Creating a Microgrid Energy Management System Using NI LabVIEW and

DAQ

"When formulating and processing matrix calculations, LabVIEW provides


programming tools to code power system applications more easily, which
saves programming time."

Bookmark and Share


Explore the NI Developer
Community

- Gooi Hoay Beng, (www.ntu.edu.sg)


Discover and collaborate on the latest
example code and tutorials with a
worldwide community of engineers and
scientists.

(
/cms/images/casestudies/mems01.jpg?size
)

(
http://decibel.ni.com/content/community/zone
)Check out the NI Community (
http://decibel.ni.com/content/community/zone
)

(
/cms/images/casestudies/mems02.jpg?size
)

Who is National Instruments?


National Instruments provides a
graphical system design platform for
test, control, and embedded design
applications that is transforming the
way engineers and scientists design,
prototype, and deploy systems.

(
/cms/images/casestudies/mems03.jpg?size
)

(
http://www.ni.com/company/standardize.htm
)Learn more about NI (
http://www.ni.com/company/standardize.htm
)

(
/cms/images/casestudies/mems04.jpg?size
)

(
/cms/images/casestudies/mems05.jpg?size
)

(
/cms/images/casestudies/mems06.jpg?size
)

The
Challenge:
(

Meeting
Singapores energy needs by exploring sustainable energy resources and enhancing the efficiency of the current supply
/cms/images/casestudies/mems07.jpg?size
system.
)

Read
the
Full
The Solution:
Using NI LabVIEW software and NI data acquisition (DAQ) hardware to develop a low-cost microgrid energy management system Case
(MEMS) that includes information and communications technology (ICT), smart meters, and advanced optimization applications to Study
manage distribution systems that serve as a platform for incorporating renewable energy resources.
Author(s):

1/7

www.ni.com

Author(s):
Cheah Peng Huat - (www.ntu.edu.sg)
Siow Lip Kian - (www.ntu.edu.sg)
Liang Hong Zhu - (www.ntu.edu.sg)
Vo Quoc Nguyen - (www.ntu.edu.sg)
Nguyen Dinh Duc - (www.ntu.edu.sg)
Gooi Hoay Beng - (www.ntu.edu.sg)
Students at the Laboratory for Clean Energy Research (LaCER) in the School of Electrical and Electronic Engineering (EEE) at
Nanyang Technical University (NTU) created a microgrid prototype. It consists of energy resources such as solar photovoltaics
(PVs), wind turbines, fuel cells, and battery banks. The entire microgrid is controlled by the Web-based MEMS server, which
controls and monitors different aspects of power management.
We developed software programs to manage information collected from the sensors and perform load control and generation
dispatch. Figure 1 shows the interface diagram between the database and different software modules. We used LabVIEW (
http://www.ni.com/labview/) software to develop modules for advanced sensing and communication, load forecasting, unit
commitment, state estimating, and optimal power flow.

Advanced Sensing and Communication System


In a microgrid, integrating and interfacing sensing and control devices is challenging because it involves different
communication protocols such as RS232 serial communication and RS422/485 modbus communication. To overcome this
challenge, we converted the information into one standard protocol Ethernet. We easily and economically made the
conversion by using a communication protocol converter.
Our main design tasks included sensing and communicating between the MEMS server and power sensors, as well as other
controlling devices such as circuit breakers, programmable AC sources, and programmable logic controllers (PLC). We installed
32 power sensors that support the Modbus protocol throughout the microgrid network for power monitoring measurements such
as voltage, current, active power, reactive power, and circuit breaker status. To deploy a cost-effective solution for
communicating between the MEMS server and all the power sensors, we divided the sensors into four groups with eight sensor
units per group. Each group eventually connects to an RS485-to-TCP/IP converter where the Modbus protocol is converted to
Modbus TCP running on the Ethernet LAN network. We issue a unique IP address to each converter and each group of power
sensors along with a respective ID.
The system extracts power measurements using the LabVIEW Datalogging and Supervisory Control (
http://www.ni.com/labview/labviewdsc/) (DSC) Module by entering the IP address, sensor ID, and register address of the
desired power sensor. Users do not need to define the exact Modbus messages to retrieve the information, which saves
valuable time. The system sends all power measurements to the respective global variables in LabVIEW where they are
displayed in the main GUI for monitoring (see Figure 2). Other applications also can easily use the measurements via global
variables. The PLC uses the same technique for controlling circuit breakers in the microgrid.
The microgrid testbed uses a programmable AC source to test the stand-alone microgrid. To communicate with the power
source, we used the TCP function block in LabVIEW. Users enter the power sources IP address without including tedious
programming code to monitor and control the power source.

