Matrix CRH 004

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

R [004-032]

HIGH PERFORMANCE AIR COOLED CHILLER

SERVICE MANUAL

English
Cod. 273044
Rev. 25.05.2005

Issued by T.D.Service

Caution
It
S
S
S

is recommended that:
the manual is retained for the entire service life of the machine;
the user reads the manual carefully before carrying out any operations on the machine;
the machine is used exclusively for the purpose for which it is intended; incorrect use of the machine shall release the
manufacturer from any liability.
This manual has been prepared to enable the end ---user to carry out only those operations that can be done with the panels
closed. Any operations that require the opening of doors or equipment panels must be carried out only by qualified personnel.
Each machine is equipped with an electric isolating device which allows the operator to work in conditions of safety. This
device must always be used to eliminate risks during maintenance (electric shocks, scalds, automatic restarting, moving
parts and remote control).
The panel key supplied with the unit must be kept by the person responsible for maintenance.
For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts, read the identification
labels affixed to the outside and inside of the unit.
IMPORTANT:

This manual may be subject to modification; for complete and up ---to---date information the user should
always consult the manual supplied with the machine.

Index
1 --

2 --

3 --

4 --

5 -6 -7 -8 --

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.1
1.2
1.3
1.4

---------

Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Responsibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1
1
1
1

2.1
2.2
2.3
2.4
2.5

-----------

Operating limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound pressure levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Foundations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1
2
2
2
2

3.1
3.2
3.3
3.4

---------

Aeraulic connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hydraulic connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection of the safety valve discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2
2
3
4

4.1
4.2
4.3
4.4
4.5
4.6

-------------

Initial check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
First start---up (or after a long stop) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting and stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chillers serving special plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Freecooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Microprocessor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5
5
5
5
5
5

Preliminary Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Start-- Up and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Refrigerant and Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

5.1 --5.2 ---

Refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Oil charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

6.1 ---

Setting thermostatic expansion valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

7.1 --7.2 ---

Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dismantling the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

8.1
8.2
8.3
8.4
8.5

Pump set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Water chiller with partial heat recovery (20%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Water chiller with total heat recovery (100%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hydraulic circuit accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Water chiller with inertia tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Safety Devices Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6


Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
-----------

8
8
8
8
9

Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

1 --- Introduction

ducts of condensation air in machine intake (if present) and


outlet.
Each unit is completely factory assembled; after evacuation, the
necessary quantity of refrigerant is added to the refrigerant circuit(s) and the unit is tested.
All the units are equipped with one or two independent refrigerating circuits, each one composed of: an air ---cooled condenser,
a hermetic Scroll compressor and a braze ---welded plate evaporator. The components of the liquid line are the charging valves,
filters---dryers, solenoid valve, shut---off valve, moisture indicator
and thermostatic expansion valve.
The hydraulic circuit --- with max. working pressure 5 bar --- is
made up on mod. 004---016 of hydraulic lines both in steel and
flexible EPDM rubber, connected by fittings and threaded joints,
on mod. 017---032 of carbon steel pipes connected with
grooved ---end (Victaulic) fittings and couplings and include also
a flow switch (optional) and, in the freecooling versions, chilled
water coils and a three ---way valve.
The hermetic scroll compressors are complete with the following
protection/safety devices: oil heater (if necessary), electronic
protection monitoring the temperature of the motor windings
and the direction of rotation (the latter may be enclosed in the
electronics of the compressor or external, depending on the
model).
Fans are radial type, with aluminum reverse curved blades and
structure, statically and dynamically balanced, directly coupled
to a motor with external rotor. It is always available the fan speed
control which normally is achieved through an adjuster with continuous speed modulation.
By simply modifying the parameters (of the Microface microprocessor control), limiting the fan max. rotation speed, it is possible
to change the useful air static pressure (equal to the difference
of the static pressure between the delivery and suction ducts
connected with the unit).
The MATRIX R water chillers are controlled by the MICROFACE microprocessor, managing all the unit operating conditions.
The user can change and/or modify the operating parameters
through the display keyboard installed on the electrical panel.
The electrical control board is equipped with all the safety and
operating devices required for reliable operation. The compressor motors are equipped with protection on all three phases and
are started by three ---pole contactors.

1.1 --- Foreword


This handbook is aimed at enabling both the installer and the operator to carry out the correct installation, operation and maintenance of the refrigerating machine, without damaging it or causing injuries to the relevant staff.
The handbook is thus an aid for the qualified staff in the arrangement of the specific equipment for the correct installation, operation and maintenance in compliance with the local regulations
in force.
The MATRIX R water chillers can be identified as follows:

CRH004
Cooling Capacity kW
Nominal cooling capacity / 10
Compressor:
H Hermetic Scroll
Version:
R Radial
Execution:
C Chiller
S Superchiller

1.2 --- Responsibility


Liebert Hiross accepts no present or future responsibility for
damage to persons, things or to the machine itself due to operators negligence, failing to comply with the installation, operation
and maintenance instructions of this handbook, failed application of the safety norms in force for the system and the qualified
staff charged with the operation and maintenance.

2 --- Preliminary Operations

1.3 --- Inspection

2.1 --- Operating limits

All units are fully assembled and wired in the manufacturing


plant. Before shipment they are charged with the necessary
quantities of refrigerant and oil and then tested at the operating
conditions normally required by the customer. The machines
hydraulic circuit is equipped with drain plugs and open vent
valves; the free ---cooling coils are supplied dry to avoid possible
problems due to frost in the storage period. Immediately inspect
the machine carefully on delivery to check for damage during
transportation or missing components; possible claims must be
made immediately to the carrier and the factory or its representative.

The units can operate within the indicated operating limits (see
Tab. 6). These limits apply to new machines, subject to correct
installation and maintenance.
S Ambient air minimum temperature: ---25C for Superchiller,
---10C for Chiller (either Triac or EC fan);
S Maximum outdoor air temperature is in relation to each model, as indicated in Tab. 6. In any case outdoor temperatures
aver 45C are not admitted; such limits are determined by
electrical and electronic components fitted on units;
S Maximum water flow allowed: depending on the pressure
drop corresponding to the required thermal difference (usually not lower than 3.5C --- 4C);
S Minimum allowed water flow: compatible with a sufficient
evaporation temperature, to avoid the intervention of the
safety devices (to be evaluated for a thermal difference not
higher than 8C);
S Temperature range of the water exiting the evaporator: 4C
--- 15C;
S Maximum temperature of the water entering the unit: 20C;
higher temperatures are allowed only at the system start--up and not during normal operation;
S Maximum glycol concentration: 50% (35% with the optional
pump assembly installed on the machine);

1.4 --- General description


MATRIX R units with air ---cooled condensers have been designed and manufactured for producing chilled water.
They are also available in versions with a built---in freecooling
module, in versions with heat recovery for simultaneous heating
of thermal circuit water, with a pump assembly installed on the
machine and/or inertial buffer tank inside the machine; the chilling units can be equipped with several options indicated in the
price list.
The MATRIX R product line has been designed utilising the
state ---of ---the ---art techniques available nowadays in the industry, and includes all the components necessary for automatic
and efficient operation.
The Matrix R units are specifically designed for indoor installation (protected from weather agents), for the connection with

3 --- Installation

Minimum allowed glycol concentration: depending on the


minimum temperature of the ambient air expected at the
installation site (see Tab. a);
S Maximum difference of air side pressure (between the one
in the delivery duct and the one, possibly negative, in the
coil suction) equal to the max. one indicated in Tab. 9 next
to the max. signal = 10 V set on the microprocessor;
S Maximum pressure of the hydraulic circuit: 5 bar;
S Voltage range for the electric supply: 400 V +/ --- 10%; max.
phase difference: 3%; tolerance on frequency: 1%.
Storage conditions: ---20C 45C for all MATRIX R models.
S

3.1 --- Aeraulic connections


The Matrix R units are arranged with connection flanges for the
air intake and delivery ducts; if the units are ordered with metal
filters to protect the condensing coils, the connection flanges for
the intake side ducting are not supplied, as there is no duct to
enable the cleaning of such filter.
Connect the ducts fitting flexible joints to prevent transmitting
vibrations and to compensate thermal expansion. Check if the
holes on the walls --- where the intake and delivery ducts are
fitted --- are protected by suitable anti ---rain grilles (equipped
with pre ---filter like the intake ones) to avoid water or dust to enter
in the chiller.
All fans are adjusted at the same speed, so that it is not necessary to install overpressure dampers next to each fan discharge.
The units are supplied with a setting in the microprocessor for
the max. fan speed of 50 Pa useful pressure; set the max. speed
according to the features required by the installation (see
Tab. 9).
The units are supplied with the condensation air discharge upwards; during the installation, it is possible to change the position of the air discharge opening (with right or left horizontal
direction) by simply inverting the position of the drilled panel
with the closed one of the required side (see size drawings).

2.2 --- Sound pressure levels


The Tab. 7 shows the noise data for the units in standard configuration (without pumps), operating continuously and measured
at 1 m from the coil side unit, with ducted air delivery and 50 Pa
of useful static pressure, in free field conditions.
The highest noise levels are detected for higher useful static
pressures of the air.
Note:
Avoid positioning in areas with possible reverberation of the
sound waves; acoustically insulate both the delivery and the intake ducts (if installed); failure to do this can adversely effect the
noise levels.

2.3 --- Transport

3.1.1 -- External air temperature probe installation

Handle the unit by lifting it with a crane from above;


The lifting holes are positioned in the frames base (when lifting, use spreader bars to protect the sides, see Fig. 3, Fig. 4
and Fig. 5).
Note:
Place the lifting tubes in the holes in the base indicated by LIFT
HERE. Lock the ends of the tubes with the locking pins and
splits pins as shown in Fig. 3 and Fig. 5. As an alternative (on
mod. 004---016 only), shackles/hooks (optional) fastened at the
base ends can be used as a lifting system: in this case the lifting
point must be on the vertical line passing through the machines
centre of gravity (as indicated in Fig. 4) to prevent any load imbalance.
The capacity of the lifting gear must be adequate to lift the load
in question. Check the weight of the units, the capacity of the lifting gear and ropes and the condition and suitability of the aforementioned equipment.
S
S

Install the external air temperature probe (shipped inside the


electric panel), at the end of the air intake duct.
The bulb must be positioned as much outside as possible but
must not be exposed to direct sunlight or weather agents such
as rain or snow. The unit operation could be jeopardized if these
precautions are not applied.
If the intake side duct is not present, fasten the probe in the room
so that it can correctly detect the external temperature of the coil
intake outer air without being influenced by other external factors
(sun rays, rain or snow, other heat or radiation sources, etc.).

3.2 --- Hydraulic connections


3.2.1 -- Hydraulic circuit construction (Fig. a)
The piping must be connected to the chiller. Construct a chilled
water circuit as described below, see Fig. a:
1) Place shut---off valves within the circuit to allow servicing;
2) Install a pump system suitable for the flow rate required at
a pressure head equal to the sum of all the pressure drops
(see project data).
Matrix R chillers can be equipped, upon request, with
pumps having performance as indicated in Tab. 8;
3) Install manometers at the chiller inlet/outlet;
4) Install thermometers at the chiller inlet/outlet;
5) Connect the pipes to the chiller by flexible joints to avoid
transmitting vibrations and to balance the thermal expansion; proceed in the same way even if the pump set is outside the chiller;
6) It is useful to include a water pressure switch to give an early
warning of low water pressure;
7) Place a mesh filter at the inlets of the pump and water chiller
(Can be supplied as an optional accessory ---Not fitted);
8) Install, at the highest points in the circuit, apparatus which
allows the bleeding of air and possibly the filling of glycol;
9) Place a drain valve at the lowest point in the circuit and immediately at the outlet of the water chiller;
10) Install a water filling set including the following:
a) filling water meter;
b) manometer;
c) non ---return valve;
d) air separator;
e) removable supply tube, which must be disconnected
after each charge/top ---up;

2.4 --- Foundations


The unit must be placed on a level surface which will support
its weight.
S If necessary, position the unit on suitable anti ---vibration supports that can be supplied as an option (in rubber or spring --type). Refer to the manual Installation of the spring anti --vibration supports for their correct positioning.
S When positioned, level the unit.
Note:
For weight distribution see Fig. 6 and Fig. 7.
Note:
The weights and their distribution refer to standard units without
options; if the pump assembly, or other options are installed on
the machine, add the weights of the installed accessories to
those of the standard units (see Tab. 8).
S

2.5 --- Service area


S

In order to allow free air flow or to enable the ducting installation and maintenance of the unit, a minimum area must be
left free of obstructions around the unit (see Fig. 1 and
Fig. 2).
Avoid recirculation of hot air between the outlet and the outdoor intake of the air conveyed in the ducts, otherwise the
unit performance may be impaired or the standard operation can be interrupted.

