Professional Documents
Culture Documents
US Department of Justice Civil Rights Division - Letter - Diga1
US Department of Justice Civil Rights Division - Letter - Diga1
b. The door between the lobby and the staff area will be
relocated to allow for the required maneuvering space,
consistent with the Standards, S 4.13. An architect's
drawing showing the modified accessible door is
attached.
c. A visual fire alarm will be installed in the lobby, and
will be tied in to the building-wide fire alarm system,
consistent with the Standards, S 4.28. An architect's
drawing showing the lobby visual fire alarm is
attached.
6. Interior route violations
a. The door to the storage area behind the front desk will
be removed, and the doorway enlarged to a width that is
consistent with the Standards, S 4.13.5. An
architect's drawing showing the modified accessible
doorway is attached.
7. Violations with respect to public and common use toilet
rooms
a. The sign for the lobby restroom will be mounted on the
wall adjacent to the restroom door, consistent with the
Standards, S 4.30.6.
b. The existing rear and side grab bars in the lobby
restroom will be replaced with grab bars of the
required length, mounted at the required heights, and
at the required distance from the bathroom walls,
consistent with the Standards, S 4.16.4. An
architect's drawing showing the modified accessible
lobby restroom and grab bars is attached.
c. The drain and hot water pipes in the lobby restroom
will be insulated against contact, consistent with the
Standards, S 4.19.4.
d. A visual fire alarm will be installed in the lobby
restroom and will be tied in to the building-wide fire
alarm system, consistent with the Standards, SS 4.1,
4.28.
8. Violations with respect to public and common use rooms and
spaces
a. The hardware on the pool gate will be mounted at the
required height, consistent with the Standards,
SS 4.3.1, 4.13.9. An architect's drawing showing the
placement of the pool gate hardware is attached.
3
01-01168
9. Violations with respect to guest rooms generally
a. Guest room number signs will be mounted on the wall
adjacent to the latch side of the door for each guest
room, consistent with the Standards, S 4.30.6.
b. Visual alarms and notification devices will be
installed in 4 guest rooms and will be tied into the
building-wide system, including visual fire alarm
strobes in two guest rooms, consistent with the
Standards, SS 9.1.2, 9.1.3, 9.3. An architect's
drawing showing the required visual alarms and
notification devices is attached.
c. Doors to bathrooms in all the first floor standard
guest rooms will be modified to have the required 32"
clear opening width, consistent with the Standards,
SS 4.13.5, 9.4. An architect's drawing showing the
modified accessible bathroom doors is attached.
10. Violations with respect to guest rooms designated accessible
-- Rooms 103 and 114
a. The thresholds in guest rooms 103 and 114 will be
modified to have heights that are consistent with the
Standards, S 4.13.8.
b. One of the guest rooms designated accessible will have
two double beds, and the other will have one king size
bed, consistent with the Standards, S 9.1.4. An
architect's drawing showing the modified accessible
guest rooms is attached.
c. The beds in the accessible guest room with two double
beds will be reconfigured to provide the required
maneuvering space alongside and between the beds,
consistent with the Standards, S 9.2.2. An architect's
drawing showing the modified accessible guest room is
attached.
d. The existing hardware on the connecting doors between
guest rooms 103 and 114 will be replaced with hardware
that is easy to grasp with one hand and does not
require tight grasping, pinching or twisting of the
wrist to operate, consistent with the Standards, S
4.13.9.
e. The existing operating controls on the lamps and drapes
in guest rooms 103 and 114 will be replaced with
operating controls that are consistent with the
Standards, S 4.27.4.
4
01-01169
f. The shelf above the clothes rod in guest rooms 103 and
114 will be mounted at a height that is consistent with
the Standards, S 4.25.3. An architect's drawing
showing the modified accessible shelf is attached.
g. The bathroom doors in guest rooms 103 and 114 will be
modified so as not to swing out into the required clear
floor space at the lavatory and toilet, consistent with
the Standards, S 4.23.2. An architect's drawing
showing the modified accessible bathroom doors and
clear floor space is attached.
h. The towel racks in the bathrooms in guest rooms 103 and
114 will be remounted so as not to encroach on required
clear floor space and at a height that is consistent
with the Standards, SS 4.25.2, 4.25.3. An architect's
drawing showing the modified accessible bathrooms and
towel racks is attached.
i. The toilets in the bathrooms in guest rooms 103 and 114
will be repositioned to the required distance from the
sidewall to the center, consistent with the Standards,
S 4.16.2. An architect's drawing showing the modified
accessible toilets is attached.
j. The existing rear and side grab bars in the toilets in
guest rooms 103 and 114 will be replaced with grab bars
of the required length, and will be mounted at the
required height, consistent with the Standards,
S 4.16.4. An architect's drawing showing the modified
accessible toilets and grab bars is attached.
k. The towel rack above the grab bar in guest rooms 103
and 114 will be mounted so as not to interfere with use
of the rear grab bar, consistent with the Standards,
S 4.20.4. An architect's drawing showing the modified
accessible towel rack is attached.
l. The existing foot and rear grab bars in the bathtubs in
guest rooms 103 and 114 will be replaced with grab bars
of the required length, and will be mounted at the
required height, consistent with the Standards,
S 4.20.4. An architect's drawing showing the
accessible grab bars is attached.
m. The operating controls for the bathtubs in guest rooms
103 and 114 will be repositioned, consistent with the
Standards S 4.20.5. An architect's drawing showing the
placement of the accessible operating controls is
attached.
5
01-01170
Ms Bass
Page 2
July 24, 1996
Thank you for working with us on this project. If you shall have any further
questions or concerns
please call me. Look forward to your response.
Sincerely,
Ray E. Cox, Jr.
REC:tc
cc: Mr Ricky Patel
Mr Robert Leverett
Enclosure
01-01173
ADDENDUM NUMBER ONE
Days Inn
Elberton, Ga.
Architect: Southern Design
Anderson, South Carolina
Architects Project Number
18 July 1996
Addendum number one consists of modifications/changes to the specification and
drawings.
SPECIFICATIONS/DRAWINGS
In section 8 DOORS AND WINDOWS for the clear meaning all lock/latch
operations
shall be leaver handles, no knobs are to be allowed. Leavers to be brushed,
stainless steel finish to match existing on site.
All other information contained on the drawings and in the specifications is
to remain as is.
END OF ADDENDUM NUMBER ONE.
01-01174
THE DAYS INN ELBERTON, GA.
RENOVATION TO EXISTING DAYS INN ELBERTON, GA.
FOR AMERICANS WITH DISABILITIES ACT COMPLIANCE
AND U.S. DEPARTMENT OF JUSTICE SETTLEMENT PURPOSES
DRAWING INDEX
A COVER SHEET
A-1 SITE PLAN
A-2 FLOOR PLANS AND DETAILS
01-01175
(MAP) SITE PLAN
01-01176
(MAP) FLOOR PLAN ROOMS 102, 103, 113 & 114
01-01177