
AGND
B/- / TX
A/+
B/A/+ / RX
1) 5)
1) Optional
2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
3) 100BaseFx / LC or 100BaseTx / RJ-45
4) RS-485 serial bus
5) Fibre Optic (ST) Serial Bus
X16
Line Differential Protection Communication
GUID-33733308-95B9-4B59-B5DC-E15AFA16E05E V1 EN
Figure 21.
29. Certificates
KEMA has issued an IEC 61850 Certificate Level A1 for
Relion 615 series. Certificate number: 74102147-MOC/INC
13-4263.
30. References
The www.abb.com/substationautomation portal provides
information on the entire range of distribution automation
products and services.
60
ABB
ABB
1MRS756500 H
61
1MRS756500 H
IEC 61850
IEC 60617
IEC-ANSI
PHLPTOC1
3I> (1)
51P-1 (1)
PHHPTOC1
3I>> (1)
51P-2 (1)
PHHPTOC2
3I>> (2)
51P-2 (2)
PHIPTOC1
3I>>> (1)
50P/51P (1)
DPHLPDOC1
67-1 (1)
DPHLPDOC2
67-1 (2)
DPHHPDOC1
67-2 (1)
EFLPTOC1
Io> (1)
51N-1 (1)
EFLPTOC2
Io> (2)
51N-1 (2)
EFHPTOC1
Io>> (1)
51N-2 (1)
EFIPTOC1
Io>>> (1)
50N/51N (1)
DEFLPDEF1
67N-1 (1)
DEFLPDEF2
67N-1 (2)
DEFHPDEF1
67N-2 (1)
EFPADM1
21YN (1)
EFPADM2
21YN (2)
EFPADM3
21YN (3)
WPWDE1
32N (1)
WPWDE2
32N (2)
WPWDE3
32N (3)
INTRPTEF1
67NIEF (1)
HAEFPTOC1
Io>HA (1)
51NHA (1)
EFHPTOC1
Io>> (1)
51N-2 (1)
NSPTOC1
I2> (1)
46 (1)
NSPTOC2
I2> (2)
46 (2)
PDNSPTOC1
I2/I1> (1)
46PD (1)
ROVPTOV1
Uo> (1)
59G (1)
ROVPTOV2
Uo> (2)
59G (2)
ROVPTOV3
Uo> (3)
59G (3)
PHPTUV1
3U< (1)
27 (1)
PHPTUV2
3U< (2)
27 (2)
PHPTUV3
3U< (3)
27 (3)
Protection
62
ABB
1MRS756500 H
IEC 61850
IEC 60617
IEC-ANSI
PHPTOV1
3U> (1)
59 (1)
PHPTOV2
3U> (2)
59 (2)
PHPTOV3
3U> (3)
59 (3)
PSPTUV1
U1< (1)
47U+ (1)
NSPTOV1
U2> (1)
47O- (1)
Frequency protection
FRPFRQ1
f>/f<,df/dt (1)
81 (1)
FRPFRQ2
f>/f<,df/dt (2)
81 (2)
FRPFRQ3
f>/f<,df/dt (3)
81 (3)
FRPFRQ4
f>/f<,df/dt (4)
81 (4)
T1PTTR1
3Ith>F (1)
49F (1)
T2PTTR1
3Ith>T (1)
49T (1)
BSTGGIO1
BST (1)
BST (1)
CCBRBRF1
3I>/Io>BF (1)
51BF/51NBF (1)
INRPHAR1
3I2f> (1)
68 (1)
Master trip
TRPPTRC1
94/86 (1)
TRPPTRC2
94/86 (2)
MAPGAPC1
MAP (1)
MAP (1)
MAPGAPC2
MAP (2)
MAP (2)
MAPGAPC3
MAP (3)
MAP (3)
MAPGAPC4
MAP (4)
MAP (4)
MAPGAPC5
MAP (5)
MAP (5)
MAPGAPC6
MAP (6)
MAP (6)
MAPGAPC7
MAP (7)
MAP (7)
MAPGAPC8
MAP (8)
MAP (8)
MAPGAPC9
MAP (9)
MAP (9)
MAPGAPC10
MAP (10)
MAP (10)
MAPGAPC11
MAP (11)
MAP (11)