11) For maximum protection ensure that all tubing exposed to


low outdoor temperatures is fitted with anti ---freeze heaters
and insulated using closed cell synthetic rubber (elastomer);
12) The circuit must include an expansion vessel (with safety
valve) of suitable capacity;
13) Connect the lines avoiding stresses on the machine inner
parts.
Note:
If the water chiller is complete with an expansion vessel (supplied as an option), check if the capacity is enough, and install
a second vessel in the circuit, if required (see par. 8.4).
Follow the indications in Fig. c for the correct sizing.
Note:
The whole circuit must contain a water volume suitable for the
capacity of the installed chiller. Check if the inertial capacity given by the sum of the hydraulic volume inside the machine (including the volume of the optional interna tank, if fitted) and the
system volume is sufficient, or possibly install a tank in the circuit.
Follow the indications in Fig. b for the correct sizing.
Note:
The hydraulic circuit must ensure a constant water supply to the
evaporator in every operating condition. Otherwise, the compressors may be damaged by repeated returns of liquid refrigerant on their suction.
Note:
The water flow switch is a compulsory safety component that
must be installed and correctly wired to the Matrix R chillers,
otherwise the guarantee will be invalidated.
It is installed, as standard, on units with the optional on ---board
pump set, and is available as a option for units without pumps
on board: in the latter case the flow switch, if not installed on the
machine, can be installed on the hydraulic circuit by the installer,
but it is compulsory that it is wired to the electric panel terminal
board, as indicated on the wiring diagram.

3.2.3 -- Water-- glycol mixture


Water ---glycol mixtures are used as the thermal carrier fluid in
very cold climates or with temperatures below zero degrees centigrade. Determine the ethylene glycol % which must be added
to the water, with the assistance of Tab. a.

Tab. a -- Ethylene glycol to be added to water (% in


weight of total mixture)

10

20

30

40

50

Freezing temperature, C (*)

---4.4

---9.9

---16.6

---25.2

---37.2

Mixture density at
20C (*), kg/l

---

1.017

1.033

1.048

1.064

1.080

For the chiller internal water volume refer to Tab. 1. If the optional
buffer tank is installed on the machine, add the tank hydraulic
volume.
ALWAYS CHARGE THE HYDRAULIC CIRCUIT WITH THE REQUIRED GLYCOL % NECESSARY FOR THE MINIMUM AMBIENT TEMPERATURE AT THE INSTALLATION SITE. FAILING
TO COMPLY WITH THIS INSTRUCTION SHALL INVALIDATE
THE UNIT WARRANTY.

3.3 --- Connection of the safety valve discharge

Very important:
Add water and ethylene glycol to the circuit with a % depending
on the minimum temperature of the outside air expected at the
installation site. Do not exceed the nominal operating pressure
of the circuits components.
Notes:

Ethylene glycol
(% in weight)

(*) Values are for Shell antifreeze 402. For different brands, check
manufacturers data.

3.2.2 -- Addition of water and ethylene glycol

Fig. a -- Ideal chilled water circuit

To avoid stratification run the circulation pump for at least 30


minutes after adding any glycol.
After adding water to the hydraulic circuit always disconnect the water supply coming from the sanitary supply;
this avoids the danger of glycol entering the sanitary water
system.
After any topping ---up of the water check the concentration
and add glycol if necessary.

Safety valves are installed on the high pressure side of the refrigeration circuit(s): the discharge of these valves must be conveyed outside through a suitable pipe, having a diameter of at
least that of the valve outlet, without burdening the valve body.
Convey the discharge to areas where the jet cannot harm
people and the surrounding environment.

1
8

CHILLER

disconnect after charge

flow

Vpt
Tank

USER
9
10a

10b

10c

10d

10e

12

11

Fig. b -- Inertia tank sizing


The total optimum hydraulic volume of the system where the Matrix R chiller is installed can be calculated by the
following formula:

V=

43 x Rt
Xd

where:
--- V=minimum required total water volume expressed in litres
--- Rt=refrigeration capacity expressed in kW
--- Xd=differential band set on the control and expressed in degrees centigrade
Please note that the sum of the hydraulic volume of the Matrix R chiller (Vm) plus the volume of the hydraulic circuit
connected to it (Vpc) must be greater than, or equal to the minimum required total water volume (V). If this condition is not satisfied, it is necessary to install an inertia tank (Vpt, as indicated in the Fig. a) with a volume at least
equal to the following value: Vpt=V ---Vm ---Vpc

Fig. c -- Sizing of the expansion vessel


The total volume of the expansion vessel is calculated with the following formula:

V=

Cxe
Pi
1 -Pf

where:
--- C=quantity of water inside the system expressed in litres
--- e=water expansion coefficient, with water at 10C as a reference
--- Pi=absolute pressure of initial charging, equivalent to the vessel pre ---charge pressure (typical value
2.5 bara)
--- Pf=absolute final tolerated pressure, lower than the operating pressure of the safety valve calibration
pressure (typical value 4.0 bara).
Use the values of the water expansion coefficient indicated in the table below:
H2O T [C]

Density [kg/m3]

10

999.6

--- --- ---

20

997.9

0.0017

30

995.6

0.0040

40

992.2

0.0075

50

988.1

0.0116

Expansion coefficient e

3.4 --- Electrical connections

1) Before proceeding with the electrical connections, ensure


that:
S all electrical components are undamaged;
S all terminal screws are tight;
S the supply voltage and frequency are in accordance with
the rating (with tolerance in accordance with IEC 8---6
norms, March 1990)
S the allowed phase to phase variability is 3% maximum
(see Fig. d). Variability in excess of 3% invalidates the
guarantee.
2) Supply cable connections (see Tab. 5):
S Connect the cable to the supply terminals.
S Use appropriately sized 3---pole cable. An earth wire
must also be connected.
S After having opened the passage in the framework (pre --punched knock ---outs) for the supply line entry, restore
the original degree of protection using suitable accessories for the wiring and junction boxes.

Fig. d -- Example of calculating phase


to phase variability
1) The 400 V supply has
the following variability:
RS = 388 V
ST = 401 V
RT = 402 V

R S T

2) The average voltage is:

388 + 401 + 402


= 397
3
3) The maximum deviation from the average is:
402 --- 397 = 5 V
4) The phase to phase variability is:

5
x 100 = 1.26 (acceptable)
397

7) During the unit start ---up an inlet water temperature


higher than 20C is allowed. Under standard operating
conditions check that the limits indicated in paragraph
2.1 are not exceeded.
8) Check the correct operation of the control and safety devices.
9) Check the outlet temperature of the chilled water (check if
the set---point set on the controller is reached).
10) Check the compressor oil level.
11) With the compressor at full load, check there are no
bubbles visible in the frefrigerant sight glass. If there are any,
charge the unit according to par. 5.

Note:
The power supply should never be disconnected, except when
performing maintenance.
Operate (open) the main switch before carrying out any maintenance work on electrical components.
Note:
It is forbidden to work on the electrical components without
using insulating platforms, and in the presence of water or fog
or mist.
Note:
The supply to the external pump assembly must be made before
starting the chiller and must be kept on as long as the chiller is
in use. Incorrect operation will cause the unit to lock ---out because of the internal protections (flow switch intervention).
Note:
The compressors are equipped with an electronic protection device blocking their start if the phase sequence is not correct, or
stopping their operation if a thermal relay intervenes. This device
is essential for the integrity of the mechanical and electrical components of the compressors. Reset the standard functions by
isolating this device and removing the causes of the lock ---out.
Note:
The chillers are equipped with their own microprocessor control
adjustment. The use of the remote ON ---OFF input (located in
the electric panel terminal board) as a system temperature control element is forbidden.

4.3 --- Starting and stopping


ALWAYS ENSURE THAT THE COMPRESSOR OIL HAS BEEN
PREHEATED.
FOR BRIEF STOPPAGES MAINTAIN THE SUPPLY TO THE
CRANKCASE HEATER (IF ANY).
S Start the unit setting the Microprocessor switch ON.
S Stop the unit setting the Microprocessor switch OFF.
S In case of long stops, turn the machine off using the Microprocessor switch OFF.
In this case the compressor crankcase heaters (if any) remain powered.
S For seasonal shutdown of the unit operate the main switch
located on the main electrical power supply. This will disconnect the compressor crankcase heaters.

4.4 --- Chillers serving special plants

4 --- Start---Up and Operation

The units are capable of cooling a water ---glycol mixture to temperatures close to 0C without the need for significant modifications. In the case of modification, the set values of the safety and
control components must also be changed. This can be carried
out in the factory (at the time of testing) or at the time of installation, only by qualified and authorised personnel.

4.1 --- Initial check


1) Check all water connections.
2) Open the shut---off valve on the liquid line.
3) Ensure that the intake pressure is higher than 4.0 bar; if this
is not the case, prolong pre ---heating of the compressor (if
possible) and check that the refrigerant shut---off valve is
properly sealed, see Fig. 12, Fig. 13, Fig. 14, Fig. 15, Fig. 16
and Fig. 17.
4) Open all isolating valves and/or water ball valves.
5) In case of climates with temperatures below zero degrees C,
make sure the chilled water circuit is filled with the correct
concentration of water/glycol.
6) Bleed all air out of the chilled water circuit.
7) Verify the water flow rate and its direction.
8) Ensure that the thermal load is sufficient for start---up.
Caution:
The ambient air temperature probe must be positioned in the
shade and protected against the weather.

4.5 --- Freecooling


The freecooling is a system of pre ---cooling and/or cooling the
water/glycol mixture using ambient air when the latter is at a temperature below the return mixture temperature. If the outside
temperature is sufficiently low to dissipate the entire heat load,
the refrigeration compressors automatically switch off, and the
mixtures temperature is controlled by the fan speed adjustment.
If the mixture temperature is too high for freecooling, the compressors will operate as long as necessary to ensure the correct
water/glycol mixture temperature.

4.6 --- Microprocessor control


Consult the Microface and Hiromatic Service Manual.

4.2 --- First start ---up

(or after a long stop)

5 --- Refrigerant and Oil Charge

Operate as follows:
1) At least 8 hours before the start ---up, power the crankcase heaters (if any, see point 4) by setting the main isolator switch ON. Make sure the auxiliary circuit has been
powered and check the operation (a fault due to an incorrect procedure will invalidate the compressor guarantee).
2) Open the valves of the refrigeration circuit that had been
closed before the initial check.
3) Check the machinery supplying the thermal load connected
with the unit and start the system pump(s).
4) MAKE SURE THE COMPRESSOR OIL HAS BEEN HEATED
FOR AT LEAST 8 HOURS; start the unit only then. In the
units not equipped with crankcase heaters (Chillers for summer operation only, without modulating fan speed control),
the start must be carried out in the warm season only (external T > 15C), and thus oil pre ---heating is not necessary.
5) Make sure the fans rotate in the correct direction (anticlockwise): check the electrical connections, if necessary.
6) Make sure the pumps rotate in the correct direction.

All work on pipes or components of the refrigerating circuit under pressure must be exclusively carried out by qualified staff,
competent in such works.

5.1 --- Refrigerant charge


WHILST REPAIRING THE REFRIGERATING CIRCUIT RECOVER ALL THE REFRIGERANT IN A CONTAINER: DO NOT
ALLOW IT TO ESCAPE. NEVER USE THE COMPRESSOR
FOR THE SYSTEM VACUUM (THIS INVALIDATES THE
WARRANTY).
S The unit is delivered charged according to the Tab. 2.
Warning for the refrigerant charge:
S Ensure there are no refrigerant leaks.
S Check the refrigerant type in the refrigeration circuit: a unit
originally charged by the manufacturer with R407C cannot
be charged with R22 and vice versa; possibly apply to the
Technical Support Department.

Charge with the compressor in operation, connecting the


cylinder with the charge connector after the thermostatic expansion valve.
Flush the connection pipe between the cylinder and the
charging point; tighten the seal joint and then start charging
the unit. It is imperative that the cylinder is weighed both before and after the operation.
S For the units with R407C the refrigerant charge must be
made exclusively with liquid refrigerant.
S Charge the unit until the bubbles in the sight glass have disappeared and the working conditions of the entire refrigeration circuit have returned to normal (sub ---cooling and superheating within the limits indicated below).
S Measure the superheating as follows:
1) Detect the temperature on the suction line, close to the
bulb of the thermostatic expansion valve, using a contact
thermometer.
2) Connect a pressure gauge (by max. a 30---cm pipe) with
the Schraeder connection and read the corresponding
saturated evaporating temperature.
3) The superheating is the difference between the two
readings.
4) For the units with R407C refer to the pressure gauge
scale indicated with the initials D.P. (Dew Point)
S Verify that the superheating is 5C --- 8C.
S Measure the sub ---cooling as follows:
1) Detect the temperature on the liquid line using a contact
thermometer.
2) Connect a pressure gauge (by max. a 30---cm pipe) with
the Schraeder connection on the liquid line and read the
corresponding saturated condensing temperature.
3) The sub ---cooling is the difference between the two readings.
4) For the units with R407C refer to the pressure gauge
scale indicated with the initials B.P. (Bubble Point)
S Verify that at the condenser outlet, sub ---cooling is 3C --5C.
IT IS IMPORTANT TO CARRY OUT CHARGING CORRECTLY.
An excess of refrigerant causes an increase in sub ---cooling and

consequent operating difficulties in the hot season; a shortage


of charge generates an increase in superheating and possible
compressor stoppages. Whenever work is carried out on the
unit, ensure afterwards that the working conditions are correct,
checking sub ---cooling and superheating.

