Relion Protection and Control

670 series 2.0 IEC


IEC 61850 Edition 1 Communication
Protocol Manual

Document ID: 1MRK 511 302-UEN


Issued: May 2014
Revision: Product version: 2.0

Copyright 2014 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license
and may be used or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the
OpenSSL Toolkit. (http://www.openssl.org/)
This product includes cryptographic software written/developed by: Eric Young
(eay@cryptsoft.com) and Tim Hudson (tjh@cryptsoft.com).

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.

Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standard EN 60255-26 for the EMC directive, and
with the product standards EN 60255-1 and EN 60255-27 for the low voltage
directive. The product is designed in accordance with the international standards of
the IEC 60255 series.

Table of contents

Table of contents
Section 1

Introduction.......................................................................9
This manual........................................................................................9
Intended audience..............................................................................9
Product documentation.....................................................................10
Product documentation set..........................................................10
Document revision history...........................................................11
Related documents......................................................................12
Document symbols and conventions................................................13
Symbols.......................................................................................13
Document conventions................................................................14
Functions included in 670 series IEDs........................................15
IEC61850 edition 1 / edition 2 mapping.......................................23

Section 2

Introduction to IEC 61850...............................................31


Related documentation to IEC 61850..........................................32

Section 3

Substation Configuration description Language


(SCL)..............................................................................35
The substation section......................................................................36
The communication section..............................................................36
The IED section................................................................................37
Tool concept.....................................................................................40
Engineering concept in IEC 61850-6................................................41

Section 4

Communication profile....................................................43

Section 5

Supported services.........................................................45

Section 6

Data sets and control blocks..........................................49


Data sets..........................................................................................49
Report control block (URCB/BRCB).................................................50
GOOSE Control Blocks (GoCB).......................................................53

Section 7

Logical node data model................................................57


Common data objects in each logical node......................................57
Logical nodes for automatic control..................................................59
Automatic tap changer control ATCC..........................................59
Automatic voltage control for tapchanger, parallel
control TR8ATCC ..................................................................68
Tap changer control and supervision, 6 binary inputs
TCMYLTC and TCLYLTC ....................................................82

670 series 2.0 IEC


Communication Protocol Manual

Table of contents

Logical nodes for control..................................................................85


Bay control CBAY........................................................................85
Bay control QCBAY................................................................85
Logical node for interlocking SCILO ...........................................87
Switch controller CSWI................................................................88
Switch controller SCSWI........................................................88
Bay reserve function QCRSV......................................................90
Logical nodes for conversion functions............................................92
Integer to Boolean converter FCVB.............................................92
Integer to Boolean 16 conversion with logic node
representation ITBGAPC........................................................92
Boolean to integer converter FCVI..............................................94
Boolean 16 to Integer conversion with logic node
representation BTIGAPC........................................................94
Logical nodes for protection functions..............................................94
Differential protection PDIF.........................................................94
Transformer differential protection, two winding
T2WPDIF ...............................................................................94
Transformer differential protection, three winding
T3WPDIF ...............................................................................98
Low impedance restricted earth fault protection
REFPDIF .............................................................................102
Generator differential protection GENPDIF .........................103
1Ph High impedance differential protection HZPDIF ...........106
Busbar differential protection, 2 zones, three phase
BCZTPDIF ...........................................................................107
Busbar differential protection, 2 zones, single phase
BCZSPDIF ...........................................................................108
Line differential protection, 3 CT sets, 23 line ends
L3CPDIF ..............................................................................108
Line differential protection, 6 CT sets, 35 line ends
L6CPDIF ..............................................................................111
Line differential protection 3 CT sets, with inzone
transformers, 23 line ends LT3CPDIF .................................114
Line differential protection 6 CT sets, with inzone
transformers, 35 line ends LT6CPDIF .................................117
Additional security logic for differential protection RGFC..........120
Additional security logic for differential protection
LDRGFC ..............................................................................120
Distance protection PDIS..........................................................122
Phase selection with load encroachment, quadrilateral
characteristic FDPSPDIS.....................................................122
Faulty phase identification with load encroachment
FMPSPDIS...........................................................................125
Loss of excitation LEXPDIS.................................................126
2

670 series 2.0 IEC


Communication Protocol Manual

Table of contents

Distance protection zone, quadrilateral characteristic


ZMQPDIS.............................................................................128
Distance protection zone, quadrilateral characteristic
ZMQAPDIS...........................................................................129
Distance measuring zone, quadrilateral characteristic
for series compensated lines ZMCPDIS..............................130
Distance measuring zone, quadrilateral characteristic
for series compensated lines ZMCAPDIS............................131
Full-scheme distance protection, mho characteristic
ZMHPDIS.............................................................................133
Fullscheme distance protection, quadrilateral for earth
faults ZMMPDIS...................................................................134
Fullscheme distance protection, quadrilateral for earth
faults ZMMAPDIS.................................................................135
Distance protection zone, quadrilateral characteristic,
separate settings ZMRAPDIS..............................................136
Distance protection zone, quadrilateral characteristic,
separate settings ZMRPDIS.................................................137
High speed distance protection ZMFPDIS...........................139
Phase selection, quadrilateral characteristic with
settable angle FRPSPDIS....................................................145
High speed distance protection for series compensated
lines ZMFCPDIS...................................................................148
Underimpedance protection for generators and
transformers ZGVPDIS........................................................154
Directional overpower PDOP.....................................................157
Directional over-power protection GOPPDOP.....................157
Directional underpower PDUP...................................................158
Rate of change of frequency PFRC...........................................160
Rate-of-change frequency protection SAPFRC ..................160
Frequency time accumulation protection QFVR........................161
Frequency time accumulation protection FTAQFVR............161
Instantaneous overcurrent PIOC...............................................162
Instantaneous phase overcurrent protection 3-phase
output PHPIOC ....................................................................162
Instantaneous residual overcurrent protection EFPIOC ......163
Local acceleration logic PLAL...................................................163
Local acceleration logic ZCLCPLAL.....................................163
Protection scheme PSCH..........................................................164
Scheme communication logic with delta based blocking
scheme signal transmit ZCPSCH.........................................164
Current reversal and WEI logic for distance protection 3phase ZCRWPSCH..............................................................166
Scheme communication logic for residual overcurrent
protection ECPSCH..............................................................167
670 series 2.0 IEC
Communication Protocol Manual

Table of contents

Current reversal and weak-end infeed logic for residual


overcurrent protection ECRWPSCH....................................169
Protection scheme [Line diff logic] LDLPSCH .....................170
Power swing logic PSLPSCH...............................................172
Phase segregated Scheme communication logic for
distance protection ZC1PPSCH...........................................173
Current reversal and weak-end infeed logic for phase
segregated communication ZC1WPSCH.............................175
Sensitive directional earth fault PSDE.......................................176
Sensitive directional residual overcurrent and power
protection SDEPSDE ..........................................................176
Switch onto fault logic PSOF.....................................................179
Automatic switch onto fault logic, voltage and current
based ZCVPSOF .................................................................179
Time over current PTOC...........................................................179
Four step residual overcurrent protection, (Zero
sequence or negative sequence directionality)
EF4PTOC ............................................................................179
Four step phase overcurrent protection 3-phase output
OC4PTOC ...........................................................................184
Stub protection STBPTOC ..................................................189
Broken conductor check BRCPTOC ...................................190
Negative-sequence time overcurrent protection for
machines NS2PTOC ...........................................................191
Three phase overcurrent LCP3PTOC..................................193
Negative sequence overcurrent protection LCNSPTOC......194
Zero sequence overcurrent protection LCZSPTOC.............195
Four step directional negative phase sequence
overcurrent protection NS4PTOC........................................196
Four step phase overcurrent protection OC4PTOC.............201
Four step single phase overcurrent protection
PH4SPTOC..........................................................................205
Four step residual overcurrent protection EF4PTOC...........209
Sudden change in current variation SCCVPTOC.................214
Overfrequency PTOF................................................................214
Overfrequency protection SAPTOF .....................................214
Overvoltage PTOV....................................................................215
Negative sequence overvoltage protection LCNSPTOV......215
Zero sequence overvoltage protection LCZSPTOV.............216
Two step overvoltage protection OV2PTOV .......................217
Two step residual overvoltage protection ROV2PTOV .......220
Voltage differential protection VDCPTOV............................222
Protection trip conditioning PTRC.............................................223
Carrier receive logic LCCRPTRC.........................................223
Tripping logic common 3-phase output SMPPTRC..............224
4

670 series 2.0 IEC


Communication Protocol Manual

Table of contents

Thermal overload PTTR............................................................225


Thermal overload protection, one time constant, Celsius
LCPTTR...............................................................................225
Thermal overload protection, one time constant,
Fahrenheit LFPTTR..............................................................227
Thermal overload protection, two time constants
TRPTTR ..............................................................................228
Rotor overload protection GRPTTR.....................................230
Stator overload protection GSPTTR.....................................232
Three phase undercurrent PTUC..............................................233
Three phase undercurrent LCP3PTUC................................233
Undervoltage PTUV...................................................................234
Two step undervoltage protection UV2PTUV ......................234
Loss of voltage check LOVPTUV ........................................237
Underfrequency PTUF...............................................................237
Underfrequency protection SAPTUF ...................................237
Volts per Hz PVPH....................................................................239
Overexcitation protection OEXPVPH ..................................239
Multipurpose analog protection GAPC......................................240
Accidental energizing protection for synchronous
generator AEGPVOC...........................................................240
Status of primary switching object for Busbar Protection
Zone Selection BDCGAPC ..................................................241
Capacitor bank protection CBPGAPC..................................242
Compensated over- and undervoltage protection
COUVGAPC.........................................................................249
General currrent and voltage protection CVGAPC...............251
Low active power and power factor protection
LAPPGAPC..........................................................................259
Mho Impedance supervision logic ZSMGAPC.....................261
Radial feeder protection PAPGAPC.....................................262
Out-of-step protection PPAM.....................................................264
Out-of-step protection OOSPPAM.......................................264
PoleSlip/Out-of-step protection PSPPPAM..........................265
Earth fault protection PHIZ........................................................267
ROTIPHIZ (64R)...................................................................267
100% Stator earth fault protection, 3rd harmonic based
STEFPHIZ............................................................................268
100% stator earth fault protection, injection based
STTIPHIZ.............................................................................271
Voltage-restrained time overcurrent PVOC...............................272
Voltage-restrained time overcurrent protection
VRPVOC..............................................................................272
System logical nodes......................................................................274
Generic security application component....................................274
670 series 2.0 IEC
Communication Protocol Manual

Table of contents

Generic security application component AGSAL.................274


Physical device information LPHD............................................276
Logical node zero LLNO............................................................276
Dual ethernet port link status PRPSTATUS..............................277
Logical nodes for protection related functions................................278
Breaker failure RBRF................................................................278
Breaker failure protection 3-phase activation and output
CCRBRF .............................................................................278
Breaker failure protection, single phase version
CCSRBRF............................................................................279
Differential supervision RDIF.....................................................280
Current circuit supervision CCSSPVC.................................280
Disturbance recorder RDRE......................................................281
Disturbance report DRPRDRE.............................................281
Fault locator RFLO....................................................................282
Fault locator LMBRFLO........................................................282
Secondary system supervision SPVC.......................................283
Fuse failure supervision SDDRFUF.....................................283
Fuse failure supervision based on voltage difference
VDSPVC...............................................................................284
Pole discordance protection RPLD ...........................................285
Pole discordance protection CCPDSC.................................285
Power swing detection RPSB....................................................286
Power swing detection ZMRPSB ........................................286
Autoreclosing RREC..................................................................287
Autorecloser for 1 phase, 2 phase and/or 3 phase
operation SMBRREC ..........................................................287
Synchronising RSYN.................................................................292
Synchrocheck, energizing check, and synchronizing
SESRSYN............................................................................292
Logical nodes for generic references.............................................297
Generic process I/O GGIO........................................................297
Logic rotating switch for function selection and LHMI
presentation SLGAPC..........................................................297
Selector mini switch VSGAPC..............................................299
Generic communication function for Double Point
indication DPGAPC..............................................................301
Single point generic control 8 signals SPC8GAPC..............301
Event counter with limit supervision L4UFCNT....................304
IEC61850 generic communication I/O functions
SPGGIO...............................................................................306
IEC61850 generic communication I/O functions 16
inputs SP16GGIO.................................................................307
Generic communication function for Measured Value
MVGAPC..............................................................................308
6

670 series 2.0 IEC


Communication Protocol Manual

Table of contents

Pulse-counter logic PCFCNT...............................................310


Trip matrix logic TMAGAPC.................................................311
Elapsed time integrator with limit transgression and
overflow supervision TEIGGIO.............................................312
Logical nodes for metering and measurement...............................313
Metering MMTR.........................................................................313
Function for energy calculation and demand handling
ETPMMTR............................................................................313
Non phase related measurement MMXN..................................317
Measurements CVMMXN.....................................................317
Measurement MMXU.................................................................321
Phase current measurement CMMXU.................................321
Phase-phase voltage measurement VMMXU......................323
Phase-neutral voltage measurement VNMMXU..................324
Sequence and imbalance MSQI................................................326
Current sequence component measurement CMSQI..........326
Voltage sequence measurement VMSQI.............................328
Logical nodes for sensors and monitoring......................................330
Circuit breaker monitoring SCBR..............................................330
Breaker monitoring SSCBR..................................................330
Insulation medium supervision (gas) SIMG...............................335
Gas medium supervision SSIMG.........................................335
Insulation medium supervision (liquid) SIML.............................336
Liquid medium supervision SSIML.......................................336
Logical nodes for switchgear..........................................................338
Circuit breaker XCBR................................................................338
Circuit breaker SXCBR.........................................................338
Switch XSWI..............................................................................340
Circuit switch SXSWI............................................................340
Logical nodes for power transformers............................................343
Tap changer YLTC....................................................................343
Tap changer control and supervision, 6 binary inputs
TCMYLTC and TCLYLTC ..................................................343
Tap changer control and supervision, 32 binary inputs
TCLYLTC.............................................................................346

Section 8

GOOSE receive blocks................................................349


Interlock receive - INTLKRCV........................................................349
Horizontal communication via GOOSE for interlocking
GOOSEINTLKRCV....................................................................349
Binary Receive - BINRCV ..............................................................350
Goose binary receive GOOSEBINRCV.....................................350
VCTR Receive - VCTRRCV...........................................................351

670 series 2.0 IEC


Communication Protocol Manual

Table of contents

Voltage control receiving block for GOOSE


GOOSEVCTRRCV....................................................................351
Double point Receive (DP) - DPRCV ............................................352
GOOSE function block to receive a double point value
GOOSEDPRCV.........................................................................352
Integer Receive - INTRCV..............................................................353
GOOSE function block to receive an integer value
GOOSEINTRCV........................................................................353
Measured Value Receive - MVRCV...............................................353
GOOSE function block to receive a measurand value
GOOSEMVRCV........................................................................353
Single Point Receive (SP) - SPRCV...............................................353
GOOSE function block to receive a single point value
GOOSESPRCV.........................................................................353

Section 9

Glossary.......................................................................355
Glossary.........................................................................................355

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

Section 1

Introduction

1.1

This manual
The communication protocol manual describes the communication protocols
supported by the IED. The manual concentrates on the vendor-specific
implementations.

1.2

Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering for communication setup in a
substation from an IED perspective.
The system engineer or system integrator must have a basic knowledge of
communication in protection and control systems and thorough knowledge of the
specific communication protocol.

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

Decommissioning
Deinstalling & disposal

Maintenance

Operation

Product documentation set

Commissioning

1.3.1

Engineering

Product documentation

Planning & purchase

1.3

Installing

1MRK 511 302-UEN -

Engineering manual
Installation manual
Commissioning manual
Operation manual
Application manual
Technical manual
Communication
protocol manual
Cyber security
deployment guideline
IEC07000220-4-en.vsd
IEC07000220 V4 EN

Figure 1:

The intended use of manuals throughout the product lifecycle

The engineering manual contains instructions on how to engineer the IEDs using
the various tools available within the PCM600 software. The manual provides
instructions on how to set up a PCM600 project and insert IEDs to the project
structure. The manual also recommends a sequence for the engineering of
protection and control functions, LHMI functions as well as communication
engineering for IEC 60870-5-103, IEC 61850 and DNP3.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in the chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED.
The manual can also be used by system engineers and maintenance personnel for
assistance during the testing phase. The manual provides procedures for the
checking of external circuitry and energizing the IED, parameter setting and

10

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

configuration as well as verifying settings by secondary injection. The manual


describes the process of testing an IED in a substation which is not in service. The
chapters are organized in the chronological order in which the IED should be
commissioned. The relevant procedures may be followed also during the service
and maintenance activities.
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for the monitoring,
controlling and setting of the IED. The manual also describes how to identify
disturbances and how to view calculated and measured power grid data to
determine the cause of a fault.
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also provide assistance
for calculating settings.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data, sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
The communication protocol manual describes the communication protocols
supported by the IED. The manual concentrates on the vendor-specific
implementations.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
The cyber security deployment guideline describes the process for handling cyber
security when communicating with the IED. Certification, Authorization with role
based access control, and product engineering for cyber security related events are
described and sorted by function. The guideline can be used as a technical
reference during the engineering phase, installation and commissioning phase, and
during normal service.

1.3.2

Document revision history


Document revision/date
-/May 2014

670 series 2.0 IEC


Communication Protocol Manual

History
First release

11

Section 1
Introduction
1.3.3

1MRK 511 302-UEN -

Related documents
Documents related to REB670

1MRK 505 302-UEN

Commissioning manual

1MRK 505 304-UEN

Product guide

1MRK 505 305-BEN

Technical manual

1MRK 505 303-UEN

Type test certificate

1MRK 505 305-TEN

Documents related to REC670

Identify number

Application manual

1MRK 511 310-UEN

Commissioning manual

1MRK 511 312-UEN

Product guide

1MRK 511 313-BEN

Technical manual

1MRK 511 311-UEN

Type test certificate

1MRK 511 313-TEN

Documents related to RED670

Identify number

Application manual

1MRK 505 307-UEN

Commissioning manual

1MRK 505 309-UEN

Product guide

1MRK 505 310-BEN

Technical manual

1MRK 505 308-UEN

Type test certificate

1MRK 505 310-TEN

Documents related to REG670

Identify number

Application manual

1MRK 502 051-UEN

Commissioning manual

1MRK 502 053-UEN

Product guide

1MRK 502 054-BEN

Technical manual

1MRK 502 052-UEN

Type test certificate

1MRK 502 054-TEN

Documents related to REL670

12

Identify number

Application manual

Identify number

Application manual

1MRK 506 338-UEN

Commissioning manual

1MRK 506 340-UEN

Product guide

1MRK 506 341-BEN

Technical manual

1MRK 506 339-UEN

Type test certificate

1MRK 506 341-TEN

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

Documents related to RET670

Identify number

Application manual

1MRK 504 138-UEN

Commissioning manual

1MRK 504 140-UEN

Product guide

1MRK 504 141-BEN

Technical manual

1MRK 504 139-UEN

Type test certificate

1MRK 504 141-TEN

670 series manuals

Identify number

Operation manual

1MRK 500 118-UEN

Engineering manual

1MRK 511 308-UEN

Installation manual

1MRK 514 019-UEN

Communication protocol manual, IEC


60870-5-103

1MRK 511 304-UEN

Communication protocol manual, IEC 61850


Edition 1

1MRK 511 302-UEN

Communication protocol manual, IEC 61850


Edition 2

1MRK 511 303-UEN

Communication protocol manual, LON

1MRK 511 305-UEN

Communication protocol manual, SPA

1MRK 511 306-UEN

Accessories guide

1MRK 514 012-BEN

Cyber security deployment guideline

1MRK 511 309-UEN

Connection and Installation components

1MRK 513 003-BEN

Test system, COMBITEST

1MRK 512 001-BEN

1.4

Document symbols and conventions

1.4.1

Symbols
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.

The information icon alerts the reader of important facts and


conditions.

The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.

670 series 2.0 IEC


Communication Protocol Manual

13

Section 1
Introduction

1MRK 511 302-UEN -

Although warning hazards are related to personal injury, it is necessary to


understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. It is important that the user fully complies with all warning and
cautionary notices.

1.4.2

Document conventions

Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
Push button navigation in the LHMI menu structure is presented by using the
push button icons.
and
.
For example, to navigate between the options, use
HMI menu paths are presented in bold.
For example, select Main menu/Settings.
LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and
press
.
Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
Each function block symbol shows the available input/output signal.

Logic diagrams describe the signal logic inside the function block and are
bordered by dashed lines.

14

the character ^ in front of an input/output signal name indicates that the


signal name may be customized using the PCM600 software.
the character * after an input/output signal name indicates that the signal
must be connected to another function block in the application
configuration to achieve a valid application configuration.

Signals in frames with a shaded area on their right hand side represent
setting parameter signals that are only settable via the PST or LHMI.
If an internal signal path cannot be drawn with a continuous line, the
suffix -int is added to the signal name to indicate where the signal starts
and continues.
Signal paths that extend beyond the logic diagram and continue in
another diagram have the suffix -cont.

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

1.4.3
Table 1:

Functions included in 670 series IEDs


Main protection functions

IEC 61850 or function


name

ANSI

Description

Differential protection
BBP3PH4B

87B

Busbar differential protection, 2 zones, three phase/4 bays


Package including functions BUTPTRC_B1-BUTPTRC_B4, BCZTPDIF, BZNTPDIF_A,
BZNTPDIF_B, BZITGGIO, BUTSM4

BBP3PH8B

87B

Busbar differential protection, 2 zones, three phase/8 bays


Package including functions BUTPTRC_B1-BUTPTRC_B8, BCZTPDIF, BZNTPDIF_A,
BZNTPDIF_B, BZITGGIO, BUTSM8

BBP1PH12B

87B

Busbar differential protection, 2 zones, single phase/12 bays


Package including functions BUSPTRC_B1-BUSPTRC_B12, BCZSPDIF, BZNSPDIF_A,
BZNSPDIF_B, BZISGGIO, BUSSM12

BBP1PH24B

87B

Busbar differential protection, 2 zones, single phase/24 bays


Package including functions BUSPTRC_B1-BUSPTRC_B24, BCZSPDIF, BZNSPDIF_A,
BZNSPDIF_B, BZISGGIO, BUSSM24

BDCGAPC

87B

Status of primary switching object for busbar protection zone selection

T2WPDIF

87T

Transformer differential protection, two winding

T3WPDIF

87T

Transformer differential protection, three winding

HZPDIF

87

1Ph High impedance differential protection

GENPDIF

87G

Generator differential protection

REFPDIF

87N

Restricted earth fault protection, low impedance

L3CPDIF

87L

Line differential protection, 3 CT sets, 23 line ends

L6CPDIF

87L

Line differential protection, 6 CT sets, 35 line ends

LT3CPDIF

87LT

Line differential protection 3 CT sets, with inzone transformers, 23 line ends

LT6CPDIF

87LT

Line differential protection 6 CT sets, with inzone transformers, 35 line ends

LDLPSCH

87L

Line differential coordination function

LDRGFC

11REL

Additional security logic for differential protection

ZMQAPDIS, ZMQPDIS

21

Distance protection zone, quadrilateral characteristic

ZDRDIR

21D

Directional impedance quadrilateral

ZMCPDIS, ZMCAPDIS

21

Distance measuring zone, quadrilateral characteristic for series compensated lines

ZDSRDIR

21D

Directional impedance quadrilateral, including series compensation

FDPSPDIS

21

Phase selection, quadrilateral characteristic with fixed angle

ZMHPDIS

21

Full-scheme distance protection, mho characteristic

ZMMPDIS, ZMMAPDIS

21

Fullscheme distance protection, quadrilateral for earth faults

ZDMRDIR

21D

Directional impedance element for mho characteristic

Impedance protection

ZDARDIR

Additional distance protection directional function for earth faults

ZSMGAPC

Mho Impedance supervision logic

FMPSPDIS

21

Faulty phase identification with load enchroachment

ZMRPDIS, ZMRAPDIS

21

Distance protection zone, quadrilateral characteristic, separate settings

FRPSPDIS

21

Phase selection, quadrilateral characteristic with settable angle

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

15

Section 1
Introduction
IEC 61850 or function
name

1MRK 511 302-UEN -

ANSI

Description

ZMFPDIS

21

High speed distance protection

ZMFCPDIS

21

High speed distance protection for series compensated lines

ZMCAPDIS

Additional distance measuring zone, quadrilateral characteristic

ZMRPSB

68

PSLPSCH

Power swing detection


Power swing logic

PSPPPAM

78

Pole slip/out-of-step protection

OOSPPAM

78

Out-of-step protection

ZCVPSOF

Automatic switch onto fault logic, voltage and current based

LEXPDIS

40

PPLPHIZ

Loss of excitation
Phase preference logic

ROTIPHIZ

64R

Sensitive rotor earth fault protection, injection based

STTIPHIZ

64S

100% stator earth fault protection, injection based

ZGVPDIS

21

Underimpedance protection for generators and transformers

Table 2:

Backup protection functions

IEC 61850 or function


name

ANSI

Description

Current protection
PHPIOC

50

Instantaneous phase overcurrent protection

OC4PTOC

51_67

Four step phase overcurrent protection

PH4SPTOC

51

Four step single phase overcurrent protection

EFPIOC

50N

Instantaneous residual overcurrent protection

EF4PTOC

51N_67
N

Four step residual overcurrent protection

NS4PTOC

46I2

Four step directional negative phase sequence overcurrent protection

SDEPSDE

67N

Sensitive directional residual over current and power protection

LCPTTR

26

Thermal overload protection, one time constant, Celsius

LFPTTR

26

Thermal overload protection, one time constant, Fahrenheit

TRPTTR

49

Thermal overload protection, two time constants

CCRBRF

50BF

Breaker failure protection

CCSRBRF

50BF

Breaker failure protection, single phase version

STBPTOC

50STB

Stub protection

CCPDSC

52PD

Pole discordance protection

GUPPDUP

37

Directional underpower protection

GOPPDOP

32

Directional overpower protection

BRCPTOC

46

Broken conductor check

CBPGAPC

Capacitor bank protection

NS2PTOC

46I2

Negative sequence time overcurrent protection for machines

AEGPVOC

50AE

Accidental energizing protection for synchronous generator

Table continues on next page


16

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

IEC 61850 or function


name

ANSI

Description

VRPVOC

51V

Voltage restrained overcurrent protection

GSPTTR

49S

Stator overload protection

GRPTTR

49R

Rotor overload protection

UV2PTUV

27

Two step undervoltage protection

OV2PTOV

59

Two step overvoltage protection

ROV2PTOV

59N

Two step residual overvoltage protection

OEXPVPH

24

Overexcitation protection

VDCPTOV

60

Voltage differential protection

STEFPHIZ

59THD

100% Stator earth fault protection, 3rd harmonic based

LOVPTUV

27

Loss of voltage check

PAPGAPC

27

Radial feeder protection

SAPTUF

81

Underfrequency protection

SAPTOF

81

Overfrequency protection

SAPFRC

81

Rate-of-change frequency protection

FTAQFVR

81A

Frequency time accumulation protection

Voltage protection

Frequency protection

Multipurpose protection
CVGAPC

Table 3:

General current and voltage protection

Control and monitoring functions

IEC 61850 or function


name

ANSI

Description

Control
SESRSYN

25

Synchrocheck, energizing check, and synchronizing

SMBRREC

79

Autorecloser

TR1ATCC

90

Automatic voltage control for tap changer, single control

TR8ATCC

90

Automatic voltage control for tap changer, parallel control

TCMYLTC

84

Tap changer control and supervision, 6 binary inputs

TCLYLTC

84

Tap changer control and supervision, 32 binary inputs

SLGAPC

Logic Rotating Switch for function selection and LHMI presentation

VSGAPC

Selector mini switch

DPGAPC

Generic communication function for Double Point indication

SPC8GAPC

Single Point Generic Control 8 signals

AUTOBITS

AutomationBits, command function for DNP3.0

SINGLECMD

Single command, 16 signals


Command function block for LON and SPA

VCTRSEND

Horizontal communication via GOOSE for VCTR

GOOSEVCTRRCV

Horizontal communication via GOOSE for VCTR

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

17

Section 1
Introduction
IEC 61850 or function
name

1MRK 511 302-UEN -

ANSI

Description

I103CMD

Function commands for IEC60870-5-103

I103GENCMD

Function commands generic for IEC60870-5-103

I103POSCMD

IED commands with position and select for IEC60870-5-103

I103IEDCMD

IED commands for IEC60870-5-103

I103USRCMD

Function commands user defined for IEC60870-5-103

Apparatus control and interlocking


SCILO

Logical node for interlocking

BB_ES

Interlocking for busbar earthing switch

A1A2_BS

Interlocking for bus-section breaker

A1A2_DC

Interlocking for bus-section disconnector

ABC_BC

Interlocking for bus-coupler bay

BH_CONN

Interlocking for 1 1/2 breaker diameter

BH_LINE_A

Interlocking for 1 1/2 breaker diameter

BH_LINE_B

Interlocking for 1 1/2 breaker diameter

DB_BUS_A

Interlocking for double CB bay

DB_BUS_B

Interlocking for double CB bay

DB_LINE

Interlocking for double CB bay

ABC_LINE

Interlocking for line bay

AB_TRAFO

Interlocking for transformer bay

SCSWI

Switch controller

SXCBR

Circuit breaker

SXSWI

Switch controller

RESIN1

Reservation input 1

RESIN2

Reservation input 2

POS_EVAL

Evaluation of position indication

QCRSV

Bay reservation

QCBAY

Apparatus control
Function for handling the status of Local/Remote switch

LOCREM

Handling of LRswitch positions

LOCREMCTRL

LHMI control of PSTO


Function for handling Internal Local/Remote switch

Secondary system supervision


CCSSPVC

87

FUFSPVC
VDSPVC

Current circuit supervision


Fuse failure supervision

60

Fuse failure supervision based on voltage difference

94

Tripping logic

Logic
SMPPTRC
TMAGAPC

Trip matrix logic

ALMCALH

Logic for group alarm

WRNCALH

Logic for group warning

Table continues on next page


18

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

IEC 61850 or function


name

ANSI

Description

INDCALH

Logic for group indication

AND

Configurable logic blocks, AND

OR

Configurable logic blocks, OR

INV

Configurable logic blocks, inverter

PULSETIMER

Configurable logic blocks, PULSETIMER

GATE

Configurable logic blocks, controllable gate

TIMERSET

Configurable logic blocks, timer

XOR

Configurable logic blocks, exclusive OR

LLD

Configurable logic blocks, LLD

SRMEMORY

Configurable logic blocks, set-reset memory

RSMEMORY

Configurable logic blocks, reset-set memory

ANDQT

Configurable logic blocks Q/T, ANDQT

ORQT

Configurable logic blocks Q/T, ORQT

INVERTERQT

Configurable logic blocks Q/T, INVERTERQT

XORQT

Configurable logic blocks Q/T, XORQT

SRMEMORYQT

Configurable logic Q/T, set-reset with memory

RSMEMORYQT

Configurable logic Q/T, reset-set with memory

TIMERSETQT

Configurable logic Q/T, settable timer

PULSETIMERQT

Configurable logic Q/T, pulse timer

INVALIDQT

Configurable logic Q/T, INVALIDQT

INDCOMBSPQT

Configurable logic Q/T, single-indication signal combining

INDEXTSPQT

Configurable logic Q/T, single-indication signal extractor

FXDSIGN

Fixed signal function block

B16I

Boolean 16 to Integer conversion

BTIGAPC

Boolean 16 to Integer conversion with Logic Node representation

IB16

Integer to Boolean 16 conversion

ITBGAPC

Integer to Boolean 16 conversion with Logic Node representation

TIGAPC

Delay on timer with input signal integration

TEIGAPC

Elapsed time integrator with limit transgression and overflow supervision

Monitoring
CVMMXN, CMMXU,
VMMXU, CMSQI
VMSQI, VNMMXU

Measurements

AISVBAS

Function block for service value presentation of secondary analog inputs

SSIMG

63

Gas medium supervision

SSIML

71

Liquid medium supervision

SSCBR

Circuit breaker condition monitoring

EVENT

Event function
Function for event reporting for LON and SPA

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

19

Section 1
Introduction
IEC 61850 or function
name

1MRK 511 302-UEN -

ANSI

Description

DRPRDRE, A1RADRA4RADR, B1RBDRB6RBDR

Disturbance report

SPGAPC

Generic communication function for Single Point indication

SP16GAPC

Generic communication function for Single Point indication 16 inputs

MVGAPC

Generic communication function for Measured Value

BINSTATREP

Logical signal status report

RANGE_XP

Measured value expander block

LMBRFLO

Fault locator

I103MEAS

Measurands for IEC60870-5-103

I103MEASUSR

Measurands user defined signals for IEC60870-5-103

I103AR

Function status auto-recloser for IEC60870-5-103

I103EF

Function status earth-fault for IEC60870-5-103

I103FLTPROT

Function status fault protection for IEC60870-5-103

I103IED

IED status for IEC60870-5-103

I103SUPERV

Supervison status for IEC60870-5-103

I103USRDEF

Status for user defiend signals for IEC60870-5-103

L4UFCNT

Event counter with limit supervision

Metering
PCFCNT

Pulse-counter logic

ETPMMTR

Function for energy calculation and demand handling

System protection and control


SMAIHPAC

Table 4:

Multipurpose filter

Station communication functions

IEC 61850 or function


name

ANSI

Description

Station communication
SPA

SPA communication protocol

ADE

LON communciation protocol

PROTOCOL

Operation selection between SPA and IEC60870-5-103 for SLM

CHSERRS485

DNP3.0 for TCP/IP and EIA-485 communication protocol

DNPFREC

DNP3.0 fault records for TCP/IP and EIA-485 communication protocol

IEC61850-8-1

Parameter setting function for IEC61850

GOOSEINTLKRCV

Horizontal communication via GOOSE for interlocking

GOOSEBINRCV

Goose binary receive

GOOSEDPRCV

GOOSE function block to receive a double point value

GOOSEINTRCV

GOOSE function block to receive an integer value

GOOSEMVRCV

GOOSE function block to receive a measurand value

Table continues on next page

20

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

IEC 61850 or function


name

ANSI

Description

GOOSESPRCV

GOOSE function block to receive a single point value

GOOSEVCTRCONF

GOOSE VCTR configuration for send and receive

VCTRSEND

Horizontal communication via GOOSE for VCTR

GOOSEVCTRRCV

Horizontal communication via GOOSE for VCTR

MULTICMDRCV,
MULTICMDSND

Multiple command and transmit

FRONT, LANABI,
LANAB, LANCDI,
LANCD

Ethernet configuration of links

MU1_4I_4U MU2_4I_4U
MU3_4I_4U MU4_4I_4U
MU5_4I_4U MU6_4I_4U

Process bus communication IEC61850-9-2

PRP

Duo driver configuration

Scheme communication
ZCPSCH

85

Scheme communication logic for distance or overcurrent protection

ZC1PPSCH

85

Phase segregated Scheme communication logic for distance protection

ZCRWPSCH

85

Current reversal and weak-end infeed logic for distance protection

ZC1WPSCH

85

Current reversal and weak-end infeed logic for phase segregated communication

ZCLCPSCH

Local acceleration logic

ECPSCH

85

Scheme communication logic for residual overcurrent protection

ECRWPSCH

85

Current reversal and weak-end infeed logic for residual overcurrent protection

LAPPGAPC

37_55

Low active power and power factor protection

COUVGAPC

59_27

Compensated over- and undervoltage protection

SCCVPTOC

51

Sudden change in current variation

LCCRPTRC

94

Carrier receive logic

LCNSPTOV

47

Negative sequence overvoltage protection

LCZSPTOV

59N

Zero sequence overvoltage protection

LCNSPTOC

46

Negative sequence overcurrent protection

LCZSPTOC

51N

Zero sequence overcurrent protection

LCP3PTOC

51

Three phase overcurrent

LCP3PTUC

37

Three phase undercurrent

Direct transfer trip

Table 5:

Basic IED functions

IEC 61850 or function


name

Description

INTERRSIG

Self supervision with internal event list

SELFSUPEVLST

Self supervision with internal event list

TIMESYNCHGEN

Time synchronization module

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

21

Section 1
Introduction
IEC 61850 or function
name

1MRK 511 302-UEN -

Description

SYNCHBIN,
SYNCHCAN,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS,
SYNCHSNTP,
SYNCHSPA,
SYNCHCMPPS

Time synchronization

TIMEZONE

Time synchronization

DSTBEGIN,
DSTENABLE, DSTEND

GPS time synchronization module

IRIG-B

Time synchronization

SETGRPS

Number of setting groups

ACTVGRP

Parameter setting groups

TESTMODE

Test mode functionality

CHNGLCK

Change lock function

SMBI

Signal matrix for binary inputs

SMBO

Signal matrix for binary outputs

SMMI

Signal matrix for mA inputs

SMAI1 - SMAI20

Signal matrix for analog inputs

3PHSUM

Summation block 3 phase

ATHSTAT

Authority status

ATHCHCK

Authority check

AUTHMAN

Authority management

FTPACCS

FTP access with password

SPACOMMMAP

SPA communication mapping

SPATD

Date and time via SPA protocol

DOSFRNT

Denial of service, frame rate control for front port

DOSLANAB

Denial of service, frame rate control for OEM port AB

DOSLANCD

Denial of service, frame rate control for OEM port CD

DOSSCKT

Denial of service, socket flow control

GBASVAL

Global base values for settings

PRIMVAL

Primary system values

ALTMS

Time master supervision

ALTIM

Time management

ALTRK

Service tracking

ACTIVLOG

Activity logging parameters

FSTACCS

Field service tool access via SPA protocol over ethernet communication

PCMACCS

IED Configuration Protocol

SECALARM

Component for mapping security events on protocols such as DNP3 and IEC103

DNPGEN

DNP3.0 communication general protocol

Table continues on next page

22

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

IEC 61850 or function


name

Description

DNPGENTCP

DNP3.0 communication general TCP protocol

CHSEROPT

DNP3.0 for TCP/IP and EIA-485 communication protocol

MSTSER

DNP3.0 for serial communication protocol

OPTICAL103

IEC60870-5-103 Optical serial communication

RS485103

IEC60870-5-103 serial communication for RS485

IEC61850-8-1

Parameter setting function for IEC61850

HORZCOMM

Network variables via LON

LONSPA

SPA communication protocol

LEDGEN

General LED indication part for LHMI

1.4.4

IEC61850 edition 1 / edition 2 mapping


Table 6:

IEC61850 edition 1 / edition 2 mapping

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

AEGPVOC

AEGGAPC

AEGPVOC

AGSAL

SECLLN0
AGSAL

AGSAL

ALMCALH

ALMCALH

ALTIM

ALTIM

ALTMS

ALTMS

ALTRK

ALTRK

BCZSPDIF

BCZSPDIF

BCZSPDIF

BCZTPDIF

BCZTPDIF

BCZTPDIF

BDCGAPC

SWSGGIO

BDCGAPC

BRCPTOC

BRCPTOC

BRCPTOC

BTIGAPC

B16IFCVI

BTIGAPC

BUSPTRC_B1

BBSPLLN0
BUSPTRC

LLN0
BUSPTRC

BUSPTRC_B2

BUSPTRC

BUSPTRC

BUSPTRC_B3

BUSPTRC

BUSPTRC

BUSPTRC_B4

BUSPTRC

BUSPTRC

BUSPTRC_B5

BUSPTRC

BUSPTRC

BUSPTRC_B6

BUSPTRC

BUSPTRC

BUSPTRC_B7

BUSPTRC

BUSPTRC

BUSPTRC_B8

BUSPTRC

BUSPTRC

BUSPTRC_B9

BUSPTRC

BUSPTRC

BUSPTRC_B10

BUSPTRC

BUSPTRC

BUSPTRC_B11

BUSPTRC

BUSPTRC

BUSPTRC_B12

BUSPTRC

BUSPTRC

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

23

Section 1
Introduction

1MRK 511 302-UEN -

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

BUSPTRC_B13

BUSPTRC

BUSPTRC

BUSPTRC_B14

BUSPTRC

BUSPTRC

BUSPTRC_B15

BUSPTRC

BUSPTRC

BUSPTRC_B16

BUSPTRC

BUSPTRC

BUSPTRC_B17

BUSPTRC

BUSPTRC

BUSPTRC_B18

BUSPTRC

BUSPTRC

BUSPTRC_B19

BUSPTRC

BUSPTRC

BUSPTRC_B20

BUSPTRC

BUSPTRC

BUSPTRC_B21

BUSPTRC

BUSPTRC

BUSPTRC_B22

BUSPTRC

BUSPTRC

BUSPTRC_B23

BUSPTRC

BUSPTRC

BUSPTRC_B24

BUSPTRC

BUSPTRC

BUTPTRC_B1

BBTPLLN0
BUTPTRC

LLN0
BUTPTRC

BUTPTRC_B2

BUTPTRC

BUTPTRC

BUTPTRC_B3

BUTPTRC

BUTPTRC

BUTPTRC_B4

BUTPTRC

BUTPTRC

BUTPTRC_B5

BUTPTRC

BUTPTRC

BUTPTRC_B6

BUTPTRC

BUTPTRC

BUTPTRC_B7

BUTPTRC

BUTPTRC

BUTPTRC_B8

BUTPTRC

BUTPTRC

BZNSPDIF_A

BZNSPDIF

BZNSGAPC
BZNSPDIF

BZNSPDIF_B

BZNSPDIF

BZNSGAPC
BZNSPDIF

BZNTPDIF_A

BZNTPDIF

BZNTGAPC
BZNTPDIF

BZNTPDIF_B

BZNTPDIF

BZNTGAPC
BZNTPDIF

CBPGAPC

CBPLLN0
CBPMMXU
CBPPTRC
HOLPTOV
HPH1PTOV
PH3PTOC
PH3PTUC
RP3PDOP

LLN0
CBPPTRC
HOLPTOV
HPH1PTOV
PH3PTOC
PH3PTUC
RP3PDOP

CCPDSC

CCRPLD

CCPDSC

CCRBRF

CCRBRF

CCRBRF

CCSRBRF

CCSRBRF

CCSRBRF

CCSSPVC

CCSRDIF

CCSSPVC

CMMXU

CMMXU

CMMXU

CMSQI

CMSQI

CMSQI

Table continues on next page

24

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

COUVGAPC

COUVLLN0
COUVPTOV
COUVPTUV

LLN0
COUVPTOV
COUVPTUV

CVGAPC

GF2LLN0
GF2MMXN
GF2PHAR
GF2PTOV
GF2PTUC
GF2PTUV
GF2PVOC
PH1PTRC

LLN0
GF2MMXN
GF2PHAR
GF2PTOV
GF2PTUC
GF2PTUV
GF2PVOC
PH1PTRC

CVMMXN

CVMMXN

CVMMXN

DPGAPC

DPGGIO

DPGAPC

DRPRDRE

DRPRDRE

DRPRDRE

ECPSCH

ECPSCH

ECPSCH

ECRWPSCH

ECRWPSCH

ECRWPSCH

EF4PTOC

EF4LLN0
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC

LLN0
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC

EFPIOC

EFPIOC

EFPIOC

ETPMMTR

ETPMMTR

ETPMMTR

FDPSPDIS

FDPSPDIS

FDPSPDIS

FMPSPDIS

FMPSPDIS

FMPSPDIS

FRPSPDIS

FPSRPDIS

FPSRPDIS

FTAQFVR

FTAQFVR

FTAQFVR

FUFSPVC

SDDRFUF

FUFSPVC

GENPDIF

GENPDIF

LLN0
GENGAPC
GENPDIF
GENPHAR
GENPTRC

GOPPDOP

GOPPDOP

LLN0
GOPPDOP
PH1PTRC

GRPTTR

GRPTTR

LLN0
GRPTTR
GRPTUC

GSPTTR

GSPTTR

GSPTTR

GUPPDUP

GUPPDUP

LLN0
GUPPDUP
PH1PTRC

HZPDIF

HZPDIF

HZPDIF

INDCALCH
ITBGAPC

INDCALH
IB16FCVB

ITBGAPC

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

25

Section 1
Introduction

1MRK 511 302-UEN -

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

L3CPDIF

L3CPDIF

LLN0
L3CGAPC
L3CPDIF
L3CPHAR
L3CPTRC

L4UFCNT

L4UFCNT

L4UFCNT

L6CPDIF

L6CPDIF

LLN0
L6CGAPC
L6CPDIF
L6CPHAR
L6CPTRC

LAPPGAPC

LAPPLLN0
LAPPPDUP
LAPPPUPF

LLN0
LAPPPDUP
LAPPPUPF

LCCRPTRC

LCCRPTRC

LCCRPTRC

LCNSPTOC

LCNSPTOC

LCNSPTOC

LCNSPTOV

LCNSPTOV

LCNSPTOV

LCP3PTOC

LCP3PTOC

LCP3PTOC

LCP3PTUC

LCP3PTUC

LCP3PTUC

LCPTTR

LCPTTR

LCPTTR

LCZSPTOC

LCZSPTOC

LCZSPTOC

LCZSPTOV

LCZSPTOV

LCZSPTOV

LD0LLN0

LLN0

LLN0

LDLPSCH

LDLPDIF

LDLPSCH

LDRGFC

STSGGIO

LDRGFC

LEXPDIS

LEXPDIS

LLN0
LEXPDIS
LEXPTRC

LFPTTR

LFPTTR

LFPTTR

LMBRFLO

LMBRFLO

LMBRFLO

LOVPTUV

LOVPTUV

LOVPTUV

LPHD

LPHD

LPHD

LT3CPDIF

LT3CPDIF

LLN0
LT3CGAPC
LT3CPDIF
LT3CPHAR
LT3CPTRC

LT6CPDIF

LT6CPDIF

LLN0
LT6CGAPC
LT6CPDIF
LT6CPHAR
LT6CPTRC

MVGAPC

MVGGIO

MVGAPC

NS2PTOC

NS2LLN0
NS2PTOC
NS2PTRC

LLN0
NS2PTOC
NS2PTRC

Table continues on next page

26

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

Function block name

Edition 1 logical nodes

Edition 2 logical nodes

NS4PTOC

EF4LLN0
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC

LLN0
EF4PTRC
EF4RDIR
PH1PTOC

OC4PTOC

OC4LLN0
GEN4PHAR
PH3PTOC
PH3PTRC

LLN0
GEN4PHAR
PH3PTOC
PH3PTRC

OEXPVPH

OEXPVPH

OEXPVPH

OOSPPAM

OOSPPAM

LLN0
OOSPPAM
OOSPTRC

OV2PTOV

GEN2LLN0
OV2PTOV
PH1PTRC

LLN0
OV2PTOV
PH1PTRC

PAPGAPC

PAPGAPC

PAPGAPC

PCFCNT

PCGGIO

PCFCNT

PH4SPTOC

OCNDLLN0
GEN4PHAR
PH1BPTOC
PH1PTRC

LLN0
GEN4PHAR
PH1BPTOC
PH1PTRC

PHPIOC

PHPIOC

PHPIOC

PRPSTATUS

RCHLCCH

RCHLCCH
SCHLCCH

PSLPSCH

ZMRPSL

PSLPSCH

PSPPPAM

PSPPPAM

LLN0
PSPPPAM
PSPPTRC

QCBAY

QCBAY

LLN0

QCRSV

QCRSV

QCRSV

REFPDIF

REFPDIF

REFPDIF

ROTIPHIZ

ROTIPHIZ

LLN0
ROTIPHIZ
ROTIPTRC

ROV2PTOV

GEN2LLN0
PH1PTRC
ROV2PTOV

LLN0
PH1PTRC
ROV2PTOV

SAPFRC

SAPFRC

SAPFRC

SAPTOF

SAPTOF

SAPTOF

SAPTUF

SAPTUF

SAPTUF

SCCVPTOC

SCCVPTOC

SCCVPTOC

SCILO

SCILO

SCILO

SCSWI

SCSWI

SCSWI

SDEPSDE

SDEPSDE

LLN0
SDEPSDE
SDEPTOC
SDEPTOV
SDEPTRC

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

27

Section 1
Introduction

1MRK 511 302-UEN -

Function block name


SESRSYN

Edition 1 logical nodes


RSY1LLN0
AUT1RSYN
MAN1RSYN
SYNRSYN

SINGLELCCH

Edition 2 logical nodes


LLN0
AUT1RSYN
MAN1RSYN
SYNRSYN
SCHLCCH

SLGAPC

SLGGIO

SLGAPC

SMBRREC

SMBRREC

SMBRREC

SMPPTRC

SMPPTRC

SMPPTRC

SP16GAPC

SP16GGIO

SP16GAPC

SPC8GAPC

SPC8GGIO

SPC8GAPC

SPGAPC

SPGGIO

SPGAPC

SSCBR

SSCBR

SSCBR

SSIMG

SSIMG

SSIMG

SSIML

SSIML

SSIML

STBPTOC

STBPTOC

STBPTOC

STEFPHIZ

STEFPHIZ

STEFPHIZ

STTIPHIZ

STTIPHIZ

STTIPHIZ

SXCBR

SXCBR

SXCBR

SXSWI

SXSWI

SXSWI

T2WPDIF

T2WPDIF

LLN0
T2WGAPC
T2WPDIF
T2WPHAR
T2WPTRC

T3WPDIF

T3WPDIF

LLN0
T3WGAPC
T3WPDIF
T3WPHAR
T3WPTRC

TCLYLTC

TCLYLTC

TCLYLTC

TCMYLTC

TCMYLTC

TCMYLTC

TEIGAPC

TEIGGIO

TEIGAPC

TMAGAPC

TMAGGIO

TMAGAPC

TR1ATCC

TR1ATCC

TR1ATCC

TR8ATCC

TR8ATCC

TR8ATCC

TRPTTR

TRPTTR

TRPTTR

UV2PTUV

GEN2LLN0
PH1PTRC
UV2PTUV

LLN0
PH1PTRC
UV2PTUV

VDCPTOV

VDCPTOV

VDCPTOV

VDSPVC

VDRFUF

VDSPVC

VMMXU

VMMXU

VMMXU

VMSQI

VMSQI

VMSQI

VNMMXU

VNMMXU

VNMMXU

Table continues on next page

28

670 series 2.0 IEC


Communication Protocol Manual

Section 1
Introduction

1MRK 511 302-UEN -

Function block name

Edition 1 logical nodes


VRLLN0
PH1PTRC
PH1PTUV
VRPVOC

LLN0
PH1PTRC
PH1PTUV
VRPVOC

VSGAPC

VSGGIO

VSGAPC

WRNCALH

670 series 2.0 IEC


Communication Protocol Manual

Edition 2 logical nodes

VRPVOC

WRNCALH

ZC1PPSCH

ZPCPSCH

ZPCPSCH

ZC1WPSCH

ZPCWPSCH

ZPCWPSCH

ZCLCPSCH

ZCLCPLAL

LLN0
ZCLCPSCH

ZCPSCH

ZCPSCH

ZCPSCH

ZCRWPSCH

ZCRWPSCH

ZCRWPSCH

ZCVPSOF

ZCVPSOF

ZCVPSOF

ZGVPDIS

ZGVLLN0
PH1PTRC
ZGVPDIS
ZGVPTUV

LLN0
PH1PTRC
ZGVPDIS
ZGVPTUV

ZMCAPDIS

ZMCAPDIS

ZMCAPDIS

ZMCPDIS

ZMCPDIS

ZMCPDIS

ZMFCPDIS

ZMFCLLN0
PSFPDIS
ZMFPDIS

LLN0
PSFPDIS
ZMFPDIS

ZMFPDIS

ZMFLLN0
PSFPDIS
ZMFPDIS

LLN0
PSFPDIS
ZMFPDIS

ZMHPDIS

ZMHPDIS

ZMHPDIS

ZMMAPDIS

ZMMAPDIS

ZMMAPDIS

ZMMPDIS

ZMMPDIS

ZMMPDIS

ZMQAPDIS

ZMQAPDIS

ZMQAPDIS

ZMQPDIS

ZMQPDIS

ZMQPDIS

ZMRAPDIS

ZMRAPDIS

ZMRAPDIS

ZMRPDIS

ZMRPDIS

ZMRPDIS

ZMRPSB

ZMRPSB

ZMRPSB

ZSMGAPC

ZSMGAPC

ZSMGAPC

29

30

Section 2
Introduction to IEC 61850

1MRK 511 302-UEN -

Section 2

Introduction to IEC 61850

The general scope of the IEC 61850 protocol standard is designed to support the
communication of all functions being performed in the substation. Its main goal is
interoperability; this is the ability for IEDs from one or different manufacturers to
exchange information and use the information for their own functions. Moreover,
the standard allows a free allocation of these functions and accepts any system
philosophy, from a distributed architecture (for example, decentralised substation
automation) to a centralised configuration (for example, RTU based).
The standard separates the functionality represented by the data model and the
related communication services from the communication implementation (stack).
The data model of the standard is an object-oriented one, grouping the data into the
smallest possible sets referring to the smallest possible functions to be
implemented independently. These smallest possible data groups or functions are
named logical nodes. The logical nodes and all data and attributes contained are
named according to a standardised semantic, which is mandatory.
This manual describes how the IEC61850 standard is in the 670 series IEDs.
References and brief descriptions of the standard are also included. It is assumed
that the reader has basic knowledge of the IEC 61850 standard.
The following parts of the IEC61850 standard are of importance as they relate to
this manual:

Station Configuration description Language (SCL) is described in IEC


61850-6. The SCL is an XML based definition of how to describe the parts of
a substation. This part of the standard also includes the roles of different tools
as well as the engineering concepts.
Communication profile (IEC 61850 stack) is described in IEC 61850-8-1. This
part of the standard includes a number of possible communication profiles, and
how the services defined in IEC 61850-7-2 are mapped to the communication
profile.
Communication services are described in IEC 61850-7-2. This part deals
mainly with the communication facilities from client and server point of view.
It includes the different possibilities of communication functionality.
Logical node data model. This is described in IEC 61850-7-3 and IEC
61850-7-4.
Conformance tests and the basis for conformance documents are handled in
IEC 61850-10.

Detailed information regarding the IEC61850 implementation of the IED 670 is


described inside the conformance documents.

670 series 2.0 IEC


Communication Protocol Manual

31

Section 2
Introduction to IEC 61850

1MRK 511 302-UEN -

MICS, Modeling Information Conformance Statement, contains the


declaration of the used logical node types.
PICS, Protocol Information Conformance Statement, contains the details and
what is supported regarding protocol facilities.
PIXIT, Protocol Extra Information, contains additional information on how the
IEC 61850 is implemented and used.
TICS, Tissue Information Conformance Statement, contains the supported
Tissues, which are handled in the Tissues process as defined by UCA, Utility
Communication Architecture forum. The Tissues handling is found in http://
www.tissue.iec61850.com.

The conformance documents are unique for each product release and refer to each
other; the identities included in the related documents refer to a specific version of
the 670 series.
The communication profile in IEC 61850 uses the MMS standard, which uses
Ethernet and TCP/IP to handle the information transport within the substation.
The data modelling uses the concept of logical nodes to identify the published
information for communication. The standard defines a set of logical nodes, each
representing a communication view of a process function with a number of data
objects. For example, a transformer differential - or line differential protection,
because the standard defines only a differential protection. Therefore, it is possible
to adapt the logical node, which is defined in the standard, as a logical node class.
The standard defines methods to describe the actually used logical node as a logical
node type which is then based upon the logical node class. This allows all partners
to interpret the logical node type information because the description is completely
given in the standard. The type description of all logical nodes is part of the Data
Type Template (DTT) section in the SCL description file of a station or the IED.
Besides the information about the configuration of the communication facilities,
this manual contains the full description of all logical nodes available in the 670
series IED. The information about the logical nodes and their data objects may be
used to identify which signals are available for the functions as described in the
technical manual. The link to the technical manual is done in the logical node
tables by listing the signal name as given in the function block, or as seen in
PCM600 or the LHMI.

2.1.1

Related documentation to IEC 61850


Use the latest revision of the documents listed, unless stated otherwise.

32

670 series 2.0 IEC


Communication Protocol Manual

Section 2
Introduction to IEC 61850

1MRK 511 302-UEN -

670 series 2.0 IEC


Communication Protocol Manual

Document ID

Title

IEC 61850-5
First edition 2003-07
Ref. number: IEC 61850-5:2003(E)

Communication networks and systems in


substations Part 5:
Communication requirements for functions and
devices models

IEC 61850-6
First edition 2004-03
Ref. number: IEC 61850-6: 2004(E)

Communication networks and systems in


substations Part 6:
Configuration description language for
communication in electrical substations related to
IEDs

IEC 61850-7-1
First edition 2003-07
Ref. number: IEC 61850-7-1: 2003(E)

Communication networks and systems in


substations Part 7-1:
Basic communication structure for substations
and feeder equipment Principles and models

IEC 61850-7-2
First edition 2003-05
Ref. number: IEC 61850-7-2: 2003(E)

Communication networks and systems in


substations Part 7-2:
Basic communication structure for substations
and feeder equipment Abstract communication service interface (ACSI)

IEC 61850-7-3
First edition 2003-05
Ref. number: IEC 61850-7-3: 2003(E)

Communication networks and systems in


substations Part 7-3:
Basic communication structure for substations
and feeder equipment Common data classes

IEC 61850-7-4
First edition 2003-05
Ref. number: IEC 61850-7-4: 2003(E)

Communication networks and systems in


substations Part 7-4:
Basic communication structure for substations
and feeder equipment Compatible logical node classes and data classes

IEC 61850-8-1
First edition 2004-05
Ref. number: IEC 61850-8-1: 2004(E)

Communication networks and systems in


substations Part 8-1:
Specific Communication Service Mapping
(SCSM) - Mappings to MMS (ISO 9506-1 and
ISO 9506-2) and to ISO/IEC 8802-3

IEC 61850-10
First edition 2005-05
Ref. number: IEC 61850-10: 2005(E)

Communication networks and systems in


substations Part 10:
Conformance testing

IEC 61850 MICS


1MRG014230

670 series version 2.0 Ed1 - MICS:


Modelling implementation conformance statement

IEC 61850 PICS


1MRG014288

670 series version 2.0 Ed1 - PICS:


Protocol implementation conformance statement

IEC 61850 PIXIT


1MRG014232

670 series version 2.0 Ed1 - PIXIT:


Protocol implementation extra information

IEC 61850 TICS


1MRG014233

670 series version 2.0 Ed1 - TICS:


Tissue implementation conformance statement

33

34

Section 3
Substation Configuration description Language (SCL)

1MRK 511 302-UEN -

Section 3

Substation Configuration description


Language (SCL)

Three different types of SCL files - SCD, CID, and ICD, can be exported from
PCM 600.
The SCL language is based on XML. However, detailed knowledge of the XML
contents is not needed.
The SCL XML file (ICD/SCD/CID) contains five sections, which are specified in
IEC 618506 clause 9.

Header
Substation section describes the functional structure and its relation to primary
devices.
Communication section describes the connection between the IED access
points to the respective subnetwork. and includes also the properties
(addresses) of the access points.
IED section contains a description of the supported communication services,
the access point(s) and the IEDs logical devices, logical nodes and their attributes.
Data type template section contains a declaration of all types used in the SCL
file, logical nodes type, DO types, attributes and enums.

The system structure is defined by the organization of the plant structure in


PCM600. The signal engineering and the signal routing are IET600 tasks. The IED
needs to be configured with PCM600 before the system is configured with IET600.
The IED section contains the logical node types included in the respective IED
configuration and the data sets and the control blocks configured by IET600. The
data sets and the control blocks are logically defined as part of the logical nodes
(see IEC 6185072 clause 9). IET600 also needs a correctly configured
communication section for GOOSE engineering.
The data type templates section provides the correct content description of each
logical node type to all tools and users (clients) of the information. Each IED and
vendor may have their own logical node type definitions included in the data type
template section together with all other logical node types based on the standard.

670 series 2.0 IEC


Communication Protocol Manual

35

Section 3
Substation Configuration description Language (SCL)

1MRK 511 302-UEN -

Substation

Station

VoltageLevel
Bay
LNode
IED
IED

LD
LD

LN
LN

Subnetwork
Connected AP
IED Name
IED Name

AccessPoint
AccessPoint

Address
Address

Commun

Communucation
GSE
GSE

IED
Services AccessPoint
Server
Authentication
LDevice
LN0

LN
DataSet

DOI
DAI

Report Control
GOOSE Control
Inputs

IED

DOI
SettingControl

DataTypeTemplates
LNodeType
DO
DOType
DOType
DA

SDO
DAType

DAType
BDA
EnumType
EnumType

IEC08000178.vsd
IEC08000178 V1 EN

Figure 2:

IEC 61850: Principle structure of the SCL XML file

The arrows show the link between the different sections given when an IED is
integrated in the substation structure and/or in the communication structure. All
needed logical nodes of an IED are linked to the substation section by the SC tool.
A reference to GOOSE Control Blocks (GoCB) is included in the communication
section when GoCB is configured.

3.1

The substation section


The substation description in IEC 61850-6 clause 9 describes the arrangement of
the primary equipment. In addition, it also includes a list of the applied logical
nodes and the relation of those logical nodes to the primary equipment.

3.2

The communication section


The organization of the physical IEDs to the communication network is
independent of the substation structure. The IEC 61850 standard defines the

36

670 series 2.0 IEC


Communication Protocol Manual

Section 3
Substation Configuration description Language (SCL)

1MRK 511 302-UEN -

communication network with no relation to an existing media or protocol. The


mapping to an existing media and protocol is specified in IEC 6185081.
The IEC 61850 standard describes in part 72 the ACSI in a media and protocol
independent form. Part 81 specifies the mapping of this ACSI to the existing
MMS.
The communication section describes how information is routed between the IEDs
and contains the following parts:

Subnetworks
IEDs connected to different subnetworks
Access points per IED to subnetworks
Address
IP address of LAN network (is exceptionally part of the address elements)
Link to GoCB message in transmission direction (extended during signal
engineering and routing)
IED
(client)

IED
(client)

- Access Point (AP)


- Address
- GSE; GoCBs

- Access Point (AP)


- Address
- GSE; GoCBs

Communication

Communication

Subnetwork

AP
AP

Communication

Communication

Communication

- Access Point (AP)


- Address
- GSE; GoCBs

- Access Point (AP)


- Address
- GSE; GoCBs

- Access Point (AP)


- Address
- GSE; GoCBs

IED
(server)

IED
(server)

IED
(server)
en06000101.vsd

IEC06000101 V1 EN

Figure 3:

IEC 618506: Communication network

Additional information about the server is part of the IED.

