BLDG A - DSN Cooling Load

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 28

Design Cooling Load Summary

By gc

Kuwait Scientific Center - Dolphin Area


Ras Salmiya
System - 1st Flr - Endoscopy
Type - Variable Volume Reheat (30% Min Flow Default)
Coil Location - System
Coil Peak Calculation Time: August, hour 15
Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Sensible
Btu/h

Latent
Btu/h

COOLING COIL SELECTION

Total
Btu/h

Percent
of Total

Coil Selection Parameters

Solar Gain
Glass Transmission

5,407
7,766

5,407
7,766

0.8%
1.1%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

110.0 / 90.0
184.03

F
gr/lb

Wall Transmission
Roof Transmission

2,253
0

2,253
0

0.3%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

56.8 / 56.0
65.81

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
2,596

0
0.00
2,596

0.0%
0.0%
0.4%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

293.77
769.55
58.62

MBh
MBh
F

Net Ceiling Load


Lighting

0
9,368

0
9,368

0.0%
1.3%

Total Cooling Airflow


Resulting Room Relative Humidity

2.3%
1.6%
0.0%
7.7%

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Exhaust Heat
Supply Fan Load
Return Fan Load
Net Duct Heat Pickup

8,847
10,979
0
47,216

6,981
0
0
6,981

15,828
10,979
0
54,197

207,374
-3,373

425,549
0

632,923
-3,373

5,298.66
53.89

cfm
%

General Engineering Checks

90.5%
-0.5%

Total Cooling Load


Area / Load

64.1
61.96

ton
ft/ton

Total Floor Area


Cooling Airflow

3,974
1.33

ft
cfm/ft

82.62

cfm/ton

11,032
0

11,032
0

1.6%
0.0%

0.0%

Airflow / Load

Wall Load to Plenum

1,747

1,747

0.2%

Percent Outdoor Air

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design

0
0
2,342
0
0
0
798
0

0
0
2,342
0
0
0
798
0

0.0%
0.0%
0.3%
0.0%
0.0%
0.0%
0.1%
0.0%

Cooling Load Methodology

0.0%

0.0%

Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

267,137

0
432,530

699,667

100.0

RTS (Heat Balance)

###

System - 1st Flr - Minor OTs


Type - Variable Volume Reheat (30% Min Flow Default)
Coil Location - System
Coil Peak Calculation Time: August, hour 15
Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Sensible
Btu/h

Latent
Btu/h

COOLING COIL SELECTION

Total
Btu/h

Percent
of Total

Coil Selection Parameters

Solar Gain
Glass Transmission

7,053
8,425

7,053
8,425

0.8%
1.0%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

110.0 / 90.0
184.03

F
gr/lb

Wall Transmission
Roof Transmission

2,134
0

2,134
0

0.2%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

56.8 / 54.9
60.93

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
3,144

0
0.00
3,144

0.0%
0.0%
0.4%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

380.21
958.62
58.68

MBh
MBh
F

Net Ceiling Load


Lighting

0
12,877

0
12,877

0.0%
1.5%

Total Cooling Airflow


Resulting Room Relative Humidity

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>

13,748
30,996
0
78,376

10,897
0
0
10,897

24,645
30,996
0
89,272

2.8%
3.6%
0.0%
10.2%

252,403
-4,081

514,927
0

767,330
-4,081

Ventilation Load
Exhaust Heat

88.0%
-0.5%

6,449.20
54.40

cfm
%

General Engineering Checks


Total Cooling Load
Area / Load

79.9
56.92

ton
ft/ton

Supply Fan Load


Return Fan Load

13,427
0

13,427
0

1.5%
0.0%

Total Floor Area


Cooling Airflow

4,547
1.42

ft
cfm/ft

Net Duct Heat Pickup


Wall Load to Plenum

0
1,677

0
1,677

0.0%
0.2%

Airflow / Load
Percent Outdoor Air

80.73
100.0

cfm/ton
%

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design

0
0
3,219
0
0
0
687
0

0
0
3,219
0
0
0
687
0

0.0%
0.0%
0.4%
0.0%
0.0%
0.0%
0.1%
0.0%

Cooling Load Methodology

0.0%

0.0%

Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

345,708

0
525,824

871,532

RTS (Heat Balance)

###

System - 1st Flr - Package AHU


Type - Single Zone
Coil Location - System
Coil Peak Calculation Time: August, hour 15
Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Total
Btu/h