Load Forecasting
The objective of load forecasting is to predict the total customer load 15 minutes in advance. It has a significant market impact
on efficiently operating, controlling, and planning microgrids. Accurate forecast values result in economic savings and enhance
system operation security.
The prediction method is based on the artificial neural network (ANN), which we developed using LabVIEW (see Figure 3). To
enhance the performance of the load forecasting algorithms, we added the following special features:
Data preprocessing to identify bad and irregular data so we can remove or adjust it before using it for training.
Early stopping to speed up convergence and prevent over-fitting the training data.
Abnormal days scheduling to identify days that have abnormal load profiles and to exclude them in the training so the load
model isnt corrupted. Users can update the abnormal days from the GUI.
Correlation and linear regression analysis to discover the linear relationship between input and target data by using a straight
line.
We use the NI USB-6215 (http://sine.ni.com/nips/cds/view/p/lang/en/nid/203483) DAQ device to collect historical load data from
the Wee Kim Wee School of Communication and Information building at NTU. We process and store the data in a database we
developed using LabVIEW. To collect the daily load data, we connect the analog inputs of the DAQ device to the distribution
grid in the building through a step-down voltage transformer, which is connected to additional current and voltage sensors to
obtain the voltage and current data, respectively.
We successfully integrated the load forecasting algorithm with the software modules in the MEMS unit. The implemented
forecasting system is reliable and accurate.

Unit Commitment
The unit commitment software module is an essential component of MEMS. Based on a forecasted demand profile, the software
module assists the microgrid operators in finding an optimized power generation schedule that minimizes the total operating
cost if the microgrid is isolated or maximizes the total benefit if the microgrid is connected to the main grid. Once the
optimization process is complete, the results, including the on/off status and the amount of kW dispatched from the generating
sources, are sent to the MEMS optimal power flow module for processing. Unit commitment is one of the most complex
optimization problems in power system management. By using the scripts we created using the LabVIEW MathScript RT
Module (http://sine.ni.com/nips/cds/view/p/lang/en/nid/207267), it takes the software only seconds to determine the optimized
solution of the formulated problem based on several constraints and hundreds of variables (see Figure 5).
The software module includes the following features:
By using the LabVIEW MathScript RT Module, it can solve a complex unit commitment problem within seconds.
With the GUI built in LabVIEW, users can easily run the unit commitment module with default/customized settings.
By using the real-time capturing function of LabVIEW, the software automatically executes at a user-defined start time.
Once the optimization completes, the results are automatically saved in a user-defined path on the server and sent to the
MEMS optimal power flow module.

State Estimation
State estimation is a MEMS real-time function that uses measurements, circuit breaker status, and voltage regulator tap
positions collected by Supervisory Control and Data Acquisition (SCADA) to verify and estimate bus voltages in power systems.
The estimated bus voltage magnitudes and voltage phase angles are considered reliable state values of the system and are
used as one of the inputs to the optimal power flow module. Its processed bus load values are used as inputs to the load
forecasting module.
The state estimation module has three subfunctions coded in the The MathWorks, Inc. MATLAB programming language based
on the LabVIEW platform:
1. Topology processor determines network configuration by converting a node-oriented network into a bus-oriented
network.
2. State estimation calculates bus voltage magnitudes and angles.

