PT C 2007 Sec 13b LR

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 38

Section 13

TemBreak 1 MCCBs 125 A 400 A Technical data


Ratings charts, selection guides MCCBs and accessories
Page
Tembreak 1 Ratings charts selection guides
30 - 400 A
XS125CS, XS125NS
16 - 125 A
XS125CJ, XS125NJ
20 - 125 A
XH125NJ
20 - 125 A
XH125PJ
20 - 125 A
XE225NC
125 - 225 A
XH160PJ
160 A
XS250NJ, XH250NJ
160 - 250 A
XH250PJ, XH400PJ
160 - 400 A
XS400CJ, XS400NJ
250 - 400 A
XS400SE, XH400SE
250 - 400 A
XH400PE
250 - 400 A
TL30F, TL100F, TL100C
15 - 100 A
TL100NJ
20 - 100 A
TL250NJ
160 - 250 A
TL400NE
400 A
Switch disconnectors (non-auto MCCBs)
125 - 630 A
Accessories for the above MCCBs (for 400 A refer section 5)
NHP TemPlug accessory
Selectivity and Cascade data MCB/MCCBs
Type 1 and 2 Motor starter co-ordination tables

13 - 100 to 13 - 105
13 - 106
13 - 107
13 - 108
13 - 109
13 - 110
13 - 111
13 - 112
13 - 113
13 - 114
13 - 115
13 - 116
13 - 117
13 - 118
13 - 119
13 - 120
13 - 121
13 - 122 to 13 - 127
13 - 128
13 - 129 to 13 - 131
13 - 132 to 13 - 135

CBs now
ak 1 MC
TemBre with superior
le
les
availab
5 hand
k 2 IP 6
a
re
B
m
Te

13
13 - 99

Standard TemBreak circuit breaker


Selection guide ratings
Type

XS125CS

Ampere frame
Number of poles
Outside view
Notes:
1
) 1 Pole breaker only, XS125CS and XS125NS respectively.
2
) 2 pole breaker is a 3 pole breaker with the centre pole omitted.
Supplied as standard.
Optional standard.
Yes or available.
Not available
i
Indent only

125A
1P 1)

2P )

XS125CJ
3P

4P

XS125NS
125A
1P 1)

Rated current (A).In NRC Nominal rated current


ASR Adjustable setting range
Rated current at 40C

NRC

AC RATED INSULATION VOLTAGE (Ui)


AC RATED BREAKING CAPACITY sym RMS [kA]
IEC 60947-2 [Icu]
IEC 60947-2 [Ics]
AS/NZS 3947-2 [Icu] AS/NZS 3947-2[Ics]
Note: Rated Impulse withstand voltage
Uimp (kV) is 8kV on all XS, XE and XH MCCBs

690

690

10/5
14/7
18/9
18/9
14/7
14
18

10

22/11
25/13
25/13
30/15
25/13
25
30

15

AS 2184
NEMA AB-1

13

without Inst.
DC RATED BREAKING
CAPACITY (kA)
RATED SHORT TIME CURRENT RMS [kA] [Icw]
DIMENSIONS (mm)
a
b
c
d
Weight (kg) marked standard type
CONNECTION AND MOUNTINGS
front
terminal screw
connect (FC)
attached flat bar
solderless terminal (PWC)
rear
bolt stud
connect (RC)
flat bar stud
plug-in (PM)
for switchboard
for distribution board
draw-out (DO)
STANDARD FEATURES
contact indicator
trip button
PROTECTIVE FUNCTIONS
Electronic type
Adjustable LTD, STD & INST
Adjustable GFT or Adjustable PTA (option)
Trip indicators (option) (contacts)
Thermal-magnetic type
thermal and fixed magnetic trips
thermal and adjustable magnetic trips
adjustable thermal and fixed magnetic trips
adjustable thermal and magnetic trips
ACCESSORIES (option)
Internally
auxiliary switch
mounted
alarm switch
shunt trip
undervoltage trip
Externally
motor operator
mounted
external panel mounted type
operating breaker mounted type
handle variable depth type
IP 65 handle variable depth type
extension handle
mechanical interlock front type
mechanical interlock rear type
mechanical interlock cable type
key interlock
handle holder
handle lock
captive padlock attachment
terminal cover front connect type
terminal cover rear/plug-in type
interpole barriers
accessories lead terminals
OCR sealing kit

13 - 100

16
20
25
32
40

1100V
1000V
690V
660V
500V
440V
415V
400V
380V
240V
440V
415V
600V
480V
240-690V
250V
125V

30
155
86
104
0.51

NRC
50
63
80
100
125

20
32
50
63
100
125

10
10
15

90

120

1.3

1.58

30
155
86
104
0.51

50
63
80
100
125

20
32
50
63
100
125

120

1.3

1.58

max
20
32
50
63
100
125

90

ASR
min
12.5
20
32
40
63
80

15
20

4P

12
22

3P

5/2.5
5/2.5
12/6
22/11
25/13
25/13
30/15
25/13

CODE
AUX
ALT
SHT
UVT
MOT
XFE
TFJ
XFH
TLK

16
20
25
32
40

XS125NJ

NRC

max
20
32
50
63
100
125

7.5/3.8
10/5
14/7
18/9
18/9
25/13

2P )

NRC

ASR
min
12.5
20
32
40
63
80

Standard TemBreak circuit breaker


Selection guide ratings
XH125NJ

XE225NC

XS250NJ

XH250NJ

XS400CJ

125A
3P

225A
3P

250A
3P

250A
3P

400A
3P

4P

NRC
20
32
50
63
100
125
690

ASR
min
12.5
20
32
40
63
80

NRC

NRC
max
20
32
50
63
100
125

125
150
175

4P

200
250

160
250

NRC

ASR
min
100
160

4P

max
160
250

160
250

4P

NRC

ASR
min
100
160

max
160
250

250
400

XS400NJ
400A
3P

max
250
400

690

690

10/5
15/7.5
15/7.5
18/9
18/9
25/13
15
18

15

10
15

8/4
8/4
22/11
25/13
25/13
25/13
35/18
50/25
30
35
22
25

40
40

15/7.5
15/7.5
25/13
42/21
50/25
50/25
50/25
85/43
50
50
25
42

40
40

105
165
67
82
1.4

105
165
86
107
1.85

90
155
86
104
1.3

120

1.58

(Bar)

140

2.4

105
165
103
124
2.1

(Bar)

690
ICU/ICS

16/8
16/8
22/11
30/15
30/15
35/18
35/18
50/25
36
36
22
30

40
40

250
400

690

8/4
8/4
25/13
42/21
50/25
50/25
50/25
85/43
50
50
25
42

40
40

140

2.6

140
260
103
131
4.7

(Bar)

ASR
min
160
250

max
250
400

690
ICU/ICS

18/9
18/9
30/15
42/12
50/25
50/25
50/25
85/43
50
50
30
42

40
40

185

6.1

140
260
103
131
4.7

185

6.1

(Bar)

4P

NRC

ASR
min
160
250

(Bar)

13
13 - 101

Standard TemBreak circuit breaker


Selection guide ratings
Type

TL30F

TL100F

Ampere frame
Number of poles
Outside view
Notes:
Supplied as standard.
i Yes or available.
Indent only

30A
3P

100A 225A
3P

AC RATED INSULATION VOLTAGE (Ui)


AC RATED BREAKING CAPACITY sym RMS [kA]
IEC 60947-2 [Icu]
IEC 60947-2 [Ics]
AS/NZS 3947-2 [Icu] AS/NZS 3947-2[Ics]
Note: Rated Impulse withstand voltage
Uimp (kV) is 8kV on all XS, XE and XH MCCBs

AS 2184
NEMA AB-1
without Inst.
DC RATED BREAKING
CAPACITY (kA)
RATED SHORT TIME CURRENT RMS [kA] [Icw]
DIMENSIONS (mm)
a
b
c
d
Weight (kg) marked standard type
CONNECTION AND MOUNTINGS
front
terminal screw
connect (FC)
attached flat bar
solderless terminal (PWC)
rear
bolt stud
connect (RC)
flat bar stud
plug-in (PM)
for switchboard
for distribution board
draw-out (DO)
STANDARD FEATURES
contact indicator
trip button
PROTECTIVE FUNCTIONS
Electronic type
Adjustable LTD, STD & INST
Adjustable GFT or Adjustable PTA (option)
Trip indicators (option) (contacts)
Thermal-magnetic type
thermal and fixed magnetic trips
thermal and adjustable magnetic trips
adjustable thermal and fixed magnetic trips
adjustable thermal and magnetic trips
ACCESSORIES (option)
Internally
auxiliary switch
mounted
alarm switch
shunt trip
undervoltage trip
Externally
motor operator
mounted
external panel mounted type
operating breaker mounted type
handle variable depth type
IP 65 handle variable depth type
extension handle
mechanical interlock front type
mechanical interlock rear type
mechanical interlock cable type
key interlock
handle holder
handle lock
captive padlock attachment
terminal cover front connect type
terminal cover rear/plug-in type
interpole barriers
accessories lead terminals
OCR sealing kit

13 - 102

4P

3P

Optional standard.
Not available

Rated current (A).In NRC Nominal rated current


Rated current at 40C

13

4P

TL225F

NRC
15
20
30

1100V
1000V
690V
660V
500V
440V
415V
400V
380V
240V
440V
415V
600V
480V
240-690V
250V
125V

690

25/13
25/13
42/31
120/60
120/60
120/60
120/60
120/60
120
120
25
42

40
40

90
155
86
104
1.3

120

1.58

105
165
125
143
3.2

60
75
100

140

3.8

NRC
125
150
175
200
225
690

25/13
25/13
60/30
120/60
120/60
120/60
120/60
120/60
120
120
60
75

40
40

140
260
133
167
6

CODE
AUX
ALT
SHT
UVT
MOT
XFE
TFJ
XFH
TLK

NRC
15
20
30
40
50
690

25/13
25/13
60/30
120/60
120/60
120/60
120/60
120/60
120
120
42
75

40
40

(Bar)

