2 Introduction
Buildings utilize 40% of the total annual global primary energy consumption and 10- 20 % of
this is consumed by HVAC system[1]. No waste alternative energy systems are required by dint
of increased energy demands, cost and its availability. Energy storage systems that are used to
provide surplus energy at the time of need have disadvantage as a consequence of large volume.
Phase change materials (PCM) bring off the same ambition with distinctly reduced volume. They
can be employed for both heating and cooling purpose.
PCM material is good towards storing heat storage compared to cold storage. Solar energy and
waste heat are in abundant and can be stored in PCM. However various problems have been
faced during cold storage due to low thermal conductivity and latent heat of PCM at low
temperature. Its solution includes active and passive cooling systems using PCM, integration of
PCM into building structures [2, 3]. Climate conditions and site are important considerations for
free cooling. It is applicable to interior and desert areas. Sea and land breezes in coastal areas
execute the temperature moderation which affects the efficiency of free cooling adversely. Free
cooling enhances heat transfer on air and PCM side. Charging time is reduced by having larger
surface area per storage volume[4]. Discharging can be proceeded further according to the load
requirement. Air velocity must be larger in the initial stages of charging followed by its reduction
in later stage in order to pursue energy efficient charging. To control volume flow and pressure
drop which decides the capacity of fan and power consumption, air velocity must be
optimized[5]. Applications of PCM are large due to the fact that it is based on the latent heat.
Latent heat thermal storage in the melting and solidification of a Phase Change Material (PCM)
has been proved an effective method, due to the high storage density[6]. However it is difficult to
utilize the capacity effectively for the reason of having low thermal conductivity. This has been
observed in organic PCMs to large extent. Research has been done to cater its low thermal
conductivity[7]. Some techniques incorporate use of fins, metal, graphite compound matrices,
dispersed high-conductivity particles inside the PCM and micro-encapsulation. Later on in the
presence of cooling fins heat transfer and phase change details became the major area of
research[4]. Extensive list of references on PCM based heat sinks have been provided by
Krishnan et al[8]. By neglecting one or more necessary features of the process, like volumetric
expansion due to the phase change, convection in the liquid phase and motion of the solid in the
melt due to density gradients various approaches were adopted to overcome difficulties in
analysis [9].
In applications where cooling can be generated more efficiently or for less cost outside of the
period of cooling demand[10], cold storage is a practical energy storage method. Likewise using
smaller cooling equipment has been made possible by thermal storage. This technology is good
in operations where refrigeration laod is needed for a short period. Again role is played by cold
storage when the electricity is more costly during the peak as compared to the non-peak hours. It
can serve as a backup in the scenario where refrigeration plant breakdown[11]. It is being
adopted by many countries to shift the peak load to off-peak hours for air conditioning
demands[12]. Sensible energy storage material is being used by most of the thermal energy
storage systems whereas the use of PCMs offers a momentous potential to increase the energy
storage density[13].
In a study by A.H. Mosaffa et al. showed numerical investigation of a thermal energy storage
(TES) unit. For climate conditions of Tabriz, Iran system that can guarantee comfort conditions
must have a coefficient of performance (COP) 7.0. Numerical investigation showed that this
cooling can be achieved by a combination of CaCl2.6H2O and RT25 with an optimized air
channel setup[14]. A.A. Rabienataj Darzi et al. in their work showed that PCM cooling can be
enhanced by increasing mass flow rate and also PCM encapsulation thickness effects linearly
melting of PCM during discharging[15]. C. Arkar et al. in their work showed that for continental
climate conditions PCM with melting temperature 22 C is most suitable[ 16]. N.H.S Tay et al. in
their work showed that tube in tank systems can store 18 times more useful energy than sensible
storage system per unit volume[17]. Experimental Study carried out by Albert Castel et al.
discuss the effect of external fins on heat transfer. Study shows that PCM module without fins
required charging time was 17 min, which was reduced to 13 min (reduction of 23.52%) by 20
mm fins and to 7 min (reduction of 58.82%) by 40mm fins[18]. Numerical study carried out by
N.H.S Tay et al shows the effect tube in tank heat exchanger. Study shows that If PCM flow rate
is five times the flow rate then dynamic melting reduces the phase change time by 36-39 % [ 19].
