INVERTER
INVERTER
FR-A8NP
IB(NA)-0600528ENG-B(1410)MEE
Printed in Japan
INSTRUCTION MANUAL
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Plug-in option
FR-A8NP
INSTRUCTION MANUAL
PROFIBUS-DP
communication function
PRE-OPERATION INSTRUCTIONS
INSTALLATION
WIRING
INVERTER SETTING
FUNCTIONS
TROUBLESHOOTING
Safety instructions
Do not attempt to install, operate, maintain or inspect the product until you have read through this Instruction Manual and appended
documents carefully and can use the equipment correctly. Do not use this product until you have a full knowledge of the equipment, safety
information and instructions. In this Instruction Manual, the safety instruction levels are classified into "Warning" and "Caution".
Incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Warning
Caution
The
Caution
Incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause only material
damage.
level may even lead to a serious consequence according to conditions. Both instruction levels must be followed
Warning
While the inverter power is ON, do not open the front cover or the wiring cover. Do not run the inverter with the front cover or the wiring cover removed. Otherwise
you may access the exposed high voltage terminals or the charging part of the circuitry and get an electric shock.
Do not remove the inverter front cover even if the power supply is disconnected. The only exception for this would be when performing wiring and periodic
inspection. You may accidentally touch the charged inverter circuits and get an electric shock.
Before wiring or inspection, LED indication of the inverter unit operation panel must be switched OFF. Any person who is involved in wiring or inspection shall wait
for at least 10 minutes after the power supply has been switched OFF and check that there is no residual voltage using a tester or the like. For some time after the
power-OFF, a high voltage remains in the smoothing capacitor, and it is dangerous.
Any person who is involved in wiring or inspection of this equipment shall be fully competent to do the work.
The plug-in option must be installed before wiring. Otherwise you may get an electric shock or be injured.
Do not touch the plug-in option or handle the cables with wet hands. Otherwise you may get an electric shock.
Do not subject the cables to scratches, excessive stress, heavy loads or pinching. Otherwise you may get an electric shock.
Injury Prevention
Caution
The voltage applied to each terminal must be the ones specified in the Instruction Manual. Otherwise a burst, damage, etc. may occur.
The cables must be connected to the correct terminals. Otherwise a burst, damage, etc. may occur.
The polarity (+ and -) must be correct. Otherwise a burst or damage may occur.
While power is ON or for some time after power OFF, do not touch the inverter as it will be extremely hot. Touching these devices may cause a burn.
Additional Instructions
The following instructions must be also followed. If the product is handled incorrectly, it may cause unexpected fault, an injury, or an electric
shock.
Caution
Transportation and mounting
Do not install or operate the plug-in option if it is damaged or has parts missing.
Do not stand or rest heavy objects on the product.
The mounting orientation must be correct.
Foreign conductive objects must be prevented from entering the inverter. That includes screws and metal fragments or other flammable substance such as oil.
If halogen-based materials (fluorine, chlorine, bromine, iodine, etc.) infiltrate into a Mitsubishi product, the product will be damaged. Halogen-based materials are
often included in fumigant, which is used to sterilize or disinfest wooden packages. When packaging, prevent residual fumigant components from being infiltrated
into Mitsubishi products, or use an alternative sterilization or disinfection method (heat disinfection, etc.) for packaging. Sterilization of disinfection of wooden
package should also be performed before packaging the product.
Trial run
Before starting operation, each parameter must be confirmed and adjusted. A failure to do so may cause some machines to make unexpected motions.
Warning
Usage
Do not modify the equipment.
Do not perform parts removal which is not instructed in this manual. Doing so may lead to fault or damage of the product.
Caution
Usage
When parameter clear or all parameter clear is performed, the required parameters must be set again before starting operations. Because all parameters return to
their initial values.
Static electricity in your body must be discharged before you touch the product.
Disposal
General instruction
Many of the diagrams and drawings in this Instruction Manual show the inverter without a cover or partially open for explanation. Never operate the inverter in this
manner. The cover must be reinstalled and the instructions in the Instruction Manual must be followed when operating the inverter.
CONTENTS
1 PRE-OPERATION INSTRUCTIONS
1.1
1.2
1.3
1.3.1
1.3.2
2 INSTALLATION
2.1
2.2
2.3
4.3.1
4.3.2
4.4
5 FUNCTIONS
5.1
20
4.2.1
4.3
16
Terminals........................................................................................................................................................................16
Wiring..............................................................................................................................................................................17
4 INVERTER SETTING
4.1
4.2
10
3 WIRING
3.1
3.2
32
5.2
Real-time monitor................................................................................................................................................................ 55
Parameter clear .................................................................................................................................................................. 56
Operation mode read/write ................................................................................................................................................. 56
Set frequency read.............................................................................................................................................................. 56
Terminal input read ............................................................................................................................................................. 57
Inverter reset ....................................................................................................................................................................... 57
REF command assignment (available only when the extended format is selected) (only for the FR-A800 series)............ 57
STS monitor function (available only when the extended format is selected) (only for the FR-A800 series)...................... 59
Node address read ............................................................................................................................................................. 59
Faults history read .............................................................................................................................................................. 60
PNU list read ....................................................................................................................................................................... 64
Standard parameters.....................................................................................................................................................65
PROFIBUS-DP communication function setting ........................................................................................................68
7.8.1
7.8.2
7.8.3
7.8.4
ID definitions ..................................................................................................................................................................42
Buffer memory configuration .......................................................................................................................................43
Buffer memory details...................................................................................................................................................45
Outline of PNU ...............................................................................................................................................................54
PROFIBUS PNU..............................................................................................................................................................55
7.6.1
7.6.2
7.6.3
7.6.4
7.6.5
7.6.6
7.6.7
7.6.8
7.6.9
7.6.10
7.6.11
7.7
7.8
40
7.1.1
7.2
7.3
7.4
7.5
7.6
34
PROFIBUS communication command source setting (Pr.1109) (only for the FR-A800 series) ......................................... 68
Torque command / torque limit via PROFIBUS communication (Pr.804) (only for the FR-A800 series) ............................ 69
Torque bias selection (Pr.840) (only for the FR-A800 series)............................................................................................. 70
Frequency command with sign (Pr.541) ............................................................................................................................. 71
8.6.1
8.6.2
8.7
72
Standard parameters.....................................................................................................................................................85
8.7.1
8.7.2
8.7.3
9 TROUBLESHOOTING
88
MEMO
1
1.1
PRE-OPERATION INSTRUCTIONS
Unpacking and product confirmation
Take the plug-in option out of the package, check the product name, and confirm that the product is as you ordered and intact.
This product is a plug-in option for the FR-A800/F800 series inverter.
Product confirmation
Spacer
..................2 (Refer to page 12.)
X1
45
23 6
CD
AB E
789
F01
X16
45
23 6
789
F01
1 2
CD
AB E
ON
Earth plate
..................1 (Refer to page 12.)
NOTE
PROFIBUS is a registered trademark of PROFIBUS User Organization.
PRE-OPERATION INSTRUCTIONS
1.2
Component names
Front view
Pin assignment
(b)
Rear view
(e)
(f)
(a)
(a)
(a)
V+
D+
DD+
VFG
(c)
X1 (SW2)
45
23 6
CD
AB E
789
F01
(d)
X16 (SW3)
45
23 6
D+
DVDCNTR
FG
F01
Symbol
1 2
789
CD
AB E
ON
(a)
Name
(a)
Description
(a)
Refer to page
Mounting hole
12
Terminal block
16
LED status
c
Description
OFF
Red (ON)
Green (ON)
15
Do not change from initially-set status. (The switches 1 and 2 are both OFF.)
