Professional Documents
Culture Documents
Chapter 3 Full
Chapter 3 Full
[3-1]
Fig 3-1: Layout showing most sheet metal parts used in conditioned air duct system.
[3-2]
In basements, the conditioned-air main duct is run across and just under the floor joists.
The branch ducts, round or rectangular, are then run between the joists to the grille or
diffuser openings. The return ducts usually use the joists and the floorboards for three
sides of the branch ducts (panned joists space) and then run the main return duct
alongside the conditioned air duct.
[3-3]
Fig 3-3:-Typical warm air grille. Many are supplied with controls for adjusting size
of opening, and to redirect airflow.
[3-4]
Fig 3-5:- Rectangular grille with adjustable airflow vanes. A- horizontal flow. BVertical flow. C- Horizontal flow. D Adjustment.
Dampers
Without some way of controlling airflow in forced air systems, some spaces would not
get enough. One method of getting even air distribution is through the use of duct
dampers.
These dampers balance airflows or they can shut off or open certain ducts for zone
control. Such a damper is shown in Fig 3-6. Some are located in the diffuser or grille,
some are in the duct itself. They are of three types:
1. Butterfly
2. Multiple blade
3. Split damper
All three types are shown in Fig 3-7. There are two types of multiple blade dampers: the
parallel blade type (Fig 3-8) and the opposed blade type (Fig 3-9). When installing a
damper, always draw a line on the end of the damper shaft that extends out of the duct to
show the position of the dampers.
For accurate air control these dampers should be tight fitting with minimum leakage.
Many are automatically controlled for either zone heating or cooling. Automatic controls
are also used to mix two airflows for either fresh air and recirculated air mixes, for
[3-5]
humidity control or for temperature control. These multiple dampers are interlocked by
controls to provide different mixes and to maintain correct total airflow.
Fig 3-6:- Three-vane adjustable damper controls airflow in duct. These dampers
may be operated either manually or automatically.
Fig 3-7:- Three types of duct airflow controls. These dampers are used to adjust
airflow volumes to help service technicians balance the system.
[3-6]
[3-7]
[3-8]
Fig 3-11:- Fire damper in open position. A-Damper vanes. B-Fusible link. If link is
heated, it will melt and vanes will fall, closing duct.
Duct Calculations
In a cooling system where a duct serves more than one room, the duct must be designed
so that each room being served receives the correct amount of air. If the distribution is
not balanced, one room will be too warm while another will be cold.
Two methods used to calculate the proper size of plenum chambers, main ducts, branch
ducts and grilles are:
1. Unit pressure drop system
2. Total pressure drop system.
Unit Pressure Drop System
Air forced through a duct follows the path of least resistance. Many air conditioning duct
systems have several openings (grilles) for the air to escape from the duct. A duct with
low resistance will allow most of the air to flow through it while other ducts with higher
resistance will not carry the correct amount of air.
[3-9]
In the past, many duct installations were made that fed too much air to some rooms and
did not heat or cool other rooms sufficiently.
The unit pressure drop calculating system uses the same pressure drop for each length of
duct throughout the system.
For example, suppose that the total heat load during the heating season is 80,000 Btu/hr,
that there are six rooms with heat loads as follows:
1. Living room
2. Dining room
3. Kitchen
4. Bathroom
5. Bedroom No. 1
6. Bedroom No. 2
= 25,000 Btu/hr
= 15,000 Btu/hr
= 5000 Btu/hr
= 8000 Btu/hr
= 15,000 Btu/hr
= 12,000 Btu/hr
Referring back to the problem, one can work out the air volume needed to heat these six
rooms. Recall the specific heat of air is 0.24 and that the volume of one pound of air is
15.28 cu. ft. Therefore:
Btu/cu. Ft./hr. for a 68 F. (38 C) change =
15.28 = .936 Btu/cu. Ft./hr.
0.24 x 68
Divide by 60 (to get the answer into minutes) one gets 0.0156 Btu/cu. Ft./min.
