5505 RTD Analog Input Module: Hardware Manual
5505 RTD Analog Input Module: Hardware Manual
5505 RTD Analog Input Module: Hardware Manual
Hardware Manual
CONTROL
MICROSYSTEMS
SCADA products... for the distance
48 Steacie Drive Telephone: 613-591-1943
Kanata, Ontario Facsimile: 613-591-1022
K2K 2A9 Technical Support: 888-226-6876
Canada 888-2CONTROL
5505 RTD Analog Input Module - Hardware Manual
©2000 - 2005 Control Microsystems Inc.
All rights reserved.
Printed in Canada.
Trademarks
TeleSAFE, TelePACE, SmartWIRE, SCADAPack, TeleSAFE Micro16 and
TeleBUS are registered trademarks of Control Microsystems Inc.
All other product names are copyright and registered trademarks or trade names
of their respective owners.
Material used in the User and Reference manual section titled SCADAServer
OLE Automation Reference is distributed under license from the OPC
Foundation.
1 OVERVIEW .................................................................................................... 4
3 INSTALLATION ............................................................................................. 6
3.1 Field Wiring .................................................................................................... 6
3.2 DIP Switch Settings........................................................................................ 7
3.2.1 Address Selection ..................................................................................... 7
3.2.2 5503 Emulation Range Selection ............................................................. 8
3.2.3 5503 Emulation Mode Switch ................................................................... 9
5 SPECIFICATIONS ....................................................................................... 14
5.1 General ........................................................................................................ 14
5.2 RTD Inputs ................................................................................................... 14
5.3 Power Supply ............................................................................................... 15
Index of Figures
Figure 1: Typical 5505 RTD Field Wiring ............................................................................ 7
Figure 2: 5505 Analog Input Module Address Switches ...................................................... 8
Figure 3: 5503 Emulation Module RTD Range Switches ..................................................... 9
WARNING !
EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY
IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2.
WARNING !
EXPLOSION HAZARD – WHEN IN HAZARDOUS LOCATIONS, TURN
OFF POWER BEFORE REPLACING OR WIRING MODULES.
WARNING !
EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT
UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS
KNOWN TO BE NONHAZARDOUS.
8 7 6 5 4 3 2 1 P4
I– S– I/S+ I+ I– S– I/S+ I+
RTD3 RTD2
4-wire RTD shown on
inputs 0 and 3.
P3 1 2 3 4 5 6 7 8 9 10
+
11-30V Supply
–
RTD0 RTD1
1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 2
4 4 4 4 4 4 4 4
8 8 8 8 8 8 8 8
1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 2
4 4 4 4 4 4 4 4
8 8 8 8 8 8 8 8
How to Set Address Switches Slide the actuator Slide the actuator
Determine the module left to ignore right to add the
switch value. switch value.
address.
Slide the switch actuators to
the position shown in gray
above.
Figure 3: 5503 Emulation Module RTD Range Switches shows the switch settings for the six
possible ranges.
0 0 0 0 0 0
1 1 1 1 1 1
2 2 2 2 2 2
EMU EMU EMU EMU EMU EMU
5503
5505 Emulation
Mode Mode
EMU EMU
4.1.3 Status
The 5505 module Input Status Registers return the following data.
RTD open or good
RTD is in or out of range
RTD is using a 3-wire or 4-wire measurement.
When the Compatibility Mode Switch is set to 5503 the Status registers are not available
Status Function
Register
0 0 = channel 0 RTD is good
1 = channel 0 RTD is open or PWR input is off
1 0 = channel 0 data is in range
1 = channel 0 data is out of range
2 0 = channel 0 RTD is using 3-wire measurement
1 = channel 0 RTD is using 4-wire measurement
3 Not used.
4 0 = channel 1 RTD is good
1 = channel 1 RTD is open or PWR input is off
5 0 = channel 1 data is in range
1 = channel 1 data is out of range
6 0 = channel 1 RTD is using 3-wire measurement
1 = channel 1 RTD is using 4-wire measurement
7 Not used.
8 0 = channel 2 RTD is good
1 = channel 2 RTD is open or PWR input is off
9 0 = channel 2 data is in range
1 = channel 2 data is out of range
10 0 = channel 2 RTD is using 3-wire measurement
1 = channel 2 RTD is using 4-wire measurement
11 Not used.
12 0 = channel 3 RTD is good
1 = channel 3 RTD is open or PWR input is off
13 0 = channel 3 data is in range
4.3 Maintenance
This module requires no routine maintenance. If the module is not functioning correctly, contact
Control Microsystems Technical Support for more information and instructions for returning the
module for repair.
4.4 Troubleshooting
Problem Action
Inputs always read 0. Check power.
Check range.
Inputs always read 32767. Check for open RTD.
Check range.
Reading is constant. Check that the analog input
Refer to the Status Registers for additional information when diagnosing problems.
4.5 Calibration
The 5505 module is calibrated at the factory. It does not require periodic calibration. Calibration
may be necessary if the module has been repaired as a result of damage. Calibration is done
electronically at the factory. There are no user calibration procedures.
5.1 General
I/O Terminations 12 to 22 AWG
15A contacts
Dimensions 2.9 inch (74 mm) wide
4.9 inch (124 mm) high
1.8 inch (45 mm) deep
Packaging corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing
o o o o
–40 C to 70 C (–40 F to 158 F) operation
o o o o
–40 C to 85 C (–40 F to 185 F) storage
Addressing 16 modules. DIP switch selectable.