Ana Lazaro et al. in their work shows that that increasing thermal conductivity increase PCM
cost whereas economical method is to enhance heat exchanger design[20]. T. Karlessi et al. in his
study show the effects of building tile coated in cool PCM and its effect on reducing cooling load
in building. His study shows that due to cooling coating on PCM, tiles absorb the excess heat and
reduce the building temperature[21]. Alvero de Gracia study shows that night cooling is the best
solution for reducing cooling load. The system incorporates a faade which is being used as cold
storage. Skin of the faade must be made of material having low thermal conductivity to enhance
system efficiency [22]. F. Frusteri in his study showed the effect of carbon fibers on thermal
conductivity of PCM and experimentally studied the effect of size of the fibers on the PCM
thermal conductivity[23].
This case study present the experimental investigation of butyl stearate as a PCM for cooling
purpose. Experimental setup was setup in Heat and Mass Transfer Lab in NUST School of
Mechanical Engineering and different experiments were carried out with results described in
following sections.
3 Experimental setup
Experimental setup consisted of wooden air duct and contain PCM encapsulated in aluminum
tubes. DC powered Air blowers are used at both inlet and outlet to force the air flow through the
air duct. Instrumentation and data acquisition of the setup is also done. Complete experimental
setup is shown in figure 1.
Parameter
Heat exchanger width
Heat exchanger length
Length of Aluminum tubes for PCM
Diameter of aluminum tubes
Air inlet & outlet Diameter
Slabs Length to place PCM filled tubes
Value (mm)
152.4
152.4
101.6
12.7
12.7
101.6
Slab width
Slab thickness
76.2
25.4
Figure 2 shows path of air flow shown by blue arrows through the wooden box and transfer or
absorbed heat from PCM. T1 to T5 shows the position of temperature sensors attached for
temperature readings, LM35temperature IC is used and is connected to a PC. Readings are taken
after every 100 seconds. Encapsulated PCM tubes are shown in figure 3 below.
Important properties of PCM are shown in table 3 and specifications of encapsulation tube are
shown in table 4. O rings are used at both ends of encapsulation tubes to avoid any leakage of
PCM through the container. System was operated for 5 hours daily; and for 3 hours system was
in charging process and for 2 hours system was in discharging phase. These terms are explained
in the next section.
Table 2: Properties of PCM
Properties
Commercial Name
Value
Butyl Stearate
Type
Organic
Melting Temperature
Latent Heat
Appearance
Relative Density
Boiling Point
19-22 C
140 KJ/Kg
Liquid (light yellow)
0.861gm/mL at 20 C
343 C at 1.013 hPa (hectopascal)
Parameters
Pipe length
Pipe thickness
Pipe diameter
Values (mm)
101.6
2
12.7
4 Experimental Procedure
During the experimentation work during charging process cold air was supplied to the heat
exchanger, and PCM was solidified as it absorbed the coldness of the air. This cold air was
supplied through ice box with the help of air blower.
Similarly during discharging process ambient air was supplied to PCM and PCM cooled the air
by providing stored coldness to the passing air.
PCM temperature in the results shown in following section shows the average temperature of all
the three PCM slabs. During experimentation for this case study following things were observed
and explained in the result and discussion section.
Effect of changing flow rate on butyl stearate charging and discharging capability
Term Ideal PCM used in next sections means pure PCM during experiment without addition of
any metal matrix and threshold temperature refers to the temperature of air within the comfort
level which in this case is set to 26 C.
Figure 4: PCM used during experiment (a) Ideal PCM (b) PCM with Al powder (c) PCM with Cu powder (d) PCM with Cu wire
Pieces
Figure 4 shows different PCM used during experimental work. 50 gm of PCM was used during
ideal PCM experiment as shown in top left corner of figure. 10 gm of metal was added in PCM
during experiment to test their effect on PCM charging as shown in the figure.
