Professional Documents
Culture Documents
Manual Servicio Pretratamiento
Manual Servicio Pretratamiento
Manual Servicio Pretratamiento
BASIC / STANDARD
Service Manual
Edition: 1/03.11
Part no.: 636 210 1
Table of contents
1
Index
Important information
2.1
2.1.1
Preface........................................................................................................................................ 2-1
Structure of the Service Manual .................................................................................................. 2-1
2.2
2.3
2.3.1
2.3.2
2.3.3
Notes........................................................................................................................................... 2-3
Significance of the warnings........................................................................................................ 2-3
Significance of the note ............................................................................................................... 2-3
Significance of the tip .................................................................................................................. 2-3
2.4
2.4.1
2.4.2
2.4.3
2.5
2.5.1
2.5.2
2.5.3
2.5.4
2.6
Component overview
3.1
3.1.1
3.1.2
4.2
4.2.1
4.2.2
Installation.................................................................................................................................. 4-3
Installation / start-up requirements .............................................................................................. 4-3
Data reporting.............................................................................................................................. 4-3
4.3
4.3.1
4.3.2
4.3.3
4.4
Maintenance............................................................................................................................... 4-6
Service Manual
SM-EN
1/03.11
iii
4.5
4.5.1
4.5.3
4.5.4
4.6
4.6.1
4.6.2
4.6.3
4.5.2
Booster pump
5.1
5.2
5.2.1
5.2.2
Installation.................................................................................................................................. 5-2
Installation / start-up requirements .............................................................................................. 5-2
Important start-up information...................................................................................................... 5-2
5.2.2.1 Booster pump assembly connection ............................................................................ 5-2
5.2.2.2 Connection to the domestic water supply network ....................................................... 5-3
5.2.2.5 Overview of electrical connections ............................................................................... 5-9
Data reporting ............................................................................................................................ 5-13
5.2.3
5.3
5.3.1
5.3.2
5.4
5.5
5.5.1
5.6
5.6.1
5.6.2
5.6.3
iv
Service Manual
SM-EN
1/03.11
Pumps
6.1
6.2
6.2.1
6.2.2
6.2.3
Installation.................................................................................................................................. 6-2
Installation / start-up requirements .............................................................................................. 6-2
Important start-up information ..................................................................................................... 6-2
Data reporting.............................................................................................................................. 6-2
6.3
6.3.1
6.3.2
6.4
Maintenance............................................................................................................................... 6-4
6.5
6.5.1
6.5.2
6.6
6.6.1
Component overview sand filters S140, S200, S300, S400 ................................................ 7-1
7.2
7.3
7.3.1
7.3.2
7.3.7
7.4
7.4.1
7.4.2
7.4.3
7.5
Maintenance............................................................................................................................. 7-32
7.6
7.6.1
7.7
7.7.1
7.3.3
7.3.4
7.3.5
7.3.6
Service Manual
SM-EN
1/03.11
7.7.2
8.2
8.2.1
8.2.2
Installation.................................................................................................................................. 8-2
Installation / start-up requirements .............................................................................................. 8-2
Data reporting .............................................................................................................................. 8-2
8.3
8.3.1
8.3.2
8.4
8.5
8.5.1
8.5.2
Softener
9.1
Component overview softener E080(B), E150(B), E225-T, E300, E400 Magnum .............. 9-1
9.2
9.2.1
9.2.2
9.2.3
9.3
9.3.1
Installation.................................................................................................................................. 9-5
Installation / start-up requirements .............................................................................................. 9-5
9.4
9.4.1
9.4.2
9.4.5
9.5
9.5.1
9.5.2
9.5.3
9.5.4
9.4.3
9.4.4
vi
Service Manual
SM-EN
1/03.11
9.5.5
9.6
Maintenance............................................................................................................................. 9-51
9.7
9.7.1
9.8
9.8.1
9.8.2
9.8.3
10.2
10.2.1
10.2.2
10.2.3
Installation................................................................................................................................ 10-2
Installation / start-up requirements ............................................................................................ 10-2
Important start-up information ................................................................................................... 10-3
Start-up of the activated carbon filter......................................................................................... 10-4
10.2.3.1 Valve heads and drain restrictor................................................................................. 10-4
10.2.3.3 Control unit design ..................................................................................................... 10-8
Programming the control unit .................................................................................................. 10-10
10.2.4.1 Control / display ....................................................................................................... 10-10
10.2.4.2 Control / operating elements .................................................................................... 10-10
10.2.4.3 Control unit ............................................................................................................... 10-11
Data reporting.......................................................................................................................... 10-21
10.2.4
10.2.5
10.3
10.3.1
10.3.2
10.4
Maintenance........................................................................................................................... 10-27
10.5
10.5.1
10.6
10.6.1
10.6.2
11.2
11.3
11.3.1
Maintenance............................................................................................................................. 11-9
Maintenance intervals for water pretreatment components....................................................... 11-9
11.3.1.1 Feed water inlet unit ................................................................................................... 11-9
11.3.1.2 Sand filter ................................................................................................................... 11-9
11.3.1.3 Particle filter ............................................................................................................... 11-9
11.3.1.4 Softener.................................................................................................................... 11-10
Service Manual
SM-EN
1/03.11
vii
12.2
12.2.1
12.2.2
12.2.3
12.3
12.3.1
13 Definitions
13.1
13.2
Abbreviations........................................................................................................................... 13-1
13.3
Symbols.................................................................................................................................... 13-1
14 Appendix
viii
Service Manual
SM-EN
1/03.11
Chapter 1: Index
Index
Abbreviations 13-1
Addresses 2-9
Alternating or parallel operation
9-24
Softener 9-1
Softener capacities 9-48
Notes 2-3
T
Target group 2-5
Warnings 2-7
Pumps 6-1
Service Manual
SM-EN
1/03.11
1-1
Chapter 1: Index
1-2
Service Manual
SM-EN
1/03.11
Important information
2.1
Preface
2.1.1
Service Manual
SM-EN
1/03.11
2-1
2.2
Page identification
Editorial information
The editorial information 1/01.05, for example, refers to: 1st edition,
January 2005.
Organization of the
chapters
Illustrations
The illustrations used in the documents (e.g. screens, photos, etc.) may
differ from the original if this does not have any influence on the
function.
Importance of the
instructions
2-2
Changes
Reproduction
Service Manual
SM-EN
1/03.11
2.3
Notes
2.3.1
Warning
Advises the operator that failure to observe this information can result
in personal injury.
Warning
Advises the operator that failure to observe this information can cause
damage to the equipment.
2.3.2
Note
Information alerting the operator to the fact that failure to follow the
steps as specified may result in the specific function not being executed
correctly, not being executed at all, or not producing the desired effect.
2.3.3
Tip
Information providing useful tips for easy handling.
Service Manual
SM-EN
1/03.11
2-3
2.4
Brief description
Design BASIC /
STANDARD
Components
2-4
Service Manual
SM-EN
1/03.11
2.4.1
Operator information
Target group
Service Manual
SM-EN
1/03.11
2-5
Disclaimer of liability
2.4.2
Guarantee / warranty
Guarantee
Warranty
2.4.3
Technical documentation
On request, descriptions and other documents are made available by
the manufacturer. These are intended to support trained personnel of
the responsible organization in servicing and repairing the device.
2-6
Service Manual
SM-EN
1/03.11
2.5
Warnings
2.5.1
Basic warnings
Warning
The design of the water pretreatment components must comply with
the requirements of the Fresenius Installation Guideline (IGL)
2.5.2
Electric hazards
Warning
Danger to life caused by electrical voltage.
Touching live parts will cause an electric shock.
Before opening electrical devices, disconnect the power plug.
Actuating the ON/OFF switch stops operation of electrical devices,
but does not disconnect the system from the supply voltage!
Warning
The national standards and regulations must be observed when
connecting the system to the power supply system.
2.5.3
Chemical hazards
Warning
Use of protective equipments
Rubber gloves (acrylonnitril latex, cotton-lined) should be worn to avoid
contact of chemicals or disinfectant with the skin.
When working with acidic substances:
Wear goggles! Observe the safety precautions of the concentrated
substance used!
In the event of contact with acid:
Eye: Immediately flush with gently flowing water for 15 minutes.
Skin: Use soap under flowing water for neutralization.
Ingestion: Do not induce vomiting, but have the person affected drink
plenty of still water. Seek medical advice.
Service Manual
SM-EN
1/03.11
2-7
Warning
The system may only be disinfected after previous consultation with the
manufacturer of the system or by personnel authorized by the
manufacturer.
2.5.4
Biological hazards
Warning
Risk of infection
Observe the applicable local laws and regulations concerning handling
of potentially infectious material.
2-8
Service Manual
SM-EN
1/03.11
2.6
Addresses
Please address any inquiries to:
Manufacturer
International
service
Local
service
Service Manual
SM-EN
1/03.11
2-9
2-10
Service Manual
SM-EN
1/03.11
Component overview
3.1
Service Manual
SM-EN
1/03.11
3-1
3-2
Service Manual
SM-EN
A050
A100
A150
A300
A400
E080
E150
E225-T
E300
E400
Birm filter
B140
B200
B300
B400
Booster pump
Sand filter
S140
S200
S300
S400
Media filter
Tubing
A Stop valve
B Water meter (optional)
C Backwashable prefilter 105 m
D Solenoid valve
E Pipe disconnector
F Pressure reducer
3.1.1
Softener
1/03.11
Service Manual
SM-EN
1/03.11
A050
A100
A150
A300
A400
E080
E150
E225-T
E300
E400
Sand filter
S140
S200
S300
S400
Birm filter
B140
B200
B300
B400
Media filter
A Stop valve
B Water meter (optional)
C Backwashable prefilter 105 m
D Solenoid valve
E Pipe disconnector
F Pressure reducer
Booster pump
Tubing
3.1.2
Softener
3-3
3-4
Service Manual
SM-EN
1/03.11
4.1
Part number:
F00002261
F00001403
INLINE OPERATION
POS
Description
Stop valve
Solenoid valve
TANK OPERATION
Note:
An additional leakage detector (6328611), which switches the solenoid valve, must be implemented.
D
Service Manual
SM-EN
1/03.11
4-1
4.1.1
Part number:
F00001116
F00001117
F00001118
POS
Description
Stop valve
Backwashable prefilter
Pipe disconnector
Drain kit
Electronics unit
Leakage sensor
4-2
Service Manual
SM-EN
1/03.11
4.2
Installation
4.2.1
General information
Note
Start-up of the system must be performed by a trained technician. The
wiring must be adapted to fit the respective field of application.
Note
Prior to its start-up, check the system for damage caused during
transport. If there are signs of damage to the electric components, do
not turn the system on.
4.2.2
Data reporting
Note
Reports for the items of the operational qualification listed below
are available as master copies in chapter 12:
Start-up
Setting
Maintenance
Service Manual
SM-EN
1/03.11
4-3
4.3
Specifications
4.3.1
Tank operation
Inline operation
Rack operation
1 1/4
1 1/2
Rated flow
1.5m/h
25 L/min
2.9 m/h
48 L/min
5.8 m/h
97 L/min
2.4 m/h
40 L/min
4 m/h
67 L/min
7.8 m/h
130 L/min
12kg empty;
17kg empty;
22kg empty
Weight
~42 kg
Weight
~46 kg
Weight
~52 kg
Kv
2.2 m/h
2.5 m/h
6.0 m/h
Maximum pressure
8.0 bar
8.0 bar
6.8 bar
Ambient temperature
145 C
145 C
145 C
Water temperature
1-36 C
1-36 C
1-36 C
230 V 50 Hz
230 V 50 Hz
230 V 50 Hz
1 1/4
External thread
1 1/4
External thread
1 1/4
External thread
Weight
Weight without rack
Operating data
Voltage supply
Floor space
Prefiltration rack
(HxWxD in mm)
Connections
Inlet and outlet
4-4
Service Manual
SM-EN
1/03.11
4.3.2
Operating conditions
For information regarding the operating conditions refer to the latest
edition of the Installation Guideline (IGL).
4.3.3
Configuration options
Possible configurations:
Configuration with AquaSOFT (see chapter 10)
Automatic backwash function
Timer
Service Manual
SM-EN
1/03.11
4-5
4.4
Maintenance
Note
The information given below is summarized for all water
pretreatment components in Chapter 14 (Appendix).:
Important information on maintenance procedures
Accessories and supplies
Test report - maintenance
Overview / maintenance intervals for water pretreatment
components
Explanations for the test report
4-6
Service Manual
SM-EN
1/03.11
4.5
Functional description
4.5.1
Design of components
4.5.1.1
Standard configuration
The standard configuration of a feed water inlet path consists of the stop
valve, a backwashable prefilter, a solenoid valve, a pipe disconnector
and a drain connector.