Knowing the amount of heat that must be carried to each room per minute, one can work
out the volumes required per minute for each room :
1. Living room
25,000 x 0.0156 = 390 cu. ft./min.
2. Dining room
15,000 x 0.0156 = 234 cu. ft./min.
3. Kitchen
5000 x 0.0156 = 78 cu. ft./min.
4. Bathroom
8000 x 0.0156 = 124.8 cu. ft./min.
5. Bedroom No. 1
15,000 x 0.0156 = 234 cu. ft./min.
6. Bedroom No. 2
12,000 x 0.0156 = 187.2 cu. ft./min.
The total air volume is 1248 cu. ft./min.
To determine duct sizes that will handle the air volumes specified in this problem, data
must be obtained about airflow. Fig 3-12 are friction air charts for straight ducts. Values
were obtained by research. These charts have four variables :
1. Friction loss in inches of water on the horizontal scale (equal value lines are
vertical).
2. Cubic feet of air/min. on the vertical scale (equal value lines are horizontal)
3. Velocity on scale line that slant down to right
4. Round duct diameter on scale lines that slant down to left
To continue with the problem, the main duct must handle 1248 cu. ft./min.
[3-10]
To keep the velocity to a low noise level, a friction loss of .04 in water column per 100 ft.
(30.5m) should be used.
On the chart, these two value meet and show that the velocity will be 700 ft./min. (214
m/min.), and the round duct will be 18 in. (46 cm) in diameter.
Using the same friction loss for the branch ducts, one gets the following round duct sizes:
1. Living room
2. Dining room
3. Kitchen
4. Bathroom
5. Bedroom No. 1
6. Bedroom No. 2
These velocities are reasonably low and the system would work. However, the total
pressure drop system is a more accurate method.
Round duct diameters may be changed to rectangular duct sizes. When changing round
duct sizes to rectangular duct sizes, remember that partition ducts basement should have
the same depth for better appearance. This also makes concealment of the ducts easier
where the basement is used as recreation space or living quarters. In most installations,
basement ducts should not exceed 8 in. in depth.
[3-11]
Fig 3-13 :- A typical duct installation. Longest air path is shown in red.
[3-12]
To be sure that the correct air volume leaves each outlet, each must have correct, equal
amount of total air pressure drop.
The method followed is to determine the longest and most complicated duct. This
combination includes ducts A, B, C, D, E, and F.
Assume a total pressure drop of .04 in. (0.1 cm) of water. This total means that the
pressure drop to each room outlet must be 0.04 in. For example, the opening to the
bathroom is the shortest overall distance. It must have the same total pressure drop as the
longest run through F.
An important part of this duct design is that the bends and elbows must be considered
when determining pressure drop. Generally speaking, the pressure drop of one elbow is
equal to 10 diameters of the duct. Assuming there is one large bend above the furnace
and that the grilles are located at the 7-ft. level in the room, the total length of duct A, B,
C, D, E and F is approximately:
Elbow (18 x 10)
A
Elbow (16 x 10)
B
C
D
E
15ft. (4.6m)
12 ft. (3.8m)
13 ft. (4.0m)
2 ft. (0.6m)
8 ft. (2.4m)
2 ft. (0.6m)
4 ft. (1.2m)
[3-13]
Elbow (9 x 10)
F
Elbow
Vertical rise
Elbow
8 ft. (2.4m)
8 ft. (2.4m)
8 ft. (2.4m)
7 ft. (21.m)
8 ft. (2.4m)
95 ft. (28.9m)
The total length (equivalent) is 95 ft. Because the 0.04 in. pressure drop was for 100 ft.
(30.5 m), the new pressure drop for the equivalent feet of duct is :
100 x 0.04 = 20 x 0.04 = 0.8 = 0.042 in. (0.105 cm) water
95
19
19
However, more important than this factor is the pressure drop in each section of the
longest duct:
Pressure drop in each part equals pressure drop/100 ft. multiplied by the ratio of length of
part to longest equivalent length.
