Project Name:

2B

Project Notes:
www.ebaa.com contact@ebaa.com 800.433.1716

RESTRAINT LENGTH VALUES


Fitting Type

Pipe
Material

Soil
Type

Safety
Factor

Trench
Type

Depth
of Bury

Test
Pressure

Nominal
Size

Bend
Angle

Horizontal Bend

Ductile Iron

GC

1.5

3.3 Ft.

150 PSI

16 In.

11.25

Site Name:

Branch
Size

Length
Along Run

Reduced
Size

Lowside
Depth

Restraint
Length

Restraint
Length 2

3 Ft.

400DI

Site Notes:

3 Ft.

3 Ft.

ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED


IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.

Defined Variables

Defined Variables

H=

3.3 Depth of Bury

fC =

0.40 Cohesion Modifier Coefficient

Sf =

1.5 Safety Factor

c=

225 Cohesion of Soil

P=

150 Internal Pressure

11.25 Bend Angle

Pipe Derived Variables


A=
D=

237.79 Cross Sec. Area of Pipe

f =
=
=
KN =

1.45 Outside Pipe Diameter

WP =

65.00 Weight of Pipe

WW =

93.00 Weight of Water in Pipe

1.00 Friction Angle Modifier


25 Internal Friction Angle of Soil
100 Soil Density
0.85 Trench Compaction Modifier

Calculations for Horizontal Bend


WE = D H =

478.500

Normal Force Due to Soil

W = 2WE + WP + WW =

1115.000

KP = tan^2(( / 180) (45 + ( / 2))) =

2.464

Rankin Passive Pressure Coeff.

HC = H + (D / 2) =

4.025

Depth From Surface to Pipe Center

h = HC KP + 2cKP =

1698.131

AP = (D / 2) =

2.278

RS = KN h D =

2092.946

FS = AP fC c + W tan(( / 180) f ) =

724.953

L = (SF P A tan(( / 180) ( / 2))) / (FS + (RS / 2)) =

2.975

Normal Force Acting on Pipeline

Horizontal Passive Soil Pressure


Area Based on Half of Circumference
Bearing Resistance of Pipelines
Frictional Resitance
Minimum Restrained Length

MEGALUG

Created by EBAA Iron's Restraint Length Calculator v7.1.2 on August 18, 2015

Project Name:

2B

Project Notes:
www.ebaa.com contact@ebaa.com 800.433.1716

RESTRAINT LENGTH VALUES


Fitting Type

Pipe
Material

Soil
Type

Safety
Factor

Trench
Type

Depth
of Bury

Test
Pressure

Nominal
Size

Bend
Angle

Horizontal Bend

Ductile Iron

GC

1.5

3.3 Ft.

150 PSI

16 In.

22.5

Branch
Size

Length
Along Run

Reduced
Size

Lowside
Depth

Restraint
Length

Restraint
Length 2

7 Ft.

Site Name:
Site Notes:

7 Ft.

7 Ft.

ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED


IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.

Defined Variables

Defined Variables

H=

3.3 Depth of Bury

fC =

0.40 Cohesion Modifier Coefficient

Sf =

1.5 Safety Factor

c=

225 Cohesion of Soil

P=

150 Internal Pressure

f =

22.5 Bend Angle

Pipe Derived Variables


A=
D=

237.79 Cross Sec. Area of Pipe

=
KN =

1.45 Outside Pipe Diameter

WP =

65.00 Weight of Pipe

WW =

93.00 Weight of Water in Pipe

1.00 Friction Angle Modifier


25 Internal Friction Angle of Soil
100 Soil Density
0.85 Trench Compaction Modifier

Calculations for Horizontal Bend


WE = D H =

478.500

Normal Force Due to Soil

W = 2WE + WP + WW =

1115.000

KP = tan^2(( / 180) (45 + ( / 2))) =

2.464

Rankin Passive Pressure Coeff.