MAPGAPC12
MAP (12)
MAP (12)
MAPGAPC13
MAP (13)
MAP (13)
MAPGAPC14
MAP (14)
MAP (14)
MAPGAPC15
MAP (15)
MAP (15)
MAPGAPC16
MAP (16)
MAP (16)
MAPGAPC17
MAP (17)
MAP (17)
MAPGAPC18
MAP (18)
MAP (18)
Fault locator
SCEFRFLO1
FLOC (1)
21FL (1)
LNPLDF1
3Id/I> (1)
87L (1)
Multi-purpose protection2)
ABB
63
1MRS756500 H
IEC 61850
IEC 60617
IEC-ANSI
PHIZ1
HIF (1)
HIZ (1)
CMHAI1
PQM3I (1)
PQM3I (1)
VMHAI1
PQM3U (1)
PQM3V (1)
Voltage variation
PHQVVR1
PQMU (1)
PQMV (1)
Circuit-breaker control
CBXCBR1
I <-> O CB (1)
I <-> O CB (1)
Disconnector control
DCXSWI1
DCXSWI2
ESXSWI1
DCSXSWI1
I <-> O DC (1)
I <-> O DC (1)
DCSXSWI2
I <-> O DC (2)
I <-> O DC (2)
DCSXSWI3
I <-> O DC (3)
I <-> O DC (3)
ESSXSWI1
I <-> O ES (1)
I <-> O ES (1)
ESSXSWI2
I <-> O ES (2)
I <-> O ES (2)
DARREC1
O -> I (1)
79 (1)
SSCBR1
CBCM (1)
CBCM (1)
TCSSCBR1
TCS (1)
TCM (1)
TCSSCBR2
TCS (2)
TCM (2)
CCRDIF1
MCS 3I (1)
MCS 3I (1)
SEQRFUF1
FUSEF (1)
60 (1)
PCSRTPC1
PCS (1)
PCS (1)
MDSOPT1
OPTS (1)
OPTM (1)
Disturbance recorder
RDRE1
DR (1)
DFR (1)
LDPMSTA1
LOADPROF (1)
LOADPROF (1)
CMMXU1
3I (1)
3I (1)
CSMSQI1
RESCMMXU1
Io (1)
In (1)
VMMXU1
3U (1)
3V (1)
RESVMMXU1
Uo (1)
Vn (1)
VSMSQI1
PEMMXU1
P, E (1)
P, E (1)
RTD/mA measurement
XRGGIO130
Frequency measurement
FMMXU1
f (1)
f (1)
Power quality
Control
Auto-reclosing
Condition monitoring
Measurement
1)
2)
64
One of the following can be ordered as an option: Admittance based E/F, Wattmetric based E/F or Harmonics based E/F. The option is an addition to the existing E/F of the original
configuration. The optional E/F has also a predefined configuration in the IED. The optional E/F can be set on or off.
For example, used for RTD/mA based protection or analog GOOSE
ABB
1MRS756500 H
Product version
History
A/2008-10-03
1.1
First release
B/2009-07-03
2.0
C/2010-06-11
3.0
D/2010-06-29
3.0
Terminology updated
E/2010-09-07
3.0
Content updated
F/2012-05-11
4.0
G/2013-02-21
4.0 FP1
H/2014-01-24
5.0
ABB
65
66
ABB Oy
Medium Voltage Products,
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
Fax
+358 10 22 41094
ABB Limited
Distribution Automation
Maneja
Vadodara 390013, India
Phone
+91 265 2604032
Fax
+91 265 2638922
www.abb.com/substationautomation
Contact us