Percent
of Total

2,797
3,520

2,797
3,520

4.7%
5.9%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

81.6 / 69.7
90.01

F
gr/lb

507
0

507
0

0.8%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

57.9 / 56.0
63.96

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
1,075

0
0.00
1,075

0.0%
0.0%
1.8%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

36.52
65.93
58.44

MBh
MBh
F

Net Ceiling Load


Lighting

0
3,660

0
3,660

0.0%
6.1%

Total Cooling Airflow


Resulting Room Relative Humidity

15,125
229
0
26,913

25.2%
0.4%
0.0%
44.8%

Solar Gain
Glass Transmission
Wall Transmission
Roof Transmission

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>

Sensible
Btu/h

8,403
229
0
20,191

Latent
Btu/h

COOLING COIL SELECTION

6,722
0
0
6,722

Coil Selection Parameters

General Engineering Checks

1,461.14
54.41

cfm
%

Ventilation Load
Exhaust Heat

9,812
-196

20,013
0

29,826
-196

49.7%
-0.3%

Total Cooling Load


Area / Load

Supply Fan Load


Return Fan Load

866
0

866
0

1.4%
0.0%

Total Floor Area


Cooling Airflow

Net Duct Heat Pickup


Wall Load to Plenum

0
543

0
543

0.0%
0.9%

Airflow / Load
Percent Outdoor Air

0
0
915
0
0
0
1,175
0

0
0
915
0
0
0
1,175
0

0.0%
0.0%
1.5%
0.0%
0.0%
0.0%
2.0%
0.0%

Cooling Load Methodology

0.0%

0.0%

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design
Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

33,306

0
26,736

60,042

5.5
262.63

ton
ft/ton

1,443
1.01

ft
cfm/ft

265.95
17.2

cfm/ton
%

RTS (Heat Balance)

###

System - 2nd Floor - Left Wing


Type - Variable Volume Reheat (30% Min Flow Default)
Coil Location - System
Coil Peak Calculation Time: August, hour 15
Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Sensible
Btu/h

Latent
Btu/h

COOLING COIL SELECTION

Total
Btu/h

Percent
of Total

Coil Selection Parameters

Solar Gain
Glass Transmission

7,316
8,327

7,316
8,327

4.0%
4.5%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

81.3 / 69.5
89.26

F
gr/lb

Wall Transmission
Roof Transmission

2,050
0

2,050
0

1.1%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

59.4 / 57.7
68.26

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
2,813

0
0.00
2,813

0.0%
0.0%
1.5%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

119.04
202.49
61.25

MBh
MBh
F

Net Ceiling Load


Lighting

0
9,941

0
9,941

0.0%
5.4%

Total Cooling Airflow


Resulting Room Relative Humidity

People

9,953

17,915

9.7%

7,962

5,119.40
54.31

cfm
%

Misc. Equipment Loads


Cooling Infiltration
Sub-Total ==>

20,251
0
60,651

0
0
7,962

20,251
0
68,613

Ventilation Load
Exhaust Heat

33,262
-562

67,928
0

101,190
-562

55.0%
-0.3%

Total Cooling Load


Area / Load

Supply Fan Load


Return Fan Load

10,658
0

10,658
0

5.8%
0.0%

Total Floor Area


Cooling Airflow

Net Duct Heat Pickup


Wall Load to Plenum

0
1,643

0
1,643

0.0%
0.9%

Airflow / Load
Percent Outdoor Air

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design

0
0
2,485
0
0
0
71
0

0
0
2,485
0
0
0
71
0

0.0%
0.0%
1.3%
0.0%
0.0%
0.0%
0.0%
0.0%

Cooling Load Methodology

0.0%

0.0%

Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

108,209

0
75,890

184,099

11.0%
0.0%
37.3%

General Engineering Checks


16.9
232.55

ton
ft/ton

3,924
1.30

ft
cfm/ft

303.39
16.6

cfm/ton
%

RTS (Heat Balance)

###

System - 2nd Floor - Right Wing


Type - Variable Volume Reheat (30% Min Flow Default)
Coil Location - System
Coil Peak Calculation Time: August, hour 15
Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Sensible
Btu/h