4.5.2
Component function
4.5.2.1
Stop valve
The function of the stop valve is to stop the water supply for servicing to
perform maintenance procedures. The stop valve is provided with a
sampling port for the collection of feed water samples.
4.5.2.2
4.5.2.3
Service Manual
SM-EN
1/03.11
4-7
Solenoid valve
Function
The feed water inlet solenoid valve is used to disconnect the water
supply in case of a leakage. In case of rack installation it is activated by
a single-station leakage detection or in case of wall-mounted installation
by a leakage detector.
In combination with a feed water tank, the feed water inlet solenoid
valve is also used as a tank fill valve. In this case, the solenoid valve is
controlled by a float switch which is supplied with the feed water tank.
Manual opening
Normal condition
(original position)
Valve open
(manually bypassed)
In case of a power failure push the lever in and turn it by 90. In this position it is automatically locked and the valve is permanently open.
Water supply is therefore still ensured even without power supply.
Note
Without power supply, leakage monitoring is not active.
After dialysis hours, the valve should be closed again by unlocking to
stop the water supply in case of leakage.
4-8
Service Manual
SM-EN
1/03.11
4.5.2.5
Pipe disconnector
If the inlet pressure drops, the pipe disconnector ensures a
disconnection from the system (DIN EN 1717) as requested by the
Drinking Water Decree if there is a risk of back-contamination.
Service Manual
SM-EN
1/03.11
4-9
4.5.3
4.5.4
4-10
Component description
Stop valve
Backwashable prefilter
Solenoid valve
Pipe disconnector
Drain kit
The drain kit is used to direct the draining water to the drain in the
building.
Electronics unit
Leakage sensor
Service Manual
SM-EN
1/03.11
4.6
Options
4.6.1
4.6.2
4.6.3
Service Manual
SM-EN
1/03.11
4-11
4-12
Service Manual
SM-EN
1/03.11
Booster pump
5.1
Part number:
F00001935
B1
W2
D
A
POS
Description
B1
B2
Control unit
Pressurizer vessel
Service Manual
SM-EN
1/03.11
5-1
5.2
Installation
5.2.1
General information
Note
Start-up of the system must be performed by a trained technician. The
wiring must be adapted to fit the respective field of application.
Note
Prior to its start-up, check the system for damage caused during
transport. If there are signs of damage to the electric components, do
not turn the system on.
5.2.2
5.2.2.1
5-2
Service Manual
SM-EN
1/03.11
5.2.2.2
Note
If a pipe separator or a pressure reducer is installed on the outlet side
of the booster pump, the pressure sensor must always be installed after
these components. For the installation, remove the screw-type adapter
in the outlet block and integrate it after the pipe disconnector.
The pressure switch installed at the water inlet ensures protection
against running dry. Upon delivery, the pressure switch is set to 1 bar.
It is recommended to retain this setting. If the pressure in the water inlet
drops below 1 bar, the booster pump assembly will be stopped. If this
dynamic minimum pressure is not reached, it is recommended to use a
feed water tank.
State upon delivery: Dismounting the adapter
State upon delivery: When the system is supplied, the pressure
sensor is installed with an adapter at the pump outlet, this adapter
must be removed and must be installed after the pressure reducer
and the pipe separator.
The pressure sensor is installed on the outlet side after the pressure
reducer and the pipe separator.
Service Manual
SM-EN
1/03.11
5-3
5-4
Service Manual
SM-EN
1/03.11
Service Manual
SM-EN
1/03.11
5-5
5-6
Service Manual
SM-EN
1/03.11
5.2.2.3
Note
In case of tank operation, the tank must be provided with a float switch
which will open a contact if the tank is empty. This contact is connected
in the pump inlet instead of the pressure switch.
Tank connection
The inlet of the booster pump assembly is directly connected to the
outlet of the tank using the pump connection set no. 6319211.
The suction line can be connected either on the right or on the outer
left of the booster pump assembly.
In case of tank operation it is recommended to connect two suction
tubes in parallel to avoid pressure drops in the suction line.
The pressure port is located in the center and can be connected
using a tubing or a pipe for a fixed connection. A high-pressure tubing
with a length of x cm is included in the accessories package of the
system.
The pressure sensor is connected directly to the pump outlet.
The inlet pressure switch on the water inlet side of the pump is not
used during tank operation. In its place the float switch (see
illustration) must be wired in. This must be done during installation.
Service Manual
SM-EN
1/03.11
5-7
5-8
Service Manual
SM-EN
1/03.11
5.2.2.4
Power supply
A 400 V; 3 N ~; 50 Hz; 16 A three-phase current connection is required
to supply the pump switching unit with voltage.
5.2.2.5
Note
When the system is supplied, positions 1 to 6 are wired.
Positions 7 and 8 must be adjusted by the technician depending on
the respective situation (feed water tank or direct operation).
Service Manual
SM-EN
1/03.11
5-9
POS
Connections
Pump 1
Pump 2
Power cable
Temperature switch 1
Temperature switch 2
Pressure sensor
5-10
Service Manual
SM-EN
1/03.11
5.2.2.6
Pressure levels
Pressure
type
Description
Pmin
Operating pressure for base load and peak load pump (0-10 bar):
Pmin is set to the pressure at which the pump is to start.
Pmax1
Cutoff pressure level for the peak load pump (difference to Pmin), (0-4 bar):
If this pressure is achieved at parallel operation, the peak load pump is turned off. Pmax1 should
be set to a value between Pmin and Pmax2.
Pmax2
Cutoff pressure level for the base load pump (difference to Pmax1), (0-2 bar):
If this pressure is reached during operation of one pump, this pump is switched off. Pmax2
should be set to approx. 0.5 bar below the pump's nominal pressure.
Caution:
If a pressure reducer was installed downstream of the booster pump assembly, the pressure
reducer should be set to 6 bar minimum as the pressure on the pressure sensor can otherwise
never reach the cutoff pressure.
Note
The settings of max1 and Pmax2 are difference values which add to the
lower pressure set.
Service Manual
SM-EN
1/03.11
5-11
Calculation example
Setting Pmin: 3 bar
Setting Pmax1: 2 bar
Setting Pmax2: 1 bar
This means
Delay times
T = Over-run (02 min):
Minimum operation time of the pump to prevent permanent start and
stop of the pump. Default setting: 2 minutes. When set to "0 minutes",
the minimum operation time is approx. 30 seconds.
T = run-dry delay (02 min):
time after which die pumps are turned off in case the pump runs dry.
Default setting: 0 minutes.
When set to "0 minutes", the delay time is approx. 10 seconds.
Motor protection
Potentiometers P1 and P2 are set to the nominal current of the motor.
Motor protection setting (nominal current of
pump 1 and pump 2)
Setting Pmax2: Cutoff pressure level for base
load pump (difference to Pmax1)
Setting Pmax1: Cutoff pressure for peak load
pump (difference to Pmin)
Setting Pmin: Operating pressure for base
load and peak load pump
5-12
Service Manual
SM-EN
1/03.11
5.2.3
Data reporting
Note
Documentation of the settings in the Settings report
As part of the Operational Qualification, the settings must be
documented in the Settings reports upon start-up.
Note
Reports for the items of the operational qualification listed below
are available as master copies in chapter 12:
Start-up
Setting
Maintenance
Service Manual
SM-EN
1/03.11
5-13
5.3
Specifications
5.3.1
Parameter
Function / specifications
Usage
Pressure increase
Component
Type
CRN5-8
Connection
Sealing material
Installation position
Vertical
Operating current
2.5 kW / kVA
Power supply
Switch-off pressure
Pressure, minimum
Pressure, maximum
6.5 bar
1 C
40 C
Flow rate
5.3.1.1
Performance characteristics
Parameter
Function / specifications
Electrical connection
380400 V 3N~ 50 Hz
Power consumption
2.5 kW / kVA
Operating pressure
Cutoff pressure
5-14
Service Manual
SM-EN
1/03.11
5.3.1.2
Pumping head
Delivery volume
5.3.2
Operating conditions
For information regarding the operating conditions refer to the latest
edition of the Installation Guideline (IGL).
Service Manual
SM-EN
1/03.11
5-15
5.4
Maintenance
Note
The information given below is summarized for all water
pretreatment components in Chapter 14 (Appendix):
Important information on maintenance procedures
Accessories and supplies
Test report maintenance
Overview / maintenance intervals for water pretreatment
components
Explanations for the test report
5-16
Service Manual
SM-EN
1/03.11
5.5
Error messages
5.5.1
Selection
Description
Service Manual
SM-EN
1/03.11
5-17
5.6
Functional description
5.6.1
Design of components
B1
B2
5.6.2
D) Pressurizer vessel
Component description
The booster pump assembly (CRN5-8) is an assembly which is ready
for connection in accordance with the requirements for the minimum
flow pressure with normal centrifugal suction pumps.
The booster pump assembly in conjunction with the two vertical pumps
provides increased operational safety of a water treatment system from
Fresenius Medical Care.
The booster pump assembly is used for the alternating control of two
booster pumps. Automatic switching ensures uniform distribution of
stress on both connected pumps and prevents damage to the pump
caused by prolonged idle times when it is not in use. To increase the
efficiency, the second pump will be turned on additionally in peak
situations.
The booster pump assembly is intended for the pressure increase in the
feed water section of the water pretreatment system. It can be used
both for increasing the pressure downstream of a feed water tank and
for direct connection to the feed water line.
5.6.2.1
Control unit
The electronic control of the booster pump assembly controls and
monitors the two connected pumps.
5-18
Service Manual
SM-EN
1/03.11
5.6.2.2
5.6.2.3
5.6.2.4
Run-dry protection
The adjustable pressure switch at the booster pump assembly inlet
protects the system against running dry and ensures a minimum
pressure of 1 bar at the booster pump inlet.
If the pressure at the inlet drops below 1 bar, first the peak load pump
will stop. If the pressure at the inlet remains below 1 bar after this pump
stop, the base load pump will also be stopped.
5.6.2.5
Tank operation
When operated with a tank, a float switch will be connected instead of
the pressure to ensure protection against running dry.
5.6.2.6
Automatic turnoff
The water temperature is also monitored; if the temperature exceeds
60 C, e.g. by a defect of the control unit and a constantly running pump
without water consumption, the respective pump will be stopped.
Service Manual
SM-EN
1/03.11
5-19
5.6.3
Functional description
5.6.3.1
5.6.3.2
Selection
Description
5-20
Service Manual
SM-EN
1/03.11
Selection
Description
Off
Service Manual
SM-EN
1/03.11
5-21
5-22
Service Manual
SM-EN
1/03.11
Chapter 6: Pumps
Pumps
6.1
Part number:
F00002253
631 248 1
POS
Description
Service Manual
SM-EN
1/03.11
6-1
Chapter 6: Pumps
6.2
Installation
6.2.1
General information
Note
Start-up of the system must be performed by a trained technician. The
wiring must be adapted to fit the respective field of application.
Note
Prior to its start-up, check the system for damage caused during
transport. If there are signs of damage to the electric components, do
not turn the system on.
6.2.2
Pump CM5-5
The pumps must be ventilated prior to start-up of the switching unit.
6.2.3
Data reporting
Note
Reports for the items of the operational qualification listed below
are available as master copies in chapter 12:
Start-up
Setting
Maintenance
6-2
Service Manual
SM-EN
1/03.11
Chapter 6: Pumps
6.3
Specifications
6.3.1
Parameter
Function / specifications
Component / use
Type
CM5-5
Connection
Rp 1 suction side
Rp 1 delivery side
Material
Stainless steel
Sealing material
FKM
Installation position
Horizontal
Other components
Pressure control
Leakage sensor
Check valve
Operating current
0.9 kW
Power supply
Pressure, minimum
1 bar
Pressure, maximum
6 bar
0 C
40 C
Flow rate
6 m at 3 bar
6.3.2
Operating conditions
For information regarding the operating conditions refer to the latest
edition of the Installation Guideline (IGL).
Service Manual
SM-EN
1/03.11
6-3
Chapter 6: Pumps
6.4
Maintenance
Note
The information given below is summarized for all water
pretreatment components in Chapter 14 (Appendix).:
Important information on maintenance procedures
Accessories and supplies
Test report - maintenance
Overview / maintenance intervals for water pretreatment
components
Explanations for the test report
6-4
Service Manual
SM-EN
1/03.11
Chapter 6: Pumps
6.5
6.5.1
6.5.1.1
Indicator
Alarm
Possible cause
The Alarm
indicator is On.