HC = H + (D / 2) =

4.025

Depth From Surface to Pipe Center

h = HC KP + 2cKP =

1698.131

AP = (D / 2) =

2.278

RS = KN h D =

2092.946

FS = AP fC c + W tan(( / 180) f ) =

724.953

L = (SF P A tan(( / 180) ( / 2))) / (FS + (RS / 2)) =

6.008

Normal Force Acting on Pipeline

Horizontal Passive Soil Pressure


Area Based on Half of Circumference
Bearing Resistance of Pipelines
Frictional Resitance
Minimum Restrained Length

MEGALUG

Created by EBAA Iron's Restraint Length Calculator v7.1.2 on August 18, 2015

Project Name:

2B

Project Notes:
www.ebaa.com contact@ebaa.com 800.433.1716

RESTRAINT LENGTH VALUES


Fitting Type

Pipe
Material

Soil
Type

Safety
Factor

Trench
Type

Depth
of Bury

Test
Pressure

Nominal
Size

Bend
Angle

Horizontal Bend

Ductile Iron

GC

1.5

3.3 Ft.

150 PSI

16 In.

45

Branch
Size

Length
Along Run

Reduced
Size

Lowside
Depth

Restraint
Length

Restraint
Length 2

13 Ft.

Site Name:
Site Notes:

13 Ft.

13 Ft.

ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED


IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.

Defined Variables

Defined Variables

H=

3.3 Depth of Bury

fC =

0.40 Cohesion Modifier Coefficient

Sf =

1.5 Safety Factor

c=

225 Cohesion of Soil

P=

150 Internal Pressure

45 Bend Angle

Pipe Derived Variables


A=
D=

237.79 Cross Sec. Area of Pipe

f =
=
=
KN =

1.45 Outside Pipe Diameter

WP =

65.00 Weight of Pipe

WW =

93.00 Weight of Water in Pipe

1.00 Friction Angle Modifier


25 Internal Friction Angle of Soil
100 Soil Density
0.85 Trench Compaction Modifier

Calculations for Horizontal Bend


WE = D H =

478.500

Normal Force Due to Soil

W = 2WE + WP + WW =

1115.000

KP = tan^2(( / 180) (45 + ( / 2))) =

2.464

Rankin Passive Pressure Coeff.

HC = H + (D / 2) =

4.025

Depth From Surface to Pipe Center

h = HC KP + 2cKP =

1698.131

AP = (D / 2) =

2.278

RS = KN h D =

2092.946

FS = AP fC c + W tan(( / 180) f ) =

724.953

L = (SF P A tan(( / 180) ( / 2))) / (FS + (RS / 2)) =

12.511

Normal Force Acting on Pipeline

Horizontal Passive Soil Pressure


Area Based on Half of Circumference
Bearing Resistance of Pipelines
Frictional Resitance
Minimum Restrained Length

MEGALUG

Created by EBAA Iron's Restraint Length Calculator v7.1.2 on August 18, 2015

Project Name:

2B

Project Notes:
www.ebaa.com contact@ebaa.com 800.433.1716

RESTRAINT LENGTH VALUES


Fitting Type

Pipe
Material

Soil
Type

Safety
Factor

Trench
Type

Depth
of Bury

Test
Pressure

Nominal
Size

Bend
Angle

Horizontal Bend

Ductile Iron

GC

1.5

3.3 Ft.

150 PSI

16 In.

90

Branch
Size

Length
Along Run

Reduced
Size

Lowside
Depth

Restraint
Length

Restraint
Length 2

31 Ft.

Site Name:
Site Notes:

31 Ft.

31 Ft.

ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED


IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.

Defined Variables

Defined Variables

H=

3.3 Depth of Bury

fC =

0.40 Cohesion Modifier Coefficient

Sf =

1.5 Safety Factor

c=

225 Cohesion of Soil

P=

150 Internal Pressure

90 Bend Angle

Pipe Derived Variables


A=
D=

237.79 Cross Sec. Area of Pipe

f =
=
=
KN =

1.45 Outside Pipe Diameter

WP =

65.00 Weight of Pipe

WW =

93.00 Weight of Water in Pipe

1.00 Friction Angle Modifier


25 Internal Friction Angle of Soil
100 Soil Density
0.85 Trench Compaction Modifier

Calculations for Horizontal Bend


WE = D H =

478.500

Normal Force Due to Soil

W = 2WE + WP + WW =

1115.000

KP = tan^2(( / 180) (45 + ( / 2))) =

2.464

Rankin Passive Pressure Coeff.