Non-automatic circuit breaker


Selection guide ratings
Type

XS125NN

XE250NNC

XS250NN

XS400NN

Ampere frame
Number of poles
Outside view
Notes:
Supplied as standard.
Yes or available.
i Indent only

125A
3P

250A
3P

250A
3P

400A
3P

4P

4P

4P

Optional standard.
Not available

RATINGS
AC
RATED OPERATIONAL VOLTAGE (V)
DC
AS/NZS 3947-2 IEC 60947-2
RATED SHORT CIRCUIT MAKING CAPACITY
peak/kA
RATED SHORT TIME CURRENT RMS [kA]
DIMENSIONS (mm)
a
b
c
d
Weight (kg) marked standard type
CONNECTION AND MOUNTINGS
front
terminal screw
connect (FC)
attached flat bar
solderless terminal (PWC)
rear
bolt stud
connect (RC)
flat bar stud
plug-in (PM)
for switchboard
for distribution board
draw-out (DO)
STANDARD FEATURES
ON-OFF colour indicator
trip button
ACCESSORIES (option)
CODE
Internally
auxiliary switch
AUX
mounted
alarm switch
ALT
shunt trip
SHT
undervoltage trip 1)
UVT
Externally
motor operator
MOT
mounted
external panel mounted type
XFE
operating breaker mounted type
TFJ
handle variable depth type
XFH
IP 65 handle variable depth type
TLK
extension handle
mechanical interlock front type
mechanical interlock rear type
handle holder
handle lock
terminal cover front connect type
terminal cover rear connect/plug-in type
interpole barriers
accessories lead terminal block 3)

690
250

690
250

690
250

690
250

2.5
1.8 (1 sec)

5.5
3 (1 sec)

6
4 (1 sec)

9
5 (0.3 secs)

105
160
60
83
2.1

105
165
86
107
1.85

2)

2)

2)

2)

door flange
IP 20 protection plug in type
Maximum switching current

750
313
AC-23A
7000
1000

1500
625
AC-23A
7000
1000

1500
625
AC-23A
7000
1000

2400
1000
AC-23A
4000
1000

Utilisation Category
Endurance
number of operations without current
number of operations with current

AC
DC

90
155
86
104
1.1

120

1.4

140

2.4

140
260
103
131
4.7

185

6.1

Notes:
) For AC UVT, a UVT Controller is mounted externally.
) Line side interpole barriers are supplied as standard.
3
) Draw-out leads, horizontally.
4
) Draw-out leads, vertically.
1
2

13
13 - 103

TemBreak Plus
Selection guide

PowerBreaker Series Ics = 50 kA

Ratings
Type
Ampere frame
Number of poles
Outside view
Notes:
1
) Adjustable ground fault available on indent,
fitted externally.
2
) LED indicators only or LED contacts, please specify.
Supplied as standard.
Optional standard.
Yes or available.
Not available
i Available on indent only
Rated current (A).In NRC Nominal rated current
ASR Adjustable setting range
Rated current at 40C

AC RATED INSULATION VOLTAGE (Ui)


AC RATED BREAKING CAPACITY sym RMS [kA]
IEC 60947-2 [Icu]
IEC 60947-2[Ics]
AS/NZS 3947-2 [Icu] AS/NZS 3947-2[Ics]
Note: Rated Impulse withstand voltage
Uimp (kV) is 8kV on all XS, XE and XH MCCBs

13

1100V
1000V
690V
500V
440V
415V
400V
240V
without Inst.
240-690V
DC RATED BREAKING
250V
CAPACITY (kA)
125V
RATED SHORT TIME CURRENT RMS [kA] [Icw]
DIMENSIONS (mm)
a
b
c
d
Weight (kg) marked standard type
CONNECTION AND MOUNTING
front
terminal screw
connect (FC)
attached flat bar
solderless terminal (PWC)
rear
bolt stud
connect (RC)
flat bar stud
plug-in (PM)
for switchboard
for distribution board
draw-out (DO)
STANDARD FEATURES
contact indicator
trip button
PROTECTIVE FUNCTIONS
Electronic type
Adjustable LTD, STD & INST
Adjustable GFT or Adjustable PTA (option)
Trip indicators (option) (contacts)
Thermal-magnetic type
thermal and fixed magnetic trips
thermal and adjustable magnetic trips
adjustable thermal and fixed magnetic trips
adjustable thermal and magnetic trips
ACCESSORIES (option)
CODE
Internally
auxiliary switch
AUX
mounted
alarm switch
ALT
shunt trip
SHT
undervoltage trip
UVT
Externally
motor operator
MOT
mounted
operating breaker mounted type TFJ
handle variable depth type
XFH
IP 65 handle variable depth type TLK
extension handle
mechanical interlock front type
mechanical interlock rear type
mechanical interlock cable type
key interlock
handle holder
handle lock
captive padlock attachment
terminal cover front connect type
terminal cover rear/plug-in type
interpole barriers
accessories lead terminals
OCR sealing kit

13 - 104

XH125PJ

XH160PJ

XH250PJ

XH400PJ

XH630PJ

125A
3P

160A
3P

250A
3P

400A
3P

630A
3P

NRC
20
32
50
63
100
125
690

4P

ASR
min max
12.5 20
32
20
50
32
63
40
100
63
125
80

8/4
25/13
42/21
50/50
50/50
85/50

40
40

90
155
86
104
1.3

120

1.6

NRC
160

min
100

ASR
max
160

250

690

690

15/7.5
23/13
42/21
50/50
50/50
85/50

40
40

18/9
42/15
42/21
65/50
65/50
85/50

40
40

105
165
103
124
2.1

140

2.6

ASR
max

NRC

min
160

250

250
400

NRC

140
260
103
145
4.7

4P

min

ASR
max

125
250

250
400

690
ICU/ICS

18/9
30/15
42/21
65/50
65/50
85/50
5
40
40
5 (0.3 sec)
185

6.1

140
260
103
145
4.7

400
630

185

6.1

210
273
103
145
9

(Bar)

(Bar)

min
250
400

ASR
max
400
630

690
ICU/ICS

45/23
65/33
85/43
85/50
100/50
125/163

40
40

NRC

(Bar)

4P

280

11.5

Selectivity
Series SE

PowerBreaker
Series (contd)

LimitorBreaker Series
Ics = 65 - 85kA

XH800PJ

XH400PE

XS400SE

XH400SE

TL100NJ

TL250NJ

TL400NE

800A

400A
3P

400A
3P

400A
3P

100A
3P

250A
3P

400A
3P

4P

NRC
800

min
500

ASR
max
800

NRC

250
400

min

ASR
max

125
200

250
400

690
ICU/ICS

20/10
42/21
65/50
65/50
65/50
100/50
5

5 (0.3 sec)

690
ICU/ICS

45/23
65/33
85/43
85/50
100/50
125/63

40
40

210
273
103
145
9

4P

280

11.5

140
260
103
14
4.8

4P

NRC
160
250
400

min
80
125
200

ASR
max
160
250
400

690
ICU/ICS

18/9
30/15
42/21
50/25
50/25
85/43
5

5 (0.3 sec)
185

6.2

140
260
103
131
4.8

4P

NRC
160
250
400

min
80
125
200

ASR
max
160
250
400

690
ICU/ICS

20/10
42/21
65/33
65/33
65/33
100/50
5

5 (0.3 sec)
185

6.2

140
260
103
131
4.8

185

6.2

NRC
min
20 12.5
32 20
50 32
63 40
100 63

4P

ASR
max
20
32
50
63
100

NRC
min
160 100
250 160

690

690

85/85
85/85
85/85
100/100

40
40

25/25
70/70
85/85
85/85
100/100
130/130

40
40

90
235
86
104
2.2

120

2.7

105
360
103
145
7.1

4P

ASR
max
160
250

NRC
400

185

9.1

140
360
103
145
7.1

(Bar)

(Bar)

(Bar)

1)

1)

1)

ASR
min max
200 400

690
ICU/ICS

25/25
70/70
85/85
85/85
100/100
130/130

4P

185

9.1

(Bar)

(Bar)

13
13 - 105

TemBreak MCCBs
XS125 single pole series (CS / NS)

Fixed thermal and magnetic trip.


Current rating @ 45C 16 A - 125 A.
Standards AS/NZS 3947-2.
Breaking capacity at 250 V DC, 500 V AC.

XS125CS (14 kA)


Ampere
rating

1 pole
Cat. No.

16

XS125CS 16 1

20

XS125CS 20 1

25

XS125CS 25 1

32

XS125CS 32 1

40

XS125CS 40 1

50

XS125CS 50 1

63

XS125CS 63 1

80

XS125CS 80 1

100

XS125CS 100 1

125

XS125CS 125 1

XS125NS (25 kA)


Ampere
rating

1 pole
Cat. No.

16

XS125NS 16 1

20

XS125NS 20 1

25

XS125NS 25 1

32

XS125NS 32 1

40

XS125NS 40 1

50

XS125NS 50 1

63

XS125NS 63 1

80

XS125NS 80 1

100

XS125NS 100 1

Short circuit capacity

125

XS125NS 125 1

Model

I/C

Voltage

XS125CS

14 kA

240 V 50 Hz

XS125NS

25 kA

240 V 50 Hz

Dimensions (mm)
Description

Height

Width

Depth

kg

XS125CS/NS

155

30

86

0.5

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

NK/JAPAN

AS/NZS 3947-2/Aust./NZ

Lloyds R/UK

AS 2184-1990/Australia

ABS/USA

JIS C 8372/JAPAN

GL/GERMANY

JEC 160/JAPAN

BV/FRANCE

Notes:

13
13 - 106

) An internal shunt trip may be mounted in an


XS125CS/NS MCCB.
Other accessories are external.

TemBreak MCCBs
XS125 series (CJ/NJ)
Adjustment range 63 - 100% of nominal current rating.
Standards AS/NZS 3947-2.
Adjustable thermal and fixed magnetic trip.