2/7

www.ni.com

2. State estimation calculates bus voltage magnitudes and angles.


3. Bad data detection and identification verifies that the raw measurements are good before using them in the state
estimation module.
When coding the state estimation module, it is challenging to ensure that it runs in any power network. Therefore, we used
script blocks to increase the flexibility when describing complex algorithms. Each subfunction is implemented using script blocks
in LabVIEW. The inputs and outputs (1D and 2D) transfer data between script blocks or to the front panel to display the results.
A feedback node is also used to detect and identify bad data.
When formulating and processing matrix calculations, LabVIEW provides programming tools to code power system applications
more easily, which saves programming time.
We successfully incorporated the state estimation function with other MEMS functions and the microgrid hardware setup at
LaCER, NTU (see Figure 6).

Optimal Power Flow


Optimal power flow is one of the MEMS online functions. The optimal power flow module finds the optimal settings of a given
power system network, such as total generation cost or system loss, while satisfying its power flow equations and equipment
operating limits, such as bus voltage constraints, branch flow limits, and generation source capacity limits. The input data for the
optimal power flow module includes network configuration and load information that are defined by the state estimate module.
As part of the output results, the optimal power flow module recommends values for:
Active/reactive power source outputs
Tap ratios of on-load tap-changing transformers
These parameters are sent to the circuit breaker CB controllers, inverter controllers, generator controllers, and load tap
controllers to keep the system running in a more economical and efficient mode.
We used quadratic programming to solve the optimal power flow problem. We coded this algorithm in MATLAB then integrated
it with LabVIEW through the MATLAB script function. We used LabVIEW to link optimal power flow to both state estimation and
SCADA to control certain microgrid components. Figure 7 shows how we used LabVIEW toolkits for the main optimal power flow
GUI for the microgrid in the LaCER, NTU.
The LF algorithm has been successfully integrated with UC of MEMS. The implemented forecasting system performs reliably
with a satisfactory accuracy.

Unit Commitment
The Unit Commitment (UC) software module acts as one of the essential components of MEMS. Based on a forecasted
demand profile, the software module is able to assist the microgrid operators to find an optimized power generation schedule
that minimizes the total operating cost while the microgrid is isolated or to maximize the total benefit while the microgrid is
connected to the main grid. Once the optimization process is complete, the results which include the on/off status and the
dispatch kW amount of the generating sources will be sent to the Optimal Power Flow (OPF) module of MEMS for processing.
UC is one of the most complex optimization problems in power system management. By using the MATLAB Script function of
LabVIEW, the software is able to determine within seconds the optimized solution of the formulated problem with several
constraints and hundreds of variables. The main GUI of UC is shown in Figure 5.
The software module has the following features:
By using MATLAB Script function of LabVIEW, a complex UC problem can be solved within seconds.
With the graphical interface built in LabVIEW, users can easily run the UC optimization with default/customized settings via
simple clicks.
By using the real-time capturing function of LabVIEW, the software can be executed automatically at a user-defined Auto Start
time.
Once the optimization completes, the results are automatically saved in a user-defined path of the server system and at the
same time they are sent to OPF of MEMS.

State Estimation
State Estimation is a MEMS real-time function which uses measurements, circuit breaker status and voltage regulator tap
positions collected by SCADA to verify and estimate bus voltages in power systems. The estimated bus voltage magnitudes and
voltage phase angles are considered as the trustable state values of the system and will be used as one of the inputs to OPF
and its processed bus load values as inputs to Load Forecasting.
State Estimator has 3 sub-functions coded in Matlab programming language based on the LabVIEW platform.
1. Topology Processor: It determines network configuration by converting a node-oriented network into a bus-oriented
network.
2. State Estimation: It calculates bus voltage magnitudes and angles
3. Bad Data Detection and Identification: It verifies that the raw measurements are good before using them in State
Estimator.
When coding State Estimator, it is a challenge to ensure that it runs in any power networks. Therefore using script blocks is a
way to increase the flexibility when describing complex algorithms. Each sub-function is implemented by using script blocks in
LabVIEW. The inputs and outputs (1D and 2D) are created to transfer data from the script blocks to others or to Front Panel for
displaying the results. A feedback node is also used as a filter of Bad Data Detection and Identification.
When formulation and processing are based on matrix calculations, LabVIEW provides programming tools to code power
system applications more easily so it can save time for programmers.
The SE function has been successfully demonstrated in corporation with other MEMS functions and the microgrid hardware
setup in the Laboratory for Clean Energy Research, NTU. The main GUI for State Estimator is shown in Figure 6.

