Saudi Aramco Inspection Checklist: Vent Piping Connection SAIC-S-4041 18-May-05 Plumb
Saudi Aramco Inspection Checklist: Vent Piping Connection SAIC-S-4041 18-May-05 Plumb
Saudi Aramco Inspection Checklist: Vent Piping Connection SAIC-S-4041 18-May-05 Plumb
SAIC NUMBER
DATE APPROVED
SAIC-S-4041
PROJECT TITLE
WBS / BI / JO NUMBER
EQUIPMENT ID NUMBER(S)
EQUIPMENT DESCRIPTION
REV. NO.
18-May-05
QR NUMBER
PLUMB
CONTRACTOR / SUBCONTRACTOR
EQPT CODE
SYSTEM ID.
PLANT NO.
MH's SPENT
TRAVEL TIME
ITEM
No.
ACCEPTANCE CRITERIA
REFERENCE
A1
SAES-S-060
Para 7.1
A2
SAES-S-060
Para 313.9
A3
SAES-S-060
Para 1.2
A4
The diameter of an individual vent shall not be less than one and onefourth (1-1/4) inches nor less than one-half the diameter of the drain to
which it is connected. (UPC Para 904.1). Also see item No. A19 in this
SAIC for extra requirements
SAES-S-060
Para 1.2
A5
Where vents connect to a horizontal drainage pipe, each vent pipe shall
have its invert taken off above the drainage center line of such pipe
downstream of the trap being served. (UPC 905.2)
SAES-S-060
Para 1.2
A6
SAES-S-060
Para 1.2
A7
Whenever two or more vent pipes converge, each such vent pipe shall
rise to a point at least in height above the flood level rim of the plumbing
fixture it serves before being connected to any other vent
(UPC Para 905.3)
SAES-S-060
Para 1.2
A8
Vents less than six (6) inches above the flood level rim of the fixture shall
be installed with approved drainage fittings, material and grade to
drain.(UPC Para 905.3)
SAES-S-060
Para 1.2
A9
Each vent pipe or stack shall extend through its flashing and shall
terminate vertically not less than six (6) inches above the roof nor less
than one (1) foot from any vertical surface (UPC Para 906.1)
SAES-S-060
Para 1.2
Each vent shall terminate not less than ten (10) feet from, or at least
three (3) feet above any openable window, door, opening, air intake, or
A10
vent shaft, nor less than three (3) feet in every direction from any lot line;
alley and street excepted (UPC Para 906.2)
SAES-S-060
Para 1.2
A11
SAES-S-060
Para 903.1.2
A12
Vent pipes for outdoor installation shall extend at least ten (10) feet
above the surrounding ground. (UPC Para 906.4)
SAES-S-060
Para 1.2
SAES-S-060
Para 905.7
A14
Vent from indirect waste shall extend separately to the outside air.
(UPC Section 803.0)
SAES-S-060
Section 1.2
A15
No vent from indirect waste piping shall combine with any sewer
connected vent. (UPC Section 803.0)
SAES-S-060
Section 1.2
Page 1 of 2
PASS
FAIL
N/A
RE-INSP DATE
SAIC-S-4041
PROJECT TITLE
ITEM
No.
DATE APPROVED
WBS / BI / JO NUMBER
ACCEPTANCE CRITERIA
REFERENCE
A16 All wet vented fixtures shall be within the same story (UPC Para 908.1)
SAES-S-060
Para 1.2
Each wet vented section (Vertical piping between any 2 consecutive inlet
levels) shall be a minimum of one pipe size larger than the required
minimum waste pipe size of the upper fixture or shall be one pipe size
A18
larger than the required minimum pipe size for the sum of the fixture
units served by such wet vented section, which ever is larger, but in no
case smaller than 2 inches. (UPC Para 908.2)
SAES-S-060
Para 1.2
SAES-S-060
Para 1.2
A19
SAES-S-060
Para 1.2
SAES-S-060
Para 313.9 c
A21
18-May-05
PLUMB
CONTRACTOR / SUBCONTRACTOR
PASS
FAIL
N/A
RE-INSP DATE
SAES-S-060
Para 1.2
Fixtures with a continuous vent discharging into a wet vent shall be within
the same story as the wet vented fixture.(UPC Para 908.1)
A17
QR NUMBER
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-S-060 -- Saudi Aramco Plumbing Code, January 28, 2004
2-SAES-S-010 -- Sanitary Sewers, 31 December, 2002
3-Uniform Plumbing Code (UPC), 2000
Contractor / Third-Party
Saudi Aramco
Construction Representative*
PMT Representative
T&I Witnessed
QC Record Reviewed
Work Verified
T&I Witnessed
QC Record Reviewed
Work Verified
T&I Witnessed
QC Record Reviewed
Work Verified
QC Inspector
PID Representative
Performed Inspection
QC Supervisor
Name, Organization,
Initials and Date:
Y = YES
Page 2 of 2
N = NO F = FAILED