XS125CJ (18 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

20

12.5

20

XS125CJ 20 3

32

20

32

XS125CJ 32 3

50

32

50

XS125CJ 50 3

63

40

63

XS125CJ 63 3

100

63

100

XS125CJ 100 3

125

80
125
125 Non-auto (1.8 kA for 1s) Refer page 13 - 121

XS125CJ 125 3

XS125NJ (25 kA) 2 pole 3)


20

12.5

20

XS125NJ 20 2

32

20

32

XS125NJ 32 2

Dimensions (mm)

50

32

50

XS125NJ 50 2

Description

63

40

63

XS125NJ 63 2

XS125CJ

3 pole 155

90

86

1.3

100

63

100

XS125NJ 100 2

XS125NJ

2 pole 155

90

86

1.3

125

80

125

XS125NJ 125 2

XS125NJ

3 pole 155

90

86

1.3

XS125NJ

4 pole 155

120

86

1.58

Height Width Depth

kg

XS125NJ (25 kA) 3 pole


20

12.5

20

XS125NJ 20 3

32

20

32

XS125NJ 32 3

50

32

50

XS125NJ 50 3

63

40

63

XS125NJ 63 3

100

63

100

XS125NJ 100 3

125

80

125

XS125NJ 125 3

Short circuit capacity


XS125NJ (25 kA) 4 pole

Model

I/C

Voltage

20

12.5

20

XS125NJ 20 4

XS125CJ
XS125NJ

18 kA
25 kA

400 V 50 Hz
400 V 50 Hz

32

20

32

XS125NJ 32 4

DC use

I/C 2)

Voltage

50

32

50

XS125NJ 50 4

63

40

63

XS125NJ 63 4

XS125CJ
XS125NJ

10 kA
15 kA

250 V DC
250 V DC

100

63

100

XS125NJ 100 4

125

80

125

XS125NJ 125 4

Notes:

) MCCBs only.
) Poles in series. Refer applications Section 13.
3
) 2 pole models use a 3 pole body with centre pole disabled.
2

Special low instantaneous magnetic, generator protection MCCBs available


on request.

Base standards

Approvals

IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2/Aust./NZ
AS 2184-1990/Australia 1)
JIS C 8372/JAPAN
JEC 160/JAPAN

ASTA/UK, Aust. standards


Marine
NK/JAPAN
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
DNV NORWAY
13 - 107

13

TemBreak MCCBs
XH125 series

Adjustment range 63 - 100 % of nominal rating.


Co-ordinated with Sprecher + Schuh contactors.
Standards AS 2184/AS/NZS 3947-2.
Adjustable thermal, fixed magnetic trip.

XH125NJ (50 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

20

12.5

20

XH125NJ 20 3

32

20

32

XH125NJ 32 3

50

32

50

XH125NJ 50 3

63

40

63

XH125NJ 63 3

100

63

100

XH125NJ 100 3

125

80

125

XH125NJ 125 3

XH125NJ (50 kA) 4 pole


20

12.5

20

XH125NJ 20 4

32

20

32

XH125NJ 32 4

50

XH125NJ 50 4
XH125NJ 63 4
XH125NJ 100 4

50

32

63

40

63

100

63

100

125

80

125

Bolt-on earth leakage module ELB 125.


Refer Section 11 for further details.

XH125NJ 125 4

Dimensions (mm)
Height

Width

Depth

kg

XH125NJ

3 pole

155

90

86

1.3

XH125NJ

4 pole

155

120

86

1.6

Description

Short circuit capacity

Notes:

) MCCBs only.
) Poles in series. Refer applications section 13.
Special low instantaneous magnetic, generator protection MCCBs available
on request.
i Available on indent only.

Model
XH125NJ

I/C
50 kA

Voltage
400/415 V 50 Hz

DC use
XH125NJ

I/C 2)
40 kA

Voltage
250 V DC

13
13 - 108

Base standards

Approvals

IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2/Aust./NZ
AS 2184-1990/Australia 1)
JIS C 8372/JAPAN
JEC 160/JAPAN

ASTA/UK, Aust. standards


Marine
NK/JAPAN
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
DNV NORWAY

TemBreak Plus MCCBs


XH125PJ PowerBreaker series
Ics = 50 kA

Powerful interrupting capacities.


Limitation of system damage.
Unique contact structure.
Icu = Ics = 50 kA.
Adjustable thermal, fixed magnetic trip.
Adjustment range 63 - 100 % of nominal current rating.
Standards IEC 60947-2/AS/NZS 3947-2.

XH125PJ (50 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

20

12.5

20

XH125PJ 20 3

32

20

32

XH125PJ 32 3

50

32

50

XH125PJ 50 3

63

40

63

XH125PJ 63 3

100

63

100

XH125PJ 100 3

125

80

125

XH125PJ 125 3

XH125PJ (50 kA) 4 pole


20

12.5

32

20

20

XH125PJ 20 4

32

XH125PJ 32 4
XH125PJ 50 4

50

32

50

63

40

63

XH125PJ 63 4

100

63

100

XH125PJ 100 4

125

80

125

XH125PJ 125 4

Dimensions (mm)
Height

Width

Depth

kg

XH125PJ

3 pole

155

90

86

1.3

XH125PJ

4 pole

155

120

86

1.6

Description

Short circuit capacity

Notes:

AC use
Model
XH125PJ

Icu
50 kA

Ics
50 kA

Voltage
400/415 V 50 Hz

DC use 1)
XH125PJ

Icu
40 kA

Ics

Voltage
250 V DC

) Poles in series. Refer applications section 13.


i Available on indent only.

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

Lloyds R/UK

AS/NZS 3947-2 Aust./NZ

ABS/USA
GL/GERMANY

13

BV/FRANCE

13 - 109

TemBreak MCCBs
XE225NC economical series
Standards AS/NZS 3947-2.
Fixed thermal magnetic trip.

XE225NC (18 kA) 3 pole


Ampere rating
(fixed)

Cat. No. 1) 2)

125

XE225NC 125 3

150

XE225NC 150 3

175

XE225NC 175 3

200

XE225NC 200 3

225

XE225NC 225 3

XE250 Isolator
Non-Auto (3 kA for 1sec) 1) 3)

250

Refer page 13 - 121

Dimensions (mm)
Description
XE225N

3 pole

Height

Width

Depth

kg

160

105

67

1.85

Short circuit capacity


Notes:

Model

I/C

Voltage

XE225NC

18 kA

400 V 50 Hz

DC use

I/C

Voltage

XE225NC

10 kA

250 V DC

) Load-break isolating switch only no protection.


2
) Chassis not available for XE225NC.
3
) Short time rating. Refer rating chart for complete technical data.
4
) MCCBs only.
Special low instantaneous magnetic, generator protection MCCBs
available on request.

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

NK/JAPAN

AS/NZS 3947-2/Aust./NZ

Lloyds R/UK
4

13
13 - 110

AS 2184-1990/Australia )

ABS/USA

JIS C 8372/JAPAN

GL/GERMANY

JEC 160/JAPAN

BV/FRANCE

TemBreak Plus MCCBs


XH160PJ PowerBreaker series
Ics = 50 kA

Powerful interrupting capacities.


Limitation of system damage.
Unique contact structure.
Icu = Ics = 50 kA.
Adjustable thermal, fixed magnetic trip.
Adjustment range 63 - 100 % of nominal current rating.
Standards IEC 60947-2/AS/NZS 3947-2.

XH160PJ (50 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

160

100

160

XH160PJ 160 3

XH160PJ (50 kA) 4 pole


160

160

100

XH160PJ 160 4

Dimensions (mm)
Description

Height

Width

Depth

kg

XH160PJ

3 pole

165

105

103

2.1

XH160PJ

4 pole

165

140

103

2.4

Short circuit capacity


AC use
Model

Icu

Ics

Voltage

50 kA

50 kA

400/415 V 50 Hz

DC use )

Icu

Ics

Voltage

XH160PJ

40 kA

250 V DC

XH160PJ
1

Notes:

) Poles in series. Refer applications section 13.


i Available on indent only.

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

Lloyds R/UK

AS/NZS 3947-2 Australia/NZ

ABS/USA
GL/GERMANY

13

BV/FRANCE

13 - 111

TemBreak MCCBs
XS250 and XH250 NJ series
Adjustment range 63 - 100 % of nominal current rating.
Standards AS/NZS 3947-2.
Adjustable thermal, fixed magnetic trip.

XS250NJ (25 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

160

100

160

XS250NJ 160 3

250

160

250

250

XS250NJ 250 3
1

Non-Auto (4 kA for 1 sec) ) )

Refer page 5 - 48

XS250NJ (25 kA) 4 pole


160
250
250

100

160

XS250NJ 160 4

160

250

XS250NJ 250 4

Non-Auto (4 kA for 1 sec) 1) 4)

Refer page 5 - 48

XH250NJ (50 kA) 3 pole


160

100

160

XH250NJ 160 3

250

160

250

XH250NJ 250 3

XH250NJ (50 kA) 4 pole


160

100

160

XH250NJ 160 4

250

160

250

XH250NJ 250 4

Dimensions (mm)
Height

Width

Depth

kg

XS250NJ

3 pole

165

105

86

1.85

XH250NJ

3 pole

165

105

103

2.1

Description

XS250NJ

4 pole

165

140

86

2.4

XH250NJ

4 pole

165

140

103

2.6

Notes:

) Isolating switch only - no protection.


) MCCBs only.
3
) Poles in series. Refer applications Section 13.
4
) Short time rating. Refer rating chart for complete technical data.
Special low instantaneous magnetic generator protection MCCBs available on
request.