Latent
Btu/h

COOLING COIL SELECTION

Total
Btu/h

Percent
of Total

Coil Selection Parameters

Solar Gain
Glass Transmission

6,369
8,795

6,369
8,795

3.7%
5.1%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

80.9 / 69.1
87.73

F
gr/lb

Wall Transmission
Roof Transmission

2,433
0

2,433
0

1.4%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

59.6 / 57.9
68.79

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
2,578

0
0.00
2,578

0.0%
0.0%
1.5%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

113.76
191.03
61.47

MBh
MBh
F

0.0%

Total Cooling Airflow

Net Ceiling Load

5,113.50

cfm

Net Ceiling Load


Lighting

0
10,019

0
10,019

0.0%
5.8%

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>

8,478
19,209
369
58,249

Ventilation Load
Exhaust Heat

30,536
-545

Supply Fan Load


Return Fan Load

7,173
0
745
7,918

15,651
19,209
1,114
66,168

9.0%
11.1%
0.6%
38.1%

62,364
0

92,899
-545

53.5%
-0.3%

Total Cooling Load


Area / Load

10,646
0

10,646
0

6.1%
0.0%

Total Floor Area


Cooling Airflow

Net Duct Heat Pickup


Wall Load to Plenum

0
1,895

0
1,895

0.0%
1.1%

Airflow / Load
Percent Outdoor Air

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design

0
0
2,505
0
0
0
108
0

0
0
2,505
0
0
0
108
0

0.0%
0.0%
1.4%
0.0%
0.0%
0.0%
0.1%
0.0%

Cooling Load Methodology

0.0%

0.0%

Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

103,394

0
70,282

173,676

Total Cooling Airflow


Resulting Room Relative Humidity

5,113.50
54.30

cfm
%

General Engineering Checks


15.9
248.74

ton
ft/ton

3,960
1.29

ft
cfm/ft

321.22
15.3

cfm/ton
%

RTS (Heat Balance)

###

System - 2nd Flr - Package AHU


Type - Single Zone
Coil Location - System
Coil Peak Calculation Time: August, hour 15
Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Total
Btu/h

Percent
of Total

992
1,411

992
1,411

1.9%
2.7%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

82.0 / 69.9
90.56

F
gr/lb

Wall Transmission
Roof Transmission

517
0

517
0

1.0%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

57.0 / 55.0
61.45

F
gr/lb

Floor Transmission

0.0%

Coil Sensible Load

32.26

MBh

Solar Gain
Glass Transmission

Sensible
Btu/h

Latent
Btu/h

COOLING COIL SELECTION


Coil Selection Parameters

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
1,311

0
0.00
1,311

0.0%
0.0%
2.5%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

Net Ceiling Load


Lighting

0
3,120

0
3,120

0.0%
6.1%

Total Cooling Airflow


Resulting Room Relative Humidity

21.2%
5.9%
0.0%
41.4%

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Exhaust Heat

6,072
3,023
0
16,446

4,858
0
0
4,858

10,930
3,023
0
21,303

8,251
-159

16,960
0

25,210
-159

49.0%
-0.3%

Total Cooling Load


Area / Load

683
0

683
0

1.3%
0.0%

Total Floor Area


Cooling Airflow

Net Duct Heat Pickup


Wall Load to Plenum

0
355

0
355

0.0%
0.7%

Airflow / Load
Percent Outdoor Air

0
0
780
0
0
0
3,269
0

0
0
780
0
0
0
3,269
0

0.0%
0.0%
1.5%
0.0%
0.0%
0.0%
6.4%
0.0%

Cooling Load Methodology

0.0%

0.0%

Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

29,624

0
21,817

51,442

1,153.30
53.74

MBh
MBh
F
cfm
%

General Engineering Checks

Supply Fan Load


Return Fan Load

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design

32.26
56.26
57.48

4.7
262.33

ton
ft/ton

1,230
0.94

ft
cfm/ft

246.00
18.3

cfm/ton
%

RTS (Heat Balance)

###

System - 7th Flr - Left Wing


Type - Variable Volume Reheat (30% Min Flow Default)
Coil Location - System
Coil Peak Calculation Time: August, hour 16
Ambient DB/WB/HR: 109 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Solar Gain
Glass Transmission

