Features
Versatile multifunction relay for the protection of circuit breaker or contactor controlled a.c. motors
The relay can also be used for the protection of feeders and transformers
Three-phase thermal overload protection
High-set overcurrent protection with instantaneous or with definite time operation
Phase unbalance and single-phasing protection with inverse time characteristic
Fast operating incorrect phase sequence
protection
Sensitive earth-fault protection with definite
time characteristic
Undercurrent protection with definite time
characteristic
Several selectable motor start-up supervision methods
Application
SPAM 150 C
1MRS 750384-MBG
Page 2
Design
Data communication
The relay is provided with a serial interface
on the rear panel. By means of a bus connection module type SPA-ZC21 or SPA-ZC 17
the feeder protection relay can be connected
to the fibre-optic SPA bus. The bus connection module SPA-ZC 21 is powered from the
host relay, whereas the bus connection module type SPA-ZC 17 is provided with a builtin power unit, which can be fed from an
external secured power source. Via the SPA
bus the relay communicates with higher-level
data acquisition and control systems.
Self-supervision
The relay incorporates a sophisticated selfsupervision system with auto-diagnosis,
which increases the availability of the relay
and the reliability of the system. The selfsupervision system continuously monitors the
hardware and the software of the relay. The
system also supervises the operation of the
auxiliary supply module and the voltages
generated by the module.
On detection of a permanent internal relay
fault the IRF indicator on the relay front
panel is lit. At the same time the output relay
of the self-supervision system operates and a
fault message is transmitted over the serial
bus to the higher-level system. Further, in
most fault situations a fault code is shown in
the display of the protection relay module.
The fault code indicates the type of fault that
has been detected.
SPAM 150 C
1MRS 750384-MBG
Page 3
Technical data
Rated current In
1A
5A
Thermal withstand
capability
continuously
4A
20 A
for 10 s
25 A
100 A
for 1 s
100 A
500 A
Half-wave value
250 A
1250 A
Input impedance
<100 m
<20 m
063 x In
0210% of In
50 Hz or 60 Hz
Dynamic current
withstand capability
NO trip
NC trip
Signalling
Terminals
65-66, 74-75
65-66
70-71-72, 68-69,
77-78, 80-81
Rated voltage
Thermal withstand
capability
Breaking capacity
for dc, when the
control/signalling
circuit time
constant
L/R 40 ms, at the
control voltages
250 V ac/dc
Carry continuously
5A
5A
5A
30 A
10 A
10 A
15 A
8A
8A
220 V dc
1A
0.15 A
0.15 A
110 V dc
3A
0.25 A
0.25 A
48 V dc
5A
1A
1A
Contact material
AgCdO2
Data communication
Terminals
10-11
18265 V dc or
80265 V ac
220 mA
Transmission mode
Data code
ASCII
SPA-ZC 21BB
SPA-ZC 21MM
SPA-ZC 17BB
SPA-ZC 17MM
SPTU 240R2/-R3
80265 V ac/dc
SPTU 48R2/-R3
1880 V dc
under quiescent
conditions
~4 W
under operating
conditions
~6 W
SPAM 150 C
