PROJECT:

OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS TRANSFORMER INCOMER CABLE


1
2

Load Taken For Calculation

Electrolyser Transformer-1 Load 630KVA

Full load current :

KVA X 1000 / (415 X 3)


630 X 1000 / (415 X 1.732)

Amps

876.485155

Overall cable derating factor:

Group derating factor x Ambient derating factor


= 0.73 x 0.9
0.657

Uprated Currents :

FLC/ Overall cable derating factor.


876.5/0.702

Amps

1334.07177

Protection

ACB Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3Run X 3Core 300 Sqmm. Al XLPE Cable

Current rating of 3Run X 3Core 300 Sqmm. Al XLPE Cable Amps (A)

452*3

Amps 1356
9

10
11

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

876.5

e) AC resistance of the cable (Ohms/km) (Rac)

0.130

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.750

c) No. of cable runs (N)

3.0

g) AC reactance of the cable (Ohms/km) (X)

0.0703

d) Cable Length (L)

50.0

h) Sin

0.661

Voltage drop in %

0.87792

Voltage drop in volt


Permissible Voltage drop in % for transformer

3.64335

Conculation

3% on operation
3Run X 3Core 300 Sqmm. Al XLPE Cable satisfies all requirements
Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECP FEED PUMP MOTOR


1
2
3

Motor Load
Full load current :
Overall cable derating factor:

55 KW
95
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

152.979066

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3Core 185 Sqmm. Al XLPE Cable

Current rating of 3Core 185 Sqmm. Al XLPE Cable Amps (A)

329

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

95.0

e) AC resistance of the cable (Ohms/km) (Rac)

0.212

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.860

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.0720

d) Cable Length (L)

300.0

h) Sin

0.510

Voltage drop in %

2.60561

Voltage drop in volt

10.81330

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

570.0

e) AC resistance of the cable (Ohms/km) (Rac)

0.212

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.300

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.072

d) Cable Length (L)

300.0

h) Sin

0.954

Voltage drop in %

9.44065

Voltage drop in volt


Permissible Voltage drop in % for motor

39.17871

Conculation

3Core 185 Sqmm. Al XLPE Cable satisfies all requirements

Amps 329

10
11

15% on operation

Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS STRAINER BACKWASH MOTOR


1
2
3

Motor Load
Full load current :
Overall cable derating factor:

0.37 KW
1.1
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

1.77133655

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3 Corex2.5 Sqmm. Cu XLPE Cable

Current rating of 3Cx2.5 Sqmm. Cu XLPE Cable Amps (A)

29
Amps 29

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

1.1

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.860

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

57.0

h) Sin

0.510

Voltage drop in %

0.21399

Voltage drop in volt

0.88805

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

6.6

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.340

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

57.0

h) Sin

0.940

Voltage drop in %

0.51908

Voltage drop in volt


Permissible Voltage drop in % for motor

2.15418

Conculation

3Core 2.5 Sqmm. Cu XLPE Cable satisfies all requirements

10
11

15% on operation
Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS HYDROGEN DILUTION BLOWER MOTOR


1
2
3

Motor Load
Full load current :
Overall cable derating factor:

7.5 KW
14.8
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

23.8325282

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3Core 6 Sqmm. Al XLPE Cable

Current rating of 3C X 6 Sqmm. Al XLPE Cable Amps (A)

42
Amps 42

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

14.8

e) AC resistance of the cable (Ohms/km) (Rac)

5.910

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.780

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.088

d) Cable Length (L)

55.0

h) Sin

0.626

Voltage drop in %

1.58470

Voltage drop in volt

6.57649

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

88.8

e) AC resistance of the cable (Ohms/km) (Rac)

5.910

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.340

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.088

d) Cable Length (L)

55.0

h) Sin

0.940

Voltage drop in %

4.26394

Voltage drop in volt


Permissible Voltage drop in % for motor

17.69536

Conculation

3CoreX6 Sqmm. Al XLPE Cable satisfies all requirements

10
11

15% on operation

Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS DILUTION LINE BOOSTER PUMP MOTOR
1
2
3

Motor Load
Full load current :
Overall cable derating factor:

7.5 KW
13.4
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

21.5780998

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3Core 6 Sqmm. Al XLPE Cable

Current rating of 3C X 6 Sqmm. Al XLPE Cable Amps (A)

42
Amps 42

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

13.4

e) AC resistance of the cable (Ohms/km) (Rac)

5.910

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.860

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.088

d) Cable Length (L)

63.0

h) Sin

0.510

Voltage drop in %

1.80650

Voltage drop in volt

7.49698

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

80.4

e) AC resistance of the cable (Ohms/km) (Rac)

5.910

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.340

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.088

d) Cable Length (L)

63.0

h) Sin

0.940

Voltage drop in %

4.42214

Voltage drop in volt


Permissible Voltage drop in % for motor

18.35187

Conculation

3CoreX6 Sqmm. Al XLPE Cable satisfies all requirements

10
11

15% on operation

Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS ACID CLEANING PUMP MOTOR


1
2
3

Motor Load
Full load current :
Overall cable derating factor:

3.7 KW
6.9
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

11.1111111

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3 Corex2.5 Sqmm. Cu XLPE Cable

Current rating of 3Cx2.5 Sqmm. Cu XLPE Cable Amps (A)

29
Amps 29

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

6.9

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.860

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

67.0

h) Sin

0.510

Voltage drop in %

1.57778

Voltage drop in volt

6.54777

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

41.4

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.340

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

67.0

h) Sin

0.940

Voltage drop in %

3.82729

Voltage drop in volt


Permissible Voltage drop in % for motor

15.88325

Conculation

3Core 2.5 Sqmm. Cu XLPE Cable satisfies all requirements

10
11

15% on operation

Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS ALKALI TRANSFER PUMP MOTOR


1
2
3

Motor Load
Full load current :
Overall cable derating factor:

1.5 KW
2.95
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

4.75040258

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3 Corex2.5 Sqmm. Cu XLPE Cable

Current rating of 3Cx2.5 Sqmm. Cu XLPE Cable Amps (A)

29
Amps 29

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

3.0

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.870

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

63.0

h) Sin

0.493

Voltage drop in %

0.64148

Voltage drop in volt

2.66215

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

17.7

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.340

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

63.0

h) Sin

0.940

Voltage drop in %

1.53861

Voltage drop in volt


Permissible Voltage drop in % for motor

6.38525

Conculation

3Core 2.5 Sqmm. Cu XLPE Cable satisfies all requirements

10
11

15% on operation
Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS NEUTRAIZATION PIT BLOWER MOTOR


1
2
3

Motor Load
Full load current :
Overall cable derating factor:

3.7 KW
7.3
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

11.75523349

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3 Corex2.5 Sqmm. Cu XLPE Cable

Current rating of 3Cx2.5 Sqmm. Cu XLPE Cable Amps (A)

29
Amps 29

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

7.3

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.820

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

74.0

h) Sin

0.572

Voltage drop in %

1.75980

Voltage drop in volt

7.30319

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

43.8

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.340

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

74.0

h) Sin

0.940

Voltage drop in %

4.47221

Voltage drop in volt


Permissible Voltage drop in % for motor

18.560

Conculation

3Core 2.5 Sqmm. Cu XLPE Cable satisfies all requirements

10
11

15% on operation

Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS NEUTRAIZATION PIT TRANSFER PUMP MOTOR
1
2
3

Motor Load
Full load current :
Overall cable derating factor:

15 KW
27.8
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

44.7665056

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3Core 16 Sqmm. Al XLPE Cable

Current rating of 3C X 25 Sqmm. Al XLPE Cable Amps (A)

93
Amps 93

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

27.8

e) AC resistance of the cable (Ohms/km) (Rac)

1.540

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.830

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.081

d) Cable Length (L)

75.0

h) Sin

0.558

Voltage drop in %

1.15147

Voltage drop in volt

4.77861

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

166.8

e) AC resistance of the cable (Ohms/km) (Rac)

1.540

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.330

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.081

d) Cable Length (L)

75.0

h) Sin

0.944

Voltage drop in %

3.05156

Voltage drop in volt


Permissible Voltage drop in % for motor

12.66398

Conculation

3CoreX25 Sqmm. Al XLPE Cable satisfies all requirements

10
11

15% on operation

Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS CW SYSTEM HYPO DOSING PUMP MOTOR
1
2
3

Motor Load
Full load current :
Overall cable derating factor:

22 KW
40
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

64.4122383

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3Core 25 Sqmm. Al XLPE Cable

Current rating of 3C X 25 Sqmm. Al XLPE Cable Amps (A)

93
Amps 93

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

40.0

e) AC resistance of the cable (Ohms/km) (Rac)

1.540

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.840

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.0808

d) Cable Length (L)

57.0

h) Sin

0.543

Voltage drop in %

1.27265

Voltage drop in volt

5.28150

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

240.0

e) AC resistance of the cable (Ohms/km) (Rac)

1.540

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.330

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.0808

d) Cable Length (L)

57.0

h) Sin

0.944

Voltage drop in %

3.33696

Voltage drop in volt


Permissible Voltage drop in % for motor

13.84838

Conculation

3CoreX25 Sqmm. Al XLPE Cable satisfies all requirements

10
11

15% on operation

Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS SWI SYSTEM HYPO DOSING PUMP MOTOR
1
2
3

Motor Load
Full load current :
Overall cable derating factor:

11 KW
19
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

30.5958132

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3Core 10 Sqmm. Al XLPE Cable

Current rating of 3C X 10 Sqmm. Al XLPE Cable Amps (A)

54
Amps 54

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

19.0

e) AC resistance of the cable (Ohms/km) (Rac)

3.950

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.900

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.084

d) Cable Length (L)

55.0

h) Sin

0.436

Voltage drop in %

1.56641

Voltage drop in volt

6.50061

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

114.0

e) AC resistance of the cable (Ohms/km) (Rac)

3.950

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.330

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.084

d) Cable Length (L)

55.0

h) Sin

0.944

Voltage drop in %

3.61847

Voltage drop in volt


Permissible Voltage drop in % for motor

15.01665

Conculation

3CoreX10 Sqmm. Al XLPE Cable satisfies all requirements

10
11

15% on operation

Selection of this cable is correct.

