User Manual Thermbox Lot5

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 26

ECM1500 Outdoor Cabinet

User Manual

Version
Revision date
BOM

V1.0
May 31, 2012
customization

Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.

Copyright 2009 by Emerson Network Power Co., Ltd.


All rights reserved. The contents in this document are subject to change without notice.

Emerson Network Power Co., Ltd.


Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
E-mail: support@emersonnetwork.com.cn

Safety Precautions
To reduce the chance of accident, please read the safety precautions very carefully before operation. The
"Caution, Note, Warning, Danger" in this book and on the product do not represent all the safety points to be
observed, and are only supplement to various safety points. Therefore, the installation and operation personnel
must receive strict training and master the correct operations and all the safety points before operation.
When operating Emerson products, the operation personnel must observe the safety rules in the industry, the
general safety points and special safety instructions specified in this book.
If you purchase an outdoor power supply without SPD, you should install an SPD at the front-end of AC input,
otherwise, the power supply system will generate over-voltage.

Electrical Safety
I. Hazardous voltage

Danger
Danger
Some components of the outdoor cabinet system carry hazardous voltage in operation. Direct contact or indirect contact
through moist objects with these components will result in fatal injury.
Observe safety rules in the industry when installing the power supply system. The installation personnel must be
licensed to operate high voltage and AC power.
In operation, the installation personnel are not allowed to wear conductive objects, such as watches, bracelets,
bangles and rings.
When you spot the cabinet with water or moisture, turn off the power immediately. In moist environment,
precautions must be taken to keep moisture out of the power supply system.
"Prohibit" warning label must be attached to the switches and buttons that are not permitted to operate during
installation.

Danger
Danger
High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance
with the local rules and regulations. Only those who are licensed to operate high voltage and AC power can perform high
voltage operations.

Danger
Danger
To avoid electric shock hazard for outdoor environment and outdoor equipment, the non-professionals are prohibited to
operate or maintain the outdoor power supply system.
II. Tools

Warning
In high voltage and AC operation, specialized tools must be used.

III. Thunderstorm

Danger
Danger
Never operate on high voltage, AC, iron tower or mast in the thunderstorm.
In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be
well earthed in time to avoid damage by lightning strikes.
IV. ESD

Note
The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale
ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from
damaging the sensitive components. The other end of the ESD wrist strap must be well earthed.
V. Short circuit

Danger
Danger
During operation, never short the positive and negative poles of the DC distribution unit of the outdoor cabinet system, or
the non-earth pole of the outdoor cabinet system and the earth. The power supply system is a constant-voltage DC power
device, short circuit will result in equipment burning and endanger human safety.
VI. Reverse connection

Warning
Never reverse-connect the AC input live line and neutral line, or else the system will be damaged.
Check the polarity of the cable and connection terminal when performing DC live operations.
As the operation space in the DC distribution unit is very tight, please carefully select the operation space.
Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.
Use insulated tools.
In live operation, keep the arm, wrist and hand tense, so that when the tool in operation slips, the movement of
the human body and tool is reduced to a minimum.

Battery
Danger
Danger
Before any operation on battery, read carefully the safety precautions for battery transportation and the correct battery
connection method.

Warning
If customers prepare batteries themselves, the battery installation and maintenance should meet relevant safety standards.

Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent
battery short circuit and overflow of electrolyte. The overflow of electrolyte will erode the metal objects and
PCBs, thus causing equipment damage and short circuit of PCBs.
Before any operation on battery, pay attention to the following points:
1. Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist.
2. Use specialized insulated tools.
3. Use eye protection device, and take preventive measures.
4. Wear rubber gloves and apron to guard against electrolyte overflow.
5. In battery transportation, the electrode of the battery should always be kept facing upward. Never put the
battery upside down or slanted.

Connection And Testing Of The Outdoor Cabinet


Before installing subrack power supply in the cabinet, you should finish the connection and testing of the
subrack power supply according to the corresponding subrack power supply user manual and then testing the
outdoor cabinet.

Others
I. Sharp object

Warning
When moving equipment by hand, wear protective gloves to avoid injury by sharp object.
II. Power cable

Note
Notice
Warning
Please verify the cable labels before connection.
III. Signal cables

Note
Notice
Warning
The signal cables should be routed at least 150mm away from power cables.