Total
.04 in. (0.1cm) of water column pressure drop.
[3-14]
Knowing the pressure drop in each part of the longest duct, now determine the pressure
loss up to each branch duct. Then, from this value and the length of the branch duct,
determine the pressure loss per 100ft. (30.5m) for the branch duct.
For example, consider the kitchen duct:
The pressure loss up to the kitchen branch duct is the sum of all pressure losses along the
way. Thus, 0.0063 + 0.0050 + 0.0055 + 0.0008 + 0.0034 + 0.0008 = 0.0218, which is the
total pressure drop.
If the total pressure drop to the outlet at the kitchen must equal 0.04 in. (0.1cm) water,
then, 0.0400 - 0.0218 = 0.0182 as the pressure drop in the kitchen branch. Assuming 87
cu. ft./min. (2.5 cu. m/min.) volume and 0.04 in. (0.1 cm) pressure drop, the kitchen
branch has length equal to the following :
Elbow (6.9 in. x 10) = 6ft. (1.8m)
Riser
= 7ft. (2.1m)
Elbow (6.9 in. x 10) = 6ft. (1.8m)
Total
19ft. (5.7m)
If the pressure drop in 19ft. is 0.0182, the pressure drop per
100 ft. = 0.0182 x 100 = 1.82 = 0.096 in. water/100 ft.
19
19
From the graph, using a volume of 87.73 cu. ft./min. and the resistance of 0.096, the
following data is obtained: Size = 5.8 in. (14.7 cm) dia. Velocity = 530 cu. ft./min. (15
cu. m/min.)
Compare this method with the unit pressure drop values. Notices how these values differ.
One calculates comfort cooling air in about the same way. If the cold air duct is exposed
to warm, moist air, condensation on the outside surface of the duct may cause corrosion.
Moisture may also drip on structural parts and cause damage. In such cases, ducts should
be insulated.
Balancing The System
Balancing means sizing the ducts and adjusting the dampers to ensure that each room
receives the correct amount of air. Conditioned air must be fed in the right amounts to
each different room of a multiple room system (home or office).
Also the correct amount of air must be returned. If the system is not balanced, rooms will
maintain different temperatures, some ducts will be noisy, some will have incorrect
humidity, and some will have stale air.
[3-15]
To total air balance (TAB) a system, one must measure the air velocity leaving each grille
and determine how much free area the grille or diffuser has. The free area is the
actual size of the air openings.
To balance a system, do the following:
1.
2.
3.
4.
5.
Inspect the complete system, locate all ducts, openings and dampers
Open all dampers in the ducts and at the grilles
Check the velocities at each outlet
Measure the free grille area
Calculate the volume at each outlet.
Velocity x area = volume flowrate
Fig 3-15:- How to use glass stem thermometer to measure room temperature. One is
placed in each room. A folded piece of heavy paper is used to keep the thermometer
from touching the tabletop.
Air Cleaning
Air pollution is a growing problem as urban areas increase in population and industries
expand. Cleaning the air has become an important part of air conditioning.
Air contaminants, as all foreign matter are called, include solids, liquids, gases and
vapors. Efficient air conditioning systems will remove 75 to 95 percent of these
contaminants.
Solid particles, kept in suspension in the air by air currents, fall into three general groups:
1. Dust. Usually, this results from wind, a sudden earth disturbance or from
mechanical work on some solid. Dust can have its origin in animal, vegetable or
mineral matter. Dust particles are usually over 600 microns in size (about 0.004
in. in diameter. Coal dust particles are usually 1 to 100 microns while atmospheric
dust is 0.001 to 30 microns in size.
2. Fumes. These are formed from materials that are ordinarily solids but have been
put into a gaseous state usually by an industrial or chemical process. Such
particles are about 1 micron in size.