Running dry
The Alarm
indicator is
flashing.
Service Manual
SM-EN
1/03.11
6-5
Chapter 6: Pumps
6.5.2
Indication
Possible cause
Action required
The ground fault interrupter or the voltagecontrolled circuit breaker has tripped.
No power supply.
Frequent switching on
and off.
6-6
Service Manual
SM-EN
1/03.11
Chapter 6: Pumps
6.6
Functional description
6.6.1
Design of components
Pump (CM5-5)
Components:
Water supply with stop valve at feed water inlet (optional)
Pump
Power supply
Pressure control
Service Manual
SM-EN
1/03.11
6-7
Chapter 6: Pumps
6-8
Service Manual
SM-EN
1/03.11
7.1
Part number:
F00001842
F00001843
F00001328
F00001329
A
B
C
D
E
F
G
H
POS
Description
Control head
Upper sieve
Riser tube
Filter bed
Tank
Gravel bed
Lower sieve
Service Manual
SM-EN
1/03.11
7-1
7.2
Part number:
F00002451
F00002452
F00002453
F00002454
A
B
C
D
E
F
G
H
POS
Description
Control head
Upper sieve
Riser tube
Filter bed
Tank
Gravel bed
Lower sieve
7-2
Service Manual
SM-EN
1/03.11
7.3
7.3.1
General information
Note
Start-up of the system must be performed by a trained technician. The
wiring must be adapted to fit the respective field of application.
Note
Prior to its start-up, check the system for damage caused during
transport. If there are signs of damage to the electric components, do
not turn the system on.
Service Manual
SM-EN
1/03.11
7-3
7.3.2
7.3.2.1
7-4
Service Manual
SM-EN
1/03.11
7.3.2.2
S140/ S200
S300 / S400
Drain
S140 / B140
S200 / B200
S300 / B300
S400 / B400
Drain rate
~45 L/min
~2000 L/h
~45 L/min
~2000 L/h
~90 L/min
~5400 L/h
~90 L/min
~5400 L/h
none
none
10 mm
10 mm
6 mm
6 mm
6.5 mm
6.5 mm
Service Manual
SM-EN
1/03.11
7-5
7-6
Betrieb
Backwash
Schnelles Splen
Service
Backwash
Fast Rinse
Service Manual
SM-EN
1/03.11
For the rinse time settings, refer to the master copies in the appendix.
Service Manual
SM-EN
1/03.11
7-7
Backwash times
The backwash must be timed to occur outside the operation time of the
reverse osmosis system. The softener may also not be regenerating.
It must also be ensured that the AquaA does not supply or rinse while
the backwash is in progress, but that a regeneration of the softener,
which may have been initiated by rinsing of the AquaA, can be
completed.
2.5 hours before the backwash of the sand filter, an operation of
10 minutes in the Supply mode using the auto-start and auto-stop
function, and a rinse interval phase, which lasts at least 4 hours,
must therefore be programmed on the AquaA.
Alternatively, the programmed start-stop times and the rinse interval
phase can be used for the calculation, so that the last rinse phase
occurs approx. 2.5 hours before the backwash of the sand filter:
AquaA
2.5 hours interval
Softener
Sand filter
7-8
Service Manual
SM-EN
1/03.11
S300 / S400
7.3.2.3
S140/ S200
Drain
S300 / S400
Drain 1
Rinse 2
Outlet
Drain 1
Inlet 4
Inlet 4 and 5
inlet
Outlet 3
Outlet 3
Rinse 2
Service Manual
SM-EN
1/03.11
7-9
7.3.2.4
Then remove the housing unit from its box and push it fully onto the
rear lugs.
Then slide the shaft back to the front. This may only be done with the
arrow marks being on the top. Refit the protective cover and
reconnect the 12 V AC; 150 mA power supply unit to the control unit.
7-10
Service Manual
SM-EN
1/03.11
7.3.3
7.3.3.1
Control / display
Current display
During operation, time and day are displayed. The day is indicated by
the triangle which moves from the left to the right.
A bar will be displayed below the date indicating the days during which
a regeneration will take place. In Europe the first day of the week is
generally the Sunday. If a regeneration is in progress, the regeneration
symbol will be displayed.
7.3.3.2
Display
manual
regeneration
Reg.
Down
Save
Set
7.3.3.3
Up
Control / programming
At the start the control must be set to the correct system configuration.
When inserting the control, the following screens may be displayed:
Service Manual
SM-EN
1/03.11
7-11
Fig. 1
Example
Fig. 1
263 F
293 F
Fig. 2
Fig. 2
7-12
Service Manual
SM-EN
1/03.11
Fig. 3
Fig. 3
The display shows only dashes. In this case, there is also a stored
configuration, and the control prompts you to enter the current time and
day. This setting is lost in case of a prolonged power loss.
Here it is also recommended to enter the system configuration again
with a Reset (see level 4).
Level 1
Level 1 can only be accessed with a new control after turning power on
or with a Reset (see level 4) for entering basic data.
The arrow keys or are used to scroll, Set is used to release
the value for changing it, the arrow keys are used to change the
value, and Set is used to save the value.
LEVEL 1
Service Manual
P1
Current time
P2
P3
Regeneration time
SM-EN
1/03.11
7-13
LEVEL 1
P4
P5
P6
P7
and
P8
not used
Level 2
Level 2 is also used to define basic parameters.
This level is accessed by simultaneously pressing the key Up and
Down keys + for 5 seconds.
This can only be done from the normal operation display. (Therefore if
Error 3 or Error 4 is displayed and the system configuration has not yet
been defined or verified,
immediately go to level 4 and make a reset.)
The arrow keys or are used to scroll, Set is used to release the
value for changing it, the arrow keys are used to change the value, and
Set is used to save the value.
LEVEL 2
7-14
P9
P10
P11
P12
P13
P19
not used
Service Manual
SM-EN
1/03.11
C1
C2C4
not used
C5
C6C8
not used
Level 4 history
Level 4 is used to see the history.
(Possibility in H0 for a reset with the Set key for 5 seconds..
This level is accessed by simultaneously pressing the Set and Up
keys + for 5 seconds. (This can even be done during a
regeneration).
Example
LEVEL 4
H0: F
H1: 0
H2
H16
0 not used
H17: 4
H18
and
H19
0 not used
Starting a regeneration
When pressing the Reg key, the Reg. symbol will be flashing. This
indicates that a delayed regeneration is due which would start at the
programmed time P3.
Service Manual
SM-EN
1/03.11
7-15
If the Reg. key is pressed for 5 seconds, the Reg. symbol will be
displayed permanently and a regeneration will be started immediately.
Pressing the Set and Up keys + briefly and simultaneously, will
quickly skip a phase. This will set the remaining phase time, which
is displayed by briefly pressing the Set key , to 0.
A regeneration which has started can be skipped completely by
pressing the Set and Up keys + for 5 seconds.
7-16
Service Manual
SM-EN
1/03.11
7.3.3.4
Programming table for S140 / S200 or B140 / B200 using the control Logix 762
Level 1
Return to default screen:
From each menu after 30 seconds idle phase.
Operation screen:
Indication of time and current day
Level 1
263
Filter
P1
E.g.: 9:30
Current time
P2
upper edge
P3
2:00
Backwash time
P4
P5
Rinse days
P6
6 / 8 (Birm 20)
P7
Capacity in m3
P8
Level 2
and for 5 seconds.
Blocking a value with the Reg. key
LEVEL 2
P9
P10
P11
P12
60 seconds
P1319
Service Manual
SM-EN
1/03.11
7-17
Rinse days in P5
Regeneration
Change
...
Yes / No
...
Continue
Level 3
+ for 5 seconds.
Time in minutes: S300 / S400
Short regeneration
Immediate regeneration
Cancel regeneration
+ for 5 seconds
Skip phase
+ briefly
During a regeneration, always the remaining time of the complete
regeneration will be displayed.
Remaining time of the phase displayed with
LEVEL 3
C1
mod
Backwash 1
S140 / B140
= 6 min / 20 min
S200 / B200
= 8 min / 20 min
C2
C3
C4
C5
mod
Fast Rinse 1
C8
7-18
Service Manual
SM-EN
1/03.11
Level 4
and for 5 seconds
In H0 : for 5 seconds, reset for control - then Reg. for synchronization.
LEVEL 4
H0
Filter display
H1
H6
H17
Months in operation
Service Manual
SM-EN
1/03.11
7-19
7.3.3.5
Programming table for S140 / S200 or B140 / B200 using the control Logix 762
Level 1
Return to default screen:
From each menu after 30 seconds idle phase.
Operation screen:
Indication of time and current day
LEVEL 1
293
Filter
P1
e.g.: 9:30
Current time
P2
upper edge
P3
2:00
Backwash time
P4
P5
Rinse days
P6
7 (Birm 20)
P7
Capacity in m3
P8
Level 2
and for 5 seconds.
Blocking a value with the Reg. key
LEVEL 2
P9
P10
P11
P12
60 seconds
P1319
7-20
Service Manual
SM-EN
1/03.11
Rinse days in P5
Regeneration
Change
...
Yes / No
...
Continue
Level 3
and for 5 seconds
Time in minutes: S300 / S400
Short regeneration
Immediate regeneration
Regeneration 5 seconds
Cancel regeneration
Skip phase
and briefly
During a regeneration, always the remaining time of the complete
regeneration will be displayed.
Remaining time of the phase displayed with
LEVEL 3
C1
mod
S300 / B300
= 7 min / 20 min
Backwash 1
S400 / B400
= 9 min / 20 min
C2
C3
C4
C5
mod
Fast Rinse 1
C8
Service Manual
SM-EN
1/03.11
7-21
Level 4
and for 5 seconds
In H0 : 5 seconds, reset for control - then Regeneration for
synchronization.
LEVEL 4
H0
Filter display
H1
H6
H17
Months in operation
7-22
Service Manual
SM-EN
1/03.11
7.3.4
Data reporting
Note
Documentation of the settings in the Settings report
As part of the Operational Qualification, the settings must be
documented in the Settings reports upon start-up.
Note
Reports for the items of the operational qualification listed below
are available as master copies in chapter 12:
Start-up
Setting
Maintenance
Service Manual
SM-EN
1/03.11
7-23
7.3.5
7.3.5.1
7.3.5.2
Substance
Iron content
< 4 mg/l
Manganese content
Free chlorine
6.8-8.0
8.0-8.5
Manganese removal
8.0-9.0
If iron and manganese are not removed in the softener but in the Birm
filter, the following applies:
Note
Until the backwash 1.7 mg iron per liter of Birm can be removed from
1 m water.
If the water also contains manganese, this value is reduced to
1.2 mg per 1 m.
Based on this information the backwash interval must be calculated.
7-24
Service Manual
SM-EN
1/03.11
7.3.5.3
S200 / B200
S300 / B300
S400 / B400
250
500
750
1000
1250
1500
1750
2000
2250
3000
4000
* at a yield of 70 %
Note
In principle, it may be said that no additional sand filter must be installed
when using a Birm filter since the Birm filter covers the sand filter's
function due to its physical characteristics.
Note
For information regarding sand and Birm layers, backwash times and
space requirements, refer to chapter Specifications / Birm filter data
sheet.
Service Manual
SM-EN
1/03.11
7-25
7.3.6
Note
A reduced drain restrictor is only required for ceramic filter media.
For Birm, the backwash time is increased to at least 20 min.
The water's oxygen content must be at least 15 % of the iron content.
All other settings are made as specified in the sand filter settings
table.
7.3.6.1
B140
Rated output*
B200
B300
B400
250
4 (3)
500
2.1 (1.5)
750
1.4 (1)
1000
1.1 (0.8)
1250
0.8 (0.6)
1.4 (1)
1500
1.2 (0.8)
1750
1 (0.7)
2000
0.9 (0.6)
2250
0.8 (0.6)
3000
0.8 (0.6)
0.6 (0.4)
4000
0.5 (0.4)
* at 70 % yield and 80 operating hours a week (corresponding to 15 dialysis shifts of 5 h each + rinsing approx.