Connector
12
PRE-OPERATION INSTRUCTIONS
1.3
1.3.1
Specifications
Inverter option specifications
Type
1.3.2
Communication specifications
Wiring length 1200 m or less
Communication speed
187.5 Kbps
PRE-OPERATION INSTRUCTIONS
2
2.1
INSTALLATION
Pre-installation instructions
Check that the inverter's input power and the control circuit power are both OFF.
Caution
10
With input power ON, do not install or remove the plug-in option. Otherwise, the inverter and plug-in option may be damaged.
To avoid damage due to static electricity, static electricity in your body must be discharged before you touch the product.
INSTALLATION
2.2
Installation procedure
2
Cut off with a nipper, etc.
(3) Fit the communication option LED display cover to the front side of the
front cover. Align the LED display cover with the LED position on the
circuit board of the option. Push the LED display cover until it is fixed with
the hooks.
Caution
Take care not to hurt your hand and such with portions left by cutting hooks of the rear of the front cover.
INSTALLATION
11
12
INSTALLATION
Inverter side
option connector
Spacer
Spacer
Earth plate
Connector 3
Mounting screw
Spacer
Connector 2
Connector 1
Spacer
Mounting screw
Mounting screw
Earth plate
INSTALLATION
13
NOTE
When mounting/removing the plug-in option, hold the sides of the option. Do not press on the parts on the option
circuit board. Stress applied to the parts by pressing, etc. may cause a failure.
Caution must be applied to mounting screws falling off when removing and mounting the plug-in option.
When using this plug-in option, insert it to the inverter option connector 1. If it is inserted to the option connector 2 or 3,
the protective function (E.2 or E.3) is activated and the inverter will not operate.
Even if the option is inserted to the option connector 1, when the inverter cannot recognize that the option is mounted
due to improper installation, etc., the protective function (E.1) is activated.
Mounted position
Fault indication
Option connector 1
Option connector 2
Option connector 3
When removing the plug-in option, remove the two screws on the left and right, then pull it straight out. Pressure
applied to the connector and to the option board may break the option.
Always attach the earth plate because a malfunction due to noises may occur without it.
14
INSTALLATION
2.3
Set the node address between "H00" and "H7D" using the node address switches on the FR-A8NP board. (Refer to page 8.)
The setting is applied at the next power-ON.
Set the arrow () of the corresponding switches to a number or an alphabet to set a desired address.
Setting example
X1 (SW2)
789
45
23 6
45
23 6
CD
AB E
789
F01
X1 (SW2)
CD
AB E
F01
X16 (SW3)
789
789
45
23 6
CD
AB E
CD
AB E
X16 (SW3)
45
23 6
Node address 1:
Set the " " of X16 (SW3) to "0" and the " " of X1
(SW2) to "1".
F01
F01
NOTE
Set the inverter node address before switching ON the inverter and do not change the setting while power is ON.
Otherwise you may get an electric shock.
Set the node address switch to the switch number (alphabet) position correctly. If the switch is set between numbers,
normal data communication cannot be established.
45
23 6
789
F01
45
23 6
789
CD
AB E
Bad
example
CD
AB E
Good
example
F01
When the node address switches are set to any of H7E to HFF, the node address is recognized as H7D.
The node addresses, H00, H01, H02, H7C, and H7D, may not be available for some master modules.
You cannot set the same node address to other devices on the network. (Doing so disables proper communication.)
INSTALLATION
15
3
3.1
WIRING
Terminals
Terminal no.
A 1 2 3 4 5 6
V+ D+ D- D+ V- FG
D+ D- V- D- CNTR FG
1 2 3 4 5 6
16
Terminal name
Definition
1-A
V+ (VP)
1-B
D+ (RXD/TXD-P)
2-A
D+ (RXD/TXD-P)
2-B
D+ (RXD/TXD-N)
3-A
D+ (RXD/TXD-N)
3-B
V- (DGND)
GND of D+/D-
4-A
D+ (RXD/TXD-P)
4-B
D+ (RXD/TXD-N)
5-A
V- (DGND)
GND of D+/D-
5-B
CNTR
6-A
FG
6-B
FG
When connecting a terminating resistor, connect the terminating resistor to these terminals. (Refer to page 19)
It may not be necessary depending on the master used.
WIRING
3.2
Wiring
Use the network connection cable which supports 12.0 Mbps communication.
(1) Strip off the sheath of the PROFIBUS communication dedicated cable and wind wires and shield
cables to use.
Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit
may occur with neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
Cable stripping length
5 mm
Use a blade terminal as necessary.
When using the blade terminal, use care so that the twisted wires do not come
ve
ee
Sl
Unstranded
wires
ire
W
m
.5m
o0
0t
Damaged
Crumpled tip
NOTE
Blade terminal commercially available (as of February 2012. The product may be changed without notice.)
Terminal
screw size
M2
Manufacturer
Phoenix Contact
Co.,Ltd.
Crimping tool
name
CRIMPFOX 6
WIRING
17
(2) Loosen the terminal screw and insert the cable into the terminal.
Tighten each cable with fixing screws to the recommended tightening torque.
<Cable connection example>
D+ D-
D+ DV-
V-
To master
Screw size
M2
Tightening torque
0.22 Nm to 0.25 Nm
Cable size
0.3 mm2 to 0.75 mm2
Screwdriver
Small
flat-blade screwdriver
(Tip thickness: 0.4 mm /tip width: 2.5 mm)
NOTE
Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or malfunction
due to damage to the screw or unit.
18
WIRING
Connection example
Master station
Inverter
Inverter
PLC etc.
Terminating
resistor
Terminating
resistor
Power
supply
Motor Power
supply
Motor
2% 1/4W
2% 1/4W
2% 1/4W
To other inverter
(node)
R1
V+
D+
R2
D-
D+
VDR3
Caution
After wiring, wire offcuts must not be left in the inverter. They may cause an error, failure or malfunction.
WIRING
19
4
4.1
INVERTER SETTING
Parameter list
The following parameters are used for the communication option (FR-A8NP).
Set the values according to need.
Pr.
Pr.
group
Name
Setting range
Minimum setting
increments
Initial
value
Refer to
page
79
D000
0 to 4, 6, 7
22
338
D010
0, 1
339
D011
0, 1, 2
340
D001
0, 1, 2, 10, 12
22
342
N001
0, 1
349
N010
0, 1
31
500
N011
0 to 999.8 s
0.1 s
0s
25
501
N012
26
502
N013
0 to 3
26
541
N100
0, 1
71
550
D012
0, 1, 9999
9999
779
N014
0.01 Hz
9999
26
804
D400
0, 1, 3 to 6
69
840
G230
0 to 3, 24, 25,
9999
9999
70
20
INVERTER SETTING
Pr.
group
Pr.
1109
G320
1110
N190
Name
Setting range
Minimum setting
increments
Initial
value
Refer to
page
68
0, 1
40
Parameters which can be displayed when the plug-in option (FR-A8NP) is mounted.
Parameters which can be displayed when the plug-in option (FR-A8AP) is mounted.
The setting is applied after an inverter reset or power-ON.
For the parameter details, refer to the Instruction Manual (Detailed) of the inverter.
The setting is available only for the FR-A800 series.
INVERTER SETTING
21
4.2
4.2.1
Operation mode selection at power ON and at restoration from instantaneous power failure
The operation mode at power ON and at restoration from instantaneous power failure can be selected.
Set a value other than "0" in Pr.340 Communication startup mode selection to select the network operation mode.