HC = H + (D / 2) =

4.025

Depth From Surface to Pipe Center

h = HC KP + 2cKP =

1698.131

AP = (D / 2) =

2.278

RS = KN h D =

2092.946

FS = AP fC c + W tan(( / 180) f ) =

724.953

L = (SF P A tan(( / 180) ( / 2))) / (FS + (RS / 2)) =

30.203

Normal Force Acting on Pipeline

Horizontal Passive Soil Pressure


Area Based on Half of Circumference
Bearing Resistance of Pipelines
Frictional Resitance
Minimum Restrained Length

MEGALUG

Created by EBAA Iron's Restraint Length Calculator v7.1.2 on August 18, 2015

Project Name:

2B

Project Notes:
www.ebaa.com contact@ebaa.com 800.433.1716

RESTRAINT LENGTH VALUES


Fitting Type

Pipe
Material

Soil
Type

Safety
Factor

Trench
Type

Depth
of Bury

Test
Pressure

Nominal
Size

Tee

Ductile Iron

GC

1.5

3.3 Ft.

150 PSI

16 In.

Bend
Angle

Branch
Size

Length
Along Run

4 In.

5 Ft.

Reduced
Size

Lowside
Depth

Restraint
Length

Restraint
Length 2

1 Ft.

Site Name:
Site Notes:

1 Ft.

ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED


IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.

Defined Variables

Defined Variables

H=

3.3 Depth of Bury

fC =

0.40 Cohesion Modifier Coefficient

Sf =

1.5 Safety Factor

c=

225 Cohesion of Soil

P=

150 Internal Pressure

f =
=

Pipe Derived Variables


A=

237.79 Cross Sec. Area (Main)

Ab =

18.10 Cross Sec. Area (Branch)

D=

1.45 Outside Pipe Diameter

Db =

0.40 Outside Diameter Branch

WP =
WW =
Lr =

13.00 Weight of Pipe


6.00 Weight of Water in Pipe
5 Min. restrained Length
either side of Tee

1.00 Friction Angle Modifier


25 Internal Friction Angle of Soil
100 Soil Density

Calculations for Tee


WE = D H =

132.000

Normal Force Due to Soil

W = 2WE + WP + WW =

283.000

Normal Force Acting on Pipeline

KP = tan^2(( / 180) (45 + ( / 2))) =

2.464

Rankin Passive Pressure Coeff.

HC = H + (D / 2) =

4.025

Depth From Surface to Pipe Center

h = HC KP + 2cKP =

1698.131

AP = (D / 2) =

2.278

Area Based on Half of Circumference

(Ap)b = Db =

1.257

Area Based on Full Branch Circumference

RS = KN h D =

2092.946

Fsb = (Ap)b fC c + W tan(( / 180) f ) =

245.095

Frictional Resistance

Lb = Sf(P Ab - RS Lr) / Fsb =

-47.429

Minimum Restrained Length Branch

Horizontal Passive Soil Pressure

Bearing Resistance of Pipelines

MEGALUG

Created by EBAA Iron's Restraint Length Calculator v7.1.2 on August 18, 2015

Project Name:

2B

Project Notes:
www.ebaa.com contact@ebaa.com 800.433.1716

RESTRAINT LENGTH VALUES


Fitting Type

Pipe
Material

Soil
Type

Safety
Factor

Trench
Type

Depth
of Bury

Test
Pressure

Nominal
Size

Tee

Ductile Iron

GC

1.5

3.3 Ft.

150 PSI

16 In.

Bend
Angle

Branch
Size

Length
Along Run

12 In.

6 Ft.

Reduced
Size

Lowside
Depth

Restraint
Length

Restraint
Length 2

18 Ft.

Site Name:
Site Notes:

18 Ft.

ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED


IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.

Defined Variables

Defined Variables

H=

3.3 Depth of Bury

fC =

0.40 Cohesion Modifier Coefficient

Sf =

1.5 Safety Factor

c=

225 Cohesion of Soil

P=

150 Internal Pressure

f =
=

Pipe Derived Variables


A=

237.79 Cross Sec. Area (Main)

Ab =

136.85 Cross Sec. Area (Branch)

D=

1.45 Outside Pipe Diameter

Db =

1.10 Outside Diameter Branch

WP =

40.00 Weight of Pipe

WW =

56.00 Weight of Water in Pipe

Lr =

6 Min. restrained Length


either side of Tee

1.00 Friction Angle Modifier


25 Internal Friction Angle of Soil
100 Soil Density

Calculations for Tee


WE = D H =

363.000

Normal Force Due to Soil

W = 2WE + WP + WW =

822.000

Normal Force Acting on Pipeline

KP = tan^2(( / 180) (45 + ( / 2))) =

2.464

Rankin Passive Pressure Coeff.

