Meiden Vt240 Circuits
Circuit diagram
Terminal functions
S equence
input
S ymbol
022L075L, 037H~132H install (optional)
018L or below, 022H or below
(standard)
Dynamic brake circuit
DC rector
VT240S
B
L+1
Analog input
MCCB AC reactor
ACL
L1
L2
Motor
M (Note 4)
EMI filter
L3
L(Note 5)
Analog output
Power
supply
+15V
AI1
11k
510
10k
R J connector
COM
Analog input:
AI1, AI2
Changeable to voltage
signal or current signal
Voltage signal Max.
10VDC Current signal
Max. 20mADC
AI3 Max. 10VDC
Terminal functions
changeable in any case
0V
AI2
11k
510
10k
DATA
0VOP
5VOP
5VOP
S erial communication
(R S -422/485)
S imultaneous use of
connectors and terminal
boards prohibited
Emergency stop
R eset signal
R everse run
Forwardinching
Reverse inching
PS I2
PS I3
PS I4
PS I5
AO1
0V
COM
R Y0
(Note 1)
AO2
(Note 1)
R Y24V
0V
COM
RA
S ync/S ource
changeover enabled
S ync
RY
R Y24V
RY
4.7k
R un
RC
FA
Fault
FB
FC
S ource
4. 7k
PS I6
PS I7
These are the COMMONterminals for PSI1PSI7. A changeover is possible betweenSync andSource Logic.
These commands canbe freely appliedtothe input signal circuit of the control block by virtue of internal input selection
setup. Achangeover is possible betweena voltage settingsignal of 0~10V anda current settingsignal of 0~20mA.
Programmable analoginput
This commandcanbe freely applied tothe input signal circuit of the control block by virtue of internal input selectionsetup.
It canbe usedas a voltage settingsignal inthe range of -10V+10V.
AI3
COM
Analoginput common
P10
This is a power supply terminal when a setter is connected for analog inputs. The setter tobe usedis a variable resistor of
2W2k.
AO1, 2
Programmable analogoutput
virtue of internal output selection setup. A changeover is possible between a voltage output signal of 0~10V and a current
output signal of 4~20mA.
COM
Analogoutput common
These are sequence outputs generated by relays. These outputs can be freely applied to the output signal circuit of the
control block by virtue of internal sequence output selectionsetup.
These are output signals for meters. These outputs canbe freely applied tothe output signal circuit of the control block by
FC, FA, FB
(1a contact)
Programmable sequence output
(1c contact)
These are sequence outputs generated by relays. These outputs can be freely applied to the output signal circuit of the
control block by virtue of internal sequence output selectionsetup.
PS O1
PS O3
(opencollector)
These are sequence outputs generated through open collectors. These outputs can be freely applied to the output signal
circuit of the control block by virtue of internal sequence output selectionsetup. PSO3 is usedfor pulse traininputs.
PS OE
0VOP
20k
R Y24
PS I1
DATA
20k
Forward run
PS O1
R eady 1
PS O2
Current detect
PS O3
R Y0V
R Y0V
(note 2)
Notes:
1. The COM terminal is internally connected.
2. R Y0, 0VOP, and COM are insulated. No connections for them.
3. This is an example of connections for sync logic.
4. An encoder is needed for sensor-attached vector control and sensor-attached PM motor control.
5. L- terminal is not available on type : 015L, 018L, 018H, 022H
11
DATA+
COM
S equence input:
DC
PS I7 changeable to pulse
inputs
Terminal functions
changeable in any case
0VOP
0V
AI3
5mA
(Note 1)
DATA+
S equence output
2k
2W
Terminating resistor
750
R Y0, R Y24
R C, R A
These commands can be freely applied to the input signal circuit of the control block by virtue of internal sequence input
selectionsetup. PSI7 is usedfor pulse traininputs.
AI1, 2
S eparate
EMI filter
Function
L+2
Name
PS I1PS I7
PS OE
Analog output:
Changeable to 0~10V or
4~20mA 0~10V Max. 1mA
4~20mA Max. 500
Terminal functions
changeable in any case
S equence output
(open collector output)
Max. 30V DC 50mA
PS O3 changeable to pulse
outputs
Speedattained Terminal functions changeable
in any case
Pulse
Settingrange Code train
Speedsetup1, 2, 3
0100
Interlockedratiobias setup
0100
0100
PIDfeedback
0100
Torque setup
0300
Functions
This functionis usedtoset upthe frequency (revolvingspeed). Speedsetup1, 2, 3 canbe selectedby
Control mode
V/f VEC PM
0100
Usedtoreduce the limit value beingmultipliedby the settingvalue of the drivingtorque limiter.
0100
Usedtoreduce the limit value beingmultipliedby the settingvalue of the regenerative torque limiter.
0300
0100
Added to speed AMP output for ASR operation or to torque setup for ACR operation. This function
becomes effective whenTorque Bias Setup1 (TRQB1) is turnedONby a sequence input.
This functionis usedfor torque bias settingwhenauto-torque bias selection(B16-0) is set at analog.
12