After started in network operation mode, parameter write from the network is enabled.
NOTE
22
Change of the Pr.340 setting is valid when powering on or resetting the inverter.
Pr.340 can be changed with the operation panel independently of the operation mode.
When setting a value other than 0 in Pr.340, make sure that the initial settings of the inverter are correct.
Refer to the Instruction Manual (Detailed) of the inverter for details of Pr.79, Pr.340.
INVERTER SETTING
Pr.340
setting
0
(initial
value)
Pr.79
setting
0 (initial
value)
PU operation mode
3, 4
1, 2
PU operation mode
3, 4
INVERTER SETTING
23
Pr.340
setting
10, 12
Pr.79
setting
0
PU operation mode
3, 4
6
7
24
Operation mode can not be directly changed between the PU operation mode and Network operation mode.
The Pr.340 settings "2, 12" are mainly used for communication operation using the inverter RS-485 terminal.
When a value other than "9999" (selection of automatic restart after instantaneous power failure) is set in Pr.57 Restart coasting time,
the inverter will resume the same operation state which was in before after power has been restored from an instantaneous power failure.
When Pr.340 = "1, 10", a start command turns off if power failure has occurred and then restored during a start command is on.
Switching between the PU and NET operation modes is available with the key on the operation panel or the X65 signal.
Pr.79 = "6" and Pr.128 to Pr.134 (PID control) are not activated simultaneously. The switchover mode and the PID control are disabled,
and the inverter performs the same operation as when "0" is set in Pr.79.
Refer to page 56, 83 for a switching method from the network.
INVERTER SETTING
4.3
4.3.1
You can select operations at communication error occurrences by setting Pr.500 to Pr.502, Pr.779 under network operation.
Waiting time for the communication line error output after a communication error
Waiting time for the communication error output after a communication line error occurrence can be set.
Pr.
500
Name
Setting range
Normal
0 to 999.8 s
Error
Minimum setting
increments
0.1 s
Normal
0s
Error
Recognition
Communication error
(E.OP1)
Pr.500
setting time
Alarm signal(LF)
(Pr.502 = 3)
Initial value
Pr.500
setting time
ON
When a communication line error occurs and lasts longer than the time set in Pr.500, it is recognized as a communication error.
If the communication returns to normal within the time, it is not recognized as a communication error, and the operation
continues.
INVERTER SETTING
25
Name
Communication error occurrence count display
Minimum setting
increments
Setting range
Normal
Error
Normal
Incremented by 1
Initial value
0
Error
Incremented by 1
At the point of communication line error occurrence, Pr.501 Communication error occurrence count display is incremented
by 1.
NOTE
Communication error count is temporarily stored in the RAM memory. The error count is stored in EEPROM only once
per hour. If power reset or converter reset is performed, Pr.501 setting will be the one that is last stored to EEPROM
depending on the reset timing.
Name
502
779
26
INVERTER SETTING
Setting range
Description
0 (Initial Value), 1, 2, 3
Refer to page 27
0 to 590 Hz
About setting
Operation at an error occurrence
Error definition
Pr.502 setting
Operation
Indication
Fault output
0
Communication line
1
2
Continued
Normal indication
Not provided
3
Communication option
itself
0, 3
Coast to stop
E. 1 lit
Provided
1, 2
Decelerated to stop
When the communication returns to normal within the time period set in Pr.500, the communication option error (E.OP1) does not occur.
Pr.502 setting
0
1
Communication line
2
3
Communication option
itself
0, 3
1, 2
Operation
Indication
Coast to stop
E.OP1 lit
Decelerated to stop
Continues operation
with the Pr.779 setting.
Normal indication
Kept stopped
Fault output
Provided
Provided after stop
Not provided
Kept provided
When an error occurs, the motor is decelerated or coasts to stop, and outputs the fault, independently of the Pr.500 setting.
INVERTER SETTING
27
Pr.502 setting
0
Communication line
Communication option
itself
Operation
Kept stopped
Restart
Normal operation
0, 3
1, 2
Kept stopped
Indication
Fault output
Kept provided
Normal indication
Not provided
E. 1 kept lit
Kept provided
NOTE
The protective function [E.OP1 (fault data: HA1)] is activated at error occurrences on the communication line. The
protective function [E.1 (fault data: HF1)] is activated at error occurrences in the communication circuit inside the
option.
Fault output indicates the fault (ALM) signal and fault bit output.
When the fault output setting is active, fault records are stored in the faults history. (A fault record is written to the
faults history at a fault output.)
When the fault output setting is not active, fault record is overwritten to the faults history temporarily but not stored.
After the error is removed, the fault indication is reset, changing the display back to normal, and the last fault is
displayed in the faults history.
When the Pr.502 setting is "1" or "2", the deceleration time is the ordinary deceleration time setting (e.g. Pr.8, Pr.44,
Pr.45).
The acceleration time at a restart is the ordinary acceleration time setting (e.g. Pr.7, Pr.44).
When the Pr.502 setting is "2", the operation/speed command at a restart is the one given before the error occurrence.
When a communication line error occurs at the Pr.502 setting of "2", removing the error during deceleration causes
acceleration to restart at that point. (Acceleration is not restarted if the error is that of the option unit itself.)
When Pr.502 = "3", in order to continue the operation in the case of a communication line error, provide a safety stop
countermeasure other than via communication. One counter measure is to input a signal to the terminal RES.
28
INVERTER SETTING
4.3.2
Network operation
External operation
Inverter trip
PU operation
Inverter operation
Inverter trip
Data communication
Continued
Continued
Continued
Inverter operation
Inverter trip
Continued
Continued
Data communication
Communication
option
Operation mode
Status
Inverter trip
Stop
Stop
Stop
Communication
option connection
error
Inverter operation
Inverter trip
Inverter trip
Inverter trip
Data
communication
Continued
Continued
Continued
Error of
communication
option itself
Inverter operation
Inverter trip
Continued
Continued
Data
communication
Stop
Stop
Stop
Error definition
Measures
E.OP1
Check the LED status of the option unit and remove the cause of the alarm. (Refer to page 8
for LED indication status)
Check the other nodes on the network.
Inspect the master.
Option fault
When faults other than the above are displayed, refer to the Instruction Manual (Detailed) of the inverter and remove the cause of the
error.
INVERTER SETTING
29
4.4
Inverter reset
Network
operation
Allowed
Pr.349 = 0
PU operation
Disallowed
Disallowed
Allowed
Allowed
Disallowed
Disallowed
Allowed
Allowed
Allowed
Pr.349 = 1
Allowed
External
operation
Allowed
Allowed
Allowed
Inverter reset
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
NOTE
When a communication line error has occurred, reset cannot be made from the network.
The inverter is set to the External operation mode if it has been reset in Network operation mode in the initial status.
To resume the network operation, the inverter must be switched to the Network operation mode again.
Set a value other than "0" in Pr.340 to start in the Network operation mode. (Refer to page 22.)
The inverter can not be controlled for about 1 s after release of a reset command.
30
INVERTER SETTING
Initial
value
Name
Communication reset selection
Setting
range
Function
INVERTER SETTING
31
5
5.1
FUNCTIONS
Output from the inverter to the network
Main items to be output from the inverter (FR-A8NP) to the network and their descriptions are explained below.
Refer to page
Item
Description
PPO type
support
specification
PPO type
non-support
specification
Inverter monitor
48, 55
80
Parameter read
45, 65
75, 85
Inverter status
48
77
48, 56
56
83
57
83
59
60
84
64
NOTE
Refer to the Instruction Manual (Detailed) of the inverter for functions controllable from the network in each operation
mode.