Short circuit capacity


Model

I/C

Voltage

XS250NJ

25 kA

400 V 50 Hz

XH250NJ

50 kA

400/415 V 50 Hz

DC use

I/C 3)

Voltage

XS250NJ

40 kA

250 V DC

XH250NJ

40 kA

250 V DC

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

NK/JAPAN

AS/NZS 3947-2/Aust./NZ

Lloyds R/UK

AS 2184-1990/Australia 2)

ABS/USA

JIS C 8372/JAPAN

GL/GERMANY

JEC 160/JAPAN

BV/FRANCE

13
13 - 112

DNV NORWAY

TemBreak Plus MCCBs


XH250PJ and XH400PJ PowerBreaker series
Ics = 50 kA

Powerful interrupting capacities.


Limitation of system damage.
Unique contact structure.
Adjustable thermal and magnetic trips.
Thermal adjustment range 63 - 100 % of nominal current rating.
Standards IEC 60947-2/AS/NZS 3947-2.

XH250PJ and XH400PJ (65 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

160

(400AF)

100

160

XH250PJ 160 3

250

(400AF)

160

250

XH250PJ 250 3

250

400

XH400PJ 400 3

400

XH250PJ and XH400PJ (65 kA) 4 pole


160
250

(400AF)
(400AF)

400

100
160
250

160

XH250PJ 160 4

250

XH250PJ 250 4

400

XH400PJ 400 4

Dimensions (mm)
Description

Height

Width

Depth

kg

XH250/400PJ

3 pole

260

140

103

4.7

XH250/400PJ

4 pole

260

185

103

6.1

Short circuit capacity


Notes:

) Poles in series. Refer applications section 13.


i Available on indent only.

AC use
Model

Icu

Ics

Voltage

XH250/400PJ

65 kA

50 kA

400/415 V 50 Hz

DC use 1)

Icu

Ics

Voltage

XH250/400PJ

40 kA

250 V DC

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

Lloyds R/UK

AS/NZS 3947-2 Aust./NZ

ABS/USA
GL/GERMANY

13

BV/FRANCE

13 - 113

TemBreak MCCBs
XS400 series thermal magnetic type
Adjustment range 63 - 100 % of nominal current rating.
Standards AS/NZS 3947-2.
Adjustable thermal and magnetic trip.

XS400CJ (35 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

250

160

250

XS400CJ 250 3

400

250

400

XS400CJ 400 3

400 Non-auto (5 kA for 0.3s) 1) Refer page 13 - 121

XS400CJ (35 kA) 4 pole


250

160

250

XS400CJ 250 4

400

250

400

XS400CJ 400 4

XS400NJ (50 kA) 3 pole


250

160

250

XS400NJ 250 3

400

250

400

XS400NJ 400 3

XS400NJ (50 kA) 4 pole


250

160

250

XS400NJ 250 4

400

250

400

XS400NJ 400 4

Short circuit capacity


Dimensions (mm)
Description
XS400CJ/NJ

Height

Width

Depth

kg

3 pole

260

140

103

4.7

4 pole

260

185

103

6.1

Model

I/C

Voltage

XS400CJ

35 kA

400 V 50 Hz

XS400NJ

50 kA

400/415 V 50 Hz

DC use 3)

I/C

Voltage

XS400CJ

40 kA

250 V DC

XS400NJ

40 kA

250 V DC

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

NK/JAPAN

AS/NZS 3947-2/Aust./NZ

Lloyds R/UK
2

Notes:

) Load-break isolating switch only no protection.


) MCCBs only.
3
) Poles in series. Refer applications Section 13.
2

13

AS 2184-1990/Australia )

ABS/USA

JIS C 8372/JAPAN

GL/GERMANY

JEC 160/JAPAN

BV/FRANCE
DNV NORWAY

13 - 114

TemBreak Plus MCCBs


XS400SE and XH400SE selectivity series
electronic type
SE Upstream Selectivity
breakers.
SE offers enhanced selectivity.
3:1 ratio between upstream &
downstream MCCBs.
Ics rating is 50 % of Icu.
I2t switch to assist in obtaining
total selectivity.

True RMS monitoring.


Electronic trip unit with Long,
Short and Instantaneous
adjustments.
Adjustment range 50 - 100 %
of nominal current rating.
Standards IEC 60947-2/
AS/NZS 3947-2.

XS400SE (50 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

250

125

250

XS400SE 250 3

400

250

400

XS400SE 400 3

XH400SE (65 kA) 3 pole


250

125

250

XH400SE 250 3

400

250

400

XH400SE 400 3

XS400SE (50 kA) 4 pole


Ampere
rating

Min

Max

250

125

250

XS400SE 250 4

400

250

400

XS400SE 400 4

250

XH400SE 250 4

400

XH400SE 400 4

Cat. No.

XH400SE (65 kA) 4 pole


250

125

400

250

Dimensions (mm)
Description

Height

Width

Depth

kg

XS/XH400SE 3 pole

260

140

103

XS/XH400SE 4 pole

260

185

103

6.2

Short circuit capacity


AC use
Model

Icu

Ics

Voltage

XS400SE

50 kA

25 kA

400/415 V 50 Hz

XH400SE

65 kA

33 kA

400/415 V 50 Hz

OCR options (factory fitted)

Notes:

Available on indent only.

Description

Code

Pre-trip alarm

LSIP

Fault indicators

FI

Special LTD curves

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

Lloyds R/UK

AS/NZS 3947-2 Aust./NZ

ABS/USA
GL/GERMANY

13

BV/FRANCE

13 - 115

TemBreak Plus MCCBs


XH400PE PowerBreaker series
Ics = 50 kA

Current limiting.
True RMS monitoring.
I2t switch to assist in obtaining total selectivity.
Powerful interrupting capacities.
Limitation of system damage.
Unique contact structure.
Electronic trip unit with Long, Short and Instantaneous adjustments.
Adjustment range 50 - 100 % of nominal current rating.
Standards IEC 60947-2/AS/NZS 3947-2.

XH400PE (65 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

250

125

250

XH400PE 250 3

400

250

400

XH400PE 400 3

XH400PE (65 kA) 4 pole


250

125

400

250

250

XH400PE 250 4

400

XH400PE 400 4

Dimensions (mm)
Description

Height

Width

Depth

kg

XH400PE

3 pole

260

140

103

XH400PE

4 pole

260

185

103

6.2

Short circuit capacity


AC use
Model

Icu

Ics

Voltage

XH400PE

65 kA

50 kA

400/415 V 50 Hz

OCR options (factory fitted)


Description

Code

Pre-trip alarm

LSIP
1

Notes:

Fault indicators )

FI

Special LTD curves

) Mounted externally.
i Available on indent only.

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

Lloyds R/UK

AS/NZS 3947-2 Aust./NZS

ABS/USA
GL/GERMANY

13

BV/FRANCE

13 - 116

TemBreak MCCBs
High fault series thermal magnetic type
Standards AS/NZS 3947-2.
Interrupting capacity @ 415 V 120 kA.
TL breakers are suitable for high fault high current
limiting applications.
Fixed thermal magnetic trip unit.

TL30F (120 kA) 3 pole


Ampere
rating

Cat. No.

15

TL30F 15 3P

20

TL30F 20 3P

30

TL30F 30 3P

TL100F (120 kA) 3 pole


15

TL100F 15 3P

20

TL100F 20 3P

30

TL100F 30 3P

40

TL100F 40 3P

50

TL100F 50 3P

60

TL100F 60 3P

75

TL100F 75 3P

100

TL100F 100 3P

TL100C (180 kA) 3 pole


15

TL100C 15 3P

20

TL100C 20 3P

30

TL100C 30 3P

40

TL100C 40 3P

50

TL100C 50 3P

60

TL100C 60 3P

Model

I/C

Voltage

75

TL100C 75 3P

TL30F

120 kA

400/415 V 50 Hz

100

TL100C 100 3P

TL100F

120 kA

400/415 V 50 Hz

TL100C

180 kA

400/415 V 50 Hz

D/C use

I/C

I/C

TL100F

40 kA

250 V DC

Short circuit capacity

Dimensions (mm)
Description

Height

Width

Depth

kg

TL30F

155

90

86

1.3

TL100F

165

105

125

3.2

TL100C

230

110

133

5.0

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

NK/JAPAN

AS/NZS 3947-2

Lloyds R/UK

AS 2184-1990/Australia

ABS/USA

JIS C 8372/JAPAN

GL/GERMANY

JEC 160/JAPAN

BV/FRANCE

13
13 - 117

TemBreak Plus MCCBs


TL100NJ LimitorBreaker series
Ics = 85 kA

Standards IEC 60947-2/AS/NZS 3947-2.


Two fast-break contacts per pole.
Powerful interrupting capacities.
Provides limitation of system damage during a fault.
Icu = Ics = 85 kA.
Variable thermal, fixed magnetic trip.
Adjustment range 63 100 % of nominal current rating.
Can be used for selectivity applications.
3 or 4 pole types available.

TL100NJ (85 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

20

12.5

20

TL100NJ 20 3

32

20

32

TL100NJ 32 3

50

32

50

TL100NJ 50 3

63

40

63

TL100NJ 63 3

100

63

100

TL100NJ 100 3

TL100NJ (85 kA) 4 pole


20

12.5

20

TL100NJ 20 4

32

20

32

TL100NJ 32 4

50

TL100NJ 50 4
TL100NJ 63 4
TL100NJ 100 4

50

32

63

40

63

100

63

100

Dimensions (mm)
Description

Height

Width

Depth

kg

TL100NJ

3 pole

235

90

86

2.2

TL100NJ

4 pole

235

120

86

2.7

Short circuit capacity


AC use
Model

Icu

Ics

Voltage

85 kA

85 kA

400/415 V 50 Hz

DC use )

Icu

Ics

Voltage

TL100NJ

40 kA

250 V DC

TL100NJ
1

Notes:

) Poles in series. Refer applications section 13.


i Available on indent only.

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

Lloyds R/UK

AS/NZS 3947-2

ABS/USA
GL/GERMANY

13

BV/FRANCE

13 - 118

TemBreak Plus MCCBs


TL250NJ LimitorBreaker series
Ics = 100 kA

Standards IEC 60947-2/AS/NZS 3947-2.