5 h)
7-26
Service Manual
SM-EN
1/03.11
B140
B200
Rated output*
B300
B400
250
4 (4.5)
500
3.4 (2.4)
750
2.2 (1.6)
1000
1.7 (1.2)
1250
1.3 (1)
2.3 (1.6)
1500
1.9 (1.3)
1750
1.6 (1.2)
2000
1.4 (1)
2250
1.3 (0.9)
3000
0.9 (0.7)
4000
0.8 (0.6)
* at 70 % yield and 50 operating hours between the backwashes (for both tables the following applies:
Calculations with 20 % loss for 3 years of operation).
Note
Depending on the actual operating hours, the actual utilization (HD
consumption) and substances, the backwash interval must be adjusted
proportionally.
Service Manual
SM-EN
1/03.11
7-27
7.3.7
Operating conditions
For information regarding the operating conditions refer to the latest
edition of the Installation Guideline (IGL).
7-28
Service Manual
SM-EN
1/03.11
7.4
Specifications
7.4.1
S140
S200
S300
S400
25 kg
1 bag
25 kg
1 bag
25 kg
1 bag
25 kg
1 bag
140 liters
250 kg
10 bag
203 liters
325 kg
13 bag
203 liters
325 kg
13 bag
250 liters
400 kg
16 bag
170 liters
16 x 65
41 x 162 cm
250 liters
18 x 65
47 x 165 cm
250 liters
18 x 65
47 x 165 cm
310 liters
21 x 60
56 x 172 cm
Freeboard +5 cm
45 cm
41 cm
41 cm
41 cm
300 kg
390 kg
400 kg
490 kg
430 kg
550 kg
560 kg
690 kg
Riser tube
Distance above upper edge
of tank
28
2025 mm
28
2025 mm
48.3
0-5 mm
48.3
0-5 mm
Backwash
Rinse volume
Backwash flow*
45 L/min
45 L/min
90 L/min
90 L/min
Backwash time
Individually
adjustable
Individually
adjustable
Individually
adjustable
Individually
adjustable
Kv
2.5 m/h
2.8 m/h
7.3 m/h
7.5 m/h
Minimum pressure
2 bar
2 bar
2 bar
2 bar
Maximum pressure
8 bar
8 bar
6.8 bar
6.8 bar
Ambient temperature
1-40C
1-40C
1-45C
1-45C
Water temperature
1-40C
1-40C
1-36C
1-36C
Voltage supply
230 V 60/50 Hz
230 V 60/50 Hz
230 V 60/50 Hz
230 V 60/50 Hz
12 V~
12 V~
12 V~
12 V~
55x72x200
55x72x200
Space requirements
Floor space
W x D x H in mm
42x60x187
50x60x192
* the values indicated are real values and depend on the prevailing conditions and the actual available pressure.
Service Manual
SM-EN
1/03.11
7-29
7.4.2
B140
B200
B300
B400
25 kg
1 bag
25 kg
1 bag
25 kg
1 bag
25 kg
1 bag
Sand bed
Sand layer per tank
16.7 liters
25 kg
1 bag
33.5 liters
50 kg
2 bags
33.5 liters
50 kg
2 bags
50 liters
75 kg
3 bags
Birm bed
Birm layer per tank
85 liters
75 kg
3 bags
142 liters
125 kg
5 bags
142 liters
125 kg
5 bags
170 liters
150 kg
6 bags
Freeboard +5 cm
68 cm
57 cm
57 cm
60 cm
Other data: Backwash times*, space requirements, etc. identical to the sand filter specifications
* The backwash times should generally be adjusted to the local water
quality so that the water is largely clear at the end of the backwash time.
With the Birm filter, the usual minimum backwash time is 20 minutes.
7-30
Service Manual
SM-EN
1/03.11
7.4.2.1
S200 / B200
S300 / B300
S400 / B400
250
500
750
1000
1250
1500
1750
2000
2250
3000
4000
* at a yield of 70 %
Note
In principle, it may be said that no additional sand filter must be installed
when using a Birm filter since the Birm filter covers the sand filter's
function due to its physical characteristics.
7.4.3
Operating conditions
For information regarding the operating conditions refer to the latest
edition of the Installation Guideline (IGL).
Service Manual
SM-EN
1/03.11
7-31
7.5
Maintenance
Note
The information given below is summarized for all water
pretreatment components in Chapter 14 (Appendix):
Important information on maintenance procedures
Accessories and supplies
Test report - maintenance
Overview / maintenance intervals for water pretreatment
components
Explanations for the test report
7-32
Service Manual
SM-EN
1/03.11
7.6
Error messages
7.6.1
Error
Possible cause
Action required
Valves contaminated
Valves leaking due to worn
spring
Water pressure too low
Sieve for servo flow clogged
Poor or no automated
regeneration
Service Manual
SM-EN
1/03.11
7-33
7.7
Functional description
7.7.1
Design of components
7.7.2
Component description
If the feed water analysis reveals a silt density index of SDI > 3, a sand
filter must be installed to reduce suspended solids.
The sand filter removes particles from the feed water. The filter media
used is garnet which prevents suspended solids from passing through
the spacing between the media granules, which formed when the filter
was filled, at slow flow velocities. The flow velocity of the water in the
sand filter is considerably lower than in the upstream pipes or fixtures.
The water is also forced to find its way through the spacing between the
sand bed. This permits the suspended solids to settle on the sand, or
first to conglomerate before being held back in the spacings. Larger
particles settle immediately on the the surface of the filter bed.
7.7.2.1
Backwash
A sand filter must be backwashed at regular intervals to remove the
retentate. On principle, the filter effect is increased with service life of
the system (formation of a so-called filter cake). For reasons of hygiene,
it is recommended to perform a backwash once a week. If the pressure
drop has increased by 50 %, this is a criteria that a backwash should be
performed. The required frequency may therefore vary depending on
7-34
Service Manual
SM-EN
1/03.11
the water. During the backwash process, particles on the surface of the
bed, and particles in the spacings are removed and rinsed to drain.
Generally the backwash process is the better, the higher the flow
velocity. However this is restricted by the settling velocity of the filter
material, which may not be removed, and by the practical technical
constraints.
7.7.2.2
Flow velocities
In practice flow velocities around 30 m/h are used for backwashing.
Backwashing can therefore only be done outside operation times. This
can only be avoided by the connection of two sand filters in parallel. For
setting the backwash times, observe the settings in chapter 5
(backwash time).
Note
The use of Birm for iron removal in the sand filter requires that the upper
sieve be provided. The upper sieve which is supplied with the sand filter
is not required if the water contains silicate to improve the rinsing away
of conglomerated particles which have been held back.
7.7.2.3
7.7.2.4
Efficiency
The efficiency of sand filters depends to a large extent on the flow rate.
The correct design of the sand filter is determined by the project
planning team.
To protect the downstream components, it is recommended to use a 20
m micro-filter in the sand filter's outlet.
Service Manual
SM-EN
1/03.11
7-35
7-36
Service Manual
SM-EN
1/03.11
8.1
Part number:
F00001222
F00001223
F00001224
F00001225
C
D
A
E
Dual version:
Single version:
POS
Description
Particle filter
Sampling port
Retaining plate
Drain valve
Service Manual
SM-EN
1/03.11
8-1
8.2
Installation
8.2.1
General information
Note
The pressure gauges on the fine filters must be pre-assembled so that
they can be easily read from the front or from the top.
Note
Start-up of the system must be performed by a trained technician. The
electrical connection is to be adjusted to the respective installation
environment.
Note
Prior to its start-up, check the system for damage caused during
transport. Do not put the system into operation if components are
damaged.
8.2.2
Data reporting
Note
Reports for the items of the operational qualification listed below
are available as master copies in chapter 12:
Start-up
Setting
Maintenance
8-2
Service Manual
SM-EN
1/03.11
8.3
Specifications
8.3.1
Parameter
Function / specifications
Usage
Fine filtration
Components
Filter
Pressure gauge; inlet / outlet
Sampling port
Type
Connection
Nominal width
20
Material
HFPP
PVC (tubing)
Sealing material
BUNA N
Filter mesh
5 m / 20 m
Dimensions
Pressure
Maximum
Pressure drop
6.2 bar
0.5 bar
Temperature
Maximum
8.3.2
37.8 C
Operating conditions
For information regarding the operating conditions refer to the latest
edition of the Installation Guideline (IGL).
8.3.2.1
2000 L/h
Permeate volume
4000 L/h
Single 5 m
Single 20 m
Dual 5 m
Dual 20 m
Service Manual
SM-EN
1/03.11
8-3
8.4
Maintenance
Note
The information given below is summarized for all water
pretreatment components in Chapter 14 (Appendix):
Important information on maintenance procedures
Accessories and supplies
Test report - maintenance
Overview / maintenance intervals for water pretreatment
components
Explanations for the test report
8-4
Service Manual
SM-EN
1/03.11
8.5
Functional description
8.5.1
Design of components
8.5.2
Component description
Particle filter
Particle filters are used to adsorb particles which may be released from
water treatment systems and other suspended solids still present in the
feed water.
A 20 m particle filter is connected downstream of the sand filter to
prevent filter media from entering into th supply path.
Another particle filter is installed upstream of the reverse osmosis
system. In the last stage before the system, the water is filtered with a
filtering efficiency of 5 m.
Service Manual
SM-EN
1/03.11
8-5
8-6
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Softener
9.1
Part number:
F00001119
F00001120
F00001453
Softener E225-T
F00001121
F00001122
E080(B) / E150(B)
E225-T
B
C
D
E
F
Service Manual
SM-EN
1/03.11
9-1
Chapter 9: Softener
POS
Description
Brine lines
Brine tank
Float cup
Grid plate
Brine valve
9-2
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.2
The following tables show the modified settings for the new softener
heads. These settings have been selected for problems with high brine
concentration.
The rinse times are extended by these times to improve rinsing out of
the brine. This ensures an optimized operation at locations with
problematic operating conditions.
9.2.1
CP 216
9.2.2
Set point
new
C1
C2
30
30
C3
28
38
C4
C5
14
C8
T Reg.
87
106
CP 213
Service Manual
SM-EN
Set point
new
C1
C2
17
17
C3
24
35
C4
C5
15
C8
T Reg.
62
83
1/03.11
9-3
Chapter 9: Softener
9.2.3
CP 210
9-4
Set point
new
C1
C2
C3
15
25
C4
C5
10
C8
T Reg.
39
56
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.3
Installation
9.3.1
General information
Note
Start-up of the system must be performed by a trained technician. The
wiring must be adapted to fit the respective field of application.
Note
Prior to its start-up, check the system for damage caused during
transport.
If there are signs of damage to the electric components, do not turn
the system on.
Service Manual
SM-EN
1/03.11
9-5
Chapter 9: Softener
9.4
9.4.1
Time / day
Regeneration time
Brine volume
Capacity
Hardness
9-6
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.4.2
9.4.2.1
Control / display
Display
manual
regeneration
Reg.
Down
Save
Set
9.4.2.2
Up
Example:
Fig. 1
Service Manual
SM-EN
1/03.11
9-7
Chapter 9: Softener
Softener valve
configuration
E080(B) / E150(B)
278 L
E225-T
298 A
E300 / E400
Fig. 2
Fig. 2
Fig. 3
The display shows only dashes. In this case, there is also a stored
configuration, and the control prompts you to enter the current time and
day. This setting is lost in case of a prolonged power loss.
Here it is also recommended to enter the system configuration again
with a Reset (see level 4).
Level 1
Level 1 can only be accessed with a new control after turning power on
or with a Reset (see level 4) for entering basic data.
For browsing use the arrow keys or , use Set to clear the
value for changing.
The value is changed with the arrow keys and set with Set .
9-8
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
LEVEL 1
P1
Current time
P2
P3
P4
P5
not used
P6
P7
P8
Level 2
Level 2 is also used to define basic parameters.
This level is accessed by simultaneously pressing the Up and Down
key + for 5 seconds.
This can only be done from the normal operation display. (Therefore if
Error3 or Error4 is displayed and the system configuration has not yet
been defined or verified, immediately go to level 4 and make a reset.)
For browsing use the arrow keys or , use Set to clear the
value for modification.
The value is changed with the arrow keys and set with Set .
LEVEL 1
Service Manual
P9
P10
P11
P12
P13
P14
P15
SM-EN
1/03.11
9-9
Chapter 9: Softener
LEVEL 1
P16
P17
P18
P19
C1
C2
C3
C4
C5
C6
C7
---
C8
Level 4 history
Level 4 is used to see the history.
(Possibility in H0 for a reset with the Set key for 5 seconds).
This level is accessed by simultaneously pressing the Set and Up
keys + for 5 seconds. (This can even be done during a
regeneration).