32
FUNCTIONS
5.2
Main items which can be commanded from the network to the inverter and their descriptions are explained below.
Refer to page
Item
Description
PPO type
support
specifications
PPO type
non-support
specifications
Frequency setting
48
83
56
83
Run command
47
82
Inverter reset
57
81
Parameter write
45, 65
75, 85
Parameter clear
56
81
49
82
NOTE
Refer to the Instruction Manual (Detailed) of the inverter for functions controllable from the network in each operation
mode.
FUNCTIONS
33
6
6.1
A GSD file is required to connect the inverter (FR-A8NP) to the Profibus network and use Profibus configuration software. The
GSD file contains information on the communication setting of the inverter (FR-A8NP).
GSD file can be downloaded from the web site.
Mitsubishi Electric FA Site
www.MitsubishiElectric.co.jp/fa
The download is free.
Contact your sales representative for details.
When editing this file, use a text editor.
For installation instructions, refer to the instruction manual of the PROFIBUS-DP Configuration Software.
Although this product complies with PPO type specification, it includes specifications which do not support PPO type
specification (FR-A5NP intercompatibility protocol). This manual states the section supporting PPO type specification as PPO
type support specification and the section not supporting PPO type as PPO type non-support specification.
NOTE
You cannot use the device data which does not include PPO supporting specification (data for the FR-A5NP).
34
Value
#Profibus_DP
GSD_Revision
Description
File header
Vendor_Name
"Mitsubishi Electric"
Manufacturer name
Model_Name
"FR-A8NP"
Product name
Revision
Product version
Ident_Number
H0EA8
Protocol_Ident
PROFIBUS-DP is 0 fixed.
Station_Type
DP slave is 0 fixed.
FMS_Supp
Hardware_Release
Hardware version
Software_Release
Software version
9.6_supp
19.2_supp
93.75_supp
187.5_supp
500_supp
1.5M_supp
3M_supp
6M_supp
12M_supp
35
Parameter
Value
Description
MaxTsdr_9.6
15
MaxTsdr_19.2
15
MaxTsdr_93.75
15
MaxTsdr_187.5
15
MaxTsdr_500
15
MaxTsdr_1.5M
25
MaxTsdr_3M
50
MaxTsdr_6M
100
MaxTsdr_12M
200
Redundancy
Repeater_Ctrl_Sig
24V_Pins
Freeze_Mode_supp
Sync_Mode_supp
Auto_Baud_supp
Set_Slave_Add_supp
Min_Slave_Intervall
Modular_Station
Max_Module
Max_Input_Len
28
Max_output_Len
28
36
Parameter
Value
Description
Max_Data_Len
56
Fail_Safe
Max_Diag_Data_Len
Slave_Family
PrmText
Text(0)
Text(1)
"Byte swapping"
1 "Byte swapping"
EndPrmText
ExtUserPrmData
Bit(0) 0 0-1
Prm_Text_Ref
Max_User_Prm_Data_Len
Ext_User_Prm_Data_Const(0)
H01
Ext_User_Prm_Data_Const(1)
H00
Ext_User_Prm_Data_Ref(1)
Module
EndExtUserPrmData
EndModule
Module
EndModule
Module
37
Parameter
Value
Description
EndModule
Module
EndModule
Module
EndModule
Module
EndModule
38
6.2
By changing the slave user parameter value, you can use the byte swapping function (byte inversion function).
Setting "1" at Address H1 (Bit 0) enable the byte swapping function.
Since "" is an unused bit, set "0".
Address
H0
Functions
For manufacturer setting (Always set "1".)
Bit 7
H1
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0:Byte swapping function disabled
1:Byte swapping function enabled
Example of when the byte swapping function is disabled (address H1 (Bit 0) = "0")
Command request
Master
WORD
H01 H02
WORD
H03 H04
Command response
slave
Master
WORD
H05 H06
WORD
H07 H08
slave
Example of when the byte swapping function is enabled (address H1 (Bit 0) = "1")
Command request
Master
WORD
H02 H01
WORD
H04 H03
Command response
WORD
H06 H05
slave
Master
WORD
H08 H07
slave
39
7
7.1
The option unit operates as a "slave of the PROFIBUS DP master" or a "controller equivalent to PROFIBUS DP master class 1
on an RS-485 network".
The PROFIBUS profile (data buffer) can be selected from among six different types, "PPO type1" to "PPO type5", and "A5NP".
(For the module type "A5NP" profile, refer to Chapter 8.)
Module type is changed with the slave module setting. For details, refer to the instruction manual of the Network Master
Configuration Software. The configuration of PPO type is as follows.
7.1.1
For the FR-A800 series, set the Profibus format in the Pr.1110 PROFIBUS format selection. (For the FR-F800 series, only the
standard format can be used.)
Set Pr.1110 = "1" to extend the PPO type 2 and PPO type 5 PROFIBUS profile formats. Then, commands and monitor items
can be assigned to Word 8 to Word 10 in PPO type 2, and Word 8 to Word 14 in PPO type 5. (The format is not extended for
PPO type 1, PPO type 3, and PPO type 4.)
Pr.
Name
1110
40
Initial value
0
Setting range
Function
Standard format
Extended format
PKE
IND
PWE
PPO type2
(Standard format)
PKE
IND
PWE
PPO type3
STW/ HSW/
ZSW HIW
PPO type4
PPO type5
(Standard format)
PKE
IND
PWE
PKW
STW/ HSW/ ECW/ Reserved Reserved Reserved Reserved Reserved Reserved Reserved
1
1
1
1
1
1
1
ZSW HIW ESW
Input Data : 14 Words
Output Data : 14 Words
1 0 fixed
: 1 Word
PZD
PKE
IND
PWE
PPO type5
(Extended format)
PKE
IND
PWE
STW/ HSW/ ECW/ REF1/ REF2/ REF3/ REF4/ REF5/ REF6/ REF7/
ZSW HIW ESW STS1 STS2 STS3 STS4 STS5 STS6 STS7
Input Data : 14 Words
Output Data : 14 Words
PKW
7
: 1 Word
PZD
41
7.2
ID definitions
ID
PKW
(Refer to page 45)
Definition
PKE
IND
PWE
STW/ZSW
HSW/HIW
PZD
(Refer to page 47)
42
ECW/ESW
REF1 to REF7/
STS1 to STS7
Reserved
STS1 to STS7: Arbitrarily set monitor item (Command response in the extended format)
7.3
Master
PKE
AK
bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sub-Index
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
PKE
PNU(parameter number)
Task
IND
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
AK
Response
bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
IND
Ext-Index
Sub-Index
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
PWE 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
PWE 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
PWE (read value)
PWE (setting)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0
1 1 1
RAM/EEPROM
MRS
RT
STR
STF
PZD enable
bit
1 1 1
Not supported
Control enable
Not supported
Fault reset
Not supported
Not supported (Standard format)
REF1 enable (Extended format)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
HSW
HSW(set frequency)
bit
Ext-Index
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 bit
STW
bit
PNU(parameter number)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
ZSW
1 0
0 1 1
bit
1 1 1
Busy
NET mode
REW
FWD
RUN
FU
Not supported
Fault
Not supported
Power-on inhibit
Alarm
Not supported
Control request
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
HIW
HIW(output frequency)
43
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
Command count
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
0 0
CS
AU
JOG
REF7 enable
REF6 enable
REF5 enable
REF4 enable
REF3 enable
RH
RM
RL
JOG
AU
CS
REF2 enable
Alarm 7
Alarm 6
Alarm 5
Alarm 4
Alarm 3
44
SU
OL
IPF
RUN
Alarm 1
Alarm 2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
STS1 to STS7 Echo back value of REF1 to 7 Echo back value of REF1 to 7
(AK=15)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
Command value
Command count
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
SU
OL
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
Command count
REF1 to REF7
(AK 15)
0 0 0 0
RUN
IPF
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
REF1 to REF7
(AK=15)
Command count
RH
RM
RL
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
STS1 to STS7
(AK 15)
Monitor value
7.4
The following indicates the buffer memory details of the Profibus profiles.