3. Smoke. Caused by incomplete combustion, smoke consists of solid particles
carried into the atmosphere by the gaseous products of combustion. These
particles vary in size from 0.01 to 13 microns. Oil and tobacco smoke particles
range from 0.01 to 1 micron in size.
Gases are on the increase as air contaminants. They include carbon monoxide, sulphur
oxides, nitrogen oxides and hydrocarbons. These gases form smog when combined with
water vapor.
There are also liquid impurities in the air. Two of the most common are:
1. Mists. These small liquid particles are mechanically ejected into the air by
splashing, mixing or atomizing
2. Fogs. These small liquid particles are formed by condensation. Fogs indicate that
the atmosphere has reached the saturation state for that chemical.
[3-17]
[3-18]
It is possible to remove almost 100 percent of the contaminants in the air, but to do so is
expensive. Removal of 90 to 95 percent is much more common and practical.
Filter efficiency is measured by;
1. Total weight of dirt it collects.
2. Size of the smallest particle it will remove
3. Checking for discoloration on the exhaust side of the filter being tested.
Many rooms gradually collect a brown-yellow color on walls, windows and light colored
drapes. This deposit does not come from smoking and open cooking such as for meats.
These gases and small particles collect on the cooler surface of a room, especially when
air movement is slow.
Fig 3-16:- Washable aluminium corrugated filter used to removed dust from a
forced air system. Aluminum is coated with adhesive material so dust particles will
adhere to the surface. Note airflow caused by honeycomb type filters. Air turbulence
insures trapping of dust particles.
[3-19]
1.
2.
3.
4.
40 percent
60 percent
85 percent
95 percent
It is important to remember that filters are more efficient dirt removers when they are
dirty, but the airflow decreases. A 40 percent efficient filter is one that has 20 percent
efficiency when clean and 60 percent efficiency. Fig 3-20 is a table of filter efficiency.
Filters are tested in laboratories and they can also be tested on the job. One test is to find
out how many 0.3 micron size particles the filter can remove. The test is made by
measuring the interference with diffused (scattered) light.
To increase filtering surface or area in filters, many different designs are used. A popular
method to increase the area is to use pockets to trap the air, as shown in Fig 3-21.
Most electronic filter systems also have cleanable filters. Remove filter. Ensure power is
switched off. Clean with a mild detergent-warm water mixture, rinse and replace. Turn on
the power. These filters last indefinitely.
[3-21]
Fig 3-19:- Throwaway type filter being installed. A-Air return B-Filter
Fig 3-21:- Pocket type disposable air filter. Air pockets increase filtering surface
considerably.
Throwaway Filters Servicing
Filters should be replaced when they lose their efficiency or when they are so clogged
that they produce too much pressure drop across the filter.
Visual inspection is one way to decide when filters need replacement. If they have turned
black, if the frame is bent or warped or if the filtering medium is punctured, replace the
filter. If the housing shows signs of corrosion, clean it by sand blasting and repaint.
Checking the pressure drop across the filter is another way to decide whether the filter
should be replaced. When the pressure drop across the filter is more than 25 percent of
the pressure drop across the fan, the filter should be changed.
[3-22]
Always replace filters with the arrows (printed on the frame) pointing in the direction of
airflow. The side towards the blower has more adhesive and must be on the air-out side
of the filter. If this is not done, the filter will quickly load with dirt and clog.
When replacing filters make these two checks:
1. Inspect filter for tears and holes. Place a strong light on one side of filter and look
through filter from other side.
2. Use manometer to check pressure drop.
Electrostatic (Electronic) Theory Of Cleaning
Static electricity has an important effect on dirt and dust clinging to walls, drapes and
ceilings of rooms. Static electricity is created by two surfaces come together, there is
rubbing contact and then separate.
Rubbing a cloth on a nonconductor will build up surplus electrons on one of the
nonconductors (negative charge). The other material will lack electrons (positive charge).
These excess electrical charge jumps an air gap and the spark can cause a fire or
explosion.
Static electricity also attracts dirt and dust to vertical and overhead surfaces.