Contents
Chapter 1 Overview.............................................................................................................................................................. 1
1.1 Model Description................................................................................................................................................... 1
1.2 Composition & Configuration.................................................................................................................................. 1
1.3 Operating Theory.................................................................................................................................................... 3
1.4 Features................................................................................................................................................................. 4
Chapter 2 Installation............................................................................................................................................................ 5
2.1 Safety Regulations................................................................................................................................................. 5
2.2 Installation Preparation........................................................................................................................................... 5
2.3 Mechanical Installation........................................................................................................................................... 6
2.3.1 Installing The Outdoor Cabinet.................................................................................................................... 6
2.3.2 Opening And Closing Cabinet Door............................................................................................................7
2.4 Electrical Installation............................................................................................................................................... 8
2.4.1 Connecting Power Cables........................................................................................................................... 8
2.4.2 Connecting Signal Cables......................................................................................................................... 10
2.4.3 Sealing The Entry Holes............................................................................................................................ 10
2.5 Battery Installation................................................................................................................................................ 10
2.6 Installation Check.................................................................................................................................................. 11
Chapter 3 Testing................................................................................................................................................................ 12
3.1 Startup.................................................................................................................................................................. 12
3.2 Alarm Check And System Operation Status Check..............................................................................................12
3.3 Final Steps............................................................................................................................................................ 12
Chapter 4 Maintenance....................................................................................................................................................... 13
4.1 Routine Maintenance............................................................................................................................................ 13
4.2 Replacing Parts Of Outdoor Cabinet.................................................................................................................... 14
4.2.1 Replacing Environment Climate Control Unit............................................................................................14
4.2.2 Replacing Fans......................................................................................................................................... 15
4.2.3 Replacing Door Status Sensor.................................................................................................................. 16
4.2.4 Replacing TEC.......................................................................................................................................... 17
Appendix 1 Technical And Engineering Parameters...........................................................................................................18
Appendix 2 Schematic Diagram.......................................................................................................................................... 19

Chapter 1 Overview
ECM1500 outdoor cabinet (outdoor cabinet for short) is a power supply system used outdoors. It provides outdoor
protection and operation environment. It contains thermal control units and AC power distribution units. The cabinet
can accommodate different Emerson subrack power supplies according to your requirement so as to form power
supply systems with different capacities.
This chapter introduces the model description, composition & configuration, operating theory and features of the
outdoor cabinet.

1.1 Model Description


The outdoor cabinet is available in three models, configured with different models of thermal control unit (forced
ventilation, heat exchanger and air-condition). Taking the forced ventilation model for example, the model description
of the outdoor cabinet is given in Figure 1.1.
EC

1500

F 1 - 48

300
Internal power capacity: 300A, 150A, 120A
Internal power voltage:48Vdc
Version No.
Thermal control method: F (forced ventilation), H (heat exchanger), A (air-condition)
Maximum heat productivity in cabinet:1500W
Application: mobile network integrated cabinet
Emerson outdoor cabinet
Figure 1.1 Model description

1.2 Composition & Configuration


Composition
The outdoor cabinet is composed of thermal control units, power distribution units and related structures. Three
models of thermal control units are available: forced ventilation, heat exchanger and air-condition.
Configuration
1. The configuration of the outdoor cabinet for the order is given in Table 1.1.
Table 1.1 Configuration list of outdoor cabinet
Component
Fan
Thermal control Environment climate
unit
control unit
air-condition

Power
distribution unit

AC power distribution

DC power distribution
Power and reserved space
Door status sensor

Configuration
4 pieces
1 piece
1 piece TEC
Two route 63A three-phase AC input MCB
Electrical plug connector 32A/380V, 3ph+N+PE for Genset
Three route 32/1ph AC output MCB
One route 25A single-phase AC input MCB for heater
Residual current circuit breaker 16A with Euro-socket ~220V
Two route 10A DC input MCB for TEC and fan
Three route 32/1ph MCB for DC system
Sharing space: 15U, you can adjust space according to requirement
1 piece

Chapter 1 Overview
The structure of the forced ventilation model outdoor cabinet is shown in Figure 1.1.