PKW
Name
Bit
Definition
PNU
0 to 10
PNU number
SPM
11
Value
0
PKE
AK
12 to 15
Operation
No task
15
Not supported
[Command response]
Value
Operation
15
Not supported
45
Name
Bit
Definition
0 to 7
Ext-Index number
When Bit 0 (extended parameter access) = "1" and AK = "1 or 2", the PNU value (parameter number) plus 1000
can be read or written.
8 to 15
Sub-Index number
At command request, set this number when AK ="6, 7".
IND
Value
0 to 15
PWE
16 to 31
46
Error definition
Invalid PNU
Without array
11
18
Other error
Valid only for the FR-A800 series when Pr.1110 PROFIBUS format selection = "1" (extended format). (Refer to page 40)
Indicates outside AK number range, write data error, external operation error, without option error, instruction code error, with STF/STR
error, with operation mode specification error, parameter calibration error (Pr.900 or later), reset disabled error (with reset input
specification of Pr.75), etc.
PZD
Name
STW
Bit
Definition
0 to 2
Control enable
4 to 6
Fault reset
(Reset)
(Standard format)
REF1 enable
(Extended format)
0: REF1 disabled, 1: REF1 enabled (The REF1 setting is applied to the inverter.)
PZD enable
10
STF signal
11
STR signal
12
Terminal RT function
13
MRS signal
14
RAM/EEPROM
15
0: Set frequency (HSW) is written to RAM (Power-on reset returns the changed
set frequency to the setting before it was written to RAM.).
1: Set frequency (HSW) is written to EEPROM.
47
Name
Bit
Definition
0 to 2
Fault
0: Inverter normal
1: Inverter alarm occurrence
4, 5
Power-on inhibit
0 is returned
Alarm
Control request
1 is returned
FU signal
10
0: OFF
1: ON (output frequency being detected) (Refer to Pr.42 and Pr.43 in the
Instruction Manual (Detailed) of the inverter.)
RUN signal
11
0: OFF
1: ON (inverter running)
FWD
12
REW
13
NET mode
14
BUSY
15
0: Ready status
1: Busy status
HSW
0 to 15
HIW
0 to 15
ZSW
48
Name
ECW
(Standard format)
Bit
Definition
Terminal RH function
Terminal RM function
Terminal RL function
Terminal AU function
Terminal CS function
6, 7
Command count
8 to 15
49
Name
ECW
(Extended format)
ESW
(Standard format)
50
Bit
Definition
Terminal RH function
Terminal RM function
Terminal RL function
Terminal AU function
Terminal CS function
REF2 enable
0: REF2 disabled, 1: REF2 enabled (The REF2 setting is applied to the inverter.)
REF3 enable
0: REF3 disabled, 1: REF3 enabled (The REF3 setting is applied to the inverter.)
REF4 enable
0: REF4 disabled, 1: REF4 enabled (The REF4 setting is applied to the inverter.)
REF5 enable
0: REF5 disabled, 1: REF5 enabled (The REF5 setting is applied to the inverter.)
REF6 enable
10
0: REF6 disabled, 1: REF6 enabled (The REF6 setting is applied to the inverter.)
REF7 enable
11
0: REF7 disabled, 1: REF7 enabled (The REF7 setting is applied to the inverter.)
Command count
12 to 15
SU signal
OL signal
IPF signal
Inverter running
4 to 7
Command count
8 to 15
Name
ESW
(Extended format)
Bit
Definition
SU signal
OL signal
IPF signal
Inverter running
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
10
Alarm 7
11
Command count
12 to 15
51
Name
Bit
Definition
0 to 7
Function number of the monitor item assigned to STS1 to STS7 (Refer to page
59)
Command assignment
to REF1 to REF7
8 to 15
Function number of the command assigned to REF1 to REF7 (Refer to page 57)
0 to 7
Echo back value of Bits 0 to 7 (STS monitor item assignment) of REF1 to REF7
Command assignment
to REF1 to REF7
8 to 15
REF1 to REF7
(when AK "15")
Command value of
REF1 to REF7
0 to 15
STS1 to STS7
(when AK "15")
Monitor value of
STS1 to STS7
0 to 15
Monitor value of the item assigned to Bits 0 to 7 (STS monitor item assignment) of
REF1 to REF7 when AK = "15"
REF1 to REF7
(when AK = "15")
STS1 to STS7
(when AK = "15")
52
Valid only for the FR-A800 series when Pr.1110 PROFIBUS format selection = "1" (extended format). (Refer to page 40)
PZD enable and command count request can be executed.
If it takes time to perform slave side processing, slave side busy status is announced since reply to the master will be delayed. During
busy status, other response data are unfixed values. When the slave side is busy, request from the master is invalid. Therefore, the same
request must be sent again. The response data of the FR-A8NP during Busy status is as follows.
ID
PKW
PZD
When a value other than 9999 is set in Pr.430 Pulse monitor selection under position control (Pr.800="3, 4") for the FR-A800 series,
pulse monitor is selected. (Refer to the Instruction Manual (Detailed) of the inverter for pulse monitor.)
Signal names are initial values. Using Pr.180 to Pr.186, you can change output signal functions. Refer to the Instruction Manual
(Detailed) of the inverter for details of Pr.180 to Pr.186.
For the FR-F800 series, no function is assigned in the initial setting.
These signals are set in the initial setting. Using Pr.190, output signal assigned to the device number can be changed.
For the details of Pr.190, refer to the Instruction Manual (Detailed) of the inverter.
NOTE
Only when the contents of the command request (request for changing the inverter setting: PKW, HSW, STW/ECW)
from the master changed, the inverter processes the request. If the contents of the command request are identical
with those of the last request, the inverter does not process the request. (The received request is cleared.)
For instance, while the master keeps sending the "network operation mode enable" command, changing the mode to
the PU operation mode with switchover function does not allow the "network operation mode enable" command to be
executed due to the same contents as that sent last time. Therefore, the operation mode remains the PU operation
mode without changing to the Network operation mode. In this case, send another command as "PU operation mode
enable" from the master once, then send the "network operation mode enable" command again.
53
7.5
Outline of PNU
You can use the PNU to make inverter settings from the network.
The data used with the network is denoted PNU (P) to differentiate it from the parameter (Pr.) of the inverter.
This chapter explains the module type "PPO type 1" to "PPO type 5".
NOTE
Parameter definitions differ according to the module type selected. When using "A5NP", refer to page 79.
Array
With
Example
P1902.1
Sub-Index Number
Unsigned 16 (Us16)
Without
P1240
NOTE
When the data type is "with array", include the sub-index number in the PNU.
54
7.6
PROFIBUS PNU
7.6.1
Real-time monitor
Item
Increments
P1.1
Output frequency
0.01 Hz
P1.2
Output current
0.01 A/0.1 A
P1.3
Output voltage
0.1 V
.
.
.
.
.
.
.
.
.
