PA10 Series en EP E 10 026D
PA10 Series en EP E 10 026D
Specifications
SENSOR CONTROLLER
PA10 SERIES
M
Model
PA10-U
PA10-V
Power supply
100-240VAC 50/60Hz
PA10-VP
PA10-W
PA10-WP
PA10-U
Power consumption
Power for external
sensor
Selectable NORM/INV.
Selection function for
IN1, IN2 individual operation.
NPN input type PNP input type NPN input type PNP input type
1
Caution Product may be damaged, or injury may result if instructions are not followed.
The following is an explanation of the symbols used in the operation manual.
Caution:Injury or danger may occur under special conditions.
Solid-state
output
1. In case of using this unit with machineries(Nuclear power control, medical equipment, vehicle,
train, airplane, combustion apparatus, entertainment or safety device etc), it is required to install fail-safe device.
It may result in serious damage, fire or human injury.
2. This unit must be mounted on panel or rail.
It may give an electric shock.
3. Do not repair or checkup when power on.
It may give an electric shock.
4. Do not disassemble and modify this unit. If needs, please contact us.
It may give an electric shock and cause a fire.
OC OUT
Time setting
function by
each mode
Only for
PA10-U
Non
NORMAL MODE
FLIP-FLOP MODE
Min.10,000,000 times
Electrical
10
NPN input
PNP input
U
V
W
10
PA
IN1, IN2
0V
IN1, IN2
9.4
0V
IN1, IN2
0V
T1
T2
O
F
F
O
N
T1
T2
O
F
F
O
N
T1
T2
PA10-W/PA10-WP
+12V GND
IN 1
OC
OUT
+12V GND
IN 2
14
15
IN 1
IN 2
16
NORM
INV
NORM
INV
POWER
NC
COM
NO
OUT
1 Power indicator
1 Power indicator
10
11
12
82
BEN300-DDT
PA10-U
IN 1
IN 2
POWER
A
D
J
OUT2
OR
AND
NORM
NORM
INV
INV
NORM
SA
O SB
M
O
O
F
D
F
E
TIME
SC
SD
O T1
N T2
O
F
F
IN2
(Sensor for
synchronization)
76
OUT1
MADE IN KOREA
IN1
(Sensor for
detecting
the target)
OC
Blue
Brown
Black OUT1 IN2
(Sensor for
synchronization)
9 10 11 12
Brown
Derivative action
13 14 15 16
Blue
Black
PA10-V/PA10-VP
Blue
10
Brown
Black
11
+12V GND
IN1
+12V GND
IN2
14
IN1
(Sensor for detecting
the target)
BEN300-DDT
15
IN 2
Sensor
controller
POWER
OR
INV
NORM
Blue
Brown
INV
M
O
O
F
D
F
E
TIME O
A
D
J
F
F
10
Black
11
IN1
+12V GND
IN2
13
14
15
Blue
Brown
11
+12V GND
IN1
+12V GND
IN2
14
15
IN 1
IN 2
16
INV
NORM
INV
IN 1
NORM
IN 2
M
O
O
F
D
F
E
POWER
TIME O
A
D
J
F
F
AND
INV
INV
OC
OUT2
IN 1
IN 2
NORM
INV
NORM
INV
ON
OFF
ON
OFF
OUT (3-4)
ON
OFF
OUT1
ON
OFF
SA
O SB
N
SC
SD
O T1
N T2
MADE IN KOREA
OC OUT1 ON
(10-12)
OFF
OUT2
ON
OFF
OC OUT1 ON
(10-12)
OFF
PA10-W
NORM
NORM
No label
12
OUT2
OUT1
PA10-V
SA
SB
SC
SD
O T1
N T2
10
13
16
OR
Label
ON
OFF
Operation
Black
9
OUT
Blue
Black
12
OC
OUT
OUT2
PA10-U
Output((OUT)
Brown
+12V GND
NORM
PA10-U:
OUT2
PA10-V: NORM
PA10-VP: NORM
MODE1 ON-DELAY
PA10-W: NORM
PA10-WP: NORM
NC
COM
NO
~
1
AND
NORM
MADE IN KOREA
SOURCE
100-240VAC
50/60Hz
OC
OUT2
16
Blue
OUT1
NORM
SOURCE
100-240VAC ~
50/60Hz
PA10-W/PA10-WP
Black
12
OC
OUT1
OUT2
IN 1
5.6
T1
T2
O
N
PA10-U
5.4
O
N
O
F
F
Black
Brown Blue
PNP open
collector type &
PNP universal
output type sensor
+12V
12
Approx. 160g
38
PA10-VP/PA10-WP
1.8
O
F
F
Brown
,
IN1
( IN2
NO
Dimensions
PA10-U
Power Amplifier
Main circuit
+12V
COM
11
If the load is connected over 200mA at the sensor output, it may cause mechanical trouble.
