Professional Documents
Culture Documents
On The Analysis of Voltage and Current Transients in Three-Phase Power Systems
On The Analysis of Voltage and Current Transients in Three-Phase Power Systems
AbstractThis paper proposes a method for analyzing measurements of voltage transients in three-phase systems. The method is
based on the Clarke transform introduced in 1950 for calculations
of travelling waves along three-phase transmission lines. The proposed method also shows close similarities with the classification
of three-phase unbalanced voltage dips. After extracting the actual
transient (e.g., by using a notch filter centered on the power-system
frequency), the three signals are decomposed into seven components. From the relation between these seven components, the dominant component is identified. The method is successfully applied
to a number of measured transients. The paper also identifies the
limitations of the method and gives suggestions for future work.
Index TermsCapacitor energizing, electromagnetic compatibility (EMC), power quality, power-system transients, power
transmission and distribution.
I. INTRODUCTION
shorter duration, transients require a wider band-width measurement circuit and higher sampling rate. Therefore, large-scale
data collection of transients is much less common than data collection for dips and interruptions. All of this has led to an underexposure of transients in the power-quality literature. However, also voltage transients may have adverse consequences on
end-user equipment, including maloperation and damage.
Low-frequency transients (from 250 Hz up to several hundred
Hertz) due to capacitor-bank energizing have received the most
attention in the power-quality literature due to their adverse impact on adjustable speed drives (e.g., [8] and [9]). Phenomena,
such as current-chopping and restrike after capacitor de-energizing, may also lead to severe transients and equipment maloperation or damage.
Different methods are available for the analysis and characterization of transients, but all of these methods consider each
phase separately. No method is available for addressing transient multiphase measurements. Transients in three-phase systems are complicated, especially when switching actions in the
three phases take place close together in time. The development
of a three-phase analysis or classification method for powersystem transients would simplify the characterization of threephase transients. More importantly, it would allow the further
development of methods for extracting additional information
from recordings of voltage and current transients in three-phase
systems, such as direction and origin.
Motivated by the above issues, a method will be proposed
in this paper for the decomposition of voltage and current transients in three-phase systems. The paper starts with a general
discussion on analysis of transients in Section II, to explain the
role of the proposed method in the overall processing of transients. The theoretical foundation of the decomposition method
is presented in Section III. Section III also shows the equivalence between the proposed method and the classification of
three-phase unbalanced voltage dips and discusses a method for
determining the dominant component. A number of measurement examples are presented in Section IV. Some limitations
and implementation issues are described in Section V. As this
is a new method a discussion on further work including testing
is part of Section VI. Finally, Section VI concludes the paper.
II. ANALYSIS OF TRANSIENTS
The overall analysis of transients in three-phase systems, as
envisaged by the authors, is shown schematically in Fig. 1. From
the three measured voltages the actual transient is extracted. The
decomposition algorithm proposed in this paper is applied to
the extracted transient, resulting in seven components. After the
1195
(2)
with the pre-event voltage and the characteristic (residual)
complex voltage.
The expressions for a Type Da dip are
(3)
The alpha-component in (1) gives a voltage in phase a and the
opposite voltage of half the amplitude, in phases b and c. This
corresponds to the type Da dip. The beta-component gives a
voltage in phase b and the opposite voltage in phase c. This
corresponds to a type Ca dip. The zero-sequence component
results in the same voltage in the three phases. Rewriting (2)
1196
(11)
(4)
and for type Ca in
(5)
Substituting
results in (1).
in (4) and
in (5)
(12)
(6)
(7)
The other dip types can be obtained by cyclic rotation of (6) and
(7). The following expressions hold for the Db and Cb components:
(8)
(9)
(13)
and for the Dc and Cc components
(10)
1197
(14)
Fig. 3. Original waveforms (top left), extracted transients in the three phases
(top center), and the seven components for a measured transient. Example I.
(15)
For example, if
component.
A. Example I
An example of a measured transient is shown on the left-hand
side of Fig. 2. The transient is due to the closing of one phase
of a three-phase capacitor bank.
The extracted transient is shown on the right in the same
figure. The non-zero signal before the start of the event is due
to the method for extracting the transient being non-ideal. Harmonic distortion is not removed by the notch filter. An appropriate high-pass filter would remove the harmonic distortion but
would also remove a significant part of the transient as its main
frequency components are around a few hundred Hertz.
The seven transient components are shown in Fig. 3. Also,
the original waveform and the extracted transients for the three
phases are shown.
1198
Fig. 4. The 2-ms rms values for the six components in Example I: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
by solid lines; the C components by dashed lines.
Fig. 7. Original waveforms (top left), extracted transients in the three phases
(top center), and the seven components for a measured transient. Example III.
Fig. 5. Original waveforms (top left), extracted transients in the three phases
(top center), and the seven components for a measured transient. Example II.
Fig. 6. The 2-ms rms values for the six components in Example II: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
by solid lines; the C components are indicated by dashed lines.
Fig. 8. The 2-ms rms values for the six components in Example III: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
by solid lines; the C components by dashed lines.
The 2-ms rms values are shown in Fig. 4 for the six non-zerosequence components. As Dc is the highest and Ca the lowest,
Dc is found to be the dominant component and the event is classified as a type Dc transient (i.e., a transient between phase C
and ground).