Sensible
Btu/h
7,315
8,278

Latent
Btu/h

COOLING COIL SELECTION

Total
Btu/h

Percent
of Total

7,315
8,278

3.7%
4.2%

Coil Selection Parameters

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

83.8 / 70.4
89.80

F
gr/lb

Wall Transmission
Roof Transmission

2,108
0

2,108
0

1.1%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
2,813

0
0.00
2,813

0.0%
0.0%
1.4%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

Net Ceiling Load


Lighting

0
9,941

0
9,941

0.0%
5.0%

Total Cooling Airflow


Resulting Room Relative Humidity

8.9%
9.9%
0.0%
34.1%

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>

9,802
19,629
0
59,886

7,841
0
0
7,841

17,643
19,629
0
67,727

Ventilation Load
Exhaust Heat

32,559
-3,287

67,426
0

99,986
-3,287

50.4%
-1.7%

Total Cooling Load


Area / Load

Supply Fan Load


Return Fan Load

10,336
0

10,336
0

5.2%
0.0%

Total Floor Area


Cooling Airflow

0
1,542

0
1,542

0.0%
0.8%

Airflow / Load
Percent Outdoor Air

19,710
0
2,485
0
0
0
0
0

19,710
0
2,485
0
0
0
0
0

9.9%
0.0%
1.3%
0.0%
0.0%
0.0%
0.0%
0.0%

Cooling Load Methodology

0.0%

0.0%

Net Duct Heat Pickup


Wall Load to Plenum
Roof Load to Plenum
Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design
Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

123,232

0
75,268

198,500

###

Type - Single Zone


Coil Location - System
Coil Peak Calculation Time: August, hour 16
Ambient DB/WB/HR: 109 / 90 / 184

COOLING COIL LOAD INFORMATION


Sensible
Btu/h

Latent
Btu/h

Total
Btu/h

F
gr/lb

135.50
218.38
60.36

MBh
MBh
F

4,964.71
54.38

cfm
%

General Engineering Checks

System - 7th Flr - Package AHU

Load Component

58.5 / 57.3
67.99

COOLING COIL SELECTION


Percent
of Total

Coil Selection Parameters

18.2
215.63

ton
ft/ton

3,924
1.27

ft
cfm/ft

272.81
17.1

cfm/ton
%

RTS (Heat Balance)

Solar Gain
Glass Transmission

978
1,399

978
1,399

1.8%
2.5%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

84.8 / 70.9
90.98

F
gr/lb

536
0

536
0

1.0%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

56.6 / 54.9
61.59

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
1,311

0
0.00
1,311

0.0%
0.0%
2.4%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

36.77
60.63
57.08

MBh
MBh
F

Net Ceiling Load


Lighting

0
3,120

0
3,120

0.0%
5.6%

Total Cooling Airflow


Resulting Room Relative Humidity

19.8%
5.5%
0.0%
38.5%

Wall Transmission
Roof Transmission

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>

6,072
3,023
0
16,439

4,858
0
0
4,858

10,930
3,023
0
21,297

Ventilation Load
Exhaust Heat

8,126
-1,019

16,833
0

24,959
-1,019

45.1%
-1.8%

Total Cooling Load


Area / Load

683
0

683
0

1.2%
0.0%

Total Floor Area


Cooling Airflow

Net Duct Heat Pickup


Wall Load to Plenum

0
329

0
329

0.0%
0.6%

Airflow / Load
Percent Outdoor Air

6,145
0
780
0
0
0
2,140
0

6,145
0
780
0
0
0
2,140
0

11.1%
0.0%
1.4%
0.0%
0.0%
0.0%
3.9%
0.0%

Cooling Load Methodology

Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

33,622

0
21,691

0.0%

0.0%

55,314

###

System - 7th Flr - Right Wing


Type - Variable Volume Reheat (30% Min Flow Default)
Coil Location - System
Coil Peak Calculation Time: August, hour 15
Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION

cfm
%

General Engineering Checks

Supply Fan Load


Return Fan Load

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design

1,151.81
54.16

COOLING COIL SELECTION

5.1
243.41

ton
ft/ton

1,230
0.94

ft
cfm/ft

227.96
18.3

cfm/ton
%

RTS (Heat Balance)

