SCHEDULES

SCHEDULE A.1
SYSTEM AND LINE DATA
Item
1.
1.1
1.2
1.3
1.4

Description
System Data
System nominal voltage
System maximum voltage
System nominal frequency
Line Data
Lower Khare to Singati S/S

Unit

Data

kV
kV
Hz

132
145
50

Km

5.3

SCHEDULE A.2
DESIGN DATA
Item
1.
1.1
1.2
1.3
1.4
2.
2.1
2.2

2.3

Description
Temperature
Maximum ambient temperature
Minimum ambient temperature
Maximum temperature of conductor 0C
Everyday temperature of conductor 0C
Wind Loads
Wind pressure on the whole
projected area of conductors
Wind pressure on the whole
projected area of steel angle
members
Wind pressure on 1.71 times
kg/m2
projected area of steel angle
face of structure

Unit

Data

0C
0C

45
0
80
32

kg/m2

75

kg/m2

121

207

SCHEDULE A.3
MINIMUM CLEARANCES
The followings are the minimum clearances between live conductors and other objects,
which
correspond to the maximum conductor sag conditions.

Item

Description

Minimum clearances (in meter)


in normal condition
___________________________________________________________
1.
Normal ground for pedestrians only
7
2.
Residential areas
7
3.
Roads and streets
8
4.
Highways
8
5.
To metal clad or roofed buildings or
5
building or structures upon which
a man may stand
6.
Power lines (above or below)
3.5
7.
Telecommunication lines
3.5
For other objects not listed in the Schedule, the requirements for minimum clearances shall
comply also with NESC (NATIONAL ELECTRIC SAFETY CODE). Approximately 0.5m shall
be added to the clearance values above to allow for survey and drawings errors and longterm creep. Crossing of houses, huts and other objects with soft roofing is not allowed.
(1) Minimum clearance from live conductor to the nearest part of tower body for suspension
tower;
(a) for still air condition and upto 20 degrees swing of insulator strings 1500 mm
(b) for 20 to 55 degree swing condition of insulator strings 1000 mm
(2) Minimum clearance from live conductor to the nearest part of tower body for tension
tower;
(a) jumper loop, from still air to 15 degree swing 1500 mm
(b) jumper loop, from 15 to 40 degree swing 1000 mm
(c) jumper suspension insulator-set, from still
air to 15 degree swing 1500 mm
(d) vertical distance between cross arm and bottom of jumper loop 1800 mm

SCHEDULE A.4
SUPPORT TYPES AND DESIGN SPANS (Single Circuit)
Tower Type
Item Tower Type

Position where used

1
2
3
4
5

traight line
Angle
Angle
Angle
Angle and Dead-end

DA
DB
DC
DM
DD/DDE

Design Spans
Item Tower Type
span

Ruling Span
(m)

1
2
3
4
5

DA
DB
DC
DM
DD/DDE

330
330
330
330
330

Angle of deviation
(degree)
0 -2
2 - 15
2 30
30 90
30 60,

Insulator type
Suspension
Tension
Tension
Tension
Tension/Dead-end

Wind span

Weight

(m)
350
350
350
350
350

(m)
700
700
700
500
500

SCHEDULE A.5
FACTORS OF SAFETY
Item

Description
Minimum
Factor of Safety

1.
1.1
1.2
1.3
1.4

Towers and Foundations


All types of towers under normal working conditions
All types of towers under broken wire conditions
Foundations for all types of towers under normal working conditions
Foundations for all types of towers under broken wire conditions

2.
2.1
2.2

Conductors and Insulators


Conductors based on ultimate tensile strength
Conductors based on ultimate tensile strength at still air every-day
temperatures
Complete insulator strings and fittings on minimum breaking
load of insulator
Dead end compression clamps and compression splices
based on conductor ultimate tensile strength

2.3
2.4

3
3.1
3.2
3.3

Earth Wires
Earth wire based on ultimate tensile strength
Complete tension assembly at earth wire maximum working tension
Complete suspension assembly at maximum vertical load

2.0
1.5
2.0
1.5

2.5
5.0
3.0
0.95

4
3
3

SCHEDULE A.6
INSULATORS
Item
1.
1.1
1.2
1.3

Description
Insulator unit
Type of insulator
Type of coupling
Dimensions

Unit

Data

a)
b)
c)

Spacing of insulator
Diameter of sheds
Creepage distance

mm
mm
mm

1.4
a)
b)

Minimum breaking load


Suspension string
Tension string

1.5
a)
b)

Power frequency withstand voltage


Dry one minute
kV
Wet one minute
kV

70
40

1.6
a)
b)

Impulse withstand voltage


Positive (Suspension / Tension)
Negative (Suspension / Tension)

kV
kV

110/115
115/120

1.7
a)
b)

Power frequency puncture voltage


Suspension-disc (70kN class)
Tension disc (120kN class)

kV
kV

110
120

2.