55
7.6.2
Parameter clear
Item
Data definition
Data type
P2.2
Parameter clear
H965A
AUs16
P2.3
H99AA
AUs16
AUs16
P2.5
Parameter clear
H5A96
P2.6
HAA99
AUs16
P2.8
H0000
AUs16
7.6.3
The communication parameters are not cleared. For details of the communication parameters, refer to the Instruction Manual (Detailed)
of the inverter.
Item
Operation mode read/write
7.6.4
Data definition
External operation mode: H10
PU operation mode: H11 (For writing, when "6" is set in Pr.79)
Network operation mode: H14
Data type
Us16
The frequency set to the inverter can be read from the master.
PNU
Item
Data definition
Data type
P4.1
AUs16
P4.2
AUs16
56
7.6.5
Item
Data definition
Data type
P5.1
AUs16
P5.2
AUs16
P5.3
AUs16
7.6.6
Inverter reset
Item
Inverter reset
Data definition
The inverter is reset after the data was written from the master.
Data type
Us16
7.6.7
When AK = "15", commands can be assigned to Bits 8 to 15 of REF1 to REF7. Command value for the assigned command can
be given in REF1 to REF7 when AK "15".
PNU
Item
Data type
P10.1
Aus16
P10.2
Aus16
P10.3
Aus16
P10.4
Aus16
P10.5
Aus16
P10.6
Aus16
P10.7
Aus16
57
For details of the commands (settings) which can be assigned to REF1 to REF7, refer to the following table.
Setting
value
0
Description
No function
Resolution
of the setting
Unit
1/0.01
Torque command
(under torque control)
1
Torque limit
(under speed control)
Refer
to page
69
68
Torque bias
0.01
70
68
0.01
68
0.001
68
Droop gain
0.1
68
58
7.6.8
STS monitor function (available only when the extended format is selected)
(only for the FR-A800 series)
When AK = "15", monitor numbers can be assigned to Bits 0 to 7 of REF1 to REF7. Assigned items can be monitored in STS1
to STS7 when AK "15".
The monitored item and the monitor number are the same as those of the RS-485 communication dedicated monitor of the
inverter.
(Refer to the Instruction Manual (Detailed) of the inverter.)
PNU
Item
Data type
P11.1
Aus16
P11.2
Aus16
P11.3
Aus16
P11.4
Aus16
P11.5
Aus16
P11.6
Aus16
P11.7
Aus16
7.6.9
Item
Node address read
Data definition
The node address settings of the inverter are read.
Data type
Us16
59
7.6.10
Fault records of past eight faults occurred in the inverter can be read.
(For the data codes or details of fault records, refer to the Instruction Manual (Detailed) of the inverter.)
PNU
Item
P947.1 to P947.8
P947.9 to P947.16
P947.17 to P947.24
P947.25 to P947.32
P947.33 to P947.40
P947.41 to P947.48
P947.49 to P947.56
P947.57 to P947.64
60
Data definition
P947.1
P947.2 to P947.8
All 0
P947.9
P947.10 to P947.16
All 0
P947.17
P947.18 to P947.24
All 0
P947.25
P947.26 to P947.32
All 0
P947.33
P947.34 to P947.40
All 0
P947.41
P947.42 to P947.48
All 0
P947.49
P947.50 to P947.56
All 0
P947.57
P947.58 to P947.64
All 0
Data type
AUs16
AUs16
AUs16
AUs16
AUs16
AUs16
AUs16
AUs16
Energization time (fault monitor) for past eight alarms at the inverter alarm occurrence can be read.
PNU
Item
Data definition
P948.1 to P948.8
P948.1
Energization time
P948.2 to P948.8
All 0
P948.9 to P948.16
P948.9
Energization time
P948.10 to P948.16
All 0
P948.17 to P948.24
P948.17
Energization time
P948.18 to P948.24
All 0
P948.25 to P948.32
P948.25
Energization time
P948.26 to P948.32
All 0
P948.33 to P948.40
P948.33
Energization time
P948.34 to P948.40
All 0
P948.41 to P948.48
P948.41
Energization time
P948.42 to P948.48
All 0
P948.49 to P948.56
P948.49
Energization time
P948.50 to P948.56
All 0
P948.57 to P948.64
P948.57
Energization time
P948.58 to P948.64
All 0
Data type
AUs16
AUs16
AUs16
AUs16
AUs16
AUs16
AUs16
AUs16
61
Output frequency, output current and output voltage for past eight alarms at the inverter alarm occurrence can be read.
PNU
P949.1 to P949.8
P949.9 to P949.16
P949.17 to P949.24
P949.25 to P949.32
P949.33 to P949.40
62
Item
Data definition
P949.1
Output frequency
P949.2
Output current
P949.3
Output voltage
P949.4 to P949.8
All 0
P949.9
Output frequency
P949.10
Output current
P949.11
Output voltage
P949.12 to P949.16
All 0
P949.17
Output frequency
P949.18
Output current
P949.19
Output voltage
P949.20 to P949.24
All 0
P949.25
Output frequency
P949.26
Output current
P949.27
Output voltage
P949.28 to P949.32
All 0
P949.33
Output frequency
P949.34
Output current
P949.35
Output voltage
P949.36 to P949.40
All 0
Data type
AUs16
AUs16
AUs16
AUs16
AUs16
PNU
P949.41 to P949.48
P949.49 to P949.56
P949.57 to P949.64
Item
Data definition
P949.41
Output frequency
P949.42
Output current
P949.43
Output voltage
P949.44 to P949.48
All 0
P949.49
Output frequency
P949.50
Output current
P949.51
Output voltage
P949.52 to P949.56
All 0
P949.57
Output frequency
P949.58
Output current
P949.59
Output voltage
P949.60 to P949.64
All 0
Data type
AUs16
AUs16
AUs16
63
7.6.11
Item
P980.1 to 116
P981.1 to 116
P982.1 to 116
P983.1 to 116
P984.1 to 116
P985.1 to 116
P986.1 to 116
P987.1 to 116
P988.1 to 116
P989.1 to 116
Data definition
P980.3
1001
P980.25
1002
64
1000
P980.24
P980.23
P980.2
P980.1
Remarks
0
When 0 is stored, read is terminated.
Data type
AUs16
7.7
Standard parameters
You can use the PNU to make parameter settings from the network.
The table below lists PNU numbers corresponding to parameter numbers.
Standard parameter examples are introduced below. Refer to the examples and make parameter settings.
The usable parameters depend on the inverter. Refer to the Instruction Manual (Detailed) of the inverter for details of the
parameters.
Representation of the PNU for standard parameters (Example: Pr.902)
P1902.1
Sub-Index Number
1000+Parameter Number
Example of parameter list
PNU
Name
Bit 0 of the ext-index number = "0"
Data
type
Us16
P1002
Us16
P1003
Us16
P1004
Us16
P1005
Us16
P1006
Us16
Us16
Pr.1001
Pr.1000
P1001
P1000
NOTE
Write to Pr.77 and Pr.79 is not allowed from the network with FR-A8NP. (Read is allowed.)
To read or write parameter of Pr.1000 or later, set Bit 0 of the ext-index number (extended parameter access) = "1".
(Refer to page 46)
65
The following parameters require the sub-index number for the PNU.
Pr.