Two fast-break contacts per pole.
Powerful interrupting capacities.
Provides limitation of system damage during a fault.
Icu = Ics = 85 kA at 415 V.
Variable thermal and magnetic trip.
Adjustment range 63 100 % of nominal current rating.
Can be used for selectivity applications.
3 or 4 pole types available.

TL250NJ (100 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

160

100

160

TL250NJ 160 3

250

160

250

TL250NJ 250 3

TL250NJ (65 kA) 4 pole


160

100

250

160

160

TL250NJ 160 4

250

TL250NJ 250 4

Dimensions (mm)
Height

Width

Depth

kg

TL250NJ

3 pole

360

140

103

7.1

TL250NJ

4 pole

360

185

103

9.1

Description

Short circuit capacity

Notes:

) Poles in series. Refer applications section 13.


i Available on indent only.

AC use
Model

Icu

Ics

Voltage

TL250NJ

100 kA

100 kA

400 V AC 50 Hz

TL250NJ

100 kA

85 kA

400 V AC 50 Hz

DC use 1)

Icu

Ics

Voltage

TL250NJ

40 kA

250 V DC

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

Lloyds R/UK

AS/NZS 3947-2 Aust./NZ

ABS/USA
GL/GERMANY

13

BV/FRANCE

13 - 119

TemBreak Plus MCCBs


TL400NE LimitorBreaker series
electronic type

Standards IEC 60947-2/AS/NZS 3947-2.


Two fast-break contacts per pole.
Powerful interrupting capacities.
Provides limitation of system damage during a fault.
Electronic trip unit with Long, Short & Instantaneous adjustments.
Icu = Ics = 85 kA at 415 V.
Adjustment range 50 100 % of nominal current rating.
True RMS monitoring.
I2t ramp switch to assist in obtaining total selectivity.
3 or 4 pole types available.

TL400NE (85 kA) 3 pole


Ampere
rating

Min

Max

Cat. No.

400

200

400

TL400NE 400 3

TL400NE (85 kA) 4 pole


400

200

400

TL400NE 400 4

Dimensions (mm)
Description

Height 1)

Width

Depth

kg

TL400NE

3 pole

360

140

103

7.1

TL400NE

4 pole

360

185

103

9.1

Short circuit capacity


AC use
Model

Icu

Ics

Voltage

TL400NE

100 kA

100 kA

400 V AC 50 Hz

TL400NE

85 kA

85 kA

415 V AC 50 Hz

OCR options (factory fitted)


Description

Code

Pre-trip alarm 2)
Notes:

) Height excludes attached busbar.


) Factory fitted OCR controller specify voltage 240 V or 110 V AC.
i Available on indent only.

LSIP
2

Fault indicators )

FI

Special LTD curves

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

Lloyds R/UK

AS/NZS 3947-2

ABS/USA
GL/GERMANY

13

BV/FRANCE

13 - 120

TemBreak MCCBs
MCCB isolating switches (non-auto MCCBs)

Accepts MCCB accessories.


Suitable for panelboards.
Standards IEC 60947-2/AS/NZS 3947-2.
Motor or motorised circuit isolation - no overcurrent protection.

Ordering details
Ampere
rating (A)

Short time
rating (kA)

3 pole
Cat. No. 1)

4 pole
Cat. No. 1)

125

1.8 kA for 1 sec

XS125NN3

XS125NN4

250

3 kA for 1 sec

XE225NNC3

XE225NNC4

250

4 kA for 1 sec

XS250NN3

XS250NN4

400

5 kA for 0.3 sec

XS400NN3

XS400NN4

630

9.6 kA for 0.3 sec

XS630NN3

XS630NN4

Dimensions (mm)
Width

Amp
rating (A)

Height )

125
225

Weight (kg)

3P

4P

Depth

155

90

120

160

105

250

165

105

400

260

630

273

Notes:

3P

4P

86

1.3

1.58

67

1.85

140

86

1.85

2.4

140

185

103

6.2

210

280

103

12.2

) Refer page 13 - 103 for additional technical details.


) Height excludes attached busbar.

Base standards

Approvals

IEC 60947-2

ASTA/UK, Aust. standards

BS EN 60947 Part 2

Marine

VDE 0660 Part 1

Lloyds R/UK

AS/NZS 3947-2 Aust./NZ

ABS/USA
GL/GERMANY

13

BV/FRANCE

13 - 121

TemBreak MCCB accessories


TemBreak standard combinations of internally mounted
accessories
AUX

Auxiliary switch

ALT

Alarm switch

SHT

Shunt trip

UVT

Undervoltage trip

Internal accessories
are NHP factory
fit only

Left pole
handle
Right pole

UVT rating
A.

Inst type
AC 100 - 120 V
AC 200 - 240 V

XS 125PJ
XS-125CJ
XS-125NJ
XH-125NJ
TL30F

AC 380 - 450 V
DC 24 V
DC 48 V
i

DC 60 V
DC 100 - 115 V
DC 200 - 230 V

B.

Time delay type


AC 100 - 120 V
AC 200 - 240 V
AC 380 - 450 V

SHT rating
AC 100 - 115 V
AC 200 - 480 V
AC 24 V
AC 48 V
i

DC 12 V
DC 24 V
DC 30 V
DC 48 V

DC 60 V
DC 100 - 115 V

13

DC 125 V
DC 200 - 230 V
Note:

13 - 122

Available on indent only.

XH 160PJ
XS-250NJ
XH-250NJ
XE-225NC

XS400
XH/XS400
XS630
XH/XS630
XS800
XH/XS800
XS1250
XS1600

TemBreak MCCB accessories


Accessories to suit 125 AF, TL30F, TL100NJ 3)
Internal accessories (factory fit)
Cat. No.

Description
Shunt trip
(1 pole)
Shunt trips
(2, 3, 4 pole)
Undervoltage trip

Undervoltage
trips

UVT controller

Auxiliary
switches

XS125CS/20 A
with shunt trip fitted

Alarm
switches
Alarm &
auxiliary switches
Extra low
or high
magnetic trip

100-440 V AC / 48-250 V DC 1 P SHT

UXVC0001C

110 V AC SHT (100-115 V)


240 V AC SHT (200-480 V)
24 V DC SHT
48 V DC SHT
110 V DC SHT (100-115 V)
24 V AC SHT
48 V AC SHT
12 V DC SHT
200 V DC SHT (200-230)
AC coil 1)
24 V DC coil 2)
100-230 V DC coil 2)
48 V DC coil 2)
60 V DC coil 2)
110 V AC instantaneous controller
240 V AC instantaneous controller
440 V AC instantaneous controller
110 V AC time delay controller
240 V AC time delay controller
440 V AC time delay controller
200-230 V DC controller
AUX SW right hand 1 C / 3 P
AUX SW right hand 2 C / 3 P
AUX SW right hand 1 C / 4 P
AUX SW right hand 2 C / 4 P
AUX SW left hand 1 C
AUX SW left hand 2 C
ALT SW right hand / 3 P
ALT SW right hand / 4 P
ALT SW left hand
ALT/AUX SW right hand 1 C / 3 P
ALT/AUX SW right hand 1 C / 4 P
ALT/AUX SW left hand 1 C
Special selectivity, generator or marine applications

2H1935BAC
2H1935BBC
2H1935BCC
2H1935BDC
2H1935BEC
2H1936BAC
2H1936BBC
2H1936BDC
2H1936BHC
2H1947BAC
2H1947BBC
2H1947BCC
2H1948BAC
2H1948BBC
UXUB0013B
UXUB0014B
UXUB0015B
UXUB0016B
UXUB0017B
UXUB0018B
UXUB0037B
UXXB0019D
UXXB0020D
2H2383DAA
2H2384DAA
UXXB0026E
UXXB0027E
UXLB0001E
2H2385DAA
UXLB0027E
UXLB0003E
2H2387DAA
UXLB0028E
-

Alarm switch
Notes:

) An AC UVT controller is required for 100-440 V AC.


) A DC UVT controller is needed for 200-230 V DC operation. None required for 24-110 V DC.
3
) AF = Ampere frame.
2

Alarm & auxiliary


switch

13
13 - 123

TemBreak MCCB accessories


Accessories to suit 125 AF, TL30F, TL100NJ 1)
External accessories
Description

Attached busbar

Tunnel Clamp
Terminals (Solderless
terminals)

Attached
busbar
Tunnel Clamp
terminals
Rear connect
studs
Motor
operators
Mechanical
interlocks
Handle
operators

Handle locks

Cat. No.
3 P attached busbars (6 in kit)

TRED0001

3 P solderless terminals (6 in kit) 2)


4 P solderless terminals (8 in kit) 2)
3 P rear connect studs (6 in kit)
4 P rear connect studs (8 in kit)
110 V AC motor
240 V AC motor
110 V DC motor
3 P rear mech I/lock
4 P rear mech I/lock
Variable depth handle, door interlocking
IP 65 rated variable depth handle, door interlocking
IP 55 direct mount rotary handle 3)
IP 65 metal variable depth handle
Handle lock
Key interlock (Fortress type) incl TFJ mechanism 4)
Padlock attachment 5)
Resin for XKA2
3 P FC terminal cover
4 P FC terminal cover
IP 20 protection cover 6)
Seal plate 7)
3 P RC terminal cover
4 P RC terminal cover
Terminal and bolt
Insulation plate
AUX conn. block (MCCB side)
3 P tulip blocks (6 in kit)
3 P mounting base
Terminal and bolt
Insulation plate
AUX Conn. block (MCCB side)
4 P tulip blocks (8 in kit)
4 P mounting base
3 P TemPlug
Cat. No. for 1 only 9)
OCR sealing kit
For use with metal escutcheon covers
Add-on earth leakage block with pre-trip alarm contacts

TXED0005A
TXED0006A
UXRC0011A
UXRC0012A
UXMB0041C
UXMB0057B
UXMB0061C
UXKB0017B
UXKB0018B
XFHA22
T1HP12XR6BNA4
TFJ22XU
YASD22
UXKB0013A
XKA2
LOCTITE
480 RESIN
2H1407DAA
2H1408DAA
2A1785DAA
2H1406DAA
UXPD0031A
UXPD0032A
UXYD0007A
UXYE0005A
UXYC0013A
TXED0010A
XDM2-3
UXYD0007A
UXYE0005A
UXYC0013A
TXED0011A
XDM2-4
UPX3125
UXQH0002B
XS1250CRSK
XAB2
ELB125A

Order one kit per breaker

TO400XS125

Rear connect studs

Terminal
covers - front
connect

Plug-in tulip blocks

Terminal covers rear connect


Plug-in
breaker parts
3 pole 9)

Plug-in
breaker parts
4 pole 8)

Plug-in base

UXMB motor operator

TemPlug
Interpole barrier
OCR sealing kit
Pole fillers
Earth leakage
block
Adapter kit for TO400
chassis
Notes:

)
)
3
)
4
)
5
)
6
)
7
)
8
)
9
)
2

13

Rear interlock

13 - 124

AF = Ampere frame.
Factory fit only.
Flush plate included.
Tech data Section 8.
Captive type. Resin fixing.
6 pieces required for 3 P / 8 pieces required for 4 P.
Specify qty required (up to 2 pieces).
Not suitable for TL100NJ types.
A total of 4 individual barriers for 3 P, and 6 barriers required for 4 P.

