40Amp UPS
Features :
SPECIFICATION
MODEL
DR-UPS40
DC INPUT / DC VOLTAGE
DC BUS
RATED CURRENT
24 ~ 29V
VOLTAGE RANGE
21 ~ 29V
CURRENT RANGE
0 ~ 40A
2A
4 / 7 / 12AH / 24V
BATTERY
INPUT /
OUTPUT
40A
DC BUS OK
FUNCTION BATTERY FAIL
BATTERY DISCHARGE
ENVIRONMENT
Relay contact : Short when battery failure is observed through the battery test function, relay contacts ; Red LED on front panel
LED(Green) : DC BUS OK : light, DC BUS fail : dark
Relay contact : Short when battery in discharge condition, relay contacts ; Yellow LED on front panel
LED(Green) : DC BUS OK : light, DC BUS fail : dark
WORKING TEMP.
-20 ~ +70
WORKING HUMIDITY
20 ~ 90% RH
, 10 ~ 95% RH
DIMENSION
PACKING
NOTE
1. All parameters NOT specially mentioned are measured at rated load and 25 of ambient temperature.
2. Every 25 seconds, send out test signal through "Battery Fail" relay contact and LED indicator once the battery is fail.
MeanWell Direct
E-mail: sales@meanwelldirect.co.uk
DR-UPS40
40Amp UPS
Mechanical Specification
Unit:mm
100
Case No.923D
125.2
LED
1
3
TB2
1
2
3
4
5
6
TB1
55.5
35
Pin No.
1
2
3
4
Block Diagram
25Ax2
+
100
+
CHARGE
CIRCUIT
LIMIT
BAT.
TEST
DETECTION
CIRCUIT
24V
BATTERY
80
60
LOAD (%)
INPUT
Assignment
BAT DISC 1
BAT DISC 2
BAT OK 1
BAT OK 2
DC OK 1
DC OK 2
Derating Curve
LOAD
POWER
SUPPLY
Assignment
BATTERY INPUT +
BATTERY INPUT DC INPUT DC INPUT +
40
20
-20
DC OK BAT OK
BAT
DISCHARGE
10
20
30
45
AMBIENT TEMPERATURE (
MeanWell Direct
E-mail: sales@meanwelldirect.co.uk
50
60
70 (VERTICAL)
DR-UPS40
40Amp UPS
Suggested Application
1.Back up connection for AC interruption
DR-UPS40
24V
PSU
Battery
24V/40A max.
BAT
+ -
Load
DC
- +
DR-UPS40
DR-RDN20
24V
Battery
PSU
BAT
DC
+ - - +
Vout
Load
Vin
+ - - - B+ A+
-