Load Component

Sensible
Btu/h

Latent
Btu/h

Total
Btu/h

Percent
of Total

Coil Selection Parameters

Solar Gain
Glass Transmission

6,123
8,775

6,123
8,775

3.2%
4.6%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

82.9 / 69.6
87.27

F
gr/lb

Wall Transmission
Roof Transmission

2,519
0

2,519
0

1.3%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

59.7 / 57.7
68.07

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
2,578

0
0.00
2,578

0.0%
0.0%
1.3%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

132.86
210.03
61.54

MBh
MBh
F

Net Ceiling Load


Lighting

0
10,019

0
10,019

0.0%
5.2%

Total Cooling Airflow


Resulting Room Relative Humidity

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>

8,478
19,209
373
58,073

7,173
0
761
7,934

15,651
19,209
1,134
66,007

8.2%
10.1%
0.6%
34.6%

Ventilation Load
Exhaust Heat

30,536
-2,850

62,297
0

92,832
-2,850

48.6%
-1.5%

Total Cooling Load


Area / Load

Supply Fan Load


Return Fan Load

11,005
0

11,005
0

5.8%
0.0%

Total Floor Area


Cooling Airflow

0
1,814

0
1,814

0.0%
0.9%

Airflow / Load
Percent Outdoor Air

19,653
0
2,505
0
0
0
0
0

19,653
0
2,505
0
0
0
0
0

10.3%
0.0%
1.3%
0.0%
0.0%
0.0%
0.0%
0.0%

Cooling Load Methodology

Net Duct Heat Pickup


Wall Load to Plenum
Roof Load to Plenum
Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design
Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

120,735

0
70,230

0.0%

0.0%

190,965

5,285.73
54.40

cfm
%

General Engineering Checks

###

System - Grd Flr - Left Wing


Type - Variable Volume Reheat (30% Min Flow Default)
Coil Location - System
Coil Peak Calculation Time: August, hour 15

17.5
226.23

ton
ft/ton

3,960
1.33

ft
cfm/ft

301.99
14.8

cfm/ton
%

RTS (Heat Balance)

Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Sensible
Btu/h

Latent
Btu/h

COOLING COIL SELECTION

Total
Btu/h

Percent
of Total

Coil Selection Parameters

Solar Gain
Glass Transmission

5,471
7,605

5,471
7,605

3.1%
4.3%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

81.8 / 69.9
90.34

F
gr/lb

Wall Transmission
Roof Transmission

1,815
0

1,815
0

1.0%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

58.2 / 56.9
67.05

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
3,712

0
0.00
3,712

0.0%
0.0%
2.1%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

108.49
193.37
60.02

MBh
MBh
F

Net Ceiling Load


Lighting

0
10,338

0
10,338

0.0%
5.9%

Total Cooling Airflow


Resulting Room Relative Humidity

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>

16,082
8,831
0
53,854

12,862
0
0
12,862

28,944
8,831
0
66,716

16.5%
5.0%
0.0%
37.9%

Ventilation Load
Exhaust Heat

31,364
-582

64,299
0

95,664
-582

54.4%
-0.3%

Total Cooling Load


Area / Load

Supply Fan Load


Return Fan Load

9,337
0

9,337
0

5.3%
0.0%

Total Floor Area


Cooling Airflow

Net Duct Heat Pickup


Wall Load to Plenum

0
1,512

0
1,512

0.0%
0.9%

Airflow / Load
Percent Outdoor Air

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design

0
0
2,584
0
0
0
615
0

0
0
2,584
0
0
0
615
0

0.0%
0.0%
1.5%
0.0%
0.0%
0.0%
0.3%
0.0%

Cooling Load Methodology

0.0%

0.0%

Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

98,686

0
77,161

175,847

4,484.85
53.98

cfm
%

General Engineering Checks

###

System - Grd Flr - Package AHU


Type - Single Zone

16.1
253.14

ton
ft/ton

4,079
1.10

ft
cfm/ft

278.32
17.9

cfm/ton
%

RTS (Heat Balance)

Coil Location - System


Coil Peak Calculation Time: August, hour 15
Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Sensible
Btu/h