PROJECT:
OWNER :
CONTRACTOR :
CONTRACTOR CONSULTANT:
OWNER'S CONSULTANT:
SYSTEM :

2 X 660 MW NCC POWER PROJECT, NELLORE DISTRICT, A.P.


NCC POWER PROJECTS LIMITED
NCC LIMITED
L&T-SARGENT & LUNDY LIMITED
TATA CONSULTING ENGINEERS LIMITED
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF PMCC TO ECS RW SYSTEM HYPO DOSING PUMP MOTOR
1
2
3

Motor Load
Full load current :
Overall cable derating factor:

2.2 KW
4.6
Group derating factor x Ambient derating factor
= 0.69 x 0.9
0.621

Uprated Currents :

FLC/ Overall cable derating factor.

Amps

7.40740741

Protection

Fuse Protection

Minimum cable size for Short circuit current rating

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm

For fuse protected cable

Aluminum cable are consider for 415V, 50Hz, AC 3PH

Cable selected:

3 Corex2.5 Sqmm. Cu XLPE Cable

Current rating of 3Cx2.5 Sqmm. Cu XLPE Cable Amps (A)

29
Amps 29

% of voltage drop for Running

3xIfl x L x (Rac x cos + X x sin) x 100/(Vn x 1000 x N)

a) Full Load Current in Amps (Ifl)

4.6

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Power Factor (Cos )

0.810

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

54.0

h) Sin

0.586

Voltage drop in %

0.79956

Voltage drop in volt

3.31816

10

Permissible Voltage drop in % for motor

3% on operation

10

% of voltage drop for Starting

3xIst x L x (Rac x cosst + X x sin) x 100/(Vn x 1000 x N)

a) Starting Current in Amps (Ist)

27.6

e) AC resistance of the cable (Ohms/km) (Rac)

9.450

b) Norminal Line Voltage in Volt (Vn)

415.0

f) Starting Power Factor (Cos st)

0.340

c) No. of cable runs (N)

1.0

g) AC reactance of the cable (Ohms/km) (X)

0.099

d) Cable Length (L)

54.0

h) Sin

0.940

Voltage drop in %

2.05645

Voltage drop in volt


Permissible Voltage drop in % for motor

8.53428

Conculation

3Core 2.5 Sqmm. Cu XLPE Cable satisfies all requirements

10
11

15% on operation

Selection of this cable is correct.

IEC DWG NO
NTPC_DRG_NO
PROJECT
CUSTOMER
NAME OF VENDOR

SYSTEM

IEC-W1309-060
0260-139-PVE-U-002
VALLUR THERMAL POWER PROJECT
NTPC TAMIL NADU ENERGY COMPANY LIMITED,CHENNAI
IEC FABCHEM LIMITED, Chennai.
ELECTRO CHLORINATION SYSTEM.

CABLE SIZING CALACULATION OF MAIN CABLES FOR ELECTRO CHLORINATION PLANT

1 Load Taken For Calculation


2 Full load current :

Process Load 230kW + Owners Load 40kW(50kVA) = 270kW

kW x 1000/(3 x V x cos x Efficiency)


270 X 1000/(1.732 X 415 X 0.85(PF) X 0.95(Efficiency)
Amps 465.2

3 Overall cable derating factor:

Group derating factor x Ambient derating factor


= 0.79 x 0.9
0.71

4 Uprated Currents :

FLC/ Overall cable derating factor.

465.2/0.71
Amps 655
5 Protection

Fuse Protection

6 Minimum cable size for Short circuit current rating


For fuse protected cable

Minimum cable size of 2.5 sq mm copper and 6.0 sq mm


Aluminum cable are consider for 433V, 50Hz, AC 3PH
and Earthed Neutral system.

7 Cable selected:

4R X Single Core 630sqmm. Al. Ar. FRLS. XLPE Cable

8 Current rating of Single Core 630sqmm. Al. Ar. FRLS. XLPE Cable
As per IS:

814A

9 % of voltage drop for Running current of 460.9A

3xIrx L x (Rac x cos + X x sin) x 100/(V x 1000)


3 x 465.2 x 50(0.065 x 0.85 + 0.075 x 0.017) x 100\(415 x 1000)

of 50 meter length cable :

% 0.5487190935
10 Permissible Voltage drop in %

2.5% on running operation

11 % of voltage drop for Starting current :

% of Voltage drop of Running current x 3.5 times

0.55 x 3.5
% 1.925
12 Permissible Voltage drop

10% at starting

13 Conculation

4R X Single Core 630sqmm. Al. Ar. FRLS. XLPE Cable satisfies all requirements

Selection of this cable is correct.