1MRS 750384-MBG
Page 4
Start-up
supervision unit
0.501.50 In
20100%
Safe stall time setting t6x, i.e. trip time at locked rotor from cold
motor
2.0120 s
164 h
(h = heating time
constant)
50100% of t
(t = thermal trip
level)
2080% of t
Start current Is
1.010.0 In
Start-up time ts
0.380.0 s
definite time
principle
(I & t)
thermal stress
principle
(I2 t)
High-set phase
overcurrent unit
Earth-fault unit
0.520.0 In
or , infinite
0.0430.0 s
1.0100% of In
0.0530.0 s
Phase
Start current I
unbalance/incorrect
phase sequence
Operate time t, at lowest possible setting, i.e. 10%
unit
Operation characteristic
Undercurrent unit
1040% of IL
(IL = Load current)
20120 s
Inverse time
1s
600 ms
3080% of Iq
<12% of Iq
2600 s
5500 s
2250 s/h
SPAM 150 C
1MRS 750384-MBG
Page 5
Interference tests
Mechanical test
Environmental conditions
>100 M, 500 V dc
High-frequency (1 MHz)
disturbance test (IEC 255-22-1),
common mode
2.5 kV
High-frequency (1 MHz)
disturbance test (IEC 255-22-1),
differential mode
1.0 kV
4 kV, 5/50 ns
2 kV, 5/50 ns
Electrostatic discharge
(IEC 255-22-2 and IEC 801-2,
class III), air discharge
8 kV
Electrostatic discharge
(IEC 255-22-2 and IEC 801-2,
class III), contact discharge
6 kV
0.55.25 g
0.57.5 g
Vibration test
20 g, 1000 bumps/direction
Corrosion test
Battelle test
-10+55C
-40+70C
<95%, +40C, 96 h
IP 54
Weight
~3.5 kg
SPAM 150 C
1MRS 750384-MBG
Page 6
Block diagram
L1
L2
L3
-
Rx
+ (~)
- (~)
CONTROL
INPUT
5A
1A
5A
1A
5A
1A
1 2 3 4 5 6 7 8 9 25 26 27 11 10
5A
1A
62 61
U aux
IRF
RESTART
ENABLE
+
START
PRIOR ALARM
PRIOR ALARM
SIGNAL 2
SIGNAL 1
70 71 72
74 75
77 78
80 81
68 69
~
+ U2 SPTU _ R2
TRIP
SS1
SS2
SS3
+
A
TS2
SG4/2
TS1
TRIP
IRF
SGB/1
SGB/2
STALL
q>q i
q>q a
q>q t
SGR2/4
SGR2/5
SGR2/6
SGR2/7
SGR2/8
SGR1/1
SGR1/2
SGR1/3
SGR1/4
SGR1/5
SGR1/6
SGR1/7
SPTE 4E3
SGR2/1
SGR2/2
SGR2/3
SG4/3
U3
SERIAL
PORT
65 66
SGB/7
SGB/8
LATCHING
SGR1/8
63
START
Is >
I s2 x t s
RESTART RESTART
INHIBIT
INHIBIT
Sts >
I>>
SGB/3
SGB/4
DI
Io>
I<
SGB/5
SPAM 150 C
Fig. 1
SGB/6
EXTERNAL TRIP
RELAY RESET
Tx
SPA-ZC_
I/O
U1
SPCJ 4D34
SPAM 150 C
1MRS 750384-MBG
Page 7
Flush mounting
250
142
216
34
139 1
136
162
129 1
186
30
Panel cutout
dim100
Fig. 2
Semi-flush mounting
a
Raising frame
SPA-ZX 111
SPA-ZX 112
SPA-ZX 113
176
136
96
74
114
154
SFM100_1
Fig. 3
Projecting mounting
When projecting mounting is preferred, a
relay case type SPA-ZX 110 is used. The
relay case for projecting mounting is provided with front connectors.
SPA-ZX110
SPA-ZX115
158
115
+0,4
10
263
6
21,5
312
292
+0,4
177 0 (4U)
482,6 0 (19")
101,6
Mounting and
dimensions
6
115
98
104_6_10
Fig. 4
SPAM 150 C
1MRS 750384-MBG
Page 8
Ordering
Ordering example
2. Order number
RS 641 014-AA
3. Rated frequency
In=5 A, fn = 50 Hz
4. Auxiliary voltage
Uaux = 110 V dc
5. Accessories
6. Special requirements
Order numbers
Motor protection relays SPAM 150
SPAM 150 C with NO trip contact
References
Additional information
Brochure Motor protection relay SPAM 150 C
1MRS 750262-MDS EN
1MRS 750637-MUM EN