9-10
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Example:
LEVEL 4
Service Manual
H0: F
200
liters
H1: 0
H2
L/min
Current flow
H3
H4
H5
2804
H6
H7
3.84
H8
17.4
H9
22.46
H10
21.24
Average consumption on
Wednesdays
H11
20.78
H12
18.58
H13
5.36
H14
Service cycle
H15
96
L/min
H16
15:19
Fr
H17:
Months
H18
1.234
liters
H19
00
liters
SM-EN
1/03.11
9-11
Chapter 9: Softener
Starting a regeneration
When pressing the Reg. key, the Reg. symbol will be flashing. This
indicates that a delayed regeneration is due which would start at the
programmed time P3.
If Reg. is briefly pressed a second time, a factor x2 will be displayed
after the flashing Reg. symbol, indicating that both tanks will be
regenerated at the set Reg time.
If the Reg. key is pressed for 5 seconds, the Reg. symbol will be
displayed permanently and a regeneration will be started
immediately.
If the Reg. key is again pressed for 5 seconds immediately
thereafter, a factor x2 will be displayed after the Reg. symbol,
indicating that both tanks will immediately be regenerated one after
the other.
Pressing the Set and Up keys + briefly and simultaneously, will
quickly skip a phase. This will set the remaining phase time, which
is displayed by briefly pressing the Set key , to 0.
A regeneration which has started can be skipped by pressing the Set
and Up keys + for 5 seconds .
9-12
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.4.3
E225-T
The design of the softener must ensure that the operating time of one
tank is at least the regeneration time and the time required for the
brine to develop (approx. 3 4 hours), and that regeneration takes
place at least once a day. Make absolutely sure to avoid prolonged
standby times, if necessary regeneration of both tanks must be
started manually or electrically.
Filling on site:
If the softeners are to be filled on site, use the immersion pipe to fill
the tanks completely with water after they have been filled with the
filter material and before mounting the control heads.
Service Manual
SM-EN
1/03.11
9-13
Chapter 9: Softener
9.4.3.1
When the softener has been set up and the control has been
programmed, the system must be carefully ventilated and rinsed.
Before this is done, it must be checked that all lines and equipment
upstream of the softener has been thoroughly rinsed. To rinse the
softener, the outlet of the softener must be dismounted and
discarded to the drain. The brine tank should remain empty until
rinsing and ventilation are finished. The water inlet valve must be
opened slowly and only partly. Watch the removal of air until water
exits. When using E300 / 400 softeners, the drain must now be
closed or considerably restricted.
When water exits, the tank or the vessel is not actually completely
ventilated. The air is actually completely removed with the
backwash.
Manual regeneration
Refill Phase C8
9-14
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Please note that, although the slow-rinse phase C3 has the same effect
as the draw-brine phase C2, the system is already rinsed clear to avoid
high concentrations of brine in the standby mode.
Especially for softeners E080(B) and E150(B) it must be ensured
that any residual brine has been rinsed away at the end of C3. This
can easily be verified by taking a taste sample on the drain.
When the first regeneration is complete and the reverse osmosis
system to be supplied continues to run in the rinse mode when the
second regeneration starts, correct switching to the tanks to be
supplied and the programmed times can be checked.
Note
The programmed values must be documented in the start-up
report.
Service Manual
SM-EN
1/03.11
9-15
Chapter 9: Softener
9.4.4
The softener has been set up and the control has been
programmed using the programming table.
2.
The brine tank has been correctly positioned, has been connected
and filled with salt tablets.
The brine tank can then be filed with feed water up to the float cup
to allow the brine in the tank to develop.
3.
Caution:
The softener system must be carefully ventilated.
5.
6.
9-16
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.
10. Check the water hardness at the softener outlet and thus the
softener function.
11. If the water hardness is zero, start-up of the RO system can be
started.
Note
Start another manual regeneration during the start-up.
This causes the tanks to switch, and the second tank can be
checked for proper service.
Service Manual
SM-EN
1/03.11
9-17
Chapter 9: Softener
9.4.4.1
E300 / E400
Drain restrictor
Connection for drain with restrictor
Softener TYPE
Drain
E080(B)
E150(B)
E225-T
E300
E400
8 -15 L/min
10 -20 L/min
10 -20 L/min
15 -30 L/min
20 -40 L/min
Restrictor hole at
4.5-6 bar
4 mm
4 mm
4 mm
Blue 5.0 mm
Red 5.5 mm
Restrictor hole at
3-4.5 bar
4 mm
4.5 mm
4.5 mm
Red 5.5 mm
Green
6.0 mm
Restrictor hole at
2-3 bar
4.5 mm
5 mm
5 mm
Green
6.0 mm
Without insert
Use the appropriate restrictors for the pressures to be reached as specified in the table.
The pressure values refer to the pressure indicated at the softener inlet.
Tip
Identification of the restrictors (for E080(B), E150(B) and E225-T):
4 mm has 1 ring
4.5 mm has 2 rings
5 mm has no ring
Restrictor hole
9-18
The restrictor hole of E300 and E400 can be adjusted on site to the
prevailing pressure. The appropriate color is installed.
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
E300 / E400
Service Manual
SM-EN
1/03.11
9-19
Chapter 9: Softener
Fast Rinse
Operation
9-20
Backwash
Draw brine
Pressure
compensation
Auxiliary and service position for E080(B) and E150(B) / small valve
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Auxiliary and service position for E300 and E400 / large valve
Auxiliary position
Service position
The tank which was last regenerated (here always tank 1) remained in
the auxiliary position. When a regeneration is initiated, this tank is
switched from the auxiliary position to the Service position. For small
softeners this means:
Fast rinsing and Service of the tank. For large softeners this means
direct switching from the auxiliary position to the Service position.
The Triplex softener regenerates in one go, i.e. without stop at the
auxiliary position.
Function
Input
Service Manual
SM-EN
1/03.11
9-21
Chapter 9: Softener
9.4.4.2
Refill
control
9.4.4.3
Brine connection
E300 / E400
Suction tube
Sieve for
servo flows
Brine connection
Brine tank
The brine level listed in the specification is a net value. The gross value
takes the offset of the brine valve into consideration.
Depending on the net level X, the brine valves are set to the gross
level H:
Softener TYPE
E080(B)
E150(B)
E225-T
E300
E400
14 cm
30 cm
30 cm
35 cm
45 cm
Lower offset
4 cm
4 cm
4 cm
12.5 cm
12.5 cm
Upper offset
6 cm
6 cm
6 cm
3.5 cm
3.5 cm
Level
24 cm
40 cm
40 cm
51 cm
61 cm
9-22
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.4.4.4
E300 / E400
Inlet 3
Refill 1
Brine
Drain #1
Outlet 4
Rinse
5 and 6
Rinse #2
Outlet #3
Drain 1
Inlet 4
Inlet
#4 and #5
Drain
7.8 and 9
Outlet 3
Rinse 2
The valves in the small head are switched directly and can be opened
manually for rinsing in case of servicing.
The large control heads switch indirectly via servo valves, therefore
each time the valve closes, a small servo flow will exit the servo drain.
Rinsing clear in case of servicing can only be done indirectly. The servo
flow sieve should be regularly checked according the the local
conditions.
To permit operation of the E080(B) / E150(B) with a brine tank, a refill
will be performed in the auxiliary position. This is not required for the
E225-T as it performs a complete regeneration.
9.4.4.5
Service Manual
SM-EN
1/03.11
9-23
Chapter 9: Softener
9.4.4.6
Efficiency
high
medium
low
9-24
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Service Manual
SM-EN
1/03.11
9-25
Chapter 9: Softener
9.4.4.7
Take the housing unit out of the carton and fit it onto the rear flaps
until it stops.
Then slide the shaft back to the front. This may only be done with the
marker arrow facing up. Refit the protective cover. Then position the
flow sensor.
9-26
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Small figure
Triplex wiring
Service Manual
SM-EN
1/03.11
9-27
Chapter 9: Softener
9.4.4.8
Level 1
Return to default screen:
From each menu after 30 seconds idle phase.
Operation screen:
Tank number
Flow in L/min alternating with remaining capacity in m
Brief indication of time with []
Level 1
278A
40
liters resin
P1
e.g.: 9:30
Current time
P2
upper edge
P3
2:00
Regeneration time
P4
P6
110
P7
1.9
P8
180
Level 2
+ for 5 seconds.
Blocking a value with the Reg. key
Level 2
P9
P10
P11
P12
60
P13
--
Salt check and chlorine processor 0=none; 1=only sensor; 2=chlorine processor and
sensor
P14
70
P15
30
gpmx 100 suction capacity - (gpm = l/min; 3.785 l/g) (change standard 26 to 30)
P16
--
P17
--
9-28
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Level 2
P18
P19
Pr
Pd
Level 3
+ for 5 seconds
Time in minutes
Short regeneration
Immediate regeneration
Regeneration 5 seconds
Cancel regeneration
+ for 5 seconds
Skip phase
+ short
During a regeneration, always the remaining time of the complete
regeneration will be displayed.
Indication of the remaining time of the phase by
LEVEL 3
C1
mod
Backwash1
C2
fixed
12
C3
mod
24
slow Rinse
C4
mod
Repressurize / Standby
C5
mod
Fast Rinse 1
C6/C
C8
fixed
57
Level 4
and for 5 seconds
In H0 : 5 seconds, reset for control - then Reg. for synchronization.
Service Manual
SM-EN
1/03.11
9-29
Chapter 9: Softener
LEVEL 4
H0
H1
H2
Current flow
H3
H4
H5
H6
H7
H8
H9
H10
H11
H12
H13
H14
H15
H16
H17
Months in operation
H18
H19
9-30
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.4.4.9
Level 1
Return to default screen:
From each menu after 30 seconds idle phase.
Operation screen:
Tank number
Flow in L/min alternating with remaining capacity in m
Brief indication of time and []
Level 1
278A
80
liters resin
P1
e.g.: 9:30
Current time
P2
upper edge
P3
2:00
Regeneration time
P4
P6
110
P7
3.8
P8
180
Level 2
+ for 5 seconds.
Blocking a value with the Reg. key
Level 2
P9
P10
P11
P12
60
P13
--
Salt check and chlorine processor 0=none; 1=only sensor; 2=chlorine processor and
sensor
P14
137
P15
40
gpmx 100 suction capacity - (gpm = l/min; 3.785 l/g) (change standard 26 to 40)
P16
--
P17
--
Service Manual
SM-EN
1/03.11
9-31
Chapter 9: Softener
Level 2
P18
1. P19
1. Pr
1. Pd
Level 3
+ for 5 seconds
Time in minutes 0
Short regeneration
Immediate regeneration
Cancel regeneration
+ for 5 seconds
Skip phase
+ short
During a regeneration, always the remaining time of the complete
regeneration will be displayed.
Indication of the remaining time of the phase by
LEVEL 3
C1
mod
Backwash1
C2
fixed
18
C3
mod
25
slow Rinse
C4
mod
Repressurize / Standby
C5
mod
Fast Rinse1
C6/C
C8
fixed
9-32
67
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Level 4
and for 5 seconds
In H0 : 5 seconds: reset for control - then Reg. for synchronization.
LEVEL 4
H0
H1
H2
current flow
H3
H4
H5
H6
H7
H8
H9
H10
H11
H12
H13
H14
H15
H16
H17
Months in operation
H18
H19
Service Manual
SM-EN
1/03.11
9-33
Chapter 9: Softener
Reserve
% **
Hardness [dH]
RO
system
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
1500
10
15
15
15
20
20
20
25
1750
10
10
10
15
15
15
20
20
20
25
2000
10
10
15
15
20
25
30
---
---
2250
10
15
20
20
25
25
30
30
---
---
---
---
3000
10
15
15
15
20
25
30
30
---
---
---
---
---
---
4000
10
15
20
25
30
30
---
---
---
---
---
---
---
---
---
---
rated
output*
* at a yield of 70%
** reserve to be set as reference value depends on the supply profile
Level 1
Return to default screen:
From each menu after 30 seconds idle phase.
Operation indicator
Tank number
Flow in L/min alternating with remaining capacity in m
Brief indication of time and []
Level 1
278L
80
liters resin
P1
e.g.: 9:30
Current time
P2
upper edge
P3
00:01 / 01:30 /
3:
P4
P6
110
P7
3.8
P8
180
9-34
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Level 2
+ for 5 seconds.