Tinitial
Similarly equation 2 and 3 are used to calculate amount of cold absorbed and released by PCM
during charging and discharging process respectively.
t
22\*
MERGEFORMAT ()
t
33\*
MERGEFORMAT ()
mair1
Where
specifies the flow rate of air, cp_air shows specific heat of air. Tair-in & Tair-out shows
the air inlet and outlet temperature respectively.
Cold extraction can be calculated as the ratio of amount of cold extracted at threshold
temperature and total cold extracted during discharging.
Figure 8 shows that by charging of almost of 120 minutes it was able to provide cold air with in
threshold temperature of 26 C for up to 45 minutes. Black line indicates the rise of air inlet
temperature as supply is changed from ice box to ambient during discharging process. Similarly
figure 9 shows discharging process of PCM and how its temperature rises as cold absorbed by
the PCM during charging is being extracted by warm air.
Figure 9 shows effect of changing air flow rate on PCM charging. As shown in the figure a linear
trend is observed by changing flow rate during charging process. At flow rate of 0.0180 Kg/sec
PCM took around 25 minutes for temperature drop of 2 C. Flow rate was then decrease by 41 %
to 0.0107 Kg/sec and time increased for this 2 C drop increase up to 50 minutes and similarly
75 minutes were taken by the system for decrease of 72 % in flow rate at 0.005 Kg/sec. So from
figure 9 it is clear that for charging process high flow rate is preferred as heat transferred is quick
and temperature drop is high.
During discharging process as shown in figure 10 it is observed that decreasing flow rate
increases discharge time of PCM. As shown in the figure 10 at lower flowrate of 0.005 Kg/sec as
heat transfer is less thus temperature increase is just by 5 C in 110 minutes, this value increase to
9 C for flow rate at 0.018 Kg/sec. Trend of effect of flow rate is almost linear at high flow rates
but as flow rate decreases graph gets closer to a constant line.
Figure 12 shows that for threshold temperature at 26, 28 and 24 C useful percentage of cold
extracted is approximately 65 %, 82% and 40% respectively. From figure 5 we can see that
almost for an hour system provides cold air with in our threshold temperature range.
Figure 13 shows that for threshold temperature of 26 C system provided cold air for almost 70
minutes and 82 % cold is in useful region and is extracted and if threshold temperature is
increase to 28 C this time increase upto 80 minutes and % extraction increase upto 86 % and
decrease to 50 minutes for threshold temperature of 24 C with % cold extraction decrease to 65
% for this case.
7 Conclusion
Experimental work shows that by charging PCM for almost 2 hours it can provide cold air for
almost 50 minutes and this time can be increased by increasing threshold temperature. Also by
increasing flow rate time for PCM charging decreases.
Similarly adding Al metal matrix in PCM enhances heat transfer during charging more compared
to Cu metal matrix addition. Also for this enhancement particle size of metal matrix is very
important. Finer the particle size more it enhance thermal conductivity of PCM.
REFERENCE
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[23]
[24]
A. Waqas and Z. U. Din, "Phase change material (PCM) storage for free cooling of buildingsA review," Renewable and sustainable
energy reviews, vol. 18, pp. 607-625, 2013.
U. Stritih and V. Butala, "Experimental investigation of energy saving in buildings with PCM cold storage," International Journal of
Refrigeration, vol. 33, pp. 1676-1683, 2010.
X. Chen, M. Worall, S. Omer, Y. Su, and S. Riffat, "Experimental investigation on PCM cold storage integrated with ejector cooling
system," Applied Thermal Engineering, vol. 63, pp. 419-427, 2/5/ 2014.
P. Lamberg and K. Siren, "Approximate analytical model for solidification in a finite PCM storage with internal fins," Applied
Mathematical Modelling, vol. 27, pp. 491-513, 2003.
V. A. A. Raj and R. Velraj, "Review on free cooling of buildings using phase change materials," Renewable and Sustainable Energy
Reviews, vol. 14, pp. 2819-2829, 12// 2010.
R. A. Crane and G. Bharadhwaj, "Evaluation of thermal energy storage devices for advanced solar dynamic systems," Journal of solar
energy engineering, vol. 113, pp. 138-145, 1991.