3.3

The IED section


The IED section describes the complete IED as it is needed for IEC 61850
communication and signal engineering. The data type template part of an IED may
be seen as part of the IED, even when separated in its own section. The IED's ICD

670 series 2.0 IEC


Communication Protocol Manual

37

Section 3
Substation Configuration description Language (SCL)

1MRK 511 302-UEN -

files include the description of the logical nodes, their data type templates and the
used or supported services. The structure of the IED section follows the definitions
made in the IEC 61850 standard.
Two basic IED types are used in system configuration.

38

Station level IEDs


are located on the station level and are identified as client IEDs when they read
or write information from or to the bay IEDs. This functionality is represented
by logical nodes of group Information (I). These are the logical nodes (LN)
= ITCI, IHMI and ITMI. Client IEDs are the receiver of information in
monitoring direction and sender of commands (control). These logical nodes
have no data objects. They are only used to link the report control blocks
(BRCBs) from the server IEDs. They have to read their information about the
signals and the signal configuration from the bay IEDs. This is possible by
checking all control blocks for a link to it as a client.
Bay level IEDs
are located on the bay level and are identified as server IEDs when they read
or write information vertically. When GOOSE messages are received, the bay
level IED also has the client role.

670 series 2.0 IEC


Communication Protocol Manual

Section 3
Substation Configuration description Language (SCL)

1MRK 511 302-UEN -

Subnetwork
AP

IED

Server
SB1.LD0
Logical
Node
LLN0
LPHD

Data

SXCBR1

Mod

SCSWI1

Beh

SXSWI1

Health

SCSWI2

NamePlt

Data
Attribute

SXSWI2

Pos

ctlVal

SCSWI3

Loc

stVal

SXSWI3

OpCnt

SCSWI4

BlkOpn

SXSWI4

BlkCls

Origin

SCSWI5

CBOpCap

ctlModel

CVMMXU1

Control
en06000104.vsd

IEC06000104 V2 EN

Figure 4:

Organization of LDs, LNs, DOs and DAs in an IED

A server represents the communication interface to the subnetwork (Ethernet).


One or more logical device(s) (LD) are connected to a server.
A set of logical nodes belong to a LD.
The LN LLN0 is a special logical node per LD and contains for example the
data sets, the various control blocks, inputs (from GOOSE messages). In IED
670 series, the data sets and the control blocks shall be located to LD0.
The LN LPHD is a special logical node per LD and contains data objects that
describe the status of the physical device (the IED)
Each logical node represents a function and contains a number of data objects
(DO)
Each DO includes a number of data attributes (DA)

The data objects represent information signals that may be routed to station level
IEDs or to other bay IEDs that are communicating via GOOSE. The signal
engineering task is to select the requested signals (DOs) and link them to the client
IEDs as receiver. When using a dataset for MMS, the requested signals are DOs
but when creating a dataset for GOOSE messaging, DAs are used.
670 series 2.0 IEC
Communication Protocol Manual

39

Section 3
Substation Configuration description Language (SCL)

1MRK 511 302-UEN -

The number of data objects and data attributes per DO is defined by the used LN
type in the IED. The content of logical node types and DO types are defined in the
DTT. This also means that the definitions in the DTT section have to be unique
within an SCD file.

3.4

Tool concept
The IEC 61850-6 defines a number of roles for tools. In the Relion series,
PCM600 is defined as the IED tool, and IET600 is defined as the system
engineering tool.
The sections in SCL contain properties that are to be configured by these tools.
There is no relation between one section and one specific tool. The task of the IED
tool is to configure all properties for the IED, while the system tool has the task to
define the place of the IED in the system and its communication dependencies. For
example, the plant structure in PCM600 results in the subsystem section in SCL
regarding the subsystem structure down to the IED level. The PCM600 also
configures the IED section as a result of the IED configuration. In PCM600, the
configuration properties for SCL are handled automatically as a result of the
configuration, except for the receiving of GOOSE information that has a
dependency with the system tool.
IEC 61850 engineering with PCM600, PCM600 IEC61850 Configuration tool and
IET600
PCM600:

When an IED is instantiated, its place in the plant structure creates the
corresponding structure in the substation section in SCL. The communication
facilities is also created in the communication section.
The functionality of the IED is configured by using ACT in PCM600. For each
function, the corresponding logical device and logical node(s) is created in the
IED section together with its type definition in data type template section
The above forms the IED capabilities from a communication perspective and
will then be included in the file exported from PCM600 as SCD, ICD or CID file

PCM600: IEC61850 Configuration tool

Included in PCM600 is the new IEC61850 Configuration tool which allows


the user to define data sets and control blocks for both Client Server and
GOOSE communication.
The IEC61850 Configuration tool gives the user the possibility to make the
IEC61850 engineering without export / import step.
It does NOT however allow the User to define the substation part.

40

670 series 2.0 IEC


Communication Protocol Manual

Section 3
Substation Configuration description Language (SCL)

1MRK 511 302-UEN -

IET600:

Open a SCD file or import/merge a SCD, ICD or CID file for the particular
IED(s).
For each IED, the user defines the datasets, the control blocks for reporting
(this means unbufffered/buffered reporting and GOOSE) and the properties for
each report control block.
Data sets (DS) are generated automatically in PCM600. Report
control blocks (RCBs) are not generated automatically in
PCM600.

If client definitions (like client. ICD) are required in the system configuration,
they are merged into IET600 and connected to the unbuffered/buffered report
control blocks.
Logical nodes, which are not related to the conducting equipment, must be
included in the bay level in the substation section.
The resulting SCD file is exported from IET600.

PCM600:
Define the inputs for the client in IET600 and cross-reference the signals in SMT.
Import the SCD file to PCM600 to receive GOOSE data. For each IED that shall
receive GOOSE information, the received data is connected to the applications
using SMT in PCM600.
If input signals are not defined for clients in IET600, they will not
be visible in SMT. Inputs (GOOSE clients) can also be defined in
PCM600.

3.5

Engineering concept in IEC 61850-6

670 series 2.0 IEC


Communication Protocol Manual

Top-down approach means that the system engineering tool has ICD files
available for each IED to be included in the system configuration. The ICD
files may be of the template type and represent a pre-configured IED.
Bottom-up approach means that the configurations are produced by the IED
tool, and that are exported as CID files (or SCD file) to be imported into the
system tools.

41

Section 3
Substation Configuration description Language (SCL)

Client A

IED A

IED B

1MRK 511 302-UEN -

Client B

IED Z

System
tool

IED
tool

IEC09000151-1-en.vsd
IEC09000151 V1 EN

Figure 5:

Relation between system and IED tools

Regardless of the engineering approach, the idea is that the IED tool provides the
CID or ICD file for each IED. These ICD/CID files are then imported into the
system tool and merged into a SCD file, representing the complete substation or a
part of the substation, like one for each voltage level.

42

670 series 2.0 IEC


Communication Protocol Manual

Section 4
Communication profile

1MRK 511 302-UEN -

Section 4

Communication profile

The IEC 61850 standard is conceptually written to be independent of an existing


communication media and message transmission concept. Out of this, a specific
communication profile is decided and has been commonly used. The profile contains:

Ethernet as the media


TCP/IP
ISO session and presentation layer
MMS (Manufacturing Message Specification (ISO 9506-1 and ISO 9506-2)

The IEC 61850 standard describes its requested services in ACSI, which is
contained in part 7-2 of the standard. The mapping to the MMS for all aspects of
services and Ethernet usage is specified in part 8-1 of IEC 61850.
Each device manufacturer, which is a partner of an IEC 61850 based
communication network, has to take these two specifications and adapt their
respective product to the requirements and definitions given in the standard. To
make this profile visible to all other partners, so they can check what they can
expect and what they have to support, the PICS document is defined. The PICS
contains in a table based form the possibility of a product or product family.
IED (client)
(61850 services; part 7-2)
- Access Point (AP) / Address
- GSE
Communication
(MMS services; part 8-1)
AP

Communication
(MMS services; part 8-1)
- Access Point (AP) / Address
- GSE

Subnetwork

Communication
(MMS services; part 8-1)
- Access Point (AP) / Address
- GSE

IED (server)

IED (server)

(61850 services; part 7-2)

(61850 services part; 7-2)


IEC08000179.vsd

IEC08000179 V1 EN

Figure 6:

670 series 2.0 IEC


Communication Protocol Manual

IEC 61850 Protocol: related standards for communication

43

Section 4
Communication profile

1MRK 511 302-UEN -

Sampled
Values
(Multicast)

Generic
Object
Oriented
Substation
Event

SV

GOOSE

Generic
Substation
Status
Event

Core
ACSI
Services

Time
Sync
TimeSync
(SNTP)

UDP/IP

MMS Protocol Suite

TCP/IP
T-Profile

ISO CO
T-Profile

GSSE

GSSE
T-Profile

ISO/IEC 8802-2 LLC


ISO/IEC 8802-3 Ethertype
ISO/IEC 8802-3
IEC09000153-1-en.vsd
IEC09000153 V1 EN

Figure 7:

Overview of functionality and profiles according to IEC 61850-8-1

Out of this content, the implementation in the 670 series supports:

GOOSE
TimeSync using SNTP
The peer-to-peer/vertical communication using MMS protocol suite with the Tprofile TCP/IP
Sampled values according to 9-2LE

For each of the above, the resulting underlying protocols as stated in Figure 7.
See the PICS and PIXIT for more information.

44

670 series 2.0 IEC


Communication Protocol Manual

Section 5
Supported services

1MRK 511 302-UEN -

Section 5

Supported services

IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describes
how the services are applied in the communication. The conformance documents
contain the description of the supported services in the IED.
Services that are not mentioned in this chapter or in the conformance document are
not supported by the IED 670.

Data set
Define data sets by the SCD description.
Create data sets under LD0/LLN0.
For more information on data sets, see ABB 670 series version 2.0
Ed1 - PIXIT 1MRG014232

Substitution
Substitution is supported for the respective DATA, according to IEC 61850-7-4,
that have the substitution attributes defined.

Setting group control block


There is only one setting group control block, which is located in LD0/LLN0
(Logical Device/Logical Node 0).
Change or edit of setting values as well as reading of setting values is neither
supported nor visible in IEC 61850.
Note that the actual number of used setting groups is defined by the
parameter MaxNoSetGRP in the function SETGRPS, which is
configured in PST in PCM600. But six setting groups is the
maximum and it cannot be exceeded.

Report control block


For properties about report control blocks, see PIXIT.
UnBuffered reporting as well as Buffered reporting is supported.

Generic object oriented substation event (GOOSE)


The structured GOOSE is supported. This means that the data sets can be defined
with FCDA as well as explicit attributes.
670 series 2.0 IEC
Communication Protocol Manual

45

Section 5
Supported services

1MRK 511 302-UEN -

The supported data types to be published and received over GOOSE are binary
values, double point values, integer values and measured values, together with their
quality. One signal is available inside the application to validate the reception of a
GOOSE message. Invalid means that the correct GOOSE message is not received
prior 2*TAL(Time Allowed to Live).
GOOSE with TAL= 0 ms is treated as GOOSE with TAL = 100 ms
and accepted.

Note that the data sets that are used or referred to by GOOSE
control blocks can only include a data attribute once. In other
words, there may not be the same data attribute in more than one
data set.
When publishing a measured value, the user must take care of which measured
value data attributes are added to a data set. If the measured value is event-handled
(like in the case of MMXU functions), then one can add that value directly to the
data set. If the value is not event-handled, (like in the case of Synchrocheck
function), it is recommended to connect the value desired to be published to a
MVGAPC function block (in ACT) and then use the measured value given by the
MVGAPC.
Example of functions that have event-handled measured values (can be added
directly to the data set).

CVMMXN - Measurements
CMMXU - Phase current measurement
VMMXU - Phase-phase voltage measurement
CMSQI - Current sequence component measurement
VMSQI - Voltage sequence measurement
VNMMXU - Phase-neutral voltage measurement
MVGAPC - IEC 61850 generic communication I/ O functions

Generic function blocks are provided to make available to the 61850 bus signals
that are not defined inside any of the available function blocks. Example of such
functions include:

SPGAPC - IEC 61850 generic communication I/ O functions


DPGAPC - IEC 61850 generic communication I/ O functions
MVGAPC - IEC 61850 generic communication I/ O functions

Control
Of the different control sequences, the direct-with-normal-security and SBO-withenhanced security are supported (defined by the ctlModel parameter, IEC
61850-7-2).

46

670 series 2.0 IEC


Communication Protocol Manual

1MRK 511 302-UEN -

Section 5
Supported services

Check bits; interlock check and synchrocheck check, are only valid for LN types
based upon CSWI class.
Verification of Originator Category is supported, see also PIXIT.

670 series 2.0 IEC


Communication Protocol Manual

47

48

Section 6
Data sets and control blocks

1MRK 511 302-UEN -

Section 6

Data sets and control blocks

6.1

Data sets
IEC 61850 has defined data sets and report control blocks to transmit signals for
monitoring purposes. Data sets are also used for GOOSE messages in horizontal
communication among IEDs. The project defines the data objects or single data
attributes that should be collected in a data set. The following figure shows a data
set where all position information of the apparatuses of a bay are put into one data
set.
PCM600 will generate default data sets, based on the current ACT configuration.
The default data sets can be modified or removed in the engineering tools. No
RCBs are created automatically by PCM600. However, the pre-configured IEDs
are delivered with RCBs for all default the data sets.
LD0

DATA-SET
LLN0

LD0/LLN0.AppPos

LPHD

LD0/SXCBR1.Pos FC=ST

SXCBR1

Pos

LD0/SXSWI2.Pos FC=ST

SCSWI1
SXSWI1

Pos

SCSWI2
SXSWI2

LD0/SXSWI1.Pos FC=ST

LD0/SXSWI3.Pos FC=ST
LD0/SXSWI4.Pos FC=ST

Pos

SCSWI3
SXSWI3

Pos

SCSWI4
SXSWI4

stVal
q

Pos

SCSWI5

t
Origin

CVMMXU1
en06000106.vsd
IEC06000106 V2 EN

Figure 8:

IEC 6185072: Example of a data set for MMS

General rules for data set configuration:

670 series 2.0 IEC


Communication Protocol Manual

49

Section 6
Data sets and control blocks

1MRK 511 302-UEN -

All data objects or their data attributes can be selected for a data set.
Only those data attributes of a data object can/will be selected which have the
same function constraint (FC).
Data objects with different FC can be selected for a data set. For example,
DOs with FC = ST and DOs with FC=MX can be member in one data set.
A single data attribute can be selected when it is specified with a trigger
option. For example, the data attribute stVal of the data object Pos can be
selected as a member of a data set, because it is specified with the trigger
option data change detected (dchg).

The description of the data sets with name and the list of data object members
(FCDAs is included in the SCL file in the IED section in the Logical device
subsection. As specified in IEC 6185072 clause 9, the data sets are part of a
logical node. They are most likely included in the LLN0.

6.2

Report control block (URCB/BRCB)


To be able to transmit the signals configured in a DataSet, a report control block
must be configured to handle and specify how the events are transmitted to the
clients. There are two types of report control blocks; unbuffered and buffered. The
buffered report control block stores the events during a communication interrupt,
while the unbuffered is sent upon data change and not stored during interruption.
The content of a BRCB is listed in IEC 61850-7-2 in clause 14. The BRCB
contains many attributes which are of interest to handle and secure the
communication between the client and the server and may be set once as default in
a project. Others are of application interest in the way events are handled in a project.

Buffer time (valid only for BRCB)

Trigger options

The data attributes know three different trigger options (dchg, qchg,
dupd). Within the BRCB, the two other can be defined (integrity and
general interrogation). The attribute Trigger option is a multiple choice
and allows to mask the supported trigger options in this BRCB.

Integrity period

50

This parameter describes how long the report should wait for other
expected events before it sends the report to the client. When it is known,
that additional events are generated as a follow up, it is useful to wait,
for example, 500 ms for additional events stored in the report. This
feature reduces the number of telegrams transmitted in case of a burst of
changes.

When integrity is selected in the trigger option attribute, it is needed to


define an integrity period to force the transmission of all data listed in
the DataSet. This is done by the attribute Integrity period. This feature

670 series 2.0 IEC


Communication Protocol Manual

Section 6
Data sets and control blocks

1MRK 511 302-UEN -

can be used as a background cycle to ensure that the process image in all
partners is the same.

General interrogation

A general interrogation is only done on request from a client. Not all Datasets may contain information which is needed for a general update of the
client. For example data with T(ransient) = TRUE are not part of a GI.
When the BRCB attribute general interrogation is set to TRUE a GI
request from the client will be handled. The report handler will transmit
all data defined in the Data-set with their actual values. The IEC 61850
standard defines that all buffered events shall be transmitted first before
the GI is started. A running GI shall be stopped and a new GI shall be
started, when a new GI request is received while a GI is running.

Purge buffer (valid only for BRCB)

This BRCB attribute can be used by a client to clean the event buffer
from old events. The events are discarded on request of the client. This
feature can be used to delete old events not transmitted to the client due
to stopped communication. After the link is reestablished the client can
decide to clean the buffer or to receive the history.

Trigger Options
IEC 61850 has defined in total five different TrgOp. Three of them belonging to
data attributes and marked per data attribute in the column TrgOp of the CDC
tables in part 73. The other two belonging to the configuration of control blocks.

dchg = data-change

qchg = quality change

This trigger forces the transmission of all process values defined in the
data set when a timer value (the integrity period) expires.

general interrogation

670 series 2.0 IEC


Communication Protocol Manual

This trigger option give the possibility to define that a transmission


should be done on a condition which can be controlled by the application.

integrity

Looking to the possibilities of the quality data attribute type (q) any
changes in the quality description will be transmitted.

dupd = data value update

Whenever a process value has changed its value either binary or a


measurement a transmission is done.

This trigger is forced by the clients (= station level IED; NCC gateway,
station HMI, ...). Normally a GI is asked for, when the client and the
server start or restart a session. When the client is able to receive the
actual values and when the logical device has scanned all process values
at least once, an image of the actual process signal status can be
transmitted to the client.

51

Section 6
Data sets and control blocks

1MRK 511 302-UEN -

Note that the possible trigger options for each attribute


are included and defined in the datatype template section
in SCL.

Link BRCB to a client LN


The BRCB has to know to whom the events shall be transmitted. This is the signal
routing engineering step. The IEC standard 618506 describes that this is given by
including the LN of the client IED in the ReportBlockEnabled option.
The selected client IED with the corresponding LN, for example, ITCI is included
in the SCL structure of the Report Control description of the IED section.
The description of the BRCB with selected DataSet, configured parameters and
selected IEDs is included in the SCL file in the IED section in the LN0 structure
for the LD where this LN0 belongs to.
IED
HSI
Client 1

IED
NCC GW 1

IHSI1

Client 2

IED
NCC GW m
Client m

ITCI1

ITCI2

Subnetwork

Server 1

LLN0

DATA-SET
LD0/LLN0.AppPos

IED 1

LD0/SXCBR1.Pos FC=ST
LD0/SXSWI1.Pos FC=ST
LD0/SXSWI2.Pos FC=ST
LD0/SXSWI3.Pos FC=ST
LD0/SXSWI4.Pos FC=ST
en06000107.vsd

IEC06000107 V2 EN

Figure 9:

52

Link BRCB to a client LN

670 series 2.0 IEC


Communication Protocol Manual

Section 6
Data sets and control blocks

1MRK 511 302-UEN -

Data-set

Data-set
LN

LN

LN

LN

Receive

Receive

Data-set
LN

LN

LN

Send

Receive

Receive

Send

Receive

Receive

GOOSE Control Blocks (GoCB)

Send

6.3

LN
LN

LN

LN

LN

LN

LN

LN

Subnetwork

Comm.

Comm.

GSE

Server

Server

LD0

LD0
GoCB
GoCB
GoCB

Input
Input
Input
DataSet
DataSet
DataSet

LN0

GSE

GoCB
GoCB
GoCB

Input
Input
Input
DataSet
DataSet
DataSet

LN0

en06000109.vsd
IEC06000109 V2 EN

Figure 10:

IEC 61850: Principle operation of GOOSE messages

The Generic Object Oriented Substation Event (GOOSE) class model is used to
distribute input and output data values between IEDs on bay level (in horizontal
direction) through the use of multicast services. GOOSE messages enable fast
transmission from a publisher to one or several subscribers (receivers).
The GOOSE service model of IEC 61850-7-2 provides the possibility for fast and
reliable system-wide distribution of input and output data values. This
implementation uses a specific scheme of re-transmission to achieve the
appropriate level of reliability. When a GOOSE server generates a
SendGOOSEMessage request, the current data set values are encoded in a GOOSE

670 series 2.0 IEC


Communication Protocol Manual

53

Section 6
Data sets and control blocks

1MRK 511 302-UEN -

message and transmitted on the multicast association. The event that causes the
server to invoke a SendGOOSE service is a local application issue as defined in
IEC 61850-7-2. Each update may generate a message in order to minimize
throughput time.
Additional reliability is achieved by re-transmitting the same data (with gradually
increasing SqNum and retransmission time).
T0

retransmission in stable conditions (no event for a long time)

(T0)

retransmission in stable conditions may be shortened by an event

T1

shortest retransmission time after the event

T2, T3

retransmission times until achieving the stable conditions time

Time of transmission

T0

(T0)

T1 T1 T2

T3

T0

event
IEC09000152-1-en.vsd
IEC09000152 V1 EN

Figure 11:

Transmission time for events

Each message in the retransmission sequence carries a timeAllowedToLive


parameter that informs the receiver of the maximum time to wait for the next retransmission. If a new message is not received within that time interval, the
receiver assumes that the association is lost. The specific intervals used by any
GOOSE publisher are a local issue. The timeAllowedtoLive parameter informs
subscribers of how long to wait. The detection time of lost GOOSE is 2*
timeAllowedToLive in the subscriber. This allows one lost GOOSE message and to
cope with possible transmission delays in the network.
The GOOSE message concept is used for all application functions where two or
more IEDs are involved. Typical example is the station-wide interlocking
procedure or breaker failure protection.
Figure 10 shows the GOOSE concept for three IEDs which interchange GOOSE
messages between each other.
To send GOOSE messages a GoCB must be defined and a data set is needed that
contains the data objects of single data attributes to be sent.

54

670 series 2.0 IEC


Communication Protocol Manual

1MRK 511 302-UEN -

Section 6
Data sets and control blocks

A GOOSE message is forced to be transmitted when a trigger change is detected


for a data attribute. All members of the data set are copied in the send buffer with
their actual value and the message is sent. The subscribers, who knows the address
of this GOOSE message, receives the telegram. The GOOSE message includes a
sequence number to verify that all messages are received.

670 series 2.0 IEC


Communication Protocol Manual

55

56

Section 7
Logical node data model

1MRK 511 302-UEN -

Section 7

Logical node data model

The data model used by IEC 61850 is based on logical nodes containing a set of
data objects. The data model is defined in the standards.

IEC 61850-7-4 Compatible logical node classes and data classes


IEC 61850-7-3 Common data classes

The standard describes only classes of logical nodes and data objects on one side
and common data classes for the data object attributes. Also here it is given has the
elements in these classes are defined as:

Mandatory (M)
Optional (O)
Conditional optional (Cxxx)
In addition, the IEC 61850 states rules for adding vendor-specific definitions
to the standard, in order to cope with extra functionality.

The possible description of the data model according to the standard allows to
adapt a logical node of a LN class to that what the product is supporting or using
for this LN. This definition of what parts of a class is used in the actual product and
possible addition is called a type, according to IEC 61850-6. There are LN types
based upon LN classes. The LN type attributes are called Data Objects (or DATA)
and are in of DO types, base upon respective CDC class. This allows all partners in
the IEC 61850 project who need this LN to understand the LN in all details for the
communication part.
The IEC 61850 standard does not describe the functionality and way of operation.
Each supplier has to describe this separately. ABB has described their function
blocks that represent a logical node and all other function blocks in the technical
manuals. This chapter in the communication protocol manual has two purposes:

7.1

Describe the Logical Node types and their data object attribute types.
Make the link to the description of the function block.

Common data objects in each logical node


The IEC 61850 standard describes in part 7-5, a Common Logical Node. The data
objects contained in that LN are both mandatory and optional. The mandatory data
objects have to be included in each LN. This clause describes the general handling
of the data objects within the 670 series products.

670 series 2.0 IEC


Communication Protocol Manual

57

Section 7
Logical node data model

1MRK 511 302-UEN -

The mandatory data objects as defined in IEC 61850-7-4 as part of the Common
Logical Node are Mode, Behavior, Health and NamePlate.
Mode
The operation modes ON (enabled) and BLOCKED are supported remotely by a
command or locally from the LHMI of the IED.
Note that if the setting RemoteModControl is set to Off
(default), all writes to Mod will be rejected.
Note also that for functions in other Logical devices than LD0, the Mod can only
be controlled by communication on LLN0. In 670 2.0, Mod can also be controlled
from the LHMI, (both in Ed.1 and Ed.2 mode).
Behaviour
The operational mode as given by the Mode control is shown in the data object Beh
with the priority rules as described for Beh in clause 6 of IEC 61850-7-4.
The Beh shows the actual state of the function, dependent upon the hierarchy
described in IEC 61850-7-4, clause 6.
In addition, it is possible that the behavior is influenced by other sources as well,
independent from the Mod, for example Insertion of the test handle, loss of SV,
IED configuration tool (PCM600), or LHMI.
In case the setting operation of a function is set to Off from the LHMI or by
using PCM600, the Beh will be set to Off independent of the value of the Mod.
The state OFF can be set from the LHMI or by using PCM600 for the functions
having the setting operation.
The TEST and the TEST/BLOCKED mode can be operated locally from the LHMI.
Health
Health will reflect the current status of the IED HW and configuration. Possible
values are: OK, Warning, and Alarm.
Health indicates OK, Warning, or Alarm, depending on the IED status.
NamePlt
The name of the logical node and its relation to namespace definition are shown in
the data object NamePlt as specified for the SCL structure.

58

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.2

Logical nodes for automatic control

7.2.1

Automatic tap changer control ATCC

Table 7:
DO name
TapChg

Mod

Beh

LN type

LN prefix

LN class

Function block name

TR1ATCC (revision 6)

TR1

ATCC

TR1ATCC

TR1ATCC Logical node data


DO type

DA name

a_dBSC

a_dINC

a_dINS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

valWTr.posVal

ST

Mon

Tap position

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

valWTr.transInd

ST

Mon

Tap position change in progress

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

ST

Mon

Quality: Tap position

ST

Mon

Timestamp: Tap position

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

59

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Beh

a_dINS

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

LTCBlk

a_dSPC

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

Voltage control blocked while in


automatic control mode

ST

Mon

Quality: Voltage control blocked


while in automatic control mode

ST

Mon

Timestamp: Voltage control


blocked while in automatic control
mode

stVal

ST

Mon

Local commands selected

ST

Mon

Quality: Local commands selected

ST

Mon

Timestamp: Local commands


selected

stVal

ST

UBLK

Mon

Busbar voltage below the settable


limit voltBusbBlockLimit

ST

UBLK

Mon

Quality: Busbar voltage below the


settable limit voltBusbBlockLimit

ST

UBLK

Mon

Timestamp: Busbar voltage


below the settable limit
voltBusbBlockLimit

stVal

ST

Mon

Tap position for max voltage

ST

Mon

Quality: Tap position for max


voltage

ST

Mon

Timestamp: Tap position for max


voltage

stVal

ST

Mon

Tap position for min voltage

ST

Mon

Quality: Tap position for min


voltage

ST

Mon

Timestamp: Tap position for min


voltage

mag.f

MX

Mon

Magnitude of measured load


current (service value)

MX

Mon

Quality: Magnitude of measured


load current (service value)

Loc

BlkV

HiTapPos

LoTapPos

LodA

a_dSPS

a_dSPS

b_dINS

b_dINS

b_dMV

Table continues on next page


60

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

LodA

b_dMV

MX

Mon

Timestamp: Magnitude of
measured load current (service
value)

CtlV

b_dMV

mag.f

MX

BUSVOLT

Mon

The average of the measured


busbar voltage (service value)

MX

BUSVOLT

Mon

Quality: The average of the


measured busbar voltage
(service value)

MX

BUSVOLT

Mon

Timestamp: The average of the


measured busbar voltage
(service value)

mag.f

MX

Mon

Calculated active power (service


value)

MX

Mon

Quality: Calculated active power


(service value)

MX

Mon

Timestamp: Calculated active


power (service value)

mag.f

MX

Mon

Calculated reactive power


(service value)

MX

Mon

Quality: Calculated reactive


power (service value)

MX

Mon

Timestamp: Calculated reactive


power (service value)

stVal

ST

Mon

The transformer operates in


parallel mode

ST

Mon

Quality: The transformer operates


in parallel mode

ST

Mon

Timestamp: The transformer


operates in parallel mode

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

AUTO

Mon

Automatic control mode is active

ST

AUTO

Mon

Quality: Automatic control mode


is active

ST

AUTO

Mon

Timestamp: Automatic control


mode is active

TotW

TotVAr

ParOp

AutoCtl

c_dMV

c_dMV

c_dSPC

v1_dSPC

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

61

Section 7
Logical node data model
DO name
LVA1On

LVA2On

LVA3On

DO type
v1_dSPC

v1_dSPC

v1_dSPC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

The setting LVAConst1 is used


(service value)

ST

Mon

Quality: The setting LVAConst1 is


used (service value)

ST

Mon

Timestamp: The setting


LVAConst1 is used (service value)

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

The setting LVAConst2 is used


(service value)

ST

Mon

Quality: The setting LVAConst2 is


used (service value)

ST

Mon

Timestamp: The setting


LVAConst2 is used (service value)

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Table continues on next page

62

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
LVA3On

LVA4On

LVAReset

HiV

DO type

DA name

v1_dSPC

v1_dSPC

v1_dSPC

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

The setting LVAConst3 is used


(service value)

ST

Mon

Quality: The setting LVAConst3 is


used (service value)

ST

Mon

Timestamp: The setting


LVAConst3 is used (service value)

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

The setting LVAConst4 is used


(service value)

ST

Mon

Quality: The setting LVAConst4 is


used (service value)

ST

Mon

Timestamp: The setting


LVAConst4 is used (service value)

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

UHIGH

Mon

Busbar voltage above the


settable limit voltBusbMaxLimit

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

63

Section 7
Logical node data model
DO name
HiV

LoV

HiWFwd

HiWRv

HiVArFwd

HiVArRv

HiABlk

ExLowerBlk

DO type
v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

UHIGH

Mon

Quality: Busbar voltage above the


settable limit voltBusbMaxLimit

ST

UHIGH

Mon

Timestamp: Busbar voltage


above the settable limit
voltBusbMaxLimit

stVal

ST

ULOW

Mon

Busbar voltage below the settable


limit voltBusbMinLimit

ST

ULOW

Mon

Quality: Busbar voltage below the


settable limit voltBusbMinLimit

ST

ULOW

Mon

Timestamp: Busbar voltage


below the settable limit
voltBusbMinLimit

stVal

ST

PGTFWD

Mon

Active power above the settable


limit powerActiveForw

ST

PGTFWD

Mon

Quality: Active power above the


settable limit powerActiveForw

ST

PGTFWD

Mon

Timestamp: Active power above


the settable limit powerActiveForw

stVal

ST

PLTREV

Mon

Active power below the settable


limit powerActiveRev

ST

PLTREV

Mon

Quality: Active power below the


settable limit powerActiveRev

ST

PLTREV

Mon

Timestamp: Active power below


the settable limit powerActiveRev

stVal

ST

QGTFWD

Mon

Reactive power above the


settable limit powerReactiveForw

ST

QGTFWD

Mon

Quality: Reactive power above


the settable limit
powerReactiveForw

ST

QGTFWD

Mon

Timestamp: Reactive power


above the settable limit
powerReactiveForw

stVal

ST

QLTREV

Mon

Reactive power below the


settable limit powerReactiveRev

ST

QLTREV

Mon

Quality: Reactive power below


the settable limit
powerReactiveRev

ST

QLTREV

Mon

Timestamp: Reactive power


below the settable limit
powerReactiveRev

stVal

ST

IBLK

Mon

One phase current is above the


settable limit

ST

IBLK

Mon

Quality: One phase current is


above the settable limit

ST

IBLK

Mon

Timestamp: One phase current is


above the settable limit

stVal

ST

Mon

External block of lower command


activated

ST

Mon

Quality: External block of lower


command activated

Table continues on next page


64

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

ExLowerBlk

v1_dSPS

ST

Mon

Timestamp: External block of


lower command activated

ExRaiseBlk

v1_dSPS

stVal

ST

Mon

External block of raise command


activated

ST

Mon

Quality: External block of raise


command activated

ST

Mon

Timestamp: External block of


raise command activated

stVal

ST

REVACBLK

Mon

Block caused by reversed action

ST

REVACBLK

Mon

Quality: Block caused by


reversed action

ST

REVACBLK

Mon

Timestamp: Block caused by


reversed action

stVal

ST

DAYHUNT

Mon

Alarm for too many tap changer


operations during the last 24 hours

ST

DAYHUNT

Mon

Quality: Alarm for too many tap


changer operations during the
last 24 hours

ST

DAYHUNT

Mon

Timestamp: Alarm for too many


tap changer operations during the
last 24 hours

stVal

ST

HOURHUNT

Mon

Alarm for too many tap changer


operations during the last hour

ST

HOURHUNT

Mon

Quality: Alarm for too many tap


changer operations during the
last hour

ST

HOURHUNT

Mon

Timestamp: Alarm for too many


tap changer operations during the
last hour

stVal

ST

HUNTING

Mon

Alarm for too many contradictory


tap changer operations within the
time sliding window

ST

HUNTING

Mon

Quality: Alarm for too many


contradictory tap changer
operations within the time sliding
window

ST

HUNTING

Mon

Timestamp: Alarm for too many


contradictory tap changer
operations within the time sliding
window

stVal

ST

TOTBLK

Mon

Block of auto and manual


commands

ST

TOTBLK

Mon

Quality: Block of auto and manual


commands

ST

TOTBLK

Mon

Timestamp: Block of auto and


manual commands

stVal

ST

AUTOBLK

Mon

Block of auto commands

ST

AUTOBLK

Mon

Quality: Block of auto commands

ST

AUTOBLK

Mon

Timestamp: Block of auto


commands

RvActBlk

DayHuntAlm

HrHuntAlm

HuntAlm

TotBlock

AutoBlock

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

65

Section 7
Logical node data model
DO name
VCTRStatus

LodV

AverA

AutoRedV

BndCtrSng

BndCtrSet

LVA1V

LVA2V

DO type
v2_dINS

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

ST

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

ST

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ULOAD

Mon

Calculated compensated voltage


(service value)

MX

ULOAD

Mon

Quality: Calculated compensated


voltage (service value)

MX

ULOAD

Mon

Timestamp: Calculated
compensated voltage (service
value)

mag.f

MX

IPRIM

Mon

Max of 3 phase currents (service


value)

MX

IPRIM

Mon

Quality: Max of 3 phase currents


(service value)

MX

IPRIM

Mon

Timestamp: Max of 3 phase


currents (service value)

mag.f

MX

Mon

Load dependent automatic


reduction voltage

MX

Mon

Quality: Load dependent


automatic reduction voltage

MX

Mon

Timestamp: Load dependent


automatic reduction voltage

mag.f

MX

Mon

Voltage setpoint single

MX

Mon

Quality: Voltage setpoint single

MX

Mon

Timestamp: Voltage setpoint


single

mag.f

MX

Mon

Voltage setpoint set by user

MX

Mon

Quality: Voltage setpoint set by


user

MX

Mon

Timestamp: Voltage setpoint set


by user

mag.f

MX

Mon

Value 1 for load voltage


adjustment

MX

Mon

Quality: Value 1 for load voltage


adjustment

MX

Mon

Timestamp: Value 1 for load


voltage adjustment

mag.f

MX

Mon

Value 2 for load voltage


adjustment

MX

Mon

Quality: Value 2 for load voltage


adjustment

MX

Mon

Timestamp: Value 2 for load


voltage adjustment

Table continues on next page

66

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
LVA3V

LVA4V

BndCtrAct

LodAIm

LodARe

BusV

SetV

PosRel

DO type

DA name

v2_dMV

v2_dMV

v2_dMV

v3_dMV

v4_dMV

v5_dMV

v6_dMV

v7_dMV

FC

Signal

Mon/
Cmd

Description

mag.f

MX

Mon

Value 3 for load voltage


adjustment

MX

Mon

Quality: Value 3 for load voltage


adjustment

MX

Mon

Timestamp: Value 3 for load


voltage adjustment

mag.f

MX

Mon

Value 4 for load voltage


adjustment

MX

Mon

Quality: Value 4 for load voltage


adjustment

MX

Mon

Timestamp: Value 4 for load


voltage adjustment

mag.f

MX

Mon

Actual voltage setpoint

MX

Mon

Quality: Actual voltage setpoint

MX

Mon

Timestamp: Actual voltage


setpoint

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

67

Section 7
Logical node data model
DO name
PosRel

X2

DO type
v7_dMV

v8_dMV

DA name

DO name
TapChg

Mod

FC

Signal

Mon/
Cmd

Description

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

7.2.1.1

Table 8:

1MRK 511 302-UEN -

Automatic voltage control for tapchanger, parallel control TR8ATCC


LN type

LN prefix

LN class

Function block name

TR8ATCC (revision 5)

TR8

ATCC

TR8ATCC

TR8ATCC Logical node data


DO type
a_dBSC

a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

valWTr.posVal

ST

Mon

Tap position

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

valWTr.transInd

ST

Mon

Tap position change in progress

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

ST

Mon

Quality: Tap position

ST

Mon

Timestamp: Tap position

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Table continues on next page


68

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

LTCBlk

Loc

BlkV

HiTapPos

DO type

DA name

a_dINC

a_dINS

a_dSPC

a_dSPS

a_dSPS

b_dINS

FC

Signal

Mon/
Cmd

Description

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

Voltage control blocked while in


automatic control mode

ST

Mon

Quality: Voltage control blocked


while in automatic control mode

ST

Mon

Timestamp: Voltage control


blocked while in automatic control
mode

stVal

ST

Mon

Local commands selected

ST

Mon

Quality: Local commands selected

ST

Mon

Timestamp: Local commands


selected

stVal

ST

UBLK

Mon

Busbar voltage below the settable


limit voltBusbBlockLimit

ST

UBLK

Mon

Quality: Busbar voltage below the


settable limit voltBusbBlockLimit

ST

UBLK

Mon

Timestamp: Busbar voltage


below the settable limit
voltBusbBlockLimit

stVal

ST

Mon

Tap position for max voltage

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

69

Section 7
Logical node data model
DO name
HiTapPos

LoTapPos

CircA

LodA

CtlV

TotW

TotVAr

ParOp

LTCId

DO type
b_dINS

b_dINS

b_dMV

b_dMV

b_dMV

c_dMV

c_dMV

c_dSPC

v1_dINS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

Mon

Quality: Tap position for max


voltage

ST

Mon

Timestamp: Tap position for max


voltage

stVal

ST

Mon

Tap position for min voltage

ST

Mon

Quality: Tap position for min


voltage

ST

Mon

Timestamp: Tap position for min


voltage

mag.f

MX

ICIRCUL

Mon

Circulating current

MX

ICIRCUL

Mon

Quality: Circulating current

MX

ICIRCUL

Mon

Timestamp: Circulating current

mag.f

MX

Mon

Magnitude of measured load


current (service value)

MX

Mon

Quality: Magnitude of measured


load current (service value)

MX

Mon

Timestamp: Magnitude of
measured load current (service
value)

mag.f

MX

BUSVOLT

Mon

The average of the measured


busbar voltage (service value)

MX

BUSVOLT

Mon

Quality: The average of the


measured busbar voltage
(service value)

MX

BUSVOLT

Mon

Timestamp: The average of the


measured busbar voltage
(service value)

mag.f

MX

Mon

Calculated active power (service


value)

MX

Mon

Quality: Calculated active power


(service value)

MX

Mon

Timestamp: Calculated active


power (service value)

mag.f

MX

Mon

Calculated reactive power


(service value)

MX

Mon

Quality: Calculated reactive


power (service value)

MX

Mon

Timestamp: Calculated reactive


power (service value)

stVal

ST

PARALLEL

Mon

The transformer operates in


parallel mode

ST

PARALLEL

Mon

Quality: The transformer operates


in parallel mode

ST

PARALLEL

Mon

Timestamp: The transformer


operates in parallel mode

stVal

ST

Mon

Identity of the transformer

ST

Mon

Quality: Identity of the transformer

Table continues on next page

70

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

LTCId

v1_dINS

ST

Mon

Timestamp: Identity of the


transformer

ParSet

v1_dINS

stVal

ST

Mon

Setting value for transformer in


parallel mode

ST

Mon

Quality: Setting value for


transformer in parallel mode

ST

Mon

Timestamp: Setting value for


transformer in parallel mode

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

AUTO

Mon

Automatic control mode is active

ST

AUTO

Mon

Quality: Automatic control mode


is active

ST

AUTO

Mon

Timestamp: Automatic control


mode is active

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

The setting LVAConst1 is used


(service value)

ST

Mon

Quality: The setting LVAConst1 is


used (service value)

ST

Mon

Timestamp: The setting


LVAConst1 is used (service value)

AutoCtl

LVA1On

v1_dSPC

v1_dSPC

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

71

Section 7
Logical node data model
DO name
LVA2On

LVA3On

LVA4On

DO type
v1_dSPC

v1_dSPC

v1_dSPC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

The setting LVAConst2 is used


(service value)

ST

Mon

Quality: The setting LVAConst2 is


used (service value)

ST

Mon

Timestamp: The setting


LVAConst2 is used (service value)

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

The setting LVAConst3 is used


(service value)

ST

Mon

Quality: The setting LVAConst3 is


used (service value)

ST

Mon

Timestamp: The setting


LVAConst3 is used (service value)

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Table continues on next page

72

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
LVA4On

LVAReset

ForceMast

HiV

DO type

DA name

v1_dSPC

v1_dSPC

v1_dSPC

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

The setting LVAConst4 is used


(service value)

ST

Mon

Quality: The setting LVAConst4 is


used (service value)

ST

Mon

Timestamp: The setting


LVAConst4 is used (service value)

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

The transformer is forced to be


master

ST

Mon

Quality: The transformer is forced


to be master

ST

Mon

Timestamp: The transformer is


forced to be master

stVal

ST

UHIGH

Mon

Busbar voltage above the


settable limit voltBusbMaxLimit

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

73

Section 7
Logical node data model
DO name
HiV

LoV

AutoSlave

Q1Conn

Q2Conn

Q3Conn

T1ParGr

T2ParGr

T3ParGr

DO type
v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

UHIGH

Mon

Quality: Busbar voltage above the


settable limit voltBusbMaxLimit

ST

UHIGH

Mon

Timestamp: Busbar voltage


above the settable limit
voltBusbMaxLimit

stVal

ST

ULOW

Mon

Busbar voltage below the settable


limit voltBusbMinLimit

ST

ULOW

Mon

Quality: Busbar voltage below the


settable limit voltBusbMinLimit

ST

ULOW

Mon

Timestamp: Busbar voltage


below the settable limit
voltBusbMinLimit

stVal

ST

Mon

Auto slave activated

ST

Mon

Quality: Auto slave activated

ST

Mon

Timestamp: Auto slave activated

stVal

ST

Mon

Reactive bank1 connected

ST

Mon

Quality: Reactive bank1


connected

ST

Mon

Timestamp: Reactive bank1


connected

stVal

ST

Mon

Reactive bank2 connected

ST

Mon

Quality: Reactive bank2


connected

ST

Mon

Timestamp: Reactive bank2


connected

stVal

ST

Mon

Reactive bank3 connected

ST

Mon

Quality: Reactive bank3


connected

ST

Mon

Timestamp: Reactive bank3


connected

stVal

ST

T1PG

Mon

Transformer1 included in parallel


group

ST

T1PG

Mon

Quality: Transformer1 included in


parallel group

ST

T1PG

Mon

Timestamp: Transformer1
included in parallel group

stVal

ST

T2PG

Mon

Transformer2 included in parallel


group

ST

T2PG

Mon

Quality: Transformer2 included in


parallel group

ST

T2PG

Mon

Timestamp: Transformer2
included in parallel group

stVal

ST

T3PG

Mon

Transformer3 included in parallel


group

ST

T3PG

Mon

Quality: Transformer3 included in


parallel group

Table continues on next page

74

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

T3ParGr

v1_dSPS

ST

T3PG

Mon

Timestamp: Transformer3
included in parallel group

T4ParGr

v1_dSPS

stVal

ST

T4PG

Mon

Transformer4 included in parallel


group

ST

T4PG

Mon

Quality: Transformer4 included in


parallel group

ST

T4PG

Mon

Timestamp: Transformer4
included in parallel group

stVal

ST

T5PG

Mon

Transformer5 included in parallel


group

ST

T5PG

Mon

Quality: Transformer5 included in


parallel group

ST

T5PG

Mon

Timestamp: Transformer5
included in parallel group

stVal

ST

T6PG

Mon

Transformer6 included in parallel


group

ST

T6PG

Mon

Quality: Transformer6 included in


parallel group

ST

T6PG

Mon

Timestamp: Transformer6
included in parallel group

stVal

ST

T7PG

Mon

Transformer7 included in parallel


group

ST

T7PG

Mon

Quality: Transformer7 included in


parallel group

ST

T7PG

Mon

Timestamp: Transformer7
included in parallel group

stVal

ST

T8PG

Mon

Transformer8 included in parallel


group

ST

T8PG

Mon

Quality: Transformer8 included in


parallel group

ST

T8PG

Mon

Timestamp: Transformer8
included in parallel group

stVal

ST

Mon

Transformer 1 is master

ST

Mon

Quality: Transformer 1 is master

ST

Mon

Timestamp: Transformer 1 is
master

stVal

ST

Mon

Transformer 2 is master

ST

Mon

Quality: Transformer 2 is master

ST

Mon

Timestamp: Transformer 2 is
master

stVal

ST

Mon

Transformer 3 is master

ST

Mon

Quality: Transformer 3 is master

ST

Mon

Timestamp: Transformer 3 is
master

stVal

ST

Mon

Transformer 4 is master

ST

Mon

Quality: Transformer 4 is master

T5ParGr

T6ParGr

T7ParGr

T8ParGr

T1Master

T2Master

T3Master

T4Master

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

75

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

T4Master

v1_dSPS

ST

Mon

Timestamp: Transformer 4 is
master

T5Master

v1_dSPS

stVal

ST

Mon

Transformer 5 is master

ST

Mon

Quality: Transformer 5 is master

ST

Mon

Timestamp: Transformer 5 is
master

stVal

ST

Mon

Transformer 6 is master

ST

Mon

Quality: Transformer 6 is master

ST

Mon

Timestamp: Transformer 6 is
master

stVal

ST

Mon

Transformer 7 is master

ST

Mon

Quality: Transformer 7 is master

ST

Mon

Timestamp: Transformer 7 is
master

stVal

ST

Mon

Transformer 8 is master

ST

Mon

Quality: Transformer 8 is master

ST

Mon

Timestamp: Transformer 8 is
master

stVal

ST

HOMING

Mon

Transformer is in homing
conditions

ST

HOMING

Mon

Quality: Transformer is in homing


conditions

ST

HOMING

Mon

Timestamp: Transformer is in
homing conditions

stVal

ST

Mon

Simultaneous tapping activated

ST

Mon

Quality: Simultaneous tapping


activated

ST

Mon

Timestamp: Simultaneous
tapping activated

stVal

ST

COMMERR

Mon

Communication error

ST

COMMERR

Mon

Quality: Communication error

ST

COMMERR

Mon

Timestamp: Communication error

stVal

ST

PGTFWD

Mon

Active power above the settable


limit powerActiveForw

ST

PGTFWD

Mon

Quality: Active power above the


settable limit powerActiveForw

ST

PGTFWD

Mon

Timestamp: Active power above


the settable limit powerActiveForw

stVal

ST

PLTREV

Mon

Active power below the settable


limit powerActiveRev

ST

PLTREV

Mon

Quality: Active power below the


settable limit powerActiveRev

ST

PLTREV

Mon

Timestamp: Active power below


the settable limit powerActiveRev

T6Master

T7Master

T8Master

Homing

SimTap

CommFlt

HiWFwd

HiWRv

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

Table continues on next page

76

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
HiVArFwd

HiVArRv

CircABlk

HiABlk

ExLowerBlk

ExRaiseBlk

RvActBlk

Adapt

DO type

DA name

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

stVal

ST

QGTFWD

Mon

Reactive power above the


settable limit powerReactiveForw

ST

QGTFWD

Mon

Quality: Reactive power above


the settable limit
powerReactiveForw

ST

QGTFWD

Mon

Timestamp: Reactive power


above the settable limit
powerReactiveForw

stVal

ST

QLTREV

Mon

Reactive power below the


settable limit powerReactiveRev

ST

QLTREV

Mon

Quality: Reactive power below


the settable limit
powerReactiveRev

ST

QLTREV

Mon

Timestamp: Reactive power


below the settable limit
powerReactiveRev

stVal

ST

ICIRC

Mon

Block from high circulating current

ST

ICIRC

Mon

Quality: Block from high


circulating current

ST

ICIRC

Mon

Timestamp: Block from high


circulating current

stVal

ST

IBLK

Mon

One phase current is above the


settable limit

ST

IBLK

Mon

Quality: One phase current is


above the settable limit

ST

IBLK

Mon

Timestamp: One phase current is


above the settable limit

stVal

ST

Mon

External block of lower command


activated

ST

Mon

Quality: External block of lower


command activated

ST

Mon

Timestamp: External block of


lower command activated

stVal

ST

Mon

External block of raise command


activated

ST

Mon

Quality: External block of raise


command activated

ST

Mon

Timestamp: External block of


raise command activated

stVal

ST

REVACBLK

Mon

Block caused by reversed action

ST

REVACBLK

Mon

Quality: Block caused by


reversed action

ST

REVACBLK

Mon

Timestamp: Block caused by


reversed action

stVal

ST

ADAPT

Mon

The transformer is adapting

ST

ADAPT

Mon

Quality: The transformer is


adapting

ST

ADAPT

Mon

Timestamp: The transformer is


adapting

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

77

Section 7
Logical node data model
DO name
DayHuntAlm

HrHuntAlm

HuntAlm

VDif

MSMode

Disc

TotBlock

AutoBlock

DO type
v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

DAYHUNT

Mon

Alarm for too many tap changer


operations during the last 24 hours

ST

DAYHUNT

Mon

Quality: Alarm for too many tap


changer operations during the
last 24 hours

ST

DAYHUNT

Mon

Timestamp: Alarm for too many


tap changer operations during the
last 24 hours

stVal

ST

HOURHUNT

Mon

Alarm for too many tap changer


operations during the last hour

ST

HOURHUNT

Mon

Quality: Alarm for too many tap


changer operations during the
last hour

ST

HOURHUNT

Mon

Timestamp: Alarm for too many


tap changer operations during the
last hour

stVal

ST

HUNTING

Mon

Alarm for too many contradictory


tap changer operations within the
time sliding window

ST

HUNTING

Mon

Quality: Alarm for too many


contradictory tap changer
operations within the time sliding
window

ST

HUNTING

Mon

Timestamp: Alarm for too many


contradictory tap changer
operations within the time sliding
window

stVal

ST

VTALARM

Mon

VT supervision alarm

ST

VTALARM

Mon

Quality: VT supervision alarm

ST

VTALARM

Mon

Timestamp: VT supervision alarm

stVal

ST

Mon

Master slave is active

ST

Mon

Quality: Master slave is active

ST

Mon

Timestamp: Master slave is active

stVal

ST

Mon

The transformer is disconnected

ST

Mon

Quality: The transformer is


disconnected

ST

Mon

Timestamp: The transformer is


disconnected

stVal

ST

TOTBLK

Mon

Block of auto and manual


commands

ST

TOTBLK

Mon

Quality: Block of auto and manual


commands

ST

TOTBLK

Mon

Timestamp: Block of auto and


manual commands

stVal

ST

AUTOBLK

Mon

Block of auto commands

ST

AUTOBLK

Mon

Quality: Block of auto commands

ST

AUTOBLK

Mon

Timestamp: Block of auto


commands

Table continues on next page

78

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
DiffPosMF

MFFlt

VCTRStatus

BndCtrAct

LodV

AverA

CCAV

Q1VAr

Q2VAr

DO type

DA name

v1_dSPS

v1_dSPS

v2_dINS

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

FC

Signal

Mon/
Cmd

Description

stVal

ST

OUTOFPOS

Mon

To high difference in tap positions

ST

OUTOFPOS

Mon

Quality: To high difference in tap


positions

ST

OUTOFPOS

Mon

Timestamp: To high difference in


tap positions

stVal

ST

MFERR

Mon

The number of masters is


different from one

ST

MFERR

Mon

Quality: The number of masters is


different from one

ST

MFERR

Mon

Timestamp: The number of


masters is different from one

stVal

ST

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

ST

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

ST

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

Mon

Actual voltage setpoint

MX

Mon

Quality: Actual voltage setpoint

MX

Mon

Timestamp: Actual voltage


setpoint

mag.f

MX

ULOAD

Mon

Calculated compensated voltage


(service value)

MX

ULOAD

Mon

Quality: Calculated compensated


voltage (service value)

MX

ULOAD

Mon

Timestamp: Calculated
compensated voltage (service
value)

mag.f

MX

IPRIM

Mon

Max of 3 phase currents (service


value)

MX

IPRIM

Mon

Quality: Max of 3 phase currents


(service value)

MX

IPRIM

Mon

Timestamp: Max of 3 phase


currents (service value)

mag.f

MX

CCAVolt

Mon

Circulating Current Adjusted


Voltage

MX

CCAVolt

Mon

Quality: Circulating Current


Adjusted Voltage

MX

CCAVolt

Mon

Timestamp: Circulating Current


Adjusted Voltage

mag.f

MX

Mon

Size of reactive bank1

MX

Mon

Quality: Size of reactive bank1

MX

Mon

Timestamp: Size of reactive bank1

mag.f

MX

Mon

Size of reactive bank2

MX

Mon

Quality: Size of reactive bank2

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

79

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Q2VAr

v2_dMV

MX

Mon

Timestamp: Size of reactive bank2

Q3VAr

v2_dMV

mag.f

MX

Mon

Size of reactive bank3

MX

Mon

Quality: Size of reactive bank3

MX

Mon

Timestamp: Size of reactive bank3

mag.f

MX

Mon

Load dependent automatic


reduction voltage

MX

Mon

Quality: Load dependent


automatic reduction voltage

MX

Mon

Timestamp: Load dependent


automatic reduction voltage

mag.f

MX

Mon

Voltage setpoint single

MX

Mon

Quality: Voltage setpoint single

MX

Mon

Timestamp: Voltage setpoint


single

mag.f

MX

USETPAR

Mon

Average voltage setpoint used in


parallel mode

MX

USETPAR

Mon

Quality: Average voltage setpoint


used in parallel mode

MX

USETPAR

Mon

Timestamp: Average voltage


setpoint used in parallel mode

mag.f

MX

Mon

Voltage setpoint set by user

MX

Mon

Quality: Voltage setpoint set by


user

MX

Mon

Timestamp: Voltage setpoint set


by user

mag.f

MX

Mon

Block level of circulating current

MX

Mon

Quality: Block level of circulating


current

MX

Mon

Timestamp: Block level of


circulating current

mag.f

MX

Mon

Value 1 for load voltage


adjustment

MX

Mon

Quality: Value 1 for load voltage


adjustment

MX

Mon

Timestamp: Value 1 for load


voltage adjustment

mag.f

MX

Mon

Value 2 for load voltage


adjustment

MX

Mon

Quality: Value 2 for load voltage


adjustment

MX

Mon

Timestamp: Value 2 for load


voltage adjustment

mag.f

MX

Mon

Value 3 for load voltage


adjustment

MX

Mon

Quality: Value 3 for load voltage


adjustment

AutoRedV

BndCtrSng

BndCtrPar

BndCtrSet

CircALim

LVA1V

LVA2V

LVA3V

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

Table continues on next page

80

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

LVA3V

v2_dMV

MX

Mon

Timestamp: Value 3 for load


voltage adjustment

LVA4V

v2_dMV

mag.f

MX

Mon

Value 4 for load voltage


adjustment

MX

Mon

Quality: Value 4 for load voltage


adjustment

MX

Mon

Timestamp: Value 4 for load


voltage adjustment

mag.f

MX

Mon

Average of measured busbar


voltage (service value)

MX

Mon

Quality: Average of measured


busbar voltage (service value)

MX

Mon

Timestamp: Average of
measured busbar voltage
(service value)

mag.f

MX

Mon

Calculated circulating voltage

MX

Mon

Quality: Calculated circulating


voltage

MX

Mon

Timestamp: Calculated circulating


voltage

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

AvBusV

CircV

LodAIm

LodARe

BusV

SetV

v2_dMV

v2_dMV

v3_dMV

v4_dMV

v5_dMV

v6_dMV

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

81

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

SetV

v6_dMV

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

PosRel

v7_dMV

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

mag.f

MX

ATCCOUT

Mon

Group connection to horizontal


communication and YLTCIN

MX

ATCCOUT

Mon

Quality: Group connection to


horizontal communication and
YLTCIN

MX

ATCCOUT

Mon

Timestamp: Group connection to


horizontal communication and
YLTCIN

X2

v8_dMV

7.2.1.2

Table 9:
DO name
Mod

Beh

Tap changer control and supervision, 6 binary inputs TCMYLTC and


TCLYLTC
LN type

LN prefix

LN class

Function block name

TCMYLTC (revision 5)

TCM

YLTC

TCMYLTC

TCMYLTC Logical node data


DO type
a_dINC

a_dINS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

Table continues on next page

82

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Beh

a_dINS

ST

Beh

Mon

Timestamp: Behaviour parameter

EndPosR

a_dSPS

stVal

ST

HIPOSAL

Mon

Alarm for tap in highest volt


position

ST

HIPOSAL

Mon

Quality: Alarm for tap in highest


volt position

ST

HIPOSAL

Mon

Timestamp: Alarm for tap in


highest volt position

stVal

ST

LOPOSAL

Mon

Alarm for tap in lowest volt position

ST

LOPOSAL

Mon

Quality: Alarm for tap in lowest


volt position

ST

LOPOSAL

Mon

Timestamp: Alarm for tap in


lowest volt position

valWTr.posVal

ST

TCPOS

Mon

Integer value corresponding to


actual tap position

valWTr.transInd

ST

Mon

Tap position change in progress

ST

TCPOS

Mon

Quality: Integer value


corresponding to actual tap
position

ST

TCPOS

Mon

Timestamp: Integer value


corresponding to actual tap
position

stVal

ST

CNT_VAL

Mon

Number of operations on tap


changer

ST

CNT_VAL

Mon

Quality: Number of operations on


tap changer

ST

CNT_VAL

Mon

Timestamp: Number of
operations on tap changer

stVal

ST

Mon

Tap position for highest voltage

ST

Mon

Quality: Tap position for highest


voltage

ST

Mon

Timestamp: Tap position for


highest voltage

stVal

ST

Mon

Tap position for lowest voltage

ST

Mon

Quality: Tap position for lowest


voltage

ST

Mon

Timestamp: Tap position for


lowest voltage

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

EndPosL

TapChg

OpCnt

HiTapPos

LoTapPos

OpRs

a_dSPS

b_dBSC

b_dINS

b_dINS

b_dINS

v1_dSPC

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

83

Section 7
Logical node data model
DO name
OpRs

CLRs

CmdFlt

ConvFlt

InvPosChg

TapChgFlt

TapPosFlt

DO type
v1_dSPC

v1_dSPC

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for Local


HMI

Oper.origin.orCat

CO

Cmd

Command parameter for Local


HMI

Oper.origin.orIdent

CO

Cmd

Command parameter for Local


HMI

Oper.ctlNum

CO

Cmd

Command parameter for Local


HMI

Oper.T

CO

Cmd

Command parameter for Local


HMI

Oper.Test

CO

Cmd

Command parameter for Local


HMI

Oper.Check

CO

Cmd

Command parameter for Local


HMI

stVal

ST

CMDERRAL

Mon

Alarm for a command without an


expected position change

ST

CMDERRAL

Mon

Quality: Alarm for a command


without an expected position
change

ST

CMDERRAL

Mon

Timestamp: Alarm for a


command without an expected
position change

stVal

ST

CONVERR

Mon

General tap position conversion


error

ST

CONVERR

Mon

Quality: General tap position


conversion error

ST

CONVERR

Mon

Timestamp: General tap position


conversion error

stVal

ST

INVALPOS

Mon

Last position change was an


invalid change

ST

INVALPOS

Mon

Quality: Last position change was


an invalid change

ST

INVALPOS

Mon

Timestamp: Last position change


was an invalid change

stVal

ST

TCERRAL

Mon

Alarm for none or illegal tap


position change

ST

TCERRAL

Mon

Quality: Alarm for none or illegal


tap position change

ST

TCERRAL

Mon

Timestamp: Alarm for none or


illegal tap position change

stVal

ST

POSERRAL

Mon

Alarm that indicates a problem


with the position indication

ST

POSERRAL

Mon

Quality: Alarm that indicates a


problem with the position
indication

Table continues on next page


84

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

TapPosFlt

v1_dSPS

ST

POSERRAL

Mon

Timestamp: Alarm that indicates


a problem with the position
indication

CLCnt

v2_dMV

mag.f

MX

CLCNT_VAL

Mon

Remaining number of operations


at rated load

MX

CLCNT_VAL

Mon

Quality: Remaining number of


operations at rated load

MX

CLCNT_VAL

Mon

Timestamp: Remaining number


of operations at rated load

7.3

Logical nodes for control

7.3.1

Bay control CBAY

7.3.1.1

Bay control QCBAY

Table 10:
DO name
Mod

Beh

LocSwPos

LN type

LN prefix

LN class

Function block name

QCBAY (revision 1)

CBAY

QCBAY

QCBAY Logical node data


DO type

DA name

a_dINC

a_dINS

v1_dINS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Position of the Local/Remote


switch

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

85

Section 7
Logical node data model
DO name
LocSwPos

SrcOpPrm

BlkCmd

BlkUpd

DO type
v1_dINS

v1_dINS

v1_dSPC

v1_dSPC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

Mon

Quality: Position of the Local/


Remote switch

ST

Mon

Timestamp: Position of the Local/


Remote switch

stVal

ST

PSTO

Mon

Value for the operator place


allocation

ST

PSTO

Mon

Quality: Value for the operator


place allocation

ST

PSTO

Mon

Timestamp: Value for the


operator place allocation

Oper.ctlVal

CO

Cmd

Special block command value


used for blockCommand

Oper.origin.orCat

CO

Cmd

Special block command value


used for blockCommand

Oper.origin.orIdent

CO

Cmd

Special block command value


used for blockCommand

Oper.ctlNum

CO

Cmd

Special block command value


used for blockCommand

Oper.T

CO

Cmd

Special block command value


used for blockCommand

Oper.Test

CO

Cmd

Special block command value


used for blockCommand

Oper.Check

CO

Cmd

Special block command value


used for blockCommand

stVal

ST

CMD_BLKD

Mon

Function is blocked for commands

ST

CMD_BLKD

Mon

Quality: Function is blocked for


commands

ST

CMD_BLKD

Mon

Timestamp: Function is blocked


for commands

Oper.ctlVal

CO

Cmd

Special block command value


used for blockUpdate

Oper.origin.orCat

CO

Cmd

Special block command value


used for blockUpdate

Oper.origin.orIdent

CO

Cmd

Special block command value


used for blockUpdate

Oper.ctlNum

CO

Cmd

Special block command value


used for blockUpdate

Oper.T

CO

Cmd

Special block command value


used for blockUpdate

Oper.Test

CO

Cmd

Special block command value


used for blockUpdate

Oper.Check

CO

Cmd

Special block command value


used for blockUpdate

stVal

ST

UPD_BLKD

Mon

Update of position is blocked

ST

UPD_BLKD

Mon

Quality: Update of position is


blocked

ST

UPD_BLKD

Mon

Timestamp: Update of position is


blocked

Table continues on next page


86

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
BlkMeas

Loc

Rem

DO type

DA name

v1_dSPS

v1_dSPS

v1_dSPS

FC

stVal

ST

Mon

Update of measurand is blocked

ST

Mon

Quality: Update of measurand is


blocked

ST

Mon

Timestamp: Update of
measurand is blocked

stVal

ST

LOC

Mon

Local operation allowed

ST

LOC

Mon

Quality: Local operation allowed

ST

LOC

Mon

Timestamp: Local operation


allowed

stVal

ST

REM

Mon

Remote operation allowed

ST

REM

Mon

Quality: Remote operation allowed

ST

REM

Mon

Timestamp: Remote operation


allowed

7.3.2

Table 11:
DO name
Mod

Beh

EnaCls

Signal

Mon/
Cmd

Description

Logical node for interlocking SCILO


LN type

LN prefix

LN class

Function block name

SCILO (revision 0)

CILO

SCILO

SCILO Logical node data


DO type

DA name

aINC

aINS

aSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

EN_CLOSE

Mon

Close operation at open or


interm. or bad pos. is enabled

ST

EN_CLOSE

Mon

Quality: Close operation at open


or interm. or bad pos. is enabled

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

87

Section 7
Logical node data model
DO name

DO type

EnaCls

aSPS

EnaOpn

aSPS

DA name

1MRK 511 302-UEN -

FC

Signal

ST

EN_CLOSE

Mon

Timestamp: Close operation at


open or interm. or bad pos. is
enabled

stVal

ST

EN_OPEN

Mon

Open operation at closed or


interm. or bad pos. is enabled

ST

EN_OPEN

Mon

Quality: Open operation at closed


or interm. or bad pos. is enabled

ST

EN_OPEN

Mon

Timestamp: Open operation at


closed or interm. or bad pos. is
enabled

7.3.3

Switch controller CSWI

7.3.3.1

Switch controller SCSWI

Table 12:
DO name
Pos

Mon/
Cmd

LN type

LN prefix

LN class

Function block name

SCSWI (revision 1)

CSWI

SCSWI

Description

SCSWI Logical node data


DO type
a_dDPC

DA name

FC

Signal

Mon/
Cmd

Description

Cancel.ctlVal

CO

Cmd

Command parameter for


IEC61850

Cancel.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

SBOw.ctlVal

CO

Cmd

Command parameter for


IEC61850

SBOw.origin.orCat

CO

Cmd

Command parameter for


IEC61850

SBOw.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Cancel.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Cancel.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

SBOw.ctlNum

CO

Cmd

Command parameter for


IEC61850

Table continues on next page

88

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Pos

Mod

Beh

OpCls

DO type

DA name

a_dDPC

a_dINC

a_dINS

b_dACT

FC

Signal

Mon/
Cmd

Description

SBOw.T

CO

Cmd

Command parameter for


IEC61850

Cancel.T

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Cancel.Test

CO

Cmd

Command parameter for


IEC61850

SBOw.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

SBOw.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

POSITION

Mon

Position indication

ST

POSITION

Mon

Quality: Position indication

ST

POSITION

Mon

Timestamp: Position indication

stSeld

ST

SELECTED

Mon

Select conditions are fulfilled

subEna

SV

Substitute enable

subVal

SV

Substituted double position value

ctlModel

CF

CtlModel

Specifies control model type

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

EXE_CL

Mon

Execute command for close


direction

ST

EXE_CL

Mon

Quality: Execute command for


close direction

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

89

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

OpCls

b_dACT

ST

EXE_CL

Mon

Timestamp: Execute command


for close direction

OpOpn

b_dACT

general

ST

EXE_OP

Mon

Execute command for open


direction

ST

EXE_OP

Mon

Quality: Execute command for


open direction

ST

EXE_OP

Mon

Timestamp: Execute command


for open direction

Oper.ctlVal

CO

Cmd

Special block command value

Oper.origin.orCat

CO

Cmd

Special block command value

Oper.origin.orIdent

CO

Cmd

Special block command value

Oper.ctlNum

CO

Cmd

Special block command value

Oper.T

CO

Cmd

Special block command value

Oper.Test

CO

Cmd

Special block command value

Oper.Check

CO

Cmd

Special block command value

stVal

ST

CMD_BLK

Mon

Commands are blocked

ST

CMD_BLK

Mon

Quality: Commands are blocked

ST

CMD_BLK

Mon

Timestamp: Commands are


blocked

BlkCmd

v1_dSPC

7.3.4

Table 13:
DO name
Mod

Beh

Bay reserve function QCRSV


LN type

LN prefix

LN class

Function block name

QCRSV (revision 0)

CRSV

QCRSV

QCRSV Logical node data


DO type
aINC

aINS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

Table continues on next page


90

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

Beh

aINS

AckRsvBay

v1SPS

PrmOp1

PrmOp2

PrmOp3

PrmOp4

PrmOp5

PrmOp6

DA name

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

FC

Signal

Mon/
Cmd

Description

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

ACK_TO_B

Mon

Acknowledge to other bays that


this bay is reserved

ST

ACK_TO_B

Mon

Quality: Acknowledge to other


bays that this bay is reserved

ST

ACK_TO_B

Mon

Timestamp: Acknowledge to
other bays that this bay is reserved

stVal

ST

RES_GRT1

Mon

Reservation is made and the app.