Blocking a value with the Reg. key
Level 2
P9
P10
P11
P12
60
P13
--
Salt check and chlorine processor 0=none; 1=only sensor; 2=chlorine processor and
sensor
P14
22
P15
40
gpmx 100 suction capacity - (gpm = l/min; 3.785 l/g) (change standard 26 to 40)
P16
P17
35
P18
P19
Pr
Pd
Level 3
+ for 5 seconds
Time in minutes 0
Short regeneration
Immediate regeneration
Cancel regeneration
+ for 5 seconds
Skip phase
+ short
During a regeneration, always the remaining time of the complete
regeneration will be displayed.
Indication of the remaining time of the phase by
Service Manual
SM-EN
1/03.11
9-35
Chapter 9: Softener
LEVEL 3
C1
mod
Backwash1
C2
fixed
18
C3
mod
25
slow Rinse
C4
mod
Repressurize / Standby
C5
mod
Fast Rinse1
C6/C
C8
fixed
30
87
Level 4
and for 5 seconds
In H0 : 5 seconds: reset for control - then Reg. for synchronization.
LEVEL 4
H0
H1
H2
Current flow
H3
H4
H5
H6
H7
H8
H9
H10
H11
H12
H13
H14
H15
H16
9-36
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
LEVEL 4
H17
Months in operation
H18
H19
Service Manual
SM-EN
1/03.11
9-37
Chapter 9: Softener
Level 1
Return to default screen:
From each menu after 30 seconds idle phase.
Operation indicator
Tank number
Flow in L/min alternating with remaining capacity in m
Brief indication of time and []
Level 1
298A
150
liters resin
P1
e.g.: 9:30
Current time
P2
upper edge
P3
2:00
Regeneration time
P4
P6
110
P7
7.2
P8
180
Level 2
+ for 5 seconds.
Blocking a value with the Reg. key
Level 2
P9
P10
P11
P12
60
P13
--
Salt check and chlorine processor 0=none; 1=only sensor; 2=chlorine processor and
sensor
P14
40
gpmx 100 refill capacity - Brine Refill (change standard 100 to 40)
P15
55
gpmx 100 suction capacity - (gpm = l/min; 3.785 l/g) (change standard 60 to 55)
P16
--
P17
--
9-38
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Level 2
P18
P19
Pr
Pd
Level 3
+ for 5 seconds
Time in minutes 0
Short regeneration
Immediate regeneration
Regeneration 5 seconds
Cancel regeneration
+ for 5 seconds
Skip phase
+ short
During a regeneration, always the remaining time of the complete
regeneration will be displayed.
Indication of the remaining time of the phase by
LEVEL 3
C1
mod
Backwash1
C2
fixed
25
C3
mod
25
slow Rinse
C4
mod
Repressurize / Standby
C5
mod
Fast Rinse1
C6/C
C8
fixed
31
94
Level 4
and for 5 seconds
In H0 : 5 seconds: reset for control - then Reg. for synchronization.
Service Manual
SM-EN
1/03.11
9-39
Chapter 9: Softener
LEVEL 4
H0
H1
H2
current flow
H3
H4
H5
H6
H7
H8
H9
H10
H11
H12
H13
H14
H15
H16
H17
Months in operation
H18
H19
9-40
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Level 1
Return to default screen:
From each menu after 30 seconds idle phase.
Operation indicator
Tank number
Flow in L/min alternating with remaining capacity in m
Brief indication of time and []
Level 1
298A
200
liters resin
P1
e.g.: 9:30
Current time
P2
upper edge
P3
2:00
Regeneration time
P4
P6
110
P7
9.6
P8
180
Level 2
+ for 5 seconds.
Blocking a value with the Reg. key
Level 2
P9
P10
P11
P12
60
P13
--
Salt check and chlorine processor 0=none; 1=only sensor; 2=chlorine processor and
sensor
P14
45
P15
60
P16
--
P17
--
Service Manual
SM-EN
1/03.11
9-41
Chapter 9: Softener
Level 2
P18
P19
Pr
Pd
Level 3
+ for 5 seconds
Time in minutes 0
Short regeneration
Immediate regeneration
Cancel regeneration
+ for 5 seconds
Skip phase
+ short
During a regeneration, always the remaining time of the complete
regeneration will be displayed.
Indication of the remaining time of the phase by
LEVEL 3
C1
mod
10
Backwash1
C2
fixed
30
C3
mod
28
slow Rinse
C4
mod
Repressurize / Standby
C5
mod
Fast Rinse1
C6/C
C8
fixed
36
110
Level 4
and for 5 seconds
In H0 : 5 seconds: reset for control - then Reg. for synchronization.
9-42
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
LEVEL 4
H0
H1
H2
Current flow
H3
H4
H5
H6
H7
H8
H9
H10
H11
H12
H13
H14
H15
H16
H17
Months in operation
H18
H19
Service Manual
SM-EN
1/03.11
9-43
Chapter 9: Softener
9.4.5
Data reporting
Note
Documentation of the settings in the Settings report
As part of the Operational Qualification, the settings must be
documented in the Settings reports upon start-up.
Note
Reports for the items of the operational qualification listed below
are available as master copies in chapter 12:
Start-up
Setting
Maintenance
9-44
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.5
Specifications
Service Manual
SM-EN
1/03.11
9-45
Chapter 9: Softener
9.5.1
Softener TYPE
E080(B)
E150(B)
E225-T
E300
E400
Duplex/altern.
Duplex/altern.
Triplex
Duplex/altern.
Duplex/altern.
12.5 kg /
0.5 bag
12.5 kg /
0.5 bag
12.5 kg /
0.5 bag
25 kg /
1 bag
25 kg /
1 bag
38 L /
1.5 bags
75 L /
3 bags
75 L /
3 bags
150 L /
6 bags
200 L /
8 bags
96
192
192
360
480
63 liters
10 x 54
26 x 139 cm
105 liters
13 x 54
34 x 139 cm
105 liters
13 x 54
34 x 139 cm
194 liters
16 x 65
41 x 162 cm
257 liters
18 x 65
47 x 165 cm
Freeboard regenerated +5 cm
34 cm
33 cm
33 cm
30 cm
43 cm
45/57 x 90
45/57 x 90
45/57 x 112
59/67 x 115
59/67 x 115
12 cm
12 cm
12 cm
38 cm
38 cm
130 kg
210 kg
290 kg
350 kg
450 kg
430 kg
600 kg
150 kg
800 kg
1200 kg
Regeneration volume
Approx.
320 liters
Approx.
575 liters
Approx.
575 liters
Approx.
920 liters
Approx.
1230 liters
20 L/min*
20 L/min*
20 L/min*
32 L/min*
32 L/min*
4.8 kg
8.7 kg
8.7 kg
17.5 kg
23 kg
(14 cm)
24 cm
(30 cm)
40 cm
(30 cm)
40 cm
(35 cm)
51 cm
(45 cm)
61 cm
Regeneration time
60 min*
70 min*
85 min*
90 min*
100 min*
Kv
2.2 m/h
2.5 m/h
5.5 m/h
5.5 m/h
6.0 m/h
Minimum pressure
2 bar
2 bar
2 bar
2 bar
2 bar
Maximum pressure
8 bar
8 bar
8 bar
6.8 bar
6.8 bar
Ambient temperature
1-45C
1-45C
1-45C
1-45C
1-45C
Water temperature
1-36C
1-36C
1-36C
1-36C
1-36C
Voltage supply
230 V 60/50 Hz
230 V 60/50 Hz
230 V 60/50 Hz
230 V 60/50 Hz
230 V 60/50 Hz
W x D x H in mm
see space
requirements
see space
requirements
see space
requirements
see space
requirements
see space
requirements
1400 x 800 x
1750
1400 x 800 x
1750
1400 x 800 x
1750
Softener design
* the values indicated are real values and depend on the actual available pressure.
9-46
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.5.2
SOFTENER TYPE
E080(B)
Required drain during
backwash and fast
rinse
E150(B)
E225-T
E300
E400
815 L/min
1020 L/min
1020 L/min
1530 L/min
2040 L/min
Restrictor hole at
4.56 bar
4.0 mm
4.0 mm
4.0 mm
Blue 5.0 mm
Red 5.5 mm
at 3-4.5 bar
4.0 mm
4.5 mm
4.5 mm
Red 5.5 mm
Green 6.0 mm
at 2-3 bar
4.5 mm
5.0 mm
5.0 mm
Green 6.0 mm
Without insert
The restrictor diameters specified are given for reference and may be optimized to meet the local conditions.
Service Manual
SM-EN
1/03.11
9-47
Chapter 9: Softener
9.5.3
Softener capacities
The table lists the softener capacities per tank in cubic meters of water,
depending on the hardness of the water entering the softener:
Capacity in m
SOFTENER
E080(B)
E150(B) /
E225-T
E300
E400
Hardness [dH]
Hardness in mg
CaCO/L
1.9*
3.8*
7.2*
9.6*
40
48.0
96.0
180.0
240.0
80
24.0
48.0
90.0
120.0
110
17.5
34.9
65.5
87.3
150
12.8
25.6
48.0
64.0
10
180
10.7
21.3
40.0
53.3
12
220
8.7
17.5
32.7
43.6
14
260
7.4
14.8
27.7
36.9
16
290
6.6
13.2
24.8
33.1
18
330
5.8
11.6
21.8
29.1
20
360
5.3
10.7
20.0
26.7
22
400
4.8
9.6
18.0
24.0
24
440
4.4
8.7
16.4
21.8
26
470
4.1
8.2
15.3
20.4
28
510
3.8
7.5
14.1
18.8
30
540
3.6
7.1
13.3
17.8
32
580
3.3
6.6
12.4
16.6
34
620
3.1
6.2
11.6
15.5
36
650
3.0
5.9
11.1
14.8
38
690
2.8
5.6
10.4
13.9
40
720
2.7
5.3
10.0
13.3
* Total capacity of a tank in kg CaCO3 (with 48g capacity/liter of resin) as by P7 (see report master copy)
9-48
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.5.4
Operating conditions
For information regarding the operating conditions refer to the latest
edition of the Installation Guideline (IGL).
9.5.4.1
Note
The choice of softener depends on the hardness of the feed water
supply and on the required volume in L/h.
Use the softener selection table shown below.
Hardness [dH]
SOFTENER TYPE
Reverse osmosis
system - rated
output*
E080(B)
E150(B)
250
1682
3082
500
850
1682
750
634
1068
2082
1000
424
850
1682
1250
420
640
1282
1500
416
634
654
1068
1750
414
628
646
1058
6078
2000
412
424
640
850
5268
2250
422
636
846
4860
3000
416*
632
634
3646
424
(424)
634
4000
E225-T
E300
E400
* at a yield of 70 %
() Values at a flow between 4060m/h or 1.1 - 1.7 cm/sec
Service Manual
SM-EN
1/03.11
9-49
Chapter 9: Softener
9.5.4.2
Reserve
% **
Hardness [dH]
Reverse
osmosis
system
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
1500
10
15
15
15
20
20
20
25
1750
10
10
10
15
15
15
20
20
20
25
2000
10
10
15
15
20
25
30
---
---
2250
10
15
20
20
25
25
30
30
---
---
---
---
3000
10
15
15
15
20
25
30
30
---
---
---
---
---
---
4000
10
15
20
25
30
30
---
---
---
---
---
---
---
---
---
---
rated
output*
* at a yield of 70 %
** reserve to be set as reference value depends on the supply profile.
9.5.5
Substance
Hardness to be added
Hard water
+3 dH
Manganese (Mn2+)
+5 dH
9-50
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.6
Maintenance
Note
The information given below is summarized for all water
pretreatment components in Chapter 14 (Appendix):
Important information on maintenance procedures
Accessories and supplies
Test report - maintenance
Overview / maintenance intervals for water pretreatment
components
Explanations for the test report
Service Manual
SM-EN
1/03.11
9-51
Chapter 9: Softener
9.7
Error messages
9.7.1
Problem
Possible cause
Action required
Error 1
Error 2
Error 3
Display
-- : --
Error 4
9-52
Valves contaminated
Valves leaking, possibly due to
worn spring
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
Problem
Possible cause
Action required
Poor or no automated
regeneration
Correct if necessary
Service Manual
SM-EN
1/03.11
9-53
Chapter 9: Softener
Problem
Possible cause
Action required
RO water shortage at
regeneration.
9-54
Service Manual
SM-EN
1/03.11
Chapter 9: Softener
9.8
Functional description
9.8.1
Design of components
Softener design
Intended purpose
The softener is an indispensable component of a central water treatment
system in a dialysis unit. It replaces all components in the water causing
water hardness, such as calcium (Ca++) and magnesium (Mg++), by
sodium (Na+).