TemBreak MCCB accessories


Accessories to suit 225 AF (XE225NC) 1)
Internal accessories (factory fit)
Description
Shunt trips
(2, 3, 4 pole)

Auxiliary switches
TFJ handle

Alarm switches
Alarm & auxiliary
switches

Cat. No.
110 V AC SHT (100 - 115 V)
240 V AC SHT (200 - 480 V)
24 V DC SHT
48 V DC SHT
110 V DC SHT (100 - 115 V)
AUX SW right hand 1 C
AUX SW right hand 2 C
AUX SW left hand 1 C
AUX SW left hand 2 C
ALT SW right hand
ALT/AUX SW right hand 1 C

2H0153CAB
2H0153CBB
2H0153CDB
2H0153CEB
2H0153CCB
2H0156CAB
2H0156CBB
2H1613BAA
2H1613CBA
2H0157CAB
2H0157CBB

External accessories
TFH Handle operator

Attached busbar
Tunnel clamp
(Solderless) terminals
Rear connect studs
Mechanical
interlocks
Handle operators
Handle locks

Terminal cover
- front connect
- rear connect
Interpole barrier
Notes:

)
)
3
)
4
)
2

Terminal cover

3 P attached busbars (6)


3 P solderless terminals (6)

7B3BA1B
2A1818CAA

3 P rear connect studs (6)


3 P rear mech. I/lock

2H1081CAA
2H0158CAA

Variable depth handle, door interlocking


IP 55 direct mount rotary handle 2)
Lock plate
Handle lock
Key interlock (Fortress Type) incl TFJ mechanism 3)

TFH23CB
TFJ23CU
UXKE0030A
KGH7123A
-

3 P FC terminal cover
3 P RC terminal cover
Interpole barrier 4)

2H1080CAA
2H1079CAA
TQQ3CA

AF = Ampere frame.
Flush plate included.
Tech data Section 8.
4 barriers required per breaker.

13
13 - 125

TemBreak MCCB accessories


Accessories to suit 160 AF / 250 AF 10)
Internal accessories (factory fit)
Description
Shunt trips

Undervoltage trip

Undervoltage trips

UVT controller

Auxiliary switches

Alarm switch

Alarm switches
Alarm & Auxiliary
switches
Extra low or high
magnetic trip

Cat. No.
110 V AC (100 - 115 V)
240 V AC (200 - 480 V)
24 V DC
48 V DC
110 V DC (100 - 115 V)
24 V AC
48 V AC
12 V DC
200 V DC (200-230 V)
AC coil 1)
24 V DC coil 2)
100-230 V DC coil 2)
48 V DC coil 2)
60 V DC coil 2)
110 V AC instantaneous controller
240 V AC instantaneous controller
440 V AC instantaneous controller
110 V AC time delay controller
240 V AC time delay controller
440 V AC time delay controller
200-230 V DC controller
AUX SW right hand 1 C
AUX SW right hand 2 C
AUX SW left hand 2 C
ALT SW right hand
ALT / AUX SW right hand 1 C

2H1937BAA
2H1937BBA
2H1937BCA
2H1937BDA
2H1937BEA
2H1938BAA
2H1938BBA
2H1938BDA
2H1938BHA
2H1949BAB
2H1949BBB
2H1949BCB
2H1950BAB
2H1950BBB
UXUB0013B
UXUB0014B
UXUB0015B
UXUB0016B
UXUB0017B
UXUB0018B
UXUB0037B
2H1951BAA
2H1952BAA
UXXB0028B
2H1953BAA
2H1954BAA

Special selectivity, generator or marine applications

External accessories
Alarm & auxiliary
switch

Attached busbars
Tunnel clamp
terminals
(solderless
terminals)
Crimp lugs
Tunnel clamp
terminals

13
13 - 126

Cat. No.

Description

Note:

3 P attached busbars (6)


4 P attached busbars (8)
3 P solderless term (6) / XS 9)
4 P solderless term (8) / XS 9)
3 P solderless term (6) / XH 9)
4 P solderless term (8) / XH 9)
Compression term (80 mm2)
Compression term (100 mm2)

Refer following page for footnotes.

TXJD0050B
TXJD0051B
2H2008DAB
2H2008DBB
2H2734DAA
2H2734DBA
80-3BA
100-3BA

TemBreak MCCB accessories


Accessories to suit 160 AF / 250 AF 10)

Note: 400 A
accessories refer
Section 5

External accessories
Description
Rear connection
studs
Motor operators
UXMB motor operator

Mechanical
interlocks

Handle operators

Rear interlock

Handle lock

Terminal covers

XFH Handle operator

Interpole barriers

OCR sealing kit

Cat. No.
3 P rear connect studs (6)
4 P rear connect studs (8)
110 V AC motor 3)
220 V AC motor 3)
240 V AC motor 3)
110 V DC motor 3)
3 P rear mech int. / XS
4 P rear mech nt. / XS
3 P rear mech int./ XH
4 P rear mech int./ XH
Variable depth handle, door interlocking 3)
IP 65 rated variable depth handle, door interlocking 3)
IP 55 direct mount rotary handle mechanism 4)
IP 65 metal variable depth handle
Handle lock
Key interlock (Fortress Type) incl TFJ mechanism 11)
Padlock attachment 5)
Resin for XKA2

3 P FC terminal cover / XS
4 P FC terminal cover / XS
3 P FC terminal cover / XH
4 P FC terminal cover / XH
IP 20 protective cover 6)
3 P RC terminal cover / XS
4 P RC terminal cover / XS
3 P RC terminal cover / XH
4 P RC terminal cover / XH
Seal plate 7)
Plug-in breaker
AUX conn. block (MCCB side)
parts 3 pole
AUX conn. block (panel side)
3 P tulip block / XS
3 P tulip block / XH
3 P mounting base
Plug-in breaker
AUX conn. block (MCCB side)
parts 4 pole
AUX conn. block (panel side)
4 P tulip block / XS
4 P tulip block / XH
4 P mounting base
3 P TemPlug / XH only
TemPlug
Interpole barrier / XS 8)
Interpole barriers
Interpole barrier / XH 8)
Pole fillers
For use with metal escutcheon covers
Earth leakage block Add-on earth leakage block with pre-trip alarm (XH250)
Add-on earth leakage block with pre-trip alarm (XS250)
OCR sealing kit
OCR sealing kit
Notes:

)
)
3
)
4
)
5
)
6
)
7
)
8
)
9
)
10
)
11
)
2

2H2266DAA
2H2266DBA
UXMB0046D
UXMB0047D
UXMB0058B
UXMB0062C
UXKB0019B
UXKB0020B
UXKB0021B
UXKB0022B
XFHA23S
T1HP25XR6BNA4
TFJ23SU
YASD23
UXKB0014A
XKA2
LOCTITE
480 RESIN
2H2135DAB
2H1410DAB
2H2136DAA
2H1412DAA
2A1786DAA
UXPD0027B
UXPD0028B
UXPD0033B
UXPD0034B
2H1406DAA
UXYC0010A
UXYB0004A
TXJD0054A
TXJD0058A
XDM3-3
UXYC0010A
UXYB0004A
TXJD0055A
TXJD0059A
XDM3-4
UPX3250
UXQH0002B
UXQH0003B
XAB3
ELB250AH
ELB250A
XS250OCRSK

An AC UVT controller is required for 100-440 V AC.


A DC UVT controller is needed for 200-230 V DC operation. None required for 24-110 V DC.
Add UXFD0016A when required for XH250NJ & XH160PJ.
Flush plate included.
Captive type. Resin fixing.
6 pieces required for 3 P / 8 pieces required for 4 P.
Specify quantity required (up to 2 pieces).
4 pieces required for 3 P (6 pieces required for 4 P).
Factory fit only.
AF = Ampere frame.
Tech data, Section 8.

13
13 - 127

TemBreak MCCB accessories


NHP TemPlug
Available for MCCBs from 12-400 Ampere
Easily fitted using supplied hardware
Low resistance connection
Moulding constructed from UL approved glass filled polyester
Polycarbonate terminal cover supplied as standard
Assembly bolts directly to module gear plate
Lowest watts loss and temperature rise
Silver plated contacts with domed face for increased
contact pressure

Ordering details
Current
rating (A)

MCCB

Vertical type
Cat. No.

12

XM30PB

UPX330PB

100

TL100F

UPX3100F

125

XH125NJ

UPX3125

250

XS250NJ

UPXS250

250

XH250NJ

UPXH250

400

XS400 / 400

UPX3440

Vertical mounted
TemPlug/MCCB

Horizontally mounted versions are indent items, please refer to NHP.