5.2 --- Oil charge


Contact the Technical Support Department for the specifications
of the oil to be used for topping up; the oil changes according to
the type of used refrigerant.
NEVER MIX DIFFERENT OILS TOGETHER. CLEAN THE PIPING COMPLETELY BEFORE CHANGING THE TYPE OF OIL
USED.
TOP---UPS OF UP TO 20---30% OF THE TOTAL AMOUNT OF
OIL CONTAINED IN THE COMPRESSOR CRANKCASE ARE
PERMITTED; FOR LARGER PERCENTAGES CONTACT THE
TECHNICAL SUPPORT DEPARTMENT.

5.2.1 -- Procedure for oil topping -- up


If there has been any loss of oil then this must be topped up as
follows:
1) Take a clean, dry, transparent container (with volume calibrations) and fill it with at least twice the amount of oil required.
2) Isolate the compressor by closing the cock on the liquid line.
3) Connect to the fittings on the compressor body (Schraeder
valves) and empty it of refrigerant until atmospheric pressure (1 bar) is reached.
4) Using a pipe, connect the oil container to the oil service fitting
on the lower part of the compressor.
5) Open the oil service cock, lifting the container, so that the oil
flows by gravity.
6) Charge the required quantity of oil (make sure the tube always remains below the oil level in the container).
7) Stop the oil flow by closing the oil service fitting, open the
shut---off cock on the refrigerating circuit and restore the
drained refrigerant charge.

6 --- Safety Devices Settings


The water chiller has already been tested and set up by the manufacturer. The following setting values are suggested in the field.
COMPONENT

SETTING

NOTES
set

diff.

Operation with R407C/R22


(standard factory setting):
Low pressure switch (LP)

START
DIFF.
STOP

0.2 1.5
0.5
5
bar

: 3.6 bar
: 0.8 bar
: 2.8 bar

bar

Operation with R407C/R22


(standard factory setting):
High pressure switch (HP)

STOP
START
DIFF.

: 26 bar
: 20 bar
: 6 bar (fixed)

reset

The settings for the safety valves installed on the machine are indicated below:
MODELS

SETTINGS

004---204---206---207---008

28 bar

006---007---011---014---016
017---020---023---025---028---030---032

29 bar

SAFETY VALVE
HP side

6.1 --- Setting


valve

thermostatic

expansion

c) The superheating is the difference between the two


readings (b ---a).
4) The superheating must be 5C --- 8C; if not, set the expansion valve as follows:
a) Remove the protective cover;
b) Turn the adjustment screw to return to the optimum values, tightening it in a clockwise direction to increase the
superheating, or slackening it to reduce the superheating.
c) Wait about 10 minutes;
d) Measure the superheating and repeat the operation if
necessary.
N.B:
If the superheating is too low, there is a risk of poor lubrication
and consequent breakage of the compressor as a result of pressure shock.
If the superheating is too high the output of the system is limited
and the compressor overheats.

THIS OPERATION MUST BE PERFORMED BY AN EXPERIENCED REFRIGERATION TECHNICIAN.


Before beginning this adjustment be sure that the refrigerant
charge is correct, checking the the sub ---cooling (3C --- 5C, as
specified in par. 5.1).
The valve has already been factory ---set and should be reset
when the superheating is not between 5C --- 8C, as follows:
1) Important:
Ensure that the instructions in par. 5.1 have been carried out.
2) Allow the compressor to operate for 15 mins.
3) Measure the superheating as follows:
a) Connect a manometer to the Schraeder connection located on the evaporator outlet tube, and read the manometric temperature on the scale for the refrigerant used
(for the units with R407C refer to the pressure gauge
scale indicated with the initials D.P. = Dew Point).
b) Using a contact thermometer, measure the temperature
on the tube coming out of the evaporator, next to the
socket used for the manometer.

7 --- Maintenance
7.1 --- Spare parts

The Maintenance Programme below must be carried out by a


qualified technician, preferably working under a maintenance
contract.
Before any intervention on the unit or accessing the inner components (removing the outer panels), always ensure the machine is switched off. If the panels are removed (fans compartment) wait for the fan(s) to come to a complete stop before
accessing the compartment; if the front panels are removed (on
mod. 004---016) or the front lower panels (on mod. 017---032),
pay special attention when working near the compressor upper
part and the discharge line: they are very hot; possibly wait for
them to cool. Be very careful when operating close to the finned
coils, as the fins are very sharp. Do not remove the fan protection
grille before electrically isolating the whole machine. Do not insert foreign matter through the fan protection grille. After the
maintenance interventions, always close the unit with the suitable panels, fastened by the tightening system.

The use of original spare parts is recommended.


When placing an order refer to the Component List enclosed
with the machine and quote the unit model no. and serial no.

7.2 --- Dismantling the unit


The machine has been designed and built to ensure continuous
operation.
The working life of some of the main components, such as the
fans and the compressors, depends on the maintenance that
they receive.
If the unit has to be dismantled, the job must be done by skilled
refrigeration technicians.
The refrigerant and the lubricating oil in the circuit must be disposed of in conformity with the laws in force in your country.

Maintenance programme -- Monthly check


FANS

S
S

Check that the fan motor rotates freely without any abnormal noise, and ensure that the
bearings are not running hot.
Also check the current absorption.

Check the conditions of the filters (if they are supplied); if necessary clean them (including
the electrical panel ventilation filter).
Check the condenser coils and clean if necessary with compressed air or soft brushes.

CONTROL

Check that the control equipment, LEDs and display are operating correctly.

ELECTRICAL CIRCUIT

S
S

Check the electrical supply on all phases.


Ensure that all electrical connections are tight.

Check the condensing and the evaporating pressures (to be done by a refrigeration technician).
Check the compressors current absorption, the delivery temperature and possible unusual
noises.
Check the refrigerant charge by means of the sight glass.
Check that the safety devices operate correctly.
Check the correct operation of the thermostatic valve (superheating between 5C --- 8C).
Check that the oil level indicated by the compressor sight glass is higher than the min. value.

CONDENSER AND AIR FILTER

S
REFRIGERATION CIRCUIT

S
S

S
S

CHILLED WATER CIRCUIT

S
S
S
S
S
S
S

Ensure that there are no water leaks.


Bleed any air out of the hydraulic circuit using the bleed valves.
Verify that the water flow rate is correct.
Check the inlet --- outlet liquid temperature and pressure.
Check the correct operation of the three--- way valve (Versions with free--- cooling only).
Check if the system is charged with the specified glycol percentage and that no ice has
formed in the hydraulic circuit.
Check the evaporator cleanliness.

8 --- Options and Accessories


8.1 --- Pump set

tected by a suitable anti ---frost heater that operates when the system is stopped. It is recommended that a safety valve be
installed in the hydraulic circuit to avoid hazards due to overpressures, if there is no water flow through the recuperator.
The water temperature at the recuperator inlet (in stable operating conditions) must be in the range of 25C --- 45C, with an outlet differential of between 3.5C --- 8C.

On mod. 004---016 the centrifugal pump units are direct driven,


with close ---coupled motors and a single shaft; the induction motor has 2 poles with IP 54 protection and class F insulation.
The materials used for the pump main components are:
S Pump body in plastic material PA 6.6 (cast iron in all high
pressure freecooling versions and on model 016 in the Chiller high head pressure version and Superchiller standard
head pressure version);
S Impeller in in plastic material PPO (stainless steel in all high
pressure freecooling versions and on model 016 in the Chiller high head pressure version and Superchiller standard
head pressure version);
S Stainless steel shaft;
S Graphite impregnated ceramic mechanical seal (EPDM in
all high pressure freecooling versions and on model 016 in
the Chiller high head pressure version and Superchiller
standard head pressure version), suitable for the use of mixtures containing ethylene glycol.
The pump units have been chosen and sized to operate within
specific limits, namely:
S Water / ethylene glycol mixtures up to 65% / 35% by weight;
S Temperatures of the standard pumped fluid not lower than
4C.
The hydraulic circuit includes, for each pump, a suction shut---off
valve and a delivery check valve if two pumps are installed, or
suction and delivery shut---off valves if a single pump is installed.

8.3 --- Water chiller with total heat recovery


(100%)
All heat discharged by the unit to the condenser is recovered.
The system includes an additional refrigerating circuit made up
of a three ---way solenoid valve, supplying --- in case of hot water
demand --- a plate exchanger, usually by ---passed and sized so
as to discharge all condensing heat (also installed before the
finned air condenser in series with it); a check valve, a liquid receiver at the exit of the finned air condenser working as storage
for the needed additional refrigerant charge (see refrigerating
scheme). The recuperator is insulated with closed cell polyurethane and is equipped with heaters activated when the recuperator is deactivated to prevent frost in winter with the system
stopped or not perfectly drained.
The operation in total recovery mode is enabled by an external
contact. The Microface control will simultaneously suit the fan
speed changing the fan speed setpoint differently from the standard operation without recovery (practically slowing the fans
down till they switch off); anyway, the operation in recovery
mode is enabled also without load at the users. Indeed, if the users do not demand heat, the water flowing to the condenser
reaches a temperature that does not enable the total condensation of the compressed gas, and the remaining portion of the
phase change can thus take place in finned coil without interrupting the recovery process through the intervention of the machine safety devices.
If the plate exchanger is supplied with too cold water, or if the system is not preset by the installation technician with a three or
two---way proportional adjustment valve for the exchanger bypass (indispensable for cold starts, see following Recommended hydraulic circuit ), the condensing pressure tends to
decrease too much; a prolonged condition of low condensing
temperature below the safety threshold leads the Microface microprocessor control to disable the heat recovery, protecting the
system from any possible malfunctioning.

On mod. 017---032 the centrifugal pump units are direct driven,


with close ---coupled motors and a single shaft; the induction motor has 2 poles with IP 55 protection and class F insulation.
Pump casings and impellers are in cast iron EN ---GJL 200, shafts
are in stainless steel, the shaft seal is a unbalanced, mechanical
shaft seal with dimensions according to DIN 24 960 and assembly length according to EN 12 756, brass neck ring permits ideal
conditions for the use of water mixtures containing ethylene glycol. The pump housing, the motor stool and the motor stator
housing are electrocoated.
The pump units have been chosen and sized to operate within
specific limits, namely:
S Water / ethylene glycol mixtures up to 65% / 35% by weight;
S Temperatures of the standard pumped fluid not lower than
4C.
The motor stool forms connection between the pump housing
and the motor, and is equipped with a manual air vent screw for
venting of the pump housing and the shaft seal chamber. It is
very important to carry out this operation as the circulation of liquid through the duct of the air vent screw ensures lubrication and
cooling of the shaft seal.
Between the outlets of the two chambers and the discharge
flange, twin ---head pumps have a non ---return flap valve in
EPDM rubber. The flap is opened by the flow of the pumped liquid and cuts off the port of the idle pump chamber.

Fig. e -- Recommended hydraulic circuit

Heat recovery
users

Heat recovery
exchanger

8.4 --- Hydraulic circuit accessories


Made up of an expansion vessel (pre ---charged at 1.5 bar, max.
operating pressure 10 bar) and a safety valve, set at 5 bar. Their
position in the hydraulic circuit is illustrated in Fig. 18, Fig. 19,
Fig. 20, Fig. 21, Fig. 21 and Fig. 22.
S Expansion vessel volume:
--- 8 litres for all 004---016 units,
--- 12 litres for all 017---032 units.
It is recommended that the total required expansion vessel capacity is always checked, depending on the units internal hydraulic volume (with the volume of the buffer tank, if installed),
the user circuit volume, the glycol percentage in the mixture, and
the expected maximum temperature variation of the mixture.
The water flow switch is a compulsory device protecting the unit.
It is installed, as standard, on units with the optional on ---board
pump set, and is available as a option for units without pumps

In the electrical panel there are, for all the models of pumps, automatic circuit breakers for each pump; the microprocessor control manages the operating rotation between the two pumps and
start---up of the stand ---by pump if the primary pump fails.
For the technical features of the pumps and the hydraulic schematic see Tab. 8, Fig. 18, Fig. 19, Fig. 20, Fig. 21, Fig. 21 and
Fig. 22.

8.2 --- Water chiller with partial heat


recovery (20%)
This option enables the recovery of up to 20% of the heat normally rejected by the condensers. The system does not require any
adjustment and is made up of plate heat exchangers installed
on each circuit before the condenser. The exchangers are pro-

on board: in the latter case the flow switch, if not installed on the
machine, must be installed on the hydraulic circuit by the installer and wired to the electric panel terminal board, as indicated on
the wiring diagram.