Figure 1.1 Structure of the forced ventilation model outdoor cabinet

ECM1500 Outdoor Cabinet User Manual

Chapter 1 Overview

1.3 Operating Theory


Heat dissipation theory for forced ventilation model outdoor cabinet
The cold air is sucked in through the front door air filter at the lower part of the outdoor cabinet. It passes through the
battery compartment, user equipment and subrack power supply in turn. Finally, the hot air is discharged by the fans
at the top of the outdoor cabinet. In this way, the equipment and power modules in the cabinet are cooled, as shown
in Figure 1.1.

Figure 1.1 Heat dissipation access for forced ventilation model outdoor cabinet

Heat dissipation theory for heat exchanger model outdoor cabinet


A heat exchanger is fitted on the door of the outdoor cabinet. It can exchange the heat between the cold air outside
the cabinet and the hot air inside the cabinet. In this way, the equipment and power modules in the cabinet are
cooled, as shown in Figure 1.1.

Internal circulation air


inlet of heat exchanger

Internal circulation air


outlet of heat exchanger

Figure 1.1 Heat dissipation theory for heat exchanger model outdoor cabinet

ECM1500 Outdoor Cabinet User Manual

Chapter 1 Overview
Heat dissipation theory for air-condition model outdoor cabinet
An outdoor air-conditioner is fitted on the door of the outdoor cabinet to cool the cabinet. It is in this that the
equipment and power modules in the cabinet are cooled. In case of air-conditioner fault or AC mains failure, the
emergent ventilation units automatically startup to dissipate heat emergently, as shown in Figure 1.1.
Top emergent ventilation fan

Return air inlet of air-condition

Outdoor air-condition

Air outlet of air-condition

Figure 1.1 Heat dissipation theory for air-condition model outdoor cabinet

1.4 Features
Variable subrack power supply: The outdoor cabinet can accommodate standard 19 and 23 subrack power
supply.
Variable space: The power space, reserved space and the battery compartment space are interchangeable.
You can adjust the space according to the actual requirement.
Thermal control unit: Three different models are available for your selection according to the local, environment
and requirement.
Safety guideline: The equipment compartment satisfies IP*5 waterproof requirement and IP5* dustproof
requirement.
Environment pollution level within the outdoor cabinets is 2.

ECM1500 Outdoor Cabinet User Manual

Chapter 2 Installation

Chapter 2 Installation
This chapter introduces installation and cable connection. Strictly follow the instructions provided in this chapter to
carry out the installation and cable connection.

2.1 Safety Regulations


Certain components in this power supply system have hazardous voltage and current. To ensure personnel safety,
always follow the instructions below:
1. Only the trained personnel with adequate knowledge of the outdoor cabinet shall carry out the installation. The
Safety Precautions listed before the Contents of this manual and local safety rules in force shall be adhered to during
installation.
2. All external circuits below -48V connected to the power supply system must comply with the SELV requirement
defined in IEC 60950.
3. To avoid electric shock, do not conduct any operation or maintenance within the outdoor cabinet under
thunderstorm or humid weather.
4. Make sure that the outdoor cabinet is powered off before any operations can be carried out within the cabinet.
5. The power cables should be routed and protected properly, so that the cables are kept away from the operation
and maintenance personnel.

2.2 Installation Preparation


Unpacking inspection
The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done
by representatives of both the user and Emerson Network Power Co., Ltd.
To inspect the equipment, you should open the packing case, take out the packing list and check against the packing
list that the equipment is correct and complete. Make sure that the equipment is delivered intact.
Preparing tools
The installation tools are given in Table 1.1. The tools must be insulated and ESD-proof processed before they are
used.
Table 1.1 Installation tools
Tool
Combination wrench (hatch,
club)
Adjustable wrench
Electrician diagonal pliers
Electrician sharp nose pliers

Specification
Wrench set (10#, 13#, 16#,
18#, 21#)
200mm
150mm
150mm

Tool

Steel tape

5m

Electric knife

Normal type

Digital multimeter

Gradienter
Blinkers

Normal type
To prevent splash

Impact electric drill


Power socket

Fireproof mud

Configured in the accessories

Safety shoes

Specification

Box wrench

16mm

Cross screwdriver
Slotted screwdriver
Wire cutters
Hydraulic-pressure compaction
pincher