The prevailing concentrations cause the sodium ions, which are
attached to the ion exchanger resin, to be substituted by ions causing
water hardness. In the course of the operating time the capacity of the
ion exchanger resin will be exhausted which means that no more ions
will be exchanged. The exhausted resin must therefore be regenerated
to be able to use a saturated saline solution (NaCl).
To ensure that a regeneration can also be performed during dialysis
hours, a softener unit is generally a twin-tank (Duplex) or triple-tank
(Triplex) design:
While the one tank is in service, the other tank is regenerating. The two
resin tanks of a twin-tank unit are controlled by a control head. The brine
for regeneration is produced in a brine tank which is connected to the
control head and which in turn is periodically refilled with salt tablets.
The control head provides the brine tank with the amount of water
required to produce the brine. It features an integrated, adjustable float
mechanism which controls both the amount of water supplied and the
amount of brine required for regeneration.
9.8.2
Component description
The scale-forming calcium and magnesium ions in the softener
pressure tanks are replaced by sodium ions. As the capacity of the
softener is directly proportional to the amount of resin, but this amount
is limited, the resin beds must be regenerated. This is done with sodium
chloride brine. The brine or sodium-chloride solution is supplied by a
brine tank.
To ensure production of brine and softening, the salt, i.e. the salt tablets,
in the brine tank must always be above the water level. If salt is refilled
too late this may lead to high concentrations of brine or hard water.
Service Manual
SM-EN
1/03.11
9-55
Chapter 9: Softener
9.8.3
9-56
Service Manual
SM-EN
1/03.11
F00001844
F00001845
F00001846
F00001330
F00001331
A
B
C
D
E
F
G
H
POS
Description
Control head
Upper sieve
Riser tube
Filter bed
Tank
Gravel bed
Lower sieve
Service Manual
SM-EN
1/03.11
10-1
10.2 Installation
10.2.1 Installation / start-up requirements
General information
Note
Start-up of the system must be performed by a trained technician. The
wiring must be adapted to fit the respective field of application.
Note
Prior to its start-up, check the system for damage caused during
transport. If there are signs of damage to the electric components, do
not turn the system on.
10-2
Service Manual
SM-EN
1/03.11
Service Manual
SM-EN
1/03.11
10-3
A300 / A400
Drain
10-4
Service Manual
SM-EN
1/03.11
Required drain
during backwash
and fast rinse
Restrictor hole
A050
A100
A150
A300
A400
approx. 45 L/min
approx. 45 L/min
approx. 45 L/min
approx. 60 L/min
approx. 3600 L/h
approx. 60 L/min
approx. 3600 L/h
6 mm
6 mm
6 mm
8 mm
8 mm
Backwash
Service
Backwash
Fast rinse
Fast Rinse
For the rinse time settings, refer to the master copies in the appendix.
Service Manual
SM-EN
1/03.11
10-5
Backwash times
The backwash of sand filters must be timed to occur outside the
operation time of the reverse osmosis system.
Additionally, the softener may not regenerate during the reverse
osmosis operating time.
It must be ensured that e.g. an AquaA is not in the Supply or Rinse
mode while the sand filter is backwashed. It should be possible to fully
run a regeneration of the softener possibly initiated by rinsing of the
AquaA.
2.5hours before the backwash of the sand filter, an operation of 10
minutes in the Supply mode using the auto-start and auto-stop function,
and a rinse interval phase, which lasts at least 4 hours, should therefore
be programmed on the AquaA.
Due to the long time intervals, it is recommended not to rinse the
activated carbon filter(s) on the same day as the sand filters.
At best they can be backwashed subsequently. First the activated
carbon filter(s) and then the sand filter.
AquaA
2.5 hours interval
Softener
Sand filter
10-6
Service Manual
SM-EN
1/03.11
S300 / S400
Service Manual
SM-EN
1/03.11
10-7
Drain
A300 / A400
Drain 1
Rinse 2
Outlet
Outlet 3
Drain 1
Inlet 4
Inlet 4 and 5
Inlet
Outlet 3
Rinse 2
Then remove the housing unit from its box and push it fully onto the
rear lugs.
10-8
Service Manual
SM-EN
1/03.11
Then slide the shaft back to the front. This may only be done with the
arrow marks being on the top.
Refit the protective cover and reconnect the 12 V/AC 150 mA power
supply unit to the control unit.
Service Manual
SM-EN
1/03.11
10-9
During operation, time and day are displayed. The day is identified by
the triangle that moves from left to right.
A bar will be displayed below the date indicating the days during which
a regeneration will take place. In Europe the first day of the week is
generally the Sunday. If a regeneration is in progress, the regeneration
symbol will be displayed.
Current display:
In the picture shown it is Sunday and the filter is currently regenerating.
10.2.4.2 Control / operating elements
Display
manual
regeneration
Reg.
Down
Save
Set
10-10
Up
Service Manual
SM-EN
1/03.11
Fig. 1
Example
Fig. 1
263 F
293 F
Fig. 2
Fig. 2
Service Manual
SM-EN
1/03.11
10-11
Fig. 3
Fig. 3
The display shows only dashes. In this case, there is also a stored
configuration, and the control prompts you to enter the current time and
day. This setting is lost in case of a prolonged power loss.
Here, it is also recommended to enter the system configuration again
with a reset (see level 4).
Level 1
Level 1 can only be accessed with a new control after turning power on
or with a Reset (see level 4). Basic data is entered in this level.
The arrow keys or are used to scroll, Set is used to release
the value for changing it, the arrow keys are used to change the
value, and Set is used to save the value.
LEVEL 1
P1
Current time
P2
P3
Regeneration time
10-12
Service Manual
SM-EN
1/03.11
LEVEL 1
P4
P5
P6
P7 and P8
not used
Level 2
Level 2 is also used to define basic parameters.
This level is accessed by simultaneously pressing the Up and Down
keys + for 5 seconds.
This can only be done from the normal operation display. (Therefore
if Error3 or Error4 is displayed and the system configuration has not
yet been defined or verified, immediately go to level 4 and make a
reset.)
The arrow keys or are used to scroll, Set is used to release
the value for changing it, the arrow keys are used to change the
value, and Set is used to save the value.
LEVEL 2
P9
P10
P11
P12
P13P19
not used
Service Manual
SM-EN
1/03.11
10-13
LEVEL 3
C1
C2C4
not used
C5
C6C8
not used
Level 4 history
Level 4 is used to see the history.
(Possibility in H0 for a reset with the Set key for 5 seconds).
This level is accessed by simultaneously pressing the Set and Up
keys + for 5 seconds. (This can even be done during a
regeneration.)
Example:
LEVEL 4
H0: F
H1: 0
H2H16
0 not used
H17: 4
0 not used
10-14
Service Manual
SM-EN
1/03.11
Start regeneration
When pressing the Reg. key, the Reg. symbol will be flashing. This
indicates that a delayed regeneration is due which would start at the
programmed time P3.
If the Reg. key is pressed for 5 seconds, the Reg. symbol will be
displayed permanently and a regeneration will be started
immediately.
Pressing the Set and Up keys + briefly and simultaneously, will
quickly skip a phase. This will set the remaining phase time, which
is displayed by briefly pressing the Set key , to 0.
A regeneration which has started,can be skipped by pressing the Set
and Up keys + for 5 seconds.
Service Manual
SM-EN
1/03.11
10-15
10.2.4.4 Activated carbon filter A050, 100, 150 programming table - control Logix 762
Level 1
Return to default screen:
From each menu after 30 seconds idle phase.
Operation indicator
Indication of time and current day
Level 1
263
Filter
P1
e.g.: 9:30
Current time
P2
upper edge
P3
2:00
Backwash time
P4
P5
Rinse days
P6
5 / 8 / 12
P7
Capacity in m3
P8
Level 2
and for 5 seconds.
Blocking a value with the Reg. key
LEVEL 2
P9
P10
P11
P12
60 seconds
P1319
10-16
Service Manual
SM-EN
1/03.11
Rinse days in P5
Regeneration
Change
...
Yes / No
...
Continue
Level 3
+ for 5 seconds
Time in minutes: A300 / A400
Short regeneration
Immediate regeneration
Regeneration 5 seconds
Cancel regeneration
+ for 5 seconds
Skip phase
+ short
During a regeneration, always the remaining time of the complete
regeneration will be displayed.
Display of the remaining time of the phase with
LEVEL 3
C1
mod
A50 = 5 min
A100 = 8 min
Backwash 1
A150 = 12 min
C2
C3
C4
C5
mod
A50 = 3 min
A100 = 4 min
Fast Rinse 1
A150 = 5 min
C6/C
C8
A50 = 8 min
A100 = 12 min
A150 = 17 min
Service Manual
SM-EN
1/03.11
10-17
Level 4
and for 5 seconds
In H0 : 5 seconds, reset for control - then Reg. for synchronization.
LEVEL 4
H0
Filter display
H1
H17
Months in operation
10-18
Service Manual
SM-EN
1/03.11
10.2.4.5 Activated carbon filter A300 / 400 programming table - control Logix 762
Level 1
Return to default screen:
From each menu after 30 seconds idle phase.
Operation indicator
Indication of time and current day
LEVEL 1
293
Filter
P1
e.g.: 9:30
Current time
P2
upper edge
P3
2:00
Backwash time
P4
P5
Rinse days
P6
8 / 10
P7
Capacity in m3
P8
Level 2
and for 5 seconds.
Blocking a value with the Reg. key
LEVEL 2
P9
P10
P11
P12
60 seconds
P1319
Service Manual
SM-EN
1/03.11
10-19
Rinse days in P5
Regeneration
Change
...
Yes / No
...
Continue
Level 3
and for 5 seconds
Time in minutes: A300 / A400
Short regeneration
Immediate regeneration
Regeneration 5 seconds
Cancel regeneration
Skip phase
+ briefly
During a regeneration, always the remaining time of the complete
regeneration will be displayed.
Display of the remaining time of the phase with
LEVEL 3
C1
mod
A300 = 8 min
Backwash 1
A400 = 10 min
C2
C3
C4
C5
mod
A300 = 4 min
Fast Rinse 1
A400 = 6 min
C6/C
C8
A300 = 12 min
A400 = 16 min
10-20
Service Manual
SM-EN
1/03.11
Level 4
and for 5 seconds
In H0 : 5 seconds, reset for control - then Regeneration for
synchronization.
LEVEL 4
H0
Filter display
H1
H6
H17
Months in operation
Note
Documentation of the settings in the Settings report
As part of the Operational Qualification, the settings must be
documented in the Settings reports upon start-up.
Note
Reports for the items of the operational qualification listed below
are available as master copies in chapter 12:
Start-up
Setting
Maintenance
Service Manual
SM-EN
1/03.11
10-21
10.3 Specifications
10.3.1 Specifications / data sheet
Softener TYPE
A050
A100
A150
A300
A400
25 kg /
1 bag
25 kg /
1 bag
25 kg /
1 bag
25 kg /
1 bag
25 kg /
1 bag
50 L /
25 kg /
1 bag
100 L /
50 kg /
2 bags
150 L /
75 kg /
3 bags
200 L /
102 kg /
4 bags
250 L /
128 kg /
5 bags
105 liters
13 x 54
34 x 140 cm
170 liters
16x65"
41x162 cm
250 liters
18x65"
47 x 165 cm
250 liters
18x65"
47 x 165 cm
310 liters
21 x 60
55 x 172 cm
Freeboard +5 cm
55 cm
69 cm
70 cm
43 cm
40 cm
70 kg
100 kg
155 kg
190 kg
220 kg
Weight (filled)
170 kg
290 kg
400 kg
430 kg
540 kg
Riser tube
distance above upper edge of
tank
28
2025 mm
28
2025 mm
28
2025 mm
48.3
0-5 mm
48.3
0-5 mm
Rinse volume
Approx.
350 liters
Approx.
500 liters
Approx.
750 liters
Approx.
720 liters
Approx.