(Horizontal type prefix is HBC3, for left or right mounting types)

Cut-out for TemPlugs 125 to 400 AF


TemPlug (125) / XM30PB

TemPlug (400)

13
13 - 128

TemPlug (250)

Application data
Selectivity and Cascade tables at 400/415 V
MCB to MCCB
Cascade
The resultant cascade level with the XH630SE (65 kA) and XH250NJ (50 ka)
MCCBs in series is 65 kA. This means that the XH630SE will back-up the
XH250NJ MCCB to 65 kA, which is beyond its breaking capacity of 50 kA.

Selectivity
From the tables, the Selectivity level between the same two breakers,
XH630SE and XH250NJ connected in series will be 50 kA. This means that
for fault levels up to and including 50 kA the XH250NJ will trip before the
XH630SE.

Conclusion
For short circuit currents up to and including 50 kA, the XH250NJ will trip
before the XH630SE, therefore ensuring Selectivity. For fault levels above
50 kA both breakers may trip, however, the XH630SE will back-up the
XH250NJ to 65 kA.

Guide

XX / YY
Selectivity

Cascade

MCB to MCCB: thermal magnetic


Upstream MCCB

kA (RMS)

XS125CJ
18

XS125NJ
25

XH125NJ
XH125PJ
TL100NJ
50

2-20 A

18/18

25/25

35/35

25/25

35/35

25-63 A

18/18

20/25

20/25

25/25

30/30

0.5-32 A

10

18/18

25/25

30/50

25/25

40/50

35/35

40/50

40/50

40-63 A

10

18/18

20/25

25/25

25/25

30/30

30/30

30/30

30/30

DSRCBH & DSRCB

0.5-32 A

10

18/18

25/25

30/50

25/25

40/50

35/35

40/50

40/50

DSRCBH & DSRCB

40 A

10

18/18

20/25

25/25

25/25

30/30

30/30

30/30

30/30

DIN-T10H

80-125 A

10

4/18

4/25

4/25

15/15

15/15

10/10

10/10

DTCB15

0.5-32 A

10

18/18

25/25

30/50

25/25

40/50

35/35

40/50

40/50

40-63 A

10

18/18

20/25

25/25

25/25

30/30

30/30

30/30

30/30

SAFE-T

16-63 A

3/10

3/10

3/10

SRCB

16-20 A

3/10

3/10

3/10

Downstream
MCB

Range
(A)

DTCB6
DTCB10

XS250NJ
25

XH250NJ
TL250NJ
50

XS400CJ
35

XS400SE
XS400NJ
50

XH400SE
65

13
13 - 129

Application data TemBreak MCCBs


Selectivity and Cascade tables at 400/415 V
Guide

XX / YY
Selectivity

Cascade

MCCB to MCCB: electronic and thermal magnetic


Upstream MCCB
Downstream kA
MCCB
(RMS)

TL400NE
TL630NE
TL800NE TL1250NE
XS400SE XH400SE XS630SE XH630SE XS800SE XH800SE XS1250SE XS1600SE XS2000NE XS2500NE
65
85
100
100
50
65
50
65
50
65

XS125CJ

18

15/50

15/50

18/30

18/30

18/30

18/30

18/18

18/18

18/18

18/18

XS125NJ

25

25/50

25/50

25/30

25/30

25/30

25/30

25/30

25/30

25/30

25/30

XH125NJ

50

35/50

35/65

50/50

50/65

50/50

50/65

50/50

50/50

50/50

50/50

XH125PJ

50

35/50

35/65

50/50

50/65

50/50

50/65

50/50

50/50

50/50

50/50

TL100NJ

85

35/50

35/65

50/50

50/65

50/50

50/65

50/65

50/85

50/85

50/85

XH160PJ

50

25/50

25/65

50/50

50/65

50/50

50/65

50/50

50/50

50/50

50/50

XE225NC

18

15/30

15/30

18/30

18/30

18/30

18/30

18/18

18/18

18/18

18/18

XS250NJ

25

15/50

15/65

25/50

25/65

25/50

25/65

25/35

25/35

25/35

25/35

XH250NJ

50

25/50

25/65

50/50

50/65

50/50

50/65

50/50

50/50

50/50

50/50

XH250PJ

65

10/50

10/65

25/50

25/65

50/65

50/65

50/65

50/65

TL250NJ

85

-/65

10/50

10/65

25/50

25/65

50/65

50/85

50/85

50/85

XS400CJ

35

-/50

-/50

10/50

10/65

25/50

25/65

35/42

35/42

35/42

35/42

XS400NJ

50

-/65

10/50

10/65

25/50

25/65

50/65

50/65

35/65

50/65

XS400SE

50

-/65

10/50

10/65

25/50

25/65

50/65

50/65

50/65

50/65

XH400PJ

65

10/50

10/65

25/50

25/65

50/65

50/65

50/65

50/65

XH400SE

65

10/50

10/65

25/50

25/65

50/65

50/65

50/65

50/65

XH400PE

65

10/50

10/65

25/50

25/65

50/65

50/65

50/65

50/65

TL400NE

85

25/50

25/65

65/65

85/85

50/85

50/85

XS630CJ

42

-/50

10/50

10/50

30/45

30/45

35/45

35/45

XS630NJ

50

10/50

10/65

30/65

30/85

35/85

35/85

XS630SE

50

-/65

10/50

10/65

30/65

30/85

30/85

30/85

XH630PJ

85

10/50

10/65

30/65

30/85

30/85

30/85

XH630SE

65

10/50

10/65

30/65

30/85

30/85

30/85

XH630PE

65

10/50

10/65

30/65

30/85

30/85

30/85

XS800NJ

50

15/65

20/85

35/85

35/85

XS800SE

50

-/65

15/65

20/85

20/85

20/85

XH800PJ

85

15/65

20/85

20/85

20/85

XH800SE

65

15/65

20/85

20/85

20/85

XH800PE

65

15/65

20/85

20/85

20/85

XS1250SE

65

20/65

35/65

35/65

XS1600SE

85

35/65

13
13 - 130

Application data TemBreak MCCBs


Selectivity and Cascade tables at 400/415 V
Guide

XX / YY
Selectivity

MCCB to MCCB: thermal magnetic

Cascade

Selectivity - Thermal magnetic MCCBs only.


Upstream MCCB
Downstream
MCCB

kA
(RMS)

XH125NJ
50

XS250NJ XH250NJ
25
50

XS400CJ XS400NJ XS630CJ XS630NJ


35
50
42
50

XS800NJ
50

XH800PJ
85

XS125CJ

18

-/50

3/25

3/50

4/35

4/50

6/30

XS125NJ

25

-/50

3/25

3/50

4/35

4/50

6/30

6/30

10/30

10/30

6/30

10/30

10/30

XH125NJ/PJ

50

12/50

12/65

XE225NC

18

-/25

-/30

-/30

-/30

6/25

6/30

8/30

8/30

XS250NJ

25

XH250NJ

50

4/50

6/42

6/50

8/50

8/65

4/50

10/50

10/65

XS400CJ

35

-/50

6/35

6/50

6/50

6/65

XS400NJ

50

6/50

6/65

XS630CJ

42

XS630NJ

50

-/50

-/85

XS800NJ

50

-/85

13
13 - 131

Type 1 short circuit co-ordination


Motor starter co-ordination table
for DOL starting
50 kA at 400-415 V to AS 3947-4-1

TYPE 1
50 kA

Approx.
(amps)

Terasaki circuit
breaker type

Sprecher + Schuh
contactor type

Sprecher + Schuh Setting range


overload type 2) (amps)

0.37

1.1

XM30PB/1.4

CA 7-9

CT 7-24

1-1.6

0.55

1.5

XM30PB/2

CA 7-9

CT 7-24

1-1.6

0.75

1.8

XM30PB/2.6

CA 7-9

CT 7-24

2.4-4

1.1

2.6

XM30PB/4.0

CA 7-9

CT 7-24

2.4-4

1.5

3.4

XM30PB/5

CA 7-9

CT 7-24

2.4-4

2.2

4.8

XM30PB/8

CA 7-9

CT 7-24

4-6

3.0

6.5

XM30PB/8

CA 7-9

CT 7-24

6-10

4.0

8.2

XM30PB/10

CA 7-9

CT 7-24

6-10

5.5

11

XH125NJ/20

CA 7-12

CT 7-24

10-16

7.5

14

XH125NJ/20

CA 7-16

CT 7-24

10-16

10

19

XH125NJ/32

CA 7-23

CT 7-24

16-24

11

21

XH125NJ/32

CA 7-23

CT 7-24

16-24

15

28

XH125NJ/50

CA 7-30

CT 7-45

18-30

18.5

34

XH125NJ/50

CA 7-37

CT 7-45

30-45

22

40

XH125NJ/63

CA 7-43

CT 7-45

30-45

30

55

XH125NJ/100

CA 7-60

CT 7-75

45-60

37

66

XH125NJ/100

CA 7-72

CT 7-75

60-75

CA 7-85

CT 7-100

70-90

Motor size
(kW)

45

80

XH125NJ/125 )

55

100

XH125NJ/125 )

CA 6-105-(El)

CT 6-110

85-110

75

130

XH250NJ/250

CA 6-140-(El)

CT 6-150

105-150

90

155

XH250NJ/250 1)

CA 6-170-El

CT 6-200

110

200

132

225

XH250NJ/250 )
XS400SE/400

CA 6-210-El
CA 6-250-El

140-200
3

160-400

160-400

CEF 1-41/42 )
CEF 1-41/42 )

150

250

XH400SE/400 )

CA 6-250-EI

CEF 1-41/41 )

160-400

160

270

XS400SE/400

CA 6-300-El

CEF 1-41/42 3)

160-400

185

310

200

361

XH400SE/400 )
XS400SE/400

CA 6-300-EI
CA 6-420-El/ CA 5-450

160-400

160-400

CEF 1-41/42 )
CEF 1-41/42 )
3

250

425

XS630SE/630

CA 6-420-El/ CA 5-450

CEF 1-52 )

160-630

315

530

XS630SE/630

CA 5-550

CEF 1-52 3)

160-630

Notes: 1) Use magnetic only breaker. Refer NHP for factory modification.
2

) Thermal or electronic overload relays may be used.

