DAU Specification (Latest)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Specifications

Data Acquisition Unit


Description
The Data Acquisition Unit (DAU) is part of the S8000 Plus System. It
samples the signal inputs such as rotating speed, vibration, process
variables, converts them from analog to digital and transfers the data to
WEB8000 Plus.
It supports the TCP/IP protocol based on the Ethernet (10M/100M)
standard, and transmits data via the enterprise network. In addition it is
characterized by high speed, high accuracy, high reliability, easy
Figure: PWR8000 Plus

installation and connection, maintenance-free.


Meanwhile, the DAU is the first field acquisition station in the world with
a WEB function. From a computer on the same network with the DAU, a
user can view spectrum and other data from the DAU with IE browser.
According to the application and capacity, there are 6 types of DAU. They
are NET8000 Plus, NET8000 Dual, PWR8000 Plus, PWR8000 Dual and
HYD8000 Plus, HYD8000 Dual.

Figure: PWR8000 Plus Rear View

Type of the DAU


Application

NET8000 Plus

PWR8000 Plus

HYD8000 Plus

NET8000 Dual

PWR8000 Dual

HYD8000 Dual

Rotating

>4000 RPM

>1000RPM

12RPM

Speed

32000 RPM

4000RPM

1000RPM

Petroleum
Industry

Coal Fired Power,

&chemical,

Nuclear Power

Steel & Aluminum

Hydro Power

Number of Inputs of the DAU


Signal Type

NET8000 Plus

NET8000 Dual

PWR8000 Plus

PWR8000 Dual

HYD8000 Plus

HYD8000 Daul

Rotating Speed

Vibration

24

48

Hard-Wired Process

12

24

Page 1 of 5

Specifications of DAU
Turn green if the corresponding vibration signal is
normal

Inputs

STATIC
(1-12/24) LEDs:

Power Supply:
AC220V10% 50Hz

Turn green if the corresponding process

AC110V10% 50Hz

signal is normal

Power
Consumption:
Max. 80 Watts

Communications
Protocol:

Data Port
(Backboard):
Max. 19.2kbps Serial Communication (2

MODBUS:
Communication with DCS system to

RS232 ports)

obtain process signals


10Base-T/100Base-TEthernet (1 RJ45

HTTP:
Communication with WEB8000 Plus

port)

server to transmit data

Outputs

Backboard
Communications:

Front Panel LEDs:

RS232
Protocol

PWR LED:
Turn green when the DAU is powered on

Supported:
MODBUS

OK LED:
Turn green when the DAU is operating

Baud Rate:
Max. 19.2kbps

properly
Cable Length:

LAN LED:

Max.15meters

Turn green if the communication with


WEB8000 Plus is fine via Ethernet

Connector:
DB9 serial cable

COM1 LED:
Turn green if the communication is fine

Backboard

on COM1 port

Communications:
Ethernet, 10Base-T/100Base-TX

COM2 LED:
Turn green if the communication is fine

Protocol

on COM2 port

Supported:
HTTP
Cable Length:

K1-K4/K8 LEDs:

Max. 100 meters

Turn green if the corresponding rotating


speed signal is normal.
DYNAMIC

(1-24/48) LEDs:

Connector:
RJ45 (telephone jack style)

Data Collection
Page 2 of 5

Filter Performance: 2-step RC filter,

Rotating Speed Inputs:

cut-off frequency: 2Hz

Supports max. 8 rotating speed


signals, 1 rotating speed processing
cards, 8 A/D cards. The speed range

Data Processing and Analysis

support is 12~32000rpm.

Characteristics of Data Processing:

Input Type: Differential DC Input

Max. Sampling Speed:

Input Resistance: 400K

4096 samples/revolution

Input Range: 100V

A/D Resolution: 14bits

Linear Range: 18V

Max. Spectrum Lines: 3200

Filter Performance: Filters AC

User-configurable Synchronous

signals whose peak-peak value is

waveform sampling rates:

less than 20% of reference threshold

-1024 samples/rev for 8 revolutions

Volts.