PNU
Name
Data
Type
C0 (900)
P1900.1
AUs16
C1 (901)
P1901.1
AM terminal calibration
AUs16
C2 (902)
P1902.1
AUs16
C3 (902)
P1902.2
AUs16
125 (903)
P1903.1
AUs16
C4 (903)
P1903.2
AUs16
C5 (904)
P1904.1
AUs16
C6 (904)
P1904.2
AUs16
126 (905)
P1905.1
AUs16
C7 (905)
P1905.2
AUs16
C12 (917)
P1917.1
AUs16
C13 (917)
P1917.2
AUs16
C14 (918)
P1918.1
AUs16
C15 (918)
P1918.2
AUs16
C16 (919)
P1919.1
AUs16
C17 (919)
P1919.2
AUs16
C18 (920)
P1920.1
AUs16
C19 (920)
P1920.2
AUs16
C8 (930)
P1930.1
AUs16
66
Pr.
C9 (930)
PNU
P1930.2
Name
Current output bias current
Data
Type
AUs16
C10 (931)
P1931.1
AUs16
C11 (931)
P1931.2
AUs16
C38 (932)
P1932.1
AUs16
C39 (932)
P1932.2
AUs16
C40 (933)
P1933.1
AUs16
C41 (933)
P1933.2
AUs16
C42 (934)
P1934.1
AUs16
C43 (934)
P1934.2
AUs16
C44 (935)
P1935.1
AUs16
C45 (935)
P1935.2
AUs16
67
7.8
7.8.1
Use Pr.1109 PROFIBUS communication command source selection to set the input source for the magnetic flux
command, speed control P gain, speed control integral time, and droop gain in the buffer memory REF1 to REF7 in the
extended format of the PROFIBUS profiles, PPO type 2 and PPO type 5.
For the details of the setting of Pr.1109, refer to the following table.
Selectable function
Magnetic flux command input
source selection
68
Pr.1109 setting
Description
Input the magnetic flux command from external analog terminals (terminals 1 and
4).
[][][]1
Settings in Pr.820 Speed control P gain 1 and Pr.830 Speed control P gain 2
are valid.
[][]1[]
[][]2[]
Settings in Pr.821 Speed control integral time 1 and Pr.831 Speed control
integral time 2 are valid.
[]1[][]
1[][][]
7.8.2
Torque command / torque limit via PROFIBUS communication (Pr.804) (only for
the FR-A800 series)
Setting Pr.804 Torque command source selection = "3 or 5" enables torque command / torque limit via PROFIBUS
communication under Real sensorless vector control, torque control under vector control, and speed control.
(When Pr.804 "3 or 5", writing a torque command/limit value via PROFIBUS communication causes turning ON of Alarm 1 to
Alarm 7 corresponding to REF1 to REF7, resulting in generation of a command execution error.)
Pr.
Name
Initial Setting
value Range
Torque command
(used under torque control)
3
Torque
804 command source 0
selection
Torque limit
(used under speed control)
Input via PROFIBUS
communication is not available.
Input via PROFIBUS
communication is available.
(Regardless of the priority of the
torque limit value input)
Input via PROFIBUS
communication is not available.
69
7.8.3
Under speed control under vector control, setting Pr.840 Torque bias selection = "24 or 25" enables torque bias setting via
PROFIBUS communication.
Pr.
840
70
Name
Initial
value
9999
Setting
range
Description
Set the torque bias amount using contact signals (X42, X43) in Pr.841 to
Pr.843.
Set the torque bias amount using terminal 1 in any of C16 to C19.
(When the squirrel cage rises during forward motor rotation.)
Set the torque bias amount using terminal 1 in any of C16 to C19.
(When the squirrel cage rises during reverse motor rotation.)
The torque bias amount using terminal 1 can be set automatically in C16 to
C19 and Pr.846 according to the load.
24
25
9999
7.8.4
By adding a sign to the frequency command value or the speed limit value, the start command (forward/reverse rotation) can
be inverted to start operation.
Select whether or not to use a sign for the frequency command value / speed limit value.
Pr.
Name
541
Initial value
Pr.541
setting
value
Not used
Used
Setting range
0, 1
Sign
Setting range
0
1
Not used
Used
0 to 59000
-32768 to 32767 (complement of 2)
0 to 590.00 Hz
-327.68 to 327.67 Hz
Not used
0 to 65535
Used
+
+
-
Forward rotation
Reverse rotation
Reverse rotation
Forward rotation
NOTE
When Pr.541 = "1" (with sign)
- The set frequency cannot be written in EEPROM.
- When power is turned ON (inverter reset), the initial setting status of the sign bit is "positive" and the set frequency
is "0 Hz". (The motor does not operate at the frequency set before turning OFF the power (inverter reset).)
Setting Pr.811 Set resolution switchover = "1 or 11" changes the unit from 1 r/min to 0.1 r/min. (The Pr.811 is only
available for the FR-A800 series.)
71
8
8.1
The option unit operates as a "slave of the PROFIBUS DP master" or a "controller equivalent to PROFIBUS DP master class 1
on an RS-485 network".
The PROFIBUS profile (data buffer) can be selected from among six different types, "PPO type 1" to "PPO type 5", and
"A5NP".
(For the module type "PPO type 1" to "PPO type 5" profiles, refer to Chapter 7.)
Module type is changed with the slave module setting. For details, refer to the instruction manual of the Network Master
Configuration Software.
NOTE
The "A5NP" profile is compatible with the FR-A5NP profile.
Use "A5NP" profile when replacing the FR-A5NP with FR-A8NP, etc.
Module
type
A5NP
PKE
IND
PWE
PKW
HIW
ZSW
PZD
1 Word
72
8.2
ID definitions
ID
PKW
(Refer to page 75)
Definition
PKE
IND
Index number
PWE
PZD
(Refer to page 77)
ZSW
HIW
8
PPO TYPE NON-SUPPORT SPECIFICATION
73
8.3
AK
bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
PKE
Response
Task
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
IND
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
IND
PP
Parameter index
Page index
IND
IND
PP
Parameter index
Page index
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
PWE 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
PWE 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit
PWE (read value)
PWE (setting)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bit
ZSW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
ABC
FU
IPF
bit
HIW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
74
bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bit
bit
AK
RUN
FWD
REV
SU
OL
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
HIW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
bit
8.4
The following indicates the buffer memory details of the PROFIBUS profiles.
PKW
Name
Bit
PNU
0 to 10
PNU number (Together, the PNU and the IND define which data word is being accessed.)
Definition
SPM
11
Value
PKE
AK
12 to 15
Operation
No task
Others
Not supported
[Command response]
Value
Operation
Command execution error (error number is stored into PWE) (Refer to page 76)
Others
Not used
8
PPO TYPE NON-SUPPORT SPECIFICATION
75
Name
PP
Bit
0 to 7
8 to 15
Parameter Index :
Specifies the area from which Parameter Number (PNU) is being accessed.
(For details, refer to page 80.)
IND = 0: real-time monitor area
IND = 1: system environment variable(sev) area (3 blocks)
IND = 2: normal parameter area
IND = 3: Pr.900 to calibration parameter (frequency) area
IND = 4: Pr.900 to calibration parameter (%) area
IND
IND
Definition
Page Index :
If IND = 1 (system environment variables (sev) area), the PP values specify different blocks of sev's:
PP = 0 : sev_I, block I
PP = 1 : sev_II, block II (alarm history)
PP = 2 : sev_III, block III
(For details, refer to page 81.)
If IND is other than 01, set PP to 0.
PNU
PWE
0 to 15
16 to 31
76
Error definition
H0
Without error
H1
H2
H3
Invalid PNU
H6
H41
Mode error
H42
H43
PZD
Name
Bit
RUN signal
0 : OFF
1 : ON (inverter running)
FWD signal
0 : OFF
1 : ON (forward rotation operation being
performed)
REV signal
0 : OFF
1 : ON (reverse rotation operation being
performed)
SU signal
0 : OFF
1 : ON (up to frequency)
OL signal
0 : OFF
1 : ON (overload alarm)
IPF signal
0 : OFF
1 : ON (an instantaneous power failure or
undervoltage occurs)
FU signal
0 : OFF
1 : ON (output frequency being detected)
ALM signal
0 : Inverter normal
1 : Inverter alarm occurrence
Command
count
8 to 14
Command count
The command count is an optional feature maintained by the PROFIBUS master and can range from H00
to H7F.