B. Example II
A second example is given in Fig. 5: it is again the transient
due to closing of one phase of a three-phase capacitor bank.
From the 2-ms rms values shown in Fig. 6, it follows that this is
a type Da transient.
Note that the zero-sequence component is much higher than
in the first example. Whereas the zero-sequence component was
about half the dominating component in the first example, it is
even somewhat higher than the dominating component in this
Fig. 9. Original waveforms (top left), extracted transients in the three phases
(top center), and the seven components for a measured transient. Example IV.
1199
Fig. 11. Original waveforms (top left), extracted transients in the three phases
(top center), and the seven components for a measured transient. Example V.
Fig. 12. The 2-ms rms values for the six components in Example V: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
by solid lines; the C components by dashed lines.
Fig. 10. The 2-ms rms values for the six components in Example IV: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
by solid lines; the C components by dashed lines.
Fig. 13. Original waveforms (top left), extracted transients in the three phases
(top center), and the seven components for a measured transient. Example VI.
F. Example VI
A final example of a transient is shown in Fig. 13. The origin
of this transient is unknown. Neither the waveform traces in
Fig. 13 nor the rms traces in Fig. 14 reveal any dominant component. The differences between corresponding D and C components, according to (15), are shown in Fig. 15. A sequence
CbDcCa would fit with the observations but no conclusion
about the origin could be derived from that. Further studies
1200
Fig. 14. The 2-ms rms values for the six components in Example VI: Da and Ca
(left); Db and Cb (center); Dc and Cc (right). The D components are indicated
by solid lines; the C components by dashed lines.
Fig. 15. Difference between the rms values for Da and Ca (solid); Db and Cb
(dashed); and Dc and Cc (dotted), for Example VI.
ACKNOWLEDGMENT
The authors would like to thank A. Ferguson of Scottish
Power, C. Roxenius of Gteborg Energi, H. Seljeseth of Sintef,
and P. Halvarsson of Trinergi for the measurement data used in
this paper.
REFERENCES
[1] R. Rdenberg, Transient Performance of Electric Power SystemsPhenomena in Lumped Networks. Cambridge, MA: MIT
Press, 1950.
[2] A. Greenwood, Electrical Transients in Power Systems, 2nd ed. New
York: Wiley, 1991.
[3] L. van der Sluis, Transients in Power Systems. Chichester, U.K.:
Wiley, 2001.
[4] L. Tihanyi, Electromagnetic Compatibility in Power Electronics.
New York: IEEE Press, 1995.
[5] W. E. Kazibwe and M. H. Sendaula, Electric Power Quality Control
Techniques. New York: Van Nostrand, 1993.
[6] R. C. Dugan, M. F. McGranaghan, S. Santoso, and H. W. Beaty, Electric Power Systems Quality, 2nd ed. New York: McGraw-Hill, 2003.
[7] M. H. J. Bollen and I. Y. H. Gu, Signal Processing of Power Quality
Disturbances. New York: Wiley, 2006.
[8] M. F. McGranaghan, T. E. Grebe, G. Hensley, M. Samotyj, and
T. Singh, Impact of utility-switched capacitors on customer systemsPart II: Adjustable-speed drive concerns, IEEE Trans. Power
Del., vol. 6, no. 4, pp. 16231628, Oct. 1991.
[9] V. E. Wagner, J. P. Staniak, and T. L. Orloff, Utility capacitor
switching and adjustable-speed drives, IEEE Trans. Ind. Appl., vol.
27, no. 4, pp. 645651, Jul./Aug. 1991.
[10] Electromagnetic Compatibility (EMC) Part 4 Section 30: Power
Quality Measurement Methods, IEC Std. 61000-4-30.
[11] J. Dafis, C. O. Nwankpa, and A. Petropoulu, Analysis of power system
transient disturbances using an ESPRIT-based method, in Proc. IEEE
Power Eng. Soc. Summer Meeting, 2000, pp. 437442.
[12] M. H. J. Bollen, E. Styvaktakis, and I. Y. H. Gu, Categorization and
analysis of power-system transients, IEEE Trans. Power Del., vol. 20,
no. 3, pp. 22982306, Jul. 2005.
[13] E. Styvaktakis, Automating Power Quality Analysis Ph.D. dissertation, Dept. Signals Syst., Chalmers Univ. Technol., Gothenburg,
Sweden, 2002 [Online]. Available: http://www.elteknik.chalmers.se.
[14] E. Clarke, Circuit Analysis of AC Systems, Symmetrical and Related
Components. Schenectady, NY: General Electric Co., 1950.
[15] G. W. Stagg and A. H. El-Abaid, Computer Methods in Power System
Analysis. Auckland, New Zealand: McGraw-Hill, 1968.
[16] N. Watson and J. Arrillaga, Power Systems Electromagnetic Transients
Simulation. London, U.K.: Inst. Elect. Eng., 2003.
[17] M. H. J. Bollen, Characterization of voltage sags experienced by
three-phase adjustable-speed drives, IEEE Trans. Power Del., vol. 12,
no. 4, pp. 16661671, Oct. 1997.
[18] L. D. Zhang and M. H. J. Bollen, Characteristics of voltage dips (sags)
in power systems, IEEE Trans. Power Del., vol. 15, no. 2, pp. 827832,
Apr. 2000.
1201