8.5 --- Water chiller with inertia tank


The machine can be supplied complete with a buffer tank; it performs the inertial stabilizer function, for better compressor operation, summed up in the following two points:
S it reduces the frequency of the compressor peaks, which is
higher the lower the system thermal inertia, improving their
performance;
S it naturally eliminates the operational problems caused by
sudden load variations (shown by variations of the chilled
water temperature).
The buffer tank is supplied insulated, with a drain valve, vent
valve and connection for immersion electric heaters; maximum
operating pressure 6 bar.
Built in carbon steel and coated with anti ---condensation insulation. It can be installed in all MATRIX R 004---016 versions inside
the coil compartment, while on mod. 017---032 it is installed inside a cabinet which can be supplied either already connected
to the unit (mechanically and hydraulically jointed to it) or loose
(completely separate from the unit).
Mod. 004 ---006 ---007 technical data
S Internal volume:
200 litres
S Net weight:
110 kg
S Working weight: 310 kg
Mod. 008 ---011 ---014 ---016 technical data
S Internal volume:
400 litres
S Net weight:
140 kg
S Working weight: 540 kg
Mod. 204 ---206 ---207 technical data
S Internal volume:
160 litres
S Net weight:
100 kg
S Working weight: 260 kg
Mod. 017 ---032 technical data
S Internal volume:
1000 litres
S Net weight:
400 kg
S Working weight: 1400 kg

Tab. 1 --- Internal hydraulic volume


Unit volume (*) [l]

Model

CRH

CRH

Unit volume (*) [l]

Model

004

004

37

006

006

38

007

14

007

75

204

10

204

39

206

10

206

40

207

18

207

79

008

24

008

97

011

27

011

101

014

38

014

146

016

46

016

156

017

37

017

129

020

37

020

129

023

45

023

158

025

45

025

158

028

51

028

186

030

60

030

195

032

60

032

195

SRH

SRH

(*) Add the tanks volume for the units with optional buffer tank

Tab. 2 --- R 407C refrigerant and oil charge


CRH 004--016
004

006

007

204

206

207

008

011

014

016

Refrigerant charge (each circuit)

Models
[kg]

12.6

7.5

13.9

7.7

23.7

12.9

12.9

14.5

19.9

20.8

Oil charge (each circuit)

[lt]

6.2

8.0

8.0

3.25

3.25

3.3

6.2

8.0

8.0

8.0

017

020

023

025

028

030

032

Refrigerant charge (each circuit)

[kg]

21.0

21.6

30.7

30.8

36.8

39.4

39.5

Oil charge (each circuit)

[lt]

12.4

14.2

16.0

16.0

16.0

16.0

16.0

004

006

007

204

206

207

008

011

014

016

Refrigerant charge (each circuit)

[kg]

12.6

7.5

13.9

7.7

23.7

12.9

12.9

14.5

19.9

20.8

Oil charge (each circuit)

[lt]

6.2

8.0

8.0

3.25

3.25

3.3

6.2

8.0

8.0

8.0

017

020

023

025

028

030

032

Refrigerant charge (each circuit)

[kg]

21.0

21.6

30.7

30.8

36.8

39.4

39.5

Oil charge (each circuit)

[lt]

12.4

14.2

16.0

16.0

16.0

16.0

16.0

CRH 017--032
Models

SRH 004--016
Models

SRH 017--032
Models:

10

Tab. 3 --- CRH/SRH 004---032 --- Partial heat recovery (20%)


CRH/SRH 004--016
004
204

Model

006
206

007
207

008

011

014

016

Heating capacity

kW

10,8

14,8

18,2

21,6

29,6

36,4

44,3

Water flow

l/s

0,516

0,707

0,870

1,032

1,414

1,739

2,117

kPa

11

14

11

14

21

BSP---T

11/4

11/4

11/4

11/4

Water pressure drop


Water connections

Working conditions: outdoor temperature 35C, water inlet/outlet 12/7C (Chiller versions), glycol mixture 30% inlet/outlet 15/10C (SuperChiller versions).
Heat recovery conditions: water inlet/outlet 40/45C.

CRH/SRH 017--032
Model

017

020

023

025

028

030

032

Heating capacity

kW

40

48

56

62

68

79

86

Water flow

l/s

1.91

2.29

2.68

2.96

3.25

3.77

4.11

kPa

15

20

16

19

16

17

20

Water pressure drop


Water connections

BSP---T

Working conditions: outdoor temperature 35C, water inlet/outlet 12/7C (Chiller versions), glycol mixture 30% inlet/outlet 15/10C (SuperChiller versions).
Heat recovery conditions: water inlet/outlet 40/45C.

Tab. 4 --- CRH/SRH 004---032 --- Total heat recovery (100%)


CRH/SRH 004--016
004
204

Model

006
206

007
207

008

011

014

016

Heating capacity

kW

53

74

91

105

144

177

223

Water flow

l/s

2,53

3,54

4,35

5,02

6,88

8,46

10,65

kPa

60

70

80

60

70

80

90

Water pressure drop


Water connections

BSP---T

21/

21/

21/

21/2

030

032

Working conditions: water inlet/outlet 12/7C (Chiller versions). Heat recovery conditions: water inlet/outlet 40/45C.

CRH/SRH 017--032
Model

017

020

023

025

028

Heating capacity

kW

212

238

290

320

357

412

453

Water flow

l/s

10.13

11.37

13.86

15.29

17.06

19.68

21.64

kPa

52

65

71

82

83

85

99

Water pressure drop


Water connections

DN 80 --- 3

BSP---T

Working conditions: water inlet/outlet 12/7C (Chiller versions). Heat recovery conditions: water inlet/outlet 40/45C.

11

Tab. 5 --- Electrical characteristics


CRH 004--016 -- R 407C
Size
Power supply

004

204

006

206

---

OA (1)
FLA
LRA
Compressors power input (1)
Compressors nominal current (1)
Compressor max. current
Fans power input

A
A
A
kW
A
A
kW

Fans max. power input


Fans max. current

kW
A

SHC std. head pressure pump model (Opt.)


Std. head pressure pump motor nom. power
Std. head pressure pump motor max. power
Std. head pressure pump max. current
SHC high head pressure pump model (Opt.)
FHE high head pressure pump model (Opt.)
High head pressure pump motor nom. power
High head pressure pump motor max. power
High head pressure pump max. current

--kW
kW
A
----kW
kW
A

Electrical cable section (min.)

mm2

007

207

008

011

014

016

80
116
281
38.6
64
50
6.8

99
163
364
43.6
74
69
10.1

123
169
417
59.4
98
72
10.2

400 V / 3 Ph / 50 Hz
31
43
183
13.2
23
35
2.9

32
46
125
13.2
24
19
2.9

40
58
223
19.3
32
50
3.3

42
66
167
19.0
34
29
3.3

48
77
278
24.1
40
69
3.1

50
72
185
24.6
42
32
3.1

62
86
226
26.3
46
35
5.8

4.9
8.2
12 --- 129
0.75
1.08
1.85
12 --- 136
--1.1
1.44
2.67
16

16

25

25

12 --- 136
1.1
1.44
2.67
20--- 128
--1.5
1.92
3.90
35

35

35

20 --- 128
1.5
1.92
3.90
20 --- 134
--1.85
2.45
4.61
50

(1) Outdoor air temperature 35C; water inlet/outlet temperature 12/7C.


Nominal air flow and 50 Pa available air static pressure.

CRH 017--032 -- R 407C


Size
Power supply

017

OA (1)
FLA
LRA
Compressors power input (1)
Compressors nominal current (1)
Compressor max. current
Fans power input

A
A
A
kW
A
A
kW

Fans max. power input


Fans max. current

kW
A

SHC std. head pressure pump model (Opt.)


Std. head pressure pump motor power
Std. head pressure pump max. current
High head pressure pump model (Opt.)
High head pressure pump motor power
High head pressure pump max. current

--kW
A
--kW
A

Electrical cable section (min.)

020

---

mm2

023

025

028

030

032

225
323
571
111.7
184
72
16.5

245
329
577
124.8
204
72
18.1

400 V / 3 Ph / 50 Hz
125
165
305
57.3
100
35
9.7

135
195
360
64.9
110
50
9.7

163
233
398
77.7
130
50
13.1

183
271
472
90.1
150
69
13.1

199
317
518
94.5
158
69
16.5

4.9
8.2
65 --- 190/2
2.2
4.45
65 --- 260/2
4.0
8.00
70

95

(1) Outdoor air temperature 35C; water inlet/outlet temperature 12/7C.


Nominal air flow and 50 Pa available air static pressure.

12

65 --- 230/2
3.0
5.95
65 --- 260/2
4.0
8.00
120

150

65 --- 260/2
4.0
8.00
65 --- 340/2
5.5
11.20
185

185

185

70

20--- 134
1.85
2.45
4.61
--40--- 160/40
4.0
4.0
8.50
95

SRH 004--016 -- R 407C


Size
Power supply

004

204

006

206

007

32
43
183
13.4
24
35
3.2

32
46
125
13.4
24
19
3.2

41
58
223
19.8
33
50
3.8

42
66
167
19.4
34
29
3.8

49
77
278
24.8
41
69
3.3

---

OA (1)
FLA
LRA
Compressors power input (1)
Compressors nominal current (1)
Compressor max. current
Fans power input

A
A
A
kW
A
A
kW

Fans max. power input


Fans max. current

kW
A

SHC std. head pressure pump model (Opt.)


FHE std. head pressure pump model (Opt.)
Std. head pressure pump motor nom. power
Std. head pressure pump motor max. power
Std. head pressure pump max. current
SHC high head pressure pump model (Opt.)
High head pressure pump motor nom. power
High head pressure pump motor max. power
High head pressure pump max. current

----kW
kW
A
--kW
A

Electrical cable section (min.)

mm2

207

008

011

014

016

82
116
281
39.6
66
50
7.6

101
163
364
44.5
76
69
11.4

125
169
417
60.8
100
72
11.4

400 V / 3 Ph / 50 Hz
50
72
185
25.0
42
32
3.3

64
86
226
26.7
48
35
6.5

4.9
8.2
12 --- 136
--1.1
1.44
2.67
32--- 160/30
3.0
6.50
16

16

20 --- 128
--1.5
1.92
3.90
32 --- 160/30
3.0
6.50
25

25

35

35

20 --- 134
--1.85
2.45
4.61
40--- 160/40
4.0
8.50
35

50

70

--40--- 160/40
4.0
4.0
8.50
40--- 200/75
7.5
15.50
95

(1) Outdoor air temperature 35C; 30% glycol water mixture; water inlet/outlet temperature 15/10C.
Nominal air flow and 50 Pa available air static pressure.

SRH 017--032 -- R 407C


Size
Power supply

020

023

127
165
305
58.5
102
35
10.8

137
195
360
66.5
112
50
10.8

165
233
398
79.7
132
50
14.6

---

OA (1)
FLA
LRA
Compressors power input (1)
Compressors nominal current (1)
Compressor max. current
Fans power input

A
A
A
kW
A
A
kW

Fans max. power input


Fans max. current

kW
A

Std. head pressure pump model (Opt.)


Std. head pressure pump motor power
Std. head pressure pump max. current
High head pressure pump model (Opt.)
High head pressure pump motor power
High head pressure pump max. current

--kW
A
--kW
A

Electrical cable section (min.)

017

mm2

025

028

030

032

229
323
571
114.8
188
72
18.3

249
329
577
128.1
208
72
20.3

400 V / 3 Ph / 50 Hz
185
271
472
92.5
152
69
14.6

203
317
518
96.9
162
69
18.3

4.9
8.2
65 --- 260/2
4.0
8.00
65 --- 340/2
5.5
11.20
70

95

65 --- 340/2
5.5
11.20
65 --- 410/2
7.5
15.20
120

150

65 --- 410/2
7.5
15.20
65 --- 460/2
11.0
21.40
185

185

185

(1) Outdoor air temperature 35C; 30% glycol water mixture; water inlet/outlet temperature 15/10C.
Nominal air flow and 50 Pa available air static pressure.

Nominal power supply = 400 V; 3 Ph; 50 Hz


Nominal power supply tolerance = 400 V 10 %
Max. voltage unbalance = 3 %
The cables have to be sized in compliance with local standards and according to the type and characteristics of installation. Suggested cables section are
referred to PVC insulation with a max. working temperature of 70 C and an ambient temperature of 30 C.

13

Tab. 6 --- Operating limits


CRH 004--016 -- R 407C
Size

004

006

007

204

206

207

008

011

014

016

45

45

42

42

42

42

45

43

45

42

Working Range
Max. outdoor air temperature (1)

Safety Device Settings


High pressure switch
High pressure safety valve
Low pressure switch

Barg
Barg
Barg

26.0
28.0 / 29.0
2.8

(1) With nominal air flow; water flow outlet at 7C; full load

CRH 017--032 -- R 407C


Size

017

020

023

025

028

030

032

42.5

40.5

42.5

40.5

43.0

40.0

39.5

Working Range
Max. outdoor air temperature (1)

Safety Device Settings


High pressure switch
High pressure safety valve
Low pressure switch

Barg
Barg
Barg

26.0
29.0
2.8

(1) With nominal air flow; water flow outlet at 7C; full load

SRH 004--016 -- R 407C


Size
Working Range
Max. outdoor air temperature (2)

004

006

007

204

206

207

008

011

014

016

45.0

45.0

41.5

41.5

41.0

41.0

45.0

42.0

45.0

41.0

Safety Device Settings


High pressure switch
High pressure safety valve
Low pressure switch
(2)

Barg
Barg
Barg

26.0
28.0 / 29.0
2.8

With nominal air flow; 30% mixture flow outlet at 10C; full load

SRH 017--032 -- R 407C


Size
Working Range
Max. outdoor air temperature (2)

017

020

023

025

028

030

032

41.5

39.5

41.5

39.5

42.0

39.0

38.5

Safety Device Settings


High pressure switch
High pressure safety valve
Low pressure switch
(2)

Barg
Barg
Barg

26.0
29.0
2.8

With nominal air flow; 30% mixture flow outlet at 10C; full load

14

Tab. 7 --- Noise levels


The following table indicates the overall sound pressure level at full load conditions, measured 1m from the unit, coil side, with ducted
air discharge (50 Pa static pressure), with an outdoor temperature of 35 C and referred to free field conditions.
Total
sound level

Models

Total
sound level

Models

[dB(A)]

[dB(A)]

CRH / SRH 004 --- 204

70

CRH / SRH 017

74.5

CRH / SRH 006 --- 206

73

CRH / SRH 020

74.5

CRH / SRH 007 --- 207

74

CRH / SRH 023

75

CRH / SRH 008

71.5

CRH / SRH 025

75

CRH / SRH 011

74.5

CRH / SRH 028

76

CRH / SRH 014

75.5

CRH / SRH 030

76

CRH / SRH 016

75.5

CRH / SRH 032

78

Tab. 8 --- Pump set characteristics (opt.)