HC = H + (D / 2) =

4.025

Depth From Surface to Pipe Center

h = HC KP + 2cKP =

1698.131

AP = (D / 2) =

2.278

Area Based on Half of Circumference

(Ap)b = Db =

3.456

Area Based on Full Branch Circumference

RS = KN h D =

2092.946

Fsb = (Ap)b fC c + W tan(( / 180) f ) =

694.345

Lb = Sf(P Ab - RS Lr) / Fsb =

17.217

Horizontal Passive Soil Pressure

Bearing Resistance of Pipelines


Frictional Resistance
Minimum Restrained Length Branch

MEGALUG

Created by EBAA Iron's Restraint Length Calculator v7.1.2 on August 18, 2015

Project Name:

2B

Project Notes:
www.ebaa.com contact@ebaa.com 800.433.1716

RESTRAINT LENGTH VALUES


Fitting Type

Pipe
Material

Soil
Type

Safety
Factor

Trench
Type

Depth
of Bury

Test
Pressure

Nominal
Size

Tee

Ductile Iron

GC

1.5

3.3 Ft.

150 PSI

16 In.

Bend
Angle

Branch
Size

Length
Along Run

6 In.

3 Ft.

Reduced
Size

Lowside
Depth

Restraint
Length

Restraint
Length 2

1 Ft.

Site Name:
Site Notes:

1 Ft.

ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED


IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.

Defined Variables

Defined Variables

H=

3.3 Depth of Bury

fC =

0.40 Cohesion Modifier Coefficient

Sf =

1.5 Safety Factor

c=

225 Cohesion of Soil

P=

150 Internal Pressure

f =
=

Pipe Derived Variables


A=

237.79 Cross Sec. Area (Main)

Ab =

37.39 Cross Sec. Area (Branch)

D=

1.45 Outside Pipe Diameter

Db =

0.58 Outside Diameter Branch

WP =

18.00 Weight of Pipe

WW =

14.00 Weight of Water in Pipe

Lr =

3 Min. restrained Length


either side of Tee

1.00 Friction Angle Modifier


25 Internal Friction Angle of Soil
100 Soil Density

Calculations for Tee


WE = D H =

191.400

Normal Force Due to Soil

W = 2WE + WP + WW =

414.800

Normal Force Acting on Pipeline

KP = tan^2(( / 180) (45 + ( / 2))) =

2.464

Rankin Passive Pressure Coeff.

HC = H + (D / 2) =

4.025

Depth From Surface to Pipe Center

h = HC KP + 2cKP =

1698.131

AP = (D / 2) =

2.278

Area Based on Half of Circumference

(Ap)b = Db =

1.822

Area Based on Full Branch Circumference

RS = KN h D =

2092.946

Fsb = (Ap)b fC c + W tan(( / 180) f ) =

357.404

Lb = Sf(P Ab - RS Lr) / Fsb =

-2.813

Horizontal Passive Soil Pressure

Bearing Resistance of Pipelines


Frictional Resistance
Minimum Restrained Length Branch

MEGALUG

Created by EBAA Iron's Restraint Length Calculator v7.1.2 on August 18, 2015

Project Name:

2B

Project Notes:
www.ebaa.com contact@ebaa.com 800.433.1716

RESTRAINT LENGTH VALUES


Fitting Type

Pipe
Material

Soil
Type

Safety
Factor

Trench
Type

Depth
of Bury

Test
Pressure

Nominal
Size

Tee

Ductile Iron

GC

1.5

3.3 Ft.

150 PSI

16 In.

Bend
Angle

Branch
Size

Length
Along Run

8 In.

6 Ft.

Reduced
Size

Lowside
Depth

Restraint
Length

Restraint
Length 2

1 Ft.

Site Name:
Site Notes:

1 Ft.

ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED


IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.