) Electronic overloads

Fuses 65 kA. XH125NJ circuit breaker combinations limited to 50 kA, others 65 kA.
Overloads may be changed to different types eg. thermal style to electronic.
Some combinations also give Type 2 performance.

13

Cat. No. CT 7-24


Contactor CA 7-9
(Refer Part A section 1)

13 - 132

XM30PB

Type 2 short circuit co-ordination

TYPE 2
50 kA

Motor starter co-ordination table


for DOL starting
50 kA at 400-415 V to AS 3947-4-1

Setting range
(amps)

Motor size
(kW)

Approx.
(amps)

Terasaki circuit
breaker type

Sprecher + Schuh
contactor type

Sprecher + Schuh
overload type 3)

0.37

1.1

XM30PB/1.4

CA 7-9

CT 7-24-1.6

1-1.6

0.55

1.5

XM30PB/2

CA 7-9

CT 7-24-1.6

1-1.6

0.75

1.8

XM30PB/2.6

CA 7-9

CT 7-24-2.4

1.6-2.4

1.1

2.6

XM30PB/4.0

CA 7-16

CT 7-24-4

2.4-4

1.5

3.4

XM30PB/5

CA 7-16

CT 7-24-4

2.4-4

2.2

4.8

XM30PB/8

CA 7-16

CT 7-24-6

4-6

6.5

XM30PB/10

CA 7-30

CT 7-24-10

6-10

8.2

XM30PB/12

CA 7-30

CT 7-24-10

6-10

5.5

11

XH125NJ/20

CA 7-30

CT 7-24-16

10-16

7.5

14

XH125NJ/20

CA 7-30

CT 7-24-16

10-16

11

21

XH125NJ/32

CA 7-30

CT 7-24-24

16-24

15

28

XH125NJ/50

CA 7-43

CT 7-45-30

18-30

18.5

34

XH125NJ/50

CA 7-43

CT 7-45-45

30-45

22

40

XH125NJ/63

CA 7-43

CT 7-45-45

30-45

30

55

XH125NJ/100

CA 7-85

CT 7-75 2)

45-60

37

66

XH125NJ/100

45

80

XH125NJ/125
1

CA 7-85

CT 7-75 )

60-75

CA 6-105-(El)

CT 6-90

70-90

55

100

XH125NJ/125 )

CA 6-105(El)

CT 6-110

85-110

75

130

XH250NJ/250

CA 6-140-(El)

CT 6-150

105-150

90

155

XH250NJ/250

CA 6-170-El

CT 6-200

110

200

XH250NJ/250 )

CA 6-210-El

140-200
4

160-400

CEF 1-41/42 )

132

225

XS400SE/400

CA 6-210-El

CEF 1-41/42 )

160-400

150

250

XS400SE/400

CA 6-250-EI

CEF 1-41/42 4)

160-400

160
200

270
361

XS400SE/400
XS400SE/400

CA 6-300-El
CA 6-420-El

160-400

160-400

CEF 1-41/42 )
CEF 1-41/42 )
2

200

361

XS400SE/400

CA 5-450

CEF 1- 22 )

160-400

250

425

XS630SE/630

CA 5-700

CEF 1- 52 2)

160-630

320

538

XS630SE/630

CA 5-700

CEF 1- 52 )

160-630

Notes: 1) Use magnetic only breaker or next higher circuit breaker/contactor combination. Refer NHP for factory
modification.
2
) Use with separate mounting bracket.
3
) Thermal or electronic overload relays may be used.
4
) Electronic overloads.
Combinations based on the thermal overload relay tripping before the circuit breaker at overload
currents up to the motor locked rotor current.

13
13 - 133

Type 2 short circuit co-ordination


Motor starter co-ordination table
for DOL starting
65 kA, 400-415 V to AS 3947-4-1

TYPE 2
65 kA

Motor size
(kW)

Approx.
(amps)

Terasaki circuit
breaker type

Sprecher + Schuh
contactor type

Sprecher + Schuh Setting range


overload type 1) (amps)

0.37

1.1

XM30PB/1.4

CA 7-9

CEP 7

1.0-2.9

0.55

1.5

XM30PB/2

CA 7-9

CEP 7

1.0-2.9

0.75

1.8

XM30PB/2.6

CA 7-9

CEP 7

1.0-2.9

1.1

2.6

XM30PB/4.0

CA 7-16

CEP 7

1.6-5

1.5

3.4

XM30PB/5

CA 7-16

CEP 7

1.6-5

2.2

4.8

XM30PB/8

CA 7-16

CEP 7

3.7-12

6.5

XM30PB/8

CA 7-30

CEP 7

3.7-12

8.2

XM30PB/12

CA 7-30

CEP 7

3.7-12

5.5

11

TL30F/20A

CA 7-30

CEP 7

3.7-12

7.5

14

TL30F/30A

CA 7-30

CEP 7

12-32

11

21

TL30F/30A

CA 7-30

CEP 7

12-32

15

28

TL100NJ/50A

CA 7-43

CEP 7

12-32

18.5

34

TL100NJ/50A

CA 7-43

CEP 7

12-37

22

40

TL100NJ/63A

CA 7-43

CEP 7

14-45

30

55

TL100NJ/100A

CA 7-72

CEP 7

26-85

37

66

TL100NJ/100A

CA 7-72

CEP 7

26-85

45

80

TL100NJ/100A

CA 6-105-(El)

CT 6-90

70-90

55

100

XH400SE/250

CA 6-105-(El)

CT 6-110

85-110

75

130

XH400SE/250

CA 6-140-(El)

CT 6-150

105-150

90

155

XH400SE/250

CA 6-170-El

CT 6-200

140-200

110

200

XH400SE/250

CA 6-210-El

CEF 1-41/42 3)

132
150

225
250

XH400SE/400
XH400SE/400

CA 6-210-El
CA 6-250-EI

160-400

CEF 1-41/42 )

270

XH400SE/400

CA 6-300-El

CEF 1-41/42 )

160-400

200

361

XH400SE/400

CA 6-420-El

CEF 1-41/42 3)

160-400

250
320

361
425
538

XH400SE/400
XH630SE/630
XH630SE/630

CA 5-450
CA 5-700
CA 5-700

160-400

160-630

160-630

CEF 1- 22 )
CEF 1- 52 )
CEF 1- 52 )

Notes: 1) Thermal or electronic overload relays may be used.


2
) Use with separate mounting bracket.
3
) Electronic overloads.
Combinations based on the overload relay tripping before the circuit breaker at overload
currents up to the motor locked rotor current.

13 - 134

160-400

CEF 1-41/42 )

160
200

13

160-400

Type 2 short circuit co-ordination


Motor starter co-ordination table
for DOL starting
85 kA, 400-415 V to AS 3947-4-1

TYPE 2
85 kA

Motor size
(kW)

Approx.
FLC (A)
at 415 V

Terasaki circuit
breaker type

Sprecher + Schuh
contactor type

Sprecher + Schuh
overload type 1)

0.37

1.1

XM30PB/1.4

CA 7-9

CEP 7-M32-2.9-10

1.0-2.9

0.55

1.5

XM30PB/2

CA 7-9

CEP 7-M32-2.9-10

1.0-2.9

0.75

1.8

XM30PB/2.6

CA 7-9

CEP 7-M32-2.9-10

1.0-2.9

1.1

2.6

XM30PB/4

CA 7-16

CEP 7-M32-2.9-10

1.0-2.9

1.5

3.4

XM30PB/5

CA 7-16

CEP 7-M32-5-10

1.6-5

2.2

4.8

XM30PB/8

CA 7-30

CEP 7-M32-12-10

3.7-12

6.5

XM30PB/8

CA 7-30

CEP 7-M32-12-10

3.7-12

8.2

XM30PB/10

CA 7-30

CEP 7-M32-12-10

3.7-12

5.5

11

TL100NJ/20

CA 7-30

CEP 7-M32-12-10

3.7-12

7.5

14

TL100NJ/20

CA 7-30

CEP 7-M32-32-10

12-32

17

TL100NJ/32

CA 7-30

CEP 7-M32-32-10

12-32

10

19

TL100NJ/32

CA 7-30

CEP 7-M32-32-10

12-32

11

21

TL100NJ/32

CA 7-30

CEP 7-M32-32-10

12-32

15

28

TL100NJ/50

CA 7-43

CEP 7-M32-32-10

12-32

18.5

34

TL100NJ/50

CA 7-43

CEP 7-M37-37-10

12-37

22

40

TL100NJ/63

CA 7-43

CEP 7-M45-45-10

14-45

30

55

TL100NJ/100

CA 7-72

CEP 7-M85-85-10

26-85

37

66

TL100NJ/100

CA 7-72

CEP 7-M85-85-10

26-85

45

80

TL250NJ/160

CA 6-105

CEP 7-M85-85-10

26-85

55

100

TL250NJ/160

CA 6-105

CEF 1-11/12

0.5-180

75

135

TL250NJ/250

CA 6-210-El

CEF 1-11/12

0.5-180

90

160

TL250NJ/250

CA 6-210-El

CEF 1-11/12

0.5-180

110

200

TL250NJ/250

CA 6-210-EI

CEF 1-41/42/52

160-630

132

230

TL400NE/400

CA 6-210-El

CEF 1-41/42/52

160-630

160

270

TL400NE/400

CA 6-300-El

CEF 1-41/42/52

160-630

200

361

TL400NE/400

CA 6-420-El

CEF 1-41/42/52

160-630

Notes:

Setting range
(amps)

1
) Thermal or electronic overload relays may be used.
Combinations based on the overload relay tripping before the circuit breaker at overload currents up
to the motor locked rotor current.

13
13 - 135

its
f
w
No Bs to

C
C
M 00 A
8

13 - 136

You might also like