100mm, 200mm
100mm, 200mm
Maximum 300mm2

Hammer

ECM1500 Outdoor Cabinet User Manual

Maximum 300mm2
Three and a half bit digital
display
With 14 impact aiguille
With 5m cable
To prevent puncture and for
insulation

Chapter 2 Installation

2.3 Mechanical Installation


2.3.1 Installing The Outdoor Cabinet
The outdoor cabinet must be installed directly onto the cement floor.
Step 1: Mark the specific installation position of the outdoor cabinet
It is recommended to determine the installation position in compliance with the clearance requirements given in Table
1.1.
Table 1.1 Installation clearances
Clearances

Front
750mm

Top
700mm

Left
100mm

Right
100mm

Back
100mm

Step 2: Install expansion bolts


For forced ventilation model outdoor cabinet, by referring to Figure 1.1; for heat exchanger model and air-condition
model outdoor cabinet, by referring to Figure 1.2, it is recommended to enlarge the installation size of the cabinet
base because of the existence of the anti-toppling device (see Figure 1.3), determine the exact central points of the
installation holes on the floor, and mark them with a pencil or oil pen. Use the electric drill (aiguille: 14) to dig holes
(depth: 70mm) at the marked points. Clean the drilled holes off dust. Put the expansion bolts into the holes and knock
them with a hammer till they are totally in.

Figure 1.1 Installation size 1 of the cabinet base (unit: mm)

Figure 1.2 Installation size 2 of the cabinet base (unit: mm)

Step 3: Fix the cabinet


ECM1500 Outdoor Cabinet User Manual

Chapter 2 Installation
Move the cabinet to the installation position. Make the installation holes on the base coincide with those dug on the
floor. Screw the M10 anchor bolt down into the expansion pipe in the floor.
Pay attention to move the cabinet from the pallet in factory and install the anti-toppling device, as shown in Figure
1.3.
After installation, the cabinet should stand firmly no matter how it is shaken, then you can remove the anti-toppling
device from the inside of the cabinet.

Anti-toppling device

Figure 1.3 Anti-toppling device

2.3.2 Opening And Closing Cabinet Door


You need to open and close the cabinet door during the cabinet installation, operation and maintenance. Procedures
for opening and closing the cabinet door are as follows:
Step 1: Insert the key into the keyhole, and turn the key clockwise until the door handle pops out.
Step 2: Turn the handle counter-clockwise 90, as shown in Figure 1.1. Pull the handle until the door opens.

90

Figure 1.1 Turning the handle

ECM1500 Outdoor Cabinet User Manual

Chapter 2 Installation
Step 3: Adjust the door stay bar to the position shown in Figure 1.2 to prevent the door from closing automatically.

Figure 1.2 Door stay bar

Step 4: Restore the door stay bar to its original position and close the door. Finally, turn the handle to its original
position and press it down until a click is heard.

2.4 Electrical Installation


All the cables must be put through metal pipes for protection. The metal pipe should be connected to the PE bar
reliably. Plastic coated metal hoses are recommended.
Earth cable and AC input cables enter the cabinet through the right side of the cabinet bottom. Signal cables, user
equipment cables and DC cables enter the cabinet through the left side of the cabinet bottom.

2.4.1 Connecting Power Cables


Connecting earth cable
Step 1: Cut the cable bushings covering the cabling holes (shown in Figure 1.1) on the bottom plate of the cabinet
with an electrician knife.
Step 2: Lead the earth cable into the cabinet through a cabling hole, and route it along the cable holders, as shown in
Figure 1.1.
Step 3: Connect one end of the earth cable to the earth terminal in the cabinet, and solder the other end to the earth
metal base reliably.

ECM1500 Outdoor Cabinet User Manual

Chapter 2 Installation

Step 4: Use nylon cable ties to tie the earth cable to the cable holders.

