Cable Sizing of Sub-Main Circuits, Working Examples
Cable Sizing of Sub-Main Circuits, Working Examples
Cable Sizing of Sub-Main Circuits, Working Examples
Cable Sizi
P = 3 UL I1 cos
Therefore,
Table 4.2A and 4.2B in the Code provide a quick initial assessment of cable size required for the common
cable types and installation methods used in Hong Kong for this example.
The tabulated current rating of the selected cable could then be corrected by applying the correction factors
accordingly. The effective-current carrying capacity of the selected cable must be checked so that its value
is larger than or equal to the nominal rating of the circuit protective device.
Case #1
Undistorted balanced condition using conventional method:
Ib = 100A
In = 100A
It(min) = 100A
Assume the correction factors Ca, Cp, Cg and Ci are all unity.
(Pcu)
= 1.02kW (1.82%)
(Cable size selected is not acceptable if the maximum allowable
copper loss is 1.5%)
Case #2
Undistorted balanced condition with a maximum copper loss of 1.5%
(cos = 0.85)
Maximum copper loss method using Table 4.2A in the Code for initial assessment of an approximate
conductor size required by calculating the max. conductor resistance at 1.5% power loss:
From Table 4.2A 35 mm2 4/C PVC/SWA/PVC cable having a conductor resistance of 0.625m/m is
required. Refer to BS7671:2008, The Requirements for Electrical Installations:
Table 4D4A for 35mm2 4/C PVC/SWA/PVC cable It = 135A
Table 4D4B for r = 1.1mV/A/m x = 0.145mV/A/m
Conductor operating temperature
52C to 70C
Voltage drop
conductors (Pcu)
= 716kW (1.28%)
(Cable size selected is acceptable, i.e. power loss < 1.5%, under
undistorted and balanced conditions)
RELATED TABLES //
TABLE 4.2A
Multicore Armoured and Non-armoured Cables (Copper Conductor), Conductor Resistance at 50 Hz
Single-phase or Three-phase a.c.
Multicore
TABLE 4.2B
Single-core PVC/XLPE Non-armoured Cables, with or without sheath (Copper Conductor), Conductor
Resistance at 50 Hz Single-phase or Three-phase a.c.
TABLE 4.2B
Single-core PVC/XLPE Non-armoured Cables, with or without sheath (Copper
Conductor), Conductor Resistance at 50 Hz Single-phase or Three-phase a.c.
TABLE 4D4A
Multicore armoured 70C thermoplastic insulated cable
TABLE 4D4B
Voltage drop (per ampere per-metre)