Environment resistance is rated at no freezing or condensation.
Multi-function
Sensor
controller
9
0
Connections
Main circuit
NPN open
collector type &
NPN universal
output type sensor
+12V
Sensor
controller
NC
MADE IN KOREA
Approx. 150g
OUT1
NPN open
collector
output
type sensor
T1
T2
ENCODER(MODE 9 to 11)
Unit weight
Input connections
PA10-V/PA10-W
SD
13
PA10-U
SC
O
N
10
(Unit: mm)
SB
35.5
: NORM
INV (Input signal reverse turn function)
NORM : When input signal is low, it is valid signal. (
)
INV : When input signal is high, it is valid signal. (
)
7 Derivative action selection of IN2 input signal (AND/OR selection switch: AND)
: NORM
(When input signal is high(
), it is effective signal)
NORM : IN2 input signal is operating as reverse turn function
: Derivative action of IN2 input signal. See " Derivation action applications"
8 Selection switch for operation mode: See " Operation mode" in next page.
9 Selection switch of time range and max. input frequency: It is the switch
to select time range(1 to 7 mode) or allowable input frequency(9 to 11 mode).
PA10-V/PA10-VP
Ordering information
PA
M
O O
D F
E F
PA10-V
Insulation resistance
6
7
8
SA
5 AND/OR selection switch : Select "AND" or "OR" for IN1, IN2 Input
6 Selection switch of sensor input signal
940.5
INV
Caution
INV
NORM
O
F
F
13
Dielectric strength
Environ
ment
AND
NORM
A
D
J
Mechanical
Ambient
temperature
Ambient
humidity
OR
NORM
MADE IN KOREA
OFF-DELAY MODE
FLICKER MODE
LOW-SPEED DETECTION MODE
ON/OFF-DELAY MODE
ON-DELAY MODE
ONE-SHOT DELAY MODE
FLICKER ONE-SHOT MODE
HIGH-SPEED DETECTION MODE
Have
Response time
Relay
life
cycle
Warning
OC OUT1, OC OUT2
16
POWER
OUT 2
IN 1
IN 2
PA10-U
[No-voltage input] Impedance at short-circuit: Max. 680, Residual voltage at shortcircuit: Max. 0.8V, Impedance at open: Min. 100k
PA10-V/PA10-W
[No-voltage input]] Impedance at short-circuit: Max. 300, Residual voltage at shortcircuit: Max. 2V, Impedance at open: Min. 100k
PA10-VP/PA10-WP
[Voltage input]] Input impedance: 5.6k, "H" level voltage: 5-30VDC, "L" level voltage: 0-2VDC
Input method
15
OUT 1
PA10-U
14
13
12
OC
OUT1
OC
IN 2
OUT2
IN 1
+12V GND
Selectable NORM/INV.
Selectable OR/AND
Selectable NORM/INV.
operation for IN1, IN2
input. Selection function Operation for IN1, IN2 AND.
for IN2 derivative action.
NPN input type
11
10
+12V GND
Input(IN1, IN2)
CONTACT OUT:
250VAC 3A
RESISTIVE LOAD
POWER
SOURCE
100-240VAC
50/60Hz
POWER
MADE IN KOREA
NC
COM
NO
~
1
CONTACT OUT:
250VAC 3A
RESISTIVE LOAD
SOURCE
100-240VAC
50/60Hz
OUT1
MADE IN KOREA
NC2
COM2
NO2
NC1
COM1
NO1
~
1
OUT1
CONTACT OUT1,OUT2:
250VAC 3A
RESISTIVE LOAD
OUT2
PA10-U
IN 1
IN 2
POWER
A
D
J
OR
AND
NORM
INV
NORM
INV
NORM
M
O
O
F
D
F
E
TIME O
F
F
SA
O SB
N SC
SD
O
N
T1
OUT
OUT1
PA10-V
IN 1
IN 2
OUT2
PA10-W
NORM
INV
NORM
INV
POWER
IN 1
IN 2
NORM
INV
NORM
INV
POWER
T2
MADE IN KOREA
MADE IN KOREA
MADE IN KOREA
Operation mode
MODE
MODE 1
: Set the setting time by TIME S/W(T1, T2) and front TIME VOLUME(ADJ).