1 is allowed to operate

ST

RES_GRT1

Mon

Quality: Reservation is made and


the app. 1 is allowed to operate

ST

RES_GRT1

Mon

Timestamp: Reservation is made


and the app. 1 is allowed to
operate

stVal

ST

RES_GRT2

Mon

Reservation is made and the app.


2 is allowed to operate

ST

RES_GRT2

Mon

Quality: Reservation is made and


the app. 2 is allowed to operate

ST

RES_GRT2

Mon

Timestamp: Reservation is made


and the app. 2 is allowed to
operate

stVal

ST

RES_GRT3

Mon

Reservation is made and the app.


3 is allowed to operate

ST

RES_GRT3

Mon

Quality: Reservation is made and


the app. 3 is allowed to operate

ST

RES_GRT3

Mon

Timestamp: Reservation is made


and the app. 3 is allowed to
operate

stVal

ST

RES_GRT4

Mon

Reservation is made and the app.


4 is allowed to operate

ST

RES_GRT4

Mon

Quality: Reservation is made and


the app. 4 is allowed to operate

ST

RES_GRT4

Mon

Timestamp: Reservation is made


and the app. 4 is allowed to
operate

stVal

ST

RES_GRT5

Mon

Reservation is made and the app.


5 is allowed to operate

ST

RES_GRT5

Mon

Quality: Reservation is made and


the app. 5 is allowed to operate

ST

RES_GRT5

Mon

Timestamp: Reservation is made


and the app. 5 is allowed to
operate

stVal

ST

RES_GRT6

Mon

Reservation is made and the app.


6 is allowed to operate

ST

RES_GRT6

Mon

Quality: Reservation is made and


the app. 6 is allowed to operate

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

91

Section 7
Logical node data model
DO name

DO type

PrmOp6

v1SPS

PrmOp7

v1SPS

PrmOp8

RqRsvBay

Rsv

v1SPS

v1SPS

v1SPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

RES_GRT6

Mon

Timestamp: Reservation is made


and the app. 6 is allowed to
operate

stVal

ST

RES_GRT7

Mon

Reservation is made and the app.


7 is allowed to operate

ST

RES_GRT7

Mon

Quality: Reservation is made and


the app. 7 is allowed to operate

ST

RES_GRT7

Mon

Timestamp: Reservation is made


and the app. 7 is allowed to
operate

stVal

ST

RES_GRT8

Mon

Reservation is made and the app.


8 is allowed to operate

ST

RES_GRT8

Mon

Quality: Reservation is made and


the app. 8 is allowed to operate

ST

RES_GRT8

Mon

Timestamp: Reservation is made


and the app. 8 is allowed to
operate

stVal

ST

RES_BAYS

Mon

Request for reservation of other


bays

ST

RES_BAYS

Mon

Quality: Request for reservation


of other bays

ST

RES_BAYS

Mon

Timestamp: Request for


reservation of other bays

stVal

ST

RESERVED

Mon

Indicates that the bay is reserved

ST

RESERVED

Mon

Quality: Indicates that the bay is


reserved

ST

RESERVED

Mon

Timestamp: Indicates that the bay


is reserved

7.4

Logical nodes for conversion functions

7.4.1

Integer to Boolean converter FCVB

7.4.1.1

Integer to Boolean 16 conversion with logic node representation


ITBGAPC

92

LN type

LN prefix

LN class

Function block name

IB16FCVB (revision 0)

IB16

FCVB

ITBGAPC

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 14:
DO name
Mod

Beh

ISCSO

ITBGAPC Logical node data


DO type

DA name

a_dINC

a_dINS

b_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

Mon

Integer to be converted to bit


pattern OUT1 to OUT16

ST

Mon

Quality: Integer to be converted


to bit pattern OUT1 to OUT16

ST

Mon

Timestamp: Integer to be
converted to bit pattern OUT1 to
OUT16

ctlModel

CF

Used by CH

93

Section 7
Logical node data model

1MRK 511 302-UEN -

7.4.2

Boolean to integer converter FCVI

7.4.2.1

Boolean 16 to Integer conversion with logic node representation


BTIGAPC

Table 15:
DO name
Mod

Beh

OutInt

LN type

LN prefix

LN class

Function block name

B16IFCVI (revision 0)

B16I

FCVI

BTIGAPC

BTIGAPC Logical node data


DO type
a_dINC

a_dINS

b_dINS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

OUT

Mon

Output value

ST

OUT

Mon

Quality: Output value

ST

OUT

Mon

Timestamp: Output value

7.5

Logical nodes for protection functions

7.5.1

Differential protection PDIF

7.5.1.1

Transformer differential protection, two winding T2WPDIF

94

LN type

LN prefix

LN class

Function block name

T2WPDIF (revision 1)

T2W

PDIF

T2WPDIF

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 16:
DO name
Str

Mod

Beh

Op

OpnCTVal

OpnCTIn

OpnCTPh

T2WPDIF Logical node data


DO type

DA name

aACD

aINC

aINS

bACT

v1INS

v1INS

v1INS

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common start signal from any


phase

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: Common start signal


from any phase

ST

START

Mon

Timestamp: Common start signal


from any phase

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRIP

Mon

General, common trip signal

ST

TRIP

Mon

Quality: General, common trip


signal

ST

TRIP

Mon

Timestamp: General, common


trip signal

stVal

ST

OCTSIDE

Mon

Open CT side : 1 -> W 1 (pri), 2 > W 2 (sec)

ST

OCTSIDE

Mon

Quality: Open CT side : 1 -> W 1


(pri), 2 -> W 2 (sec)

ST

OCTSIDE

Mon

Timestamp: Open CT side : 1 ->


W 1 (pri), 2 -> W 2 (sec)

stVal

ST

OPENCTIN

Mon

Open CT on Input : 1 for input 1,


2 for input 2

ST

OPENCTIN

Mon

Quality: Open CT on Input : 1 for


input 1, 2 for input 2

ST

OPENCTIN

Mon

Timestamp: Open CT on Input : 1


for input 1, 2 for input 2

stVal

ST

OPENCTPH

Mon

Open CT in Phase : 1 for L1, 2 for


L2, 3 for L3

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

95

Section 7
Logical node data model
DO name
OpnCTPh

OpRst

OpNSSen

OpNSUnRst

OpUnRst

Blk2H

Blk5H

BlkWav

DO type
v1INS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

OPENCTPH

Mon

Quality: Open CT in Phase : 1 for


L1, 2 for L2, 3 for L3

ST

OPENCTPH

Mon

Timestamp: Open CT in Phase :


1 for L1, 2 for L2, 3 for L3

stVal

ST

TRIPRES

Mon

Trip signal from restrained


differential protection

ST

TRIPRES

Mon

Quality: Trip signal from


restrained differential protection

ST

TRIPRES

Mon

Timestamp: Trip signal from


restrained differential protection

stVal

ST

TRNSSENS

Mon

Trip signal from sensitive neg.


seq. diff. protection

ST

TRNSSENS

Mon

Quality: Trip signal from sensitive


neg. seq. diff. protection

ST

TRNSSENS

Mon

Timestamp: Trip signal from


sensitive neg. seq. diff. protection

stVal

ST

TRNSUNR

Mon

Trip signal from unrestr. neg. seq.


diff. protection

ST

TRNSUNR

Mon

Quality: Trip signal from unrestr.


neg. seq. diff. protection

ST

TRNSUNR

Mon

Timestamp: Trip signal from


unrestr. neg. seq. diff. protection

stVal

ST

TRIPUNRE

Mon

Trip signal from unrestrained


differential protection

ST

TRIPUNRE

Mon

Quality: Trip signal from


unrestrained differential protection

ST

TRIPUNRE

Mon

Timestamp: Trip signal from


unrestrained differential protection

stVal

ST

BLK2H

Mon

Common second harmonic block


signal from any phase

ST

BLK2H

Mon

Quality: Common second


harmonic block signal from any
phase

ST

BLK2H

Mon

Timestamp: Common second


harmonic block signal from any
phase

stVal

ST

BLK5H

Mon

Common fifth harmonic block


signal from any phase

ST

BLK5H

Mon

Quality: Common fifth harmonic


block signal from any phase

ST

BLK5H

Mon

Timestamp: Common fifth


harmonic block signal from any
phase

stVal

ST

BLKWAV

Mon

Common block signal, waveform


criterion, from any phase

ST

BLKWAV

Mon

Quality: Common block signal,


waveform criterion, from any
phase

Table continues on next page

96

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

BlkWav

v1SPS

ExFlt

v1SPS

ItrFlt

Blk2HPhA

Blk2HPhB

Blk2HPhC

Blk5HPhA

Blk5HPhB

Blk5HPhC

DA name

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

FC

Signal

Mon/
Cmd

Description

ST

BLKWAV

Mon

Timestamp: Common block


signal, waveform criterion, from
any phase

stVal

ST

Mon

Indication that external fault/


disturbance has been detected

ST

Mon

Quality: Indication that external


fault/disturbance has been
detected

ST

Mon

Timestamp: Indication that


external fault/disturbance has
been detected

stVal

ST

Mon

Indication that internal fault has


been detected

ST

Mon

Quality: Indication that internal


fault has been detected

ST

Mon

Timestamp: Indication that


internal fault has been detected

stVal

ST

BLK2HL1

Mon

Second harmonic block signal,


phase L1

ST

BLK2HL1

Mon

Quality: Second harmonic block


signal, phase L1

ST

BLK2HL1

Mon

Timestamp: Second harmonic


block signal, phase L1

stVal

ST

BLK2HL2

Mon

Second harmonic block signal,


phase L2

ST

BLK2HL2

Mon

Quality: Second harmonic block


signal, phase L2

ST

BLK2HL2

Mon

Timestamp: Second harmonic


block signal, phase L2

stVal

ST

BLK2HL3

Mon

Second harmonic block signal,


phase L3

ST

BLK2HL3

Mon

Quality: Second harmonic block


signal, phase L3

ST

BLK2HL3

Mon

Timestamp: Second harmonic


block signal, phase L3

stVal

ST

BLK5HL1

Mon

Fifth harmonic block signal,


phase L1

ST

BLK5HL1

Mon

Quality: Fifth harmonic block


signal, phase L1

ST

BLK5HL1

Mon

Timestamp: Fifth harmonic block


signal, phase L1

stVal

ST

BLK5HL2

Mon

Fifth harmonic block signal,


phase L2

ST

BLK5HL2

Mon

Quality: Fifth harmonic block


signal, phase L2

ST

BLK5HL2

Mon

Timestamp: Fifth harmonic block


signal, phase L2

stVal

ST

BLK5HL3

Mon

Fifth harmonic block signal,


phase L3

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

97

Section 7
Logical node data model
DO name
Blk5HPhC

BlkWavPhA

BlkWavPhB

BlkWavPhC

OpnCT

OpnCTAlm

DifAlm

7.5.1.2

98

DO type
v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

BLK5HL3

Mon

Quality: Fifth harmonic block


signal, phase L3

ST

BLK5HL3

Mon

Timestamp: Fifth harmonic block


signal, phase L3

stVal

ST

BLKWAVL1

Mon

Block signal, waveform criterion,


phase L1

ST

BLKWAVL1

Mon

Quality: Block signal, waveform


criterion, phase L1

ST

BLKWAVL1

Mon

Timestamp: Block signal,


waveform criterion, phase L1

stVal

ST

BLKWAVL2

Mon

Block signal, waveform criterion,


phase L2

ST

BLKWAVL2

Mon

Quality: Block signal, waveform


criterion, phase L2

ST

BLKWAVL2

Mon

Timestamp: Block signal,


waveform criterion, phase L2

stVal

ST

BLKWAVL3

Mon

Block signal, waveform criterion,


phase L3

ST

BLKWAVL3

Mon

Quality: Block signal, waveform


criterion, phase L3

ST

BLKWAVL3

Mon

Timestamp: Block signal,


waveform criterion, phase L3

stVal

ST

OPENCT

Mon

An open CT was detected

ST

OPENCT

Mon

Quality: An open CT was detected

ST

OPENCT

Mon

Timestamp: An open CT was


detected

stVal

ST

OPENCTAL

Mon

Open CT Alarm output signal.


Issued after a delay ...

ST

OPENCTAL

Mon

Quality: Open CT Alarm output


signal. Issued after a delay ...

ST

OPENCTAL

Mon

Timestamp: Open CT Alarm


output signal. Issued after a
delay ...

stVal

ST

IDALARM

Mon

Alarm for sustained diff currents


in all three phases

ST

IDALARM

Mon

Quality: Alarm for sustained diff


currents in all three phases

ST

IDALARM

Mon

Timestamp: Alarm for sustained


diff currents in all three phases

Transformer differential protection, three winding T3WPDIF


LN type

LN prefix

LN class

Function block name

T3WPDIF (revision 1)

T3W

PDIF

T3WPDIF

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 17:
DO name
Str

Mod

Beh

Op

OpnCTVal

OpnCTIn

OpnCTPh

T3WPDIF Logical node data


DO type

DA name

aACD

aINC

aINS

bACT

v1INS

v1INS

v1INS

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common start signal from any


phase

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: Common start signal


from any phase

ST

START

Mon

Timestamp: Common start signal


from any phase

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRIP

Mon

General, common trip signal

ST

TRIP

Mon

Quality: General, common trip


signal

ST

TRIP

Mon

Timestamp: General, common


trip signal

stVal

ST

OCTSIDE

Mon

Open CT side : 1 -> W 1 (pri), 2 > W 2 (sec), 3 -> W 3

ST

OCTSIDE

Mon

Quality: Open CT side : 1 -> W 1


(pri), 2 -> W 2 (sec), 3 -> W 3

ST

OCTSIDE

Mon

Timestamp: Open CT side : 1 ->


W 1 (pri), 2 -> W 2 (sec), 3 -> W 3

stVal

ST

OPENCTIN

Mon

Open CT on Input : 1 for input 1,


2 for input 2

ST

OPENCTIN

Mon

Quality: Open CT on Input : 1 for


input 1, 2 for input 2

ST

OPENCTIN

Mon

Timestamp: Open CT on Input : 1


for input 1, 2 for input 2

stVal

ST

OPENCTPH

Mon

Open CT in Phase : 1 for L1, 2 for


L2, 3 for L3

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

99

Section 7
Logical node data model
DO name
OpnCTPh

OpRst

OpNSSen

OpNSUnRst

OpUnRst

Blk2H

Blk5H

BlkWav

DO type
v1INS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

OPENCTPH

Mon

Quality: Open CT in Phase : 1 for


L1, 2 for L2, 3 for L3

ST

OPENCTPH

Mon

Timestamp: Open CT in Phase :


1 for L1, 2 for L2, 3 for L3

stVal

ST

TRIPRES

Mon

Trip signal from restrained


differential protection

ST

TRIPRES

Mon

Quality: Trip signal from


restrained differential protection

ST

TRIPRES

Mon

Timestamp: Trip signal from


restrained differential protection

stVal

ST

TRNSSENS

Mon

Trip signal from sensitive neg.


seq. diff. protection

ST

TRNSSENS

Mon

Quality: Trip signal from sensitive


neg. seq. diff. protection

ST

TRNSSENS

Mon

Timestamp: Trip signal from


sensitive neg. seq. diff. protection

stVal

ST

TRNSUNR

Mon

Trip signal from unrestr. neg. seq.


diff. protection

ST

TRNSUNR

Mon

Quality: Trip signal from unrestr.


neg. seq. diff. protection

ST

TRNSUNR

Mon

Timestamp: Trip signal from


unrestr. neg. seq. diff. protection

stVal

ST

TRIPUNRE

Mon

Trip signal from unrestrained


differential protection

ST

TRIPUNRE

Mon

Quality: Trip signal from


unrestrained differential protection

ST

TRIPUNRE

Mon

Timestamp: Trip signal from


unrestrained differential protection

stVal

ST

BLK2H

Mon

Common second harmonic block


signal from any phase

ST

BLK2H

Mon

Quality: Common second


harmonic block signal from any
phase

ST

BLK2H

Mon

Timestamp: Common second


harmonic block signal from any
phase

stVal

ST

BLK5H

Mon

Common fifth harmonic block


signal from any phase

ST

BLK5H

Mon

Quality: Common fifth harmonic


block signal from any phase

ST

BLK5H

Mon

Timestamp: Common fifth


harmonic block signal from any
phase

stVal

ST

BLKWAV

Mon

Common block signal, waveform


criterion, from any phase

ST

BLKWAV

Mon

Quality: Common block signal,


waveform criterion, from any
phase

Table continues on next page

100

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

BlkWav

v1SPS

ExFlt

v1SPS

ItrFlt

Blk2HPhA

Blk2HPhB

Blk2HPhC

Blk5HPhA

Blk5HPhB

Blk5HPhC

DA name

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

FC

Signal

Mon/
Cmd

Description

ST

BLKWAV

Mon

Timestamp: Common block


signal, waveform criterion, from
any phase

stVal

ST

Mon

Indication that external fault/


disturbance has been detected

ST

Mon

Quality: Indication that external


fault/disturbance has been
detected

ST

Mon

Timestamp: Indication that


external fault/disturbance has
been detected

stVal

ST

Mon

Indication that internal fault has


been detected

ST

Mon

Quality: Indication that internal


fault has been detected

ST

Mon

Timestamp: Indication that


internal fault has been detected

stVal

ST

BLK2HL1

Mon

Second harmonic block signal,


phase L1

ST

BLK2HL1

Mon

Quality: Second harmonic block


signal, phase L1

ST

BLK2HL1

Mon

Timestamp: Second harmonic


block signal, phase L1

stVal

ST

BLK2HL2

Mon

Second harmonic block signal,


phase L2

ST

BLK2HL2

Mon

Quality: Second harmonic block


signal, phase L2

ST

BLK2HL2

Mon

Timestamp: Second harmonic


block signal, phase L2

stVal

ST

BLK2HL3

Mon

Second harmonic block signal,


phase L3

ST

BLK2HL3

Mon

Quality: Second harmonic block


signal, phase L3

ST

BLK2HL3

Mon

Timestamp: Second harmonic


block signal, phase L3

stVal

ST

BLK5HL1

Mon

Fifth harmonic block signal,


phase L1

ST

BLK5HL1

Mon

Quality: Fifth harmonic block


signal, phase L1

ST

BLK5HL1

Mon

Timestamp: Fifth harmonic block


signal, phase L1

stVal

ST

BLK5HL2

Mon

Fifth harmonic block signal,


phase L2

ST

BLK5HL2

Mon

Quality: Fifth harmonic block


signal, phase L2

ST

BLK5HL2

Mon

Timestamp: Fifth harmonic block


signal, phase L2

stVal

ST

BLK5HL3

Mon

Fifth harmonic block signal,


phase L3

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

101

Section 7
Logical node data model
DO name
Blk5HPhC

BlkWavPhA

BlkWavPhB

BlkWavPhC

OpnCT

OpnCTAlm

DifAlm

7.5.1.3

102

DO type
v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

BLK5HL3

Mon

Quality: Fifth harmonic block


signal, phase L3

ST

BLK5HL3

Mon

Timestamp: Fifth harmonic block


signal, phase L3

stVal

ST

BLKWAVL1

Mon

Block signal, waveform criterion,


phase L1

ST

BLKWAVL1

Mon

Quality: Block signal, waveform


criterion, phase L1

ST

BLKWAVL1

Mon

Timestamp: Block signal,


waveform criterion, phase L1

stVal

ST

BLKWAVL2

Mon

Block signal, waveform criterion,


phase L2

ST

BLKWAVL2

Mon

Quality: Block signal, waveform


criterion, phase L2

ST

BLKWAVL2

Mon

Timestamp: Block signal,


waveform criterion, phase L2

stVal

ST

BLKWAVL3

Mon

Block signal, waveform criterion,


phase L3

ST

BLKWAVL3

Mon

Quality: Block signal, waveform


criterion, phase L3

ST

BLKWAVL3

Mon

Timestamp: Block signal,


waveform criterion, phase L3

stVal

ST

OPENCT

Mon

An open CT was detected

ST

OPENCT

Mon

Quality: An open CT was detected

ST

OPENCT

Mon

Timestamp: An open CT was


detected

stVal

ST

OPENCTAL

Mon

Open CT Alarm output signal.


Issued after a delay ...

ST

OPENCTAL

Mon

Quality: Open CT Alarm output


signal. Issued after a delay ...

ST

OPENCTAL

Mon

Timestamp: Open CT Alarm


output signal. Issued after a
delay ...

stVal

ST

IDALARM

Mon

Alarm for sustained diff currents


in all three phases

ST

IDALARM

Mon

Quality: Alarm for sustained diff


currents in all three phases

ST

IDALARM

Mon

Timestamp: Alarm for sustained


diff currents in all three phases

Low impedance restricted earth fault protection REFPDIF


LN type

LN prefix

LN class

Function block name

REFPDIF (revision 1)

REF

PDIF

REFPDIF

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 18:
DO name
Mod

Beh

Str

Op

Blk2H

ItrFlt

REFPDIF Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

v1_dSPS

7.5.1.4

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

START

Mon

Start by restricted earth fault


protection function

ST

START

Mon

Quality: Start by restricted earth


fault protection function

ST

START

Mon

Timestamp: Start by restricted


earth fault protection function

general

ST

TRIP

Mon

Trip by restricted earth fault


protection function

ST

TRIP

Mon

Quality: Trip by restricted earth


fault protection function

ST

TRIP

Mon

Timestamp: Trip by restricted


earth fault protection function

stVal

ST

BLK2H

Mon

Block due to 2-nd harmonic

ST

BLK2H

Mon

Quality: Block due to 2-nd


harmonic

ST

BLK2H

Mon

Timestamp: Block due to 2-nd


harmonic

stVal

ST

DIROK

Mon

Directional Criteria has operated


for internal fault

ST

DIROK

Mon

Quality: Directional Criteria has


operated for internal fault

ST

DIROK

Mon

Timestamp: Directional Criteria


has operated for internal fault

Generator differential protection GENPDIF


LN type

LN prefix

LN class

Function block name

GENPDIF (revision 1)

GEN

PDIF

GENPDIF
103

Section 7
Logical node data model

Table 19:
DO name
Str

Mod

Beh

Op

OpnCTVal

OpnCTIn

1MRK 511 302-UEN -

GENPDIF Logical node data


DO type

DA name

aACD

aINC

aINS

bACT

v1INS

v1INS

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common start signal from any


phase

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: Common start signal


from any phase

ST

START

Mon

Timestamp: Common start signal


from any phase

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

General, common trip signal

ST

TRIP

Mon

Quality: General, common trip


signal

ST

TRIP

Mon

Timestamp: General, common


trip signal

stVal

ST

OPENCTSI

Mon

Open CT side : 1 -> Terminal


side, 2 -> Neutral side

ST

OPENCTSI

Mon

Quality: Open CT side : 1 ->


Terminal side, 2 -> Neutral side

ST

OPENCTSI

Mon

Timestamp: Open CT side : 1 ->


Terminal side, 2 -> Neutral side

stVal

ST

OPENCTIN

Mon

Open CT on Input : 1 for input 1,


2 for input 2

ST

OPENCTIN

Mon

Quality: Open CT on Input : 1 for


input 1, 2 for input 2

ST

OPENCTIN

Mon

Timestamp: Open CT on Input : 1


for input 1, 2 for input 2

Table continues on next page

104

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
OpnCTPh

OpRst

OpUnRst

OpNSUnRst

OpNSSen

ItrFlt

ExFlt

BlkH

DO type

DA name

v1INS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

FC

Signal

Mon/
Cmd

Description

stVal

ST

OPENCTPH

Mon

Open CT in Phase : 1 for L1, 2 for


L2, 3 for L3

ST

OPENCTPH

Mon

Quality: Open CT in Phase : 1 for


L1, 2 for L2, 3 for L3

ST

OPENCTPH

Mon

Timestamp: Open CT in Phase :


1 for L1, 2 for L2, 3 for L3

stVal

ST

TRIPRES

Mon

Trip signal from restrained


differential protection

ST

TRIPRES

Mon

Quality: Trip signal from


restrained differential protection

ST

TRIPRES

Mon

Timestamp: Trip signal from


restrained differential protection

stVal

ST

TRIPUNRE

Mon

Trip signal from unrestrained


differential protection

ST

TRIPUNRE

Mon

Quality: Trip signal from


unrestrained differential protection

ST

TRIPUNRE

Mon

Timestamp: Trip signal from


unrestrained differential protection

stVal

ST

TRNSUNR

Mon

Trip signal from unrestr. neg. seq.


diff. protection

ST

TRNSUNR

Mon

Quality: Trip signal from unrestr.


neg. seq. diff. protection

ST

TRNSUNR

Mon

Timestamp: Trip signal from


unrestr. neg. seq. diff. protection

stVal

ST

TRNSSENS

Mon

Trip signal from sensitive neg.


seq. diff. protection

ST

TRNSSENS

Mon

Quality: Trip signal from sensitive


neg. seq. diff. protection

ST

TRNSSENS

Mon

Timestamp: Trip signal from


sensitive neg. seq. diff. protection

stVal

ST

Mon

Indication that internal fault has


been detected

ST

Mon

Quality: Indication that internal


fault has been detected

ST

Mon

Timestamp: Indication that


internal fault has been detected

stVal

ST

Mon

Indication that external fault/


disturbance has been detected

ST

Mon

Quality: Indication that external


fault/disturbance has been
detected

ST

Mon

Timestamp: Indication that


external fault/disturbance has
been detected

stVal

ST

BLKH

Mon

Common harmonic block signal

ST

BLKH

Mon

Quality: Common harmonic block


signal

ST

BLKH

Mon

Timestamp: Common harmonic


block signal

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

105

Section 7
Logical node data model
DO name

DO type

BlkHPhA

v1SPS

BlkHPhB

BlkHPhC

OpnCT

OpnCTAlm

DifANS

RstMaxA

7.5.1.5

106

v1SPS

v1SPS

v1SPS

v1SPS

v2MV

v2MV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Harmonic block signal, phase L1

ST

Mon

Quality: Harmonic block signal,


phase L1

ST

Mon

Timestamp: Harmonic block


signal, phase L1

stVal

ST

Mon

Harmonic block signal, phase L2

ST

Mon

Quality: Harmonic block signal,


phase L2

ST

Mon

Timestamp: Harmonic block


signal, phase L2

stVal

ST

Mon

Harmonic block signal, phase L3

ST

Mon

Quality: Harmonic block signal,


phase L3

ST

Mon

Timestamp: Harmonic block


signal, phase L3

stVal

ST

OPENCT

Mon

An open CT was detected

ST

OPENCT

Mon

Quality: An open CT was detected

ST

OPENCT

Mon

Timestamp: An open CT was


detected

stVal

ST

OPENCTAL

Mon

Open CT Alarm output signal.


Issued after a delay ...

ST

OPENCTAL

Mon

Quality: Open CT Alarm output


signal. Issued after a delay ...

ST

OPENCTAL

Mon

Timestamp: Open CT Alarm


output signal. Issued after a
delay ...

mag.f

MX

IDNSMAG

Mon

Negative Sequence Differential


current; in primary Amperes

MX

IDNSMAG

Mon

Quality: Negative Sequence


Differential current; in primary
Amperes

MX

IDNSMAG

Mon

Timestamp: Negative Sequence


Differential current; in primary
Amperes

mag.f

MX

IBIAS

Mon

Magnitude of the common Bias


current; in primary Amperes

MX

IBIAS

Mon

Quality: Magnitude of the


common Bias current; in primary
Amperes

MX

IBIAS

Mon

Timestamp: Magnitude of the


common Bias current; in primary
Amperes

1Ph High impedance differential protection HZPDIF


LN type

LN prefix

LN class

Function block name

HZPDIF (revision 2)

HZ

PDIF

HZPDIF
670 series 2.0 IEC
Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 20:
DO name
Mod

Beh

Alm

Op

HZPDIF Logical node data


DO type

DA name

a_dINC

a_dINS

a_dSPS

b_dACT

DO name
Op

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

ALARM

Mon

Alarm signal

ST

ALARM

Mon

Quality: Alarm signal

ST

ALARM

Mon

Timestamp: Alarm signal

general

ST

TRIP

Mon

Trip signal

ST

TRIP

Mon

Quality: Trip signal

ST

TRIP

Mon

Timestamp: Trip signal

7.5.1.6

Table 21:

FC

Busbar differential protection, 2 zones, three phase BCZTPDIF


LN type

LN prefix

LN class

Function block name

BCZTPDIF instance 3 (revision 0)

BCZT

PDIF

BCZTPDIF

BCZTPDIF Logical node data (instance 3)


DO type

DA name

FC

aACT

general

ST

phsA

Signal

Mon/
Cmd

Description

TRIP

Mon

Check zone general trip

ST

TRL1

Mon

Check zone trip phase L1

phsB

ST

TRL2

Mon

Check zone trip phase L2

phsC

ST

TRL3

Mon

Check zone trip phase L3

ST

TRIP

Mon

Quality: Check zone general trip

ST

TRIP

Mon

Timestamp: Check zone general


trip

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

107

Section 7
Logical node data model
DO name
Beh

DO type
aINS

DA name

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

7.5.1.7

Table 22:
DO name
Beh

Op

DO name
Str

Op

Description

Busbar differential protection, 2 zones, single phase BCZSPDIF


LN type

LN prefix

LN class

Function block name

BCZSPDIF instance 3 (revision 0)

BCZS

PDIF

BCZSPDIF

BCZSPDIF Logical node data (instance 3)


DO type
aINS

bACT

DA name

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRIP

Mon

Check zone general trip

ST

TRIP

Mon

Quality: Check zone general trip

ST

TRIP

Mon

Timestamp: Check zone general


trip

7.5.1.8

Table 23:

1MRK 511 302-UEN -

Description

Line differential protection, 3 CT sets, 23 line ends L3CPDIF


LN type

LN prefix

LN class

Function block name

L3CPDIF (revision 2)

L3C

PDIF

L3CPDIF

L3CPDIF Logical node data


DO type
a_dACD

a_dACT

DA name

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common, main, start output signal

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: Common, main, start


output signal

ST

START

Mon

Timestamp: Common, main, start


output signal

general

ST

TRIP

Mon

Common, main, trip output signal

phsA

ST

TRL1

Mon

Trip signal from phase L1

Table continues on next page


108

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Op

Mod

Beh

OpnCTIn

OpnCTPh

Blk2H

Blk5H

DO type

DA name

a_dACT

a_dINC

a_dINS

v1_dINS

v1_dINS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: Common, main, trip


output signal

ST

TRIP

Mon

Timestamp: Common, main, trip


output signal

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

OPENCTIN

Mon

Open CT on Input : 1 for input 1,


2 for input 2

ST

OPENCTIN

Mon

Quality: Open CT on Input : 1 for


input 1, 2 for input 2

ST

OPENCTIN

Mon

Timestamp: Open CT on Input : 1


for input 1, 2 for input 2

stVal

ST

OPENCTPH

Mon

Open CT in Phase : 1 for L1, 2 for


L2, 3 for L3

ST

OPENCTPH

Mon

Quality: Open CT in Phase : 1 for


L1, 2 for L2, 3 for L3

ST

OPENCTPH

Mon

Timestamp: Open CT in Phase :


1 for L1, 2 for L2, 3 for L3

stVal

ST

BLK2H

Mon

Common block signal, due to 2nd


harmonic

ST

BLK2H

Mon

Quality: Common block signal,


due to 2nd harmonic

ST

BLK2H

Mon

Timestamp: Common block


signal, due to 2nd harmonic

stVal

ST

BLK5H

Mon

Common block signal, due to 5-th


harmonic

ST

BLK5H

Mon

Quality: Common block signal,


due to 5-th harmonic

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

109

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Blk5H

v1_dSPS

ST

BLK5H

Mon

Timestamp: Common block


signal, due to 5-th harmonic

ExFlt

v1_dSPS

stVal

ST

EXTFAULT

Mon

External fault has been detected

ST

EXTFAULT

Mon

Quality: External fault has been


detected

ST

EXTFAULT

Mon

Timestamp: External fault has


been detected

stVal

ST

INTFAULT

Mon

Internal fault has been detected

ST

INTFAULT

Mon

Quality: Internal fault has been


detected

ST

INTFAULT

Mon

Timestamp: Internal fault has


been detected

stVal

ST

STARTENH

Mon

Start of enhanced restrained


differential protection

ST

STARTENH

Mon

Quality: Start of enhanced


restrained differential protection

ST

STARTENH

Mon

Timestamp: Start of enhanced


restrained differential protection

stVal

ST

STARTRES

Mon

Start of restrained differential


protection

ST

STARTRES

Mon

Quality: Start of restrained


differential protection

ST

STARTRES

Mon

Timestamp: Start of restrained


differential protection

stVal

ST

STARTUNR

Mon

Start of unrestrained differential


protection

ST

STARTUNR

Mon

Quality: Start of unrestrained


differential protection

ST

STARTUNR

Mon

Timestamp: Start of unrestrained


differential protection

stVal

ST

BLK2HL1

Mon

Block signal due to 2nd harmonic,


phase L1

ST

BLK2HL1

Mon

Quality: Block signal due to 2nd


harmonic, phase L1

ST

BLK2HL1

Mon

Timestamp: Block signal due to


2nd harmonic, phase L1

stVal

ST

BLK2HL2

Mon

Block signal due to 2nd harmonic,


phase L2

ST

BLK2HL2

Mon

Quality: Block signal due to 2nd


harmonic, phase L2

ST

BLK2HL2

Mon

Timestamp: Block signal due to


2nd harmonic, phase L2

stVal

ST

BLK2HL3

Mon

Block signal due to 2nd harmonic,


phase L3

ST

BLK2HL3

Mon

Quality: Block signal due to 2nd


harmonic, phase L3

ST

BLK2HL3

Mon

Timestamp: Block signal due to


2nd harmonic, phase L3

ItrFlt

StrNSUnRst

StrRst

StrUnRst

Blk2HPhA

Blk2HPhB

Blk2HPhC

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

Table continues on next page


110

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Blk5HPhA

Blk5HPhB

Blk5HPhC

OpnCT

OpnCTAlm

DO type

DA name

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

7.5.1.9

Table 24:
DO name
Str

FC

Signal

Mon/
Cmd

Description

stVal

ST

BLK5HL1

Mon

Block signal due to 5th harmonic,


phase L1

ST

BLK5HL1

Mon

Quality: Block signal due to 5th


harmonic, phase L1

ST

BLK5HL1

Mon

Timestamp: Block signal due to


5th harmonic, phase L1

stVal

ST

BLK5HL2

Mon

Block signal due to 5th harmonic,


phase L2

ST

BLK5HL2

Mon

Quality: Block signal due to 5th


harmonic, phase L2

ST

BLK5HL2

Mon

Timestamp: Block signal due to


5th harmonic, phase L2

stVal

ST

BLK5HL3

Mon

Block signal due to 5th harmonic,


phase L3

ST

BLK5HL3

Mon

Quality: Block signal due to 5th


harmonic, phase L3

ST

BLK5HL3

Mon

Timestamp: Block signal due to


5th harmonic, phase L3

stVal

ST

OPENCT

Mon

An open CT was detected

ST

OPENCT

Mon

Quality: An open CT was detected

ST

OPENCT

Mon

Timestamp: An open CT was


detected

stVal

ST

OPENCTAL

Mon

Open CT Alarm output signal.


Issued after a delay ...

ST

OPENCTAL

Mon

Quality: Open CT Alarm output


signal. Issued after a delay ...

ST

OPENCTAL

Mon

Timestamp: Open CT Alarm


output signal. Issued after a
delay ...

Line differential protection, 6 CT sets, 35 line ends L6CPDIF


LN type

LN prefix

LN class

Function block name

L6CPDIF (revision 2)

L6C

PDIF

L6CPDIF

L6CPDIF Logical node data


DO type

DA name

a_dACD

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common, main, start output signal

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

111

Section 7
Logical node data model
DO name
Str

Op

Mod

Beh

OpnCTIn

OpnCTPh

Blk2H

DO type
a_dACD

a_dACT

a_dINC

a_dINS

v1_dINS

v1_dINS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

START

Mon

Quality: Common, main, start


output signal

ST

START

Mon

Timestamp: Common, main, start


output signal

general

ST

TRIP

Mon

Common, main, trip output signal

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: Common, main, trip


output signal

ST

TRIP

Mon

Timestamp: Common, main, trip


output signal

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

OPENCTIN

Mon

Open CT on Input : 1 for input 1,


2 for input 2

ST

OPENCTIN

Mon

Quality: Open CT on Input : 1 for


input 1, 2 for input 2

ST

OPENCTIN

Mon

Timestamp: Open CT on Input : 1


for input 1, 2 for input 2

stVal

ST

OPENCTPH

Mon

Open CT in Phase : 1 for L1, 2 for


L2, 3 for L3

ST

OPENCTPH

Mon

Quality: Open CT in Phase : 1 for


L1, 2 for L2, 3 for L3

ST

OPENCTPH

Mon

Timestamp: Open CT in Phase :


1 for L1, 2 for L2, 3 for L3

stVal

ST

BLK2H

Mon

Common block signal, due to 2nd


harmonic

ST

BLK2H

Mon

Quality: Common block signal,


due to 2nd harmonic

Table continues on next page


112

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Blk2H

v1_dSPS

ST

BLK2H

Mon

Timestamp: Common block


signal, due to 2nd harmonic

Blk5H

v1_dSPS

stVal

ST

BLK5H

Mon

Common block signal, due to 5-th


harmonic

ST

BLK5H

Mon

Quality: Common block signal,


due to 5-th harmonic

ST

BLK5H

Mon

Timestamp: Common block


signal, due to 5-th harmonic

stVal

ST

EXTFAULT

Mon

External fault has been detected

ST

EXTFAULT

Mon

Quality: External fault has been


detected

ST

EXTFAULT

Mon

Timestamp: External fault has


been detected

stVal

ST

INTFAULT

Mon

Internal fault has been detected

ST

INTFAULT

Mon

Quality: Internal fault has been


detected

ST

INTFAULT

Mon

Timestamp: Internal fault has


been detected

stVal

ST

STARTENH

Mon

Start of enhanced restrained


differential protection

ST

STARTENH

Mon

Quality: Start of enhanced


restrained differential protection

ST

STARTENH

Mon

Timestamp: Start of enhanced


restrained differential protection

stVal

ST

STARTRES

Mon

Start of restrained differential


protection

ST

STARTRES

Mon

Quality: Start of restrained


differential protection

ST

STARTRES

Mon

Timestamp: Start of restrained


differential protection

stVal

ST

STARTUNR

Mon

Start of unrestrained differential


protection

ST

STARTUNR

Mon

Quality: Start of unrestrained


differential protection

ST

STARTUNR

Mon

Timestamp: Start of unrestrained


differential protection

stVal

ST

BLK2HL1

Mon

Block signal due to 2nd harmonic,


phase L1

ST

BLK2HL1

Mon

Quality: Block signal due to 2nd


harmonic, phase L1

ST

BLK2HL1

Mon

Timestamp: Block signal due to


2nd harmonic, phase L1

stVal

ST

BLK2HL2

Mon

Block signal due to 2nd harmonic,


phase L2

ST

BLK2HL2

Mon

Quality: Block signal due to 2nd


harmonic, phase L2

ST

BLK2HL2

Mon

Timestamp: Block signal due to


2nd harmonic, phase L2

ExFlt

ItrFlt

StrNSUnRst

StrRst

StrUnRst

Blk2HPhA

Blk2HPhB

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

113

Section 7
Logical node data model
DO name
Blk2HPhC

Blk5HPhA

Blk5HPhB

Blk5HPhC

OpnCT

OpnCTAlm

7.5.1.10

114

DO type
v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

BLK2HL3

Mon

Block signal due to 2nd harmonic,


phase L3

ST

BLK2HL3

Mon

Quality: Block signal due to 2nd


harmonic, phase L3

ST

BLK2HL3

Mon

Timestamp: Block signal due to


2nd harmonic, phase L3

stVal

ST

BLK5HL1

Mon

Block signal due to 5th harmonic,


phase L1

ST

BLK5HL1

Mon

Quality: Block signal due to 5th


harmonic, phase L1

ST

BLK5HL1

Mon

Timestamp: Block signal due to


5th harmonic, phase L1

stVal

ST

BLK5HL2

Mon

Block signal due to 5th harmonic,


phase L2

ST

BLK5HL2

Mon

Quality: Block signal due to 5th


harmonic, phase L2

ST

BLK5HL2

Mon

Timestamp: Block signal due to


5th harmonic, phase L2

stVal

ST

BLK5HL3

Mon

Block signal due to 5th harmonic,


phase L3

ST

BLK5HL3

Mon

Quality: Block signal due to 5th


harmonic, phase L3

ST

BLK5HL3

Mon

Timestamp: Block signal due to


5th harmonic, phase L3

stVal

ST

OPENCT

Mon

An open CT was detected

ST

OPENCT

Mon

Quality: An open CT was detected

ST

OPENCT

Mon

Timestamp: An open CT was


detected

stVal

ST

OPENCTAL

Mon

Open CT Alarm output signal.


Issued after a delay ...

ST

OPENCTAL

Mon

Quality: Open CT Alarm output


signal. Issued after a delay ...

ST

OPENCTAL

Mon

Timestamp: Open CT Alarm


output signal. Issued after a
delay ...

Line differential protection 3 CT sets, with inzone transformers, 23


line ends LT3CPDIF
LN type

LN prefix

LN class

Function block name

LT3CPDIF (revision 2)

LT3C

PDIF

LT3CPDIF

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 25:
DO name
Str

Op

Mod

Beh

OpnCTIn

OpnCTPh

LT3CPDIF Logical node data


DO type

DA name

a_dACD

a_dACT

a_dINC

a_dINS

v1_dINS

v1_dINS

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common, main, start output signal

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: Common, main, start


output signal

ST

START

Mon

Timestamp: Common, main, start


output signal

general

ST

TRIP

Mon

Common, main, trip output signal

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: Common, main, trip


output signal

ST

TRIP

Mon

Timestamp: Common, main, trip


output signal

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

OPENCTIN

Mon

Open CT on Input : 1 for input 1,


2 for input 2

ST

OPENCTIN

Mon

Quality: Open CT on Input : 1 for


input 1, 2 for input 2

ST

OPENCTIN

Mon

Timestamp: Open CT on Input : 1


for input 1, 2 for input 2

stVal

ST

OPENCTPH

Mon

Open CT in Phase : 1 for L1, 2 for


L2, 3 for L3

ST

OPENCTPH

Mon

Quality: Open CT in Phase : 1 for


L1, 2 for L2, 3 for L3

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

115

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

OpnCTPh

v1_dINS

ST

OPENCTPH

Mon

Timestamp: Open CT in Phase :


1 for L1, 2 for L2, 3 for L3

Blk2H

v1_dSPS

stVal

ST

BLK2H

Mon

Common block signal, due to 2nd


harmonic

ST

BLK2H

Mon

Quality: Common block signal,


due to 2nd harmonic

ST

BLK2H

Mon

Timestamp: Common block


signal, due to 2nd harmonic

stVal

ST

BLK5H

Mon

Common block signal, due to 5-th


harmonic

ST

BLK5H

Mon

Quality: Common block signal,


due to 5-th harmonic

ST

BLK5H

Mon

Timestamp: Common block


signal, due to 5-th harmonic

stVal

ST

EXTFAULT

Mon

External fault has been detected

ST

EXTFAULT

Mon

Quality: External fault has been


detected

ST

EXTFAULT

Mon

Timestamp: External fault has


been detected

stVal

ST

INTFAULT

Mon

Internal fault has been detected

ST

INTFAULT

Mon

Quality: Internal fault has been


detected

ST

INTFAULT

Mon

Timestamp: Internal fault has


been detected

stVal

ST

STARTENH

Mon

Start of enhanced restrained


differential protection

ST

STARTENH

Mon

Quality: Start of enhanced


restrained differential protection

ST

STARTENH

Mon

Timestamp: Start of enhanced


restrained differential protection

stVal

ST

STARTRES

Mon

Start of restrained differential


protection

ST

STARTRES

Mon

Quality: Start of restrained


differential protection

ST

STARTRES

Mon

Timestamp: Start of restrained


differential protection

stVal

ST

STARTUNR

Mon

Start of unrestrained differential


protection

ST

STARTUNR

Mon

Quality: Start of unrestrained


differential protection

ST

STARTUNR

Mon

Timestamp: Start of unrestrained


differential protection

stVal

ST

BLK2HL1

Mon

Block signal due to 2nd harmonic,


phase L1

ST

BLK2HL1

Mon

Quality: Block signal due to 2nd


harmonic, phase L1

ST

BLK2HL1

Mon

Timestamp: Block signal due to


2nd harmonic, phase L1

Blk5H

ExFlt

ItrFlt

StrNSUnRst

StrRst

StrUnRst

Blk2HPhA

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

Table continues on next page


116

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Blk2HPhB

Blk2HPhC

Blk5HPhA

Blk5HPhB

Blk5HPhC

OpnCT

OpnCTAlm

DO type

DA name

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

7.5.1.11

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

BLK2HL2

Mon

Block signal due to 2nd harmonic,


phase L2

ST

BLK2HL2

Mon

Quality: Block signal due to 2nd


harmonic, phase L2

ST

BLK2HL2

Mon

Timestamp: Block signal due to


2nd harmonic, phase L2

stVal

ST

BLK2HL3

Mon

Block signal due to 2nd harmonic,


phase L3

ST

BLK2HL3

Mon

Quality: Block signal due to 2nd


harmonic, phase L3

ST

BLK2HL3

Mon

Timestamp: Block signal due to


2nd harmonic, phase L3

stVal

ST

BLK5HL1

Mon

Block signal due to 5th harmonic,


phase L1

ST

BLK5HL1

Mon

Quality: Block signal due to 5th


harmonic, phase L1

ST

BLK5HL1

Mon

Timestamp: Block signal due to


5th harmonic, phase L1

stVal

ST

BLK5HL2

Mon

Block signal due to 5th harmonic,


phase L2

ST

BLK5HL2

Mon

Quality: Block signal due to 5th


harmonic, phase L2

ST

BLK5HL2

Mon

Timestamp: Block signal due to


5th harmonic, phase L2

stVal

ST

BLK5HL3

Mon

Block signal due to 5th harmonic,


phase L3

ST

BLK5HL3

Mon

Quality: Block signal due to 5th


harmonic, phase L3

ST

BLK5HL3

Mon

Timestamp: Block signal due to


5th harmonic, phase L3

stVal

ST

OPENCT

Mon

An open CT was detected

ST

OPENCT

Mon

Quality: An open CT was detected

ST

OPENCT

Mon

Timestamp: An open CT was


detected

stVal

ST

OPENCTAL

Mon

Open CT Alarm output signal.


Issued after a delay ...

ST

OPENCTAL

Mon

Quality: Open CT Alarm output


signal. Issued after a delay ...

ST

OPENCTAL

Mon

Timestamp: Open CT Alarm


output signal. Issued after a
delay ...

Line differential protection 6 CT sets, with inzone transformers, 35


line ends LT6CPDIF
LN type

LN prefix

LN class

Function block name

LT6CPDIF (revision 2)

LT6C

PDIF

LT6CPDIF
117

Section 7
Logical node data model

Table 26:
DO name
Str

Op

Mod

Beh

OpnCTIn

OpnCTPh

1MRK 511 302-UEN -

LT6CPDIF Logical node data


DO type
a_dACD

a_dACT

a_dINC

a_dINS

v1_dINS

v1_dINS

DA name

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common, main, start output signal

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: Common, main, start


output signal

ST

START

Mon

Timestamp: Common, main, start


output signal

general

ST

TRIP

Mon

Common, main, trip output signal

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: Common, main, trip


output signal

ST

TRIP

Mon

Timestamp: Common, main, trip


output signal

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

OPENCTIN

Mon

Open CT on Input : 1 for input 1,


2 for input 2

ST

OPENCTIN

Mon

Quality: Open CT on Input : 1 for


input 1, 2 for input 2

ST

OPENCTIN

Mon

Timestamp: Open CT on Input : 1


for input 1, 2 for input 2

stVal

ST

OPENCTPH

Mon

Open CT in Phase : 1 for L1, 2 for


L2, 3 for L3

ST

OPENCTPH

Mon

Quality: Open CT in Phase : 1 for


L1, 2 for L2, 3 for L3

Table continues on next page


118

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

OpnCTPh

v1_dINS

ST

OPENCTPH

Mon

Timestamp: Open CT in Phase :


1 for L1, 2 for L2, 3 for L3

Blk2H

v1_dSPS

stVal

ST

BLK2H

Mon

Common block signal, due to 2nd


harmonic

ST

BLK2H

Mon

Quality: Common block signal,


due to 2nd harmonic

ST

BLK2H

Mon

Timestamp: Common block


signal, due to 2nd harmonic

stVal

ST

BLK5H

Mon

Common block signal, due to 5-th


harmonic

ST

BLK5H

Mon

Quality: Common block signal,


due to 5-th harmonic

ST

BLK5H

Mon

Timestamp: Common block


signal, due to 5-th harmonic

stVal

ST

EXTFAULT

Mon

External fault has been detected

ST

EXTFAULT

Mon

Quality: External fault has been


detected

ST

EXTFAULT

Mon

Timestamp: External fault has


been detected

stVal

ST

INTFAULT

Mon

Internal fault has been detected

ST

INTFAULT

Mon

Quality: Internal fault has been


detected

ST

INTFAULT

Mon

Timestamp: Internal fault has


been detected

stVal

ST

STARTENH

Mon

Start of enhanced restrained


differential protection

ST

STARTENH

Mon

Quality: Start of enhanced


restrained differential protection

ST

STARTENH

Mon

Timestamp: Start of enhanced


restrained differential protection

stVal

ST

STARTRES

Mon

Start of restrained differential


protection

ST

STARTRES

Mon

Quality: Start of restrained


differential protection

ST

STARTRES

Mon

Timestamp: Start of restrained


differential protection

stVal

ST

STARTUNR

Mon

Start of unrestrained differential


protection

ST

STARTUNR

Mon

Quality: Start of unrestrained


differential protection

ST

STARTUNR

Mon

Timestamp: Start of unrestrained


differential protection

stVal

ST

BLK2HL2

Mon

Block signal due to 2nd harmonic,


phase L2

ST

BLK2HL2

Mon

Quality: Block signal due to 2nd


harmonic, phase L2

ST

BLK2HL2

Mon

Timestamp: Block signal due to


2nd harmonic, phase L2

Blk5H

ExFlt

ItrFlt

StrNSUnRst

StrRst

StrUnRst

Blk2HPhB

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

119

Section 7
Logical node data model
DO name
Blk2HPhC

Blk5HPhA

Blk5HPhB

Blk5HPhC

OpnCT

OpnCTAlm

Blk2HPhA

DO type
v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

BLK2HL3

Mon

Block signal due to 2nd harmonic,


phase L3

ST

BLK2HL3

Mon

Quality: Block signal due to 2nd


harmonic, phase L3

ST

BLK2HL3

Mon

Timestamp: Block signal due to


2nd harmonic, phase L3

stVal

ST

BLK5HL1

Mon

Block signal due to 5th harmonic,


phase L1

ST

BLK5HL1

Mon

Quality: Block signal due to 5th


harmonic, phase L1

ST

BLK5HL1

Mon

Timestamp: Block signal due to


5th harmonic, phase L1

stVal

ST

BLK5HL2

Mon

Block signal due to 5th harmonic,


phase L2

ST

BLK5HL2

Mon

Quality: Block signal due to 5th


harmonic, phase L2

ST

BLK5HL2

Mon

Timestamp: Block signal due to


5th harmonic, phase L2

stVal

ST

BLK5HL3

Mon

Block signal due to 5th harmonic,


phase L3

ST

BLK5HL3

Mon

Quality: Block signal due to 5th


harmonic, phase L3

ST

BLK5HL3

Mon

Timestamp: Block signal due to


5th harmonic, phase L3

stVal

ST

OPENCT

Mon

An open CT was detected

ST

OPENCT

Mon

Quality: An open CT was detected

ST

OPENCT

Mon

Timestamp: An open CT was


detected

stVal

ST

OPENCTAL

Mon

Open CT Alarm output signal.


Issued after a delay ...

ST

OPENCTAL

Mon

Quality: Open CT Alarm output


signal. Issued after a delay ...