2 pole pump set, standard head pressure (data refers to each pump)
Models
CRH

004

204

006

206

007

207

008

011

014

016

Water flow

m3/h

6.79

6.79

8.86

8.73

10.94

11.11

13.41

17.53

22.78

28.00

Available head pressure

kPa

127

156

122

146

104

127

141

142

88

78

Pump quantity
Pump rotor model
Nominal motor power
Noise level

(*)

Nr.

---

12--- 129

12--- 136

20--- 128

20--- 134

kW

0.75

1.1

1.5

1.85

63

65

12.7

13.8

15.4

58

dB(A)

Pump weight

10.4

kg

(*) According to ISO 3744

2 pole pump set, high head pressure (data refers to each pump)
Models
CRH

004

204

006

206

007

207

008

011

014

016

Water flow

m3/h

6.79

6.79

8.86

8.73

10.94

11.11

13.41

17.53

22.78

28.00

Available head pressure

kPa

169

198

163

187

145

168

167

191

145

173

Pump quantity

Nr.

---

12--- 136

20--- 128

20--- 134

kW

1.1

1.5

1.85

Noise level (*)

dB(A)

58

63

65

70

Pump weight

kg

12.7

13.8

15.4

42

Pump rotor model


Nominal motor power

(*) According to ISO 3744

2 pole pump set, standard head pressure (data refers to each pump)
Models
CRH

017

020

023

025

028

030

032

Water flow

m3/h

26.93

29.26

35.67

38.38

44.20

50.71

55.23

Available head pressure

kPa

119

107

136

123

145

111

73

Pump quantity
Pump rotor model

1/2

Nr.
---

65--- 190 / 2

65--- 230 / 2

kW

2.2

Noise level (*)

dB(A)

60

59

63

Pump weight

kg

57.9 / 116.4

69.3 / 139.2

74.3 / 149.2

Nominal motor power

(*) According to ISO 3744

15

65--- 260 / 2

40--- 160/40

2 pole pump set, high head pressure (data refers to each pump)
Models
CRH

017

020

023

025

028

030

032

Water flow

m3/h

26.93

29.26

35.67

38.38

44.20

50.71

55.23

Available head pressure

kPa

197

187

182

170

230

204

173

Pump quantity

1/2

Nr.

Pump rotor model


Nominal motor power

---

65--- 260 / 2

kW

Noise level (*)

dB(A)

Pump weight

kg

65--- 340 / 2
6
63

74.3 / 149.2

89.2 / 178.9

(*) According to ISO 3744

2 pole pump set, standard head pressure (data refers to each pump)
Models
SRH

004

204

006

206

007

207

008

011

014

016

30% glycol/water mixture flow

m3/h

7.83

7.83

10.26

10.08

12.58

12.64

15.45

20.12

26.24

31.92

Available head pressure

kPa

98

142

62

100

93

128

96

91

50

79

Pump quantity
Nominal motor power
Noise level

Nr.

Pump rotor model


(*)

Pump weight

---

12--- 136

20--- 128

20--- 134

40--- 160/40

kW

1.1

1.5

1.85

dB(A)

58

63

65

70

kg

12.7

13.8

15.4

42

(*) According to ISO 3744

2 pole pump set, high head pressure (data refers to each pump)
Models
SRH

004

204

006

206

007

207

008

011

014

016

30% glycol/water mixture flow

m3/h

7.83

7.83

10.26

10.08

12.58

12.64

15.45

20.12

26.24

31.92

Available head pressure

kPa

233

277

183

221

199

234

197

170

138

223

Pump quantity

Nr.

Pump rotor model

32--- 160/30

---

Nominal motor power

2
40--- 160/40

40--- 200/75

kW

7.5

Noise level (*)

dB(A)

66

70

74

Pump weight

kg

35

42

64

(*) According to ISO 3744

2 pole pump set, standard head pressure (data refers to each pump)
Models
SRH

017

020

023

025

028

030

032

30% glycol/water mixture flow

m3/h

31.06

33.49

41.26

43.98

51.08

58.3

63.27

Available head pressure

kPa

77

51

118

92

103

146

94

Pump quantity

1/2

Nr.

Pump rotor model

---

65--- 260 / 2

65--- 340 / 2

65--- 410 / 2

kW

5.5

7.5

Noise level (*)

dB(A)

63

63

68

Pump weight

kg

74.3 / 149.2

89.2 / 178.9

91.1 / 182.7

Nominal motor power

(*) According to ISO 3744

2 pole pump set, high head pressure (data refers to each pump)
Models
SRH

017

020

023

025

028

030

032

30% glycol/water mixture flow

m3/h

31.06

33.49

41.26

43.98

51.08

58.3

63.27

Available head pressure

kPa

157

133

207

183

190

205

159

Pump quantity
Pump rotor model

1/2

Nr.
---

65--- 340 / 2

65--- 410 / 2

65--- 460 / 2

kW

5.5

7.5

11

Noise level (*)

dB(A)

63

68

65

Pump weight

kg

89.2 / 178.9

91.1 / 182.7

149.4 / 306.4

Nominal motor power

(*) According to ISO 3744

16

Tab. 9 --- Fan performances and settings


Standard air flow [12000 m3/h], 3 Ph fan + TRIAC
Models: CRH 004 --- 204 --- 008
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Pa
V
Rpm
W
dB(A)

50
5.0
1034
2860
87

100
5.2
1066
3090
88

150
5.4
1097
3320
88

200
5.6
1128
3530
88

250
5.8
1158
3720
89

300
6.0
1189
3910
89

350
6.3
1220
4090
89

400
6.7
1252
4250
90

450
7.2
1283
4420
90

500
7.9
1313
4600
91

Pa
V
Rpm
W
dB(A)

50
5.3
1081
3210
88

100
5.5
1113
3430
88

150
5.7
1143
3620
89

200
5.9
1173
3810
89

250
6.1
1204
4010
89

300
6.5
1236
4170
90

350
6.9
1268
4330
90

400
7.6
1298
4510
91

450
8.6
1328
4680
91

490
10.0
1351
4810
91

Pa
V
Rpm
W
dB(A)

50
8.2
1041
1560
86

100
8.5
1080
1790
87

150
8.8
1117
2030
87

200
9.1
1153
2270
88

250
9.4
1190
2520
88

300
9.6
1225
2780
89

350
9.9
1259
3040
89

370
10.0
1270
3120
89

Pa
V
Rpm
W
dB(A)

50
8.6
1099
1910
87

100
8.9
1135
2140
88

150
9.2
1172
2390
88

200
9.5
1208
2650
88

250
9.8
1242
2910
89

290
10.0
1270
3120
89

Pa
V
Rpm
W
dB(A)

50
5.6
1162
3320
91

100
5.8
1189
3550
91

150
6.1
1216
3770
92

200
6.4
1245
3980
92

250
6.9
1274
4170
92

300
7.5
1302
4360
92

350
8.4
1329
4560
93

395
10.0
1354
4740
93

Pa
V
Rpm
W
dB(A)

50
6.1
1215
3760
92

100
6.4
1243
3970
92

150
6.9
1273
4160
92

200
7.5
1301
4360
92

250
8.3
1328
4550
93

298
10.0
1355
4740
93

Pa
V
Rpm
W
dB(A)

50
9.1
1165
2100
90

100
9.4
1200
2360
90

150
9.7
1233
2620
91

210
10.0
1271
2940
91

Pa
V
Rpm
W
dB(A)

50
9.7
1232
2610
91

100
9.9
1264
2880
91

112
10.0
1271
2940
91

Models: SRH 004 --- 204 --- 008


Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Standard air flow [12000 m3/h], EC fan


Models: CRH 004 --- 204 --- 008
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]
Models: SRH 004 --- 204 --- 008
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Standard air flow [14000 m3/h], 3 Ph fan + TRIAC


Models: CRH 006 --- 206 --- 011 --- 014 --- 016
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]
Models: SRH 006 --- 206 --- 011 --- 014 --- 016
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Standard air flow [14000 m3/h], EC fan


Models: CRH 006 --- 206 --- 011 --- 014 --- 016
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]
Models: SRH 006 --- 206 --- 011 --- 014 --- 016
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Unit performances are referred to sea level conditions.

17

550
9.5
1343
4760
91

570
10.0
1352
4810
91

Standard air flow [15000 m3/h], 3 Ph fan + TRIAC


Models: CRH 007 --- 207
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Pa
V
Rpm
W
dB(A)

50
5.5
1179
3140
93

100
5.8
1205
3380
93

150
6.1
1232
3610
93

200
6.4
1259
3830
93

250
6.9
1287
4040
93

300
7.6
1313
4250
93

350
8.6
1339
4450
94

388
10.0
1360
4620
94

Pa
V
Rpm
W
dB(A)

50
5.7
1197
3300
93

100
6.0
1223
3540
93

150
6.3
1250
3770
93

200
6.8
1278
3980
93

250
7.4
1305
4180
93

300
8.1
1331
4380
94

354
10.0
1360
4620
94

Pa
V
Rpm
W
dB(A)

50
9.2
1169
1950
91

100
9.4
1204
2210
91

150
9.7
1236
2480
92

206
10.0
1272
2780
92

Pa
V
Rpm
W
dB(A)

50
9.4
1193
2130
91

100
9.6
1226
2390
92

150
9.9
1258
2660
92

172
10.0
1272
2780
92

50
5.4
1123
3230
90

100
5.6
1151
3440
90

150
5.8
1179
3660
90

200
6.1
1208
3870
91

250
6.4
1237
4060
91

300
6.9
1268
4240
91

350
7.5
1296
4430
92

400
8.3
1325
4620
92

50
5.8
1172
3600
90

100
6.0
1200
3810
91

150
6.3
1229
4010
91

200
6.8
1260
4190
91

250
7.3
1289
4380
91

300
7.9
1317
4570
92

350
9.6
1346
4750
92

360
10.0
1352
4790
92

50
8.9
1129
1960
89

100
9.1
1164
2200
89

150
9.4
1199
2460
90

200
9.7
1233
2720
90

258
10.0
1271
3030
90

50
9.4
1190
2390
89

100
9.6
1224
2650
90

150
9.9
1257
2920
90

170
10.0
1271
3030
90

Models: SRH 007 --- 207


Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Standard air flow [15000 m3/h], EC fan


Models: CRH 007 --- 207
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]
Models: SRH 007 --- 207
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Standard air flow [13250 m3/h], 3 Ph fan + TRIAC


Models: CRH 017 --- 020 --- 023 --- 025 --- 028 --- 030
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Pa
V
Rpm
W
dB(A)

Models: SRH 017 --- 020 --- 023 --- 025 --- 028 --- 030
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Pa
V
Rpm
W
dB(A)

Standard air flow [13250 m3/h], EC fan


Models: CRH 017 --- 020 --- 023 --- 025 --- 028 --- 030
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Pa
V
Rpm
W
dB(A)

Models: SRH 017 --- 020 --- 023 --- 025 --- 028 --- 030
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Pa
V
Rpm
W
dB(A)

Unit performances are referred to sea level conditions.

18

448
10.0
1352
4790
92

Standard air flow [14500 m3/h], 3 Ph fan + TRIAC


Models: CRH 032
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Pa
V
Rpm
W
dB(A)

50
6.0
1216
3620
92

100
6.3
1243
3850
92

150
6.8
1272
4050
93

200
7.3
1299
4250
93

250
8.0
1325
4450
93

Pa
V
Rpm
W
dB(A)

50
6.8
1272
4050
93

100
7.3
1300
4250
93

150
8.0
1326
4450
93

200
9.8
1354
4660
93

206
10.0
1357
4690
94

Pa
V
Rpm
W
dB(A)

50
9.6
1225
2470
91

100
9.9
1257
2740
91

124
10.0
1272
2870
91

Models: SRH 032


Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Standard air flow [14500 m3/h], EC fan


Models: CRH 032
Useful static pressure
Max. fan speed signal
Fan speed
Absorbed unitary power
Fan discharge sound power [PWL]

Unit performances are referred to sea level conditions.