H. Inaba, K. Matsuo, and A. Horibe, "Numerical simulation for fin effect of a rectangular latent heat storage vessel packed with
molten salt under heat release process," Heat and mass transfer, vol. 39, pp. 231-237, 2003.
S. Krishnan, S. V. Garimella, and S. S. Kang, "A novel hybrid heat sink using phase change materials for transient thermal
management of electronics," Components and Packaging Technologies, IEEE Transactions on, vol. 28, pp. 281-289, 2005.
P. Lamberg, R. Lehtiniemi, and A.-M. Henell, "Numerical and experimental investigation of melting and freezing processes in phase
change material storage," International Journal of Thermal Sciences, vol. 43, pp. 277-287, 2004.
V. Shatikian, G. Ziskind, and R. Letan, "Numerical investigation of a PCM-based heat sink with internal fins: constant heat flux,"
International Journal of Heat and Mass Transfer, vol. 51, pp. 1488-1493, 2008.
C. Zamfirescu and A. Bejan, "Tree-shaped structures for cold storage," International journal of refrigeration, vol. 28, pp. 231-241,
2005.
A. Saito, "Recent advances in research on cold thermal energy storage," International Journal of Refrigeration, vol. 25, pp. 177-189,
2002.
B. Zalba, J. M. Marn, L. F. Cabeza, and H. Mehling, "Review on thermal energy storage with phase change: materials, heat transfer
analysis and applications," Applied thermal engineering, vol. 23, pp. 251-283, 2003.
A. H. Mosaffa, C. A. Infante Ferreira, F. Talati, and M. A. Rosen, "Thermal performance of a multiple PCM thermal storage unit for
free cooling," Energy Conversion and Management, vol. 67, pp. 1-7, 2013.
A. A. R. Darzi, S. M. Moosania, F. L. Tan, and M. Farhadi, "Numerical investigation of free-cooling system using plate type PCM
storage," International Communications in Heat and Mass Transfer, vol. 48, pp. 155-163, 2013.
C. Arkar, B. Vidrih, and S. Medved, "Efficiency of free cooling using latent heat storage integrated into the ventilation system of a low
energy building," International Journal of Refrigeration, vol. 30, pp. 134-143, 2007.
N. H. S. Tay, M. Belusko, and F. Bruno, "Designing a PCM storage system using the effectiveness-number of transfer units method in
low energy cooling of buildings," Energy and Buildings, vol. 50, pp. 234-242, 2012.
A. Castell, C. Sol, M. Medrano, J. Roca, L. F. Cabeza, and D. Garca, "Natural convection heat transfer coefficients in phase change
material (PCM) modules with external vertical fins," Applied Thermal Engineering, vol. 28, pp. 1676-1686, 9// 2008.
N. H. S. Tay, M. Belusko, M. Liu, and F. Bruno, "Investigation of the effect of dynamic melting in a tube-in-tank PCM system using a
CFD model," Applied Energy, vol. 137, pp. 738-747, 1/1/ 2015.
A. Lazaro, P. Dolado, J. M. Marn, and B. Zalba, "PCMair heat exchangers for free-cooling applications in buildings: Experimental
results of two real-scale prototypes," Energy Conversion and Management, vol. 50, pp. 439-443, 3// 2009.
T. Karlessi, M. Santamouris, A. Synnefa, D. Assimakopoulos, P. Didaskalopoulos, and K. Apostolakis, "Development and testing of
PCM doped cool colored coatings to mitigate urban heat island and cool buildings," Building and Environment, vol. 46, pp. 570-576,
2011.
A. de Gracia, L. Navarro, A. Castell, . Ruiz-Pardo, S. lvarez, and L. F. Cabeza, "Thermal analysis of a ventilated facade with PCM
for cooling applications," Energy and Buildings, vol. 65, pp. 508-515, 2013.
F. Frusteri, V. Leonardi, S. Vasta, and G. Restuccia, "Thermal conductivity measurement of a PCM based storage system containing
carbon fibers," Applied Thermal Engineering, vol. 25, pp. 1623-1633, 2005.
M. Iten and S. Liu, "Experimental Study on the Performance of RT 25 to be Used as Ambient Energy Storage," Energy Procedia, vol.
70, pp. 229-240, 2015.