ST

OPENCTAL

Mon

Timestamp: Open CT Alarm


output signal. Issued after a
delay ...

stVal

ST

BLK2HL1

Mon

Block signal due to 2nd harmonic,


phase L1

ST

BLK2HL1

Mon

Quality: Block signal due to 2nd


harmonic, phase L1

ST

BLK2HL1

Mon

Timestamp: Block signal due to


2nd harmonic, phase L1

7.5.2

Additional security logic for differential protection RGFC

7.5.2.1

Additional security logic for differential protection LDRGFC

120

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 27:
DO name
Mod

Beh

StUpLoCurr

Startup

StUpCV1

StUpCV2

LN type

LN prefix

LN class

Function block name

STSGGIO (revision 0)

STS

GGIO

LDRGFC

LDRGFC Logical node data


DO type

DA name

a_dINC

a_dINS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

STUC

Mon

Start signal for low current criterion

ST

STUC

Mon

Quality: Start signal for low


current criterion

ST

STUC

Mon

Timestamp: Start signal for low


current criterion

stVal

ST

START

Mon

General startup signal

ST

START

Mon

Quality: General startup signal

ST

START

Mon

Timestamp: General startup signal

stVal

ST

STCVL2L3

Mon

Start signal for current variation


criterion for phase L2L3

ST

STCVL2L3

Mon

Quality: Start signal for current


variation criterion for phase L2L3

ST

STCVL2L3

Mon

Timestamp: Start signal for


current variation criterion for
phase L2L3

stVal

ST

STCVL3L1

Mon

Start signal for current variation


criterion for phase L3L1

ST

STCVL3L1

Mon

Quality: Start signal for current


variation criterion for phase L3L1

ST

STCVL3L1

Mon

Timestamp: Start signal for


current variation criterion for
phase L3L1

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

121

Section 7
Logical node data model
DO name
StUpCV3

StUpZroA

StUpLoVol

DO type
v1_dSPS

v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

STCVL1L2

Mon

Start signal for current variation


criterion for phase L1L2

ST

STCVL1L2

Mon

Quality: Start signal for current


variation criterion for phase L1L2

ST

STCVL1L2

Mon

Timestamp: Start signal for


current variation criterion for
phase L1L2

stVal

ST

ST3I0

Mon

Start signal for zero sequence


current criterion

ST

ST3I0

Mon

Quality: Start signal for zero


sequence current criterion

ST

ST3I0

Mon

Timestamp: Start signal for zero


sequence current criterion

stVal

ST

STUV

Mon

Start signal for under voltage


criterion

ST

STUV

Mon

Quality: Start signal for under


voltage criterion

ST

STUV

Mon

Timestamp: Start signal for under


voltage criterion

7.5.3

Distance protection PDIS

7.5.3.1

Phase selection with load encroachment, quadrilateral characteristic


FDPSPDIS

Table 28:
DO name
Str

LN type

LN prefix

LN class

Function block name

FDPSPDIS (revision 2)

FDPS

PDIS

FDPSPDIS

FDPSPDIS Logical node data


DO type

DA name

FC

aACD

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Start in any phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STNDL1

Mon

Non directional start in L1

dirPhsA

ST

Mon

Integer coded info about direction


of fault, phase L1

phsB

ST

STNDL2

Mon

Non directional start in L2

dirPhsB

ST

Mon

Integer coded info about direction


of fault, phase L2

phsC

ST

STNDL3

Mon

Non directional start in L3

dirPhsC

ST

Mon

Integer coded info about direction


of fault, phase L3

ST

START

Mon

Quality: Start in any phase or loop

Table continues on next page


122

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Str

aACD

ST

START

Mon

Timestamp: Start in any phase or


loop

Mod

aINC

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

Trip output

ST

TRIP

Mon

Quality: Trip output

ST

TRIP

Mon

Timestamp: Trip output

stVal

ST

STCNDZ

Mon

Start condition (Z< with LE and


3I0 E/F detection)

ST

STCNDZ

Mon

Quality: Start condition (Z< with


LE and 3I0 E/F detection)

ST

STCNDZ

Mon

Timestamp: Start condition (Z<


with LE and 3I0 E/F detection)

stVal

ST

STCNDLE

Mon

Start condition (only LE and 3I0 E/


F detection)

ST

STCNDLE

Mon

Quality: Start condition (only LE


and 3I0 E/F detection)

ST

STCNDLE

Mon

Timestamp: Start condition (only


LE and 3I0 E/F detection)

stVal

ST

STFWL1

Mon

Fault detected in phase L1 forward direction

ST

STFWL1

Mon

Quality: Fault detected in phase


L1 - forward direction

ST

STFWL1

Mon

Timestamp: Fault detected in


phase L1 - forward direction

stVal

ST

STFWL2

Mon

Fault detected in phase L2 forward direction

ST

STFWL2

Mon

Quality: Fault detected in phase


L2 - forward direction

Beh

Op

StrCndZ

StrCndA

StrFwdPhA

StrFwdPhB

aINS

bACT

v1INS

v1INS

v1SPS

v1SPS

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

123

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

StrFwdPhB

v1SPS

ST

STFWL2

Mon

Timestamp: Fault detected in


phase L2 - forward direction

StrFwdPhC

v1SPS

stVal

ST

STFWL3

Mon

Fault detected in phase L3 forward direction

ST

STFWL3

Mon

Quality: Fault detected in phase


L3 - forward direction

ST

STFWL3

Mon

Timestamp: Fault detected in


phase L3 - forward direction

stVal

ST

STFWPE

Mon

Earth fault detected in forward


direction

ST

STFWPE

Mon

Quality: Earth fault detected in


forward direction

ST

STFWPE

Mon

Timestamp: Earth fault detected


in forward direction

stVal

ST

STRVL1

Mon

Fault detected in phase L1 reverse direction

ST

STRVL1

Mon

Quality: Fault detected in phase


L1 - reverse direction

ST

STRVL1

Mon

Timestamp: Fault detected in


phase L1 - reverse direction

stVal

ST

STRVL2

Mon

Fault detected in phase L2 reverse direction

ST

STRVL2

Mon

Quality: Fault detected in phase


L2 - reverse direction

ST

STRVL2

Mon

Timestamp: Fault detected in


phase L2 - reverse direction

stVal

ST

STRVL3

Mon

Fault detected in phase L3 reverse direction

ST

STRVL3

Mon

Quality: Fault detected in phase


L3 - reverse direction

ST

STRVL3

Mon

Timestamp: Fault detected in


phase L3 - reverse direction

stVal

ST

STRVPE

Mon

Earth fault detected in reverse


direction

ST

STRVPE

Mon

Quality: Earth fault detected in


reverse direction

ST

STRVPE

Mon

Timestamp: Earth fault detected


in reverse direction

stVal

ST

STNDL1

Mon

Non directional start in L1

ST

STNDL1

Mon

Quality: Non directional start in L1

ST

STNDL1

Mon

Timestamp: Non directional start


in L1

stVal

ST

STNDL2

Mon

Non directional start in L2

ST

STNDL2

Mon

Quality: Non directional start in L2

ST

STNDL2

Mon

Timestamp: Non directional start


in L2

stVal

ST

STNDL3

Mon

Non directional start in L3

StrFwdGnd

StrRvPhA

StrRvPhB

StrRvPhC

StrRvGnd

StrNDPhA

StrNDPhB

StrNDPhC

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

Table continues on next page


124

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
StrNDPhC

StrNDGnd

Str1Ph

Str2Ph

Str3Ph

RelGnd

RelPP

DO type

DA name

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

7.5.3.2

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

ST

STNDL3

Mon

Quality: Non directional start in L3

ST

STNDL3

Mon

Timestamp: Non directional start


in L3

stVal

ST

STNDPE

Mon

Non directional start, phase-earth

ST

STNDPE

Mon

Quality: Non directional start,


phase-earth

ST

STNDPE

Mon

Timestamp: Non directional start,


phase-earth

stVal

ST

STFW1PH

Mon

Start in forward direction for singlephase fault

ST

STFW1PH

Mon

Quality: Start in forward direction


for single-phase fault

ST

STFW1PH

Mon

Timestamp: Start in forward


direction for single-phase fault

stVal

ST

STFW2PH

Mon

Start in forward direction for twophase fault

ST

STFW2PH

Mon

Quality: Start in forward direction


for two- phase fault

ST

STFW2PH

Mon

Timestamp: Start in forward


direction for two- phase fault

stVal

ST

STFW3PH

Mon

Start in forward direction for threphase fault

ST

STFW3PH

Mon

Quality: Start in forward direction


for thre-phase fault

ST

STFW3PH

Mon

Timestamp: Start in forward


direction for thre-phase fault

stVal

ST

STPE

Mon

Current conditions release of


phase-earth measuring elements

ST

STPE

Mon

Quality: Current conditions


release of phase-earth measuring
elements

ST

STPE

Mon

Timestamp: Current conditions


release of phase-earth measuring
elements

stVal

ST

STPP

Mon

Current conditions release of


phase-phase measuring elements

ST

STPP

Mon

Quality: Current conditions


release of phase-phase
measuring elements

ST

STPP

Mon

Timestamp: Current conditions


release of phase-phase
measuring elements

Faulty phase identification with load encroachment FMPSPDIS


LN type

LN prefix

LN class

Function block name

FMPSPDIS (revision 0)

FMPS

PDIS

FMPSPDIS

125

Section 7
Logical node data model

Table 29:
DO name
Str

Op

Mod

Beh

EFlt

7.5.3.3

126

1MRK 511 302-UEN -

FMPSPDIS Logical node data


DO type

DA name

aACD

aACT

aINC

aINS

v1SPS

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Indicates that something has


started

phsA

ST

STL1

Mon

Fault detected in phase L1

phsB

ST

STL2

Mon

Fault detected in phase L2

phsC

ST

STL3

Mon

Fault detected in phase L3

ST

START

Mon

Quality: Indicates that something


has started

ST

START

Mon

Timestamp: Indicates that


something has started

general

ST

START

Mon

Indicates that something has


started

phsA

ST

STL1

Mon

Fault detected in phase L1

phsB

ST

STL2

Mon

Fault detected in phase L2

phsC

ST

STL3

Mon

Fault detected in phase L3

ST

START

Mon

Quality: Indicates that something


has started

ST

START

Mon

Timestamp: Indicates that


something has started

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

STPE

Mon

Earth fault detected

ST

STPE

Mon

Quality: Earth fault detected

ST

STPE

Mon

Timestamp: Earth fault detected

Loss of excitation LEXPDIS


LN type

LN prefix

LN class

Function block name

LEXPDIS (revision 1)

LEX

PDIS

LEXPDIS

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 30:
DO name
Mod

Beh

Str

Op

OpZ1

OpZ2

StrZ1

StrZ2

LEXPDIS Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

START

Mon

Common start signal

ST

START

Mon

Quality: Common start signal

ST

START

Mon

Timestamp: Common start signal

general

ST

TRIP

Mon

Common trip signal

ST

TRIP

Mon

Quality: Common trip signal

ST

TRIP

Mon

Timestamp: Common trip signal

stVal

ST

TRZ1

Mon

Trip signal from impedance zone


Z1

ST

TRZ1

Mon

Quality: Trip signal from


impedance zone Z1

ST

TRZ1

Mon

Timestamp: Trip signal from


impedance zone Z1

stVal

ST

TRZ2

Mon

Trip signal from impedance zone


Z2

ST

TRZ2

Mon

Quality: Trip signal from


impedance zone Z2

ST

TRZ2

Mon

Timestamp: Trip signal from


impedance zone Z2

stVal

ST

STZ1

Mon

Start signal from impedance zone


Z1

ST

STZ1

Mon

Quality: Start signal from


impedance zone Z1

ST

STZ1

Mon

Timestamp: Start signal from


impedance zone Z1

stVal

ST

STZ2

Mon

Start signal from impedance zone


Z2

ST

STZ2

Mon

Quality: Start signal from


impedance zone Z2

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

127

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

StrZ2

v1_dSPS

ST

STZ2

Mon

Timestamp: Start signal from


impedance zone Z2

PriRis

v2_dMV

mag.f

MX

ROHM

Mon

Resistance in Primary Ohms

MX

ROHM

Mon

Quality: Resistance in Primary


Ohms

MX

ROHM

Mon

Timestamp: Resistance in
Primary Ohms

mag.f

MX

XOHM

Mon

Reactance in Primary Ohms

MX

XOHM

Mon

Quality: Reactance in Primary


Ohms

MX

XOHM

Mon

Timestamp: Reactance in
Primary Ohms

PriReact

v2_dMV

7.5.3.4

Table 31:
DO name
Str

Op

Mod

Distance protection zone, quadrilateral characteristic ZMQPDIS


LN type

LN prefix

LN class

Function block name

ZMQPDIS (revision 0)

ZMQ

PDIS

ZMQPDIS

ZMQPDIS Logical node data


DO type

DA name

aACD

aACT

aINC

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General Start, issued from any


phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: General Start, issued


from any phase or loop

ST

START

Mon

Timestamp: General Start, issued


from any phase or loop

general

ST

TRIP

Mon

General Trip, issued from any


phase or loop

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General Trip, issued from


any phase or loop

ST

TRIP

Mon

Timestamp: General Trip, issued


from any phase or loop

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Table continues on next page


128

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

StrNDir

DO type

DA name

aINC

aINS

v1SPS

DO name
Str

Op

Signal

Mon/
Cmd

Description

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

STND

Mon

Non-directional start, issued from


any phase or loop

ST

STND

Mon

Quality: Non-directional start,


issued from any phase or loop

ST

STND

Mon

Timestamp: Non-directional start,


issued from any phase or loop

7.5.3.5

Table 32:

FC

Distance protection zone, quadrilateral characteristic ZMQAPDIS


LN type

LN prefix

LN class

Function block name

ZMQAPDIS (revision 0)

ZMQA

PDIS

ZMQAPDIS

ZMQAPDIS Logical node data


DO type

DA name

aACD

aACT

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General Start, issued from any


phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: General Start, issued


from any phase or loop

ST

START

Mon

Timestamp: General Start, issued


from any phase or loop

general

ST

TRIP

Mon

General Trip, issued from any


phase or loop

phsA

ST

TRL1

Mon

Trip signal from phase L1

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

129

Section 7
Logical node data model
DO name
Op

Mod

Beh

StrNDir

DO type
aACT

aINC

aINS

v1SPS

7.5.3.6

Table 33:
DO name
Str

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General Trip, issued from


any phase or loop

ST

TRIP

Mon

Timestamp: General Trip, issued


from any phase or loop

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

STND

Mon

Non-directional start, issued from


any phase or loop

ST

STND

Mon

Quality: Non-directional start,


issued from any phase or loop

ST

STND

Mon

Timestamp: Non-directional start,


issued from any phase or loop

Distance measuring zone, quadrilateral characteristic for series


compensated lines ZMCPDIS
LN type

LN prefix

LN class

Function block name

ZMCPDIS (revision 0)

ZMC

PDIS

ZMCPDIS

ZMCPDIS Logical node data


DO type

DA name

FC

aACD

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General Start, issued from any


phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STL1

Mon

Start signal from phase L1

Table continues on next page


130

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Str

Op

Mod

Beh

StrNDir

DO type

DA name

aACD

aACT

aINC

aINS

v1SPS

7.5.3.7

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: General Start, issued


from any phase or loop

ST

START

Mon

Timestamp: General Start, issued


from any phase or loop

general

ST

TRIP

Mon

General Trip, issued from any


phase or loop

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General Trip, issued from


any phase or loop

ST

TRIP

Mon

Timestamp: General Trip, issued


from any phase or loop

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

STND

Mon

Non-directional start, issued from


any phase or loop

ST

STND

Mon

Quality: Non-directional start,


issued from any phase or loop

ST

STND

Mon

Timestamp: Non-directional start,


issued from any phase or loop

Distance measuring zone, quadrilateral characteristic for series


compensated lines ZMCAPDIS
LN type

LN prefix

LN class

Function block name

ZMCAPDIS (revision 0)

ZMCA

PDIS

ZMCAPDIS

131

Section 7
Logical node data model

Table 34:
DO name
Str

Op

Mod

Beh

StrNDir

132

1MRK 511 302-UEN -

ZMCAPDIS Logical node data


DO type

DA name

aACD

aACT

aINC

aINS

v1SPS

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General Start, issued from any


phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: General Start, issued


from any phase or loop

ST

START

Mon

Timestamp: General Start, issued


from any phase or loop

general

ST

TRIP

Mon

General Trip, issued from any


phase or loop

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General Trip, issued from


any phase or loop

ST

TRIP

Mon

Timestamp: General Trip, issued


from any phase or loop

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

STND

Mon

Non-directional start, issued from


any phase or loop

ST

STND

Mon

Quality: Non-directional start,


issued from any phase or loop

ST

STND

Mon

Timestamp: Non-directional start,


issued from any phase or loop

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.5.3.8

Table 35:
DO name
Str

Op

Mod

Beh

StrPP

StrPh

Full-scheme distance protection, mho characteristic ZMHPDIS


LN type

LN prefix

LN class

Function block name

ZMHPDIS (revision 0)

ZMH

PDIS

ZMHPDIS

ZMHPDIS Logical node data


DO type

DA name

aACD

aACT

aINC

aINS

v1SPS

v1SPS

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Start General

phsA

ST

STL1

Mon

Start phase L1

phsB

ST

STL2

Mon

Start phase L2

phsC

ST

STL3

Mon

Start phase L3

ST

START

Mon

Quality: Start General

ST

START

Mon

Timestamp: Start General

general

ST

TRIP

Mon

Trip General

phsA

ST

TRL1

Mon

Trip phase L1

phsB

ST

TRL2

Mon

Trip phase L2

phsC

ST

TRL3

Mon

Trip phase L3

ST

TRIP

Mon

Quality: Trip General

ST

TRIP

Mon

Timestamp: Trip General

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

STPP

Mon

Start phase-to-phase

ST

STPP

Mon

Quality: Start phase-to-phase

ST

STPP

Mon

Timestamp: Start phase-to-phase

stVal

ST

STPE

Mon

Start phase-to-earth

ST

STPE

Mon

Quality: Start phase-to-earth

ST

STPE

Mon

Timestamp: Start phase-to-earth

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

133

Section 7
Logical node data model
DO name
OpPP

OpPh

DO type
v1SPS

v1SPS

DA name

FC

Signal

Mon/
Cmd

stVal

ST

TRPP

Mon

Trip phase-to-phase

ST

TRPP

Mon

Quality: Trip phase-to-phase

ST

TRPP

Mon

Timestamp: Trip phase-to-phase

stVal

ST

TRPE

Mon

Trip phase-to-earth

ST

TRPE

Mon

Quality: Trip phase-to-earth

ST

TRPE

Mon

Timestamp: Trip phase-to-earth

7.5.3.9

Table 36:
DO name
Str

Op

Mod

1MRK 511 302-UEN -

Description

Fullscheme distance protection, quadrilateral for earth faults ZMMPDIS


LN type

LN prefix

LN class

Function block name

ZMMPDIS (revision 0)

ZMM

PDIS

ZMMPDIS

ZMMPDIS Logical node data


DO type

DA name

aACD

aACT

aINC

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General Start, issued from any


phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: General Start, issued


from any phase or loop

ST

START

Mon

Timestamp: General Start, issued


from any phase or loop

general

ST

TRIP

Mon

General Trip, issued from any


phase or loop

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General Trip, issued from


any phase or loop

ST

TRIP

Mon

Timestamp: General Trip, issued


from any phase or loop

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Table continues on next page


134

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

StrNDir

DO type

DA name

aINC

aINS

v1SPS

DO name
Str

Op

Signal

Mon/
Cmd

Description

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

STND

Mon

Non-directional start, issued from


any phase or loop

ST

STND

Mon

Quality: Non-directional start,


issued from any phase or loop

ST

STND

Mon

Timestamp: Non-directional start,


issued from any phase or loop

7.5.3.10

Table 37:

FC

Fullscheme distance protection, quadrilateral for earth faults


ZMMAPDIS
LN type

LN prefix

LN class

Function block name

ZMMAPDIS (revision 0)

ZMMA

PDIS

ZMMAPDIS

ZMMAPDIS Logical node data


DO type

DA name

aACD

aACT

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General Start, issued from any


phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: General Start, issued


from any phase or loop

ST

START

Mon

Timestamp: General Start, issued


from any phase or loop

general

ST

TRIP

Mon

General Trip, issued from any


phase or loop

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General Trip, issued from


any phase or loop

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

135

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Op

aACT

ST

TRIP

Mon

Timestamp: General Trip, issued


from any phase or loop

Mod

aINC

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

STND

Mon

Non-directional start, issued from


any phase or loop

ST

STND

Mon

Quality: Non-directional start,


issued from any phase or loop

ST

STND

Mon

Timestamp: Non-directional start,


issued from any phase or loop

Beh

StrNDir

aINS

v1SPS

7.5.3.11

Table 38:
DO name
Str

Distance protection zone, quadrilateral characteristic, separate


settings ZMRAPDIS
LN type

LN prefix

LN class

Function block name

ZMRAPDIS (revision 0)

ZMRA

PDIS

ZMRAPDIS

ZMRAPDIS Logical node data


DO type

DA name

FC

aACD

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General Start, issued from any


phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: General Start, issued


from any phase or loop

Table continues on next page


136

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Str

aACD

ST

START

Mon

Timestamp: General Start, issued


from any phase or loop

Op

aACT

general

ST

TRIP

Mon

General Trip, issued from any


phase or loop

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General Trip, issued from


any phase or loop

ST

TRIP

Mon

Timestamp: General Trip, issued


from any phase or loop

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

STND

Mon

Non-directional start, issued from


any phase or loop

ST

STND

Mon

Quality: Non-directional start,


issued from any phase or loop

ST

STND

Mon

Timestamp: Non-directional start,


issued from any phase or loop

Mod

Beh

StrNDir

aINC

aINS

v1SPS

7.5.3.12

670 series 2.0 IEC


Communication Protocol Manual

Distance protection zone, quadrilateral characteristic, separate


settings ZMRPDIS
LN type

LN prefix

LN class

Function block name

ZMRPDIS (revision 0)

ZMR

PDIS

ZMRPDIS

137

Section 7
Logical node data model

Table 39:
DO name
Str

Op

Mod

Beh

StrNDir

138

1MRK 511 302-UEN -

ZMRPDIS Logical node data


DO type

DA name

aACD

aACT

aINC

aINS

v1SPS

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General Start, issued from any


phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: General Start, issued


from any phase or loop

ST

START

Mon

Timestamp: General Start, issued


from any phase or loop

general

ST

TRIP

Mon

General Trip, issued from any


phase or loop

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General Trip, issued from


any phase or loop

ST

TRIP

Mon

Timestamp: General Trip, issued


from any phase or loop

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

STND

Mon

Non-directional start, issued from


any phase or loop

ST

STND

Mon

Quality: Non-directional start,


issued from any phase or loop

ST

STND

Mon

Timestamp: Non-directional start,


issued from any phase or loop

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.5.3.13

Table 40:
DO name
Str

Op

Beh

High speed distance protection ZMFPDIS


LN type

LN prefix

LN class

Function block name

PSFPDIS instance 7 (revision 0)

PSF

PDIS

ZMFPDIS

ZMFLLN0 instance 1 (revision 0)

LLN0

ZMFPDIS

ZMFPDIS instance 1 (revision 0)

ZMF

PDIS

ZMFPDIS

ZMFPDIS instance 2 (revision 0)

ZMF

PDIS

ZMFPDIS

ZMFPDIS instance 3 (revision 0)

ZMF

PDIS

ZMFPDIS

ZMFPDIS instance 4 (revision 0)

ZMF

PDIS

ZMFPDIS

ZMFPDIS instance 5 (revision 0)

ZMF

PDIS

ZMFPDIS

ZMFPDIS instance 6 (revision 0)

ZMF

PDIS

ZMFPDIS

ZMFPDIS Logical node data (instance 7)


DO type

DA name

a_dACD

a_dACT

a_dINS

FC

Signal

Mon/
Cmd

Description

general

ST

STARTND

Mon

Fault detected in any phase or


phases - any direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

phsA

ST

STNDL1

Mon

Fault detected in phase L1 - any


direction

dirPhsA

ST

L1Dir

Mon

Direction in phase L1

phsB

ST

STNDL2

Mon

Fault detected in phase L2 - any


direction

dirPhsB

ST

L2Dir

Mon

Direction in phase L2

phsC

ST

STNDL3

Mon

Fault detected in phase L3 - any


direction

dirPhsC

ST

L3Dir

Mon

Direction in phase L3

ST

STARTND

Mon

Quality: Fault detected in any


phase or phases - any direction

ST

STARTND

Mon

Timestamp: Fault detected in any


phase or phases - any direction

general

ST

STARTND

Mon

Fault detected in any phase or


phases - any direction

phsA

ST

STNDL1

Mon

Fault detected in phase L1 - any


direction

phsB

ST

STNDL2

Mon

Fault detected in phase L2 - any


direction

phsC

ST

STNDL3

Mon

Fault detected in phase L3 - any


direction

ST

STARTND

Mon

Quality: Fault detected in any


phase or phases - any direction

ST

STARTND

Mon

Timestamp: Fault detected in any


phase or phases - any direction

stVal

ST

Beh

Mon

Behaviour parameter for 61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

139

Section 7
Logical node data model
DO name
Beh

Mod

Table 41:
DO name
Mod

Beh

Table 42:
DO name
Beh

Str

DO type
a_dINS

c_dINC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ZMFPDIS Logical node data (instance 1)


DO type
a_dINC

a_dINS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ1

Mon

Start in any phase or phases from


zone 1 - forward direction

ZMFPDIS Logical node data (instance 1)


DO type
a_dINS

b_dACD

DA name

Description

Table continues on next page

140

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Str

Op

Mod

Table 43:
DO name
Beh

Str

Op

DO type

DA name

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ1

Mon

Quality: Start in any phase or


phases from zone 1 - forward
direction

ST

STARTZ1

Mon

Timestamp: Start in any phase or


phases from zone 1 - forward
direction

general

ST

TRIPZ1

Mon

Trip in any phase or phases from


zone 1 - forward direction

ST

TRIPZ1

Mon

Quality: Trip in any phase or


phases from zone 1 - forward
direction

ST

TRIPZ1

Mon

Timestamp: Trip in any phase or


phases from zone 1 - forward
direction

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ZMFPDIS Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

b_dACT

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ2

Mon

Start in any phase or phases from


zone 2 - forward direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ2

Mon

Quality: Start in any phase or


phases from zone 2 - forward
direction

ST

STARTZ2

Mon

Timestamp: Start in any phase or


phases from zone 2 - forward
direction

general

ST

TRIPZ2

Mon

Trip in any phase or phases from


zone 2 - forward direction

ST

TRIPZ2

Mon

Quality: Trip in any phase or


phases from zone 2 - forward
direction

ST

TRIPZ2

Mon

Timestamp: Trip in any phase or


phases from zone 2 - forward
direction

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

141

Section 7
Logical node data model
DO name
Mod

Table 44:
DO name
Beh

Str

Op

Mod

142

DO type
c_dINC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ZMFPDIS Logical node data (instance 3)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ3

Mon

Start in any phase or phases from


zone 3 - zone direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ3

Mon

Quality: Start in any phase or


phases from zone 3 - zone
direction

ST

STARTZ3

Mon

Timestamp: Start in any phase or


phases from zone 3 - zone
direction

general

ST

TRIPZ3

Mon

Trip in any phase or phases from


zone 3 - zone direction

ST

TRIPZ3

Mon

Quality: Trip in any phase or


phases from zone 3 - zone
direction

ST

TRIPZ3

Mon

Timestamp: Trip in any phase or


phases from zone 3 - zone
direction

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 45:
DO name
Beh

Str

Op

Mod

Table 46:
DO name
Beh

Str

ZMFPDIS Logical node data (instance 4)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ4

Mon

Start in any phase or phases from


zone 4 - zone direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ4

Mon

Quality: Start in any phase or


phases from zone 4 - zone
direction

ST

STARTZ4

Mon

Timestamp: Start in any phase or


phases from zone 4 - zone
direction

general

ST

TRIPZ4

Mon

Trip in any phase or phases from


zone 4 - zone direction

ST

TRIPZ4

Mon

Quality: Trip in any phase or


phases from zone 4 - zone
direction

ST

TRIPZ4

Mon

Timestamp: Trip in any phase or


phases from zone 4 - zone
direction

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ZMFPDIS Logical node data (instance 5)


DO type

DA name

a_dINS

b_dACD

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ5

Mon

Start in any phase or phases from


zone 5 - zone direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ5

Mon

Quality: Start in any phase or


phases from zone 5 - zone
direction

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

143

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Str

b_dACD

ST

STARTZ5

Mon

Timestamp: Start in any phase or


phases from zone 5 - zone
direction

Op

b_dACT

general

ST

TRIPZ5

Mon

Trip in any phase or phases from


zone 5 - zone direction

ST

TRIPZ5

Mon

Quality: Trip in any phase or


phases from zone 5 - zone
direction

ST

TRIPZ5

Mon

Timestamp: Trip in any phase or


phases from zone 5 - zone
direction

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Mod

Table 47:
DO name
Beh

Str

Op

Mod

144

c_dINC

ZMFPDIS Logical node data (instance 6)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZRV

Mon

Start in any phase or phases from


zone RV - reverse dir.

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZRV

Mon

Quality: Start in any phase or


phases from zone RV - reverse dir.

ST

STARTZRV

Mon

Timestamp: Start in any phase or


phases from zone RV - reverse dir.

general

ST

TRIPZRV

Mon

Trip in any phase or phases from


zone RV - reverse dir.

ST

TRIPZRV

Mon

Quality: Trip in any phase or


phases from zone RV - reverse dir.

ST

TRIPZRV

Mon

Timestamp: Trip in any phase or


phases from zone RV - reverse dir.

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.5.3.14

Table 48:
DO name
Str

Mod

Beh

Op

Phase selection, quadrilateral characteristic with settable angle


FRPSPDIS
LN type

LN prefix

LN class

Function block name

FPSRPDIS (revision 0)

FPSR

PDIS

FRPSPDIS

FRPSPDIS Logical node data


DO type

DA name

aACD

aINC

aINS

bACT

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Start in any phase or loop

dirGeneral

ST

Mon

Integer coded info about general


direction of fault

phsA

ST

STNDL1

Mon

Non directional start in L1

dirPhsA

ST

Mon

Integer coded info about direction


of fault, phase L1

phsB

ST

STNDL2

Mon

Non directional start in L2

dirPhsB

ST

Mon

Integer coded info about direction


of fault, phase L2

phsC

ST

STNDL3

Mon

Non directional start in L3

dirPhsC

ST

Mon

Integer coded info about direction


of fault, phase L3

ST

START

Mon

Quality: Start in any phase or loop

ST

START

Mon

Timestamp: Start in any phase or


loop

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

Trip output

ST

TRIP

Mon

Quality: Trip output

ST

TRIP

Mon

Timestamp: Trip output

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

145

Section 7
Logical node data model
DO name

DO type

StrCndZ

v1INS

StrCndA

StrFwdPhA

StrFwdPhB

StrFwdPhC

StrFwdGnd

StrRvPhA

StrRvPhB

v1INS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

STCNDZ

Mon

Start condition (Z< with LE and


3I0 E/F detection)

ST

STCNDZ

Mon

Quality: Start condition (Z< with


LE and 3I0 E/F detection)

ST

STCNDZ

Mon

Timestamp: Start condition (Z<


with LE and 3I0 E/F detection)

stVal

ST

STCNDLE

Mon

Start condition (only LE and 3I0 E/


F detection)

ST

STCNDLE

Mon

Quality: Start condition (only LE


and 3I0 E/F detection)

ST

STCNDLE

Mon

Timestamp: Start condition (only


LE and 3I0 E/F detection)

stVal

ST

STFWL1

Mon

Fault detected in phase L1 forward direction

ST

STFWL1

Mon

Quality: Fault detected in phase


L1 - forward direction

ST

STFWL1

Mon

Timestamp: Fault detected in


phase L1 - forward direction

stVal

ST

STFWL2

Mon

Fault detected in phase L2 forward direction

ST

STFWL2

Mon

Quality: Fault detected in phase


L2 - forward direction

ST

STFWL2

Mon

Timestamp: Fault detected in


phase L2 - forward direction

stVal

ST

STFWL3

Mon

Fault detected in phase L3 forward direction

ST

STFWL3

Mon

Quality: Fault detected in phase


L3 - forward direction

ST

STFWL3

Mon

Timestamp: Fault detected in


phase L3 - forward direction

stVal

ST

STFWPE

Mon

Earth fault detected in forward


direction

ST

STFWPE

Mon

Quality: Earth fault detected in


forward direction

ST

STFWPE

Mon

Timestamp: Earth fault detected


in forward direction

stVal

ST

STRVL1

Mon

Fault detected in phase L1 reverse direction

ST

STRVL1

Mon

Quality: Fault detected in phase


L1 - reverse direction

ST

STRVL1

Mon

Timestamp: Fault detected in


phase L1 - reverse direction

stVal

ST

STRVL2

Mon

Fault detected in phase L2 reverse direction

ST

STRVL2

Mon

Quality: Fault detected in phase


L2 - reverse direction

ST

STRVL2

Mon

Timestamp: Fault detected in


phase L2 - reverse direction

Table continues on next page

146

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
StrRvPhC

StrRvGnd

StrNDPhA

StrNDPhB

StrNDPhC

StrNDGnd

Str1Ph

Str2Ph

Str3Ph

DO type

DA name

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

FC

Signal

Mon/
Cmd

Description

stVal

ST

STRVL3

Mon

Fault detected in phase L3 reverse direction

ST

STRVL3

Mon

Quality: Fault detected in phase


L3 - reverse direction

ST

STRVL3

Mon

Timestamp: Fault detected in


phase L3 - reverse direction

stVal

ST

STRVPE

Mon

Earth fault detected in reverse


direction

ST

STRVPE

Mon

Quality: Earth fault detected in


reverse direction

ST

STRVPE

Mon

Timestamp: Earth fault detected


in reverse direction

stVal

ST

STNDL1

Mon

Non directional start in L1

ST

STNDL1

Mon

Quality: Non directional start in L1

ST

STNDL1

Mon

Timestamp: Non directional start


in L1

stVal

ST

STNDL2

Mon

Non directional start in L2

ST

STNDL2

Mon

Quality: Non directional start in L2

ST

STNDL2

Mon

Timestamp: Non directional start


in L2

stVal

ST

STNDL3

Mon

Non directional start in L3

ST

STNDL3

Mon

Quality: Non directional start in L3

ST

STNDL3

Mon

Timestamp: Non directional start


in L3

stVal

ST

STNDPE

Mon

Non directional start, phase-earth

ST

STNDPE

Mon

Quality: Non directional start,


phase-earth

ST

STNDPE

Mon

Timestamp: Non directional start,


phase-earth

stVal

ST

STFW1PH

Mon

Start in forward direction for singlephase fault

ST

STFW1PH

Mon

Quality: Start in forward direction


for single-phase fault

ST

STFW1PH

Mon

Timestamp: Start in forward


direction for single-phase fault

stVal

ST

STFW2PH

Mon

Start in forward direction for twophase fault

ST

STFW2PH

Mon

Quality: Start in forward direction


for two- phase fault

ST

STFW2PH

Mon

Timestamp: Start in forward


direction for two- phase fault

stVal

ST

STFW3PH

Mon

Start in forward direction for threphase fault

ST

STFW3PH

Mon

Quality: Start in forward direction


for thre-phase fault

ST

STFW3PH

Mon

Timestamp: Start in forward


direction for thre-phase fault

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

147

Section 7
Logical node data model
DO name

DO type

RelGnd

v1SPS

RelPP

v1SPS

7.5.3.15

Table 49:
DO name
Str

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

STPE

Mon

Current conditions release of


phase-earth measuring elements

ST

STPE

Mon

Quality: Current conditions


release of phase-earth measuring
elements

ST

STPE

Mon

Timestamp: Current conditions


release of phase-earth measuring
elements

stVal

ST

STPP

Mon

Current conditions release of


phase-phase measuring elements

ST

STPP

Mon

Quality: Current conditions


release of phase-phase
measuring elements

ST

STPP

Mon

Timestamp: Current conditions


release of phase-phase
measuring elements

High speed distance protection for series compensated lines


ZMFCPDIS
LN type

LN prefix

LN class

Function block name

PSFPDIS instance 7 (revision 0)

PSF

PDIS

ZMFCPDIS

ZMFCLLN0 instance 1 (revision 0)

LLN0

ZMFCPDIS

ZMFPDIS instance 1 (revision 0)

ZMF

PDIS

ZMFCPDIS

ZMFPDIS instance 2 (revision 0)

ZMF

PDIS

ZMFCPDIS

ZMFPDIS instance 3 (revision 0)

ZMF

PDIS

ZMFCPDIS

ZMFPDIS instance 4 (revision 0)

ZMF

PDIS

ZMFCPDIS

ZMFPDIS instance 5 (revision 0)

ZMF

PDIS

ZMFCPDIS

ZMFPDIS instance 6 (revision 0)

ZMF

PDIS

ZMFCPDIS

ZMFCPDIS Logical node data (instance 7)


DO type
a_dACD

DA name

FC

Signal

Mon/
Cmd

Description

general

ST

STARTND

Mon

Fault detected in any phase or


phases - any direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

phsA

ST

STNDL1

Mon

Fault detected in phase L1 - any


direction

dirPhsA

ST

L1Dir

Mon

Direction in phase L1

phsB

ST

STNDL2

Mon

Fault detected in phase L2 - any


direction

dirPhsB

ST

L2Dir

Mon

Direction in phase L2

Table continues on next page

148

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Str

Op

Beh

Mod

Table 50:
DO name
Mod

DO type

DA name

a_dACD

a_dACT

a_dINS

c_dINC

FC

Signal

Mon/
Cmd

Description

phsC

ST

STNDL3

Mon

Fault detected in phase L3 - any


direction

dirPhsC

ST

L3Dir

Mon

Direction in phase L3

ST

STARTND

Mon

Quality: Fault detected in any


phase or phases - any direction

ST

STARTND

Mon

Timestamp: Fault detected in any


phase or phases - any direction

general

ST

STARTND

Mon

Fault detected in any phase or


phases - any direction

phsA

ST

STNDL1

Mon

Fault detected in phase L1 - any


direction

phsB

ST

STNDL2

Mon

Fault detected in phase L2 - any


direction

phsC

ST

STNDL3

Mon

Fault detected in phase L3 - any


direction

ST

STARTND

Mon

Quality: Fault detected in any


phase or phases - any direction

ST

STARTND

Mon

Timestamp: Fault detected in any


phase or phases - any direction

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ZMFCPDIS Logical node data (instance 1)


DO type

DA name

a_dINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

149

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Mod

a_dINC

ST

Mon

Timestamp: Mode status value


parameter for 61850

Beh

a_dINS

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ1

Mon

Start in any phase or phases from


zone 1 - forward direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ1

Mon

Quality: Start in any phase or


phases from zone 1 - forward
direction

ST

STARTZ1

Mon

Timestamp: Start in any phase or


phases from zone 1 - forward
direction

general

ST

TRIPZ1

Mon

Trip in any phase or phases from


zone 1 - forward direction

ST

TRIPZ1

Mon

Quality: Trip in any phase or


phases from zone 1 - forward
direction

ST

TRIPZ1

Mon

Timestamp: Trip in any phase or


phases from zone 1 - forward
direction

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Table 51:
DO name
Beh

Str

Op

Mod

150

ZMFCPDIS Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

Description

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 52:
DO name
Beh

Str

Op

Mod

Table 53:
DO name
Beh

Str

ZMFCPDIS Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ2

Mon

Start in any phase or phases from


zone 2 - forward direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ2

Mon

Quality: Start in any phase or


phases from zone 2 - forward
direction

ST

STARTZ2

Mon

Timestamp: Start in any phase or


phases from zone 2 - forward
direction

general

ST

TRIPZ2

Mon

Trip in any phase or phases from


zone 2 - forward direction

ST

TRIPZ2

Mon

Quality: Trip in any phase or


phases from zone 2 - forward
direction

ST

TRIPZ2

Mon

Timestamp: Trip in any phase or


phases from zone 2 - forward
direction

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ZMFCPDIS Logical node data (instance 3)


DO type

DA name

a_dINS

b_dACD

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ3

Mon

Start in any phase or phases from


zone 3 - zone direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ3

Mon

Quality: Start in any phase or


phases from zone 3 - zone
direction

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

151

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Str

b_dACD

ST

STARTZ3

Mon

Timestamp: Start in any phase or


phases from zone 3 - zone
direction

Op

b_dACT

general

ST

TRIPZ3

Mon

Trip in any phase or phases from


zone 3 - zone direction

ST

TRIPZ3

Mon

Quality: Trip in any phase or


phases from zone 3 - zone
direction

ST

TRIPZ3

Mon

Timestamp: Trip in any phase or


phases from zone 3 - zone
direction

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Mod

Table 54:
DO name
Beh

Str

Op

Mod

152

c_dINC

ZMFCPDIS Logical node data (instance 4)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ4

Mon

Start in any phase or phases from


zone 4 - zone direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ4

Mon

Quality: Start in any phase or


phases from zone 4 - zone
direction

ST

STARTZ4

Mon

Timestamp: Start in any phase or


phases from zone 4 - zone
direction

general

ST

TRIPZ4

Mon

Trip in any phase or phases from


zone 4 - zone direction

ST

TRIPZ4

Mon

Quality: Trip in any phase or


phases from zone 4 - zone
direction

ST

TRIPZ4

Mon

Timestamp: Trip in any phase or


phases from zone 4 - zone
direction

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850
670 series 2.0 IEC
Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 55:
DO name
Beh

Str

Op

Mod

Table 56:
DO name
Beh

Str

ZMFCPDIS Logical node data (instance 5)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZ5

Mon

Start in any phase or phases from


zone 5 - zone direction

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZ5

Mon

Quality: Start in any phase or


phases from zone 5 - zone
direction

ST

STARTZ5

Mon

Timestamp: Start in any phase or


phases from zone 5 - zone
direction

general

ST

TRIPZ5

Mon

Trip in any phase or phases from


zone 5 - zone direction

ST

TRIPZ5

Mon

Quality: Trip in any phase or


phases from zone 5 - zone
direction

ST

TRIPZ5

Mon

Timestamp: Trip in any phase or


phases from zone 5 - zone
direction

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ZMFCPDIS Logical node data (instance 6)


DO type

DA name

a_dINS

b_dACD

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STARTZRV

Mon

Start in any phase or phases from


zone RV - reverse dir.

dirGeneral

ST

Mon

Integer (binary) coded info about


general direction of fault

ST

STARTZRV

Mon

Quality: Start in any phase or


phases from zone RV - reverse dir.

ST

STARTZRV

Mon

Timestamp: Start in any phase or


phases from zone RV - reverse dir.

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

153

Section 7
Logical node data model
DO name
Op

Mod

DO type
b_dACT

c_dINC

DA name

DO name
Beh

Str

Op

Mod

154

FC

Signal

Mon/
Cmd

Description

general

ST

TRIPZRV

Mon

Trip in any phase or phases from


zone RV - reverse dir.

ST

TRIPZRV

Mon

Quality: Trip in any phase or


phases from zone RV - reverse dir.

ST

TRIPZRV

Mon

Timestamp: Trip in any phase or


phases from zone RV - reverse dir.

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

7.5.3.16

Table 57:

1MRK 511 302-UEN -

Underimpedance protection for generators and transformers ZGVPDIS


LN type

LN prefix

LN class

Function block name

PH1PTRC instance 1 (revision 3)

PH1

PTRC

ZGVPDIS

ZGVLLN0 instance 1 (revision 0)

LLN0

ZGVPDIS

ZGVPDIS instance 1 (revision 0)

ZGV

PDIS

ZGVPDIS

ZGVPDIS instance 2 (revision 0)

ZGV

PDIS

ZGVPDIS

ZGVPDIS instance 3 (revision 0)

ZGV

PDIS

ZGVPDIS

ZGVPTUV instance 1 (revision 0)

ZGV

PTUV

ZGVPDIS

ZGVPDIS Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start

ST

START

Mon

Quality: General start

ST

START

Mon

Timestamp: General start

general

ST

TRIP

Mon

General Trip

ST

TRIP

Mon

Quality: General Trip

ST

TRIP

Mon

Timestamp: General Trip

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 58:
DO name
Mod

Beh

Table 59:
DO name
Beh

Str

Op

Mod

ZGVPDIS Logical node data (instance 1)


DO type

DA name

a_dINC

a_dINS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STZ1

Mon

Start signal Zone 1

ST

STZ1

Mon

Quality: Start signal Zone 1

ST

STZ1

Mon

Timestamp: Start signal Zone 1

general

ST

TRZ1

Mon

Trip signal Zone 1

ST

TRZ1

Mon

Quality: Trip signal Zone 1

ST

TRZ1

Mon

Timestamp: Trip signal Zone 1

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ZGVPDIS Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

Description

155

Section 7
Logical node data model

Table 60:
DO name
Beh

Str

Op

Mod

Table 61:
DO name
Beh

Str

Op

Mod

156

1MRK 511 302-UEN -

ZGVPDIS Logical node data (instance 2)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STZ2

Mon

Start signal Zone 2

ST

STZ2

Mon

Quality: Start signal Zone 2

ST

STZ2

Mon

Timestamp: Start signal Zone 2

general

ST

TRZ2

Mon

Trip signal Zone 2

ST

TRZ2

Mon

Quality: Trip signal Zone 2

ST

TRZ2

Mon

Timestamp: Trip signal Zone 2

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ZGVPDIS Logical node data (instance 3)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STZ3

Mon

Start signal Zone 3

ST

STZ3

Mon

Quality: Start signal Zone 3

ST

STZ3

Mon

Timestamp: Start signal Zone 3

general

ST

TRZ3

Mon

Trip signal Zone 3

ST

TRZ3

Mon

Quality: Trip signal Zone 3

ST

TRZ3

Mon

Timestamp: Trip signal Zone 3

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 62:
DO name
Beh

Str

Op

Mod

ZGVPDIS Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STUV

Mon

Start of under voltage seal in

ST

STUV

Mon

Quality: Start of under voltage


seal in

ST

STUV

Mon

Timestamp: Start of under


voltage seal in

general

ST

TRUV

Mon

Trip from Under voltage seal in

ST

TRUV

Mon

Quality: Trip from Under voltage


seal in

ST

TRUV

Mon

Timestamp: Trip from Under


voltage seal in

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

7.5.4

Directional overpower PDOP

7.5.4.1

Directional over-power protection GOPPDOP

Table 63:
DO name
Mod

Description

LN type

LN prefix

LN class

Function block name

GOPPDOP (revision 1)

GOP

PDOP

GOPPDOP

GOPPDOP Logical node data


DO type

DA name

a_dINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

157

Section 7
Logical node data model
DO name
Mod

Beh

Str

Op

OpZ1

OpZ2

StrZ1

StrZ2

MW

MVAr

7.5.5

158

DO type
a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v2_dMV

v2_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

START

Mon

Common start

ST

START

Mon

Quality: Common start

ST

START

Mon

Timestamp: Common start

general

ST

TRIP

Mon

Common trip signal

ST

TRIP

Mon

Quality: Common trip signal

ST

TRIP

Mon

Timestamp: Common trip signal

stVal

ST

TRIP1

Mon

Trip of stage 1

ST

TRIP1

Mon

Quality: Trip of stage 1

ST

TRIP1

Mon

Timestamp: Trip of stage 1

stVal

ST

TRIP2

Mon

Trip of stage 2

ST

TRIP2

Mon

Quality: Trip of stage 2

ST

TRIP2

Mon

Timestamp: Trip of stage 2

stVal

ST

START1

Mon

Start of stage 1

ST

START1

Mon

Quality: Start of stage 1

ST

START1

Mon

Timestamp: Start of stage 1

stVal

ST

START2

Mon

Start of stage 2

ST

START2

Mon

Quality: Start of stage 2

ST

START2

Mon

Timestamp: Start of stage 2

mag.f

MX

Mon

Active power P in MW

MX

Mon

Quality: Active power P in MW

MX

Mon

Timestamp: Active power P in MW

mag.f

MX

Mon

Reactive power Q in MVAr

MX

Mon

Quality: Reactive power Q in MVAr

MX

Mon

Timestamp: Reactive power Q in


MVAr

Directional underpower PDUP


LN type

LN prefix

LN class

Function block name

GUPPDUP (revision 1)

GUP

PDUP

GUPPDUP

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 64:
DO name
Mod

Beh

Str

Op

OpZ1

OpZ2

StrZ1

StrZ2

MW

MVAr

GUPPDUP Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v2_dMV

v2_dMV

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

START

Mon

Common start

ST

START

Mon

Quality: Common start

ST

START

Mon

Timestamp: Common start

general

ST

TRIP

Mon

Common trip signal

ST

TRIP

Mon

Quality: Common trip signal

ST

TRIP

Mon

Timestamp: Common trip signal

stVal

ST

TRIP1

Mon

Trip of stage 1

ST

TRIP1

Mon

Quality: Trip of stage 1

ST

TRIP1

Mon

Timestamp: Trip of stage 1

stVal

ST

TRIP2

Mon

Trip of stage 2

ST

TRIP2

Mon

Quality: Trip of stage 2

ST

TRIP2

Mon

Timestamp: Trip of stage 2

stVal

ST

START1

Mon

Start of stage 1

ST

START1

Mon

Quality: Start of stage 1

ST

START1

Mon

Timestamp: Start of stage 1

stVal

ST

START2

Mon

Start of stage 2

ST

START2

Mon

Quality: Start of stage 2

ST

START2

Mon

Timestamp: Start of stage 2

mag.f

MX

Mon

Active Power in MW

MX

Mon

Quality: Active Power in MW

MX

Mon

Timestamp: Active Power in MW

mag.f

MX

Mon

Reactive power in MVAr

MX

Mon

Quality: Reactive power in MVAr

MX

Mon

Timestamp: Reactive power in


MVAr
159

Section 7
Logical node data model

1MRK 511 302-UEN -

7.5.6

Rate of change of frequency PFRC

7.5.6.1

Rate-of-change frequency protection SAPFRC

Table 65:
DO name
Mod

Beh

Str

Op

BlkLoMg

LN type

LN prefix

LN class

Function block name

SAPFRC (revision 1)

SA

PFRC

SAPFRC

SAPFRC Logical node data


DO type
a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

Start/pick-up signal for frequency


gradient

ST

START

Mon

Quality: Start/pick-up signal for


frequency gradient

ST

START

Mon

Timestamp: Start/pick-up signal


for frequency gradient

general

ST

TRIP

Mon

Operate/trip signal for frequency


gradient

ST

TRIP

Mon

Quality: Operate/trip signal for


frequency gradient

ST

TRIP

Mon

Timestamp: Operate/trip signal


for frequency gradient

stVal

ST

BLKDMAGN

Mon

Blocking indication due to low


amplitude

ST

BLKDMAGN

Mon

Quality: Blocking indication due to


low amplitude

ST

BLKDMAGN

Mon

Timestamp: Blocking indication


due to low amplitude

Table continues on next page


160

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
RestLd

DO type

DA name

v1_dSPS

FC

Signal

Mon/
Cmd

Description

stVal

ST

RESTORE

Mon

Restore signal for load restoring


purposes

ST

RESTORE

Mon

Quality: Restore signal for load


restoring purposes

ST

RESTORE

Mon

Timestamp: Restore signal for


load restoring purposes

7.5.7

Frequency time accumulation protection QFVR

7.5.7.1

Frequency time accumulation protection FTAQFVR

Table 66:
DO name
Mod

Beh

HzVaTm

VarStr

LN type

LN prefix

LN class

Function block name

FTAQFVR (revision 1)

FTA

QFVR

FTAQFVR

FTAQFVR Logical node data


DO type

DA name

a_dINC

a_dINS

a_dMV

a_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

mag.f

MX

LASTEVTD

Mon

Accumulation time for last event


of frequency within band

MX

LASTEVTD

Mon

Quality: Accumulation time for


last event of frequency within band

MX

LASTEVTD

Mon

Timestamp: Accumulation time


for last event of frequency within
band

stVal

ST

START

Mon

Start signal of the function

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

161

Section 7
Logical node data model
DO name
VarStr

AccHzVaTm

DO type
a_dSPS

v1_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

START

Mon

Quality: Start signal of the function

ST

START

Mon

Timestamp: Start signal of the


function

mag.f

MX

ACCTIME

Mon

Accumulated time for frequency


band limits

MX

ACCTIME

Mon

Quality: Accumulated time for


frequency band limits

MX

ACCTIME

Mon

Timestamp: Accumulated time for


frequency band limits

7.5.8

Instantaneous overcurrent PIOC

7.5.8.1

Instantaneous phase overcurrent protection 3-phase output PHPIOC

Table 67:
DO name
Op

Mod

LN type

LN prefix

LN class

Function block name

PHPIOC (revision 0)

PH

PIOC

PHPIOC

PHPIOC Logical node data


DO type

DA name

aACT

general

ST

phsA

aINC

FC

Signal

Mon/
Cmd

Description

TRIP

Mon

Trip signal from any phase

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: Trip signal from any phase

ST

TRIP

Mon

Timestamp: Trip signal from any


phase

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

Table continues on next page

162

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Beh

DO type

DA name

aINS

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

7.5.8.2

Table 68:
DO name
Mod

Beh

Op

Description

Instantaneous residual overcurrent protection EFPIOC


LN type

LN prefix

LN class

Function block name

EFPIOC (revision 0)

EF

PIOC

EFPIOC

EFPIOC Logical node data


DO type

DA name

aINC

aINS

bACT

FC

Signal

Mon/
Cmd

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRIP

Mon

Trip signal

ST

TRIP

Mon

Quality: Trip signal

ST

TRIP

Mon

Timestamp: Trip signal

7.5.9

Local acceleration logic PLAL

7.5.9.1

Local acceleration logic ZCLCPLAL

670 series 2.0 IEC


Communication Protocol Manual

Description

LN type

LN prefix

LN class

Function block name

ZCLCPLAL (revision 0)

ZCLC

PLAL

ZCLCPSCH

163

Section 7
Logical node data model

Table 69:
DO name
Mod

Beh

OpLosLod

OpZnExd

1MRK 511 302-UEN -

ZCLCPSCH Logical node data


DO type
aINC

aINS

v2ACT

v2ACT

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRLL

Mon

Trip by loss of load

ST

TRLL

Mon

Quality: Trip by loss of load

ST

TRLL

Mon

Timestamp: Trip by loss of load

general

ST

TRZE

Mon

Trip by zone extension

ST

TRZE

Mon

Quality: Trip by zone extension

ST

TRZE

Mon

Timestamp: Trip by zone


extension

7.5.10

Protection scheme PSCH

7.5.10.1

Scheme communication logic with delta based blocking scheme


signal transmit ZCPSCH

Table 70:
DO name
Mod

LN type

LN prefix

LN class

Function block name

ZCPSCH (revision 2)

ZC

PSCH

ZCPSCH

ZCPSCH Logical node data


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Table continues on next page

164

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

LosOfGrd

ProRx

ProTx

Str

CarRx

Op

DO type

DA name

a_dINC

Oper.T

a_dINS

a_dSPS

a_dSPS

a_dSPS

b_dACD

b_dACT

b_dACT

FC

Signal

Mon/
Cmd

Description

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

LCG

Mon

Loss of carrier guard signal

ST

LCG

Mon

Quality: Loss of carrier guard


signal

ST

LCG

Mon

Timestamp: Loss of carrier guard


signal

stVal

ST

Mon

Teleprotection permissive signal


received from remote end

ST

Mon

Quality: Teleprotection
permissive signal received from
remote end

ST

Mon

Timestamp: Teleprotection
permissive signal received from
remote end

stVal

ST

Mon

Teleprotection permissive signal


transmitted to remote end

ST

Mon

Quality: Teleprotection
permissive signal transmitted to
remote end

ST

Mon

Timestamp: Teleprotection
permissive signal transmitted to
remote end

general

ST

CS

Mon

Carrier Send signal

dirGeneral

ST

Mon

Directional attribute of carrier


send signal

ST

CS

Mon

Quality: Carrier Send signal

ST

CS

Mon

Timestamp: Carrier Send signal

general

ST

CRL

Mon

Carrier signal received or missing


carrier guard signal

ST

CRL

Mon

Quality: Carrier signal received or


missing carrier guard signal

ST

CRL

Mon

Timestamp: Carrier signal


received or missing carrier guard
signal

general

ST

TRIP

Mon

Trip output

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

165

Section 7
Logical node data model
DO name

DO type

Op

b_dACT

StopTxBlk

v1_dSPS

DA name

DO name
Op

Mod

Beh

FC

Signal

Mon/
Cmd

Description

ST

TRIP

Mon

Quality: Trip output

ST

TRIP

Mon

Timestamp: Trip output

stVal

ST

CHSTOP

Mon

Stops the blocking signal to


remote end

ST

CHSTOP

Mon

Quality: Stops the blocking signal


to remote end

ST

CHSTOP

Mon

Timestamp: Stops the blocking


signal to remote end

7.5.10.2

Table 71:

1MRK 511 302-UEN -

Current reversal and WEI logic for distance protection 3-phase


ZCRWPSCH
LN type

LN prefix

LN class

Function block name

ZCRWPSCH (revision 2)

ZCRW

PSCH

ZCRWPSCH

ZCRWPSCH Logical node data


DO type
a_dACT

a_dINC

a_dINS

DA name

FC

Signal

Mon/
Cmd

Description

general

ST

TRWEI

Mon

Trip signal from weak end infeed


logic

phsA

ST

TRWEIL1

Mon

Trip signal from weak end infeed


logic in phase L1

phsB

ST

TRWEIL2

Mon

Trip signal from weak end infeed


logic in phase L2

phsC

ST

TRWEIL3

Mon

Trip signal from weak end infeed


logic in phase L3

ST

TRWEI

Mon

Quality: Trip signal from weak


end infeed logic

ST

TRWEI

Mon

Timestamp: Trip signal from weak


end infeed logic

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

Table continues on next page


166

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

Beh

a_dINS

ProRx

a_dSPS

ProTx

Str

Echo

RvABlk

WeiOp

DA name

a_dSPS

b_dACD

b_dACT

b_dACT

b_dACT

7.5.10.3

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Teleprotection permissive signal


received from remote end

ST

Mon

Quality: Teleprotection
permissive signal received from
remote end

ST

Mon

Timestamp: Teleprotection
permissive signal received from
remote end

stVal

ST

ECHO

Mon

Carrier send by WEI logic

ST

ECHO

Mon

Quality: Carrier send by WEI logic

ST

ECHO

Mon

Timestamp: Carrier send by WEI


logic

general

ST

ECHO

Mon

Carrier send by WEI logic

ST

ECHO

Mon

Quality: Carrier send by WEI logic

ST

ECHO

Mon

Timestamp: Carrier send by WEI


logic

general

ST

ECHO

Mon

Carrier send by WEI logic

ST

ECHO

Mon

Quality: Carrier send by WEI logic

ST

ECHO

Mon

Timestamp: Carrier send by WEI


logic

general

ST

IRVL

Mon

Operation of current reversal logic

ST

IRVL

Mon

Quality: Operation of current


reversal logic

ST

IRVL

Mon

Timestamp: Operation of current


reversal logic

general

ST

TRWEI

Mon

Trip signal from weak end infeed


logic

ST

TRWEI

Mon

Quality: Trip signal from weak


end infeed logic

ST

TRWEI

Mon

Timestamp: Trip signal from weak


end infeed logic

Scheme communication logic for residual overcurrent protection


ECPSCH
LN type

LN prefix

LN class

Function block name

ECPSCH (revision 1)

EC

PSCH

ECPSCH

167

Section 7
Logical node data model

Table 72:
DO name
Mod

Beh

ProRx

ProTx

LosOfGrd

Str

Op

1MRK 511 302-UEN -

ECPSCH Logical node data


DO type
a_dINC

a_dINS

a_dSPS

a_dSPS

a_dSPS

b_dACD

b_dACT

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Teleprotection permissive signal


received from remote end

ST

Mon

Quality: Teleprotection
permissive signal received from
remote end

ST

Mon

Timestamp: Teleprotection
permissive signal received from
remote end

stVal

ST

Mon

Teleprotection permissive signal


transmitted to remote end

ST

Mon

Quality: Teleprotection
permissive signal transmitted to
remote end

ST

Mon

Timestamp: Teleprotection
permissive signal transmitted to
remote end

stVal

ST

LCG

Mon

loss of carrier guard signal

ST

LCG

Mon

Quality: loss of carrier guard signal

ST

LCG

Mon

Timestamp: loss of carrier guard


signal

general

ST

CS

Mon

Carrier Send by Communication


Scheme Logic

dirGeneral

ST

Mon

Directional attribute of Carrier


Send signal

ST

CS

Mon

Quality: Carrier Send by


Communication Scheme Logic

ST

CS

Mon

Timestamp: Carrier Send by


Communication Scheme Logic

general

ST

TRIP

Mon

Trip signal by communication


scheme logic

Table continues on next page


168

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Op

CarRx

DO type

DA name

b_dACT

b_dACT

DO name
Mod

Beh

ProRx

Signal

Mon/
Cmd

Description

ST

TRIP

Mon

Quality: Trip signal by


communication scheme logic

ST

TRIP

Mon

Timestamp: Trip signal by


communication scheme logic

general

ST

CRL

Mon

Carrier Receive from


Communication Scheme Logic

ST

CRL

Mon

Quality: Carrier Receive from


Communication Scheme Logic

ST

CRL

Mon

Timestamp: Carrier Receive from


Communication Scheme Logic

7.5.10.4

Table 73:

FC

Current reversal and weak-end infeed logic for residual overcurrent


protection ECRWPSCH
LN type

LN prefix

LN class

Function block name

ECRWPSCH (revision 2)

ECRW

PSCH

ECRWPSCH

ECRWPSCH Logical node data


DO type

DA name

a_dINC

a_dINS

a_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Teleprotection permissive signal


received from remote end

ST

Mon

Quality: Teleprotection
permissive signal received from
remote end

ST

Mon

Timestamp: Teleprotection
permissive signal received from
remote end

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

169

Section 7
Logical node data model
DO name
ProTx

Str

Op

RvABlk

Echo

WeiOp

7.5.10.5

170

DO type
a_dSPS

b_dACD

b_dACT

b_dACT

b_dACT

b_dACT

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

ECHO

Mon

Permissive signal transmitted as


echo signal or in case of weak
end infeed

ST

ECHO

Mon

Quality: Permissive signal


transmitted as echo signal or in
case of weak end infeed

ST

ECHO

Mon

Timestamp: Permissive signal


transmitted as echo signal or in
case of weak end infeed

general

ST

ECHO

Mon

Permissive signal transmitted as


echo signal or in case of weak
end infeed

ST

ECHO

Mon

Quality: Permissive signal


transmitted as echo signal or in
case of weak end infeed

ST

ECHO

Mon

Timestamp: Permissive signal


transmitted as echo signal or in
case of weak end infeed

general

ST

TRWEI

Mon

Trip signal from weak end infeed


logic

ST

TRWEI

Mon

Quality: Trip signal from weak


end infeed logic

ST

TRWEI

Mon

Timestamp: Trip signal from weak


end infeed logic

general

ST

IRVL

Mon

Operation of current reversal logic

ST

IRVL

Mon

Quality: Operation of current


reversal logic

ST

IRVL

Mon

Timestamp: Operation of current


reversal logic

general

ST

ECHO

Mon

Permissive signal transmitted as


echo signal or in case of weak
end infeed

ST

ECHO

Mon

Quality: Permissive signal


transmitted as echo signal or in
case of weak end infeed

ST

ECHO

Mon

Timestamp: Permissive signal


transmitted as echo signal or in
case of weak end infeed

general

ST

TRWEI

Mon

Trip signal from weak end infeed


logic

ST

TRWEI

Mon

Quality: Trip signal from weak


end infeed logic

ST

TRWEI

Mon

Timestamp: Trip signal from weak


end infeed logic

Protection scheme [Line diff logic] LDLPSCH


LN type

LN prefix

LN class

Function block name

LDLPDIF (revision 0)

LDL

PDIF

LDLPSCH
670 series 2.0 IEC
Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 74:
DO name
Op