19

300
9.7
1353
4660
93

308
10.0
1357
4690
94

500 (with duct)


1500 (without duct)

Fig. 1 --- Service areas CRH/SRH 004---016 (top view)

1000

Ordinary
maintenance area

AIR

Extraordinary
maintenance area
1000

1000 (*)

Notes:
Minimum distance between 2 units from condensing coil side = 2 m
(*) 1500 mm (with 160 --- 200 Lt Tank); 2500 mm (with 400 Lt Tank)

Fig. 2 --- Service areas CRH/SRH 017---032 (top view)

Ordinary
maintenance area

1500

AIR

Extraordinary
maintenance area
1000

Notes:
Minimum distance between 2 units from condensing coil side = 3 m

20

1000

Fig. 3 --- Lifting instructions with tubes CRH/SRH 004---016

PROTECTION PLANK
RIGID STRUTS
(POSSIBILY STEEL)

PART. A

LIFTING SYSTEM WITH TUBES

BELT OR CHORD

PART. A

BLOCKING PEG
(NOT SUPPLIED)
LIFTING TUBE
(NOT SUPPLIED)
(BASE HOLES 45)

PART. A

SPLIT PIN
(NOT SUPPLIED)

N.B:

Place the lifting tubes in the holes in the base indicated by the words LIFT HERE. Lock the ends of the tubes in position with
the locking pins and split pins as shown above A.
The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the unit, the capacity of the
lifting gear and ropes and the condition and suitability of the aforementioned equipment. Lift the unit with a speed suitable
for the load to be moved, so as not to damage the structure.
Lifting
(mm)

(m)

CRH / SRH 004 - 204 - 006 - 206

2006

1.7

' 3.5

' 8.5

CRH / SRH 007 - 207 - 008 - 011

3006

1.7

' 4.5

' 8.5

CRH / SRH 014 - 016

4006

1.7

' 4.5

' 8.5

Models

21

(m)

(m)

Fig. 4 --- Lifting instructions with straight shackle CRH/SRH 004---016

A2

A1

N.B.: LIFT IN THE BARICENTRE LINE G OF THE UNIT

PART. A

LIFTING SYSTEM WITH


STRAIGHT SHACKLE

Yg

Xg

PART. A

N.B:

STRAIGHT SHACKLE 14 (UNI 1947) A TYPE


(OPTIONAL)

The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the unit, the capacity of the
lifting gear and ropes and the condition and suitability of the aforementioned equipment.
Lift the unit with a speed suitable for the load to be moved, so as not to damage the structure.
Lifting
L

A1 + A2

CRH / SRH 004 - 204 - 006 - 206

2006

' 5.5

CRH / SRH 007 - 207 - 008 - 011

3006

' 6.5

CRH / SRH 014 - 016

4006

' 6.5

Models

22

(mm)

(m)

Baricentre G --- CRH/SRH 004 ---016

Unit baricentre position G --- (without water)


Models

Without tank

With tank

Xg
(m)

Yg
(m)

Xg
(m)

Yg
(m)

CRH 004

0.83

0.58

0.89

0.58

CRH 204

0.79

0.62

CRH 006

0.80

0.56

CRH 206

0.78

0.62

CRH 007

1.22

0.59

CRH 207

1.18

0.64

CRH 008

1.17

0.63

1.25

0.63

CRH 011

1.10

0.63

1.18

0.62

CRH 014

1.50

0.64

1.62

0.63

CRH 016

1.45

0.63

1.57

0.63

SRH 004

0.86

0.60

0.92

0.60

SRH 204

0.82

0.64

SRH 006

0.83

0.58

SRH 206

0.82

0.64

SRH 007

1.27

0.63

SRH 207

1.23

0.67

SRH 008

1.22

0.66

1.30

0.65

SRH 011

1.16

0.65

1.23

0.65

SRH 014

1.58

0.67

1.68

0.66

SRH 016

1.53

0.67

1.64

0.66

23

Not available

0.86

0.56
Not available

1.32

0.59
Not available

Not available

0.89

0.59
Not available

1.36

0.62
Not available

Fig. 5 --- Lifting instructions with tubes CRH/SRH 017---032

PROTECTION PLANK
RIGID STRUTS
(POSSIBILY STEEL)

BELTOR CHORD
BLOCKING PEG
(NOT SUPPLIED)
SPLIT PIN
(NOT SUPPLIED)
LIFTING TUBE
(NOT SUPPLIED)
(BASE HOLES 56)

N.B:

Place the lifting tubes in the holes in the base indicated by the words LIFT HERE. Lock the ends of the tubes in position with
the locking pins and split pins as shown above A.
The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the unit, the capacity of the
lifting gear and ropes and the condition and suitability of the aforementioned equipment. Lift the unit with a speed suitable
for the load to be moved, so as not to damage the structure.
Lifting
Models

CRH 017 - 020 - 023 - 025 - 028 - 030 - 032


SRH 017 - 020 - 023 - 025 - 028 - 030 - 032

24

10
1.0

' 5.5
55

' 9.0
90

(m)

(m)

(m)

Fig. 6 --- Support positions and loads (Note: weights refer to standard units)
CRH/SRH 004 - 016

W1

W2

W3

W4

W5

W9

W10

1127

1161

FOOT PRINT

1195

34

17

d=14
W7

W8

34

17

W6

120

120

Dimensions --- CRH/SRH 004 --- 016


Dimensions (mm)
Model

Size

CRH
SRH

004 --- 204 --- 006 --- 206


004 --- 204 --- 006 --- 206

2000

1760

---

---

---

CRH
SRH

007 --- 207 --- 008 --- 011


007 --- 207 --- 008 --- 011

3000

---

1380

---

---

CRH
SRH

014 --- 016


014 --- 016

4000

---

---

1160

1440

Weight distribution --- CRH/SRH 004 --- 016


Weight distribution (kg)

W1

W2

W3

W4

W5

W6

W7

W8

W9

W 10

004

221

---

---

---

151

241

---

---

---

165

204

276

---

---

---

173

262

---

---

---

164

006

238

---

---

---

151

276

---

---

---

176

206

283

---

---

---

174

269

---

---

---

165

007

240

---

137

---

137

246

---

140

---

140

207

288

---

152

---

152

253

---

134

---

134

008

314

---

164

---

164

285

---

149

---

149

011

369

---

169

---

169

338

---

155

---

155

014

299

299

---

136

136

265

265

---

121

121

016

320

320

---

136

136

285

285

---

121

121

004

254

---

---

---

193

241

---

---

---

183

204

308

---

---

---

215

262

---

---

---

182

006

271

---

---

---

192

275

---

---

---

195

206

316

---

---

---

216

268

---

---

---

184

007

280

---

186

---

186

241

---

161

---

161

207

328

---

203

---

203

248

---

154

---

154

008

361

---

222

---

222

278

---

171

---

171

011

419

---

227

---

227

329

---

178

---

178

014

356

356

---

198

198

265

265

---

148

148

016

378

378

---

197

197

284

284

---

148

148

Model

Size

CRH

SRH

25

Weight distribution with tank --- CRH/SRH 004 --- 016


Weight distribution (kg)
Model

Size

CRH

004

W1

W2

W3

W4

271

---

---

---

204
006

W6

W7

W8

W9

W 10

257

288

---

---

---

272

---

---

---

285

---

223

---

223

Not available
289

---

---

---

230

---

219

---

008

334

---

289

---

289

312

---

270

---

270

011

389

---

294

---

294

365

---

277

---

277

014

310

310

---

260

260

283

283

---

238

238

016

331

331

---

259

259

304

304

---

238

238

004

301

---

---

---

300

290

---

---

---

289

320

---

---

---

---

---

---

302

---

237

---

243

---

290

---

290

206
007

235

298

323

Not available
267

---

267

---

207

273

237

Not available

008

375

011
014
016

26

219

Not available

206
007

322

Not available

204
006

255

Not available

207

SRH

W5

---

350

---

350

311

433

---

362

362

354

---

354

362

---

297

---

297

---

326

326

289

289

---

259

259

385

385

---

325

325

308

308

---

260

260

Fig. 7 --- Support positions and loads (Note: weights refer to standard units)
CRH/SRH 017 - 032
A

W1

125

W3

W4

W7

W8

FOOT PRINT
d = 20
W5

W6
125

875

1500

60

1060

TANK
MOUNTED
(OPTION)
WT2

120

W2

1180

WT1

1300

60

120

1000

125

Dimensions --- CRH/SRH 017 --- 032


Tank
(supply not mounted on unit)

Dimensions (mm)
Model

120

60

1000

WA

125

017 --- 020

3750

1000

CRH / SRH

023 --- 025

4750

1500

CRH / SRH

028 --- 030 --- 032

5750

2000

1300

Weight distribution (kg)

WD

750

Size

CRH / SRH

W1

W2

W3

W4

W5

W6

W7

W8

Model

Size

CRH

017

196

196

233

233

261

261

310

310

020

203

203

250

250

274

274

337

337

023

240

240

327

327

312

312

427

427

025

240

240

327

327

312

312

427

427

028

273

273

382

382

345

345

482

482

030

281

281

383

383

368

368

502

502

032

280

280

393

393

371

371

520

520

017

252

252

283

283

293

293

328

328

020

259

259

300

300

306

306

355

355

023

305

305

395

395

348

348

450

450

025

305

305

395

395

348

348

450

450

028

351

351

463

463

385

385

508

508

030

359

359

471

471

402

402

528

528

032

358

358

482

482

405

405

545

545

60

d = 20

Weight distribution --- CRH/SRH 017 --- 032


1180

1060

FOOT PRINT

WC
120

WB

125

WA = WB = 406 kg
WC = WD = 299 kg
SRH

Weight distribution with tank --- CRH/SRH 017 --- 032


Weight distribution (kg)

WT1

W1

W2

W3

W4

WT2

W5

W6

W7

W8

Model

Size

CRH

017

443

443

261

261

261

462

462

273

273

273

020

440

440

279

279

279

467

467

296

296

296

023

447

447

351

351

351

477

477

374

374

374

025

447

447

351

351

351

477

477

374

374

374

028

460

460

400

400

400

489

489

425

425

425

030

464

464

403

403

403

508

508

441

441

441

032

460

460

412

412

412

507

507

455

455

455

017

478

478

309

309

309

467

467

302

302

302

020

475

475

326

326

326

473

473

325

325

325

023

486

486

413

413

413

482

482

410

410

410

025

486

486

413

413

413

482

482

410

410

410

028

507

507

475

475

475

496

496

464

464

464

030

508

508

485

485

485

505

505

483

483

483

032

504

504

494

494

494

505

505

496

496

496

SRH

27

Fig. 8 --- Rubber anti---vibration support + 1000 liters tank


Rubber support dimensions

Rubber support installation

Unit base

Fixing screw

Screw anchor
(not supplied)

CF

Cement base
L
Access hole for
support fixing

Single support code


Code

CF

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

270327

82

35

M10

11.0

110

60

128

270326

108

50

M16

16.5

160

83

190

Rubber supports + 1000 liters tank


Unit

Configuration

CRH --- SRH


204--- 206--- 004--- 006
CRH --- SRH
207--- 007--- 008--- 011

Support
kit code

Single support
code

485620
With or without
tank
ta

CRH --- SRH


014--- 016

485621

4
270327

485622

CRH --- SRH


017--- 020--- 023--- 025--- 028--- 030--- 032

Without tank

CRH --- SRH


017--- 020--- 023--- 025--- 028--- 030--- 032

With tank

485626

1000 liters tank

Loose supplied

485620

Kit support
pieces

6
8

485625

8
270326

Each kit is complete with stainless steel fixing screws and plain washers for unit assembly.

28

10
270327

279

6995

30

30

279

148

30

852 Ext.

Lateral view
(from D)

Flanged
942 (Opt.)

6995

30

769

875

Rear view
(Std. unit)

Fan and hole panel not


present on
mod. 007 - 207

1942 Flanged (Opt.)

279

148

2942 Flanged (Opt.)

852 Ext.

Rear view
(with heat recovery)

720

1522

132

852 Ext.
279

852 Ext.

Fan and hole panel not


present on mod. 007 - 207

875

A+40

148

852 Ext.

Top view

148

279

852 Ext.

Lateral view

Supply cable inlet


(Prepunch 67 + 30)

875

148

Fan and hole panel not


present on mod. 007 - 207

279

279

148

852 Ext.

852 Ext.

279

279

30

158

30

Removable panel
M

Duct Flanged (Opt.),


not possible with coil metal filters
E

Coil metal filters (Opt.), not possible


with ducted flange

Left air discharge


(move the A with C panel/s)
C

Right air discharge


(move the A with B panel/s)
B

30

691

Front view

352 Ext.

Over air discharge


(Standard supply)

Air flow

Electric panel and


control unit
(rear front
removable panel)

352 Ext. 151


1739

430,5 170 600,5

852 Ext.

2365

30
30

2242
2022
80
140
1201
30 (Opt.)

30

A + 40 (Heat recovery, Opt.)