Defined Variables

Defined Variables

H=

3.3 Depth of Bury

fC =

0.40 Cohesion Modifier Coefficient

Sf =

1.5 Safety Factor

c=

225 Cohesion of Soil

P=

150 Internal Pressure

f =
=

Pipe Derived Variables


A=

237.79 Cross Sec. Area (Main)

Ab =

64.33 Cross Sec. Area (Branch)

D=

1.45 Outside Pipe Diameter

Db =

0.75 Outside Diameter Branch

WP =

26.00 Weight of Pipe

WW =

24.00 Weight of Water in Pipe

Lr =

6 Min. restrained Length


either side of Tee

1.00 Friction Angle Modifier


25 Internal Friction Angle of Soil
100 Soil Density

Calculations for Tee


WE = D H =

247.500

Normal Force Due to Soil

W = 2WE + WP + WW =

545.000

Normal Force Acting on Pipeline

KP = tan^2(( / 180) (45 + ( / 2))) =

2.464

Rankin Passive Pressure Coeff.

HC = H + (D / 2) =

4.025

Depth From Surface to Pipe Center

h = HC KP + 2cKP =

1698.131

AP = (D / 2) =

2.278

Area Based on Half of Circumference

(Ap)b = Db =

2.356

Area Based on Full Branch Circumference

RS = KN h D =

2092.946

Fsb = (Ap)b fC c + W tan(( / 180) f ) =

466.178

Lb = Sf(P Ab - RS Lr) / Fsb =

-9.358

Horizontal Passive Soil Pressure

Bearing Resistance of Pipelines


Frictional Resistance
Minimum Restrained Length Branch

MEGALUG

Created by EBAA Iron's Restraint Length Calculator v7.1.2 on August 18, 2015

Project Name:

2B

Project Notes:
www.ebaa.com contact@ebaa.com 800.433.1716

RESTRAINT LENGTH VALUES


Fitting Type

Pipe
Material

Soil
Type

Safety
Factor

Trench
Type

Depth
of Bury

Test
Pressure

Nominal
Size

Tee

Ductile Iron

GC

1.5

3.3 Ft.

150 PSI

10 In.

Bend
Angle

Branch
Size

Length
Along Run

16 In.

1 Ft.

Reduced
Size

Lowside
Depth

Restraint
Length

Restraint
Length 2

56 Ft.

Site Name:
Site Notes:

56 Ft.

ALL JOINTS WITHIN THE CALCULATED LENGTH MUST BE RESTRAINED


IF YOUR DISTANCE BETWEEN FITTINGS IS LESS THAN OR EQUAL TO THE CALCULATED RESTRAINT LENGTH, RESTRAIN ALL JOINTS BETWEEN THOSE FITTINGS.

Defined Variables

Defined Variables

H=

3.3 Depth of Bury

fC =

0.40 Cohesion Modifier Coefficient

Sf =

1.5 Safety Factor

c=

225 Cohesion of Soil

P=

150 Internal Pressure

f =
=

Pipe Derived Variables


A=

96.77 Cross Sec. Area (Main)

Ab =

237.79 Cross Sec. Area (Branch)

D=

0.93 Outside Pipe Diameter

Db =

1.45 Outside Diameter Branch

WP =

65.00 Weight of Pipe

WW =

93.00 Weight of Water in Pipe

Lr =

1 Min. restrained Length


either side of Tee

1.00 Friction Angle Modifier


25 Internal Friction Angle of Soil
100 Soil Density

Calculations for Tee


WE = D H =

478.500

Normal Force Due to Soil

W = 2WE + WP + WW =

1115.000

KP = tan^2(( / 180) (45 + ( / 2))) =

2.464

Rankin Passive Pressure Coeff.

HC = H + (D / 2) =

3.765

Depth From Surface to Pipe Center

h = HC KP + 2cKP =

1634.067

AP = (D / 2) =

1.461

Area Based on Half of Circumference

(Ap)b = Db =

4.555

Area Based on Full Branch Circumference

RS = KN h D =

1291.730

Fsb = (Ap)b fC c + W tan(( / 180) f ) =

929.883

Lb = Sf(P Ab - RS Lr) / Fsb =

55.453

Normal Force Acting on Pipeline

Horizontal Passive Soil Pressure

Bearing Resistance of Pipelines


Frictional Resistance
Minimum Restrained Length Branch

MEGALUG

Created by EBAA Iron's Restraint Length Calculator v7.1.2 on August 18, 2015