Mod

Beh

OpLoc

LocDifBlk

LDLPSCH Logical node data


DO type

DA name

aACT

general

ST

phsA

aINC

aINS

v1ACT

v1SPS

FC

Signal

Mon/
Cmd

Description

TRIP

Mon

General trip from differential


protection system

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General trip from


differential protection system

ST

TRIP

Mon

Timestamp: General trip from


differential protection system

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRLOCAL

Mon

Trip from local differential function

phsA

ST

TRLOCL1

Mon

Trip from local differential function


in phase L1

phsB

ST

TRLOCL2

Mon

Trip from local differential function


in phase L2

phsC

ST

TRLOCL3

Mon

Trip from local differential function


in phase L3

ST

TRLOCAL

Mon

Quality: Trip from local differential


function

ST

TRLOCAL

Mon

Timestamp: Trip from local


differential function

stVal

ST

DIFLBLKD

Mon

Local line differential function


blocked

ST

DIFLBLKD

Mon

Quality: Local line differential


function blocked

ST

DIFLBLKD

Mon

Timestamp: Local line differential


function blocked

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

171

Section 7
Logical node data model
DO name

DO type

DA name

OpRem

v2ACT

FC

general

ST

TRREMOTE

Mon

Trip from remote differential


function

ST

TRREMOTE

Mon

Quality: Trip from remote


differential function

ST

TRREMOTE

Mon

Timestamp: Trip from remote


differential function

7.5.10.6

Table 75:
DO name
Mod

Beh

Op

BlkLoSetZn

1MRK 511 302-UEN -

Signal

Mon/
Cmd

Description

Power swing logic PSLPSCH


LN type

LN prefix

LN class

Function block name

ZMRPSL (revision 2)

ZM

RPSL

PSLPSCH

PSLPSCH Logical node data


DO type
aINC

aINS

bACT

v1SPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

Trip through Power Swing Logic

ST

TRIP

Mon

Quality: Trip through Power


Swing Logic

ST

TRIP

Mon

Timestamp: Trip through Power


Swing Logic

stVal

ST

BLKZMUR

Mon

Block trip of underreaching


impedance zone

ST

BLKZMUR

Mon

Quality: Block trip of


underreaching impedance zone

ST

BLKZMUR

Mon

Timestamp: Block trip of


underreaching impedance zone

Table continues on next page


172

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
BlkHiSetZn

OpUnRchZn

CarSend

DO type

DA name

v1SPS

v2ACT

v2ACT

7.5.10.7

Table 76:
DO name
Str

FC

Signal

Mon/
Cmd

Description

stVal

ST

BLKZMOR

Mon

Block trip of overreaching


distance protection zones

ST

BLKZMOR

Mon

Quality: Block trip of overreaching


distance protection zones

ST

BLKZMOR

Mon

Timestamp: Block trip of


overreaching distance protection
zones

general

ST

STZMURPS

Mon

Start of Underreaching zone


controlled by PSL to be used in
configuration

ST

STZMURPS

Mon

Quality: Start of Underreaching


zone controlled by PSL to be
used in configuration

ST

STZMURPS

Mon

Timestamp: Start of
Underreaching zone controlled by
PSL to be used in configuration

general

ST

CS

Mon

Carrier send signal controlled by


the power swing

ST

CS

Mon

Quality: Carrier send signal


controlled by the power swing

ST

CS

Mon

Timestamp: Carrier send signal


controlled by the power swing

Phase segregated Scheme communication logic for distance


protection ZC1PPSCH
LN type

LN prefix

LN class

Function block name

ZPCPSCH (revision 0)

ZPC

PSCH

ZC1PPSCH

ZC1PPSCH Logical node data


DO type

DA name

FC

aACD

Signal

Mon/
Cmd

Description

general

ST

Mon

Logical OR of carrier Send signal


from all the three phases

dirGeneral

ST

Mon

Directional attribute of Carrier


Send signal

phsA

ST

CSL1

Mon

Carrier Send in phase L1

dirPhsA

ST

Mon

Directional attribute of Carrier


Send signal of Phase L1

phsB

ST

CSL2

Mon

Carrier Send in phase L2

dirPhsB

ST

Mon

Directional attribute of Carrier


Send signal of Phase L2

phsC

ST

CSL3

Mon

Carrier Send in phase L3

dirPhsC

ST

Mon

Directional attribute of Carrier


Send signal of Phase L3

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

173

Section 7
Logical node data model
DO name
Str

CarRx

Op

Mod

Beh

ProRx

DO type
aACD

aACT

aACT

aINC

aINS

aSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

Mon

Quality: Logical OR of carrier


Send signal from all the three
phases

ST

Mon

Timestamp: Logical OR of carrier


Send signal from all the three
phases

general

ST

Mon

Common carrier signal received


in either of the phases

phsA

ST

CRLL1

Mon

Carrier signal received in Phase


L1

phsB

ST

CRLL2

Mon

Carrier signal received in Phase


L2

phsC

ST

CRLL3

Mon

Carrier signal received in Phase


L3

ST

Mon

Quality: Common carrier signal


received in either of the phases

ST

Mon

Timestamp: Common carrier


signal received in either of the
phases

general

ST

TRIP

Mon

Common trip output in any of the


phase

phsA

ST

TRL1

Mon

Trip output in Phase L1

phsB

ST

TRL2

Mon

Trip output in Phase L2

phsC

ST

TRL3

Mon

Trip output in Phase L3

ST

TRIP

Mon

Quality: Common trip output in


any of the phase

ST

TRIP

Mon

Timestamp: Common trip output


in any of the phase

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Carrier signal received or missing


carrier guard signal

Table continues on next page

174

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
ProRx

ProTx

DO type

DA name

aSPS

aSPS

DO name
Str

Op

RvABlk

Signal

Mon/
Cmd

Description

ST

Mon

Quality: Carrier signal received or


missing carrier guard signal

ST

Mon

Timestamp: Carrier signal


received or missing carrier guard
signal

stVal

ST

Mon

Teleprotection signal transmitted


for a forward fault

ST

Mon

Quality: Teleprotection signal


transmitted for a forward fault

ST

Mon

Timestamp: Teleprotection signal


transmitted for a forward fault

7.5.10.8

Table 77:

FC

Current reversal and weak-end infeed logic for phase segregated


communication ZC1WPSCH
LN type

LN prefix

LN class

Function block name

ZPCWPSCH (revision 0)

ZPCW

PSCH

ZC1WPSCH

ZC1WPSCH Logical node data


DO type

DA name

aACD

aACT

aACT

FC

Signal

Mon/
Cmd

Description

general

ST

ECHO

Mon

Carrier Send by WEI logic

phsA

ST

ECHOL1

Mon

Carrier Send by WEI logic in


Phase L1

phsB

ST

ECHOL2

Mon

Carrier Send by WEI logic in


Phase L2

phsC

ST

ECHOL3

Mon

Carrier Send by WEI logic in


Phase L3

ST

ECHO

Mon

Quality: Carrier Send by WEI logic

ST

ECHO

Mon

Timestamp: Carrier Send by WEI


logic

general

ST

TRPWEI

Mon

Trip of WEI logic

phsA

ST

TRPWEIL1

Mon

Trip of WEI logic in Phase L1

phsB

ST

TRPWEIL2

Mon

Trip of WEI logic in Phase L2

phsC

ST

TRPWEIL3

Mon

Trip of WEI logic in Phase L3

ST

TRPWEI

Mon

Quality: Trip of WEI logic

ST

TRPWEI

Mon

Timestamp: Trip of WEI logic

general

ST

IRVOP

Mon

Operation of current reversal logic

phsA

ST

IRVOPL1

Mon

Operation of current reversal


logic in Phase L1

phsB

ST

IRVOPL2

Mon

Operation of current reversal


logic in Phase L2

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

175

Section 7
Logical node data model
DO name

DO type

RvABlk

aACT

Mod

Beh

ProRx

aINC

aINS

aSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

phsC

ST

IRVOPL3

Mon

Operation of current reversal


logic in Phase L3

ST

IRVOP

Mon

Quality: Operation of current


reversal logic

ST

IRVOP

Mon

Timestamp: Operation of current


reversal logic

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Teleprotection signal received for


a fault detected in forward
direction

ST

Mon

Quality: Teleprotection signal


received for a fault detected in
forward direction

ST

Mon

Timestamp: Teleprotection signal


received for a fault detected in
forward direction

7.5.11

Sensitive directional earth fault PSDE

7.5.11.1

Sensitive directional residual overcurrent and power protection


SDEPSDE

176

LN type

LN prefix

LN class

Function block name

SDEPSDE (revision 1)

SDE

PSDE

SDEPSDE

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 78:
DO name
Mod

Beh

Str

Op

OpResA

OpResV

StrResA

SDEPSDE Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start of the function

dirGeneral

ST

STDIR

Mon

Direction of fault. A general signal


common to all three mode of
residual over current protection

ST

START

Mon

Quality: General start of the


function

ST

START

Mon

Timestamp: General start of the


function

general

ST

TRIP

Mon

General trip of the function

ST

TRIP

Mon

Quality: General trip of the function

ST

TRIP

Mon

Timestamp: General trip of the


function

stVal

ST

TRNDIN

Mon

Trip of non directional residual


over current

ST

TRNDIN

Mon

Quality: Trip of non directional


residual over current

ST

TRNDIN

Mon

Timestamp: Trip of non


directional residual over current

stVal

ST

TRUN

Mon

Trip of non directional residual


over voltage

ST

TRUN

Mon

Quality: Trip of non directional


residual over voltage

ST

TRUN

Mon

Timestamp: Trip of non


directional residual over voltage

stVal

ST

STNDIN

Mon

Start of non directional residual


over current

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

177

Section 7
Logical node data model
DO name
StrResA

StrResV

StrDirResA

OpDirResA

AngAV

ResA

ResV

ResP

178

DO type
v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v2_dMV

v2_dMV

v2_dMV

v2_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

STNDIN

Mon

Quality: Start of non directional


residual over current

ST

STNDIN

Mon

Timestamp: Start of non


directional residual over current

stVal

ST

STUN

Mon

Start of non directional residual


over voltage

ST

STUN

Mon

Quality: Start of non directional


residual over voltage

ST

STUN

Mon

Timestamp: Start of non


directional residual over voltage

stVal

ST

STDIRIN

Mon

Start of the directional residual


over current function

ST

STDIRIN

Mon

Quality: Start of the directional


residual over current function

ST

STDIRIN

Mon

Timestamp: Start of the


directional residual over current
function

stVal

ST

TRDIRIN

Mon

Trip of the directional residual


over current function

ST

TRDIRIN

Mon

Quality: Trip of the directional


residual over current function

ST

TRDIRIN

Mon

Timestamp: Trip of the directional


residual over current function

mag.f

MX

ANG FI-RCA

Mon

Angle between 3U0 and 3I0


minus RCA (Fi-RCA)

MX

ANG FI-RCA

Mon

Quality: Angle between 3U0 and


3I0 minus RCA (Fi-RCA)

MX

ANG FI-RCA

Mon

Timestamp: Angle between 3U0


and 3I0 minus RCA (Fi-RCA)

mag.f

MX

IN

Mon

Measured magnitude of the


residual current 3I0

MX

IN

Mon

Quality: Measured magnitude of


the residual current 3I0

MX

IN

Mon

Timestamp: Measured magnitude


of the residual current 3I0

mag.f

MX

UN

Mon

Measured magnitude of the


residual voltage 3U0

MX

UN

Mon

Quality: Measured magnitude of


the residual voltage 3U0

MX

UN

Mon

Timestamp: Measured magnitude


of the residual voltage 3U0

mag.f

MX

SN

Mon

Measured magnitude of residual


power 3I03U0cos(Fi-RCA)

MX

SN

Mon

Quality: Measured magnitude of


residual power 3I03U0cos(FiRCA)

MX

SN

Mon

Timestamp: Measured magnitude


of residual power 3I03U0cos(FiRCA)

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.5.12

Switch onto fault logic PSOF

7.5.12.1

Automatic switch onto fault logic, voltage and current based ZCVPSOF

Table 79:
DO name
Mod

Beh

Op

LN type

LN prefix

LN class

Function block name

ZCVPSOF (revision 3)

ZCV

PSOF

ZCVPSOF

ZCVPSOF Logical node data


DO type

DA name

aINC

aINS

bACT

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRIP

Mon

Trip output

ST

TRIP

Mon

Quality: Trip output

ST

TRIP

Mon

Timestamp: Trip output

7.5.13

Time over current PTOC

7.5.13.1

Four step residual overcurrent protection, (Zero sequence or


negative sequence directionality) EF4PTOC

670 series 2.0 IEC


Communication Protocol Manual

LN type

LN prefix

LN class

Function block name

EF4LLN0 instance 1 (revision 1)

LLN0

EF4PTOC

EF4PTRC instance 1 (revision 3)

EF4

PTRC

EF4PTOC

EF4RDIR instance 1 (revision 6)

EF4

RDIR

EF4PTOC

GEN4PHAR instance 1 (revision 3)

GEN4

PHAR

EF4PTOC

PH1PTOC instance 1 (revision 3)

PH1

PTOC

EF4PTOC

179

Section 7
Logical node data model

Table 80:
DO name
Mod

Beh

IvdCrv

Table 81:
DO name
Beh

Str

Op

1MRK 511 302-UEN -

PH1PTOC instance 2 (revision 3)

PH1

PTOC

EF4PTOC

PH1PTOC instance 3 (revision 3)

PH1

PTOC

EF4PTOC

PH1PTOC instance 4 (revision 3)

PH1

PTOC

EF4PTOC

EF4PTOC Logical node data (instance 1)


DO type
aINC

aINS

v1SPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Invalid coefficients for user


programmable curve

ST

Mon

Quality: Invalid coefficients for


user programmable curve

ST

Mon

Timestamp: Invalid coefficients


for user programmable curve

EF4PTOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

General trip signal

Table continues on next page


180

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

Op

b_dACT

Mod

c_dINC

StrSOF

OpSOF

Table 82:
DO name
Beh

Dir

Mod

DA name

v2_dACD

v2_dACT

FC

Signal

Mon/
Cmd

Description

ST

TRIP

Mon

Quality: General trip signal

ST

TRIP

Mon

Timestamp: General trip signal

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

general

ST

STSOTF

Mon

Start signal from earth fault


switch onto fault function

ST

STSOTF

Mon

Quality: Start signal from earth


fault switch onto fault function

ST

STSOTF

Mon

Timestamp: Start signal from


earth fault switch onto fault
function

general

ST

TRSOTF

Mon

Trip signal from earth fault switch


onto fault function

ST

TRSOTF

Mon

Quality: Trip signal from earth


fault switch onto fault function

ST

TRSOTF

Mon

Timestamp: Trip signal from earth


fault switch onto fault function

EF4PTOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

dirGeneral

ST

Mon

Fault direction coded as integer

ST

Mon

Quality: Fault direction coded as


integer

ST

Mon

Timestamp: Fault direction coded


as integer

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

181

Section 7
Logical node data model

Table 83:
DO name
Beh

Str

Mod

Table 84:
DO name
Beh

Str

Op

Mod

182

1MRK 511 302-UEN -

EF4PTOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

2NDHARMD

Mon

2nd harmonic block signal

ST

2NDHARMD

Mon

Quality: 2nd harmonic block signal

ST

2NDHARMD

Mon

Timestamp: 2nd harmonic block


signal

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

EF4PTOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STIN1

Mon

Start signal step 1

ST

STIN1

Mon

Quality: Start signal step 1

ST

STIN1

Mon

Timestamp: Start signal step 1

general

ST

TRIN1

Mon

Trip signal from step 1

ST

TRIN1

Mon

Quality: Trip signal from step 1

ST

TRIN1

Mon

Timestamp: Trip signal from step 1

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 85:
DO name
Beh

Str

Op

Mod

Table 86:
DO name
Beh

Str

Op

Mod

EF4PTOC Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STIN2

Mon

Start signal step 2

ST

STIN2

Mon

Quality: Start signal step 2

ST

STIN2

Mon

Timestamp: Start signal step 2

general

ST

TRIN2

Mon

Trip signal from step 2

ST

TRIN2

Mon

Quality: Trip signal from step 2

ST

TRIN2

Mon

Timestamp: Trip signal from step 2

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

EF4PTOC Logical node data (instance 3)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STIN3

Mon

Start signal step 3

ST

STIN3

Mon

Quality: Start signal step 3

ST

STIN3

Mon

Timestamp: Start signal step 3

general

ST

TRIN3

Mon

Trip signal from step 3

ST

TRIN3

Mon

Quality: Trip signal from step 3

ST

TRIN3

Mon

Timestamp: Trip signal from step 3

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

183

Section 7
Logical node data model

Table 87:
DO name
Beh

Str

Op

Mod

EF4PTOC Logical node data (instance 4)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STIN4

Mon

Start signal step 4

ST

STIN4

Mon

Quality: Start signal step 4

ST

STIN4

Mon

Timestamp: Start signal step 4

general

ST

TRIN4

Mon

Trip signal from step 4

ST

TRIN4

Mon

Quality: Trip signal from step 4

ST

TRIN4

Mon

Timestamp: Trip signal from step 4

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

7.5.13.2

Table 88:
DO name
Beh

Str

1MRK 511 302-UEN -

Description

Four step phase overcurrent protection 3-phase output OC4PTOC


LN type

LN prefix

LN class

Function block name

GEN4PHAR instance 1 (revision 3)

GEN4

PHAR

OC4PTOC

OC4LLN0 instance 1 (revision 0)

LLN0

OC4PTOC

PH3PTOC instance 1 (revision 0)

PH3

PTOC

OC4PTOC

PH3PTOC instance 2 (revision 0)

PH3

PTOC

OC4PTOC

PH3PTOC instance 3 (revision 0)

PH3

PTOC

OC4PTOC

PH3PTOC instance 4 (revision 0)

PH3

PTOC

OC4PTOC

PH3PTRC instance 1 (revision 5)

PH3

PTRC

OC4PTOC

OC4PTOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST2NDHRM

Mon

Second harmonic detected

ST

ST2NDHRM

Mon

Quality: Second harmonic


detected

Table continues on next page


184

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Str

b_dACD

ST

ST2NDHRM

Mon

Timestamp: Second harmonic


detected

Mod

c_dINC

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

Table 89:
DO name
Mod

Beh

IvdCrv

Table 90:
DO name
Str

OC4PTOC Logical node data (instance 1)


DO type

DA name

aINC

aINS

v1SPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Invalid coefficients for user


programmable curve

ST

Mon

Quality: Invalid coefficients for


user programmable curve

ST

Mon

Timestamp: Invalid coefficients


for user programmable curve

OC4PTOC Logical node data (instance 1)


DO type

DA name

FC

Signal

Mon/
Cmd

aACD

Description

general

ST

ST1

Mon

Common start signal from step1

phsA

ST

ST1L1

Mon

Start signal from step1 phase L1

phsB

ST

ST1L2

Mon

Start signal from step1 phase L2

phsC

ST

ST1L3

Mon

Start signal from step1 phase L3

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

185

Section 7
Logical node data model
DO name
Str

Op

Beh

Mod

Table 91:
DO name
Str

Op

Beh

DO type
aACD

aACT

aINS

cINC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

ST1

Mon

Quality: Common start signal


from step1

ST

ST1

Mon

Timestamp: Common start signal


from step1

general

ST

TR1

Mon

Common trip signal from step1

phsA

ST

TR1L1

Mon

Trip signal from step1 phase L1

phsB

ST

TR1L2

Mon

Trip signal from step1 phase L2

phsC

ST

TR1L3

Mon

Trip signal from step1 phase L3

ST

TR1

Mon

Quality: Common trip signal from


step1

ST

TR1

Mon

Timestamp: Common trip signal


from step1

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

OC4PTOC Logical node data (instance 2)


DO type

DA name

aACD

aACT

aINS

FC

Signal

Mon/
Cmd

Description

general

ST

ST2

Mon

Common start signal from step2

phsA

ST

ST2L1

Mon

Start signal from step2 phase L1

phsB

ST

ST2L2

Mon

Start signal from step2 phase L2

phsC

ST

ST2L3

Mon

Start signal from step2 phase L3

ST

ST2

Mon

Quality: Common start signal


from step2

ST

ST2

Mon

Timestamp: Common start signal


from step2

general

ST

TR2

Mon

Common trip signal from step2

phsA

ST

TR2L1

Mon

Trip signal from step2 phase L1

phsB

ST

TR2L2

Mon

Trip signal from step2 phase L2

phsC

ST

TR2L3

Mon

Trip signal from step2 phase L3

ST

TR2

Mon

Quality: Common trip signal from


step2

ST

TR2

Mon

Timestamp: Common trip signal


from step2

stVal

ST

Beh

Mon

Behaviour parameter for 61850

Table continues on next page

186

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Beh

Mod

Table 92:
DO name
Str

Op

Beh

Mod

DO type

DA name

aINS

cINC

FC

Signal

Mon/
Cmd

Description

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

OC4PTOC Logical node data (instance 3)


DO type

DA name

aACD

aACT

aINS

cINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

general

ST

ST3

Mon

Common start signal from step3

phsA

ST

ST3L1

Mon

Start signal from step3 phase L1

phsB

ST

ST3L2

Mon

Start signal from step3 phase L2

phsC

ST

ST3L3

Mon

Start signal from step3 phase L3

ST

ST3

Mon

Quality: Common start signal


from step3

ST

ST3

Mon

Timestamp: Common start signal


from step3

general

ST

TR3

Mon

Common trip signal from step3

phsA

ST

TR3L1

Mon

Trip signal from step3 phase L1

phsB

ST

TR3L2

Mon

Trip signal from step3 phase L2

phsC

ST

TR3L3

Mon

Trip signal from step3 phase L3

ST

TR3

Mon

Quality: Common trip signal from


step3

ST

TR3

Mon

Timestamp: Common trip signal


from step3

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

187

Section 7
Logical node data model

Table 93:
DO name
Str

Op

Beh

Mod

Table 94:
DO name
Str

Op

1MRK 511 302-UEN -

OC4PTOC Logical node data (instance 4)


DO type

DA name

aACD

aACT

aINS

cINC

FC

Signal

Mon/
Cmd

Description

general

ST

ST4

Mon

Common start signal from step4

phsA

ST

ST4L1

Mon

Start signal from step4 phase L1

phsB

ST

ST4L2

Mon

Start signal from step4 phase L2

phsC

ST

ST4L3

Mon

Start signal from step4 phase L3

ST

ST4

Mon

Quality: Common start signal


from step4

ST

ST4

Mon

Timestamp: Common start signal


from step4

general

ST

TR4

Mon

Common trip signal from step4

phsA

ST

TR4L1

Mon

Trip signal from step4 phase L1

phsB

ST

TR4L2

Mon

Trip signal from step4 phase L2

phsC

ST

TR4L3

Mon

Trip signal from step4 phase L3

ST

TR4

Mon

Quality: Common trip signal from


step4

ST

TR4

Mon

Timestamp: Common trip signal


from step4

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

OC4PTOC Logical node data (instance 1)


DO type

DA name

aACD

aACT

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General start signal

phsA

ST

STL1

Mon

Start signal from phase L1

dirPhsA

ST

DIRL1

Mon

Direction for phase1

phsB

ST

STL2

Mon

Start signal from phase L2

dirPhsB

ST

DIRL2

Mon

Direction for phase2

phsC

ST

STL3

Mon

Start signal from phase L3

dirPhsC

ST

DIRL3

Mon

Direction for phase3

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

Trip

phsA

ST

TRL1

Mon

Trip signal from phase L1

Table continues on next page


188

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Op

Beh

Mod

DO type

DA name

aACT

aINS

cINC

FC

Signal

Mon/
Cmd

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: Trip

ST

TRIP

Mon

Timestamp: Trip

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

7.5.13.3

Table 95:
DO name
Str

Op

Mod

Description

Stub protection STBPTOC


LN type

LN prefix

LN class

Function block name

STBPTOC (revision 0)

STB

PTOC

STBPTOC

STBPTOC Logical node data


DO type

DA name

aACD

aACT

aINC

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General start

dirGeneral

ST

Mon

Output for reporting the fault type:


undir during start

phsA

ST

Mon

Start signal from phase L1

phsB

ST

Mon

Start signal from phase L2

phsC

ST

Mon

Start signal from phase L3

ST

START

Mon

Quality: General start

ST

START

Mon

Timestamp: General start

general

ST

TRIP

Mon

General trip

phsA

ST

Mon

Trip signal from phase L1

phsB

ST

Mon

Trip signal from phase L2

phsC

ST

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General trip

ST

TRIP

Mon

Timestamp: General trip

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

189

Section 7
Logical node data model
DO name
Mod

Beh

DO type
aINC

aINS

DA name

DO name
Mod

Beh

Str

FC

Signal

Mon/
Cmd

Description

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

7.5.13.4

Table 96:

1MRK 511 302-UEN -

Broken conductor check BRCPTOC


LN type

LN prefix

LN class

Function block name

BRCPTOC (revision 3)

BRC

PTOC

BRCPTOC

BRCPTOC Logical node data


DO type
a_dINC

a_dINS

b_dACD

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

START

Mon

Start signal of the protection logic

ST

START

Mon

Quality: Start signal of the


protection logic

Table continues on next page

190

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Str

b_dACD

ST

START

Mon

Timestamp: Start signal of the


protection logic

Op

b_dACT

general

ST

TRIP

Mon

Operate signal of the protection


logic

ST

TRIP

Mon

Quality: Operate signal of the


protection logic

ST

TRIP

Mon

Timestamp: Operate signal of the


protection logic

mag.f

MX

IUNBAL

Mon

Measured unbalance of phase


currents

MX

IUNBAL

Mon

Quality: Measured unbalance of


phase currents

MX

IUNBAL

Mon

Timestamp: Measured unbalance


of phase currents

mag.f

MX

Mon

Start duration in percents of the


total operating time

MX

Mon

Quality: Start duration in percents


of the total operating time

MX

Mon

Timestamp: Start duration in


percents of the total operating time

UnbA

StrDur

v2_dMV

v2_dMV

7.5.13.5

Table 97:
DO name
Mod

Negative-sequence time overcurrent protection for machines


NS2PTOC
LN type

LN prefix

LN class

Function block name

NS2LLN0 instance 1 (revision 1)

LLN0

NS2PTOC

NS2PTOC instance 1 (revision 1)

NS2

PTOC

NS2PTOC

NS2PTOC instance 2 (revision 1)

NS2

PTOC

NS2PTOC

NS2PTRC instance 1 (revision 2)

NS2

PTRC

NS2PTOC

NS2PTOC Logical node data (instance 1)


DO type

DA name

a_dINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

191

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Mod

a_dINC

ST

Mon

Timestamp: Mode status


parameter for 61850

Beh

a_dINS

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

ALARM

Mon

Alarm signal

ST

ALARM

Mon

Quality: Alarm signal

ST

ALARM

Mon

Timestamp: Alarm signal

mag.f

MX

NSCURR

Mon

Negative sequence current in


primary amps

MX

NSCURR

Mon

Quality: Negative sequence


current in primary amps

MX

NSCURR

Mon

Timestamp: Negative sequence


current in primary amps

Alm

NSCurr

Table 98:
DO name
Beh

Str

Op

Mod

192

a_dSPS

v2_dMV

NS2PTOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST1

Mon

Start signal from step 1

ST

ST1

Mon

Quality: Start signal from step 1

ST

ST1

Mon

Timestamp: Start signal from step


1

general

ST

TR1

Mon

Trip signal from step 1

ST

TR1

Mon

Quality: Trip signal from step 1

ST

TR1

Mon

Timestamp: Trip signal from step 1

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 99:
DO name
Beh

Str

Op

Mod

Table 100:
DO name
Beh

Str

Op

Mod

NS2PTOC Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST2

Mon

Start signal from step 2

ST

ST2

Mon

Quality: Start signal from step 2

ST

ST2

Mon

Timestamp: Start signal from step


2

general

ST

TR2

Mon

Trip signal from step 2

ST

TR2

Mon

Quality: Trip signal from step 2

ST

TR2

Mon

Timestamp: Trip signal from step 2

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

NS2PTOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

7.5.13.6

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

Common start signal

ST

START

Mon

Quality: Common start signal

ST

START

Mon

Timestamp: Common start signal

general

ST

TRIP

Mon

Common trip signal

ST

TRIP

Mon

Quality: Common trip signal

ST

TRIP

Mon

Timestamp: Common trip signal

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

Three phase overcurrent LCP3PTOC


LN type

LN prefix

LN class

Function block name

LCP3PTOC (revision 0)

LCP3

PTOC

LCP3PTOC
193

Section 7
Logical node data model

Table 101:
DO name
Str

Op

Mod

Beh

7.5.13.7

194

1MRK 511 302-UEN -

LCP3PTOC Logical node data


DO type
a_dACD

a_dACT

a_dINC

a_dINS

DA name

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common start signal

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: Common start signal

ST

START

Mon

Timestamp: Common start signal

general

ST

TRIP

Mon

Common trip signal

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: Common trip signal

ST

TRIP

Mon

Timestamp: Common trip signal

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Negative sequence overcurrent protection LCNSPTOC


LN type

LN prefix

LN class

Function block name

LCNSPTOC (revision 0)

LCNS

PTOC

LCNSPTOC

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 102:
DO name
Mod

Beh

Op

Str

LCNSPTOC Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACT

d_dACD

7.5.13.8

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

Trip signal negative sequence


over current protection

ST

TRIP

Mon

Quality: Trip signal negative


sequence over current protection

ST

TRIP

Mon

Timestamp: Trip signal negative


sequence over current protection

general

ST

START

Mon

Start signal for negative


sequence over current protection

ST

START

Mon

Quality: Start signal for negative


sequence over current protection

ST

START

Mon

Timestamp: Start signal for


negative sequence over current
protection

Zero sequence overcurrent protection LCZSPTOC


LN type

LN prefix

LN class

Function block name

LCZSPTOC (revision 0)

LCZS

PTOC

LCZSPTOC

195

Section 7
Logical node data model

Table 103:
DO name
Mod

Beh

Op

Str

7.5.13.9

196

1MRK 511 302-UEN -

LCZSPTOC Logical node data


DO type
a_dINC

a_dINS

b_dACT

d_dACD

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

Trip signal for zero sequence


over current protection

ST

TRIP

Mon

Quality: Trip signal for zero


sequence over current protection

ST

TRIP

Mon

Timestamp: Trip signal for zero


sequence over current protection

general

ST

START

Mon

Start signal for zero sequence


over current protection

ST

START

Mon

Quality: Start signal for zero


sequence over current protection

ST

START

Mon

Timestamp: Start signal for zero


sequence over current protection

Four step directional negative phase sequence overcurrent


protection NS4PTOC
LN type

LN prefix

LN class

Function block name

EF4LLN0 instance 1 (revision 1)

LLN0

NS4PTOC

EF4PTRC instance 1 (revision 4)

EF4

PTRC

NS4PTOC

EF4RDIR instance 1 (revision 6)

EF4

RDIR

NS4PTOC

GEN4PHAR instance 1 (revision 3)

GEN4

PHAR

NS4PTOC

PH1PTOC instance 1 (revision 3)

PH1

PTOC

NS4PTOC

PH1PTOC instance 2 (revision 3)

PH1

PTOC

NS4PTOC

PH1PTOC instance 3 (revision 3)

PH1

PTOC

NS4PTOC

PH1PTOC instance 4 (revision 3)

PH1

PTOC

NS4PTOC

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 104:
DO name
Mod

Beh

IvdCrv

Table 105:
DO name
Beh

Str

Op

NS4PTOC Logical node data (instance 1)


DO type

DA name

aINC

aINS

v1SPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Invalid coefficients for user


programmable curve

ST

Mon

Quality: Invalid coefficients for


user programmable curve

ST

Mon

Timestamp: Invalid coefficients


for user programmable curve

NS4PTOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

General trip signal

ST

TRIP

Mon

Quality: General trip signal

ST

TRIP

Mon

Timestamp: General trip signal

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

197

Section 7
Logical node data model
DO name
Mod

Table 106:
DO name
Beh

Dir

Mod

Table 107:
DO name
Beh

Mod

198

DO type
c_dINC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

NS4PTOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

dirGeneral

ST

Mon

Fault direction coded as integer

ST

Mon

Quality: Fault direction coded as


integer

ST

Mon

Timestamp: Fault direction coded


as integer

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

NS4PTOC Logical node data (instance 1)


DO type
a_dINS

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 108:
DO name
Beh

Str

Op

Mod

Table 109:
DO name
Beh

Str

Op

Mod

NS4PTOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST1

Mon

Start signal step 1

ST

ST1

Mon

Quality: Start signal step 1

ST

ST1

Mon

Timestamp: Start signal step 1

general

ST

TR1

Mon

Trip signal from step 1

ST

TR1

Mon

Quality: Trip signal from step 1

ST

TR1

Mon

Timestamp: Trip signal from step 1

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

NS4PTOC Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST2

Mon

Start signal step 2

ST

ST2

Mon

Quality: Start signal step 2

ST

ST2

Mon

Timestamp: Start signal step 2

general

ST

TR2

Mon

Trip signal from step 2

ST

TR2

Mon

Quality: Trip signal from step 2

ST

TR2

Mon

Timestamp: Trip signal from step 2

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

199

Section 7
Logical node data model

Table 110:
DO name
Beh

Str

Op

Mod

Table 111:
DO name
Beh

Str

Op

Mod

200

1MRK 511 302-UEN -

NS4PTOC Logical node data (instance 3)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST3

Mon

Start signal step 3

ST

ST3

Mon

Quality: Start signal step 3

ST

ST3

Mon

Timestamp: Start signal step 3

general

ST

TR3

Mon

Trip signal from step 3

ST

TR3

Mon

Quality: Trip signal from step 3

ST

TR3

Mon

Timestamp: Trip signal from step 3

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

NS4PTOC Logical node data (instance 4)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST4

Mon

Start signal step 4

ST

ST4

Mon

Quality: Start signal step 4

ST

ST4

Mon

Timestamp: Start signal step 4

general

ST

TR4

Mon

Trip signal from step 4

ST

TR4

Mon

Quality: Trip signal from step 4

ST

TR4

Mon

Timestamp: Trip signal from step 4

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.5.13.10

Table 112:
DO name
Beh

Str

Mod

Table 113:
DO name
Mod

Four step phase overcurrent protection OC4PTOC


LN type

LN prefix

LN class

Function block name

GEN4PHAR instance 1 (revision 3)

GEN4

PHAR

OC4PTOC

OC4LLN0 instance 1 (revision 0)

LLN0

OC4PTOC

PH3PTOC instance 1 (revision 0)

PH3

PTOC

OC4PTOC

PH3PTOC instance 2 (revision 0)

PH3

PTOC

OC4PTOC

PH3PTOC instance 3 (revision 0)

PH3

PTOC

OC4PTOC

PH3PTOC instance 4 (revision 0)

PH3

PTOC

OC4PTOC

PH3PTRC instance 1 (revision 5)

PH3

PTRC

OC4PTOC

OC4PTOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST2NDHRM

Mon

Second harmonic detected

ST

ST2NDHRM

Mon

Quality: Second harmonic


detected

ST

ST2NDHRM

Mon

Timestamp: Second harmonic


detected

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

OC4PTOC Logical node data (instance 1)


DO type

DA name

aINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

201

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Mod

aINC

ST

Mon

Timestamp: Mode status


parameter for 61850

Beh

aINS

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Invalid coefficients for user


programmable curve

ST

Mon

Quality: Invalid coefficients for


user programmable curve

ST

Mon

Timestamp: Invalid coefficients


for user programmable curve

IvdCrv

Table 114:
DO name
Str

Op

Beh

Mod

202

v1SPS

OC4PTOC Logical node data (instance 1)


DO type

DA name

aACD

aACT

aINS

cINC

FC

Signal

Mon/
Cmd

Description

general

ST

ST1

Mon

Common start signal from step1

phsA

ST

ST1L1

Mon

Start signal from step1 phase L1

phsB

ST

ST1L2

Mon

Start signal from step1 phase L2

phsC

ST

ST1L3

Mon

Start signal from step1 phase L3

ST

ST1

Mon

Quality: Common start signal


from step1

ST

ST1

Mon

Timestamp: Common start signal


from step1

general

ST

TR1

Mon

Common trip signal from step1

phsA

ST

TR1L1

Mon

Trip signal from step1 phase L1

phsB

ST

TR1L2

Mon

Trip signal from step1 phase L2

phsC

ST

TR1L3

Mon

Trip signal from step1 phase L3

ST

TR1

Mon

Quality: Common trip signal from


step1

ST

TR1

Mon

Timestamp: Common trip signal


from step1

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 115:
DO name
Str

Op

Beh

Mod

Table 116:
DO name
Str

Op

OC4PTOC Logical node data (instance 2)


DO type

DA name

aACD

aACT

aINS

cINC

FC

Signal

Mon/
Cmd

Description

general

ST

ST2

Mon

Common start signal from step2

phsA

ST

ST2L1

Mon

Start signal from step2 phase L1

phsB

ST

ST2L2

Mon

Start signal from step2 phase L2

phsC

ST

ST2L3

Mon

Start signal from step2 phase L3

ST

ST2

Mon

Quality: Common start signal


from step2

ST

ST2

Mon

Timestamp: Common start signal


from step2

general

ST

TR2

Mon

Common trip signal from step2

phsA

ST

TR2L1

Mon

Trip signal from step2 phase L1

phsB

ST

TR2L2

Mon

Trip signal from step2 phase L2

phsC

ST

TR2L3

Mon

Trip signal from step2 phase L3

ST

TR2

Mon

Quality: Common trip signal from


step2

ST

TR2

Mon

Timestamp: Common trip signal


from step2

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

OC4PTOC Logical node data (instance 3)


DO type

DA name

aACD

aACT

FC

Signal

Mon/
Cmd

Description

general

ST

ST3

Mon

Common start signal from step3

phsA

ST

ST3L1

Mon

Start signal from step3 phase L1

phsB

ST

ST3L2

Mon

Start signal from step3 phase L2

phsC

ST

ST3L3

Mon

Start signal from step3 phase L3

ST

ST3

Mon

Quality: Common start signal


from step3

ST

ST3

Mon

Timestamp: Common start signal


from step3

general

ST

TR3

Mon

Common trip signal from step3

phsA

ST

TR3L1

Mon

Trip signal from step3 phase L1

phsB

ST

TR3L2

Mon

Trip signal from step3 phase L2

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

203

Section 7
Logical node data model
DO name
Op

Beh

Mod

Table 117:
DO name
Str

Op

Beh

Mod

204

DO type
aACT

aINS

cINC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

phsC

ST

TR3L3

Mon

Trip signal from step3 phase L3

ST

TR3

Mon

Quality: Common trip signal from


step3

ST

TR3

Mon

Timestamp: Common trip signal


from step3

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

OC4PTOC Logical node data (instance 4)


DO type

DA name

aACD

aACT

aINS

cINC

FC

Signal

Mon/
Cmd

Description

general

ST

ST4

Mon

Common start signal from step4

phsA

ST

ST4L1

Mon

Start signal from step4 phase L1

phsB

ST

ST4L2

Mon

Start signal from step4 phase L2

phsC

ST

ST4L3

Mon

Start signal from step4 phase L3

ST

ST4

Mon

Quality: Common start signal


from step4

ST

ST4

Mon

Timestamp: Common start signal


from step4

general

ST

TR4

Mon

Common trip signal from step4

phsA

ST

TR4L1

Mon

Trip signal from step4 phase L1

phsB

ST

TR4L2

Mon

Trip signal from step4 phase L2

phsC

ST

TR4L3

Mon

Trip signal from step4 phase L3

ST

TR4

Mon

Quality: Common trip signal from


step4

ST

TR4

Mon

Timestamp: Common trip signal


from step4

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 118:
DO name
Str

Op

Beh

Mod

OC4PTOC Logical node data (instance 1)


DO type

DA name

aACD

aACT

aINS

cINC

7.5.13.11

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

General start signal

phsA

ST

STL1

Mon

Start signal from phase L1

dirPhsA

ST

DIRL1

Mon

Direction for phase1

phsB

ST

STL2

Mon

Start signal from phase L2

dirPhsB

ST

DIRL2

Mon

Direction for phase2

phsC

ST

STL3

Mon

Start signal from phase L3

dirPhsC

ST

DIRL3

Mon

Direction for phase3

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

Trip

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: Trip

ST

TRIP

Mon

Timestamp: Trip

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

Four step single phase overcurrent protection PH4SPTOC


LN type

LN prefix

LN class

Function block name

GEN4PHAR instance 1 (revision 3)

GEN4

PHAR

PH4SPTOC

OCNDLLN0 instance 1 (revision 0)

LLN0

PH4SPTOC

PH1BPTOC instance 1 (revision 1)

PH1B

PTOC

PH4SPTOC

PH1BPTOC instance 2 (revision 1)

PH1B

PTOC

PH4SPTOC

PH1BPTOC instance 3 (revision 1)

PH1B

PTOC

PH4SPTOC

PH1BPTOC instance 4 (revision 1)

PH1B

PTOC

PH4SPTOC

PH1PTRC instance 1 (revision 3)

PH1

PTRC

PH4SPTOC

205

Section 7
Logical node data model

Table 119:
DO name
Beh

Str

Mod

Table 120:
DO name
Mod

Beh

IvdCrv

206

1MRK 511 302-UEN -

PH4SPTOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST2NDHRM

Mon

Second harmonic detected

ST

ST2NDHRM

Mon

Quality: Second harmonic


detected

ST

ST2NDHRM

Mon

Timestamp: Second harmonic


detected

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

PH4SPTOC Logical node data (instance 1)


DO type
aINC

aINS

v1SPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Invalid coefficients for user


programmable curve

ST

Mon

Quality: Invalid coefficients for


user programmable curve

ST

Mon

Timestamp: Invalid coefficients


for user programmable curve

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 121:
DO name
Beh

Str

Op

Mod

Table 122:
DO name
Beh

Str

Op

Mod

PH4SPTOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST1

Mon

Common start signal from step1

ST

ST1

Mon

Quality: Common start signal


from step1

ST

ST1

Mon

Timestamp: Common start signal


from step1

general

ST

TR1

Mon

Common trip signal from step1

ST

TR1

Mon

Quality: Common trip signal from


step1

ST

TR1

Mon

Timestamp: Common trip signal


from step1

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

PH4SPTOC Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST2

Mon

Common start signal from step2

ST

ST2

Mon

Quality: Common start signal


from step2

ST

ST2

Mon

Timestamp: Common start signal


from step2

general

ST

TR2

Mon

Common trip signal from step2

ST

TR2

Mon

Quality: Common trip signal from


step2

ST

TR2

Mon

Timestamp: Common trip signal


from step2

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

207

Section 7
Logical node data model

Table 123:
DO name
Beh

Str

Op

Mod

Table 124:
DO name
Beh

Str

Op

Mod

208

1MRK 511 302-UEN -

PH4SPTOC Logical node data (instance 3)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST3

Mon

Common start signal from step3

ST

ST3

Mon

Quality: Common start signal


from step3

ST

ST3

Mon

Timestamp: Common start signal


from step3

general

ST

TR3

Mon

Common trip signal from step3

ST

TR3

Mon

Quality: Common trip signal from


step3

ST

TR3

Mon

Timestamp: Common trip signal


from step3

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

PH4SPTOC Logical node data (instance 4)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST4

Mon

Common start signal from step4

ST

ST4

Mon

Quality: Common start signal


from step4

ST

ST4

Mon

Timestamp: Common start signal


from step4

general

ST

TR4

Mon

Common trip signal from step4

ST

TR4

Mon

Quality: Common trip signal from


step4

ST

TR4

Mon

Timestamp: Common trip signal


from step4

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 125:
DO name
Beh

Str

Op

Mod

PH4SPTOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

7.5.13.12

Table 126:
DO name
Mod

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

Trip

ST

TRIP

Mon

Quality: Trip

ST

TRIP

Mon

Timestamp: Trip

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

Four step residual overcurrent protection EF4PTOC


LN type

LN prefix

LN class

Function block name

EF4LLN0 instance 1 (revision 1)

LLN0

EF4PTOC

EF4PTRC instance 1 (revision 3)

EF4

PTRC

EF4PTOC

EF4RDIR instance 1 (revision 6)

EF4

RDIR

EF4PTOC

GEN4PHAR instance 1 (revision 3)

GEN4

PHAR

EF4PTOC

PH1PTOC instance 1 (revision 3)

PH1

PTOC

EF4PTOC

PH1PTOC instance 2 (revision 3)

PH1

PTOC

EF4PTOC

PH1PTOC instance 3 (revision 3)

PH1

PTOC

EF4PTOC

PH1PTOC instance 4 (revision 3)

PH1

PTOC

EF4PTOC

EF4PTOC Logical node data (instance 1)


DO type

DA name

aINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

209

Section 7
Logical node data model
DO name
Mod

Beh

IvdCrv

Table 127:
DO name
Beh

Str

Op

Mod

StrSOF

DO type
aINC

aINS

v1SPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Invalid coefficients for user


programmable curve

ST

Mon

Quality: Invalid coefficients for


user programmable curve

ST

Mon

Timestamp: Invalid coefficients


for user programmable curve

EF4PTOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

v2_dACD

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

General trip signal

ST

TRIP

Mon

Quality: General trip signal

ST

TRIP

Mon

Timestamp: General trip signal

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

general

ST

STSOTF

Mon

Start signal from earth fault


switch onto fault function

ST

STSOTF

Mon

Quality: Start signal from earth


fault switch onto fault function

ST

STSOTF

Mon

Timestamp: Start signal from


earth fault switch onto fault
function

Table continues on next page

210

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
OpSOF

Table 128:
DO name
Beh

Dir

Mod

Table 129:
DO name
Beh

Str

Mod

DO type

DA name

v2_dACT

FC

Signal

Mon/
Cmd

Description

general

ST

TRSOTF

Mon

Trip signal from earth fault switch


onto fault function

ST

TRSOTF

Mon

Quality: Trip signal from earth


fault switch onto fault function

ST

TRSOTF

Mon

Timestamp: Trip signal from earth


fault switch onto fault function

EF4PTOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

dirGeneral

ST

Mon

Fault direction coded as integer

ST

Mon

Quality: Fault direction coded as


integer

ST

Mon

Timestamp: Fault direction coded


as integer

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

EF4PTOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

2NDHARMD

Mon

2nd harmonic block signal

ST

2NDHARMD

Mon

Quality: 2nd harmonic block signal

ST

2NDHARMD

Mon

Timestamp: 2nd harmonic block


signal

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

211

Section 7
Logical node data model

Table 130:
DO name
Beh

Str

Op

Mod

Table 131:
DO name
Beh

Str

Op

Mod

212

1MRK 511 302-UEN -

EF4PTOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STIN1

Mon

Start signal step 1

ST

STIN1

Mon

Quality: Start signal step 1

ST

STIN1

Mon

Timestamp: Start signal step 1

general

ST

TRIN1

Mon

Trip signal from step 1

ST

TRIN1

Mon

Quality: Trip signal from step 1

ST

TRIN1

Mon

Timestamp: Trip signal from step 1

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

EF4PTOC Logical node data (instance 2)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STIN2

Mon

Start signal step 2

ST

STIN2

Mon

Quality: Start signal step 2

ST

STIN2

Mon

Timestamp: Start signal step 2

general

ST

TRIN2

Mon

Trip signal from step 2

ST

TRIN2

Mon

Quality: Trip signal from step 2

ST

TRIN2

Mon

Timestamp: Trip signal from step 2

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 132:
DO name
Beh

Str

Op

Mod

Table 133:
DO name
Beh

Str

Op

Mod

EF4PTOC Logical node data (instance 3)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STIN3

Mon

Start signal step 3

ST

STIN3

Mon

Quality: Start signal step 3

ST

STIN3

Mon

Timestamp: Start signal step 3

general

ST

TRIN3

Mon

Trip signal from step 3

ST

TRIN3

Mon

Quality: Trip signal from step 3

ST

TRIN3

Mon

Timestamp: Trip signal from step 3

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

EF4PTOC Logical node data (instance 4)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STIN4

Mon

Start signal step 4

ST

STIN4

Mon

Quality: Start signal step 4

ST

STIN4

Mon

Timestamp: Start signal step 4

general

ST

TRIN4

Mon

Trip signal from step 4

ST

TRIN4

Mon

Quality: Trip signal from step 4

ST

TRIN4

Mon

Timestamp: Trip signal from step 4

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

213

Section 7
Logical node data model
7.5.13.13

Table 134:
DO name
Mod

Beh

Str

Op

1MRK 511 302-UEN -

Sudden change in current variation SCCVPTOC


LN type

LN prefix

LN class

Function block name

SCCVPTOC (revision 0)

SCCV

PTOC

SCCVPTOC

SCCVPTOC Logical node data


DO type
a_dINC

a_dINS

b_dACD

b_dACT

DA name

FC

Signal

Mon/
Cmd

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

Common start signal

ST

START

Mon

Quality: Common start signal

ST

START

Mon

Timestamp: Common start signal

general

ST

TRIP

Mon

Common trip signal

ST

TRIP

Mon

Quality: Common trip signal

ST

TRIP

Mon

Timestamp: Common trip signal

7.5.14

Overfrequency PTOF

7.5.14.1

Overfrequency protection SAPTOF

214

Description

LN type

LN prefix

LN class

Function block name

SAPTOF (revision 1)

SA

PTOF

SAPTOF

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 135:
DO name
Mod

Beh

Str

Op

BlkLoMg

SAPTOF Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

General trip signal

ST

TRIP

Mon

Quality: General trip signal

ST

TRIP

Mon

Timestamp: General trip signal

stVal

ST

BLKDMAGN

Mon

Measurement blocked due to low


amplitude

ST

BLKDMAGN

Mon

Quality: Measurement blocked


due to low amplitude

ST

BLKDMAGN

Mon

Timestamp: Measurement
blocked due to low amplitude

7.5.15

Overvoltage PTOV

7.5.15.1

Negative sequence overvoltage protection LCNSPTOV

670 series 2.0 IEC


Communication Protocol Manual

LN type

LN prefix

LN class

Function block name

LCNSPTOV (revision 0)

LCNS

PTOV

LCNSPTOV

215

Section 7
Logical node data model

Table 136:
DO name
Mod

Beh

Op

Str

LCNSPTOV Logical node data


DO type
a_dINC

a_dINS

b_dACT

d_dACD

7.5.15.2

Table 137:
DO name
Mod

1MRK 511 302-UEN -

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

Trip signal for negative sequence


over voltage

ST

TRIP

Mon

Quality: Trip signal for negative


sequence over voltage

ST

TRIP

Mon

Timestamp: Trip signal for


negative sequence over voltage

general

ST

START

Mon

Start signal for negative


sequence over voltage

ST

START

Mon

Quality: Start signal for negative


sequence over voltage

ST

START

Mon

Timestamp: Start signal for


negative sequence over voltage

Zero sequence overvoltage protection LCZSPTOV


LN type

LN prefix

LN class

Function block name

LCZSPTOV (revision 0)

LCZS

PTOV

LCZSPTOV

LCZSPTOV Logical node data


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Table continues on next page


216

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

Op

Str

DO type

DA name

a_dINC

a_dINS

b_dACT

d_dACD

7.5.15.3

Table 138:
DO name
Mod

FC

Signal

Mon/
Cmd

Description

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

TRIP signal for zero sequence


over voltage protection

ST

TRIP

Mon

Quality: TRIP signal for zero


sequence over voltage protection

ST

TRIP

Mon

Timestamp: TRIP signal for zero


sequence over voltage protection

general

ST

START

Mon

Start signal for zero sequence


over voltage protection

ST

START

Mon

Quality: Start signal for zero


sequence over voltage protection

ST

START

Mon

Timestamp: Start signal for zero


sequence over voltage protection

Two step overvoltage protection OV2PTOV


LN type

LN prefix

LN class

Function block name

GEN2LLN0 instance 1 (revision 0)

LLN0

OV2PTOV

OV2PTOV instance 1 (revision 0)

OV2

PTOV

OV2PTOV

OV2PTOV instance 2 (revision 0)

OV2

PTOV

OV2PTOV

PH1PTRC instance 1 (revision 3)

PH1

PTRC

OV2PTOV

OV2PTOV Logical node data (instance 1)


DO type

DA name

aINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

217

Section 7
Logical node data model
DO name
Mod

Beh

Table 139:
DO name
Str

Op

Beh

Mod

218

DO type
aINC

aINS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

FC

Signal

Mon/
Cmd

OV2PTOV Logical node data (instance 1)


DO type

DA name

aACD

general

ST

ST1

Mon

Common start signal from step1

phsA

ST

ST1L1

Mon

Start signal from step1 phase L1

phsB

ST

ST1L2

Mon

Start signal from step1 phase L2

phsC

ST

ST1L3

Mon

Start signal from step1 phase L3

ST

ST1

Mon

Quality: Common start signal


from step1

ST

ST1

Mon

Timestamp: Common start signal


from step1

general

ST

TR1

Mon

Common trip signal from step1

phsA

ST

TR1L1

Mon

Trip signal from step1 phase L1

phsB

ST

TR1L2

Mon

Trip signal from step1 phase L2

phsC

ST

TR1L3

Mon

Trip signal from step1 phase L3

ST

TR1

Mon

Quality: Common trip signal from


step1

ST

TR1

Mon

Timestamp: Common trip signal


from step1

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

aACT

aINS

cINC

Description

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 140:
DO name
Str

Op

Beh

Mod

Table 141:
DO name
Beh

Str

Op

Mod

OV2PTOV Logical node data (instance 2)


DO type

DA name

aACD

aACT

aINS

cINC

FC

Signal

Mon/
Cmd

Description

general

ST

ST2

Mon

Common start signal from step2

phsA

ST

ST2L1

Mon

Start signal from step2 phase L1

phsB

ST

ST2L2

Mon

Start signal from step2 phase L2

phsC

ST

ST2L3

Mon

Start signal from step2 phase L3

ST

ST2

Mon

Quality: Common start signal


from step2

ST

ST2

Mon

Timestamp: Common start signal


from step2

general

ST

TR2

Mon

Common trip signal from step2

phsA

ST

TR2L1

Mon

Trip signal from step2 phase L1

phsB

ST

TR2L2

Mon

Trip signal from step2 phase L2

phsC

ST

TR2L3

Mon

Trip signal from step2 phase L3

ST

TR2

Mon

Quality: Common trip signal from


step2

ST

TR2

Mon

Timestamp: Common trip signal


from step2

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

OV2PTOV Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

Trip

ST

TRIP

Mon

Quality: Trip

ST

TRIP

Mon

Timestamp: Trip

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850
219

Section 7
Logical node data model
7.5.15.4

Table 142:
DO name
Mod

Beh

Table 143:
DO name
Beh

Str

Op

1MRK 511 302-UEN -

Two step residual overvoltage protection ROV2PTOV


LN type

LN prefix

LN class

Function block name

GEN2LLN0 instance 1 (revision 1)

LLN0

ROV2PTOV

PH1PTRC instance 1 (revision 3)

PH1

PTRC

ROV2PTOV

ROV2PTOV instance 1 (revision 1)

ROV2

PTOV

ROV2PTOV

ROV2PTOV instance 2 (revision 1)

ROV2

PTOV

ROV2PTOV

ROV2PTOV Logical node data (instance 1)


DO type
a_dINC

a_dINS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

Trip

ST

TRIP

Mon

Quality: Trip

ROV2PTOV Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

DA name

Description

Table continues on next page


220

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Op

b_dACT

ST

TRIP

Mon

Timestamp: Trip

Mod

c_dINC

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Table 144:
DO name
Beh

Str

Op

Mod

Table 145:
DO name
Beh

Str

ROV2PTOV Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST1

Mon

Common start signal from step1

ST

ST1

Mon

Quality: Common start signal


from step1

ST

ST1

Mon

Timestamp: Common start signal


from step1

general

ST

TR1

Mon

Common trip signal from step1

ST

TR1

Mon

Quality: Common trip signal from


step1

ST

TR1

Mon

Timestamp: Common trip signal


from step1

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

ROV2PTOV Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

ST2

Mon

Common start signal from step2

ST

ST2

Mon

Quality: Common start signal


from step2

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

221

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Str

b_dACD

ST

ST2

Mon

Timestamp: Common start signal


from step2

Op

b_dACT

general

ST

TR2

Mon

Common trip signal from step2

ST

TR2

Mon

Quality: Common trip signal from


step2

ST

TR2

Mon

Timestamp: Common trip signal


from step2

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Mod

c_dINC

7.5.15.5

Table 146:
DO name
Mod

Beh

Str

Voltage differential protection VDCPTOV


LN type

LN prefix

LN class

Function block name

VDCPTOV (revision 2)

VDC

PTOV

VDCPTOV

VDCPTOV Logical node data


DO type
a_dINC

a_dINS

b_dACD

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

START

Mon

Start of voltage differential


protection

ST

START

Mon

Quality: Start of voltage


differential protection

Table continues on next page

222

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Str

b_dACD

ST

START

Mon

Timestamp: Start of voltage


differential protection

Op

b_dACT

general

ST

TRIP

Mon

Voltage differential protection


operated

ST

TRIP

Mon

Quality: Voltage differential


protection operated

ST

TRIP

Mon

Timestamp: Voltage differential


protection operated

7.5.16

Protection trip conditioning PTRC

7.5.16.1

Carrier receive logic LCCRPTRC

Table 147:
DO name
Op

Mod

Beh

LN type

LN prefix

LN class

Function block name

LCCRPTRC (revision 1)

LCCR

PTRC

LCCRPTRC

LCCRPTRC Logical node data


DO type

DA name

a_dACT

a_dINC

a_dINS

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

general

ST

TRIP

Mon

Common trip

phsA

ST

TRL1

Mon

Trip phase 1

phsB

ST

TRL2

Mon

Trip phase 2

phsC

ST

TRL3

Mon

Trip phase 3

ST

TRIP

Mon

Quality: Common trip

ST

TRIP

Mon

Timestamp: Common trip

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850
223

Section 7
Logical node data model
7.5.16.2

Table 148:
DO name
Op

Mod

Beh

LORs

1MRK 511 302-UEN -

Tripping logic common 3-phase output SMPPTRC


LN type

LN prefix

LN class

Function block name

SMPPTRC (revision 2)

SMP

PTRC

SMPPTRC

SMPPTRC Logical node data


DO type

DA name

aACT

aINC

aINS

v1SPC

FC

Signal

Mon/
Cmd

Description

general

ST

TRIP

Mon

General trip output signal

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: General trip output signal

ST

TRIP

Mon

Timestamp: General trip output


signal

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Table continues on next page


224

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

LORs

v1SPC

Oper.Check

CO

Cmd

Command parameter for


IEC61850

SPTr

v1SPS

stVal

ST

TR1P

Mon

Tripping single-pole

ST

TR1P

Mon

Quality: Tripping single-pole

ST

TR1P

Mon

Timestamp: Tripping single-pole

stVal

ST

TR2P

Mon

Tripping two-pole

ST

TR2P

Mon

Quality: Tripping two-pole

ST

TR2P

Mon

Timestamp: Tripping two-pole

stVal

ST

TR3P

Mon

Tripping three-pole

ST

TR3P

Mon

Quality: Tripping three-pole

ST

TR3P

Mon

Timestamp: Tripping three-pole

stVal

ST

CLLKOUT

Mon

Circuit breaker lockout output (set


until reset)

ST

CLLKOUT

Mon

Quality: Circuit breaker lockout


output (set until reset)

ST

CLLKOUT

Mon

Timestamp: Circuit breaker


lockout output (set until reset)

TwoPTr

TPTr

ClsLO

v1SPS

v1SPS

v1SPS

7.5.17

Thermal overload PTTR

7.5.17.1

Thermal overload protection, one time constant, Celsius LCPTTR

Table 149:
DO name
Mod

LN type

LN prefix

LN class

Function block name

LCPTTR (revision 0)

LC

PTTR

LCPTTR

LCPTTR Logical node data


DO type

DA name

a_dINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

225

Section 7
Logical node data model
DO name
Beh

AlmThm

Str

Op

Tmp

TmpRl

TmmOp

TmmRsLO

BlkRecSt

SenFlt

DO type
a_dINS

a_dSPS

b_dACD

b_dACT

b_dMV

b_dMV

v1_dINS

v1_dINS

v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

ALARM

Mon

Alarm signal

ST

ALARM

Mon

Quality: Alarm signal

ST

ALARM

Mon

Timestamp: Alarm signal

general

ST

START

Mon

Start Signal

ST

START

Mon

Quality: Start Signal

ST

START

Mon

Timestamp: Start Signal

general

ST

TRIP

Mon

Trip

ST

TRIP

Mon

Quality: Trip

ST

TRIP

Mon

Timestamp: Trip

mag.f

MX

TEMP

Mon

Calculated temperature of the


device

MX

TEMP

Mon

Quality: Calculated temperature


of the device

MX

TEMP

Mon

Timestamp: Calculated
temperature of the device

mag.f

MX

TERMLOAD

Mon

Temperature relative to operate


temperature

MX

TERMLOAD

Mon

Quality: Temperature relative to


operate temperature

MX

TERMLOAD

Mon

Timestamp: Temperature relative


to operate temperature

stVal

ST

TTRIP

Mon

Estimated time to trip (in min)

ST

TTRIP

Mon

Quality: Estimated time to trip (in


min)

ST

TTRIP

Mon

Timestamp: Estimated time to trip


(in min)

stVal

ST

TENRECL

Mon

Estimated time to reset of lockout


(in min)

ST

TENRECL

Mon

Quality: Estimated time to reset of


lockout (in min)

ST

TENRECL

Mon

Timestamp: Estimated time to


reset of lockout (in min)

stVal

ST

LOCKOUT

Mon

Lockout signal

ST

LOCKOUT

Mon

Quality: Lockout signal

ST

LOCKOUT

Mon

Timestamp: Lockout signal

stVal

ST

Mon

Error signal from the temperature


sensor

ST

Mon

Quality: Error signal from the


temperature sensor

Table continues on next page

226

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

SenFlt

v1_dSPS

ST

Mon

Timestamp: Error signal from the


temperature sensor

TmpAmb

v2_dMV

mag.f

MX

TEMPAMB

Mon

Ambient temperature used in the


calculations

MX

TEMPAMB

Mon

Quality: Ambient temperature


used in the calculations

MX

TEMPAMB

Mon

Timestamp: Ambient temperature


used in the calculations

7.5.17.2

Table 150:
DO name
Mod

Beh

AlmThm

Str

Op

Thermal overload protection, one time constant, Fahrenheit LFPTTR


LN type

LN prefix

LN class

Function block name

LFPTTR (revision 0)