AC Input

Earth terminal

Cabling hole

Figure 1.1 Positions of earth terminal and cabling hole

Connecting AC input cables


If the outdoor cabinet has been installed Emerson matched subrack before delivery, the AC cable connection
between subrack and cabinet should have been done by Emerson. You only need to connect the AC input cables
according to the subrack user manual.
If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 220V AC
power to the AC input MCB on the right side of the cabinet (shown in Figure 1.1), so as to ensure the cabinet
operation.
Connecting DC cables
If the outdoor cabinet has been installed Emerson matched subrack before delivery, the DC cable connection
between subrack and cabinet should have been done by Emerson. You only need to connect load cables according
to the subrack user manual.
If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 48V DC
power to DC input terminal on the left side of the cabinet (shown in 2.4.2 1Figure 1.1), so as to ensure the cabinet
operation.

ECM1500 Outdoor Cabinet User Manual

10

Chapter 2 Installation

2.4.2 Connecting Signal Cables


The ECCU inside the outdoor cabinet provides four pairs of alarm output dry contacts for the user. All the dry contact
outputs need to be led out from the ECCU. The silkprint of the alarm output dry contacts is shown in Figure 1.1.

Figure 1.1 Position of signal output

When connecting alarm cables, you should peel the signal cables and insert their ends into the corresponding
terminals, and then tighten the screws on the terminals.The functions of the dry contact are given in Table 1.2.
Table 1.2 Dry contact functions
Port No.
Definition
1, 2
Over temperature alarm
3, 4
Fan failure
5, 6
Door alarm
General alarm (temperature low alarm, humidity high alarm, humidity low alarm,
7, 8
temperature and humidity sensor failure alarm, waterlogging alarm, smoke alarm)

Remark
Normally open (configurable)
Normally open (configurable)
Normally open (configurable)
Normally open (configurable)

2.4.3 Sealing The Entry Holes


After cable connection, use fireproof mud to seal the cabling holes (shown in 2.4.1 1Figure 1.1).

2.5 Battery Installation


The battery compartment can accommodate a battery string of capacity not higher than 50Ah. Batteries are classified
into front-terminal battery and general battery.
1.

Note

1. The batteries may carry dangerous current. Before connecting the battery cables, make sure all the battery input MCBs are off.
2. Make sure that the battery cable polarities are correct. Otherwise, both the battery and the cabinet will be damaged!
3. Insulate the installation tools. Be careful not to damage the plastic battery case or the battery terminals during installation.
Check before installation
1. Check that the battery shells are in good condition.
2. Check that the polarities of the terminals are in accordance with the polarity marks on the battery shell.
3. Check that the terminal screws are fastened.
ECM1500 Outdoor Cabinet User Manual

Chapter 2 Installation

11

Installation procedures
2.

Note

1. When installing two battery strings or more, install the lower battery string first. While removing them, remove the upper
battery string first.
2. This chapter is applicable to Emerson subrack and battery cables. It is a reference when you configure subrack and battery
cables for yourself.
Step 1: Open the battery MCBs and AC input MCBs.
Step 2: Place the batteries one by one in the battery compartment from right to left, with distance between adjacent
batteries at least 10mm.
Step 3: Remove the battery terminal covers, and connect the plate electrodes between the batteries in turn. Note that
the mid-voltage sampling cable should be connected to the plate electrode between the second and the third
batteries.
Step 4: Connect the positive battery cables (red) in the battery compartment to the battery positive terminals.
Connect the negative battery cables (black) in the battery compartment to the battery negative terminals. Attach the
acid and alkali integration box (battery accessory) to the internal side of the right panel of the cabinet.
Step 5: After installing the battery strings, use the 3M double-side adhesive tape pasted on the battery temperature
sensor to paste the sensor onto the center of the upper-layer battery string.
Step 6: Measure the battery string voltage. If the voltage value is correct, replace the battery terminal covers.

2.6 Installation Check


After installation, check the installation against the list given in Table 1.1.
Table 1.1 Installation check list
Check item

No.
1
2
3

Cabinet
installation

4
5
6
7
1
2

Electrical
connection

3
4
5
6

Description
Check that the cabinet is level, upright and steadily fixed
Check that all bolts are tightened, especially those in electrical connections, that all bolts have plain
washers and spring washers, and that the washers are not reversed
Check that there are no irrelevant materials in the cabinet, and clear them away if any
Check that the cabinet paint is intact. If there are scratches, paint them immediately with antirust paint to
prevent corrosion
Clean up the cabinet
Check that the door can move freely, the locks are in good condition and the door stay bar is fixed
Check that the dummy plates are installed at the reserved space where no customer device is installed.
Check that the burglarproof components (if configured) and battery baffles (if configured) are installed
Verify the specifications of all MCBs and cables
Check the correctness of bus bar connections, input and output cable connection, and connection
between the power system and the system grounding
Check the correctness of the batteries number and connection, and battery strings polarities
Make sure all the cable connections are firm and reliable
Check the connection point, line sequence and polarities of DC cables. Check the connection polarities of
the batteries. Check that the connection points are fixed and the cable connections are correct and
reliable
Check that the cables are tidy, and the cable binding is normative