1501 Flanged (Opt.)


110

151
352
Ext.
1739

Fig. 9 --- Overall dimensions CRH/SRH 004 --- 016

2365

30 1441 Flanged (Opt.) 30

110

600
1642

29

30

21/

Inlet
2 Gas male

Outlet
2 Gas male

Inlet
2 Gas male (mod. 007 --- 207)
21/2 Gas male (mod. 008 --- 011)

Outlet
2 Gas male (mod. 007 --- 207)
21/2 Gas male (mod. 008 --- 011)

Total
heat recovery outlet

Partial
heat recovery outlet

2 Gas male

1 Gas male

2 Gas male

1 Gas male

Partial
heat recovery inlet

Total
heat recovery inlet

CRH
004 ---006 ---007 ---204 ---206 ---207

Models

Not available

1 Gas male

Not available

1 Gas male

SRH
004 ---006 ---007 ---204 ---206 ---207

Tab. 11 --- Heat recovery water connection (optional) CRH/SRH 004 --- 016

21/2 Gas male

11/4 Gas male

21/2 Gas male

11/4 Gas male

CRH
008 ---011 ---014 ---016

Outlet
2 Gas male (mod. 007 --- 207)
2 Gas male (mod. 008 --- 011)

21/

Inlet
2 Gas male (mod. 007 --- 207)
2 Gas male (mod. 008 --- 011)

(*) ON 204 --- 206 --- 207 MODELS, TANK VERSION WITH / WITHOUT PUMP IS NOT AVAILABLE

Chilled water
connection

Outlet
2 Gas male

3006
1 (007 --- 207) --- 2 (008 --- 011)

CRH/SRH
007 --- 207 (*) --- 008 --- 011

2006

Inlet
2 Gas male

---

CRH/SRH
004 --- 204 (*) --- 006 --- 206 (*)

mm

Fans number

J = With pump/s (without tank)

j = Standard, with tank, with


tank + pump/s
p p

Tab. 10 --- Chilled water connection CRH/SRH 004 --- 016

4006

Inlet
21/2 Gas male

Outlet
21/2 Gas male

Not available

11/4 Gas male

Not available

11/4 Gas male

SRH
008 ---011 ---014 ---016

Outlet
21/2 Gas male

Inlet
21/2 Gas male

CRH/SRH
014 --- 016

88

1300

Part. H

352

Coil metal filters (Opt.), not possible with ducted flange

Removable panel

60

Unit connecting
pipe

Unit overall frame (A)

Victaulic
coupling

UNIT CONNECTING SYSTEM

N View

Duct Flanged (Opt.), not possible with coil metal filters

PART. G

Left air discharge (move the A with C panel/s)

102

Right air discharge (move the A with B panel/s)

Part. H

Over air discharge (Standard supply)

Air flow

30 (Opt.)

30

98

30

Supply cable inlet


(Prepunchs No 2 67 - No 1 30)

Right lateral
view

30

2240

352

1800

88

352

1800

850

1382 Ext.
Flanged (Opt.)

179

Part. G

Heat recovery and


std. pipe projection

Electric panel and control unit


(behind front removable panel)

210 80

90

60

405

459

459

459

405

832 Ext. 168


459

832 Ext.

832 Ext.

459

168

832 Ext.
459

Part. L
2940 Ext. Flanged (Opt.)

3940 Ext. Flanged (Opt.)

168

832 Ext. 168 832 Ext.

459

832 Ext. 168

Top view

168 832 Ext.

459

168 832 Ext.

4940 Ext. Flanged (Opt.)

405

459

832 Ext. 168

832 Ext. 168 832 Ext.

Front view

832 Ext.

832 Ext. 168

168

168

832 Ext.

Heat recovery

Fig. 10 --- Overall dimensions CRH/SRH 017 --- 032

405

459

459

459

679
1382 Ext.
Flanged (Opt.)

Rear view
(from D)

179

115

115

27
Plane for
canalization fixing all
around the opening

2940 Ext.
3940 Ext.
4940 Ext.
Flanged (Opt.)

Part. L

Left lateral view


(with heat recovery)

1185

1185

Left lateral view


(Std. unit)

1220
765
255
155
765
300
765
255
1382 Ext.
Flanged (Opt.)

27

31

32

Total
heat recovery outlet

Partial
heat recovery outlet

Total
heat recovery inlet

Z
DN 80 --- 3 --- 88.9 mm
(like Part. G)

2 Gas male

DN 80 --- 3 --- 88.9 mm


(like Part. G)

2 Gas male

Partial
heat recovery inlet

CRH
017 --- 020 --- 023 --- 025 --- 028 --- 030 --- 032

Models

Outlet
DN 80 --- 3 --- 88.9 mm

Inlet
DN 80 --- 3 --- 88.9 mm

5750

CRH/SRH
028 --- 030 --- 032

Not available

2 Gas male

Not available

2 Gas male

SRH
017 --- 020 --- 023 --- 025 --- 028 --- 030 --- 032

Outlet
DN 80 --- 3 --- 88.9 mm

Outlet
DN 80 --- 3 --- 88.9 mm

Tab. 13 --- Heat recovery water connection (optional) CRH/SRH 017 --- 032

Chilled water
connection

4
Inlet
DN 80 --- 3 --- 88.9 mm

3
Inlet
DN 80 --- 3 --- 88.9 mm

Fans number
---

4750

3750

mm

CRH/SRH
023 --- 025

CRH/SRH
017 --- 020

Models

Tab. 12 --- Chilled water connection CRH/SRH 017 --- 032

60

30

Part. H

Removable panel

102

Unit overall frame (A)

Unit connecting
pipe

Over air discharge


(standard supply)
Right air discharge
(move the A with B panel/s)
Left air discharge
(move the A with C panel/s)
Duct Flanged (Opt.),
not possible with coil metal filters

Air flow

Supply cable inlet


(Prepunchs
No 2 67 - No 1 30)

N View

Victaulic
coupling

Coil metal filters (Opt.),


not possible with ducted flange

UNIT CONNECTING SYSTEM

PART. G

2240

88

352

1800

Right lateral
view

352

Left lateral view

1185

115

Part. G

Inlet/Outlet pipes
projection

1382 Ext.
Flanged (Opt.)

Part. H

30 (Opt.)

30

98

Plane for
canalization fixing all
around the opening

27

Part. L

1300

2940 Ext.
3940 Ext.
4940 Ext.
Flanged (Opt.)

30

850

1800

Electric panel and control unit


(behind front removable panel)

1382 Ext.
Flanged (Opt.)
179

352

88

60

405

459

405

459

168

459

459

832 Ext.

1000

Fig. 11 --- Overall Dimensions (with tank) CRH/SRH 017 --- 032

90

210 80

27
920
1065
255

2940 Ext. Flanged (Opt.)

Part. L

E
E
E

832 Ext.

459

832 Ext. 168

832 Ext.

168

Top view

168

459

832 Ext.

832 Ext.

168 832 Ext.

832 Ext.

Front view

168

3940 Ext. Flanged (Opt.)


4940 Ext. Flanged (Opt.)

405

459

832 Ext.

832 Ext. 168

832 Ext.

832 Ext.

168

168

832 Ext.

168

405

832 Ext.
459

459

168

832 Ext.

459

168

Rear view
(from D)

459

459

679
1382 Ext.
Flanged (Opt.)
179

33

34

4
Inlet
DN 80 --- 3 --- 88.9 mm
Outlet
DN 80 --- 3 --- 88.9 mm

3
Inlet
DN 80 --- 3 --- 88.9 mm
Outlet
DN 80 --- 3 --- 88.9 mm

---

X
Y

Chilled water
connection

5750

4750

mm

CRH/SRH
023 --- 025

CRH/SRH
017 --- 020

Fans number

Models

Tab. 14 --- Chilled water connection (with tank) CRH/SRH 017 --- 032

Outlet
DN 80 --- 3 --- 88.9 mm

Inlet
DN 80 --- 3 --- 88.9 mm

6750

CRH/SRH
028 --- 030 --- 032

Fig. 12 --- Refrigerant circuit (std.) with partial recovery (opt.)


CRH/SRH 004---006---007

7
9

19

HEAT RECOVERY WATER OUTLET


1 GAS MALE (OPT.)
11

19
10
22

21

12

HEAT RECOVERY WATER INLET


1 GAS MALE (OPT.)

19
2

FG

14

1
19
MC

13

18
CHILLED WATER INLET
2 GAS MALE

16

17

19

15

CHILLED WATER OUTLET


2 GAS MALE

20

Refrigerant components
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14

Description

Item

Compressor
High pressure switch (HP)
Low pressure switch (LP)
Crankcase heater
High pressure manometer (Opt.)
Low pressure manometer (Opt.)
Safety valve
Condenser
Fan(s)
Pressure transducer
Shut--- off valve
Filter dryer
Shut--- off solenoid valve
Sight glass

15
16
17
18
19
20
21
22

35

Description
Thermostatic expansion valve
Evaporator
Antifreeze heater (Opt.)
Control temperature sensor
Charge connection
Antifreeze sensor
Partial recovery heat exchanger (Opt.)
Antifreeze heater (Std. with heat recovery)

Fig. 13 --- Refrigerant circuit (std.) with partial recovery (opt.)


CRH/SRH 204---206---207---008---011---014---016
7

HEAT RECOVERY WATER OUTLET


G --- GAS MALE (OPT.)
19

19

19

19

11

10
22
12

FG

22

21

19

HEAT RECOVERY
WATER INLET
G --- GAS MALE (OPT.)

14

18

19

13

12

21

CHILLED WATER
INLET
H --- GAS MALE

19

MC

16

19

19

15

17
20

CHILLED WATER OUTLET


H --- GAS MALE

CRH/SRH
204

206

207

008

011

014

016

11/4

11/4

11/4

11/4

21/2

21/2

21/2

21/2

Refrigerant components

1
2
3
4
5
6
7
8
9
10
11
12
13
14

19

14

MC

15

Item

11

10

Description

Item

Compressor
High pressure switch (HP)
Low pressure switch (LP)
Crankcase heater
High pressure manometer (Opt.)
Low pressure manometer (Opt.)
Safety valve
Condenser
Fan(s)
Pressure transducer
Shut--- off valve
Filter dryer
Shut--- off solenoid valve
Sight glass

15
16
17
18
19
20
21
22

36

Description
Thermostatic expansion valve
Evaporator
Antifreeze heater (Opt.)
Control temperature sensor
Charge connection
Antifreeze sensor
Partial recovery heat exchanger (Opt.)
Antifreeze heater (Std. with heat recovery)

13

FG

Fig. 14 --- Refrigerant circuit with total recovery (opt.)


CRH 004---006---007
ONLY FOR:
CRH 007

25
9

ONLY FOR:
CRH 004--- 006--- 007
25
8

7
25

19

HEAT RECOVERY WATER OUTLET


2 GAS MALE
19

11

21

22

10

24

HEAT RECOVERY
WATER INLET
2 GAS MALE

12
23

19

14

FG

19

18

MC

13

1
4

16

17

CHILLED WATER INLET


2 GAS MALE

CHILLED WATER OUTLET


2 GAS MALE

19

15

T
20

Refrigerant components
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14

Description

Item

Compressor
High pressure switch (HP)
Low pressure switch (LP)
Crankcase heater
High pressure manometer (Opt.)
Low pressure manometer (Opt.)
Safety valve
Condenser
Fan(s)
Pressure transducer
Shut--- off valve
Filter dryer
Shut--- off solenoid valve
Sight glass

15
16
17
18
19
20
21
22
23
24
25

37

Description
Thermostatic expansion valve
Evaporator
Antifreeze heater (Opt.)
Control temperature sensor
Charge connection
Antifreeze sensor
Total recovery heat exchanger
Three way valve
Non return valve
Antifreeze heater
Liquid receiver

Fig. 15 --- Refrigerant circuit with total recovery (opt.)


CRH 204---206---207---008---011---014---016
ONLY FOR:
CRH 207--- 008--- 011--- 014--- 016

ONLY FOR:
CRH 207--- 008--- 011--- 014--- 016
9

25

25
8

HEAT RECOVERY
WATER OUTLET
G --- GAS MALE

25

19

11

25

19
10

21

22

11

19

21

24

19

10

22

24

12

12
23

19

14

23
HEAT RECOVERY
WATER INLET
G --- GAS MALE

FG

18

19

CHILLED WATER
INLET
H --- GAS MALE

16

19

15

19

15

17
20

CHILLED WATER OUTLET


H --- GAS MALE

CRH
204

206

207

008

011

014

016

21/2

21/2

21/2

21/2

21/2

21/2

21/2

21/2

Refrigerant components

1
2
3
4
5
6
7
8
9
10
11
12
13
14

19

14

MC

Item

FG

19

MC

13

Description

Item

Compressor
High pressure switch (HP)
Low pressure switch (LP)
Crankcase heater
High pressure manometer (Opt.)
Low pressure manometer (Opt.)
Safety valve
Condenser
Fan(s)
Pressure transducer
Shut--- off valve
Filter dryer
Shut--- off solenoid valve
Sight glass

15
16
17
18
19
20
21
22
23
24
25

38

Description
Thermostatic expansion valve
Evaporator
Antifreeze heater (Opt.)
Control temperature sensor
Charge connection
Antifreeze sensor
Total recovery heat exchanger
Three way valve
Non return valve
Antifreeze heater
Liquid receiver

13

Fig. 16 --- Refrigerant circuit (std.) with partial recovery (opt.)