LF

PTTR

LFPTTR

LFPTTR Logical node data


DO type

DA name

a_dINC

a_dINS

a_dSPS

b_dACD

b_dACT

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

ALARM

Mon

Alarm signal

ST

ALARM

Mon

Quality: Alarm signal

ST

ALARM

Mon

Timestamp: Alarm signal

general

ST

START

Mon

Start Signal

ST

START

Mon

Quality: Start Signal

ST

START

Mon

Timestamp: Start Signal

general

ST

TRIP

Mon

Trip

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

227

Section 7
Logical node data model
DO name

DO type

Op

b_dACT

Tmp

b_dMV

TmpRl

TmmOp

TmmRsLO

BlkRecSt

SenFlt

TmpAmb

7.5.17.3

228

b_dMV

v1_dINS

v1_dINS

v1_dSPS

v1_dSPS

v2_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

TRIP

Mon

Quality: Trip

ST

TRIP

Mon

Timestamp: Trip

mag.f

MX

TEMP

Mon

Calculated temperature of the


device

MX

TEMP

Mon

Quality: Calculated temperature


of the device

MX

TEMP

Mon

Timestamp: Calculated
temperature of the device

mag.f

MX

TERMLOAD

Mon

Temperature relative to operate


temperature

MX

TERMLOAD

Mon

Quality: Temperature relative to


operate temperature

MX

TERMLOAD

Mon

Timestamp: Temperature relative


to operate temperature

stVal

ST

TTRIP

Mon

Estimated time to trip (in min)

ST

TTRIP

Mon

Quality: Estimated time to trip (in


min)

ST

TTRIP

Mon

Timestamp: Estimated time to trip


(in min)

stVal

ST

TENRECL

Mon

Estimated time to reset of lockout


(in min)

ST

TENRECL

Mon

Quality: Estimated time to reset of


lockout (in min)

ST

TENRECL

Mon

Timestamp: Estimated time to


reset of lockout (in min)

stVal

ST

LOCKOUT

Mon

Lockout signal

ST

LOCKOUT

Mon

Quality: Lockout signal

ST

LOCKOUT

Mon

Timestamp: Lockout signal

stVal

ST

Mon

Error signal from the temperature


sensor

ST

Mon

Quality: Error signal from the


temperature sensor

ST

Mon

Timestamp: Error signal from the


temperature sensor

mag.f

MX

TEMPAMB

Mon

Ambient temperature used in the


calculations

MX

TEMPAMB

Mon

Quality: Ambient temperature


used in the calculations

MX

TEMPAMB

Mon

Timestamp: Ambient temperature


used in the calculations

Thermal overload protection, two time constants TRPTTR


LN type

LN prefix

LN class

Function block name

TRPTTR (revision 4)

TR

PTTR

TRPTTR

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 151:
DO name
Mod

Beh

AlmThm2

AlmThm

Str

Op

LO

Wrn

TmmOp

TRPTTR Logical node data


DO type

DA name

a_dINC

a_dINS

a_dSPS

a_dSPS

b_dACD

b_dACT

v1_dSPS

v1_dSPS

v2_dMV

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

ALARM2

Mon

Second level alarm signal

ST

ALARM2

Mon

Quality: Second level alarm signal

ST

ALARM2

Mon

Timestamp: Second level alarm


signal

stVal

ST

ALARM1

Mon

First level alarm signal

ST

ALARM1

Mon

Quality: First level alarm signal

ST

ALARM1

Mon

Timestamp: First level alarm


signal

general

ST

START

Mon

Start signal

ST

START

Mon

Quality: Start signal

ST

START

Mon

Timestamp: Start signal

general

ST

TRIP

Mon

Trip Signal

ST

TRIP

Mon

Quality: Trip Signal

ST

TRIP

Mon

Timestamp: Trip Signal

stVal

ST

LOCKOUT

Mon

Lockout signal

ST

LOCKOUT

Mon

Quality: Lockout signal

ST

LOCKOUT

Mon

Timestamp: Lockout signal

stVal

ST

WARNING

Mon

Warning signal: Trip within set


warning time

ST

WARNING

Mon

Quality: Warning signal: Trip


within set warning time

ST

WARNING

Mon

Timestamp: Warning signal: Trip


within set warning time

mag.f

MX

TTRIP

Mon

Estimated time to trip (in min)

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

229

Section 7
Logical node data model
DO name
TmmOp

TmmRsLO

AClcPct

TmpPct

DO type
v2_dMV

v2_dMV

v2_dMV

v2_dMV

DA name

DO name
Mod

FC

Signal

Mon/
Cmd

Description

MX

TTRIP

Mon

Quality: Estimated time to trip (in


min)

MX

TTRIP

Mon

Timestamp: Estimated time to trip


(in min)

mag.f

MX

TRESLO

Mon

Estimated time to reset of the


function (in min)

MX

TRESLO

Mon

Quality: Estimated time to reset of


the function (in min)

MX

TRESLO

Mon

Timestamp: Estimated time to


reset of the function (in min)

mag.f

MX

I-MEASUR

Mon

Current measured by the function


in % of the rated current

MX

I-MEASUR

Mon

Quality: Current measured by the


function in % of the rated current

MX

I-MEASUR

Mon

Timestamp: Current measured by


the function in % of the rated
current

mag.f

MX

HEATCONT

Mon

Percentage of the heat content of


the transformer

MX

HEATCONT

Mon

Quality: Percentage of the heat


content of the transformer

MX

HEATCONT

Mon

Timestamp: Percentage of the


heat content of the transformer

7.5.17.4

Table 152:

1MRK 511 302-UEN -

Rotor overload protection GRPTTR


LN type

LN prefix

LN class

Function block name

GRPTTR (revision 1)

GR

PTTR

GRPTTR

GRPTTR Logical node data


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

Table continues on next page

230

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Mod

a_dINC

ST

Mon

Timestamp: Mode status value


parameter for 61850

Beh

a_dINS

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal from the


function

ST

START

Mon

Quality: General start signal from


the function

ST

START

Mon

Timestamp: General start signal


from the function

general

ST

TRIP

Mon

General trip signal from the


function

ST

TRIP

Mon

Quality: General trip signal from


the function

ST

TRIP

Mon

Timestamp: General trip signal


from the function

stVal

ST

BLKRECL

Mon

Block machine closing command

ST

BLKRECL

Mon

Quality: Block machine closing


command

ST

BLKRECL

Mon

Timestamp: Block machine


closing command

stVal

ST

LOCKOUT

Mon

Trip lockout output (latched)

ST

LOCKOUT

Mon

Quality: Trip lockout output


(latched)

ST

LOCKOUT

Mon

Timestamp: Trip lockout output


(latched)

stVal

ST

ALRIPPLE

Mon

Ripple alarm, is set (with delay-on


20ms) if instRippleAlarm is active
longer than tAlarmRipple

ST

ALRIPPLE

Mon

Quality: Ripple alarm, is set (with


delay-on 20ms) if instRippleAlarm
is active longer than tAlarmRipple

ST

ALRIPPLE

Mon

Timestamp: Ripple alarm, is set


(with delay-on 20ms) if
instRippleAlarm is active longer
than tAlarmRipple

general

ST

STARTUC

Mon

Start signal from under-current


feature

ST

STARTUC

Mon

Quality: Start signal from undercurrent feature

ST

STARTUC

Mon

Timestamp: Start signal from


under-current feature

general

ST

TRIPUC

Mon

Trip signal from under-current


feature

ST

TRIPUC

Mon

Quality: Trip signal from undercurrent feature

Str

Op

BlkGnStr

LO

AlmRpl

StrAUn

OpAUn

b_dACD

b_dACT

v1_dSPS

v1_dSPS

v1_dSPS

v2_dACD

v2_dACT

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

231

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

OpAUn

v2_dACT

ST

TRIPUC

Mon

Timestamp: Trip signal from


under-current feature

TmpPct

v2_dMV

mag.f

MX

THETA

Mon

Overload in percent of set trip


level (i.e. Trip=100%)

MX

THETA

Mon

Quality: Overload in percent of


set trip level (i.e. Trip=100%)

MX

THETA

Mon

Timestamp: Overload in percent


of set trip level (i.e. Trip=100%)

7.5.17.5

Table 153:
DO name
Mod

Beh

Str

Op

Stator overload protection GSPTTR


LN type

LN prefix

LN class

Function block name

GSPTTR (revision 1)

GS

PTTR

GSPTTR

GSPTTR Logical node data


DO type
a_dINC

a_dINS

b_dACD

b_dACT

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal from the


function

ST

START

Mon

Quality: General start signal from


the function

ST

START

Mon

Timestamp: General start signal


from the function

general

ST

TRIP

Mon

General trip signal from the


function

Table continues on next page

232

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Op

BlkGnStr

LO

TmpPct

DO type

DA name

b_dACT

v1_dSPS

v1_dSPS

v2_dMV

FC

Signal

Mon/
Cmd

ST

TRIP

Mon

Quality: General trip signal from


the function

ST

TRIP

Mon

Timestamp: General trip signal


from the function

stVal

ST

BLKRECL

Mon

Block machine closing command

ST

BLKRECL

Mon

Quality: Block machine closing


command

ST

BLKRECL

Mon

Timestamp: Block machine


closing command

stVal

ST

LOCKOUT

Mon

Trip lockout output (latched)

ST

LOCKOUT

Mon

Quality: Trip lockout output


(latched)

ST

LOCKOUT

Mon

Timestamp: Trip lockout output


(latched)

mag.f

MX

THETA

Mon

Overload in percent of set trip


level (i.e. Trip=100%)

MX

THETA

Mon

Quality: Overload in percent of


set trip level (i.e. Trip=100%)

MX

THETA

Mon

Timestamp: Overload in percent


of set trip level (i.e. Trip=100%)

7.5.18

Three phase undercurrent PTUC

7.5.18.1

Three phase undercurrent LCP3PTUC

Table 154:
DO name
Str

Op

Description

LN type

LN prefix

LN class

Function block name

LCP3PTUC (revision 0)

LCP3

PTUC

LCP3PTUC

LCP3PTUC Logical node data


DO type

DA name

a_dACD

a_dACT

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common start signal

phsA

ST

STL1

Mon

Start signal from phase L1

phsB

ST

STL2

Mon

Start signal from phase L2

phsC

ST

STL3

Mon

Start signal from phase L3

ST

START

Mon

Quality: Common start signal

ST

START

Mon

Timestamp: Common start signal

general

ST

TRIP

Mon

Common trip signal

phsA

ST

TRL1

Mon

Trip signal from phase L1

phsB

ST

TRL2

Mon

Trip signal from phase L2

phsC

ST

TRL3

Mon

Trip signal from phase L3

ST

TRIP

Mon

Quality: Common trip signal

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

233

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Op

a_dACT

ST

TRIP

Mon

Timestamp: Common trip signal

Mod

a_dINC

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Beh

a_dINS

7.5.19

Undervoltage PTUV

7.5.19.1

Two step undervoltage protection UV2PTUV

Table 155:
DO name
Mod

LN type

LN prefix

LN class

Function block name

GEN2LLN0 instance 1 (revision 1)

LLN0

UV2PTUV

PH1PTRC instance 1 (revision 3)

PH1

PTRC

UV2PTUV

UV2PTUV instance 1 (revision 2)

UV2

PTUV

UV2PTUV

UV2PTUV instance 2 (revision 2)

UV2

PTUV

UV2PTUV

UV2PTUV Logical node data (instance 1)


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Table continues on next page

234

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

Table 156:
DO name
Beh

Str

Op

Mod

Table 157:
DO name
Str

Op

DO type

DA name

a_dINC

a_dINS

FC

Signal

Mon/
Cmd

Description

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

Trip

ST

TRIP

Mon

Quality: Trip

ST

TRIP

Mon

Timestamp: Trip

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

UV2PTUV Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

Description

UV2PTUV Logical node data (instance 1)


DO type

DA name

a_dACD

a_dACT

FC

Signal

Mon/
Cmd

Description

general

ST

ST1

Mon

Common start signal from step1

phsA

ST

ST1L1

Mon

Start signal from step1 phase L1

phsB

ST

ST1L2

Mon

Start signal from step1 phase L2

phsC

ST

ST1L3

Mon

Start signal from step1 phase L3

ST

ST1

Mon

Quality: Common start signal


from step1

ST

ST1

Mon

Timestamp: Common start signal


from step1

general

ST

TR1

Mon

Common trip signal from step1

phsA

ST

TR1L1

Mon

Trip signal from step1 phase L1

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

235

Section 7
Logical node data model
DO name
Op

Beh

Mod

Table 158:
DO name
Str

Op

Beh

Mod

236

DO type
a_dACT

a_dINS

c_dINC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

phsB

ST

TR1L2

Mon

Trip signal from step1 phase L2

phsC

ST

TR1L3

Mon

Trip signal from step1 phase L3

ST

TR1

Mon

Quality: Common trip signal from


step1

ST

TR1

Mon

Timestamp: Common trip signal


from step1

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

UV2PTUV Logical node data (instance 2)


DO type
a_dACD

a_dACT

a_dINS

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

general

ST

ST2

Mon

Common start signal from step2

phsA

ST

ST2L1

Mon

Start signal from step2 phase L1

phsB

ST

ST2L2

Mon

Start signal from step2 phase L2

phsC

ST

ST2L3

Mon

Start signal from step2 phase L3

ST

ST2

Mon

Quality: Common start signal


from step2

ST

ST2

Mon

Timestamp: Common start signal


from step2

general

ST

TR2

Mon

Common trip signal from step2

phsA

ST

TR2L1

Mon

Trip signal from step2 phase L1

phsB

ST

TR2L2

Mon

Trip signal from step2 phase L2

phsC

ST

TR2L3

Mon

Trip signal from step2 phase L3

ST

TR2

Mon

Quality: Common trip signal from


step2

ST

TR2

Mon

Timestamp: Common trip signal


from step2

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.5.19.2

Table 159:
DO name
Mod

Beh

Str

Op

Loss of voltage check LOVPTUV


LN type

LN prefix

LN class

Function block name

LOVPTUV (revision 2)

LOV

PTUV

LOVPTUV

LOVPTUV Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACD

b_dACT

FC

Signal

Mon/
Cmd

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

Start signal

ST

START

Mon

Quality: Start signal

ST

START

Mon

Timestamp: Start signal

general

ST

TRIP

Mon

Trip signal

ST

TRIP

Mon

Quality: Trip signal

ST

TRIP

Mon

Timestamp: Trip signal

7.5.20

Underfrequency PTUF

7.5.20.1

Underfrequency protection SAPTUF

670 series 2.0 IEC


Communication Protocol Manual

Description

LN type

LN prefix

LN class

Function block name

SAPTUF (revision 1)

SA

PTUF

SAPTUF

237

Section 7
Logical node data model

Table 160:
DO name
Mod

Beh

Str

Op

BlkLoMg

RstLd

238

1MRK 511 302-UEN -

SAPTUF Logical node data


DO type
a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

v1_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

General trip signal

ST

TRIP

Mon

Quality: General trip signal

ST

TRIP

Mon

Timestamp: General trip signal

stVal

ST

BLKDMAGN

Mon

Measurement blocked due to low


voltage amplitude

ST

BLKDMAGN

Mon

Quality: Measurement blocked


due to low voltage amplitude

ST

BLKDMAGN

Mon

Timestamp: Measurement
blocked due to low voltage
amplitude

stVal

ST

RESTORE

Mon

Restore signal for load restoring


purposes

ST

RESTORE

Mon

Quality: Restore signal for load


restoring purposes

ST

RESTORE

Mon

Timestamp: Restore signal for


load restoring purposes

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.5.21

Volts per Hz PVPH

7.5.21.1

Overexcitation protection OEXPVPH

Table 161:
DO name
Mod

Beh

Str

Op

ExtAlm

GenFctFlt

LN type

LN prefix

LN class

Function block name

OEXPVPH (revision 3)

OEX

PVPH

OEXPVPH

OEXPVPH Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

START

Mon

Overexcitation above set operate


level (instantaneous)

ST

START

Mon

Quality: Overexcitation above set


operate level (instantaneous)

ST

START

Mon

Timestamp: Overexcitation above


set operate level (instantaneous)

general

ST

TRIP

Mon

Trip from overexcitation function

ST

TRIP

Mon

Quality: Trip from overexcitation


function

ST

TRIP

Mon

Timestamp: Trip from


overexcitation function

stVal

ST

ALARM

Mon

Overexcitation above set alarm


level (delayed)

ST

ALARM

Mon

Quality: Overexcitation above set


alarm level (delayed)

ST

ALARM

Mon

Timestamp: Overexcitation above


set alarm level (delayed)

stVal

ST

Mon

Out of measuring range for


voltage or frequency

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

239

Section 7
Logical node data model
DO name
GenFctFlt

VHzRat

DO type
v1_dSPS

v2_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

Mon

Quality: Out of measuring range


for voltage or frequency

ST

Mon

Timestamp: Out of measuring


range for voltage or frequency

mag.f

MX

VPERHZ

Mon

Voltage to frequency ratio in perunit

MX

VPERHZ

Mon

Quality: Voltage to frequency


ratio in per-unit

MX

VPERHZ

Mon

Timestamp: Voltage to frequency


ratio in per-unit

7.5.22

Multipurpose analog protection GAPC

7.5.22.1

Accidental energizing protection for synchronous generator


AEGPVOC

Table 162:
DO name
Mod

Beh

Str

LN type

LN prefix

LN class

Function block name

AEGGAPC (revision 2)

AEG

GAPC

AEGPVOC

AEGPVOC Logical node data


DO type
a_dINC

a_dINS

b_dACD

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

Start signal from accidental


energizing of generator protection

Table continues on next page

240

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Str

Op

Armed

DO type

DA name

b_dACD

b_dACT

v1_dSPS

FC

ST

START

Mon

Quality: Start signal from


accidental energizing of
generator protection

ST

START

Mon

Timestamp: Start signal from


accidental energizing of
generator protection

general

ST

TRIP

Mon

Trip signal from accidental


energizing of generator protection

ST

TRIP

Mon

Quality: Trip signal from


accidental energizing of
generator protection

ST

TRIP

Mon

Timestamp: Trip signal from


accidental energizing of
generator protection

stVal

ST

ARMED

Mon

True when accidental energizing


of generator protection is armed

ST

ARMED

Mon

Quality: True when accidental


energizing of generator protection
is armed

ST

ARMED

Mon

Timestamp: True when accidental


energizing of generator protection
is armed

7.5.22.2

Table 163:
DO name
Mod

Signal

Mon/
Cmd

Description

Status of primary switching object for Busbar Protection Zone


Selection BDCGAPC
LN type

LN prefix

LN class

Function block name

SWSGGIO (revision 0)

SWS

GGIO

BDCGAPC

BDCGAPC Logical node data


DO type

DA name

aINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

241

Section 7
Logical node data model
DO name
Beh

Alm

Fcd

DO type
aINS

bSPS

v1SPS

7.5.22.3

Table 164:
DO name
Mod

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

ALARM

Mon

Delayed alarm for abnormal aux.


contact status, 00 or 11

ST

ALARM

Mon

Quality: Delayed alarm for


abnormal aux. contact status, 00
or 11

ST

ALARM

Mon

Timestamp: Delayed alarm for


abnormal aux. contact status, 00
or 11

stVal

ST

FORCED

Mon

Primary object status forced to


open or closed by setting

ST

FORCED

Mon

Quality: Primary object status


forced to open or closed by setting

ST

FORCED

Mon

Timestamp: Primary object status


forced to open or closed by setting

Capacitor bank protection CBPGAPC


LN type

LN prefix

LN class

Function block name

CBPLLN0 instance 1 (revision 1)

LLN0

CBPGAPC

CBPMMXU instance 1 (revision 1)

CBP

MMXU

CBPGAPC

CBPPTRC instance 1 (revision 0)

CBP

PTRC

CBPGAPC

HOLPTOV instance 1 (revision 1)

HOL

PTOV

CBPGAPC

HPH1PTOV instance 1 (revision 1)

HPH1

PTOV

CBPGAPC

HPH1PTOV instance 2 (revision 1)

HPH1

PTOV

CBPGAPC

PH3PTOC instance 1 (revision 3)

PH3

PTOC

CBPGAPC

PH3PTUC instance 1 (revision 0)

PH3

PTUC

CBPGAPC

RP3PDOP instance 1 (revision 1)

RP3

PDOP

CBPGAPC

CBPGAPC Logical node data (instance 1)


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Table continues on next page

242

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

Table 165:
DO name
Beh

Mod

APeakPhA

APeakPhB

APeakPhC

DO type

DA name

a_dINC

a_dINS

FC

Signal

Mon/
Cmd

Description

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

mag.f

MX

IPEAKL1

Mon

Equivalant RMS current for phase


L1

MX

IPEAKL1

Mon

Quality: Equivalant RMS current


for phase L1

MX

IPEAKL1

Mon

Timestamp: Equivalant RMS


current for phase L1

mag.f

MX

IPEAKL2

Mon

Equivalant RMS current for phase


L2

MX

IPEAKL2

Mon

Quality: Equivalant RMS current


for phase L2

MX

IPEAKL2

Mon

Timestamp: Equivalant RMS


current for phase L2

mag.f

MX

IPEAKL3

Mon

Equivalant RMS current for phase


L3

MX

IPEAKL3

Mon

Quality: Equivalant RMS current


for phase L3

MX

IPEAKL3

Mon

Timestamp: Equivalant RMS


current for phase L3

CBPGAPC Logical node data (instance 1)


DO type

DA name

a_dINS

c_dINC

v2_dMV

v2_dMV

v2_dMV

Description

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

243

Section 7
Logical node data model
DO name
VRMSPhA

VRMSPhB

VRMSPhC

VArPhA

VArPhB

VArPhC

Table 166:
DO name
Beh

Str

DO type
v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

mag.f

MX

URMSL1

Mon

Calculated voltage RMS for


phase L1

MX

URMSL1

Mon

Quality: Calculated voltage RMS


for phase L1

MX

URMSL1

Mon

Timestamp: Calculated voltage


RMS for phase L1

mag.f

MX

URMSL2

Mon

Calculated voltage RMS for


phase L2

MX

URMSL2

Mon

Quality: Calculated voltage RMS


for phase L2

MX

URMSL2

Mon

Timestamp: Calculated voltage


RMS for phase L2

mag.f

MX

URMSL3

Mon

Calculated voltage RMS for


phase L3

MX

URMSL3

Mon

Quality: Calculated voltage RMS


for phase L3

MX

URMSL3

Mon

Timestamp: Calculated voltage


RMS for phase L3

mag.f

MX

QL1

Mon

Reactive power value for phase L1

MX

QL1

Mon

Quality: Reactive power value for


phase L1

MX

QL1

Mon

Timestamp: Reactive power


value for phase L1

mag.f

MX

QL2

Mon

Reactive power value for phase L2

MX

QL2

Mon

Quality: Reactive power value for


phase L2

MX

QL2

Mon

Timestamp: Reactive power


value for phase L2

mag.f

MX

QL3

Mon

Reactive power value for phase L3

MX

QL3

Mon

Quality: Reactive power value for


phase L3

MX

QL3

Mon

Timestamp: Reactive power


value for phase L3

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

CBPGAPC Logical node data (instance 1)


DO type
a_dINS

b_dACD

DA name

Description

Table continues on next page

244

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Op

Mod

CapDisc

Inh

Table 167:
DO name
Str

Beh

Op

DO type

DA name

b_dACT

c_dINC

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

general

ST

TRIP

Mon

General trip signal

ST

TRIP

Mon

Quality: General trip signal

ST

TRIP

Mon

Timestamp: General trip signal

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

CAPDISC

Mon

Capcitor bank disconnected

ST

CAPDISC

Mon

Quality: Capcitor bank


disconnected

ST

CAPDISC

Mon

Timestamp: Capcitor bank


disconnected

stVal

ST

RECNINH

Mon

Capacitor bank reconnection


inhibit signal

ST

RECNINH

Mon

Quality: Capacitor bank


reconnection inhibit signal

ST

RECNINH

Mon

Timestamp: Capacitor bank


reconnection inhibit signal

CBPGAPC Logical node data (instance 1)


DO type

DA name

a_dACD

a_dINS

b_dACT

FC

Signal

Mon/
Cmd

Description

general

ST

STHOL

Mon

Start signal for harmonic over load

phsA

ST

STHIDML1

Mon

Start signal for harmonic over


load IDMT stage of phase L1

phsB

ST

STHIDML2

Mon

Start signal for harmonic over


load IDMT stage of phase L2

phsC

ST

STHIDML3

Mon

Start signal for harmonic over


load IDMT stage of phase L3

ST

STHOL

Mon

Quality: Start signal for harmonic


over load

ST

STHOL

Mon

Timestamp: Start signal for


harmonic over load

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRHOL

Mon

Trip signal for harmonic over load

ST

TRHOL

Mon

Quality: Trip signal for harmonic


over load

ST

TRHOL

Mon

Timestamp: Trip signal for


harmonic over load

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

245

Section 7
Logical node data model
DO name
Mod

Table 168:
DO name
Beh

Mod

Table 169:
DO name
Str

Beh

Op

DO type
c_dINC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

CBPGAPC Logical node data (instance 1)


DO type
a_dINS

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

CBPGAPC Logical node data (instance 2)


DO type
a_dACD

a_dINS

b_dACT

DA name

FC

Signal

Mon/
Cmd

Description

general

ST

STHOL

Mon

Start signal for harmonic over load

phsA

ST

STHDTL1

Mon

Start signal harmonic over load


Definite Time stage phase L1

phsB

ST

STHDTL2

Mon

Start signal harmonic over load


Definite Time stage phase L2

phsC

ST

STHDTL3

Mon

Start signal harmonic over load


Definite Time stage phase L3

ST

STHOL

Mon

Quality: Start signal for harmonic


over load

ST

STHOL

Mon

Timestamp: Start signal for


harmonic over load

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRHOL

Mon

Trip signal for harmonic over load

ST

TRHOL

Mon

Quality: Trip signal for harmonic


over load

Table continues on next page

246

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Op

b_dACT

ST

TRHOL

Mon

Timestamp: Trip signal for


harmonic over load

Mod

c_dINC

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Table 170:
DO name
Str

Op

Beh

Mod

CBPGAPC Logical node data (instance 1)


DO type

DA name

a_dACD

a_dACT

a_dINS

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

general

ST

STOC

Mon

Start signals for over current

phsA

ST

STOCL1

Mon

Start signal for over current of


phase L1

phsB

ST

STOCL2

Mon

Start signal for over current of


phase L2

phsC

ST

STOCL3

Mon

Start signal for over current of


phase L3

ST

STOC

Mon

Quality: Start signals for over


current

ST

STOC

Mon

Timestamp: Start signals for over


current

general

ST

TROC

Mon

Trip signal for over current

phsA

ST

Mon

Trip signal for over current of


phase L1

phsB

ST

Mon

Trip signal for over current of


phase L2

phsC

ST

Mon

Trip signal for over current of


phase L3

ST

TROC

Mon

Quality: Trip signal for over current

ST

TROC

Mon

Timestamp: Trip signal for over


current

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

247

Section 7
Logical node data model

Table 171:
DO name
Str

Op

Beh

Mod

Table 172:
DO name
Str

1MRK 511 302-UEN -

CBPGAPC Logical node data (instance 1)


DO type
a_dACD

a_dACT

a_dINS

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

general

ST

STUC

Mon

Start signal for under current

phsA

ST

STUCL1

Mon

Start signal for under current of


phase L1

phsB

ST

STUCL2

Mon

Start signal for under current of


phase L2

phsC

ST

STUCL3

Mon

Start signal for under current of


phase L3

ST

STUC

Mon

Quality: Start signal for under


current

ST

STUC

Mon

Timestamp: Start signal for under


current

general

ST

TRUC

Mon

Trip signal for under current

phsA

ST

Mon

Trip signal for under current of


phase L1

phsB

ST

Mon

Trip signal for under current of


phase L2

phsC

ST

Mon

Trip signal for under current of


phase L3

ST

TRUC

Mon

Quality: Trip signal for under


current

ST

TRUC

Mon

Timestamp: Trip signal for under


current

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

CBPGAPC Logical node data (instance 1)


DO type
a_dACD

DA name

FC

Signal

Mon/
Cmd

Description

general

ST

STQOL

Mon

Start signal for reactive power


over load

phsA

ST

STQOLL1

Mon

Start signal for reactive power


over load of phase L1

phsB

ST

STQOLL2

Mon

Start signal for reactive power


over load of phase L2

phsC

ST

STQOLL3

Mon

Start signal for reactive power


over load of phase L3

Table continues on next page


248

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Str

Op

Beh

Mod

DO type

DA name

a_dACD

a_dACT

a_dINS

c_dINC

FC

ST

STQOL

Mon

Quality: Start signal for reactive


power over load

ST

STQOL

Mon

Timestamp: Start signal for


reactive power over load

general

ST

TRQOL

Mon

Trip signal for reactive power


over load

ST

TRQOL

Mon

Quality: Trip signal for reactive


power over load

ST

TRQOL

Mon

Timestamp: Trip signal for


reactive power over load

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

7.5.22.4

Table 173:
DO name
Mod

Signal

Mon/
Cmd

Description

Compensated over- and undervoltage protection COUVGAPC


LN type

LN prefix

LN class

Function block name

COUVLLN0 instance 1 (revision 0)

LLN0

COUVGAPC

COUVPTOV instance 1 (revision 0)

COUV

PTOV

COUVGAPC

COUVPTUV instance 1 (revision 0)

COUV

PTUV

COUVGAPC

COUVGAPC Logical node data (instance 1)


DO type

DA name

a_dINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

249

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Mod

a_dINC

ST

Mon

Timestamp: Mode status value


parameter for 61850

Beh

a_dINS

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

FC

Signal

Mon/
Cmd

general

ST

STOV

Mon

Common start signal for


compensated over voltage

phsA

ST

STOVL1

Mon

Start signal for compensated over


voltage of phase 1

phsB

ST

STOVL2

Mon

Start signal for compensated over


voltage of phase 2

phsC

ST

STOVL3

Mon

Start signal for compensated over


voltage of phase 3

ST

STOV

Mon

Quality: Common start signal for


compensated over voltage

ST

STOV

Mon

Timestamp: Common start signal


for compensated over voltage

general

ST

TROV

Mon

Common trip signal for


compensated over voltage

phsA

ST

TROVL1

Mon

Trip signal for compensated over


voltage of phase 1

phsB

ST

TROVL2

Mon

Trip signal for compensated over


voltage of phase 2

phsC

ST

TROVL3

Mon

Trip signal for compensated over


voltage of phase 3

ST

TROV

Mon

Quality: Common trip signal for


compensated over voltage

ST

TROV

Mon

Timestamp: Common trip signal


for compensated over voltage

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Table 174:
DO name
Str

Op

Beh

Mod

250

COUVGAPC Logical node data (instance 1)


DO type
a_dACD

a_dACT

a_dINS

c_dINC

DA name

Description

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 175:
DO name
Str

Op

Beh

Mod

COUVGAPC Logical node data (instance 1)


DO type

DA name

a_dACD

a_dACT

a_dINS

c_dINC

7.5.22.5

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

general

ST

STUV

Mon

Common start signal for


compensated under voltage

phsA

ST

STUVL1

Mon

Start signal for compensated


under voltage of phase 1

phsB

ST

STUVL2

Mon

Start signal for compensated


under voltage of phase 2

phsC

ST

STUVL3

Mon

Start signal for compensated


under voltage of phase 3

ST

STUV

Mon

Quality: Common start signal for


compensated under voltage

ST

STUV

Mon

Timestamp: Common start signal


for compensated under voltage

general

ST

TRUV

Mon

Common trip signal for


compensated under voltage

phsA

ST

TRUVL1

Mon

Trip signal for compensated


under voltage of phase 1

phsB

ST

TRUVL2

Mon

Trip signal for compensated


under voltage of phase 2

phsC

ST

TRUVL3

Mon

Trip signal for compensated


under voltage of phase 3

ST

TRUV

Mon

Quality: Common trip signal for


compensated under voltage

ST

TRUV

Mon

Timestamp: Common trip signal


for compensated under voltage

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

General currrent and voltage protection CVGAPC


LN type

LN prefix

LN class

Function block name

GF2LLN0 instance 1 (revision 0)

LLN0

CVGAPC

GF2MMXN instance 1 (revision 3)

GF2

MMXN

CVGAPC

GF2PHAR instance 1 (revision 2)

GF2

PHAR

CVGAPC

GF2PTOV instance 1 (revision 2)

GF2

PTOV

CVGAPC

GF2PTOV instance 2 (revision 2)

GF2

PTOV

CVGAPC

GF2PTUC instance 1 (revision 2)

GF2

PTUC

CVGAPC
251

Section 7
Logical node data model

Table 176:
DO name
Mod

Beh

IvdCrv

UnVBehMem

252

1MRK 511 302-UEN -

GF2PTUC instance 2 (revision 2)

GF2

PTUC

CVGAPC

GF2PTUV instance 1 (revision 2)

GF2

PTUV

CVGAPC

GF2PTUV instance 2 (revision 2)

GF2

PTUV

CVGAPC

GF2PVOC instance 1 (revision 2)

GF2

PVOC

CVGAPC

GF2PVOC instance 2 (revision 2)

GF2

PVOC

CVGAPC

PH1PTRC instance 1 (revision 3)

PH1

PTRC

CVGAPC

CVGAPC Logical node data (instance 1)


DO type
aINC

aINS

v1SPS

v1SPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Error signal from overcurrent


functions

ST

Mon

Quality: Error signal from


overcurrent functions

ST

Mon

Timestamp: Error signal from


overcurrent functions

stVal

ST

UDIRLOW

Mon

Low voltage for directional


polarization

ST

UDIRLOW

Mon

Quality: Low voltage for


directional polarization

ST

UDIRLOW

Mon

Timestamp: Low voltage for


directional polarization

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 177:
DO name
Beh

Amp

Vol

Mod

AmpPwrFact

VolAmpAng

Table 178:
DO name
Beh

Str

CVGAPC Logical node data (instance 1)


DO type

DA name

aINS

bMV

bMV

cINC

v2MV

v2MV

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

mag.f

MX

CURRENT

Mon

Measured current value

MX

CURRENT

Mon

Quality: Measured current value

MX

CURRENT

Mon

Timestamp: Measured current


value

mag.f

MX

VOLTAGE

Mon

Measured voltage value

MX

VOLTAGE

Mon

Quality: Measured voltage value

MX

VOLTAGE

Mon

Timestamp: Measured voltage


value

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

mag.f

MX

ICOSFI

Mon

Measured current multiplied with


cos (Phi)

MX

ICOSFI

Mon

Quality: Measured current


multiplied with cos (Phi)

MX

ICOSFI

Mon

Timestamp: Measured current


multiplied with cos (Phi)

mag.f

MX

UIANGLE

Mon

Angle between voltage and


current

MX

UIANGLE

Mon

Quality: Angle between voltage


and current

MX

UIANGLE

Mon

Timestamp: Angle between


voltage and current

CVGAPC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

BLK2ND

Mon

Block from second harmonic


detection

ST

BLK2ND

Mon

Quality: Block from second


harmonic detection

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

253

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Str

b_dACD

ST

BLK2ND

Mon

Timestamp: Block from second


harmonic detection

Mod

c_dINC

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

Table 179:
DO name
Beh

Str

Op

Mod

Table 180:
DO name
Beh

Str

CVGAPC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STOV1

Mon

Start signal from overvoltage


function OV1

ST

STOV1

Mon

Quality: Start signal from


overvoltage function OV1

ST

STOV1

Mon

Timestamp: Start signal from


overvoltage function OV1

general

ST

TROV1

Mon

Trip signal from overvoltage


function OV1

ST

TROV1

Mon

Quality: Trip signal from


overvoltage function OV1

ST

TROV1

Mon

Timestamp: Trip signal from


overvoltage function OV1

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

CVGAPC Logical node data (instance 2)


DO type
a_dINS

b_dACD

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STOV2

Mon

Start signal from overvoltage


function OV2

Table continues on next page

254

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Str

Op

Mod

Table 181:
DO name
Beh

Str

Op

Mod

DO type

DA name

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

ST

STOV2

Mon

Quality: Start signal from


overvoltage function OV2

ST

STOV2

Mon

Timestamp: Start signal from


overvoltage function OV2

general

ST

TROV2

Mon

Trip signal from overvoltage


function OV2

ST

TROV2

Mon

Quality: Trip signal from


overvoltage function OV2

ST

TROV2

Mon

Timestamp: Trip signal from


overvoltage function OV2

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

CVGAPC Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STUC2

Mon

Start signal from undercurrent


function UC2

ST

STUC2

Mon

Quality: Start signal from


undercurrent function UC2

ST

STUC2

Mon

Timestamp: Start signal from


undercurrent function UC2

general

ST

TRUC2

Mon

Trip signal from undercurrent


function UC2

ST

TRUC2

Mon

Quality: Trip signal from


undercurrent function UC2

ST

TRUC2

Mon

Timestamp: Trip signal from


undercurrent function UC2

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

255

Section 7
Logical node data model

Table 182:
DO name
Beh

Str

Op

Mod

Table 183:
DO name
Beh

Str

Op

1MRK 511 302-UEN -

CVGAPC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STUC1

Mon

Start signal from undercurrent


function UC1

ST

STUC1

Mon

Quality: Start signal from


undercurrent function UC1

ST

STUC1

Mon

Timestamp: Start signal from


undercurrent function UC1

general

ST

TRUC1

Mon

Trip signal from undercurrent


function UC1

ST

TRUC1

Mon

Quality: Trip signal from


undercurrent function UC1

ST

TRUC1

Mon

Timestamp: Trip signal from


undercurrent function UC1

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

CVGAPC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STUV1

Mon

Start signal from undervoltage


function UV1

ST

STUV1

Mon

Quality: Start signal from


undervoltage function UV1

ST

STUV1

Mon

Timestamp: Start signal from


undervoltage function UV1

general

ST

TRUV1

Mon

Trip signal from undervoltage


function UV1

ST

TRUV1

Mon

Quality: Trip signal from


undervoltage function UV1

ST

TRUV1

Mon

Timestamp: Trip signal from


undervoltage function UV1

Table continues on next page

256

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Table 184:
DO name
Beh

Str

Op

Mod

Table 185:
DO name
Beh

Str

DO type

DA name

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

CVGAPC Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STUV2

Mon

Start signal from undervoltage


function UV2

ST

STUV2

Mon

Quality: Start signal from


undervoltage function UV2

ST

STUV2

Mon

Timestamp: Start signal from


undervoltage function UV2

general

ST

TRUV2

Mon

Trip signal from undervoltage


function UV2

ST

TRUV2

Mon

Quality: Trip signal from


undervoltage function UV2

ST

TRUV2

Mon

Timestamp: Trip signal from


undervoltage function UV2

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

CVGAPC Logical node data (instance 2)


DO type

DA name

a_dINS

b_dACD

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STOC2

Mon

Start signal from overcurrent


function OC2

dirGeneral

ST

DIROC2

Mon

Directional mode of OC2 (nondir,


forward,reverse)

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

257

Section 7
Logical node data model
DO name
Str

Op

Mod

IvdCrv

Table 186:
DO name
Beh

Str

Op

Mod

DO type
b_dACD

b_dACT

c_dINC

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

STOC2

Mon

Quality: Start signal from


overcurrent function OC2

ST

STOC2

Mon

Timestamp: Start signal from


overcurrent function OC2

general

ST

TROC2

Mon

Trip signal from overcurrent


function OC2

ST

TROC2

Mon

Quality: Trip signal from


overcurrent function OC2

ST

TROC2

Mon

Timestamp: Trip signal from


overcurrent function OC2

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Mon

Error signal from overcurrent


function OC2

ST

Mon

Quality: Error signal from


overcurrent function OC2

ST

Mon

Timestamp: Error signal from


overcurrent function OC2

CVGAPC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STOC1

Mon

Start signal from overcurrent


function OC1

dirGeneral

ST

DIROC1

Mon

Directional mode of OC1 (nondir,


forward,reverse)

ST

STOC1

Mon

Quality: Start signal from


overcurrent function OC1

ST

STOC1

Mon

Timestamp: Start signal from


overcurrent function OC1

general

ST

TROC1

Mon

Trip signal from overcurrent


function OC1

ST

TROC1

Mon

Quality: Trip signal from


overcurrent function OC1

ST

TROC1

Mon

Timestamp: Trip signal from


overcurrent function OC1

stVal

ST

Mon

Mode status parameter for 61850

Table continues on next page

258

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

IvdCrv

Table 187:
DO name
Beh

Str

Op

Mod

DO type

DA name

c_dINC

v1_dSPS

FC

Signal

Mon/
Cmd

Description

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Mon

Error signal from overcurrent


function OC1

ST

Mon

Quality: Error signal from


overcurrent function OC1

ST

Mon

Timestamp: Error signal from


overcurrent function OC1

CVGAPC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

7.5.22.6

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

General trip signal

ST

TRIP

Mon

Quality: General trip signal

ST

TRIP

Mon

Timestamp: General trip signal

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

Low active power and power factor protection LAPPGAPC


LN type

LN prefix

LN class

Function block name

LAPPLLN0 instance 1 (revision 0)

LLN0

LAPPGAPC

LAPPPDUP instance 1 (revision 0)

LAPP

PDUP

LAPPGAPC

LAPPPUPF instance 1 (revision 0)

LAPP

PUPF

LAPPGAPC

259

Section 7
Logical node data model

Table 188:
DO name
Mod

Beh

Table 189:
DO name
Str

Beh

Op

Mod

260

1MRK 511 302-UEN -

LAPPGAPC Logical node data (instance 1)


DO type
a_dINC

a_dINS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

FC

Signal

Mon/
Cmd

general

ST

STLAP

Mon

Start low active power

phsA

ST

STLAPL1

Mon

Start low active power phase 1

phsB

ST

STLAPL2

Mon

Start low active power phase 2

phsC

ST

STLAPL3

Mon

Start low active power phase 3

ST

STLAP

Mon

Quality: Start low active power

ST

STLAP

Mon

Timestamp: Start low active power

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRLAP

Mon

Trip low active power

ST

TRLAP

Mon

Quality: Trip low active power

ST

TRLAP

Mon

Timestamp: Trip low active power

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

LAPPGAPC Logical node data (instance 1)


DO type
a_dACD

a_dINS

b_dACT

c_dINC

DA name

Description

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 190:
DO name
Str

Op

Beh

Mod

LAPPGAPC Logical node data (instance 1)


DO type

DA name

a_dACD

a_dACT

a_dINS

c_dINC

7.5.22.7

Table 191:
DO name
Mod

FC

Signal

Mon/
Cmd

Description

general

ST

STLPF

Mon

Start low power factor

phsA

ST

STLPFL1

Mon

Start low power factor phase 1

phsB

ST

STLPFL2

Mon

Start low power factor phase 2

phsC

ST

STLPFL3

Mon

Start low power factor phase 3

ST

STLPF

Mon

Quality: Start low power factor

ST

STLPF

Mon

Timestamp: Start low power factor

general

ST

TRLPF

Mon

Trip low power factor

phsA

ST

TRLPFL1

Mon

Trip low power factor phase 1

phsB

ST

TRLPFL2

Mon

Trip low power factor phase 2

phsC

ST

TRLPFL3

Mon

Trip low power factor phase 3

ST

TRLPF

Mon

Quality: Trip low power factor

ST

TRLPF

Mon

Timestamp: Trip low power factor

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Mho Impedance supervision logic ZSMGAPC


LN type

LN prefix

LN class

Function block name

ZSMGAPC (revision 0)

ZSM

GAPC

ZSMGAPC

ZSMGAPC Logical node data


DO type

DA name

aINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

261

Section 7
Logical node data model
DO name
Mod

Beh

FLtIncp

BLkTDmnImp

CarTcBlk

StopCarTx

IndHiSIR

7.5.22.8

262

DO type
aINC

aINS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

Mon

Fault inception detected for any


phase voltage

ST

Mon

Quality: Fault inception detected


for any phase voltage

ST

Mon

Timestamp: Fault inception


detected for any phase voltage

stVal

ST

BLKZMTD

Mon

Block signal for blocking of time


domained mho

ST

BLKZMTD

Mon

Quality: Block signal for blocking


of time domained mho

ST

BLKZMTD

Mon

Timestamp: Block signal for


blocking of time domained mho

stVal

ST

BLKCHST

Mon

Blocking signal to remote end to


block overreaching zone

ST

BLKCHST

Mon

Quality: Blocking signal to remote


end to block overreaching zone

ST

BLKCHST

Mon

Timestamp: Blocking signal to


remote end to block overreaching
zone

stVal

ST

CHSTOP

Mon

Stops the blocking signal to


remote end

ST

CHSTOP

Mon

Quality: Stops the blocking signal


to remote end

ST

CHSTOP

Mon

Timestamp: Stops the blocking


signal to remote end

stVal

ST

HSIR

Mon

Indication of source impedance


ratio above set limit

ST

HSIR

Mon

Quality: Indication of source


impedance ratio above set limit

ST

HSIR

Mon

Timestamp: Indication of source


impedance ratio above set limit

Radial feeder protection PAPGAPC


LN type

LN prefix

LN class

Function block name

PAPGAPC (revision 1)

PAP

GAPC

PAPGAPC

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 192:
DO name
Mod

Beh

Str

Op

AutoRecStr

ARStrTP

PAPGAPC Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACD

e_dACT

v2_dSPS

v2_dSPS

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

General trip

ST

TRIP

Mon

Quality: General trip

ST

TRIP

Mon

Timestamp: General trip

general

ST

TRIP

Mon

General trip

phsA

ST

TRL1

Mon

Trip phase L1

phsB

ST

TRL2

Mon

Trip phase L2

phsC

ST

TRL3

Mon

Trip phase L3

neut

ST

TRIN

Mon

Trip caused by residual current


detection

ST

TRIP

Mon

Quality: General trip

ST

TRIP

Mon

Timestamp: General trip

stVal

ST

ARST

Mon

Start signal to the autorecloser


function

ST

ARST

Mon

Quality: Start signal to the


autorecloser function

ST

ARST

Mon

Timestamp: Start signal to the


autorecloser function

stVal

ST

ARST3PH

Mon

Three phase reclosing to be


performed

ST

ARST3PH

Mon

Quality: Three phase reclosing to


be performed

ST

ARST3PH

Mon

Timestamp: Three phase


reclosing to be performed

263

Section 7
Logical node data model

1MRK 511 302-UEN -

7.5.23

Out-of-step protection PPAM

7.5.23.1

Out-of-step protection OOSPPAM

Table 193:
DO name
Mod

Beh

Str

Op

Zn1SlpDet

LN type

LN prefix

LN class

Function block name

OOSPPAM (revision 1)

OOS

PPAM

OOSPPAM

OOSPPAM Logical node data


DO type
a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

Set when measured impedance


enters lens characteristic

ST

START

Mon

Quality: Set when measured


impedance enters lens
characteristic

ST

START

Mon

Timestamp: Set when measured


impedance enters lens
characteristic

general

ST

TRIP

Mon

Common trip, issued when either


zone 1 or zone 2 give trip

ST

TRIP

Mon

Quality: Common trip, issued


when either zone 1 or zone 2 give
trip

ST

TRIP

Mon

Timestamp: Common trip, issued


when either zone 1 or zone 2 give
trip

stVal

ST

TRIPZ1

Mon

Zone 1 trip

ST

TRIPZ1

Mon

Quality: Zone 1 trip

Table continues on next page


264

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

Zn1SlpDet

v1_dSPS

ST

TRIPZ1

Mon

Timestamp: Zone 1 trip

Zn2SlpDet

v1_dSPS

stVal

ST

TRIPZ2

Mon

Zone 2 trip

ST

TRIPZ2

Mon

Quality: Zone 2 trip

ST

TRIPZ2

Mon

Timestamp: Zone 2 trip

stVal

ST

GENMODE

Mon

Generator rotates faster than the


system during pole slip

ST

GENMODE

Mon

Quality: Generator rotates faster


than the system during pole slip

ST

GENMODE

Mon

Timestamp: Generator rotates


faster than the system during
pole slip

stVal

ST

MOTMODE

Mon

Generator rotates slower than the


system during pole slip

ST

MOTMODE

Mon

Quality: Generator rotates slower


than the system during pole slip

ST

MOTMODE

Mon

Timestamp: Generator rotates


slower than the system during
pole slip

Gen

Mot

v1_dSPS

v1_dSPS

7.5.23.2

Table 194:
DO name
Mod

Beh

PoleSlip/Out-of-step protection PSPPPAM


LN type

LN prefix

LN class

Function block name

PSPPPAM (revision 3)

PSP

PPAM

PSPPPAM

PSPPPAM Logical node data


DO type

DA name

a_dINC

a_dINS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

265

Section 7
Logical node data model
DO name
Str

Op

Gen

Mot

N2SlpDet

SlpZ1

SlpZ2

N1SlpDet

SlpHz

SlpZOhm

DO type
b_dACD

b_dACT

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v2_dMV

v2_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

general

ST

START

Mon

Common start signal

dirGeneral

ST

START

Mon

Common start signal

ST

START

Mon

Quality: Common start signal

ST

START

Mon

Timestamp: Common start signal

general

ST

TRIP

Mon

Common trip signal

ST

TRIP

Mon

Quality: Common trip signal

ST

TRIP

Mon

Timestamp: Common trip signal

stVal

ST

GEN

Mon

Generator is faster than the


system

ST

GEN

Mon

Quality: Generator is faster than


the system

ST

GEN

Mon

Timestamp: Generator is faster


than the system

stVal

ST

MOTOR

Mon

Generator is slower than the


system

ST

MOTOR

Mon

Quality: Generator is slower than


the system

ST

MOTOR

Mon

Timestamp: Generator is slower


than the system

stVal

ST

TRIP2

Mon

Trip2 after the N2Limit slip in


zone2

ST

TRIP2

Mon

Quality: Trip2 after the N2Limit


slip in zone2

ST

TRIP2

Mon

Timestamp: Trip2 after the


N2Limit slip in zone2

stVal

ST

ZONE1

Mon

First slip in zone1 region

ST

ZONE1

Mon

Quality: First slip in zone1 region

ST

ZONE1

Mon

Timestamp: First slip in zone1


region

stVal

ST

ZONE2

Mon

First slip in zone2 region

ST

ZONE2

Mon

Quality: First slip in zone2 region

ST

ZONE2

Mon

Timestamp: First slip in zone2


region

stVal

ST

TRIP1

Mon

Trip1 after the N1Limit slip in


zone1

ST

TRIP1

Mon

Quality: Trip1 after the N1Limit


slip in zone1

ST

TRIP1

Mon

Timestamp: Trip1 after the


N1Limit slip in zone1

mag.f

MX

SFREQ

Mon

Slip frequency

MX

SFREQ

Mon

Quality: Slip frequency

MX

SFREQ

Mon

Timestamp: Slip frequency

mag.f

MX

SLIPZOHM

Mon

Slip impedance in ohms

MX

SLIPZOHM

Mon

Quality: Slip impedance in ohms

Table continues on next page

266

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

SlpZOhm

v2_dMV

MX

SLIPZOHM

Mon

Timestamp: Slip impedance in


ohms

CosUkV

v2_dMV

mag.f

MX

UCOS

Mon

UCosPhi voltage

MX

UCOS

Mon

Quality: UCosPhi voltage

MX

UCOS

Mon

Timestamp: UCosPhi voltage

7.5.24

Earth fault protection PHIZ

7.5.24.1

ROTIPHIZ (64R)

Table 195:
DO name
Mod

Beh

Str

Op

Mon/
Cmd

Description

LN type

LN prefix

LN class

Function block name

ROTIPHIZ (revision 1)

ROTI

PHIZ

ROTIPHIZ

ROTIPHIZ Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACD

b_dACT

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

Start (common AC and DC side


of exciter)

ST

START

Mon

Quality: Start (common AC and


DC side of exciter)

ST

START

Mon

Timestamp: Start (common AC


and DC side of exciter)

general

ST

TRIP

Mon

Trip (common AC and DC side of


exciter)

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

267

Section 7
Logical node data model
DO name
Op

ErrorSt

Alm

Error

StrDC

StrAC

OpDC

OpAC

DO type
b_dACT

v1_dINS

v1_dSPS

v1_dSPS

v2_dACD

v2_dACD

v2_dACT

v2_dACT

7.5.24.2

Table 196:
DO name
Mod

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

TRIP

Mon

Quality: Trip (common AC and


DC side of exciter)

ST

TRIP

Mon

Timestamp: Trip (common AC


and DC side of exciter)

stVal

ST

ERRSTAT

Mon

Error indication

ST

ERRSTAT

Mon

Quality: Error indication

ST

ERRSTAT

Mon

Timestamp: Error indication

stVal

ST

ALARM

Mon

Alarm

ST

ALARM

Mon

Quality: Alarm

ST

ALARM

Mon

Timestamp: Alarm

stVal

ST

ERROR

Mon

Error

ST

ERROR

Mon

Quality: Error

ST

ERROR

Mon

Timestamp: Error

general

ST

STARTDC

Mon

Start for DC side of exciter

ST

STARTDC

Mon

Quality: Start for DC side of exciter

ST

STARTDC

Mon

Timestamp: Start for DC side of


exciter

general

ST

STARTAC

Mon

Start for AC side of exciter

ST

STARTAC

Mon

Quality: Start for AC side of exciter

ST

STARTAC

Mon

Timestamp: Start for AC side of


exciter

general

ST

TRIPDC

Mon

Trip for DC side of exciter

ST

TRIPDC

Mon

Quality: Trip for DC side of exciter

ST

TRIPDC

Mon

Timestamp: Trip for DC side of


exciter

general

ST

TRIPAC

Mon

Trip for AC side of exciter

ST

TRIPAC

Mon

Quality: Trip for AC side of exciter

ST

TRIPAC

Mon

Timestamp: Trip for AC side of


exciter

100% Stator earth fault protection, 3rd harmonic based STEFPHIZ


LN type

LN prefix

LN class

Function block name

STEFPHIZ (revision 2)

STEF

PHIZ

STEFPHIZ

STEFPHIZ Logical node data


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Table continues on next page


268

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

Str

Op

Op3rdH

OpUN

Str3rdH

StrUN

DO type

DA name

a_dINC

a_dINS

b_dACD

b_dACT

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

Main, common start signal

ST

START

Mon

Quality: Main, common start signal

ST

START

Mon

Timestamp: Main, common start


signal

general

ST

TRIP

Mon

Main, common trip command

ST

TRIP

Mon

Quality: Main, common trip


command

ST

TRIP

Mon

Timestamp: Main, common trip


command

stVal

ST

TRIP3H

Mon

Trip by one of two 3rd harmonic


voltage-based prot.

ST

TRIP3H

Mon

Quality: Trip by one of two 3rd


harmonic voltage-based prot.

ST

TRIP3H

Mon

Timestamp: Trip by one of two


3rd harmonic voltage-based prot.

stVal

ST

TRIPUN

Mon

Trip by fund. freq. neutral overvoltage protection

ST

TRIPUN

Mon

Quality: Trip by fund. freq. neutral


over-voltage protection

ST

TRIPUN

Mon

Timestamp: Trip by fund. freq.


neutral over-voltage protection

stVal

ST

START3H

Mon

Start by one of two 3rd harmonic


voltage-based prot.

ST

START3H

Mon

Quality: Start by one of two 3rd


harmonic voltage-based prot.

ST

START3H

Mon

Timestamp: Start by one of two


3rd harmonic voltage-based prot.

stVal

ST

STARTUN

Mon

Start signal by fund. freq. neutral


over-voltage prot.

ST

STARTUN

Mon

Quality: Start signal by fund. freq.


neutral over-voltage prot.

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

269

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

StrUN

v1_dSPS

ST

STARTUN

Mon

Timestamp: Start signal by fund.


freq. neutral over-voltage prot.