Insulator Strings

2.1
a)
b)
c)
d)
e)
f)

Number of units: (minimum)


Single suspension string 10
Double suspension string
Single tension string
Double tension string
Jumper suspension set
Light duty tension set

2.2

Standards ANSI/IEC

2.3
(a)
(b)

Electrical Characteristics of Insulator Strings


Impulse withstand voltage
kV
Power frequency withstand voltage kV

Porcelain or Toughened glass disc


ball & socket

approx. 146
approx. 254
approx. 292

kN
kN

70
120

2x10
11
2x11
10
11

650
275

SCHEDULE A.7
LINE CONDUCTOR
Item

Description

1.
1.1
1.2
1.3
1.3.1

ACSR "WOLF"
Conductor size
Conductor type ACSR WOLF
Number and size of wires
Aluminum

1.3.2

Steel

1.4
1.4.1
1.4.2
1.4.3
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12

Cross section
Aluminum
Steel
Total
Conductor diameter
Ultimate strength
Modulus of elasticity final
Coefficient of linear expansion per
Standard mass of conductor
Electrical D.C. resistance at 25
Standard of jointed length on reel
Standards BS 215

Unit

Data

mm2

326.10

No
dia., mm
No.
dia. mm

30
3.35
7
3.35

mm2
mm2
mm2
mm 2
kg
kg/ mm2
0C
kg/km
0 C ohm/km
m
PART

264.4
61.7
326.10
3.45
11,340
8,200
17.8x10-6
1,214
0.1093
2,000
2

SCHEDULE A.8
EARTH WIRE
Item
1.
1.1
1.2

Data
7/3.35
61.7
7/3.35

1.3
1.4
1.5
1.6

Description
Unit
E.H.S.Galvanized Steel Wire
Nominal sectional area
mm2
Number and diameter of component No/mm
Wire
Weight of wire
kg/km
Overall diameter
mm
Ultimate breaking strength
kg
Modulus of elasticity final
kg/mm2

1.7

Coefficient of linear per expansion

OC

1.5x10-5

1.8
1.9
1.10
1.11

Electrical D.C resistance at 20 C


Standard unjointed length on reel
Every day stress
Standards

ohm/km
m
2,000
N/mm2
180
ASTM A363 (IEC 209)

483
10.05
7,400
19,000

SCHEDULE A.9
MATERIAL FOR TOWER GROUNDING
Item
1.
1.1

Description
Ground rods
Galvanized steel pipes/ angle

2.
2.1
3.
3.1
3.2

Ground wire
Galvanized steel wire/ strip
38mm2 / strip 25/3mm
Connection of ground electrode with stub angle
For connection of steel angle:
Steel wire as above
For connection of copper weld rods: Copper conductor as above

60mm dia/50 x 50 x 5mm steel


angles 2 m long

SCHEDULE A.10
INSPECTION TESTS AT MANUFACTURER'S PLANT
The following tests shall be carried out at the manufacturer's premises.
Item
Description
Standards
1.
Insulators
1.1
Temperature cycle test, mechanical
IEC 383 & IEC 575
failing load test
1.2
Porosity test, continuity of zinc
BS 137
coating
1.3
Electrical test on complete insulator
ANSI C-29.1
strings
2.
Insulator Fittings
2.1
Routine and sample mechanical tests
BS 3288
2.2
Galvanizing tests
BS 729
3.
Clamps and joints
3.1
Mechanical and electrical type tests,
BS 3288
galvanizing and mechanical routine
BS 729
tests
ISO
4.
Dampers
4.1
Fatigue resistant tests
4.2
Test of clamp slippage resistance
BS 729
4.3
Galvanizing tests
ISO
5.
Line Conductor and earth wire
5.1
Mechanical test, galvanizing test
IEC 209
and resistivity test, ultimate tensile
BS 2627
stress of complete conductor

Employers representatives will inspect and witness the tests of ACSR Conductors and other
materials at manufacturers plant as listed below.
The number of Employers inspectors for testing different items of equipment and materials
at manufacturers plant shall be as follows:
Item
1.
2.

Description
Insulators and Hardware
ACSR Conductors and Earth wire

No. of Inspectors
Two (2), one visit
Two (2), one visit