NORMAL MODE
MODE 2
<AND function>
ON
OFF
ON
IN2
OFF
ON
OUT
OFF
Output will be ON when both
IN1 and IN2 are ON.
ON-DELAY MODE
OFF-DELAY MODE
: OUT will be ON at the same time when IN1 or IN2 is ON then OUT will be OFF after setting time when
IN1 or IN2 is OFF. (This is when input logic is OR)
ON
IN1
OFF
SA
M
O
ON
O
SB
O
IN2 OFF
F
SC
D
T
T
N
F
E
SD
ON
OUT
T: Setting time
OFF
MODE 3
IN1
: OUT will be ON after setting time when one of IN1 and IN2 is ON. When IN1 and IN2 are OFF,
OUT will be OFF. (This is when input logic is OR)
ON
IN1
SA
OFF
M
O
ON
O SB
O
IN2
F
OFF
SC
D
T
F
N
T
E
SD
ON
OUT
T: Setting time
OFF
MODE 7
100 to 10Hz
6,000 to 600rpm
PA10 Series
O T1
N T2
O
F
F
O T1
N T2
0.1 to 1sec
O
F
F
O T1
N T2
1 to 10sec
1 to 0.1Hz
60 to 6rpm
O
F
F
O T1
N T2
10 to 100sec
0.1 to 0.01Hz
6 to 0.6rpm
MODE 8
0.01 to 0.1sec
NO
10 to 1Hz
600 to 60rpm
COM
DC POWER
NORM
AND
INV
IN1 input indicator
NORM
OC +12V
OUT1
Control
box
9 ENCODER
(Input pulse1time)
MODE
10 ENCODER
(Input pulse2times)
SA
M
O
O
F
D
F
E
SC
SD
Input pulse X 1
MODE 10
Input pulse X 2
MODE 11
Input pulse X 4
SC
SD
SC
SD
OC ON
OUT1 OFF
OC ON
OUT1 OFF
OC ON
OUT1 OFF
O
F
F
O T1
N T2
100kHz
Approx. 0.5
Min. 2000kHz(2,000kcps)
O
F
F
O T1
N T2
10kHz
Approx. 5
Min. 200kHz(200kcps)
O
F
F
O T1
N T2
1kHz
Approx. 50
Min. 20kHz(20kcps)
O
F
F
O T1
N T2
100Hz
Approx. 500
Min. 2kHz(2kcps)
MODE 12
ON/OFF-DELAY MODE
SA
O SB
IN1
ON
OFF
SC
IN2
ON
OFF
OUT
ON
OFF
SD
+12V
NORM
OUT
IN1
+12V
INV
NORM
OC
OUT
IN2
INV
+12V
+12V
OUT1
NORM
IN1
+12V
+12V
INV
NORM
OUT2
IN2
INV
1. Power
The inner circuit voltage starts to rise up for
the first 100ms after power on, the input may Power ON
OFF 100ms
not work at this time.
500mS
The unstable time
And also the inner circuit voltage drops down
against the input signal
for the last 500ms after power off, the input
may not work at this time.
ON
ON
Please use the power within the rated power
Power
Power
OFF
and apply or cut the power at once to prevent
OFF
from chattering.
2. Input signal line
Shorten the cable distance between the sensor and this product.
Please shielded wire for input signal needed to be long.
Please wire input signal line separated from power line.
3. When test dielectric voltage and insulation resistance of the control panel with this unit installed.
Please isolate this unit from the circuit of control panel.
Please make all terminals of this unit short-circuited.
4. Do not use this unit at below places.
Place where there are severe vibration or impact.
Place where strong alkalis or acids are used.
Place where there are direct ray of the sun
Place where strong magnetic field or electric noise are generated.