ECM1500 Outdoor Cabinet User Manual

12

Chapter 3 Testing

Chapter 3 Testing
This chapter introduces the testing after installation. The corresponding safety rules shall be adhered to in the testing.
This testing should be done after the subracks in the cabinet are tested.

3.1 Startup
3.

Note

Before the test, inform the chief manufacturer representative. Only the trained electrical engineer can maintain and operate this
equipment. In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets, bangles
and rings.
During operation, parts of this equipment carry hazardous voltage. Misoperation can result in severe or fatal injuries
and property damage. Before the test, check the equipment to ensure the proper earthing.
Make sure that the AC input and DC input are normal.
Forced ventilation check
After power-on, the heat control board enters self testing and the fans accelerate to full speed gradually. After a few
minutes, the fans stop. If the environmental temperature is about 35C, the fans will operate at low speed.
Heat exchanger check
After power-on, the simple control unit enters self testing and the fans accelerate to full speed gradually. After a few
minutes, the fans stop. If the environmental temperature is about 35C, the internal fans will operate at low speed and
the external fans will stop.
Air-condition check
After power-on, the air-condition starts to operate. If the environmental temperature is about 35C, the internal fans of
the air-condition will operate at low speed and the compressors of the external fans will stop.

3.2 Alarm Check And System Operation Status Check


Alarm check
Disconnect the thermal control units, so as to check that if the thermal control units can trigger thermal control unit
alarm.
System operation status check
There should be no alarms during normal system operation.

3.3 Final Steps


Disconnect all test equipment from the outdoor cabinet and make sure that materials irrelevant to the
equipment have been all removed.
Restore the outdoor cabinet to its original condition and close the cabinet door.
Check and handover the equipment that the user has purchased.
Note down all the operations taken, including time of the operation and name of the operator.

OK

Comments

If any defect is found in this equipment, inform the personnel responsible for the contract.
If repairing is needed, please fill in the FAILURE REPORT and send the report together with the faulty unit to the
repairing center for fault analysis.

ECM1500 Outdoor Cabinet User Manual

Chapter 4 Maintenance

13

Chapter 4 Maintenance
This chapter describes the routine maintenance, alarm and fault handling, and part replacement of the power supply
system.
4.

Note

1. The maintenance must be conducted in compliance with relevant safety rules.


2. Only the trained personnel with adequate knowledge about the outdoor cabinet shall work on the internal parts of the system.

4.1 Routine Maintenance


Inspect the power supply system periodically and shoot the troubles in time if any. The routine maintenance items are
given in Table 1.1.
Table 1.1 Routine maintenance list
Item
Thermal control
unit
Paint and
galvanization layer
on the cabinet
Front door air filter
(for forced
ventilation model
and air-condition
model)

Period

Inspection method

Guide
Check alarm and operation states. If the thermal control units
run abnormally, refer this chapter to replace relevant
components

Once half a year

Visual inspection

Once half a year

Visual inspection

If there is any paint peeling or scratches, mend the painting


immediately

Visual inspection

If dust accumulated on the front door air filter, loosen the fixing
screws of the air filter cover of the front door (shown in Figure
1.1). Then take off the air filter cover and brush off the dust. If
the air filter is damaged, replace it. Finally, replace the air filter
cover

Once half a year

Air filter
Fixing screw
of air filter
Air filter
Fixing screw
of air filter

Air-condition model outdoor cabinet

Forced ventilation model outdoor cabinet


Figure 1.1 Air filter

ECM1500 Outdoor Cabinet User Manual

14

Chapter 4 Maintenance

4.2 Replacing Parts Of Outdoor Cabinet


4.2.1 Replacing Environment Climate Control Unit
Appearance and terminal layout
The appearance of the environment climate control unit is shown in Figure 1.1, and the terminal layout is shown in
Figure 1.2.