The option unit copies the command count from the command it receives to the same byte offset in the
response it sends. The master may use this to synchronize commands and responses.
15
0 to 15
ZSW
HIW
Definition
8
PPO TYPE NON-SUPPORT SPECIFICATION
77
NOTE
Only when the contents of the command request (request for changing the inverter setting: PKW) from the master
changed, the inverter processes the request. If the contents of the command request are identical with those of the
last request, the inverter does not process the request. (The received request is cleared.)
For instance, while the master keeps sending the "network operation mode enable" command, changing the mode to
the PU operation mode with switchover function does not allow the "network operation mode enable" command to be
executed due to the same contents as that sent last time. Therefore, the operation mode remains the PU operation
mode without changing to the Network operation mode.
In this case, send another command as "PU operation mode enable" from the master once, then send the "network
operation mode enable" command again.
78
8.5
Outline of PNU
You can use the PNU to make inverter settings from the network.
The data used with the network is denoted PNU (P) to differentiate it from the parameter (Pr.) of the inverter.
This chapter explains the module type "A5NP".
NOTE
Parameter definitions differ according to the module type selected. When using "PPO type 1" to "PPO type 5", refer to
page 54.
8
PPO TYPE NON-SUPPORT SPECIFICATION
79
8.6
8.6.1
PNU
H0000 H0
Item
Output frequency
Increments
0.01 Hz
H0000 H1
Output current
0.01 A/0.1 A
H0000 H2
Output voltage
0.1 V
.
.
.
.
.
.
.
.
.
.
.
.
NOTE
The PNU number of each monitor item corresponds to the number of the inverter's RS-485 communication dedicated
monitor that is one less than the PNU number in hexadecimal.
For the details of the monitor items, refer to the monitor display section in the Instruction Manual (Detailed) of the
inverter.
80
8.6.2
System environment variable (sev) area (IND = H01PP (IND = H01, PP = H00, H01))
Parameter clear
Inverter reset and parameter clear can be performed from the master.
IND
H0100
PNU
H1
Item
Inverter reset
Data definition
H0000
H0100
H2
Parameter clear
H965A
H0100
H3
H99AA
H0100
H5
Parameter clear
H5A96
H0100
H6
HAA99
The communication parameters are not cleared. For details of the communication parameters, refer to the Instruction Manual (Detailed)
of the inverter.
8
PPO TYPE NON-SUPPORT SPECIFICATION
81
PNU
Item
Inverter status
For details, refer to ZSW on page 77.
Run command
Bit
0
H0100
HA
82
Name
Definition
Not used (0 is set)
Terminal STF
Terminal STR
Terminal RH
Terminal RM
Terminal RL
Terminal JOG
Terminal RT
Terminal AU
Terminal CS
10
Terminal MRS
11 to 15
Signal names are initial values. Using Pr.180 to Pr.187, you can change output signal functions. Refer to the Instruction Manual
(Detailed) of the inverter for details of Pr.180 to Pr.187.
For the FR-F800 series, no function is assigned in the initial setting.
PNU
HB
Item
Data definition
External operation mode : H10
PU operation mode : H11 (When Pr.79 = "6")
Network operation mode : H14
Operation mode
PNU
Item
Data definition
H0100
HD
H0100
HE
IND
PNU
Item
Minimum
setting
increments
H0100
HF
0.1%
H0100
H10
0.1%
H0100
H11
0.1%
8
PPO TYPE NON-SUPPORT SPECIFICATION
83
PNU
Item
H0101
H0
H0101
H1
H0101
H2
H0101
H3
H0101
H4
H0101
H5
H0101
H6
H0101
H7
84
Writing a value of H0000 to this parameter clear all fault history. All other parameters at this index are read only.
8.7
8.7.1
Standard parameters
Normal parameter area (IND = H0200 (IND = H02, PP = H00))
You can use the PNU to make parameter settings from the network.
The table below lists PNU numbers corresponding to parameter numbers.
Standard parameter examples are introduced below. Refer to the examples and make parameter settings.
Refer to the Instruction Manual (Detailed) of the inverter for details of the parameters.
Example of parameter list
Pr.
Name
Torque boost
H1
Maximum frequency
H2
Minimum frequency
H3
Base frequency
H4
H5
H6
H0
H0200
PNU
IND
NOTE
Write to Pr.77 and Pr.79 is not allowed from the network with FR-A8NP. (Read is allowed.)
8
PPO TYPE NON-SUPPORT SPECIFICATION
85
8.7.2
PNU
Pr.
Name
H0300
H0
C0(900)
H0300
H1
C1(901)
AM terminal calibration
H0300
H2
C2(902)
H0300
H3
125(903)
H0300
H4
C5(904)
H0300
H5
126(905)
H0300
H11
C12(917)
H0300
H12
C14(918)
H0300
H13
C16(919)
H0300
H14
C18(920)
H0300
H1E
C8(930)
H0300
H1F
C10(931)
H0300
H20
C38(932)
H0300
H21
C40(933)
H0300
H22
C42(934)
H0300
H23
C44(935)
86
8.7.3
PNU
Pr.
Name
H0400
H2
C3(902)
H0400
H3
C4(903)
H0400
H4
C6(904)
H0400
H5
C7(905)
H0400
H11
C13(917)
H0400
H12
C15(918)
H0400
H13
C16(919)
H0400
H14
C19(920)
H0400
H1E
C9(930)
H0400
H1F
C11(931)
H0400
H20
C39(932)
H0400
H21
C41(933)
H0400
H22
C43(934)
H0400
H23
C45(935)
8
PPO TYPE NON-SUPPORT SPECIFICATION
87
TROUBLESHOOTING
When a fault occurs where the inverter trips itself and the option unit, check the inverter's operation panel, the LED on the
option unit, and the following checkpoints to identify the cause, then take appropriate countermeasures. If the fault does not
correspond to any of the following faults or if you have any other problem, please contact your sales representative.
Operation
panel display
on the inverter
LED on
FR-A8NP
Possible cause
The option
unit is not
operating.
0.00
OFF
The network
is unstable.
88
TROUBLESHOOTING
Checkpoint / troubleshooting
Operation
panel display
on the inverter
LED on
FR-A8NP
OFF
0.00
Red (ON)
E.OP1
Red (ON)
Possible cause
The network
is unstable.
Checkpoint / troubleshooting
TROUBLESHOOTING
89
REVISIONS
*The manual number is given on the bottom left of the back cover.
Print Date
*Manual Number
Revision
Feb. 2014
IB(NA)-0600528ENG-A
First edition
Oct. 2014
IB(NA)-0600528ENG-B
Addition
Compatibility with the FR-F800 series
90
IB(NA)-0600528ENG-B
INVERTER
INVERTER
INVERTER
FR-A8NP
IB(NA)-0600528ENG-B(1410)MEE
Printed in Japan
INSTRUCTION MANUAL
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Plug-in option
FR-A8NP
INSTRUCTION MANUAL
PROFIBUS-DP
communication function
PRE-OPERATION INSTRUCTIONS
INSTALLATION
WIRING
INVERTER SETTING
FUNCTIONS
TROUBLESHOOTING