5. Installation environment
It shall be used indoor
Altitude Max. 2000m
Pollution Degree 2
Installation Category.
It may cause malfunction if above instructions are not followed.
Major products
: OUT will be ON after setting time when IN1 (or IN2) is ON. When IN1 (or IN2) is OFF, OUT will be OFF
after setting time. (This is when input logic is OR)
If IN1 (or IN2) ON/OFF time is shorter than setting time, OUT does not turn.
+12V
OC ON
Direction
CW
CCW
OFF
detection output OUT2
Note)Tw(pulse width) can be changed according to max. input frequency.
(OUT)
TIME S/W
PA10-V/PA10-VP
O SB
N
OR
ON
IN1
(A phase) OFF
ON
IN2
(B phase OFF
MODE 9
SA
M
O
O
F
D
F
E
NORM
(Derivative)
INV
IN2 input indicator
11 ENCODER
(Input pulse4times)
O SB
N
IN2
MODE
SA
M
O
O
F
D
F
E
O SB
OUT
OC
OUT2
ON
OFF
Note)IN2 will be the first of input signal.
AND and NORM
Note)It is not different between OR
S/W.
Note)There is no Timer function in Flip-Flop Mode, therefore use this unit with Time S/W(T1, T2) as OFF.
M
O
O
F
D
F
E
+5V
SD
10
PA10-U
: OUT will be ON when input signal (IN1) is shorter than setting time by comparing it to to the setting
time by one cycle.
ON
IN1
(IN2) OFF
Progressing time
SA
M
O
O SB
TIME
O
Setting
F
SC
D
time
N
F
E
SD
ON
OUT
OFF
Note)Above is when input logic is OR and it will be the same by using IN2 input signal terminal instead
of IN1.
~ SOURCE
Function diagram
OUT
12
PA10 Series
NC
: When IN1 signal is input then the Flip-Flop output will be ON(SET). When the IN2 signal is input,
Flip-Flop Signal will be OFF(RESET).
ON
IN1
OFF
SA
M
O
O SB
ON
O
F
IN2 OFF
D
SC
: OUT will be ON when input signal (IN1) is longer than setting time by comparing it to to the setting
time by one cycle.
IN1 ON
(IN2) OFF
SA
Progressing time
M
O
O SB
TIME
O
Setting
F
SC
D
time
N
F
E
SD
ON
OUT
OFF
Note)Above is when input logic is OR and it will be the same by using IN2 input signal terminal instead
of IN1.
Note)When use MODE 6 as above, be sure that OUT will be work at the same time with power supply.
rpm
O
F
F
MODE 6
It is able to reduce noise generating if install surge obsorber between inductive loads(Motor, Solenoid, etc) as Picture 1.
When use DC Relay for load, please install a diode at relay coils as Picture 2. (Be sure to power polarity)
MODE 6 to MODE 7
Input frequency
: OUT will be ON at the same time when IN1 or IN2 is ON then OUT will be OFF after setting time.
(This is when input logic is OR)
ON
IN1
SA
OFF
M
O
O SB
ON
O
IN2 OFF
F
SC
D
N
T
T
F
E
SD
ON
OUT
T: Setting time
OFF
Output
T
T: Setting time
Proximity sensors
Area sensors
Photoelectric sensors
Fiber optic sensors
Door/Door side sensors
Sensor controllers
Graphic/Logic panels
Temperature controllers
Temperature/Humidity transducers
Stepping motors/drivers/motion controllers
Laser marking system(CO, Nd:YAG)
Laser welding/soldering system
Counters
Timers
Display units
Panel meters
Pressure sensors
Rotary encoders
Power controllers
Tachometer/Pulse(Rate) meters
Switching power supplies
Field network devices
http://www.autonics.com
Satisfiable Partner For Factory Automation
HEAD QUARTERS :
41-5. Yongdang-dong, Yangsan-si, Gyeongnam, 626-847,
Korea
OVERSEAS SALES :
Bldg. 402 3rd FL., Bucheon Techno Park, 193, Yakdae-dong,
Wonmi-gu, Bucheon-si, Gyeonggi-do, 420-734, Korea
TEL : 82-32-610-2730 / FAX : 82-32-329-0728
E-mail : sales@autonics.com
EP-E-10-026D