DIP switch
Earth nut

Figure 1.1 Environment climate control unit


J8

J14

J4
FAN 4

FAN 3

TEM P.
J12

AC _O FF

ALM O U T

J5

SW 101

J10

LED _FAU LT
LED _ALM

J11

LED _R U N

R S232

J6

J9

SW 100

C AN

J13
J7
J15

T E M P .& H U M .

J3

FAN 2

W ATER

J2
FAN 1

P O W E R D O O R S M O K E IN F R A R E D

J1

Figure 1.2 Terminal layout of the environment climate control unit

DIP switch description


DIP switch function description and setting method:
1. Bit 1 ~ 4 are used to set addresses of the environment climate control unit. OFF: 0, ON: 1. Default address: 16.
The setting method of the environment climate control unit (ECCU for short) is given in Table 1.1.
Table 1.1 Setting method of ECCU address
Bit 4
0
0
0

Bit 3
0
0
0

Bit 21
0
0
1

Bit 1
0
1
0

Address
16
1
2

15

Bit 1 ~ Bit 4 have been set in factory. You can change the settings according to your communication requirement.
2. The function description and setting method of Bit 5 ~ Bit 8 are given in Table 1.2.

ECM1500 Outdoor Cabinet User Manual

Chapter 4 Maintenance

15

Table 1.2 Function sescription and setting method of Bit 5 ~ 8


Bit No.

Function

Setting method
OFF: heat exchanger model
5
Choose cabinet model
ON: forced ventilation
OFF: normal when open; alarm when closed
6
Choose dry contact alarm mode
ON: normal when closed; alarm when open
OFF: serial port termperature & humidity sensor
*
7
Choose sensor
ON: temperature sensor
Choose whether stopping fans
OFF: No
8
when AC mains fails
ON: Yes
Note*: When Bit 7 is placed to ON position, ECCU has no humidity acquisition function

Default value
ON
ON
ON
OFF

Replacing procedures of the ECCU


Step 1: Loosen the two fixing screws to remove the cover, and then you can see the ECCU. The position of cover is
shown in Figure 1.1.

cover

f ix in g s c r e w o f c o v e r

Figure 1.1 Cover position

Step 2: Disconnect J15 terminal (shown in 1Figure 1.2), and then disconnect the rest connection terminals on the
ECCU.
Step 3: Loosen the fixing screws on the ECCU. Replace the ECCU with a new one.
Step 4: Reverse connection sequence in step 2 to connect terminals, so as to check that the LED_FAULT (shown in
1Figure 1.2) indicator show correctly. Under normal instance, the LED_FAULT indicator is power-off.
Step 5: Place the DIP switch to the correct position according to Table 1.1 and Table 1.2.
Step 6: Press the SW1 self-test button (shown in 1Figure 1.2) to ensure that the fan can start normally.
Step 7: Replace the cover of the ECCU.

4.2.2 Replacing Fans


Fan alarm circuit
The fan-cooling unit of the outdoor cabinet is mainly composed of 2 ~ 4 axial flow fans. The fan alarm circuit is shown
in Figure 4-5.where the blue line is the alarm line.
VCC
(Red)
(Blue)
MOTOR
DRIVER IC

VFG

Ic

R
FG SIGNAL

VCE
(Black)
(Yellow)
Figure 1.1 Illustration of the fan alarm circuit

Fan replacing procedures


Follow the following procedures to replace the fan.
ECM1500 Outdoor Cabinet User Manual

GROUND

16

Chapter 4 Maintenance
Step 1: Make sure that the fan-control terminals (J1 and J2 are hot pluggable) on the environment climate control unit
are inserted firmly. The fan-control terminals are shown in Figure 4-3.
Step 2: Ensure that Bit 5 of SW100 switch is put to the ON position.
Step 3: Press the SW101 self-test button (shown in Figure 4-3). If the fans do not work, make sure that the fan cables
are perfect.
Step 4: Loosen the fixing screws at the cabinet top cover to open the top cover. (Opening the top cover, pull it forward
and then lift up its front not more than 30. Otherwise the top cover will be fallen.)
Step 5: Disconnect the fan power terminals at the top of the cabinet. Use a multimeter to measure the voltage
between the positive power cable and the negative power cable. Check if the voltage is close to the DC output
voltage (54.0V).
If the fan power voltage is normal, the fans are damaged. Carry out the next step.
Step 6: Loosen the fixing screws of the fans and replace the fans, as shown in Figure 4-6.
Fan

