PENDING PUNCH POINTS FOR 765 kV SWITCHYARD

Sl.
No.
1
Indore Dia

Punch Point Description

Sump pit height should be increased according to the yard level. Their cover also
need to be placed.
Cable trench covers with lifting lugs shall be placed at interval of 10 cover slabs.
Excavated material from earthing activity on side parallel to boundary wall should be
cleaned and dumped outside the fence area.
Increase of turning radius at 3.75 meter road near reactor-1 (Spare indore dia).

Bus Reactor Dia


Bus reactor dia main drain D48 is balance 150 meters

Kiosk No. 2
JB cutouts & switchboard are not properly fitted, need to repair.

Kiosk No. 3
JB cutouts & switchboard are not properly fitted, need to repair.

Transformer Area
ICT 1 rail cum road rail is settle down from its PL level, need to reconstruct.

Reactor Area
Reactor 1 pheriphery wall height shall be increased as per site level conditions.

Common Points
Area levelling and proper slope for smooth drainage of rain water from switchyard to
pheriphery drains balance.
Wheel roller fixing and painting balance for five nos switchyard fencing gates.

New Points
Damaged Drain parallel to Indore dia needed to be repaired.
Damaged Drain parallel to Bus reactor dia needed to be repaired.
Damaged Drain behind ICT's and towards Store side needed to be repaired.

PENDING PUNCH POINTS FOR CONTROL ROOM

BUILDING
Sl.
No
.
1

Punch Point Description


Control Room
Cut out for cable from panel room to scada room shall be sealed properly to prevent
entry of mouse.

Electrical storage room


Cut out for switchboard left uncovered
Replacement of hatch bolt and door handle with approved quality and fixing of body
lock at door.

LT Panel Room
JB cutouts in the ceiling are uncovered.

Battery Room
Skirting top not filled with white cement properly.
JB cutouts in the ceiling are uncovered.
Replacement of hatch bolt and door handle with approved quality and fixing of body
lock at door.

Passage Ground Floor


2 nos. light fitting in false ceiling are not as per the approved specifications. Those
shall be replaced.

Oil Test Lab


Plaster work remaining.
Painting remaining.
Exhaust fan installation is balance.
Door fixing balance.
Replacement of hatch bolt and door handle with approved quality and fixing of body
lock at door.

Electrical Test lab


JB cutouts in the ceiling and walls are uncovered.

Reception Area
Door not opening properly and cleaning of door frame is required.
Replacement of hatch bolt and door handle with approved quality and fixing of body
lock at door.

Stair Case
Point on wall where the hand rail is fixed shall be repaired and fixed.
JB cutouts in the ceiling and walls are uncovered.

10

NT Panel Room
JB cutouts in the ceiling and walls are uncovered.

11

Station In charge Room


DC light fixing balance

12

Pantry
Big JB cutouts in the ceiling and walls shall be covered
One power socket is required nearby slab.
Exhaust fan installation required

13

First Floor Toilet


Lids of all WC's are local made and not sitting properly, needs to be changed.

JB cutouts in the ceiling and walls are uncovered.


Fixing of approved quality hatch bolts, handle and locks at doors where they are not
fixed.
No automatic flushing sensor in urinals for automatic flushing after use.
No liquid soap dispenser in toilets.
No geyser in bathing space.

14

Common points for CRB


Five/Three coat paint of anti-fungal paint shall be painted over primer which is not
done properly.

15

New Points
Leakage from false Ceiling of conference room, SCADA room.
Leakage from side walls in the stair case area.
Replacement of dirty fiber door glass of Auxiliary Panel in the NT Panel room.

PENDING PUNCH POINTS FOR 400 kV SWITCHYARD


Sl.
No
.
1
2
3
4
5
6
7
8
9
10

Punch Point Description


2 nos. fence gate installation near reactor and SPR in 400 kV Switchyard is
balance
Road balance 70 mtr in 400 kV Switchyard.
Cleaning of all cable trenches balance.
Stairs to be constructed in front of all CB ladders to access smoothly to CB ladder
Gravel spreading done 100 mm thick, 150 mm is required as per technical
specification/CEA requirement. Additional 50 mm later to be spread over the
switchyard.
Steel stairs in front of SPR 4 & 5 main door not yet provided.
Provide wire net inside the cable trench of SPR 4 & 5 to prevent snake & frogs
entering the false flooring.
Switch board wall & crack below beam to be repaired.
Door closer for SPR 4 & 5 need to be installed
Construction of rain water harvesting pit and connection of 400 kV Switchyard
drain with pit are balance.