960 liters
Backwash flow*
45 L/min*
45 L/min*
45 L/min*
60 L/min*
60 L/min*
Backwash time
15/20/25 min
15/20/25 min
15/20/25 min
Individually
adjustable
Individually
adjustable
Kv
2.7 m/h
2.8 m/h
3.0 m/h
6.1 m/h
6.5 m/h
Minimum pressure
2 bar
2 bar
2 bar
2 bar
2 bar
Maximum pressure
6 bar
6 bar
6 bar
6.8 bar
6.8 bar
Ambient temperature
1-40C
1-40C
1-40C
1-45C
1-45C
Water temperature
1-40C
1-40C
1-40C
1-36C
1-36C
Voltage supply
230 V
60/50 Hz
230 V
60/50 Hz
230 V
60/50 Hz
230 V
60/50 Hz
230 V
60/50 Hz
12 V~
12 V~
12 V~
12 V~
12 V~
Filter design
10-22
Service Manual
SM-EN
1/03.11
Softener TYPE
A050
A100
A150
A300
A400
35x60x160
42x60x187
50x60x192
55x72x200
55x72x200
Floor space
W x D x H in mm
* the values indicated are real values and depend on the actual conditions and available pressure (values given in brackets
are theoretical limits for flow velocities of 15-20 m/h)
Service Manual
SM-EN
1/03.11
10-23
10-24
Service Manual
SM-EN
1/03.11
* at a yield of 70 %
A050
A100
A150
A300
A400
250
8 (minimum)
500
4 (minimum)
8 (minimum)
750
6 (minimum)
8 (minimum)
1000
4 (minimum)
6 (minimum)
1250
3 (minimum)
5 (minimum)
8 (minimum)
1500
4 (minimum)
6 (minimum)
8 (minimum)
1750
4 (minimum)
6 (minimum)
7 (minimum)
2000
3 (minimum)
5 (minimum)
6 (minimum)
2250
3 (minimum)
4 (minimum)
5 (minimum)
3 (minimum)
4 (minimum)
3000
4000
3 (minimum)
* at a yield of 70 %
A050
A100
A150
A300
A400
250
16 (minimum)
500
8 (minimum)
16 (minimum)
750
12 (minimum)
16 (minimum)
1000
8 (minimum)
12 (minimum)
1250
6 (minimum)
10 (minimum)
16 (minimum)
1500
8 (minimum)
12 (minimum)
16 (minimum)
1750
8 (minimum)
12 (minimum)
14 (minimum)
2000
6 (minimum)
10 (minimum)
12 (minimum)
Service Manual
SM-EN
1/03.11
10-25
* at a yield of 70 %
6 (minimum)
3000
8 (minimum)
10 (minimum)
6 (minimum)
8 (minimum)
4000
10-26
6 (minimum)
Service Manual
SM-EN
1/03.11
10.4 Maintenance
Note
The information given below is summarized for all water
pretreatment components in Chapter 14 (Appendix):
Important information on maintenance procedures
Accessories and supplies
Test report - maintenance
Maintenance intervals / overview for components of the water
pretreatment
Explanations for the test report
Service Manual
SM-EN
1/03.11
10-27
Problem
Possible cause
Action required
Valves contaminated
Valves leaking due to worn
spring
Water inlet pressure too low
Sieve for servo flows clogged
Poor or no automated
regeneration
Correct if necessary
10-28
Service Manual
SM-EN
1/03.11
Service Manual
SM-EN
1/03.11
10-29
10-30
Service Manual
SM-EN
1/03.11
Service Manual
SM-EN
1/03.11
11-1
11-2
Service Manual
SM-EN
1/03.11
DAILY REPORT
Water pretreatment
Site of installation
_____________________________________________________
Address
_____________________________________________________
ZIP code
_____________________________________________________
Place
_____________________________________________________
Responsible technician:
Phone:
GENERAL NOTES
Monitoring of the operating parameters is indispensable to ensure a safe and continuous operation of the reverse osmosis unit.
Meticulous recording of the data is also an absolute requirement for potential warranty claims. If values deviate, inform the
technical service to be able to take appropriate action before a malfunction occurs.
International
service
Local
service
Service Manual
SM-EN
1/03.11
11-3
Water pretreatment
Procedure
Alarm
limit
Weekday
Entries (operator)
Unit
Mon
Tue
Wed
Thu
Fri
Sat
Sun
__:__
__:__
__:__
__:__
__:__
__:__
__:__
______
______
______
______
______
______
______
---
<1 dH
(green)
Time
Coarse filter
Backwashed
Pressure
---
36
bar
Salt
refilled
Soft water sample
checked
< 0.1
mg/L
---
measured
(at the filter
output)
---
-----------
-----------
-----------
-----------
-----------
-----------
-----------
-----------
-----------
-----------
-----------
-----------
-----------
-----------
bar
bar
* The difference between the inlet and outlet pressure of the prefilter must not exceed 1 bar.
Pressure of 20 m prefilter with sand filter (optional)* installed
measured
(upstream)
---
measured
(downstream)
---
bar
-----------
-----------
-----------
-----------
-----------
-----------
----------bar
-----------
-----------
-----------
-----------
-----------
-----------
-----------
* The difference between the inlet and outlet pressure of the prefilter must not exceed 1 bar.
Initials
11-4
Service Manual
SM-EN
1/03.11
Service Manual
SM-EN
1/03.11
11-5
Customer:
Address:
Zip code / place:
Phone:
Fax:
Instructions
Coarse filter
Booster pump
Sand filter
Pipe disconnector
Softener
11-6
Service Manual
SM-EN
1/03.11
Comments:
Service Manual
SM-EN
1/03.11
11-7
Instructor:
Date, signature
Participant:
Date, signature
11-8
Service Manual
SM-EN
1/03.11
11.3 Maintenance
11.3.1 Maintenance intervals for water pretreatment components
Note
The manufacturer recommends to perform the following
maintenance procedures within the specified intervals.
Component
Check / maintenance
Backwashable prefilter
Solenoid valve
Monthly
Press the test key (black) on the single place leakage
socket while the water is running: The valve closes.
Pipe disconnector
Pressure reducer
Leakage sensor
Monthly
Test of position alarm: Turn the sensor upside down, red
LED illuminated.
Component
Check / maintenance
Annually
Check time
Component
Check / maintenance
Filter insert
Filtration unit
Service Manual
SM-EN
1/03.11
11-9
Particle filter
A / drain valve
Interrupt water supply.
Drain the water by means of the drain valve.
Use the filter wrench to unscrew the housing.
Replace the filter.
Screw on the housing with the new filter medium.
Turn the system on.
11.3.1.4 Softener
Component
Check / maintenance
Refill salt -
Daily, as required
Annually as required
Annually, as required
Check time
Annually, as required
11-10
Service Manual
SM-EN
1/03.11
Component
Check / maintenance
Annually, as required
Check time
Component
Check / maintenance
Interval
Monthly
631 916 1)
Monthly
Service Manual
SM-EN
1/03.11
11-11
11-12
Service Manual
SM-EN
1/03.11
Service Manual
SM-EN
1/03.11
12-1
START-UP REPORT
Water pretreatment
Technician's name:
Customer/customer no.:
Serial no.:
Inventory no.:
Operating hours:
Equipment code:
No.
Description
Reading
Measured value
(display)
1 Visual inspection and preparation
1.1
1.2
1.3
1.4
1.5
2 Default settings
2.1
2.2
2.3
Salt refilled
2.4
12-2
Service Manual
SM-EN
1/03.11
No.
Description
Reading
Measured value
(display)
2.5
2.6
2.7
2.8
2.9
2.10
________dH
Yes
No
3.2
New installation
Yes
No
3.3
Serial number
___________________
3.4
Material
___________________
3.5
4 Functional test
4.1
Solenoid valve:
Trigger the water leakage indicator - valve closes and
an alarm is generated.
4.2
Pipe disconnector:
Close the stop valve and start a backwash on the
coarse filter; the pipe disconnector disconnects.
4.3
Service Manual
SM-EN
1/03.11
12-3
No.
Description
Reading
Measured value
(display)
4.4
Sand filter:
Installed
Yes
No
OK
OK
Installed
Yes
No
OK
4.7
OK
Booster pump:
Installed
Yes
No
OK
SDI:___________________
SDI:___________________
SDI:___________________
Comments:
Date:
12-4
Signature:
Stamp:
Service Manual
SM-EN
1/03.11
Date:
Signature:
Service Manual
SM-EN
Stamp:
1/03.11
12-5
12-6
Service Manual
SM-EN
1/03.11
SETTINGS REPORT
COARSE FILTER TIMER
BOOSTER PUMP ASSEMBLY (CRN5-8)
Water pretreatment
Fresenius Medical Care
Technician's name:
Customer/customer no.:
Serial no.:
Inventory no.:
Operating hours:
Equipment code:
Component
Setting
Standard
Every day
04:00
1 bar
Float switch
---
Pmin
Operating pressure:_______bar
0-10 bar
P1max
_________ h. / min.
0-4 bar
P2max
Service Manual
SM-EN
1/03.11
0-2 bar
12-7
12-8
Service Manual
SM-EN
1/03.11
Filter
P1
Current time
P2
P3
Backwash time
P4
P5
P6
P7
- - --
P8
- - --
Capacity in m3
Level 2
P9
P10
P11
P12
P1319
- - --
Rinse days in P5
Regeneration
Change
...
Yes / No
...
Continue
Level 3
C1
mod
Backwash 1
C2
C3
C4
C5
mod
Fast Rinse 1
C6/C
C8
Service Manual
SM-EN
1/03.11
12-9
12-10
Service Manual
SM-EN
1/03.11
Filter
P1
Current time
P2
P3
Backwash time
P4
P5
P6
P7
- - --
P8
- - --
Capacity in m3
Level 2
P9
P10
P11
P12
P1319
- - --
Rinse days in P5
Regeneration
Change
...
Yes / No
...
Continue
Level 3
C1
mod
Backwash 1
C2
C3
C4
C5
mod
Fast Rinse 1
C6/C
C8
Service Manual
SM-EN
1/03.11
12-11
12-12
Service Manual
SM-EN
1/03.11
Lliters of resin
P1
Current time
P2
P3
Regeneration time
P4
P6
P7
P8
Level 2
P19
Pr
Pd
Level 3
C1
Backwash1
C2
C3
slow Rinse
C4
Repressurize / Standby
C5
Fast Rinse 1
C6/C
C8
Service Manual
SM-EN
1/03.11
12-13
12.2 Maintenance
12.2.1 Important information on maintenance procedures
Checks
Tester's qualification
Specifications
Precautions
ESD precautions
12-14
When repairing the system and when replacing spare parts, observe
the applicable ESD precautions.
Service Manual
SM-EN
1/03.11
Note
The required accessories and supplies are listed in the electronic
Spare Parts Catalog eSPC.
Note
The required replacement intervals are specified in the maintenance
report.
Service Manual
SM-EN
1/03.11
12-15
MAINTENANCE REPORT
Water pretreatment
Manufacturer:
Date:
Technician's name:
System:
Technician:
The following inspections must be carried out at no greater than 24 months' intervals.
MA
No.
Description
1.1
MA
1.2
Mechanical condition of
components.
MA
1.3
Damage or contamination.
Not detectable.
MA
1.4
Power cable.
No signs of damage.
Perform a backwash.
2 Water sensor
MA
2.1
Water sensor.
3 Pipe disconnector
MA
3.1
Functional test.
4.1
Backwash.
5 Booster pump
MA
5.1
Leakage.
No leakage.
MA
5.2
Running noise
No running noise.
12-16
Service Manual
SM-EN
1/03.11
MA
No.
Description
6 Sand filter
MA
6.1
MA
6.2
Time
MA
6.3
SDI test.
MA
6.4
7.1
MA
7.2
Time.
MA
7.3
Collect a sample:
MA
7.4
8 Softener
MA
8.1
Hardness: ______________________ dH
MA
8.2
MA
8.3
Hardness: 0 dH
MA
8.4
Brine valve.
MA
8.5
Brine tank
MA
8.6
in C4 - completely aspirated
8.7
Values OK?
MA
8.8
6 Particle filter
MA
9.1
Filter element.
MA
9.1
SDI test.
Service Manual
SM-EN
1/03.11
12-17
Yes
No
Comments:
Date:
12-18
Signature:
Stamp:
Service Manual
SM-EN
1/03.11
Service Manual
SM-EN
1/03.11
12-19
12-20
Service Manual
SM-EN
1/03.11
13 Definitions
13.1 Definitions and terms
Dialysate
13.2 Abbreviations
Fig.
Figure (diagram)
13.3 Symbols
See component documentation.
Service Manual
SM-EN
1/03.11
13-1
13-2
Service Manual
SM-EN
1/03.11
14 Appendix
Note
Reports required as master copies for use by operators and service
technicians are to be found in Chapter 11 (user relevant) and
Chapter 12 (service relevant).
Service Manual
SM-EN
1/03.11
14-1
14-2
Service Manual
SM-EN
1/03.11