CRH/SRH 017---020---023---025---028---030---032

8
HEAT RECOVERY WATER OUTLET
2 GAS MALE (OPT.)

19

11

19

10

11

10

22

22

19

19
21

12

21

12

5
CHILLED WATER INLET
VICTAULIC COUPLING
DN 80 --- 3 --- 88.9 mm

HEAT RECOVERY WATER INLET


2 GAS MALE (OPT.)

19

14

3
MC

FG

6
19

18

MC

FG

19

16

13

MC

13

MC

4
19

4
15

19

19

15

19

17
20

Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14

19

CHILLED WATER OUTLET


VICTAULIC COUPLING
DN 80 --- 3 --- 88.9 mm

Description

Item

Compressor
High pressure switch (HP)
Low pressure switch (LP)
Crankcase heater
High pressure manometer (Opt.)
Low pressure manometer (Opt.)
Safety valve
Condenser
Fan(s)
Pressure transducer
Shut--- off valve
Filter dryer
Shut--- off solenoid valve
Sight glass

15
16
17
18
19
20
21
22

39

Description
Thermostatic expansion valve
Evaporator
Antifreeze heater (Opt.)
Control temperature sensor
Charge connection
Antifreeze sensor
Partial recovery heat exchanger (Opt.)
Antifreeze heater (Std. with heat recovery)

14

Fig. 17 --- Refrigerant circuit with total recovery (opt.)


CRH 017---020---023---025---028---030---032

NOT PRESENT FOR:


CRH 017--- 020

NOT PRESENT FOR:


CRH 017--- 020

24

24

9
8

24

24

HEAT RECOVERY
WATER INLET
VICTAULIC COUPLING (OPT.)
DN 80 --- 3 --- 88.9 mm

13

13

19
11

19
10

23

11

10

23
21

13

19

13

12

HEAT RECOVERY
WATER OUTLET
VICTAULIC COUPLING (OPT.)
DN 80 --- 3 --- 88.9 mm

19
14

22
CHILLED WATER INLET
VICTAULIC COUPLING
DN 80 --- 3 --- 88.9 mm

19
1

MC

FG

19

18 T

19

14
FG

16

MC

13

MC

1
4

15

15

17
19

19

20

1
2
3
4
5
6
7
8
9
10
11
12
13
14

13

Item

MC

19

19
12

Description

Item

Compressor
High pressure switch (HP)
Low pressure switch (LP)
Crankcase heater
High pressure manometer (Opt.)
Low pressure manometer (Opt.)
Safety valve
Condenser
Fan(s)
Pressure transducer
Shut--- off valve
Filter dryer
Shut--- off solenoid valve
Sight glass

15
16
17
18
19
20
21
22
23
24
25

40

CHILLED WATER OUTLET


VICTAULIC COUPLING
DN 80 --- 3 --- 88.9 mm

Description
Thermostatic expansion valve
Evaporator
Antifreeze heater (Opt.)
Control temperature sensor
Charge connection
Antifreeze sensor
Total recovery heat exchanger
Three way valve
Non return valve
Antifreeze heater
Liquid receiver

19

Fig. 18 --- Hydraulic circuit --- CRH 004---006---007---204---206---207


LIEBERT--- HIROSS UNIT

ONLY WITH TANK VERSION


18

NOT AVAILABLE IN
204--- 206--- 207 MODELS
8

4
ONLY WITH PUMP VERSION
7
4

6
5

5
9

13

CHILLED WATER INLET


2 GAS MALE

14b
F
16

10

ONLY FOR 004--- 006--- 007 MODELS

11

14a

15

12

CHILLED WATER OUTLET


2 GAS MALE

ONLY FOR 204--- 206--- 207 MODELS

T
T

11
12

Hydraulic components
Item
1
2
3
4
5
6
7
8
9
10

Description

Item

Evaporator
Evaporator antifreeze heater (Opt.)
Rubber flexible pipe (only with pumps and/or tank))
Manual air valve
Gate valve
Pump
Safety valve
Expansion tank
Service ball valve
Drain valve

11
12
13
14a
14b
15
16
17
18

41

Description
Control temperature sensor
Antifreeze temperature sensor
Tank antifreeze heater (Opt.)
Flow switch (unit without tank, Opt. without pumps)
Flow switch (unit with tank, Opt. without pumps)
Rubber flexible pipe (only with pumps, without tank)
Filter (Opt.)
Non return valve
Expansion tank + Safety valve (Opt. without tank)

Fig. 19 --- Hydraulic circuit --- CRH 008---011---014---016


LIEBERT--- HIROSS UNIT

ONLY WITH TANK VERSION


18
8
4
ONLY WITH PUMP VERSION
17

17

13

CHILLED WATER INLET


21/2 GAS MALE

14b
F

16

10

T
T

11
12

14a

15

CHILLED WATER OUTLET


21/2 GAS MALE

Hydraulic components
Item
1
2
3
4
5
6
7
8
9
10

Description

Item

Evaporator
Evaporator antifreeze heater (Opt.)
Rubber flexible pipe (only with pumps and/or tank))
Manual air valve
Gate valve
Pump
Safety valve
Expansion tank
Service ball valve
Drain valve

11
12
13
14a
14b
15
16
17
18

42

Description
Control temperature sensor
Antifreeze temperature sensor
Tank antifreeze heater (Opt.)
Flow switch (unit without tank, Opt. without pumps)
Flow switch (unit with tank, Opt. without pumps)
Rubber flexible pipe (only with pumps, without tank)
Filter (Opt.)
Non--- return valve
Expansion tank + Safety valve (Opt. without tank)

Fig. 20 --- Hydraulic circuit --- SRH 004---006---007---204---206---207


LIEBERT--- HIROSS UNIT

ONLY WITH TANK VERSION

21

NOT AVAILABLE IN
204--- 206--- 207 MODELS

24

4
4

ONLY WITH PUMP VERSION


22 22

18

4
T

20

23

5
9

10

10

23

19

CHILLED WATER INLET


2 GAS MALE

14b
13

23

16

23

10

1
3
T
T

11

14a

15

12

ONLY FOR 004--- 006--- 007 MODELS

CHILLED WATER OUTLET


2 GAS MALE

ONLY FOR 204--- 206--- 207 MODELS

T
T

11
12

Hydraulic components
Item
1
2
3
4
5
6
7
8
9
10
11
12
13

Description

Item

Evaporator
Evaporator antifreeze heater (Opt.)
Rubber flexible pipe (only with pumps and/or tank))
Manual air valve
Gate valve
Pump
Safety valve
Expansion tank
Service ball valve
Drain valve
Control temperature sensor
Antifreeze temperature sensor
Tank antifreeze heater (Opt.)

14a
14b
15
16
17
18
19
20
21
22
23
24

43

Description
Flow switch (unit without tank, Opt. without pumps)
Flow switch (unit with tank, Opt. without pumps)
Rubber flexible pipe (only with pumps, without tank)
Filter (Opt.)
Non return valve
Air temperature sensor
3--- way valve
Freecooling control temperature sensor
Fan(s)
Freecooling coil
Rubber flexible pipe
Expansion tank + Safety valve (Opt. without tank)

Fig. 21 --- Hydraulic circuit --- SRH 008---011---014---016


LIEBERT--- HIROSS UNIT

ONLY WITH TANK VERSION

21
4

24

22 22

18

20

17

ONLY WITH PUMP VERSION


7

23

10

10

23

19
17

23

13

CHILLED WATER INLET


21/2 GAS MALE

14b
F

16

23
10

1
3
T
T

11
12

14a

15

CHILLED WATER OUTLET


21/2 GAS MALE

Hydraulic components
Item
1
2
3
4
5
6
7
8
9
10
11
12
13

Description

Item

Evaporator
Evaporator antifreeze heater (Opt.)
Rubber flexible pipe (only with pumps and/or tank))
Manual air valve
Gate valve
Pump
Safety valve
Expansion tank
Service ball valve
Drain valve
Control temperature sensor
Antifreeze temperature sensor
Tank antifreeze heater (Opt.)

14a
14b
15
16
17
18
19
20
21
22
23
24

44

Description
Flow switch (unit without tank, Opt. without pumps)
Flow switch (unit with tank, Opt. without pumps)
Rubber flexible pipe (only with pumps, without tank)
Filter (Opt.)
Non--- return valve
Air temperature sensor
3--- way valve
Freecooling control temperature sensor
Fans
Freecooling coil
Rubber flexible pipe
Expansion tank + Safety valve (Opt. without tank)

1
2
3
4
5
6
7
8
9
10

Item

M2

M1

Evaporator
Evaporator antifreeze heater (Opt.)
Filter (Opt.)
Manual air valve
Butterfly valve
Single pump
Twin pump
Expansion tank + Safety valve (Opt.)
Manometer
Discharge valve

Description

Hydraulic components

ONLY WITH TWIN


PUMP VERSION

12

11

15

16

M1

6
5

LIEBERT--- HIROSS BASE UNIT

T
T

15

ONLY WITH SINGLE


PUMP VERSION

UNIT FRAME (WITHOUT TANK)

10

TANK FRAME

13

45

11
12
13
14
15
16

Item

CHILLED WATER INLET


VICTAULIC CONNECTION
DN 80 --- 3 --- 88.9 mm

10

13

Control temperature sensor


Antifreeze temperature sensor
Tank antifreeze heater (Opt.)
Flow switch (Opt. without pumps)
Service valve with cap
Differential trasducer (only with electronic pump)

OPTION:
WATER TANK NOT ASSEMBLY
WITH UNIT

CHILLED WATER OUTLET


VICTAULIC CONNECTION
DN 80 --- 3 --- 88.9 mm

WATER TANK OUTLET--VICTAULIC CONNECTION


DN 80 --- 3 --- 88.9 mm

Description

ONLY WITH WATER TANK VERSION


ASSEMBLY WITH UNIT

14

UNIT FRAME (WITH ASSEMBLED TANK)

Fig. 22 --- Hydraulic circuit --- CRH 017---020---023---025---028---030---032

WATER TANK INLET--VICTAULIC


CONNECTION
DN 80--- 3 --- 88.9mm

1
2
3
4
5
6
7
8
9
10

Item

20

M2

M1

16

10

T
T

12

11

15

15

18

19

15

p 21

M1

LIEBERT--- HIROSS BASE UNIT

ONLY WITH SINGLE


PUMP VERSION
5

UNIT FRAME (WITH ASSEMBLED TANK)

UNIT FRAME (WITHOUT TANK)

ONLY WITH TWIN


PUMP VERSION

Evaporator
Evaporator antifreeze heater (Opt.)
Filter (Opt.)
Manual air valve
Butterfly valve
Single pump
Twin pump
Expansion tank + Safety valve (Opt.)
Manometer
Discharge valve

Description

Hydraulic components

17

14

10

13

46

11
12
13
14
15
16
17
18
19
20
21

Item

CHILLED WATER OUTLET


VICTAULIC CONNECTION
DN 80 --- 3 --- 88.9 mm

10

13

Control temperature sensor


Antifreeze temperature sensor
Tank antifreeze heater (Opt.)
Flow switch (Opt. without pumps)
Service valve with cap
Freecooling coil
Air temperature sensor
3 way valve
Control freecooling thermostat sensor
Fans
Differential trasducer (only with electronic pump)

Description

OPTION:
WATER TANK NOT ASSEMBLY
WITH UNIT

CHILLED WATER INLET


VICTAULIC CONNECTION
DN 80 --- 3 --- 88.9 mm

WATER TANK OUTLET--VICTAULIC CONNECTION


DN 80 --- 3 --- 88.9 mm

ONLY WITH WATER TANK VERSION


ASSEMBLY WITH UNIT

TANK FRAME

Fig. 23 --- Hydraulic circuit --- SRH 017---020---023---025---028---030---032

WATER TANK INLET--VICTAULIC


CONNECTION
DN 80--- 3 --- 88.9mm

specifications without previous notice.

98/37/CE; 89/336/CEE; 73/23/CEE; 97/23/CE

Printed in Italy by Liebert HIROSS S.p A.

Since the Liebert HIROSS Company has a policy of continuous

product
j

improvement,
it reserves
the
right
to change
design
andm m m j j j ..:

Issued by T.D.Service

Il Fabbricante dichiara che questo prodotto conforme alle direttive Europee:


The Manufacturer hereby declares that this product conforms to the European Union directives:
Der Hersteller erklrt hiermit, dass dieses Produkt den Anforderungen der Europischen Richtlinien gerecht wird:
Le Fabricant dclare que ce produit est conforme aux directives Europennes:
El Fabricante declara que este producto es conforme a las directivas Europeas:
O Fabricante declara que este produto est em conformidade com as directivas Europeias:
Tillverkare frskrar hrmed att denna produkt verensstmmer med Europeiska Uniones direktiv:
De Fabrikant verklaart dat dit produkt conform de Europese richtlijnen is:
Vaimistaja vakuuttaa tten, ett tm tuote tytt seuraavien EU-direktiivien vaatimukset:
Produsent erklrer herved at dette produktet er i samsvar med EU-direktiver:
Fabrikant erklrer herved, at dette produkt opfylder kravene i EU direktiverne:

Since the Liebert HIROSS Company has a policy of continuous


product improvement, it reserves the right to change design and
specifications without previous notice.

Liebert HIROSS
is a division of
EMERSON

Printed in Italy by Liebert HIROSS S.p A.

Tel. +39 049 9719111


Telefax +39 049 5841257
Internet : www.liebert-hiross.com

Issued by T.D.Service

Zona Industriale Tognana


Via Leonardo da Vinci, 16/18
35028 Piove di Sacco (PD)
ITALY

You might also like