- 512 samples/rev for 16/8

Phase Delay:

revolutions

<1 degree when

- 256 samples/rev for 32/16/8

rotating speed24000 RPM

revolutions

Rotating Speed Error <1.5rpm

-128 samples/rev for 64/32/16/8

Reference Threshold Voltage:

revolutions

Strong Rotating Speed Signal:

-64 samples/rev for

1V/2V/3V/4V/5V/6V/7V/8V;

128/64/32/16/8 revolutions

Weak Rotating Speed Signal:

-32 samples/rev for

0.2V/0.4V/0.6V/0.8V/1.0V/1.2V/1.

256/128/64/32/16/8 revolutions

4V/1.6V

Characteristics of Data analysis:

Vibration Inputs:
Supports max. 48 vibration signals,

Vibration waveform

12 vibration condition cards

Tacho phase signal waveform

Input Type: Displacement

Harmonic component vibration

/velocity/acceleration

Vibration harmonic component:

Input Resistance: 400K

1X,

Input Range: 100V

frequency bands

DC Linear Range: 20V

Different vibration type, ture p-p,

AC Linear Range: 4V/2V (Max.)

p-p, Rms, P;

DC Error:

<0.01V

Parameter value.

AC Error:

<0.008V

1P, 2X, 2P, 0.5X, two

Filter Performance: 1-step RC filter,

Data Storage

cut-off frequency: 0.1Hz, 1.6K Hz

Sensitive Monitoring Technology:


Distinguish frequency component

Process Inputs:
Support Max. 24 process signals, 2

of vibration: overall value, 1X, 1P,

process condition cards

2X, 2P, frequency band X, residual

Input Type: Differential DC Input

Input Resistance: 400K

Thresholds for event identification:

Input Range: 100V

-Overall value amplitude

Linear Range: 20V

-1X amplitude and phase

DC Error:

-2X amplitude and phase

<0.01V

Page 3 of 5

-Frequency band 1 amplitude

Max. relative humidity 80%

-Frequency band 2 amplitude

Main supply voltage fluctuations up

-Residual amplitude

to 10% of the nominal voltage

Automatic statistic learning to get

Rated pollution degree II

thresholds

Degree of protection IP 20

Characteristics of Data Storage:


Time-driven

CE Mark Directives

Event-driven

EMC Compliance

Data Type:

Management Group Issued


Real time data

Certificate No.:
EC10147

Trend data
Previous hour data

EC61326:
2006, Emissions

8, previous day data


9, previous week data

EN55011:

10, previous month data

1998+A1: 1999, Radiated and

11, previous year data

Conducted Emissions

13, startup/shutdown data

EN61000-3-2:
2000, Harmonic Current Emissions

14, sensitive monitoring data


3, 4, 5, black box data

EN61000-3-3:
1995+A1:2001,Voltage Fluctuations

6, before sensitive monitoring data


7, load throw-off data

EC61326:
2006, Immunity

Data Upload

EN61000-4-2:
Edition 1.2(2001), Electrostatic

Under good network condition;

Discharger Immunity Test

- Data upload frequency: up to


1s/time

EN61000-4-3:
2002, Radiated, Radio-Frequency,

- With high ratio data compress

Electromagnetic Field Immunity Test

technology, narrow net band


needed: 2kbps/channel.

EN61000-4-4:
2004, EFT/Burst Immunity

When network interrupted:


- Data be temporarily saved in

EN61000-4-5:
Edition 1.1:2001, Surge Immunity Test

the memory
- Memory space can last for 15

EN61000-4-6:
Edition 2.0(2003), Conducted Immunity

days.
- Upload be continued

EN61000-4-8:

automatically when network

Edition 1.1(2001), Power Frequency

recovered

Magnetic Field Immunity Test

Environmental Requirement

EN61000-4-11:
2004, Voltage Dips and Short
Interruptions Immunity Test

Indoor use
Altitude up to 2000m
Temperature 5 to 40

EC61010:
Safety requirement for electrical

Page 4 of 5

equipment for measurement, control,


and laboratory use

Physical Parameters
Dimensions
(Height Width Depth):
134mm452mm451mm
Weight:
17kg
Rack Installation
Requirement:
3U

Page 5 of 5