Figure 1.1 Fan position

Step 7: Reconnect the fan power terminals, and press SW1 self-test button (shown in Figure 4-3) to ensure that the
fan can startup normally.
Step 8: Replace the cabinet top cover.

4.2.3 Replacing Door Status Sensor


There is a door status sensor installed in the cabinet for detecting the close or open status of the cabinet door. The
alarm will be eliminated only when the cabinet door is closed.
The door status sensor requires no particular maintenance; just replace it when it is damaged. If the door is closed,
while the door status sensor alarm occurs, the sensor must have been damaged. The position of the sensor is shown
in Figure 4-7.
Remove the sensor top cover and then the two screws. Replace the old sensor with a new one and finally fix the
sensor and the signal cables with the screws.

ECM1500 Outdoor Cabinet User Manual

Chapter 4 Maintenance

Figure 1.1 Position of the door status sensor

4.2.4 Replacing TEC


Step 1: Switch off the TEC MCB, as shown in Figure 1.1. Disconnect all the cable connectors.

Figure 1.1 AC input MCB position

Step 2: Loosen the fixing screws of TEC to remove and replace TEC.

ECM1500 Outdoor Cabinet User Manual

17

18

Appendix 1 Technical And Engineering Parameters

Appendix 1 Technical And Engineering Parameters


Table 1 Technical parameters
Parameter
category

Parameter
Operating temperature

Environmental

EMC

Storage temperature
Relative humidity
Altitude
Others
Conducted emission
Radiated emission
Immunity to EFT
Immunity to ESD
Immunity to Surges
Immunity to radiation
Immunity to conduction
Safety regulation
Insulation resistance

Others
Insulation strength

MTBF
ROHS
Mechanical

Dimensions (mm)

Description
-10C ~ +45C (forced ventilation model), -40C ~ +45C (heat exchanger
model), -40C ~ +50C (air-condition model)
-40C ~ +70C
5%RH ~ 100%RH
2,000m (derating is required above 2,000m)
No conductive dust or erosive gases. No possibility of explosion
Class A

EN55022

Level 3 EN61000-4-4
Level 3 EN61000-4-2
Level 4 EN61000-4-5
Level 3 EN61000-4-3
Level 3 EN61000-4-6
Compliant with IEC60950-1, IEC60950-22
At temperature of 15C ~ 35C and relative humidity not bigger than 90%RH,
apply a test voltage of 500Vdc. The insulation resistances between AC circuit
and earth, DC circuit and earth, and AC and DC circuits are all not less than
10M
(Remove the SPD, monitoring module and rectifiers from the system before the
test.)
AC circuit to earth: 50Hz, 2,500Vac
DC circuit to earth: 50Hz, 1,000Vac
Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac
AC to DC circuits: 50Hz, 3,000Vac
For all the three tests above, there should be no breakdown or flashover within
1min, with leakage current not bigger than 10mA
100,000hr
Compliant with R5 requirement
Cabinet
800 (W) 750 (D) 2500 (H)
Internal space of
613 (W) 575 (D) 400 (H)
battery compartment
Table 2 Spart part list

Part
Fan
Fan

Specification or model
DC axial flow fan
DC centrifugal fan

ECM1500 Outdoor Cabinet User Manual

BOM
32010191
32010261

Appendix 2 Schematic Diagram

Appendix 2 Schematic Diagram

Figure 1 Schematic diagram of heating and cooling

ECM1500 Outdoor Cabinet User Manual

19

20

Appendix 2 Schematic Diagram

Figure 2 Schematic diagram of AC Power Distribution Unit

ECM1500 Outdoor Cabinet User Manual

Appendix 2 Schematic Diagram

Figure 3 Schematic diagram of forced ventilation model outdoor cabine

ECM1500 Outdoor Cabinet User Manual

21

You might also like