VT3rdH

v2_dMV

mag.f

MX

UT3

Mon

Mag. of 3rd harm. voltage at


generator terminal side, Volts

MX

UT3

Mon

Quality: Mag. of 3rd harm.


voltage at generator terminal
side, Volts

MX

UT3

Mon

Timestamp: Mag. of 3rd harm.


voltage at generator terminal
side, Volts

mag.f

MX

UN3

Mon

Mag. of 3rd harm. voltage at


generator neutral side, Volts

MX

UN3

Mon

Quality: Mag. of 3rd harm.


voltage at generator neutral side,
Volts

MX

UN3

Mon

Timestamp: Mag. of 3rd harm.


voltage at generator neutral side,
Volts

mag.f

MX

E3

Mon

Total induced stator 3rd harmonic


voltage, primary Volts

MX

E3

Mon

Quality: Total induced stator 3rd


harmonic voltage, primary Volts

MX

E3

Mon

Timestamp: Total induced stator


3rd harmonic voltage, primary
Volts

mag.f

MX

DU3

Mon

Diff. between 3rd harm. volt. at


both sides of gen., Volts

MX

DU3

Mon

Quality: Diff. between 3rd harm.


volt. at both sides of gen., Volts

MX

DU3

Mon

Timestamp: Diff. between 3rd


harm. volt. at both sides of gen.,
Volts

mag.f

MX

BU3

Mon

Bias voltage, a part of


voltN3rdHarmonic, primary Volts

MX

BU3

Mon

Quality: Bias voltage, a part of


voltN3rdHarmonic, primary Volts

MX

BU3

Mon

Timestamp: Bias voltage, a part


of voltN3rdHarmonic, primary
Volts

mag.f

MX

UN

Mon

Fund. frequency voltage at


generator neutral, primary Volts

MX

UN

Mon

Quality: Fund. frequency voltage


at generator neutral, primary Volts

MX

UN

Mon

Timestamp: Fund. frequency


voltage at generator neutral,
primary Volts

VN3rdH

E3

VDif3rdH

VBias3rdH

UN

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v2_dMV

Table continues on next page

270

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
VolAngClc

DO type

DA name

v2_dMV

DO name
Mod

Beh

Op

Str

ErrorSt

Signal

Mon/
Cmd

Description

mag.f

MX

ANGLE

Mon

Angle between 3rd harmonic


votage phasors, radians

MX

ANGLE

Mon

Quality: Angle between 3rd


harmonic votage phasors, radians

MX

ANGLE

Mon

Timestamp: Angle between 3rd


harmonic votage phasors, radians

7.5.24.3

Table 197:

FC

100% stator earth fault protection, injection based STTIPHIZ


LN type

LN prefix

LN class

Function block name

STTIPHIZ (revision 1)

STTI

PHIZ

STTIPHIZ

STTIPHIZ Logical node data


DO type

DA name

a_dINC

a_dINS

b_dACT

d_dACD

v1_dINS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

TRIP

Mon

Trip

ST

TRIP

Mon

Quality: Trip

ST

TRIP

Mon

Timestamp: Trip

general

ST

START

Mon

Start

ST

START

Mon

Quality: Start

ST

START

Mon

Timestamp: Start

stVal

ST

ERRSTAT

Mon

Error indication

ST

ERRSTAT

Mon

Quality: Error indication

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

271

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ErrorSt

v1_dINS

ST

ERRSTAT

Mon

Timestamp: Error indication

Alm

v1_dSPS

stVal

ST

ALARM

Mon

Alarm

ST

ALARM

Mon

Quality: Alarm

ST

ALARM

Mon

Timestamp: Alarm

stVal

ST

OPCIRC

Mon

Injection circuit open

ST

OPCIRC

Mon

Quality: Injection circuit open

ST

OPCIRC

Mon

Timestamp: Injection circuit open

stVal

ST

ERROR

Mon

Error

ST

ERROR

Mon

Quality: Error

ST

ERROR

Mon

Timestamp: Error

OpnCir

Error

v1_dSPS

v1_dSPS

7.5.25

Voltage-restrained time overcurrent PVOC

7.5.25.1

Voltage-restrained time overcurrent protection VRPVOC

Table 198:
DO name
Beh

Str

Op

Mod

272

LN type

LN prefix

LN class

Function block name

PH1PTRC instance 1 (revision 3)

PH1

PTRC

VRPVOC

PH1PTUV instance 1 (revision 0)

PH1

PTUV

VRPVOC

VRLLN0 instance 1 (revision 0)

LLN0

VRPVOC

VRPVOC instance 1 (revision 0)

VR

PVOC

VRPVOC

VRPVOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

START

Mon

General start signal

ST

START

Mon

Quality: General start signal

ST

START

Mon

Timestamp: General start signal

general

ST

TRIP

Mon

General trip signal

ST

TRIP

Mon

Quality: General trip signal

ST

TRIP

Mon

Timestamp: General trip signal

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 199:
DO name
Beh

Str

Op

Mod

Table 200:
DO name
Mod

Beh

VRPVOC Logical node data (instance 1)


DO type

DA name

a_dINS

b_dACD

b_dACT

c_dINC

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STUV

Mon

Start signal from undervoltage


function

ST

STUV

Mon

Quality: Start signal from


undervoltage function

ST

STUV

Mon

Timestamp: Start signal from


undervoltage function

general

ST

TRUV

Mon

Trip signal from undervoltage


function

ST

TRUV

Mon

Quality: Trip signal from


undervoltage function

ST

TRUV

Mon

Timestamp: Trip signal from


undervoltage function

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

VRPVOC Logical node data (instance 1)


DO type

DA name

a_dINC

a_dINS

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

273

Section 7
Logical node data model

Table 201:
DO name
Beh

Str

Op

Mod

1MRK 511 302-UEN -

VRPVOC Logical node data (instance 1)


DO type
a_dINS

b_dACD

b_dACT

c_dINC

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

STOC

Mon

Start signal from voltage


restrained overcurrent stage

ST

STOC

Mon

Quality: Start signal from voltage


restrained overcurrent stage

ST

STOC

Mon

Timestamp: Start signal from


voltage restrained overcurrent
stage

general

ST

TROC

Mon

Trip signal from voltage


restrained overcurrent stage

ST

TROC

Mon

Quality: Trip signal from voltage


restrained overcurrent stage

ST

TROC

Mon

Timestamp: Trip signal from


voltage restrained overcurrent
stage

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

7.6

System logical nodes

7.6.1

Generic security application component

7.6.1.1

Generic security application component AGSAL

274

LN type

LN prefix

LN class

Function block name

AGSAL instance 1 (revision 1)

GSAL

AGSAL

SECLLN0 instance 1 (revision 1)

LLN0

AGSAL

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 202:
DO name
Beh

AcsCtlFail

AuthFail

Ina

SvcViol

Mod

OpCntRs

NumCntRs

AGSAL Logical node data (instance 1)


DO type

DA name

a_dINS

a_dSEC

a_dSEC

a_dSEC

a_dSEC

c_dINC

f_dINC

m_dINS

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

cnt

ST

Mon

Mapping tag

ST

Mon

Timestamp: Mapping tag

cnt

ST

Mon

Mapping tag

ST

Mon

Timestamp: Mapping tag

cnt

ST

Mon

Mapping tag

ST

Mon

Timestamp: Mapping tag

cnt

ST

Mon

Mapping tag

ST

Mon

Timestamp: Mapping tag

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Oper.ctlVal

CO

Cmd

Mapping tag

Oper.origin.orCat

CO

Cmd

Mapping tag

Oper.origin.orIdent

CO

Cmd

Mapping tag

Oper.ctlNum

CO

Cmd

Mapping tag

Oper.T

CO

Cmd

Mapping tag

Oper.Test

CO

Cmd

Mapping tag

Oper.Check

CO

Cmd

Mapping tag

stVal

ST

Mon

Mapping tag

ST

Mon

Quality: Mapping tag

ST

Mon

Timestamp: Mapping tag

stVal

ST

Mon

Mapping tag

ST

Mon

Quality: Mapping tag

ST

Mon

Timestamp: Mapping tag

275

Section 7
Logical node data model

Table 203:
DO name
Beh

Mod

AGSAL Logical node data (instance 1)


DO type
a_dINS

c_dINC

DA name

FC

Signal

Mon/
Cmd

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

7.6.2

Table 204:

1MRK 511 302-UEN -

Description

Physical device information LPHD


LN type

LN prefix

LN class

Function block name

LPHD (revision 6)

LPHD

LPHD

LPHD Logical node data

DO name

DO type

DA name

PhyNam

b_dDPL

swRev

DC

Firmware version

serNum

DC

Serial Number

model

DC

IEDModel for IEC61850

stVal

ST

PhyHealth

Mon

Physical health

ST

PhyHealth

Mon

Quality: Physical health

ST

PhyHealth

Mon

Timestamp: Physical health

PhyHealth

n_dINS

7.6.3

Table 205:
DO name
Mod

FC

Signal

Mon/
Cmd

Description

Logical node zero LLNO


LN type

LN prefix

LN class

Function block name

LLN0 (revision 2)

LLN0

LD0LLN0

LD0LLN0 Logical node data


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Table continues on next page

276

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

DO type

DA name

a_dINC

a_dINS

FC

Signal

Mon/
Cmd

Description

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

NamPlt

ln0_dLPL

swRev

DC

Firmware version

Health

n_dINS

stVal

ST

Mon

Physical health

ST

Mon

Quality: Physical health

ST

Mon

Timestamp: Physical health

7.6.4

Table 206:
DO name
Mod

Dual ethernet port link status PRPSTATUS


LN type

LN prefix

LN class

Function block name

RCHLCCH (revision 1)

RCH

LCCH

PRPSTATUS

PRPSTATUS Logical node data


DO type

DA name

a_dINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Cmd

Mode parameter for 61850

Oper.T

CO

Cmd

Mode parameter for 61850

Oper.Test

CO

Cmd

Mode parameter for 61850

Oper.Check

CO

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

277

Section 7
Logical node data model
DO name
Beh

ChLiv

RedChLiv

FerCh

RedFerCh

DO type
a_dINS

a_dSPS

a_dSPS

b_dINS

b_dINS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

PRP-A LINK

Mon

PRP-A Link Status

ST

PRP-A LINK

Mon

Quality: PRP-A Link Status

ST

PRP-A LINK

Mon

Timestamp: PRP-A Link Status

stVal

ST

PRP-B LINK

Mon

PRP-B Link Status

ST

PRP-B LINK

Mon

Quality: PRP-B Link Status

ST

PRP-B LINK

Mon

Timestamp: PRP-B Link Status

stVal

ST

Mon

PRP-A Error Rate

ST

Mon

Quality: PRP-A Error Rate

ST

Mon

Timestamp: PRP-A Error Rate

stVal

ST

Mon

PRP-B Error Rate

ST

Mon

Quality: PRP-B Error Rate

ST

Mon

Timestamp: PRP-B Error Rate

7.7

Logical nodes for protection related functions

7.7.1

Breaker failure RBRF

7.7.1.1

Breaker failure protection 3-phase activation and output CCRBRF

Table 207:
DO name
OpIn

LN type

LN prefix

LN class

Function block name

CCRBRF (revision 0)

CC

RBRF

CCRBRF

CCRBRF Logical node data


DO type

DA name

FC

Signal

Mon/
Cmd

Description

aACT

general

ST

TRRET

Mon

Retrip by breaker failure


protection function

phsA

ST

TRRETL1

Mon

Retrip by breaker failure


protection function phase L1

phsB

ST

TRRETL2

Mon

Retrip by breaker failure


protection function phase L2

phsC

ST

TRRETL3

Mon

Retrip by breaker failure


protection function phase L3

Table continues on next page

278

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
OpIn

Mod

Beh

OpEx

OpEx2

DO type

DA name

aACT

aINC

aINS

bACT

v2ACT

7.7.1.2

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

ST

TRRET

Mon

Quality: Retrip by breaker failure


protection function

ST

TRRET

Mon

Timestamp: Retrip by breaker


failure protection function

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRBU

Mon

Back-up trip by breaker failure


protection function

ST

TRBU

Mon

Quality: Back-up trip by breaker


failure protection function

ST

TRBU

Mon

Timestamp: Back-up trip by


breaker failure protection function

general

ST

TRBU2

Mon

Second back-up trip by breaker


failure protection function

ST

TRBU2

Mon

Quality: Second back-up trip by


breaker failure protection function

ST

TRBU2

Mon

Timestamp: Second back-up trip


by breaker failure protection
function

Breaker failure protection, single phase version CCSRBRF


LN type

LN prefix

LN class

Function block name

CCSRBRF (revision 0)

CCS

RBRF

CCSRBRF

279

Section 7
Logical node data model

Table 208:
DO name
Mod

Beh

OpEx

OpIn

OpEx2

1MRK 511 302-UEN -

CCSRBRF Logical node data


DO type
aINC

aINS

bACT

bACT

v2ACT

DA name

FC

Signal

Mon/
Cmd

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRBU

Mon

Back-up trip by breaker failure


protection

ST

TRBU

Mon

Quality: Back-up trip by breaker


failure protection

ST

TRBU

Mon

Timestamp: Back-up trip by


breaker failure protection

general

ST

TRRET

Mon

Retrip by breaker failure protection

ST

TRRET

Mon

Quality: Retrip by breaker failure


protection

ST

TRRET

Mon

Timestamp: Retrip by breaker


failure protection

general

ST

TRBU2

Mon

Second back-up trip by breaker


failure protection

ST

TRBU2

Mon

Quality: Second back-up trip by


breaker failure protection

ST

TRBU2

Mon

Timestamp: Second back-up trip


by breaker failure protection

7.7.2

Differential supervision RDIF

7.7.2.1

Current circuit supervision CCSSPVC

280

Description

LN type

LN prefix

LN class

Function block name

CCSRDIF (revision 2)

CCS

RDIF

CCSSPVC

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 209:
DO name
Mod

Beh

Op

Alm

CCSSPVC Logical node data


DO type

DA name

aINC

aINS

bACT

v1SPS

FC

Signal

Mon/
Cmd

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

FAIL

Mon

Detection of current circuit failure

ST

FAIL

Mon

Quality: Detection of current


circuit failure

ST

FAIL

Mon

Timestamp: Detection of current


circuit failure

stVal

ST

ALARM

Mon

Alarm for current circuit failure

ST

ALARM

Mon

Quality: Alarm for current circuit


failure

ST

ALARM

Mon

Timestamp: Alarm for current


circuit failure

7.7.3

Disturbance recorder RDRE

7.7.3.1

Disturbance report DRPRDRE

Table 210:
DO name
Mod

Description

LN type

LN prefix

LN class

Function block name

DRPRDRE (revision 0)

DRP

RDRE

DRPRDRE

DRPRDRE Logical node data


DO type

DA name

a_dINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

281

Section 7
Logical node data model
DO name
Mod

Beh

RcdMade

FltNum

DO type
a_dINC

a_dINS

a_dSPS

b_dINS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

ModeSt

Mon

Mode status parameter for 61850

ST

ModeSt

Mon

Quality: Mode status parameter


for 61850

ST

ModeSt

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

RECMADE

Mon

Disturbance recording made

ST

RECMADE

Mon

Quality: Disturbance recording


made

ST

RECMADE

Mon

Timestamp: Disturbance
recording made

stVal

ST

FaultNumber

Mon

Disturbance fault number

ST

FaultNumber

Mon

Quality: Disturbance fault number

ST

FaultNumber

Mon

Timestamp: Disturbance fault


number

7.7.4

Fault locator RFLO

7.7.4.1

Fault locator LMBRFLO

Table 211:
DO name
Mod

Description

LN type

LN prefix

LN class

Function block name

LMBRFLO (revision 1)

LMB

RFLO

LMBRFLO

LMBRFLO Logical node data


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

Table continues on next page


282

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

FltZ

FltDiskm

FltLoop

ClcFlt

FltDisRl

DO type

DA name

a_dINC

a_dINS

b_dCMV

b_dMV

e_dINS

v1_dSPS

v2_dMV

FC

Signal

Mon/
Cmd

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

cVal.mag.f

MX

FLT_X

Mon

Reactive distance to fault

MX

FLT_X

Mon

Quality: Reactive distance to fault

MX

FLT_X

Mon

Timestamp: Reactive distance to


fault

mag.f

MX

FLT_DIST

Mon

Distance to fault in line length unit

MX

FLT_DIST

Mon

Quality: Distance to fault in line


length unit

MX

FLT_DIST

Mon

Timestamp: Distance to fault in


line length unit

stVal

ST

FLT_LOOP

Mon

Fault loop

ST

FLT_LOOP

Mon

Quality: Fault loop

ST

FLT_LOOP

Mon

Timestamp: Fault loop

stVal

ST

CALCMADE

Mon

Fault calculation made

ST

CALCMADE

Mon

Quality: Fault calculation made

ST

CALCMADE

Mon

Timestamp: Fault calculation


made

mag.f

MX

FLT_REL

Mon

Distance to fault, relative

MX

FLT_REL

Mon

Quality: Distance to fault, relative

MX

FLT_REL

Mon

Timestamp: Distance to fault,


relative

7.7.5

Secondary system supervision SPVC

7.7.5.1

Fuse failure supervision SDDRFUF

670 series 2.0 IEC


Communication Protocol Manual

Description

LN type

LN prefix

LN class

Function block name

SDDRFUF (revision 0)

SDD

RFUF

FUFSPVC

283

Section 7
Logical node data model

Table 212:
DO name
Mod

Beh

Str3Ph

Str

StrRst

7.7.5.2

284

1MRK 511 302-UEN -

FUFSPVC Logical node data


DO type
aINC

aINS

v2ACD

v2ACD

v2ACD

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

3PH

Mon

Three-phase start of function

ST

3PH

Mon

Quality: Three-phase start of


function

ST

3PH

Mon

Timestamp: Three-phase start of


function

general

ST

BLKU

Mon

General start of function

ST

BLKU

Mon

Quality: General start of function

ST

BLKU

Mon

Timestamp: General start of


function

general

ST

BLKZ

Mon

Start of current and voltage


controlled function

ST

BLKZ

Mon

Quality: Start of current and


voltage controlled function

ST

BLKZ

Mon

Timestamp: Start of current and


voltage controlled function

Fuse failure supervision based on voltage difference VDSPVC


LN type

LN prefix

LN class

Function block name

VDRFUF (revision 0)

VD

RFUF

VDSPVC

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 213:
DO name
Str

Mod

Beh

AlmRef

VDSPVC Logical node data


DO type

DA name

a_dACD

a_dINC

a_dINS

v1_dACD

FC

Signal

general

ST

MAINFUF

Mon

Block of main fuse failure

phsA

ST

U1L1FAIL

Mon

Fuse failure of Main fuse group


phase L1

phsB

ST

U1L2FAIL

Mon

Fuse failure of Main fuse group


phase L2

phsC

ST

U1L3FAIL

Mon

Fuse failure of Main fuse group


phase L3

ST

MAINFUF

Mon

Quality: Block of main fuse failure

ST

MAINFUF

Mon

Timestamp: Block of main fuse


failure

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

general

ST

PILOTFUF

Mon

Alarm of pilot fuse failure

phsA

ST

U2L1FAIL

Mon

Fuse failure of Pilot fuse group


phase L1

phsB

ST

U2L2FAIL

Mon

Fuse failure of Pilot fuse group


phase L2

phsC

ST

U2L3FAIL

Mon

Fuse failure of Pilot fuse group


phase L3

ST

PILOTFUF

Mon

Quality: Alarm of pilot fuse failure

ST

PILOTFUF

Mon

Timestamp: Alarm of pilot fuse


failure

7.7.6

Pole discordance protection RPLD

7.7.6.1

Pole discordance protection CCPDSC

670 series 2.0 IEC


Communication Protocol Manual

Mon/
Cmd

Description

285

Section 7
Logical node data model

Table 214:
DO name
Mod

Beh

Op

Str

1MRK 511 302-UEN -

LN type

LN prefix

LN class

Function block name

CCRPLD (revision 0)

CC

RPLD

CCPDSC

CCPDSC Logical node data


DO type
aINC

aINS

bACT

v2ACD

DA name

FC

Signal

Mon/
Cmd

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

TRIP

Mon

Trip signal to CB

ST

TRIP

Mon

Quality: Trip signal to CB

ST

TRIP

Mon

Timestamp: Trip signal to CB

general

ST

START

Mon

Trip condition TRUE, waiting for


time delay

ST

START

Mon

Quality: Trip condition TRUE,


waiting for time delay

ST

START

Mon

Timestamp: Trip condition TRUE,


waiting for time delay

7.7.7

Power swing detection RPSB

7.7.7.1

Power swing detection ZMRPSB

286

Description

LN type

LN prefix

LN class

Function block name

ZMRPSB (revision 2)

ZM

RPSB

ZMRPSB

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 215:
DO name
Mod

Beh

BlkZn

Str

ZOuter

ZInner

ZMRPSB Logical node data


DO type

DA name

a_dINC

a_dINS

a_dSPS

b_dACD

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

START

Mon

Power swing detected

ST

START

Mon

Quality: Power swing detected

ST

START

Mon

Timestamp: Power swing detected

general

ST

START

Mon

Power swing detected

ST

START

Mon

Quality: Power swing detected

ST

START

Mon

Timestamp: Power swing detected

stVal

ST

ZOUT

Mon

Measured impedance within outer


impedance boundary

ST

ZOUT

Mon

Quality: Measured impedance


within outer impedance boundary

ST

ZOUT

Mon

Timestamp: Measured
impedance within outer
impedance boundary

stVal

ST

ZIN

Mon

Measured impedance within inner


impedance boundary

ST

ZIN

Mon

Quality: Measured impedance


within inner impedance boundary

ST

ZIN

Mon

Timestamp: Measured
impedance within inner
impedance boundary

7.7.8

Autoreclosing RREC

7.7.8.1

Autorecloser for 1 phase, 2 phase and/or 3 phase operation SMBRREC

670 series 2.0 IEC


Communication Protocol Manual

287

Section 7
Logical node data model

Table 216:
DO name
Mod

Beh

Op

BlkRec

AutoRecSt

Rec1PhCnt

Rec2PhCnt

1MRK 511 302-UEN -

LN type

LN prefix

LN class

Function block name

SMBRREC (revision 1)

SMB

RREC

SMBRREC

SMBRREC Logical node data


DO type
aINC

aINS

bACT

bSPC

dINS

v1INS

v1INS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

general

ST

CLOSECB

Mon

Closing command for CB

ST

CLOSECB

Mon

Quality: Closing command for CB

ST

CLOSECB

Mon

Timestamp: Closing command for


CB

stVal

ST

BLOCKED

Mon

The AR is in blocked state

ST

BLOCKED

Mon

Quality: The AR is in blocked state

ST

BLOCKED

Mon

Timestamp: The AR is in blocked


state

stVal

ST

Mon

AR status

ST

Mon

Quality: AR status

ST

Mon

Timestamp: AR status

stVal

ST

COUNT1P

Mon

Counting the number of singlephase reclosing shots

ST

COUNT1P

Mon

Quality: Counting the number of


single-phase reclosing shots

ST

COUNT1P

Mon

Timestamp: Counting the number


of single-phase reclosing shots

stVal

ST

COUNT2P

Mon

Counting the number of twophase reclosing shots

ST

COUNT2P

Mon

Quality: Counting the number of


two-phase reclosing shots

ST

COUNT2P

Mon

Timestamp: Counting the number


of two-phase reclosing shots

Table continues on next page


288

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Rec31Cnt

Rec32Cnt

Rec33Cnt

Rec34Cnt

Rec35Cnt

TotRecCnt

OpRs

DO type

DA name

v1INS

v1INS

v1INS

v1INS

v1INS

v1INS

v1SPC

FC

Signal

Mon/
Cmd

Description

stVal

ST

COUNT3P1

Mon

Counting the number of threephase reclosing shot 1

ST

COUNT3P1

Mon

Quality: Counting the number of


three-phase reclosing shot 1

ST

COUNT3P1

Mon

Timestamp: Counting the number


of three-phase reclosing shot 1

stVal

ST

COUNT3P2

Mon

Counting the number of threephase reclosing shot 2

ST

COUNT3P2

Mon

Quality: Counting the number of


three-phase reclosing shot 2

ST

COUNT3P2

Mon

Timestamp: Counting the number


of three-phase reclosing shot 2

stVal

ST

COUNT3P3

Mon

Counting the number of threephase reclosing shot 3

ST

COUNT3P3

Mon

Quality: Counting the number of


three-phase reclosing shot 3

ST

COUNT3P3

Mon

Timestamp: Counting the number


of three-phase reclosing shot 3

stVal

ST

COUNT3P4

Mon

Counting the number of threephase reclosing shot 4

ST

COUNT3P4

Mon

Quality: Counting the number of


three-phase reclosing shot 4

ST

COUNT3P4

Mon

Timestamp: Counting the number


of three-phase reclosing shot 4

stVal

ST

COUNT3P5

Mon

Counting the number of threephase reclosing shot 5

ST

COUNT3P5

Mon

Quality: Counting the number of


three-phase reclosing shot 5

ST

COUNT3P5

Mon

Timestamp: Counting the number


of three-phase reclosing shot 5

stVal

ST

COUNTAR

Mon

Counting total number of


reclosing shots

ST

COUNTAR

Mon

Quality: Counting total number of


reclosing shots

ST

COUNTAR

Mon

Timestamp: Counting total


number of reclosing shots

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

289

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

OpRs

v1SPC

Oper.Check

CO

Cmd

Command parameter for


IEC61850

EnaRec

v1SPS

stVal

ST

SETON

Mon

The AR operation is switched on,


operative

ST

SETON

Mon

Quality: The AR operation is


switched on, operative

ST

SETON

Mon

Timestamp: The AR operation is


switched on, operative

stVal

ST

READY

Mon

Indicates that the AR function is


ready for a new sequence

ST

READY

Mon

Quality: Indicates that the AR


function is ready for a new
sequence

ST

READY

Mon

Timestamp: Indicates that the AR


function is ready for a new
sequence

stVal

ST

ACTIVE

Mon

Reclosing sequence in progress

ST

ACTIVE

Mon

Quality: Reclosing sequence in


progress

ST

ACTIVE

Mon

Timestamp: Reclosing sequence


in progress

stVal

ST

SUCCL

Mon

Activated if CB closes during the


time tUnsucCl

ST

SUCCL

Mon

Quality: Activated if CB closes


during the time tUnsucCl

ST

SUCCL

Mon

Timestamp: Activated if CB
closes during the time tUnsucCl

stVal

ST

UNSUCCL

Mon

Reclosing unsuccessful, signal


resets after the reclaim time

ST

UNSUCCL

Mon

Quality: Reclosing unsuccessful,


signal resets after the reclaim time

ST

UNSUCCL

Mon

Timestamp: Reclosing
unsuccessful, signal resets after
the reclaim time

stVal

ST

INPROGR

Mon

Reclosing shot in progress,


activated during open time

ST

INPROGR

Mon

Quality: Reclosing shot in


progress, activated during open
time

ST

INPROGR

Mon

Timestamp: Reclosing shot in


progress, activated during open
time

stVal

ST

1PT1

Mon

Single-phase reclosing is in
progress, shot 1

ST

1PT1

Mon

Quality: Single-phase reclosing is


in progress, shot 1

ST

1PT1

Mon

Timestamp: Single-phase
reclosing is in progress, shot 1

RdyRec

ActRec

SucRec

UnsRec

PrgRec

PrgRec11

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

Table continues on next page

290

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
PrgRec21

PrgRec31

PrgRec32

PrgRec33

PrgRec34

PrgRec35

Prm1PhOp

Prp3PhOp

DO type

DA name

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

v1SPS

FC

Signal

Mon/
Cmd

Description

stVal

ST

2PT1

Mon

Two-phase reclosing is in
progress, shot 1

ST

2PT1

Mon

Quality: Two-phase reclosing is in


progress, shot 1

ST

2PT1

Mon

Timestamp: Two-phase reclosing


is in progress, shot 1

stVal

ST

3PT1

Mon

Three-phase reclosing in
progress, shot 1

ST

3PT1

Mon

Quality: Three-phase reclosing in


progress, shot 1

ST

3PT1

Mon

Timestamp: Three-phase
reclosing in progress, shot 1

stVal

ST

3PT2

Mon

Three-phase reclosing in
progress, shot 2

ST

3PT2

Mon

Quality: Three-phase reclosing in


progress, shot 2

ST

3PT2

Mon

Timestamp: Three-phase
reclosing in progress, shot 2

stVal

ST

3PT3

Mon

Three-phase reclosing in
progress, shot 3

ST

3PT3

Mon

Quality: Three-phase reclosing in


progress, shot 3

ST

3PT3

Mon

Timestamp: Three-phase
reclosing in progress, shot 3

stVal

ST

3PT4

Mon

Three-phase reclosing in
progress, shot 4

ST

3PT4

Mon

Quality: Three-phase reclosing in


progress, shot 4

ST

3PT4

Mon

Timestamp: Three-phase
reclosing in progress, shot 4

stVal

ST

3PT5

Mon

Three-phase reclosing in
progress, shot 5

ST

3PT5

Mon

Quality: Three-phase reclosing in


progress, shot 5

ST

3PT5

Mon

Timestamp: Three-phase
reclosing in progress, shot 5

stVal

ST

PERMIT1P

Mon

Permit single-phase trip, inverse


signal to PREP3P

ST

PERMIT1P

Mon

Quality: Permit single-phase trip,


inverse signal to PREP3P

ST

PERMIT1P

Mon

Timestamp: Permit single-phase


trip, inverse signal to PREP3P

stVal

ST

PREP3P

Mon

Prepare three-phase trip, control


of the next trip operation

ST

PREP3P

Mon

Quality: Prepare three-phase trip,


control of the next trip operation

ST

PREP3P

Mon

Timestamp: Prepare three-phase


trip, control of the next trip
operation

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

291

Section 7
Logical node data model
DO name
WtMst

DO type
v1SPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

WFMASTER

Mon

Signal to Slave issued by Master


for sequential reclosing

ST

WFMASTER

Mon

Quality: Signal to Slave issued by


Master for sequential reclosing

ST

WFMASTER

Mon

Timestamp: Signal to Slave


issued by Master for sequential
reclosing

7.7.9

Synchronising RSYN

7.7.9.1

Synchrocheck, energizing check, and synchronizing SESRSYN

Table 217:
DO name
Beh

Rel

HzInd

AngInd

LN type

LN prefix

LN class

Function block name

AUT1RSYN instance 1 (revision 2)

AUT1

RSYN

SESRSYN

MAN1RSYN instance 2 (revision 2)

MAN1

RSYN

SESRSYN

RSY1LLN0 instance 1 (revision 2)

LLN0

SESRSYN

SYNRSYN instance 3 (revision 3)

SYN

RSYN

SESRSYN

SESRSYN Logical node data (instance 1)


DO type
a_dINS

a_dSPS

a_dSPS

a_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Automatic release

ST

Mon

Quality: Automatic release

ST

Mon

Timestamp: Automatic release

stVal

ST

FRDIFFA

Mon

Frequency difference out of limit


for Auto operation

ST

FRDIFFA

Mon

Quality: Frequency difference out


of limit for Auto operation

ST

FRDIFFA

Mon

Timestamp: Frequency difference


out of limit for Auto operation

stVal

ST

PHDIFFA

Mon

Phase angle difference out of


limit for Auto operation

ST

PHDIFFA

Mon

Quality: Phase angle difference


out of limit for Auto operation

ST

PHDIFFA

Mon

Timestamp: Phase angle


difference out of limit for Auto
operation

Table continues on next page

292

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
VInd

DifAngClc

DifHzClc

DifVClc

Mod

EnOK

TestSCOK

VBus

VLin

DO type

DA name

a_dSPS

b_dMV

b_dMV

b_dMV

c_dINC

v1_dSPS

v1_dSPS

v2_dMV

v2_dMV

670 series 2.0 IEC


Communication Protocol Manual

FC

Signal

Mon/
Cmd

Description

stVal

ST

UDIFFSC

Mon

Voltage difference out of limit

ST

UDIFFSC

Mon

Quality: Voltage difference out of


limit

ST

UDIFFSC

Mon

Timestamp: Voltage difference


out of limit

mag.f

MX

PHDIFFME

Mon

Calculated difference of phase


angle

MX

PHDIFFME

Mon

Quality: Calculated difference of


phase angle

MX

PHDIFFME

Mon

Timestamp: Calculated difference


of phase angle

mag.f

MX

FRDIFFME

Mon

Calculated difference of frequency

MX

FRDIFFME

Mon

Quality: Calculated difference of


frequency

MX

FRDIFFME

Mon

Timestamp: Calculated difference


of frequency

mag.f

MX

UDIFFME

Mon

Calculated difference of voltage


in p.u of set voltage base value

MX

UDIFFME

Mon

Quality: Calculated difference of


voltage in p.u of set voltage base
value

MX

UDIFFME

Mon

Timestamp: Calculated difference


of voltage in p.u of set voltage
base value

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

AUTOENOK

Mon

Automatic energizing check OK

ST

AUTOENOK

Mon

Quality: Automatic energizing


check OK

ST

AUTOENOK

Mon

Timestamp: Automatic energizing


check OK

stVal

ST

TSTAUTSY

Mon

Auto synchro check OK test output

ST

TSTAUTSY

Mon

Quality: Auto synchro check OK


test output

ST

TSTAUTSY

Mon

Timestamp: Auto synchro check


OK test output

mag.f

MX

UBUS

Mon

Bus voltage

MX

UBUS

Mon

Quality: Bus voltage

MX

UBUS

Mon

Timestamp: Bus voltage

mag.f

MX

ULINE

Mon

Line voltage

MX

ULINE

Mon

Quality: Line voltage

MX

ULINE

Mon

Timestamp: Line voltage

293

Section 7
Logical node data model

Table 218:
DO name
Beh

Rel

HzInd

AngInd

VInd

Mod

EnOK

TestSCOK

294

1MRK 511 302-UEN -

SESRSYN Logical node data (instance 2)


DO type
a_dINS

a_dSPS

a_dSPS

a_dSPS

a_dSPS

c_dINC

v1_dSPS

v1_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

Mon

Manual release

ST

Mon

Quality: Manual release

ST

Mon

Timestamp: Manual release

stVal

ST

FRDIFFM

Mon

Frequency difference out of limit


for Manual operation

ST

FRDIFFM

Mon

Quality: Frequency difference out


of limit for Manual operation

ST

FRDIFFM

Mon

Timestamp: Frequency difference


out of limit for Manual operation

stVal

ST

PHDIFFM

Mon

Phase angle difference out of


limit for Manual Operation

ST

PHDIFFM

Mon

Quality: Phase angle difference


out of limit for Manual Operation

ST

PHDIFFM

Mon

Timestamp: Phase angle


difference out of limit for Manual
Operation

stVal

ST

UDIFFSC

Mon

Voltage difference out of limit

ST

UDIFFSC

Mon

Quality: Voltage difference out of


limit

ST

UDIFFSC

Mon

Timestamp: Voltage difference


out of limit

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

MANENOK

Mon

Manual energizing check OK

ST

MANENOK

Mon

Quality: Manual energizing check


OK

ST

MANENOK

Mon

Timestamp: Manual energizing


check OK

stVal

ST

TSTMANSY

Mon

Manual synchro check OK test


output

ST

TSTMANSY

Mon

Quality: Manual synchro check


OK test output

ST

TSTMANSY

Mon

Timestamp: Manual synchro


check OK test output

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 219:
DO name
Mod

Beh

Bus1Sel

Bus2Sel

Lin1Sel

Lin2Sel

SelFuFail

TestEnOK

SESRSYN Logical node data (instance 1)


DO type

DA name

a_dINC

a_dINS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

B1SEL

Mon

Bus1 selected

ST

B1SEL

Mon

Quality: Bus1 selected

ST

B1SEL

Mon

Timestamp: Bus1 selected

stVal

ST

B2SEL

Mon

Bus2 selected

ST

B2SEL

Mon

Quality: Bus2 selected

ST

B2SEL

Mon

Timestamp: Bus2 selected

stVal

ST

LN1SEL

Mon

Line1 selected

ST

LN1SEL

Mon

Quality: Line1 selected

ST

LN1SEL

Mon

Timestamp: Line1 selected

stVal

ST

LN2SEL

Mon

Line2 selected

ST

LN2SEL

Mon

Quality: Line2 selected

ST

LN2SEL

Mon

Timestamp: Line2 selected

stVal

ST

USELFAIL

Mon

Selected voltage transformer fuse


failed

ST

USELFAIL

Mon

Quality: Selected voltage


transformer fuse failed

ST

USELFAIL

Mon

Timestamp: Selected voltage


transformer fuse failed

stVal

ST

TSTENOK

Mon

Energizing check OK test output

ST

TSTENOK

Mon

Quality: Energizing check OK test


output

ST

TSTENOK

Mon

Timestamp: Energizing check OK


test output

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

295

Section 7
Logical node data model
DO name
VHiAlm

InadCBCls

Table 220:
DO name
Beh

Rel

SynPrg

Mod

FailSyn

TestSynOK

VHiAlmSyn

DO type
v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

UOKSC

Mon

Voltage amplitudes above set


limits

ST

UOKSC

Mon

Quality: Voltage amplitudes


above set limits

ST

UOKSC

Mon

Timestamp: Voltage amplitudes


above set limits

stVal

ST

INADVCLS

Mon

Inadvertent circuit breaker closing

ST

INADVCLS

Mon

Quality: Inadvertent circuit


breaker closing

ST

INADVCLS

Mon

Timestamp: Inadvertent circuit


breaker closing

SESRSYN Logical node data (instance 3)


DO type
a_dINS

a_dSPS

a_dSPS

c_dINC

v1_dSPS

v1_dSPS

v1_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

SYNOK

Mon

Synchronizing OK output

ST

SYNOK

Mon

Quality: Synchronizing OK output

ST

SYNOK

Mon

Timestamp: Synchronizing OK
output

stVal

ST

SYNPROGR

Mon

Synchronizing in progress

ST

SYNPROGR

Mon

Quality: Synchronizing in progress

ST

SYNPROGR

Mon

Timestamp: Synchronizing in
progress

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

SYNFAIL

Mon

Synchronizing failed

ST

SYNFAIL

Mon

Quality: Synchronizing failed

ST

SYNFAIL

Mon

Timestamp: Synchronizing failed

stVal

ST

TSTSYNOK

Mon

Synchronizing OK test output

ST

TSTSYNOK

Mon

Quality: Synchronizing OK test


output

ST

TSTSYNOK

Mon

Timestamp: Synchronizing OK
test output

stVal

ST

UOKSYN

Mon

Voltage amplitudes for


synchronizing above set limits

Table continues on next page

296

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
VHiAlmSyn

VIndSyn

HzIndSyn

HzInBndSyn

HzRCIndSyn

DO type

DA name

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

ST

UOKSYN

Mon

Quality: Voltage amplitudes for


synchronizing above set limits

ST

UOKSYN

Mon

Timestamp: Voltage amplitudes


for synchronizing above set limits

stVal

ST

UDIFFSYN

Mon

Voltage difference out of limit for


synchronizing

ST

UDIFFSYN

Mon

Quality: Voltage difference out of


limit for synchronizing

ST

UDIFFSYN

Mon

Timestamp: Voltage difference


out of limit for synchronizing

stVal

ST

FRDIFSYN

Mon

Frequency difference out of limit


for synchronizing

ST

FRDIFSYN

Mon

Quality: Frequency difference out


of limit for synchronizing

ST

FRDIFSYN

Mon

Timestamp: Frequency difference


out of limit for synchronizing

stVal

ST

FRDIFFOK

Mon

Frequency difference in band for


synchronizing

ST

FRDIFFOK

Mon

Quality: Frequency difference in


band for synchronizing

ST

FRDIFFOK

Mon

Timestamp: Frequency difference


in band for synchronizing

stVal

ST

FRDERIVA

Mon

Frequency derivative out of limit


for synchronizing

ST

FRDERIVA

Mon

Quality: Frequency derivative out


of limit for synchronizing

ST

FRDERIVA

Mon

Timestamp: Frequency derivative


out of limit for synchronizing

7.8

Logical nodes for generic references

7.8.1

Generic process I/O GGIO

7.8.1.1

Logic rotating switch for function selection and LHMI presentation


SLGAPC

670 series 2.0 IEC


Communication Protocol Manual

LN type

LN prefix

LN class

Function block name

SLGGIO (revision 4)

SL

GGIO

SLGAPC

297

Section 7
Logical node data model

Table 221:
DO name
Mod

Beh

IntIn

SPCCO

SwPosC1

1MRK 511 302-UEN -

SLGAPC Logical node data


DO type
a_dINC

a_dINS

b_dINS

v2_dSPC

v3_dISC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

SWPOSN

Mon

Switch position (integer)

ST

SWPOSN

Mon

Quality: Switch position (integer)

ST

SWPOSN

Mon

Timestamp: Switch position


(integer)

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

ctlModel

CF

Control model type for step cmd

sboTimeout

CF

Maximum time between select


and execute signals for step cmd

sboClass

CF

Select for many used for step cmd

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

valWTr.posVal

ST

Mon

Position

Table continues on next page

298

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
SwPosC1

DO type

DA name

v3_dISC

DO name
Mod

Beh

Signal

Mon/
Cmd

Description

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

ST

Mon

Quality: Position

ST

Mon

Timestamp: Position

ctlModel

CF

Control model type for jump cmd

sboTimeout

CF

Maximum time between select


and execute signals for jump cmd

sboClass

CF

Select for many used for jump cmd

7.8.1.2

Table 222:

FC

Selector mini switch VSGAPC


LN type

LN prefix

LN class

Function block name

VSGGIO (revision 1)

VS

GGIO

VSGAPC

VSGAPC Logical node data


DO type

DA name

a_dINC

a_dINS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

299

Section 7
Logical node data model
DO name
DPCSO

300

DO type
d_dDPC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Cancel.ctlVal

CO

Cmd

Command parameter for


IEC61850

Cancel.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

SBOw.ctlVal

CO

Cmd

Command parameter for


IEC61850

SBOw.origin.orCat

CO

Cmd

Command parameter for


IEC61850

SBOw.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Cancel.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Cancel.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

SBOw.ctlNum

CO

Cmd

Command parameter for


IEC61850

SBOw.T

CO

Cmd

Command parameter for


IEC61850

Cancel.T

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Cancel.Test

CO

Cmd

Command parameter for


IEC61850

SBOw.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

SBOw.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

POSITION

Mon

Position indication, integer

ST

POSITION

Mon

Quality: Position indication,


integer

ST

POSITION

Mon

Timestamp: Position indication,


integer

stSeld

ST

Mon

Select conditions are fulfilled

ctlModel

CF

CtlModel

Specifies the type for control


model according to IEC 61850

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.8.1.3

Table 223:
DO name
Mod

Beh

DPCSO

Generic communication function for Double Point indication DPGAPC

DO name
Mod

LN prefix

LN class

Function block name

DPGGIO (revision 0)

DP

GGIO

DPGAPC

DPGAPC Logical node data


DO type

DA name

aINC

aINS

bDPC

7.8.1.4

Table 224:

LN type

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

POSITION

Mon

Double point indication

ST

POSITION

Mon

Quality: Double point indication

ST

POSITION

Mon

Timestamp: Double point


indication

Single point generic control 8 signals SPC8GAPC


LN type

LN prefix

LN class

Function block name

SPC8GGIO (revision 2)

SPC8

GGIO

SPC8GAPC

SPC8GAPC Logical node data


DO type

DA name

a_dINC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

301

Section 7
Logical node data model
DO name
Mod

Beh

SPCSO1

SPCSO2

SPCSO3

DO type

DA name

a_dINC

Oper.T

a_dINS

d_dSPC

d_dSPC

d_dSPC

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Table continues on next page


302

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
SPCSO3

SPCSO4

SPCSO5

SPCSO6

DO type

DA name

d_dSPC

d_dSPC

d_dSPC

d_dSPC

FC

Signal

Mon/
Cmd

Description

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

303

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

SPCSO6

d_dSPC

Oper.Check

CO

Cmd

Command parameter for


IEC61850

SPCSO7

d_dSPC

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

SPCSO8

d_dSPC

7.8.1.5

Table 225:
DO name
CntRs

Mod

Event counter with limit supervision L4UFCNT


LN type

LN prefix

LN class

Function block name

L4UFCNT (revision 0)

L4U

FCNT

L4UFCNT

L4UFCNT Logical node data


DO type
a_dBCR

a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

actVal

ST

VALUE

Mon

Counted value

ST

VALUE

Mon

Quality: Counted value

ST

VALUE

Mon

Timestamp: Counted value

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Table continues on next page

304

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

RsCnt

Lim1

Lim2

Lim3

DO type

DA name

a_dINC

a_dINS

v1_dSPC

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

LIMIT1

Mon

Counted value is larger than or


equal to CounterLimit1

ST

LIMIT1

Mon

Quality: Counted value is larger


than or equal to CounterLimit1

ST

LIMIT1

Mon

Timestamp: Counted value is


larger than or equal to
CounterLimit1

stVal

ST

LIMIT2

Mon

Counted value is larger than or


equal to CounterLimit2

ST

LIMIT2

Mon

Quality: Counted value is larger


than or equal to CounterLimit2

ST

LIMIT2

Mon

Timestamp: Counted value is


larger than or equal to
CounterLimit2

stVal

ST

LIMIT3

Mon

Counted value is larger than or


equal to CounterLimit3

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

305

Section 7
Logical node data model
DO name
Lim3

Lim4

DO type
v1_dSPS

v1_dSPS

DA name

FC

ST

LIMIT3

Mon

Quality: Counted value is larger


than or equal to CounterLimit3

ST

LIMIT3

Mon

Timestamp: Counted value is


larger than or equal to
CounterLimit3

stVal

ST

LIMIT4

Mon

Counted value is larger than or


equal to CounterLimit4

ST

LIMIT4

Mon

Quality: Counted value is larger


than or equal to CounterLimit4

ST

LIMIT4

Mon

Timestamp: Counted value is


larger than or equal to
CounterLimit4

7.8.1.6

Table 226:
DO name
Mod

Beh

Ind

306

1MRK 511 302-UEN -

Signal

Mon/
Cmd

Description

IEC61850 generic communication I/O functions SPGGIO


LN type

LN prefix

LN class

Function block name

SPGGIO (revision 1)

SP

GGIO

SPGAPC

SPGAPC Logical node data


DO type
a_dINC

a_dINS

c_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

OUT

Mon

Output status

ST

OUT

Mon

Quality: Output status

ST

OUT

Mon

Timestamp: Output status

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.8.1.7

Table 227:
DO name
Mod

Beh

Ind

Ind2

Ind3

Ind4

Ind5

Ind6

IEC61850 generic communication I/O functions 16 inputs SP16GGIO


LN type

LN prefix

LN class

Function block name

SP16GGIO (revision 2)

SP16

GGIO

SP16GAPC

SP16GAPC Logical node data


DO type

DA name

a_dINC

a_dINS

c_dSPS

c_dSPS

c_dSPS

c_dSPS

c_dSPS

c_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

OUT1

Mon

Output 1 status

ST

OUT1

Mon

Quality: Output 1 status

ST

OUT1

Mon

Timestamp: Output 1 status

stVal

ST

OUT2

Mon

Output 2 status

ST

OUT2

Mon

Quality: Output 2 status

ST

OUT2

Mon

Timestamp: Output 2 status

stVal

ST

OUT3

Mon

Output 3 status

ST

OUT3

Mon

Quality: Output 3 status

ST

OUT3

Mon

Timestamp: Output 3 status

stVal

ST

OUT4

Mon

Output 4 status

ST

OUT4

Mon

Quality: Output 4 status

ST

OUT4

Mon

Timestamp: Output 4 status

stVal

ST

OUT5

Mon

Output 5 status

ST

OUT5

Mon

Quality: Output 5 status

ST

OUT5

Mon

Timestamp: Output 5 status

stVal

ST

OUT6

Mon

Output 6 status

ST

OUT6

Mon

Quality: Output 6 status

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

307

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Ind6

c_dSPS

ST

OUT6

Mon

Timestamp: Output 6 status

Ind7

c_dSPS

stVal

ST

OUT7

Mon

Output 7 status

ST

OUT7

Mon

Quality: Output 7 status

ST

OUT7

Mon

Timestamp: Output 7 status

stVal

ST

OUT8

Mon

Output 8 status

ST

OUT8

Mon

Quality: Output 8 status

ST

OUT8

Mon

Timestamp: Output 8 status

stVal

ST

OUT9

Mon

Output 9 status

ST

OUT9

Mon

Quality: Output 9 status

ST

OUT9

Mon

Timestamp: Output 9 status

stVal

ST

OUT10

Mon

Output 10 status

ST

OUT10

Mon

Quality: Output 10 status

ST

OUT10

Mon

Timestamp: Output 10 status

stVal

ST

OUT11

Mon

Output 11 status

ST

OUT11

Mon

Quality: Output 11 status

ST

OUT11

Mon

Timestamp: Output 11 status

stVal

ST

OUT12

Mon

Output 12 status

ST

OUT12

Mon

Quality: Output 12 status

ST

OUT12

Mon

Timestamp: Output 12 status

stVal

ST

OUT13

Mon

Output 13 status

ST

OUT13

Mon

Quality: Output 13 status

ST

OUT13

Mon

Timestamp: Output 13 status

stVal

ST

OUT14

Mon

Output 14 status

ST

OUT14

Mon

Quality: Output 14 status

ST

OUT14

Mon

Timestamp: Output 14 status

stVal

ST

OUT15

Mon

Output 15 status

ST

OUT15

Mon

Quality: Output 15 status

ST

OUT15

Mon

Timestamp: Output 15 status

stVal

ST

OUT16

Mon

Output 16 status

ST

OUT16

Mon

Quality: Output 16 status

ST

OUT16

Mon

Timestamp: Output 16 status

stVal

ST

OUTOR

Mon

Output status logic OR gate for


input 1 to 16

ST

OUTOR

Mon

Quality: Output status logic OR


gate for input 1 to 16

ST

OUTOR

Mon

Timestamp: Output status logic


OR gate for input 1 to 16

Ind8

Ind9

Ind10

Ind11

Ind12

Ind13

Ind14

Ind15

Ind16

GrInd

7.8.1.8

308

c_dSPS

c_dSPS

c_dSPS

c_dSPS

c_dSPS

c_dSPS

c_dSPS

c_dSPS

c_dSPS

v1_dSPS

Generic communication function for Measured Value MVGAPC

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 228:
DO name
Mod

Beh

AnIn

LN type

LN prefix

LN class

Function block name

MVGGIO (revision 1)

MV

GGIO

MVGAPC

MVGAPC Logical node data


DO type

DA name

a_dINC

a_dINS

a_dMV

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

rangeC.hhLim.f

CF

MV hhLim

High High limit multiplied with the


base prefix (multiplication factor)

rangeC.hLim.f

CF

MV hLim

High limit multiplied with the base


prefix (multiplication factor)

rangeC.lLim.f

CF

MV lLim

Low limit multiplied with the base


prefix (multiplication factor)

rangeC.llLim.f

CF

MV llLim

Low Low limit multiplied with the


base prefix (multiplication factor)

rangeC.max.f

CF

MV max

Maximum value multiplied with


the base prefix (multiplication
factor)

rangeC.min.f

CF

MV min

Minimum value multiplied with the


base prefix (multiplication factor)

mag.f

MX

VALUE

Mon

Magnitude of deadband value

subMag.f

SV

Substituted value

range

MX

RANGE

Mon

Range

MX

VALUE

Mon

Quality: Magnitude of deadband


value

MX

VALUE

Mon

Timestamp: Magnitude of
deadband value

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

309

Section 7
Logical node data model
DO name
AnIn

DO type

DA name

a_dMV

subEna

SV

Enable substitution

db

CF

MV db

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

MV zeroDb

Zero point clamping in 0,001% of


range

7.8.1.9

Table 229:
DO name
Mod

Beh

AnIn

TotVal

ValUpd

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Pulse-counter logic PCFCNT


LN type

LN prefix

LN class

Function block name

PCGGIO (revision 0)

PC

GGIO

PCFCNT

PCFCNT Logical node data


DO type
aINC

aINS

bMV

v1BCR

v1SPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

mag.f

MX

SCAL_VAL

Mon

Scaled value with time and status


information

MX

SCAL_VAL

Mon

Quality: Scaled value with time


and status information

MX

SCAL_VAL

Mon

Timestamp: Scaled value with


time and status information

actVal

ST

CNT_VAL

Mon

Actual pulse counter value

ST

CNT_VAL

Mon

Quality: Actual pulse counter value

ST

CNT_VAL

Mon

Timestamp: Actual pulse counter


value

stVal

ST

NEW_VAL

Mon

A new pulse counter value is


generated

Table continues on next page


310

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name

DO type

ValUpd

v1SPS

IcpCyc

DA name

v1SPS

FC

ST

NEW_VAL

Mon

Quality: A new pulse counter


value is generated

ST

NEW_VAL

Mon

Timestamp: A new pulse counter


value is generated

stVal

ST

RESTART

Mon

The reported value does not


comprise a complete integration
cycle

ST

RESTART

Mon

Quality: The reported value does


not comprise a complete
integration cycle

ST

RESTART

Mon

Timestamp: The reported value


does not comprise a complete
integration cycle

7.8.1.10

Table 230:
DO name
Mod

Beh

Out1

Signal

Mon/
Cmd

Description

Trip matrix logic TMAGAPC


LN type

LN prefix

LN class

Function block name

TMAGGIO (revision 0)

TMA

GGIO

TMAGAPC

TMAGAPC Logical node data


DO type

DA name

aINC

aINS

v1SPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

OUTPUT1

Mon

OR function betweeen inputs 1 to


16

ST

OUTPUT1

Mon

Quality: OR function betweeen


inputs 1 to 16

ST

OUTPUT1

Mon

Timestamp: OR function
betweeen inputs 1 to 16

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

311

Section 7
Logical node data model
DO name
Out2

Out3

DO type
v1SPS

v1SPS

DA name

FC

stVal

ST

OUTPUT2

Mon

OR function between inputs 17 to


32

ST

OUTPUT2

Mon

Quality: OR function between


inputs 17 to 32

ST

OUTPUT2

Mon

Timestamp: OR function between


inputs 17 to 32

stVal

ST

OUTPUT3

Mon

OR function between inputs 1 to 32

ST

OUTPUT3

Mon

Quality: OR function between


inputs 1 to 32

ST

OUTPUT3

Mon

Timestamp: OR function between


inputs 1 to 32

7.8.1.11

Table 231:
DO name
Mod

Beh

Alm

1MRK 511 302-UEN -

Signal

Mon/
Cmd

Description

Elapsed time integrator with limit transgression and overflow


supervision TEIGGIO
LN type

LN prefix

LN class

Function block name

TEIGGIO (revision 0)

TEI

GGIO

TEIGAPC

TEIGAPC Logical node data


DO type
a_dINC

a_dINS

a_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status value parameter for


61850

ST

Mon

Quality: Mode status value


parameter for 61850

ST

Mon

Timestamp: Mode status value


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

ALARM

Mon

Indicator of the integrated time


has reached the alarm limit

Table continues on next page

312

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Alm

RsAccTms

Wrn

AccTms

DO type

DA name

a_dSPS

v1_dSPC

v1_dSPS

v2_dMV

FC

Signal

Mon/
Cmd

Description

ST

ALARM

Mon

Quality: Indicator of the integrated


time has reached the alarm limit

ST

ALARM

Mon

Timestamp: Indicator of the


integrated time has reached the
alarm limit

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

WARNING

Mon

Indicator of the integrated time


has reached the warning limit

ST

WARNING

Mon

Quality: Indicator of the integrated


time has reached the warning limit

ST

WARNING

Mon

Timestamp: Indicator of the


integrated time has reached the
warning limit

mag.f

MX

ACCTIME

Mon

Integrated elapsed time in


seconds

MX

ACCTIME

Mon

Quality: Integrated elapsed time


in seconds

MX

ACCTIME

Mon

Timestamp: Integrated elapsed


time in seconds

7.9

Logical nodes for metering and measurement

7.9.1

Metering MMTR

7.9.1.1

Function for energy calculation and demand handling ETPMMTR

670 series 2.0 IEC


Communication Protocol Manual

LN type

LN prefix

LN class

Function block name

ETPMMTR (revision 3)

ETP

MMTR

ETPMMTR

313

Section 7
Logical node data model

Table 232:
DO name
Mod

Beh

SupRs

MaxDmdRs

1MRK 511 302-UEN -

ETPMMTR Logical node data


DO type
a_dINC

a_dINS

v1_dSPC

v1_dSPC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Table continues on next page


314

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
StrAcc

WhFwdAlm

WhRvAlm

VArhFwdAlm

VArhRvAlm

VArsAccFwd

VArsAccRev

DO type

DA name

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v2_dBCR

v2_dBCR

FC

Signal

Mon/
Cmd

Description

stVal

ST

ACCINPRG

Mon

Accumulation of energy values in


progress

ST

ACCINPRG

Mon

Quality: Accumulation of energy


values in progress

ST

ACCINPRG

Mon

Timestamp: Accumulation of
energy values in progress

stVal

ST

EAFALM

Mon

Alarm for active forward energy


exceed limit in set interval

ST

EAFALM

Mon

Quality: Alarm for active forward


energy exceed limit in set interval

ST

EAFALM

Mon

Timestamp: Alarm for active


forward energy exceed limit in set
interval

stVal

ST

EARALM

Mon

Alarm for active reverse energy


exceed limit in set interval

ST

EARALM

Mon

Quality: Alarm for active reverse


energy exceed limit in set interval

ST

EARALM

Mon

Timestamp: Alarm for active


reverse energy exceed limit in set
interval

stVal

ST

ERFALM

Mon

Alarm for reactive forward energy


exceed limit in set interval

ST

ERFALM

Mon

Quality: Alarm for reactive


forward energy exceed limit in set
interval

ST

ERFALM

Mon

Timestamp: Alarm for reactive


forward energy exceed limit in set
interval

stVal

ST

ERRALM

Mon

Alarm for reactive reverse energy


exceed limit in set interval

ST

ERRALM

Mon

Quality: Alarm for reactive


reverse energy exceed limit in set
interval

ST

ERRALM

Mon

Timestamp: Alarm for reactive


reverse energy exceed limit in set
interval

actVal

ST

Mon

Accumulated forward reactive


energy value (BCR)

ST

Mon

Quality: Accumulated forward


reactive energy value (BCR)

ST

Mon

Timestamp: Accumulated forward


reactive energy value (BCR)

pulsQty

CF

ERFAccPlsQty

Pulse quantity for reactive


forward accumulated energy value

actVal

ST

Mon

Accumulated reverse reactive


energy value (BCR)

ST

Mon

Quality: Accumulated reverse


reactive energy value (BCR)

ST

Mon

Timestamp: Accumulated reverse


reactive energy value (BCR)

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

315

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

VArsAccRev

v2_dBCR

pulsQty

CF

ERRAccPlsQty

Pulse quantity for reactive


reverse accumulated energy value

WsAccFwd

v2_dBCR

actVal

ST

Mon

Accumulated forward active


energy value (BCR)

ST

Mon

Quality: Accumulated forward


active energy value (BCR)

ST

Mon

Timestamp: Accumulated forward


active energy value (BCR)

pulsQty

CF

EAFAccPlsQty

Pulse quantity for active forward


accumulated energy value

actVal

ST

Mon

Accumulated reverse active


energy value (BCR)

ST

Mon

Quality: Accumulated reverse


active energy value (BCR)

ST

Mon

Timestamp: Accumulated reverse


active energy value (BCR)

pulsQty

CF

EARAccPlsQty

Pulse quantity for active reverse


accumulated energy value

mag.f

MX

MAXPRFD

Mon

Maximum forward reactive power


demand value for set interval

MX

MAXPRFD

Mon

Quality: Maximum forward


reactive power demand value for
set interval

MX

MAXPRFD

Mon

Timestamp: Maximum forward


reactive power demand value for
set interval

mag.f

MX

MAXPRRD

Mon

Maximum reactive power demand


value in reverse direction

MX

MAXPRRD

Mon

Quality: Maximum reactive power


demand value in reverse direction

MX

MAXPRRD

Mon

Timestamp: Maximum reactive


power demand value in reverse
direction

mag.f

MX

MAXPAFD

Mon

Maximum forward active power


demand value for set interval

MX

MAXPAFD

Mon

Quality: Maximum forward active


power demand value for set
interval

MX

MAXPAFD

Mon

Timestamp: Maximum forward


active power demand value for
set interval

mag.f

MX

MAXPARD

Mon

Maximum reverse active power


demand value for set interval

MX

MAXPARD

Mon

Quality: Maximum reverse active


power demand value for set
interval

MX

MAXPARD

Mon

Timestamp: Maximum reverse


active power demand value for
set interval

WsAccRev

MaxVArFwdD

MaxVArRvDm

MaxWFwdDmd

MaxWRvDmd

316

v2_dBCR

v2_dMV

v2_dMV

v2_dMV

v2_dMV

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.9.2

Non phase related measurement MMXN

7.9.2.1

Measurements CVMMXN

Table 233:
DO name
Mod

Beh

Amp

LN type

LN prefix

LN class

Function block name

CVMMXN (revision 1)

CV

MMXN

CVMMXN

CVMMXN Logical node data


DO type

DA name

a_dINC

a_dINS

a_dMV

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

mag.f

MX

Mon

Calculated current magnitude of


deadband value

rangeC.hhLim.f

CF

IHiHiLim

High High limit in % of IBase

rangeC.hLim.f

CF

IHiLim

High limit in % of IBase

rangeC.lLim.f

CF

ILowLim

Low limit in % of IBase

rangeC.llLim.f

CF

ILowLowLim

Low Low limit in % of IBase

rangeC.max.f

CF

IMax

Maximum value in % of IBase

rangeC.min.f

CF

IMin

Minimum value in % of IBase

subMag.f

SV

Substituted value

range

MX

I_RANGE

Mon

Calculated current range

MX

Mon

Quality: Calculated current


magnitude of deadband value

MX

Mon

Timestamp: Calculated current


magnitude of deadband value

subEna

SV

Enable substitution

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

317

Section 7
Logical node data model
DO name
Amp

Hz

PwrFact

Vol

DO type
a_dMV

a_dMV

a_dMV

a_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

db

CF

IDbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

IZeroDb

Zero point clamping in 0,001% of


range

mag.f

MX

Mon

System frequency magnitude of


deadband value

rangeC.hhLim.f

CF

FrHiHiLim

High High limit (physical value)

rangeC.hLim.f

CF

FrHiLim

High limit (physical value)

rangeC.lLim.f

CF

FrLowLim

Low limit (physical value)

rangeC.llLim.f

CF

FrLowLowLim

Low Low limit (physical value)

rangeC.max.f

CF

FrMax

Maximum value

rangeC.min.f

CF

FrMin

Minimum value

subMag.f

SV

Substituted value

range

MX

F_RANGE

Mon

System frequency range

MX

Mon

Quality: System frequency


magnitude of deadband value

MX

Mon

Timestamp: System frequency


magnitude of deadband value

subEna

SV

Enable substitution

db

CF

FrDbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

FrZeroDb

Zero point clamping in 0,001% of


range

rangeC.hhLim.f

CF

PFHiHiLim

High High limit (physical value)

rangeC.hLim.f

CF

PFHiLim

High limit (physical value)

rangeC.lLim.f

CF

PFLowLim

Low limit (physical value)

rangeC.llLim.f

CF

PFLowLowLim

Low Low limit (physical value)

rangeC.max.f

CF

PFMax

Maximum value

rangeC.min.f

CF

PFMin

Minimum value

mag.f

MX

PF

Mon

Power Factor magnitude of


deadband value

subMag.f

SV

Substituted value

range

MX

PF_RANGE

Mon

Power Factor range

MX

PF

Mon

Quality: Power Factor magnitude


of deadband value

MX

PF

Mon

Timestamp: Power Factor


magnitude of deadband value

subEna

SV

Enable substitution

db

CF

PFDbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

PFZeroDb

Zero point clamping in 0,001% of


range

rangeC.hhLim.f

CF

UHiHiLim

High High limit in % of UBase

Table continues on next page

318

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Vol

VolAmp

VolAmpr

DO type

DA name

a_dMV

a_dMV

a_dMV

FC

Signal

Mon/
Cmd

Description

rangeC.hLim.f

CF

UHiLim

High limit in % of UBase

rangeC.lLim.f

CF

ULowLim

Low limit in % of UBase

rangeC.llLim.f

CF

ULowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

UMax

Maximum value in % of UBase

rangeC.min.f

CF

UMin

Minimum value in % of UBase

subMag.f

SV

Substituted value

mag.f

MX

Mon

Calculated voltage magnitude of


deadband value

range

MX

U_RANGE

Mon

Calculated voltage range

MX

Mon

Quality: Calculated voltage


magnitude of deadband value

MX

Mon

Timestamp: Calculated voltage


magnitude of deadband value

subEna

SV

Enable substitution

db

CF

UDbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

UZeroDb

Zero point clamping in 0,001% of


range

mag.f

MX

Mon

Apparent Power magnitude of


deadband value

rangeC.hhLim.f

CF

SHiHiLim

High High limit in % of SBase

rangeC.hLim.f

CF

SHiLim

High limit in % of SBase

rangeC.lLim.f

CF

SLowLim

Low limit in % of SBase

rangeC.llLim.f

CF

SLowLowLim

Low Low limit in % of SBase

rangeC.max.f

CF

SMax

Maximum value in % of SBase

rangeC.min.f

CF

SMin

Minimum value in % of SBase

subMag.f

SV

Substituted value

range

MX

S_RANGE

Mon

Apparent Power range

MX

Mon

Quality: Apparent Power


magnitude of deadband value

MX

Mon

Timestamp: Apparent Power


magnitude of deadband value

subEna

SV

Enable substitution

db

CF

SDbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

SZeroDb

Zero point clamping in 0,001% of


range

rangeC.hhLim.f

CF

QHiHiLim

High High limit in % of SBase

rangeC.hLim.f

CF

QHiLim

High limit in % of SBase

rangeC.lLim.f

CF

QLowLim

Low limit in % of SBase

rangeC.llLim.f

CF

QLowLowLim

Low Low limit in % of SBase

rangeC.max.f

CF

QMax

Maximum value in % of SBase

rangeC.min.f

CF

QMin

Minimum value in % of SBase

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

319

Section 7
Logical node data model
DO name

DO type

VolAmpr

a_dMV

Watt

ALd

ALg

320

a_dMV

v1_dSPS

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

mag.f

MX

Mon

Reactive Power magnitude of


deadband value

subMag.f

SV

Substituted value

range

MX

Q_RANGE

Mon

Reactive Power range

MX

Mon

Quality: Reactive Power


magnitude of deadband value

MX

Mon

Timestamp: Reactive Power


magnitude of deadband value

subEna

SV

Enable substitution

db

CF

QDbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

QZeroDb

Zero point clamping in 0,001% of


range

mag.f

MX

Mon

Active Power magnitude of


deadband value

rangeC.hhLim.f

CF

PHiHiLim

High High limit in % of SBase

rangeC.hLim.f

CF

PHiLim

High limit in % of SBase

rangeC.lLim.f

CF

PLowLim

Low limit in % of SBase

rangeC.llLim.f

CF

PLowLowLim

Low Low limit in % of SBase

rangeC.max.f

CF

PMax

Maximum value in % of SBase

rangeC.min.f

CF

PMin

Minimum value in % of SBase

subMag.f

SV

Substituted value

range

MX

P_RANGE

Mon

Active Power range

MX

Mon

Quality: Active Power magnitude


of deadband value

MX

Mon

Timestamp: Active Power


magnitude of deadband value

subEna

SV

Enable substitution

db

CF

PDbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

PZeroDb

Zero point clamping in 0,001% of


range

stVal

ST

ILEAD

Mon

Current is leading voltage

ST

ILEAD

Mon

Quality: Current is leading voltage

ST

ILEAD

Mon

Timestamp: Current is leading


voltage

stVal

ST

ILAG

Mon

Current is lagging voltage

ST

ILAG

Mon

Quality: Current is lagging voltage

ST

ILAG

Mon

Timestamp: Current is lagging


voltage

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.9.3

Measurement MMXU

7.9.3.1

Phase current measurement CMMXU

Table 234:
DO name
Mod

Beh

LN type

LN prefix

LN class

Function block name

CMMXU (revision 3)