Optimal Power Flow


Optimal Power Flow (OPF) is one of the MEMS online functions. The objective of OPF is to find the optimal settings of a given
power system network that optimize the system objective function such as total generation cost or system loss while satisfying
its power flow equations and equipment operating limits such as bus voltage constraints, branch flow limits and generation
source capacity limits. The input data for OPF includes network configuration and load information that are defined by SE and
as part of the output results, OPF will advise the recommended values for
1. Active/reactive power outputs of sources
2. Tap ratios of on-load tap-changing transformers
These parameters will be sent to CB controllers, inverter controllers, generator controllers and load tap controllers to keep the
system running in more economical and efficient mode.
The quadratic programming is used to solve the OPF problem. This algorithm is coded in MATLAB and then integrated into
LabVIEW through the MATLAB Script function. Based on the LabVIEW platform, OPF is linked to both SE and SCADA to take
control over certain microgrid components. By using LabVIEW toolboxes, the main OPF GUI for the Microgrid in the LaCER,
NTU is created as shown in Figure 7.
MATLAB is a registered trademark of MathWorks, Inc.

3/7

www.ni.com

Author Information:
Gooi Hoay Beng
(www.ntu.edu.sg)
School of Electrical and Electronic Engineering (S2-B7c-05) Nanyang Technological University
Singapore 639798
Singapore
Tel: +65-67905481
Fax: +65-67933318
ehbgooi@ntu.edu.sg (mailto:ehbgooi@ntu.edu.sg)

Figure 1: MEMS Data Interface Block Diagram

Figure 2: MEMS Main GUI developed using LabVIEW 2009 for monitoring all the power sensors installed.

4/7

www.ni.com

Figure 3: Artificial Neural Network training GUI developed using LabVIEW

Figure 4: Load Forecasting Main GUI developed using LabVIEW

5/7

www.ni.com

Figure 5: GUI for Unit Commitment developed using LabVIEW

Figure 6: Main GUI for State Estimation Function developed using LabVIEW

6/7

www.ni.com

Figure 7: Main GUI for Optimal Power Flow Function developed using LabVIEW
Legal
This case study (this "case study") was developed by a National Instruments ("NI") customer. THIS CASE STUDY IS PROVIDED "AS IS"
WITHOUT WARRANTY OF ANY KIND AND SUBJECT TO CERTAIN RESTRICTIONS AS MORE SPECIFICALLY SET FORTH IN
NI.COM'S TERMS OF USE (http://ni.com/legal/termsofuse/unitedstates/us/ (http://ni.com/legal/termsofuse/unitedstates/us/)).

PRODUCT

SUPPORT

COMPANY

Order status and history (http://www.ni.com/status/)

Submit a service request (


https://sine.ni.com/srm/app/myServiceRequests)

About National Instruments (http://www.ni.com/company

Order by part number (


http://sine.ni.com/apps/utf8/nios.store?action=purchase_form)

Events (http://www.ni.com/events/)
Manuals (http://www.ni.com/manuals/)
Careers (http://www.ni.com/careers/)

Activate a product (
http://sine.ni.com/myproducts/app/main.xhtml?lang=en)

Drivers (http://www.ni.com/downloads/drivers/)
Alliance Partners (http://www.ni.com/alliance/)

Order and payment information (http://www.ni.com/how-to-buy/)

MISSION
NI equips engineers and scientists with systems that accelerate productivity, innovation, and discovery.

(http://twitter.com/niglobal)
http://www.linkedin.com/company/3433?trk=tyah)

(http://www.facebook.com/NationalInstruments)
(http://www.ni.com/rss/)

(http://www.youtube.com/nationalinstrument

Contact Us (http://www.ni.com/contact-us/)

(//privacy.truste.com/privacy-seal/National-Instruments-Corporation/validation?rid=bc6daa8f-7051-4eea-b7b5-fb24dcd96d95)
Legal (http://www.ni.com/legal/) | National Instruments. All rights reserved. | Site map (http://www.ni.com/help/map.htm)

7/7

www.ni.com

You might also like