Latent
Btu/h

COOLING COIL SELECTION

Total
Btu/h

Percent
of Total

Coil Selection Parameters

Solar Gain
Glass Transmission

1,851
2,419

1,851
2,419

2.6%
3.4%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

81.9 / 69.7
89.30

F
gr/lb

Wall Transmission
Roof Transmission

1,314
0

1,314
0

1.9%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

56.2 / 54.4
60.29

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
1,562

0
0.00
1,562

0.0%
0.0%
2.2%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

43.95
76.49
56.72

MBh
MBh
F

Net Ceiling Load


Lighting

0
4,239

0
4,239

0.0%
6.0%

Total Cooling Airflow


Resulting Room Relative Humidity

23.1%
0.4%
0.0%
39.7%

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>

8,997
265
0
20,646

7,198
0
0
7,198

16,195
265
0
27,844

Ventilation Load
Exhaust Heat

10,786
-252

22,383
0

33,169
-252

47.3%
-0.4%

Total Cooling Load


Area / Load

916
0

916
0

1.3%
0.0%

Total Floor Area


Cooling Airflow

Net Duct Heat Pickup


Wall Load to Plenum

0
797

0
797

0.0%
1.1%

Airflow / Load
Percent Outdoor Air

0
0
1,060
0
0
0
6,607
0

0
0
1,060
0
0
0
6,607
0

0.0%
0.0%
1.5%
0.0%
0.0%
0.0%
9.4%
0.0%

Cooling Load Methodology

0.0%

0.0%

Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

40,560

0
29,581

70,140

###

cfm
%

General Engineering Checks

Supply Fan Load


Return Fan Load

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design

1,544.92
53.02

6.4
262.14

ton
ft/ton

1,671
0.92

ft
cfm/ft

242.36
17.9

cfm/ton
%

RTS (Heat Balance)

System - Grd Flr - Right Wing


Type - Variable Volume Reheat (30% Min Flow Default)
Coil Location - System
Coil Peak Calculation Time: August, hour 15
Ambient DB/WB/HR: 110 / 90 / 184

COOLING COIL LOAD INFORMATION


Load Component

Sensible
Btu/h

Latent
Btu/h

COOLING COIL SELECTION

Total
Btu/h

Percent
of Total

Coil Selection Parameters

Solar Gain
Glass Transmission

4,458
7,202

4,458
7,202

2.6%
4.2%

Coil Entering Air (DB / WB)


Coil Entering Humidity Ratio

82.1 / 70.0
90.76

F
gr/lb

Wall Transmission
Roof Transmission

2,034
0

2,034
0

1.2%
0.0%

Coil Leaving Air (DB / WB)


Coil Leaving Humidity Ratio

57.2 / 56.8
68.40

F
gr/lb

Floor Transmission
Adj Floor Transmission
Partition Transmission

0
0
2,926

0
0.00
2,926

0.0%
0.0%
1.7%

Coil Sensible Load


Coil Total Load
Cooling Supply Air Temperature

104.76
189.40
59.03

MBh
MBh
F

Net Ceiling Load


Lighting

0
9,075

0
9,075

0.0%
5.3%

Total Cooling Airflow


Resulting Room Relative Humidity

14.8%
6.2%
0.9%
36.8%

People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>

14,466
10,651
493
51,304

11,027
0
1,015
12,042

25,492
10,651
1,508
63,346

Ventilation Load
Exhaust Heat

31,501
-593

64,903
0

96,404
-593

56.0%
-0.3%

Total Cooling Load


Area / Load

Supply Fan Load


Return Fan Load

8,989
0

8,989
0

5.2%
0.0%

Total Floor Area


Cooling Airflow

Net Duct Heat Pickup


Wall Load to Plenum

0
1,559

0
1,559

0.0%
0.9%

Airflow / Load
Percent Outdoor Air

Roof Load to Plenum


Adj Floor to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to
Plenum
Glass Solar to Plenum
Over/Under Sizing
Reheat at Design

0
0
2,269
0
0
0
226
0

0
0
2,269
0
0
0
226
0

0.0%
0.0%
1.3%
0.0%
0.0%
0.0%
0.1%
0.0%

Cooling Load Methodology

4,317.66
53.54

cfm
%

General Engineering Checks


15.8
211.82

ton
ft/ton

3,343
1.29

ft
cfm/ft

273.56
18.6

cfm/ton
%

RTS (Heat Balance)

Underfloor Sup Heat Pickup

Supply Air Leakage

Total Cooling Loads

Project Name:
Dataset
Name:

95,255

0
76,945

Kuwait Scientific Center - Dolphin Area


DAR_SHIFA-A.TRC

0.0%

0.0%

172,200

###

TRACE 700 v6.3.1 calculated at 10:53 AM on 10/22/2015


Alternative - 1 Design Cooling Load Report Page 12 of 12

on

ce)

on

ce)

on

ce)

on

ce)

on

ce)

on

ce)

on

ce)

on

ce)

on

ce)

on

ce)

on

ce)

on

ce)

:53 AM on 10/22/2015
d Report Page 12 of 12