Ionizing the air will neutralize this static electrical charge. (Ionizing means to break it
down into positive and negative particles or charge). When this is done, dirt and dust will
settle to the floor and the danger of a static electricity spark is over.
Instruments are used to measure static electricity. They can read both a lack of
electrons (positive charged) and a surplus of electrons (negative charged)
Materials vary in their ability to generate static electricity. The farther apart the
substances are on the list, the greater their ability to generate static electricity. The
material at the top assumes a positive (+) (-) charge.
There are three ways to ionize air:
1. Power
2. Non Power
3. Nuclear
The power unit is the electronic filter. A non power unit uses metal to remove the static
electrical charge. The nuclear power unit gives off a double positive or alpha particle.
Basically, the electrostatic filter puts a static electrical charge on all particles that pass
through it. These charged particles are then attached to collector plates with an opposite
electrical charge.
[3-23]
Usually the air is first passed through a throw away filter to remove most of the larger
particles of dirt. Then it is fed through the electrostatic filter. In this filter, the air first
passes through a highly ionized field. A wire with a high positive voltage is suspended
between ground wires.
Electrons passing through the air space put a positive electrical charge on any particle
that attempts to pass through the ionized field. This particle is the drawn to the grounded
plates (negative potential).
Potentials of as high as 12,000V are used.
Because of the high voltages used, the electrostatic filter may be dangerous. The units
should be designed to shut off automatically when the service doors are opened to gain
access to the units. Fig 3-22 shows an electronic cleaner designed for duct installation.
[3-24]
manually operated with a hand valve. Some are semiautomatic. A push button switch
shuts off the system, opens the water solenoid valve and starts a timer which will put the
system back in operation after the wash cycle. The fully automatic system uses a timer to
turn wash cycle on and off. All built in washing systems require a water supply and a
drain.
Electronic filters have four main parts:
1. Frame
2. Power supply
3. Prefilter and airflow distributor
4. Electronic cell
The unit must be installed level and plumb for proper drainage and more efficient air
flow. The hot water line to the washer should have a strainer.
Airflow should be evenly distributed across the face of the air cleaner for maximum
efficiency. If the unit is near the airflow elbow, use movable air vanes or baffles.
Excessive lint interferes with electronic air cleaner (EAC) operation. A fine-mesh screen
or filter should be installed ahead (upstream) of the filter.
Servicing Electronic Filters
Electronic air cleaners (EAC) need service when:
1.
2.
3.
4.
5.
6.
Check on last cleaning of filter. Be sure power switch is on. Be sure the power doors or
panels are closed. Check fuses. Check the meter readings. (refer to service manual or
owners manual.) These meters will show if:
1.
2.
3.
4.
Some meters will show if electrical trouble is in the power source circuit or in the highvoltage circuit.
[3-25]
If the trouble is in the high-voltage circuit, inspect and electrically test the power pack
capacitors and collecting cell ionizing wires. A portable electronic filter with the collector
cell removed and connected for testing purposes.
In the power pack, inspect the low side first with either a test light or voltmeter. Test each
part starting with the wall outlet or power source.
Then check the transformer, rectifiers (a-c to d-c), the capacitor resistors (should
discharge capacitance in about 10 seconds). The capacitor can be checked by
replacement.
In the collector section, inspect the bent plates, plates out of position, dirt bridging the
gap between ionizing wires and the plates, broken insulators and broken wires. Plates
must be straight. Remove and replace broken insulators and ionizing wires.
One should inspect the building and the complete air-handling system. New carpeting, for
example, may temporarily cause an overload on the filter. Leaking duct systems and
untreated concrete floors are all unusual high load conditions. Dusty construction work in
the vicinity may also overload the unit.
A properly operating unit will be indicated by black water when the cell is cleaned. A
properly operating unit allows only fine white dust to leave the ducts. A cheesecloth over
a grille if it becomes discolored shows that the EAC is not working properly.
[3-26]