MMXU

CMMXU

CMMXU Logical node data


DO type

DA name

a_dINC

a_dINS

k_dWYE

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

rangeC.hhLim.f

CF

IL1HiHiLim

High High limit in % of IBase

rangeC.hLim.f

CF

IL1HiLim

High limit in % of IBase

rangeC.lLim.f

CF

IL1LowLim

Low limit in % of IBase

rangeC.llLim.f

CF

IL1LowLowLim

Low Low limit in % of IBase

rangeC.max.f

CF

IL1Max

Maximum value in % of IBase

rangeC.min.f

CF

IL1Min

Minimum value in % of IBase

cVal.mag.f

MX

IL1

Mon

IL1 Amplitude, magnitude of


reported value

rangeC.hhLim.f

CF

IL2HiHiLim

High High limit in % of IBase

rangeC.hLim.f

CF

IL2HiLim

High limit in % of IBase

rangeC.lLim.f

CF

IL2LowLim

Low limit in % of IBase

rangeC.llLim.f

CF

IL2LowLowLim

Low Low limit in % of IBase

rangeC.max.f

CF

IL2Max

Maximum value in % of IBase

rangeC.min.f

CF

IL2Min

Minimum value in % of IBase

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

321

Section 7
Logical node data model
DO name
A

322

DO type
k_dWYE

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

cVal.mag.f

MX

IL2

Mon

IL2 Amplitude, magnitude of


reported value

subCVal.mag.f

SV

Substituted value

rangeC.hhLim.f

CF

IL3HiHiLim

High High limit in % of IBase

rangeC.hLim.f

CF

IL3HiLim

High limit in % of IBase

rangeC.lLim.f

CF

IL3LowLim

Low limit in % of IBase

rangeC.llLim.f

CF

IL3LowLowLim

Low Low limit in % of IBase

rangeC.max.f

CF

IL3Max

Maximum value in % of IBase

rangeC.min.f

CF

IL3Min

Minimum value in % of IBase

cVal.mag.f

MX

IL3

Mon

IL3 Amplitude, magnitude of


reported value

subCVal.mag.f

SV

Substituted value

subCVal.mag.f

SV

Substituted value

range

MX

IL3RANG

Mon

IL3 Amplitude range

range

MX

IL1RANG

Mon

IL1 Amplitude range

range

MX

IL2RANG

Mon

IL2 Amplitude range

MX

IL3

Mon

Quality: IL3 Amplitude, magnitude


of reported value

MX

IL2

Mon

Quality: IL2 Amplitude, magnitude


of reported value

MX

IL1

Mon

Quality: IL1 Amplitude, magnitude


of reported value

MX

IL1

Mon

Timestamp: IL1 Amplitude,


magnitude of reported value

MX

IL2

Mon

Timestamp: IL2 Amplitude,


magnitude of reported value

MX

IL3

Mon

Timestamp: IL3 Amplitude,


magnitude of reported value

subEna

SV

Enable substitution

subEna

SV

Enable substitution

subEna

SV

Enable substitution

db

CF

IL3DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

IL1DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

IL2DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

IL1ZeroDb

Zero point clamping

zeroDb

CF

IL3ZeroDb

Zero point clamping

zeroDb

CF

IL2ZeroDb

Zero point clamping

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

7.9.3.2

Table 235:
DO name
PPV

Phase-phase voltage measurement VMMXU


LN type

LN prefix

LN class

Function block name

VMMXU (revision 1)

MMXU

VMMXU

VMMXU Logical node data


DO type

DA name

a_dDEL

FC

Signal

Mon/
Cmd

Description

rangeC.hhLim.f

CF

UL12HiHiLim

High High limit in % of UBase

rangeC.hLim.f

CF

UL12HiLim

High limit in % of UBase

rangeC.lLim.f

CF

UL12LowLim

Low limit in % of UBase

rangeC.llLim.f

CF

UL12LowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

UL12Max

Maximum value in % of UBase

rangeC.min.f

CF

UL12Min

Minimum value in in % of UBase

cVal.mag.f

MX

UL12

Mon

UL12 Amplitude, magnitude of


reported value

rangeC.hhLim.f

CF

UL23HiHiLim

High High limit in % of UBase

rangeC.hLim.f

CF

UL23HiLim

High limit in % of UBase

rangeC.lLim.f

CF

UL23LowLim

Low limit in % of UBase

rangeC.llLim.f

CF

UL23LowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

UL23Max

Maximum value in % of UBase

rangeC.min.f

CF

UL23Min

Minimum value in % of UBase

cVal.mag.f

MX

UL23

Mon

UL23 Amplitude, magnitude of


reported value

subCVal.mag.f

SV

Substituted value

subCVal.mag.f

SV

Substituted value

rangeC.hhLim.f

CF

UL31HiHiLim

High High limit in % of UBase

rangeC.hLim.f

CF

UL31HiLim

High limit in % of UBase

rangeC.lLim.f

CF

UL31LowLim

Low limit in % of UBase

rangeC.llLim.f

CF

UL31LowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

UL31Max

Maximum value in % of UBase

rangeC.min.f

CF

UL31Min

Minimum value in % of UBase

cVal.mag.f

MX

UL31

Mon

UL31 Amplitude, magnitude of


reported value

subCVal.mag.f

SV

Substituted value

range

MX

UL31RANG

Mon

UL31 Amplitude range

range

MX

UL23RANG

Mon

UL23 Amplitude range

range

MX

UL12RANG

Mon

UL12 Amplitude range

MX

UL31

Mon

Quality: UL31 Amplitude,


magnitude of reported value

MX

UL23

Mon

Quality: UL23 Amplitude,


magnitude of reported value

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

323

Section 7
Logical node data model
DO name
PPV

Mod

Beh

7.9.3.3

324

DO type
a_dDEL

a_dINC

a_dINS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

MX

UL12

Mon

Quality: UL12 Amplitude,


magnitude of reported value

MX

UL12

Mon

Timestamp: UL12 Amplitude,


magnitude of reported value

MX

UL23

Mon

Timestamp: UL23 Amplitude,


magnitude of reported value

MX

UL31

Mon

Timestamp: UL31 Amplitude,


magnitude of reported value

subEna

SV

Enable substitution

subEna

SV

Enable substitution

subEna

SV

Enable substitution

db

CF

UL12DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

UL31DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

UL23DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Phase-neutral voltage measurement VNMMXU


LN type

LN prefix

LN class

Function block name

VNMMXU (revision 3)

VN

MMXU

VNMMXU

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 236:
DO name
Mod

Beh

PhV

VNMMXU Logical node data


DO type

DA name

a_dINC

a_dINS

k_dWYE

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

rangeC.hhLim.f

CF

UL1HiHiLim

High High limit in % of UBase

rangeC.hLim.f

CF

UL1HiLim

High limit in % of UBase

rangeC.lLim.f

CF

UL1LowLim

Low limit in % of UBase

rangeC.llLim.f

CF

UL1LowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

UL1Max

Maximum value in % of UBase

rangeC.min.f

CF

UL1Min

Minimum value in % of UBase

cVal.mag.f

MX

UL1

Mon

UL1 Amplitude, magnitude of


reported value

rangeC.hhLim.f

CF

UL2HiHiLim

High High limit in % of UBase

rangeC.hLim.f

CF

UL2HiLim

High limit in % of UBase

rangeC.lLim.f

CF

UL2LowLim

Low limit in % of UBase

rangeC.llLim.f

CF

UL2LowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

UL2Max

Maximum value in % of UBase

rangeC.min.f

CF

UL2Min

Minimum value in % of UBase

cVal.mag.f

MX

UL2

Mon

UL2 Amplitude, magnitude of


reported value

subCVal.mag.f

SV

Substituted value

subCVal.mag.f

SV

Substituted value

rangeC.hhLim.f

CF

UL3HiHiLim

High High limit in % of UBase

rangeC.hLim.f

CF

UL3HiLim

High limit in % of UBase

rangeC.lLim.f

CF

UL3LowLim

Low limit in % of UBase

rangeC.llLim.f

CF

UL3LowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

UL3Max

Maximum value in % of UBase

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

325

Section 7
Logical node data model
DO name
PhV

DO type
k_dWYE

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

rangeC.min.f

CF

UL3Min

Minimum value in % of UBase

cVal.mag.f

MX

UL3

Mon

UL3 Amplitude, magnitude of


reported value

subCVal.mag.f

SV

Substituted value

range

MX

UL3RANG

Mon

UL3 Amplitude range

range

MX

UL2RANG

Mon

UL2 Amplitude range

range

MX

UL1RANG

Mon

UL1 Amplitude range

MX

UL3

Mon

Quality: UL3 Amplitude,


magnitude of reported value

MX

UL2

Mon

Quality: UL2 Amplitude,


magnitude of reported value

MX

UL1

Mon

Quality: UL1 Amplitude,


magnitude of reported value

MX

UL1

Mon

Timestamp: UL1 Amplitude,


magnitude of reported value

MX

UL2

Mon

Timestamp: UL2 Amplitude,


magnitude of reported value

MX

UL3

Mon

Timestamp: UL3 Amplitude,


magnitude of reported value

subEna

SV

Enable substitution

subEna

SV

Enable substitution

subEna

SV

Enable substitution

db

CF

UL1DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

UL3DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

UL2DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

zeroDb

CF

UL2ZeroDb

Zero point clamping

zeroDb

CF

UL3ZeroDb

Zero point clamping

zeroDb

CF

UL1ZeroDb

Zero point clamping

7.9.4

Sequence and imbalance MSQI

7.9.4.1

Current sequence component measurement CMSQI

326

LN type

LN prefix

LN class

Function block name

CMSQI (revision 3)

MSQI

CMSQI

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 237:
DO name
Mod

Beh

SeqA

CMSQI Logical node data


DO type

DA name

a_dINC

a_dINS

b_dSEQ

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

rangeC.hhLim.f

CF

3I0HiHiLim

High High limit in % of IBase

rangeC.hLim.f

CF

3I0HiLim

High limit in % of IBase

rangeC.lLim.f

CF

3I0LowLim

Low limit in % of IBase

rangeC.llLim.f

CF

3I0LowLowLim

Low Low limit in % of IBase

rangeC.max.f

CF

3I0Max

Maximum value in % of IBase

rangeC.min.f

CF

3I0Min

Minimum value in % of IBase

cVal.mag.f

MX

3I0

Mon

3I0 Amplitude, magnitude of


reported value

rangeC.hhLim.f

CF

I1HiHiLim

High High limit in % of IBase

rangeC.hLim.f

CF

I1HiLim

High limit in % of IBase

rangeC.lLim.f

CF

I1LowLim

Low limit in % of IBase

rangeC.llLim.f

CF

I1LowLowLim

Low Low limit in % of IBase

rangeC.max.f

CF

I1Max

Maximum value in % of IBase

rangeC.min.f

CF

I1Min

Minimum value in % of IBase

cVal.mag.f

MX

I1

Mon

I1 Amplitude, magnitude of
reported value

subCVal.mag.f

SV

Substituted value

subCVal.mag.f

SV

Substituted value

rangeC.hhLim.f

CF

I2HiHiLim

High High limit in % of IBase

rangeC.hLim.f

CF

I2HiLim

High limit in % of IBase

rangeC.lLim.f

CF

I2LowLim

Low limit in % of IBase

rangeC.llLim.f

CF

I2LowLowLim

Low Low limit in % of IBase

rangeC.max.f

CF

I2Max

Maximum value in % of IBase

rangeC.min.f

CF

I2Min

Minimum value in % of IBase

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

327

Section 7
Logical node data model
DO name
SeqA

DO type
b_dSEQ

7.9.4.2

Table 238:
DO name
Mod

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

cVal.mag.f

MX

I2

Mon

I2 Amplitude, magnitude of
reported value

subCVal.mag.f

SV

Substituted value

range

MX

I2RANG

Mon

I2 Amplitude range

range

MX

I1RANG

Mon

I1 Amplitude range

range

MX

3I0RANG

Mon

3I0 Amplitude range

MX

I2

Mon

Quality: I2 Amplitude, magnitude


of reported value

MX

I1

Mon

Quality: I1 Amplitude, magnitude


of reported value

MX

3I0

Mon

Quality: 3I0 Amplitude, magnitude


of reported value

MX

3I0

Mon

Timestamp: 3I0 Amplitude,


magnitude of reported value

MX

I1

Mon

Timestamp: I1 Amplitude,
magnitude of reported value

MX

I2

Mon

Timestamp: I2 Amplitude,
magnitude of reported value

subEna

SV

Enable substitution

subEna

SV

Enable substitution

subEna

SV

Enable substitution

db

CF

3I0DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

I2DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

I1DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

Voltage sequence measurement VMSQI


LN type

LN prefix

LN class

Function block name

VMSQI (revision 3)

MSQI

VMSQI

VMSQI Logical node data


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Table continues on next page

328

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

SeqV

DO type

DA name

a_dINC

a_dINS

b_dSEQ

FC

Signal

Mon/
Cmd

Description

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

rangeC.hhLim.f

CF

3U0HiHiLim

High High limit in % of UBase

rangeC.hLim.f

CF

3U0HiLim

High limit in % of UBase

rangeC.lLim.f

CF

3U0LowLim

Low limit in % of UBase

rangeC.llLim.f

CF

3U0LowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

3U0Max

Maximum value in % of UBase

rangeC.min.f

CF

3U0Min

Minimum value in % of UBase

cVal.mag.f

MX

3U0

Mon

3U0 Amplitude, magnitude of


reported value

rangeC.hhLim.f

CF

U1HiHiLim

High High limit in % of UBase

rangeC.hLim.f

CF

U1HiLim

High limit in % of UBase

rangeC.lLim.f

CF

U1LowLim

Low limit in % of UBase

rangeC.llLim.f

CF

U1LowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

U1Max

Maximum value in % of UBase

rangeC.min.f

CF

U1Min

Minimum value in % of UBase

cVal.mag.f

MX

U1

Mon

U1 Amplitude, magnitude of
reported value

subCVal.mag.f

SV

Substituted value

subCVal.mag.f

SV

Substituted value

rangeC.hhLim.f

CF

U2HiHiLim

High High limit in % of UBase

rangeC.hLim.f

CF

U2HiLim

High limit in % of UBase

rangeC.lLim.f

CF

U2LowLim

Low limit in % of UBase

rangeC.llLim.f

CF

U2LowLowLim

Low Low limit in % of UBase

rangeC.max.f

CF

U2Max

Maximum value in % of UBase

rangeC.min.f

CF

U2Min

Minimum value in % of UBase

cVal.mag.f

MX

U2

Mon

U2 Amplitude, magnitude of
reported value

subCVal.mag.f

SV

Substituted value

range

MX

U2RANG

Mon

U2 Amplitude range

range

MX

U1RANG

Mon

U1 Amplitude range

range

MX

3U0RANG

Mon

3U0 Amplitude range

MX

U2

Mon

Quality: U2 Amplitude, magnitude


of reported value

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

329

Section 7
Logical node data model
DO name
SeqV

DO type
b_dSEQ

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

MX

U1

Mon

Quality: U1 Amplitude, magnitude


of reported value

MX

3U0

Mon

Quality: 3U0 Amplitude,


magnitude of reported value

MX

3U0

Mon

Timestamp: 3U0 Amplitude,


magnitude of reported value

MX

U1

Mon

Timestamp: U1 Amplitude,
magnitude of reported value

MX

U2

Mon

Timestamp: U2 Amplitude,
magnitude of reported value

subEna

SV

Enable substitution

subEna

SV

Enable substitution

subEna

SV

Enable substitution

db

CF

3U0DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

U2DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

db

CF

U1DbRepInt

Cycl: Report interval (s), Db: In %


of range, Int Db: In %s

7.10

Logical nodes for sensors and monitoring

7.10.1

Circuit breaker monitoring SCBR

7.10.1.1

Breaker monitoring SSCBR

Table 239:
DO name
Mod

LN type

LN prefix

LN class

Function block name

SSCBR (revision 3)

SCBR

SSCBR

SSCBR Logical node data


DO type
a_dINC

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

Table continues on next page

330

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Mod

Beh

InaTmdCnt

RmnLif

RsAccAPwr

RsCBWear

DO type

DA name

a_dINC

a_dINS

v1_dINS

v1_dINS

v1_dSPC

v1_dSPC

FC

Signal

Mon/
Cmd

Description

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

INADAYS

Mon

The number of days CB has been


inactive

ST

INADAYS

Mon

Quality: The number of days CB


has been inactive

ST

INADAYS

Mon

Timestamp: The number of days


CB has been inactive

stVal

ST

CBLIFEPH

Mon

CB Remaining life of respective


phase

ST

CBLIFEPH

Mon

Quality: CB Remaining life of


respective phase

ST

CBLIFEPH

Mon

Timestamp: CB Remaining life of


respective phase

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

331

Section 7
Logical node data model
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

RsCBWear

v1_dSPC

Oper.Check

CO

Cmd

Command parameter for


IEC61850

RsTrvTm

v1_dSPC

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

TRVTOPAL

Mon

CB open travel time exceeded set


value

ST

TRVTOPAL

Mon

Quality: CB open travel time


exceeded set value

ST

TRVTOPAL

Mon

Timestamp: CB open travel time


exceeded set value

stVal

ST

TRVTCLAL

Mon

CB close travel time exceeded


set value

ST

TRVTCLAL

Mon

Quality: CB close travel time


exceeded set value

ST

TRVTCLAL

Mon

Timestamp: CB close travel time


exceeded set value

stVal

ST

OPERALM

Mon

Number of CB operations
exceeds alarm limit

ST

OPERALM

Mon

Quality: Number of CB operations


exceeds alarm limit

ST

OPERALM

Mon

Timestamp: Number of CB
operations exceeds alarm limit

RsSprChaTm

OpnAlm

ClsAlm

OpNumAlm

v1_dSPC

v1_dSPS

v1_dSPS

v1_dSPS

Table continues on next page

332

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
OpNumLO

APwrAlm

APwrLO

LonTmAlm

SprChaAlm

PosOpn

PosIvd

PosCls

DO type

DA name

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

stVal

ST

OPERLO

Mon

Number of CB operations
exceeds lockout limit

ST

OPERLO

Mon

Quality: Number of CB operations


exceeds lockout limit

ST

OPERLO

Mon

Timestamp: Number of CB
operations exceeds lockout limit

stVal

ST

IPOWALPH

Mon

Accum I^CurrExponent integr


over CB open travel time exceeds
alarm limit

ST

IPOWALPH

Mon

Quality: Accum I^CurrExponent


integr over CB open travel time
exceeds alarm limit

ST

IPOWALPH

Mon

Timestamp: Accum
I^CurrExponent integr over CB
open travel time exceeds alarm
limit

stVal

ST

IPOWLOPH

Mon

Accum I^CurrExponent integr


over CB open travel time exceeds
lockout limit

ST

IPOWLOPH

Mon

Quality: Accum I^CurrExponent


integr over CB open travel time
exceeds lockout limit

ST

IPOWLOPH

Mon

Timestamp: Accum
I^CurrExponent integr over CB
open travel time exceeds lockout
limit

stVal

ST

MONALM

Mon

CB 'not operated for long time'


alarm

ST

MONALM

Mon

Quality: CB 'not operated for long


time' alarm

ST

MONALM

Mon

Timestamp: CB 'not operated for


long time' alarm

stVal

ST

SPCHALM

Mon

Spring charging time has crossed


the set value

ST

SPCHALM

Mon

Quality: Spring charging time has


crossed the set value

ST

SPCHALM

Mon

Timestamp: Spring charging time


has crossed the set value

stVal

ST

OPENPOS

Mon

CB is in open position

ST

OPENPOS

Mon

Quality: CB is in open position

ST

OPENPOS

Mon

Timestamp: CB is in open position

stVal

ST

INVDPOS

Mon

CB is in Invalid Position

ST

INVDPOS

Mon

Quality: CB is in Invalid Position

ST

INVDPOS

Mon

Timestamp: CB is in Invalid
Position

stVal

ST

CLOSEPOS

Mon

CB is in closed position

ST

CLOSEPOS

Mon

Quality: CB is in closed position

ST

CLOSEPOS

Mon

Timestamp: CB is in closed
position

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

333

Section 7
Logical node data model
DO name
CBLifAlm

PresLO

ColOpn

TmmsCls

TmmsOpn

TmsSprCha

AccAPwr

PresAlm

DO type
v1_dSPS

v1_dSPS

v1_dSPS

v2_dMV

v2_dMV

v2_dMV

v2_dMV

v3_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

stVal

ST

CBLIFEAL

Mon

Remaining life of CB reduced to


Life alarm level

ST

CBLIFEAL

Mon

Quality: Remaining life of CB


reduced to Life alarm level

ST

CBLIFEAL

Mon

Timestamp: Remaining life of CB


reduced to Life alarm level

stVal

ST

GPRESLO

Mon

Pressure below lockout level

ST

GPRESLO

Mon

Quality: Pressure below lockout


level

ST

GPRESLO

Mon

Timestamp: Pressure below


lockout level

stVal

ST

TRCMD

Mon

Open command issued to CB

ST

TRCMD

Mon

Quality: Open command issued


to CB

ST

TRCMD

Mon

Timestamp: Open command


issued to CB

mag.f

MX

TTRVCL

Mon

Travel time of the CB during


closing operation

MX

TTRVCL

Mon

Quality: Travel time of the CB


during closing operation

MX

TTRVCL

Mon

Timestamp: Travel time of the CB


during closing operation

mag.f

MX

TTRVOP

Mon

Travel time of the CB during


opening operation

MX

TTRVOP

Mon

Quality: Travel time of the CB


during opening operation

MX

TTRVOP

Mon

Timestamp: Travel time of the CB


during opening operation

mag.f

MX

SPCHT

Mon

The charging time of the CB spring

MX

SPCHT

Mon

Quality: The charging time of the


CB spring

MX

SPCHT

Mon

Timestamp: The charging time of


the CB spring

mag.f

MX

IPOWPH

Mon

Accumulated I^CurrExponent
integrated over CB open travel
time

MX

IPOWPH

Mon

Quality: Accumulated
I^CurrExponent integrated over
CB open travel time

MX

IPOWPH

Mon

Timestamp: Accumulated
I^CurrExponent integrated over
CB open travel time

stVal

ST

GPRESALM

Mon

Pressure below alarm level

ST

GPRESALM

Mon

Quality: Pressure below alarm


level

ST

GPRESALM

Mon

Timestamp: Pressure below


alarm level

Table continues on next page

334

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
OpCnt

DO type

DA name

v5_dINS

FC

Signal

Mon/
Cmd

Description

stVal

ST

NOOPER

Mon

Number of CB operation cycle

ST

NOOPER

Mon

Quality: Number of CB operation


cycle

ST

NOOPER

Mon

Timestamp: Number of CB
operation cycle

7.10.2

Insulation medium supervision (gas) SIMG

7.10.2.1

Gas medium supervision SSIMG

Table 240:
DO name
Mod

Beh

InsAlm

PresAlm

LN type

LN prefix

LN class

Function block name

SSIMG (revision 0)

SIMG

SSIMG

SSIMG Logical node data


DO type

DA name

a_dINC

a_dINS

a_dSPS

a_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

PRES_LO

Mon

Pressure below lockout level

ST

PRES_LO

Mon

Quality: Pressure below lockout


level

ST

PRES_LO

Mon

Timestamp: Pressure below


lockout level

stVal

ST

PRES_ALM

Mon

Pressure below alarm level

ST

PRES_ALM

Mon

Quality: Pressure below alarm


level

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

335

Section 7
Logical node data model
DO name

DO type

PresAlm

a_dSPS

TmpAlm

a_dSPS

Pres

Tmp

LORs

TmpLO

b_dMV

b_dMV

v1_dSPC

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

PRES_ALM

Mon

Timestamp: Pressure below


alarm level

stVal

ST

TEMP_ALM

Mon

Temperature above alarm level

ST

TEMP_ALM

Mon

Quality: Temperature above


alarm level

ST

TEMP_ALM

Mon

Timestamp: Temperature above


alarm level

mag.f

MX

PRESSURE

Mon

Pressure service value

MX

PRESSURE

Mon

Quality: Pressure service value

MX

PRESSURE

Mon

Timestamp: Pressure service


value

mag.f

MX

TEMP

Mon

Temperature of the insulation


medium

MX

TEMP

Mon

Quality: Temperature of the


insulation medium

MX

TEMP

Mon

Timestamp: Temperature of the


insulation medium

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

TEMP_LO

Mon

Temperature above lockout level

ST

TEMP_LO

Mon

Quality: Temperature above


lockout level

ST

TEMP_LO

Mon

Timestamp: Temperature above


lockout level

7.10.3

Insulation medium supervision (liquid) SIML

7.10.3.1

Liquid medium supervision SSIML

336

LN type

LN prefix

LN class

Function block name

SSIML (revision 0)

SIML

SSIML

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 241:
DO name
Mod

Beh

InsAlm

PresAlm

TmpAlm

Pres

Tmp

LORs

SSIML Logical node data


DO type

DA name

a_dINC

a_dINS

a_dSPS

a_dSPS

a_dSPS

b_dMV

b_dMV

v1_dSPC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

stVal

ST

LVL_LO

Mon

Level below lockout level

ST

LVL_LO

Mon

Quality: Level below lockout level

ST

LVL_LO

Mon

Timestamp: Level below lockout


level

stVal

ST

LVL_ALM

Mon

Level below alarm level

ST

LVL_ALM

Mon

Quality: Level below alarm level

ST

LVL_ALM

Mon

Timestamp: Level below alarm


level

stVal

ST

TEMP_ALM

Mon

Temperature above alarm level

ST

TEMP_ALM

Mon

Quality: Temperature above


alarm level

ST

TEMP_ALM

Mon

Timestamp: Temperature above


alarm level

mag.f

MX

LEVEL

Mon

Level service value

MX

LEVEL

Mon

Quality: Level service value

MX

LEVEL

Mon

Timestamp: Level service value

mag.f

MX

TEMP

Mon

Temperature of the insulation


medium

MX

TEMP

Mon

Quality: Temperature of the


insulation medium

MX

TEMP

Mon

Timestamp: Temperature of the


insulation medium

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

337

Section 7
Logical node data model
DO name
LORs

TmpLo

DO type
v1_dSPC

v1_dSPS

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

TEMP_LO

Mon

Temperature above lockout level

ST

TEMP_LO

Mon

Quality: Temperature above


lockout level

ST

TEMP_LO

Mon

Timestamp: Temperature above


lockout level

7.11

Logical nodes for switchgear

7.11.1

Circuit breaker XCBR

7.11.1.1

Circuit breaker SXCBR

Table 242:
DO name
Mod

Beh

Description

LN type

LN prefix

LN class

Function block name

SXCBR (revision 1)

XCBR

SXCBR

SXCBR Logical node data


DO type
a_dINC

a_dINS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

Table continues on next page


338

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
Beh

BlkCls

BlkOpn

Loc

OpCnt

DO type

DA name

a_dINS

a_dSPC

a_dSPC

a_dSPS

b_dINS

FC

Signal

Mon/
Cmd

Description

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Oper.ctlVal

CO

Cmd

Special block command value

Oper.origin.orCat

CO

Cmd

Special block command value

Oper.origin.orIdent

CO

Cmd

Special block command value

Oper.ctlNum

CO

Cmd

Special block command value

Oper.T

CO

Cmd

Special block command value

Oper.Test

CO

Cmd

Special block command value

Oper.Check

CO

Cmd

Special block command value

stVal

ST

CL_BLKD

Mon

Indication that the function is


blocked for close commands

ST

CL_BLKD

Mon

Quality: Indication that the


function is blocked for close
commands

ST

CL_BLKD

Mon

Timestamp: Indication that the


function is blocked for close
commands

Oper.ctlVal

CO

Cmd

Special block command value

Oper.origin.orCat

CO

Cmd

Special block command value

Oper.origin.orIdent

CO

Cmd

Special block command value

Oper.ctlNum

CO

Cmd

Special block command value

Oper.T

CO

Cmd

Special block command value

Oper.Test

CO

Cmd

Special block command value

Oper.Check

CO

Cmd

Special block command value

stVal

ST

OP_BLKD

Mon

Indication that the function is


blocked for open commands

ST

OP_BLKD

Mon

Quality: Indication that the


function is blocked for open
commands

ST

OP_BLKD

Mon

Timestamp: Indication that the


function is blocked for open
commands

stVal

ST

Mon

Indication that the function is in


local mode (process level)

ST

Mon

Quality: Indication that the


function is in local mode (process
level)

ST

Mon

Timestamp: Indication that the


function is in local mode (process
level)

stVal

ST

CNT_VAL

Mon

Operation counter value

ST

CNT_VAL

Mon

Quality: Operation counter value

ST

CNT_VAL

Mon

Timestamp: Operation counter


value

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

339

Section 7
Logical node data model
DO name
Pos

CBOpCap

BlkUpd

DO type
c_dDPC

h_dINS

v1_dSPC

DA name

1MRK 511 302-UEN -

FC

stVal

ST

POSITION

Mon

Apparatus position indication

ST

POSITION

Mon

Quality: Apparatus position


indication

ST

POSITION

Mon

Timestamp: Apparatus position


indication

subEna

SV

Substitute enable

subVal

SV

Substituted double position value

stVal

ST

CBOPCAP

Mon

Breaker operating capability 1 =


None, 2 = O, 3 = CO, 4 = OCO, 5
= COCO, 6+ = More

ST

CBOPCAP

Mon

Quality: Breaker operating


capability 1 = None, 2 = O, 3 =
CO, 4 = OCO, 5 = COCO, 6+ =
More

ST

CBOPCAP

Mon

Timestamp: Breaker operating


capability 1 = None, 2 = O, 3 =
CO, 4 = OCO, 5 = COCO, 6+ =
More

Oper.ctlVal

CO

Cmd

Special block command value

Oper.origin.orCat

CO

Cmd

Special block command value

Oper.origin.orIdent

CO

Cmd

Special block command value

Oper.ctlNum

CO

Cmd

Special block command value

Oper.T

CO

Cmd

Special block command value

Oper.Test

CO

Cmd

Special block command value

Oper.Check

CO

Cmd

Special block command value

stVal

ST

UPD_BLKD

Mon

Update of position indication is


blocked

ST

UPD_BLKD

Mon

Quality: Update of position


indication is blocked

ST

UPD_BLKD

Mon

Timestamp: Update of position


indication is blocked

7.11.2

Switch XSWI

7.11.2.1

Circuit switch SXSWI

340

Signal

Mon/
Cmd

LN type

LN prefix

LN class

Function block name

SXSWI (revision 1)

XSWI

SXSWI

Description

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

Table 243:
DO name
Mod

Beh

BlkCls

BlkOpn

SXSWI Logical node data


DO type

DA name

a_dINC

a_dINS

a_dSPC

a_dSPC

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

Mod

Cmd

Mode parameter for 61850

Oper.Test

CO

Mod

Cmd

Mode parameter for 61850

Oper.Check

CO

Mod

Cmd

Mode parameter for 61850

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter for 61850

ST

Beh

Mon

Quality: Behaviour parameter for


61850

ST

Beh

Mon

Timestamp: Behaviour parameter


for 61850

Oper.ctlVal

CO

Cmd

Special block command value

Oper.origin.orCat

CO

Cmd

Special block command value

Oper.origin.orIdent

CO

Cmd

Special block command value

Oper.ctlNum

CO

Cmd

Special block command value

Oper.T

CO

Cmd

Special block command value

Oper.Test

CO

Cmd

Special block command value

Oper.Check

CO

Cmd

Special block command value

stVal

ST

CL_BLKD

Mon

Indication that the function is


blocked for close commands

ST

CL_BLKD

Mon

Quality: Indication that the


function is blocked for close
commands

ST

CL_BLKD

Mon

Timestamp: Indication that the


function is blocked for close
commands

Oper.ctlVal

CO

Cmd

Special block command value

Oper.origin.orCat

CO

Cmd

Special block command value

Oper.origin.orIdent

CO

Cmd

Special block command value

Oper.ctlNum

CO

Cmd

Special block command value

Oper.T

CO

Cmd

Special block command value

Oper.Test

CO

Cmd

Special block command value

Oper.Check

CO

Cmd

Special block command value

stVal

ST

OP_BLKD

Mon

Indication that the function is


blocked for open commands

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

341

Section 7
Logical node data model
DO name
BlkOpn

Loc

OpCnt

Pos

SwOpCap

SwTyp

BlkUpd

DO type
a_dSPC

a_dSPS

b_dINS

c_dDPC

f_dINS

g_dINS

v1_dSPC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

OP_BLKD

Mon

Quality: Indication that the


function is blocked for open
commands

ST

OP_BLKD

Mon

Timestamp: Indication that the


function is blocked for open
commands

stVal

ST

Mon

Indication that the function is in


local mode (process level)

ST

Mon

Quality: Indication that the


function is in local mode (process
level)

ST

Mon

Timestamp: Indication that the


function is in local mode (process
level)

stVal

ST

CNT_VAL

Mon

Operation counter value

ST

CNT_VAL

Mon

Quality: Operation counter value

ST

CNT_VAL

Mon

Timestamp: Operation counter


value

stVal

ST

POSITION

Mon

Apparatus position indication

ST

POSITION

Mon

Quality: Apparatus position


indication

ST

POSITION

Mon

Timestamp: Apparatus position


indication

subEna

SV

Substitute enable

subVal

SV

Substituted double position value

stVal

ST

SWOPCAP

Mon

Switch operating capability 1 =


None, 2 = O, 3 = C, 4 = O and C

ST

SWOPCAP

Mon

Quality: Switch operating


capability 1 = None, 2 = O, 3 = C,
4 = O and C

ST

SWOPCAP

Mon

Timestamp: Switch operating


capability 1 = None, 2 = O, 3 = C,
4 = O and C

stVal

ST

Mon

1=LoadBreak,2=Disconnector,
3=EarthSw,
4=HighSpeedEarthSw

ST

Mon

Quality: 1=LoadBreak,
2=Disconnector,3=EarthSw,
4=HighSpeedEarthSw

ST

Mon

Timestamp: 1=LoadBreak,
2=Disconnector,3=EarthSw,
4=HighSpeedEarthSw

Oper.ctlVal

CO

Cmd

Special block command value

Oper.origin.orCat

CO

Cmd

Special block command value

Oper.origin.orIdent

CO

Cmd

Special block command value

Oper.ctlNum

CO

Cmd

Special block command value

Oper.T

CO

Cmd

Special block command value

Oper.Test

CO

Cmd

Special block command value

Table continues on next page


342

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
BlkUpd

DO type

DA name

v1_dSPC

FC

Signal

Mon/
Cmd

Description

Oper.Check

CO

Cmd

Special block command value

stVal

ST

UPD_BLKD

Mon

Update of position indication is


blocked

ST

UPD_BLKD

Mon

Quality: Update of position


indication is blocked

ST

UPD_BLKD

Mon

Timestamp: Update of position


indication is blocked

7.12

Logical nodes for power transformers

7.12.1

Tap changer YLTC

7.12.1.1

Tap changer control and supervision, 6 binary inputs TCMYLTC and


TCLYLTC

Table 244:
DO name
Mod

Beh

EndPosR

LN type

LN prefix

LN class

Function block name

TCMYLTC (revision 5)

TCM

YLTC

TCMYLTC

TCMYLTC Logical node data


DO type

DA name

a_dINC

a_dINS

a_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

HIPOSAL

Mon

Alarm for tap in highest volt


position

ST

HIPOSAL

Mon

Quality: Alarm for tap in highest


volt position

Table continues on next page


670 series 2.0 IEC
Communication Protocol Manual

343

Section 7
Logical node data model
DO name

DO type

EndPosR

a_dSPS

EndPosL

a_dSPS

TapChg

OpCnt

HiTapPos

LoTapPos

OpRs

CLRs

b_dBSC

b_dINS

b_dINS

b_dINS

v1_dSPC

v1_dSPC

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

ST

HIPOSAL

Mon

Timestamp: Alarm for tap in


highest volt position

stVal

ST

LOPOSAL

Mon

Alarm for tap in lowest volt position

ST

LOPOSAL

Mon

Quality: Alarm for tap in lowest


volt position

ST

LOPOSAL

Mon

Timestamp: Alarm for tap in


lowest volt position

valWTr.posVal

ST

TCPOS

Mon

Integer value corresponding to


actual tap position

valWTr.transInd

ST

Mon

Tap position change in progress

ST

TCPOS

Mon

Quality: Integer value


corresponding to actual tap
position

ST

TCPOS

Mon

Timestamp: Integer value


corresponding to actual tap
position

stVal

ST

CNT_VAL

Mon

Number of operations on tap


changer

ST

CNT_VAL

Mon

Quality: Number of operations on


tap changer

ST

CNT_VAL

Mon

Timestamp: Number of
operations on tap changer

stVal

ST

Mon

Tap position for highest voltage

ST

Mon

Quality: Tap position for highest


voltage

ST

Mon

Timestamp: Tap position for


highest voltage

stVal

ST

Mon

Tap position for lowest voltage

ST

Mon

Quality: Tap position for lowest


voltage

ST

Mon

Timestamp: Tap position for


lowest voltage

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for Local


HMI

Table continues on next page


344

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
CLRs

CmdFlt

ConvFlt

InvPosChg

TapChgFlt

TapPosFlt

DO type

DA name

v1_dSPC

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

FC

Signal

Mon/
Cmd

Description

Oper.origin.orCat

CO

Cmd

Command parameter for Local


HMI

Oper.origin.orIdent

CO

Cmd

Command parameter for Local


HMI

Oper.ctlNum

CO

Cmd

Command parameter for Local


HMI

Oper.T

CO

Cmd

Command parameter for Local


HMI

Oper.Test

CO

Cmd

Command parameter for Local


HMI

Oper.Check

CO

Cmd

Command parameter for Local


HMI

stVal

ST

CMDERRAL

Mon

Alarm for a command without an


expected position change

ST

CMDERRAL

Mon

Quality: Alarm for a command


without an expected position
change

ST

CMDERRAL

Mon

Timestamp: Alarm for a


command without an expected
position change

stVal

ST

CONVERR

Mon

General tap position conversion


error

ST

CONVERR

Mon

Quality: General tap position


conversion error

ST

CONVERR

Mon

Timestamp: General tap position


conversion error

stVal

ST

INVALPOS

Mon

Last position change was an


invalid change

ST

INVALPOS

Mon

Quality: Last position change was


an invalid change

ST

INVALPOS

Mon

Timestamp: Last position change


was an invalid change

stVal

ST

TCERRAL

Mon

Alarm for none or illegal tap


position change

ST

TCERRAL

Mon

Quality: Alarm for none or illegal


tap position change

ST

TCERRAL

Mon

Timestamp: Alarm for none or


illegal tap position change

stVal

ST

POSERRAL

Mon

Alarm that indicates a problem


with the position indication

ST

POSERRAL

Mon

Quality: Alarm that indicates a


problem with the position
indication

ST

POSERRAL

Mon

Timestamp: Alarm that indicates


a problem with the position
indication

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

345

Section 7
Logical node data model
DO name
CLCnt

DO type
v2_dMV

DA name

DO name
Mod

Beh

EndPosR

EndPosL

FC

Signal

Mon/
Cmd

Description

mag.f

MX

CLCNT_VAL

Mon

Remaining number of operations


at rated load

MX

CLCNT_VAL

Mon

Quality: Remaining number of


operations at rated load

MX

CLCNT_VAL

Mon

Timestamp: Remaining number


of operations at rated load

7.12.1.2

Table 245:

1MRK 511 302-UEN -

Tap changer control and supervision, 32 binary inputs TCLYLTC


LN type

LN prefix

LN class

Function block name

TCLYLTC (revision 5)

TCL

YLTC

TCLYLTC

TCLYLTC Logical node data


DO type
a_dINC

a_dINS

a_dSPS

a_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

Oper.ctlVal

CO

Mod

Cmd

Mode parameter

Oper.origin.orCat

CO

Mod

Cmd

Mode parameter

Oper.origin.orIdent

CO

Mod

Cmd

Mode parameter

Oper.ctlNum

CO

Mod

Cmd

Mode parameter

Oper.T

CO

Mod

Cmd

Mode parameter

Oper.Test

CO

Mod

Cmd

Mode parameter

Oper.Check

CO

Mod

Cmd

Mode parameter

stVal

ST

Mon

Mode status parameter for 61850

ST

Mon

Quality: Mode status parameter


for 61850

ST

Mon

Timestamp: Mode status


parameter for 61850

stVal

ST

Beh

Mon

Behaviour parameter

ST

Beh

Mon

Quality: Behaviour parameter

ST

Beh

Mon

Timestamp: Behaviour parameter

stVal

ST

HIPOSAL

Mon

Alarm for tap in highest volt


position

ST

HIPOSAL

Mon

Quality: Alarm for tap in highest


volt position

ST

HIPOSAL

Mon

Timestamp: Alarm for tap in


highest volt position

stVal

ST

LOPOSAL

Mon

Alarm for tap in lowest volt position

ST

LOPOSAL

Mon

Quality: Alarm for tap in lowest


volt position

ST

LOPOSAL

Mon

Timestamp: Alarm for tap in


lowest volt position

Table continues on next page

346

670 series 2.0 IEC


Communication Protocol Manual

Section 7
Logical node data model

1MRK 511 302-UEN -

DO name
TapChg

OpCnt

HiTapPos

LoTapPos

OpRs

CLRs

DO type

DA name

b_dBSC

b_dINS

b_dINS

b_dINS

v1_dSPC

v1_dSPC

FC

Signal

Mon/
Cmd

Description

valWTr.posVal

ST

TCPOS

Mon

Integer value corresponding to


actual tap position

valWTr.transInd

ST

Mon

Tap position change in progress

ST

TCPOS

Mon

Quality: Integer value


corresponding to actual tap
position

ST

TCPOS

Mon

Timestamp: Integer value


corresponding to actual tap
position

stVal

ST

CNT_VAL

Mon

Number of operations on tap


changer

ST

CNT_VAL

Mon

Quality: Number of operations on


tap changer

ST

CNT_VAL

Mon

Timestamp: Number of
operations on tap changer

stVal

ST

Mon

Tap position for highest voltage

ST

Mon

Quality: Tap position for highest


voltage

ST

Mon

Timestamp: Tap position for


highest voltage

stVal

ST

Mon

Tap position for lowest voltage

ST

Mon

Quality: Tap position for lowest


voltage

ST

Mon

Timestamp: Tap position for


lowest voltage

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

Oper.ctlVal

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orCat

CO

Cmd

Command parameter for


IEC61850

Oper.origin.orIdent

CO

Cmd

Command parameter for


IEC61850

Oper.ctlNum

CO

Cmd

Command parameter for


IEC61850

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

347

Section 7
Logical node data model
DO name
CLRs

CmdFlt

ConvFlt

InvPosChg

TapChgFlt

TapPosFlt

CLCnt

348

DO type
v1_dSPC

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v1_dSPS

v2_dMV

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

Oper.T

CO

Cmd

Command parameter for


IEC61850

Oper.Test

CO

Cmd

Command parameter for


IEC61850

Oper.Check

CO

Cmd

Command parameter for


IEC61850

stVal

ST

CMDERRAL

Mon

Alarm for a command without an


expected position change

ST

CMDERRAL

Mon

Quality: Alarm for a command


without an expected position
change

ST

CMDERRAL

Mon

Timestamp: Alarm for a


command without an expected
position change

stVal

ST

CONVERR

Mon

General tap position conversion


error

ST

CONVERR

Mon

Quality: General tap position


conversion error

ST

CONVERR

Mon

Timestamp: General tap position


conversion error

stVal

ST

INVALPOS

Mon

Last position change was an


invalid change

ST

INVALPOS

Mon

Quality: Last position change was


an invalid change

ST

INVALPOS

Mon

Timestamp: Last position change


was an invalid change

stVal

ST

TCERRAL

Mon

Alarm for none or illegal tap


position change

ST

TCERRAL

Mon

Quality: Alarm for none or illegal


tap position change

ST

TCERRAL

Mon

Timestamp: Alarm for none or


illegal tap position change

stVal

ST

POSERRAL

Mon

Alarm that indicates a problem


with the position indication

ST

POSERRAL

Mon

Quality: Alarm that indicates a


problem with the position
indication

ST

POSERRAL

Mon

Timestamp: Alarm that indicates


a problem with the position
indication

mag.f

MX

CLCNT_VAL

Mon

Remaining number of operations


at rated load

MX

CLCNT_VAL

Mon

Quality: Remaining number of


operations at rated load

MX

CLCNT_VAL

Mon

Timestamp: Remaining number


of operations at rated load

670 series 2.0 IEC


Communication Protocol Manual

Section 8
GOOSE receive blocks

1MRK 511 302-UEN -

Section 8

GOOSE receive blocks

8.1

Interlock receive - INTLKRCV

8.1.1

Horizontal communication via GOOSE for interlocking


GOOSEINTLKRCV

Table 246:
DO name
TagApp1

LN type

LN prefix

LN class

Function block name

INTGREC instance 1 (revision 0)

INT

GREC

GOOSEINTLKRCV

GOOSEINTLKRCV Logical node data (instance 1)


DO type

DA name

a_dDPS

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

ST

Mon

Quality: Internal parameter tag to


handle 61850 mapping

TagApp2

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp3

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp4

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp5

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp6

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp7

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp8

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp9

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp10

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp11

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp12

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp13

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

349

Section 8
GOOSE receive blocks
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

TagApp14

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagApp15

a_dDPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagReservR

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagReservG

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

8.2

Binary Receive - BINRCV

8.2.1

Goose binary receive GOOSEBINRCV

Table 247:
DO name
TagBinOut1

TagBinOut2

LN type

LN prefix

LN class

Function block name

BINGREC instance 1 (revision 0)

BIN

GREC

GOOSEBINRCV

GOOSEBINRCV Logical node data (instance 1)


DO type
a_dSPS

a_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

ST

Mon

Quality: Internal parameter tag to


handle 61850 mapping

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

ST

Mon

Quality: Internal parameter tag to


handle 61850 mapping

TagBinOut3

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOut4

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOut5

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOut6

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOut7

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOut8

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOut9

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOu10

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

Table continues on next page

350

670 series 2.0 IEC


Communication Protocol Manual

Section 8
GOOSE receive blocks

1MRK 511 302-UEN -

DO name

DO type

DA name

FC

Signal

Mon/
Cmd

Description

TagBinOu11

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOu12

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOu13

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOu14

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOu15

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

TagBinOu16

a_dSPS

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

8.3

VCTR Receive - VCTRRCV

8.3.1

Voltage control receiving block for GOOSE


GOOSEVCTRRCV

Table 248:
DO name
In_LodAIm

In_LodARe

In_BusV

LN type

LN prefix

LN class

Function block name

VCTRGREC instance 1 (revision 0)

VCTR

GREC

GOOSEVCTRRCV

GOOSEVCTRRCV Logical node data (instance 1)


DO type

DA name

V10_dMV

V11_dMV

V12_dMV

FC

Signal

Mon/
Cmd

Description

mag.f

MX

Mon

Imaginary part of load current


(horizontal communication)

MX

Mon

Quality: Imaginary part of load


current (horizontal
communication)

MX

Mon

Timestamp: Imaginary part of


load current (horizontal
communication)

mag.f

MX

Mon

Real part of load current


(horizontal communication)

MX

Mon

Quality: Real part of load current


(horizontal communication)

MX

Mon

Timestamp: Real part of load


current (horizontal
communication)

mag.f

MX

Mon

Busbar voltage (horizontal


communication)

MX

Mon

Quality: Busbar voltage


(horizontal communication)

Table continues on next page

670 series 2.0 IEC


Communication Protocol Manual

351

Section 8
GOOSE receive blocks
DO name

DO type

DA name

1MRK 511 302-UEN -

FC

Signal

Mon/
Cmd

Description

In_BusV

V12_dMV

MX

Mon

Timestamp: Busbar voltage


(horizontal communication)

In_SetV

V13_dMV

mag.f

MX

Mon

Voltage setpoint (horizontal


communication)

MX

Mon

Quality: Voltage setpoint


(horizontal communication)

MX

Mon

Timestamp: Voltage setpoint


(horizontal communication)

mag.f

MX

Mon

Relative tap position (horizontal


communication)

MX

Mon

Quality: Relative tap position


(horizontal communication)

MX

Mon

Timestamp: Relative tap position


(horizontal communication)

mag.f

MX

Mon

Transformer reactance secondary


side (horizontal communication)

MX

Mon

Quality: Transformer reactance


secondary side (horizontal
communication)

MX

Mon

Timestamp: Transformer
reactance secondary side
(horizontal communication)

stVal

ST

Mon

VCTR Control word (horizontal


communication)

ST

Mon

Quality: VCTR Control word


(horizontal communication)

ST

Mon

Timestamp: VCTR Control word


(horizontal communication)

In_PosRel

In_X2

In_status

V14_dMV

V15_dMV

V6_dINS

8.4

Double point Receive (DP) - DPRCV

8.4.1

GOOSE function block to receive a double point value


GOOSEDPRCV

Table 249:
DO name
TagDPOut

352

LN type

LN prefix

LN class

Function block name

DPGREC instance 1 (revision 0)

DP

GREC

GOOSEDPRCV

GOOSEDPRCV Logical node data (instance 1)


DO type
a_dDPS

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

ST

Mon

Quality: Internal parameter tag to


handle 61850 mapping

670 series 2.0 IEC


Communication Protocol Manual

Section 8
GOOSE receive blocks

1MRK 511 302-UEN -

8.5

Integer Receive - INTRCV

8.5.1

GOOSE function block to receive an integer value


GOOSEINTRCV

Table 250:
DO name
TagIntOut

LN type

LN prefix

LN class

Function block name

INTSGREC instance 1 (revision 0)

INTS

GREC

GOOSEINTRCV

GOOSEINTRCV Logical node data (instance 1)


DO type

DA name

l_dINS

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

ST

Mon

Quality: Internal parameter tag to


handle 61850 mapping

8.6

Measured Value Receive - MVRCV

8.6.1

GOOSE function block to receive a measurand value


GOOSEMVRCV

Table 251:
DO name
TagMVOut

LN type

LN prefix

LN class

Function block name

MVGREC instance 1 (revision 0)

MV

GREC

GOOSEMVRCV

GOOSEMVRCV Logical node data (instance 1)


DO type

DA name

a_dMV

FC

Signal

Mon/
Cmd

Description

mag.f

MX

Mon

Internal parameter tag to handle


61850 mapping

MX

Mon

Quality: Internal parameter tag to


handle 61850 mapping

8.7

Single Point Receive (SP) - SPRCV

8.7.1

GOOSE function block to receive a single point value


GOOSESPRCV

670 series 2.0 IEC


Communication Protocol Manual

LN type

LN prefix

LN class

Function block name

BINSGREC instance 1 (revision 0)

BINS

GREC

GOOSESPRCV

353

Section 8
GOOSE receive blocks

Table 252:
DO name
TagBinOut

354

1MRK 511 302-UEN -

GOOSESPRCV Logical node data (instance 1)


DO type
a_dSPS

DA name

FC

Signal

Mon/
Cmd

Description

stVal

ST

Mon

Internal parameter tag to handle


61850 mapping

ST

Mon

Quality: Internal parameter tag to


handle 61850 mapping

670 series 2.0 IEC


Communication Protocol Manual

Section 9
Glossary

1MRK 511 302-UEN -

Section 9

Glossary

9.1

Glossary

670 series 2.0 IEC


Communication Protocol Manual

AC

Alternating current

ACC

Actual channel

ACT

Application configuration tool within PCM600

A/D converter

Analog-to-digital converter

ADBS

Amplitude deadband supervision

ADM

Analog digital conversion module, with time


synchronization

AI

Analog input

ANSI

American National Standards Institute

AR

Autoreclosing

ASCT

Auxiliary summation current transformer

ASD

Adaptive signal detection

ASDU

Application service data unit

AWG

American Wire Gauge standard

BBP

Busbar protection

BFOC/2,5

Bayonet fibre optic connector

BFP

Breaker failure protection

BI

Binary input

BIM

Binary input module

BOM

Binary output module

BOS

Binary outputs status

BR

External bistable relay

BS

British Standards

BSR

Binary signal transfer function, receiver blocks

BST

Binary signal transfer function, transmit blocks

C37.94

IEEE/ANSI protocol used when sending binary signals


between IEDs

CAN

Controller Area Network. ISO standard (ISO 11898) for


serial communication
355

Section 9
Glossary

356

1MRK 511 302-UEN -

CB

Circuit breaker

CBM

Combined backplane module

CCITT

Consultative Committee for International Telegraph and


Telephony. A United Nations-sponsored standards body
within the International Telecommunications Union.

CCM

CAN carrier module

CCVT

Capacitive Coupled Voltage Transformer

Class C

Protection Current Transformer class as per IEEE/ ANSI

CMPPS

Combined megapulses per second

CMT

Communication Management tool in PCM600

CO cycle

Close-open cycle

Codirectional

Way of transmitting G.703 over a balanced line. Involves


two twisted pairs making it possible to transmit
information in both directions

COM

Command

COMTRADE

Standard Common Format for Transient Data Exchange


format for Disturbance recorder according to IEEE/ANSI
C37.111, 1999 / IEC60255-24

Contra-directional

Way of transmitting G.703 over a balanced line. Involves


four twisted pairs, two of which are used for transmitting
data in both directions and two for transmitting clock signals

COT

Cause of transmission

CPU

Central processing unit

CR

Carrier receive

CRC

Cyclic redundancy check

CROB

Control relay output block

CS

Carrier send

CT

Current transformer

CU

Communication unit

CVT or CCVT

Capacitive voltage transformer

DAR

Delayed autoreclosing

DARPA

Defense Advanced Research Projects Agency (The US


developer of the TCP/IP protocol etc.)

DBDL

Dead bus dead line

DBLL

Dead bus live line

DC

Direct current

DFC

Data flow control


670 series 2.0 IEC
Communication Protocol Manual

Section 9
Glossary

1MRK 511 302-UEN -

670 series 2.0 IEC


Communication Protocol Manual

DFT

Discrete Fourier transform

DHCP

Dynamic Host Configuration Protocol

DIP-switch

Small switch mounted on a printed circuit board

DI

Digital input

DLLB

Dead line live bus

DNP

Distributed Network Protocol as per IEEE Std 1815-2012

DR

Disturbance recorder

DRAM

Dynamic random access memory

DRH

Disturbance report handler

DSP

Digital signal processor

DTT

Direct transfer trip scheme

EHV network

Extra high voltage network

EIA

Electronic Industries Association

EMC

Electromagnetic compatibility

EMF

Electromotive force

EMI

Electromagnetic interference

EnFP

End fault protection

EPA

Enhanced performance architecture

ESD

Electrostatic discharge

F-SMA

Type of optical fibre connector

FAN

Fault number

FCB

Flow control bit; Frame count bit

FOX 20

Modular 20 channel telecommunication system for speech,


data and protection signals

FOX 512/515

Access multiplexer

FOX 6Plus

Compact time-division multiplexer for the transmission of


up to seven duplex channels of digital data over optical fibers

FUN

Function type

G.703

Electrical and functional description for digital lines used


by local telephone companies. Can be transported over
balanced and unbalanced lines

GCM

Communication interface module with carrier of GPS


receiver module

GDE

Graphical display editor within PCM600

GI

General interrogation command

GIS

Gas-insulated switchgear
357

Section 9
Glossary

358

1MRK 511 302-UEN -

GOOSE

Generic object-oriented substation event

GPS

Global positioning system

GSAL

Generic security application

GSM

GPS time synchronization module

GTM

GPS Time Module

HDLC protocol

High-level data link control, protocol based on the HDLC


standard

HFBR connector
type

Plastic fiber connector

HMI

Human-machine interface

HSAR

High speed autoreclosing

HV

High-voltage

HVDC

High-voltage direct current

ICT

Installation and Commissioning Tool for injection based


protection in REG670

IDBS

Integrating deadband supervision

IEC

International Electrical Committee

IEC 60044-6

IEC Standard, Instrument transformers Part 6:


Requirements for protective current transformers for
transient performance

IEC 60870-5-103

Communication standard for protection equipment. A


serial master/slave protocol for point-to-point
communication

IEC 61850

Substation automation communication standard

IEC 6185081

Communication protocol standard

IEEE

Institute of Electrical and Electronics Engineers

IEEE 802.12

A network technology standard that provides 100 Mbits/s


on twisted-pair or optical fiber cable

IEEE P1386.1

PCI Mezzanine Card (PMC) standard for local bus


modules. References the CMC (IEEE P1386, also known
as Common Mezzanine Card) standard for the mechanics
and the PCI specifications from the PCI SIG (Special
Interest Group) for the electrical EMF (Electromotive force).

IEEE 1686

Standard for Substation Intelligent Electronic Devices


(IEDs) Cyber Security Capabilities

IED

Intelligent electronic device

I-GIS

Intelligent gas-insulated switchgear

IOM

Binary input/output module


670 series 2.0 IEC
Communication Protocol Manual

Section 9
Glossary

1MRK 511 302-UEN -

670 series 2.0 IEC


Communication Protocol Manual

Instance

When several occurrences of the same function are


available in the IED, they are referred to as instances of
that function. One instance of a function is identical to
another of the same kind but has a different number in the
IED user interfaces. The word "instance" is sometimes
defined as an item of information that is representative of a
type. In the same way an instance of a function in the IED
is representative of a type of function.

IP

1. Internet protocol. The network layer for the TCP/IP


protocol suite widely used on Ethernet networks. IP is a
connectionless, best-effort packet-switching protocol. It
provides packet routing, fragmentation and reassembly
through the data link layer.
2. Ingression protection, according to IEC 60529

IP 20

Ingression protection, according to IEC 60529, level 20

IP 40

Ingression protection, according to IEC 60529, level 40

IP 54

Ingression protection, according to IEC 60529, level 54

IRF

Internal failure signal

IRIG-B:

InterRange Instrumentation Group Time code format B,


standard 200

ITU

International Telecommunications Union

LAN

Local area network

LIB 520

High-voltage software module

LCD

Liquid crystal display

LDCM

Line differential communication module

LDD

Local detection device

LED

Light-emitting diode

LNT

LON network tool

LON

Local operating network

MCB

Miniature circuit breaker

MCM

Mezzanine carrier module

MIM

Milli-ampere module

MPM

Main processing module

MVAL

Value of measurement

MVB

Multifunction vehicle bus. Standardized serial bus


originally developed for use in trains.

NCC

National Control Centre

NOF

Number of grid faults


359

Section 9
Glossary

360

1MRK 511 302-UEN -

NUM

Numerical module

OCO cycle

Open-close-open cycle

OCP

Overcurrent protection

OEM

Optical Ethernet module

OLTC

On-load tap changer

OTEV

Disturbance data recording initiated by other event than


start/pick-up

OV

Overvoltage

Overreach

A term used to describe how the relay behaves during a


fault condition. For example, a distance relay is
overreaching when the impedance presented to it is smaller
than the apparent impedance to the fault applied to the
balance point, that is, the set reach. The relay sees the
fault but perhaps it should not have seen it.

PCI

Peripheral component interconnect, a local data bus

PCM

Pulse code modulation

PCM600

Protection and control IED manager

PC-MIP

Mezzanine card standard

PMC

PCI Mezzanine card

POR

Permissive overreach

POTT

Permissive overreach transfer trip

Process bus

Bus or LAN used at the process level, that is, in near


proximity to the measured and/or controlled components

PSM

Power supply module

PST

Parameter setting tool within PCM600

PT ratio

Potential transformer or voltage transformer ratio

PUTT

Permissive underreach transfer trip

RASC

Synchrocheck relay, COMBIFLEX

RCA

Relay characteristic angle

RISC

Reduced instruction set computer

RMS value

Root mean square value

RS422

A balanced serial interface for the transmission of digital


data in point-to-point connections

RS485

Serial link according to EIA standard RS485

RTC

Real-time clock

RTU

Remote terminal unit

SA

Substation Automation
670 series 2.0 IEC
Communication Protocol Manual

Section 9
Glossary

1MRK 511 302-UEN -

670 series 2.0 IEC


Communication Protocol Manual

SBO

Select-before-operate

SC

Switch or push button to close

SCL

Short circuit location

SCS

Station control system

SCADA

Supervision, control and data acquisition

SCT

System configuration tool according to standard IEC 61850

SDU

Service data unit

SLM

Serial communication module.

SMA connector

Subminiature version A, A threaded connector with


constant impedance.

SMT

Signal matrix tool within PCM600

SMS

Station monitoring system

SNTP

Simple network time protocol is used to synchronize


computer clocks on local area networks. This reduces the
requirement to have accurate hardware clocks in every
embedded system in a network. Each embedded node can
instead synchronize with a remote clock, providing the
required accuracy.

SOF

Status of fault

SPA

Strmberg Protection Acquisition (SPA), a serial master/


slave protocol for point-to-point communication

SRY

Switch for CB ready condition

ST

Switch or push button to trip

Starpoint

Neutral point of transformer or generator

SVC

Static VAr compensation

TC

Trip coil

TCS

Trip circuit supervision

TCP

Transmission control protocol. The most common


transport layer protocol used on Ethernet and the Internet.

TCP/IP

Transmission control protocol over Internet Protocol. The


de facto standard Ethernet protocols incorporated into
4.2BSD Unix. TCP/IP was developed by DARPA for
Internet working and encompasses both network layer and
transport layer protocols. While TCP and IP specify two
protocols at specific protocol layers, TCP/IP is often used
to refer to the entire US Department of Defense protocol
suite based upon these, including Telnet, FTP, UDP and
RDP.

TEF

Time delayed earth-fault protection function


361

Section 9
Glossary

1MRK 511 302-UEN -

TM

Transmit (disturbance data)

TNC connector

Threaded Neill-Concelman, a threaded constant impedance


version of a BNC connector

TP

Trip (recorded fault)

TPZ, TPY, TPX, TPS Current transformer class according to IEC

362

TRM

Transformer Module. This module transforms currents and


voltages taken from the process into levels suitable for
further signal processing.

TYP

Type identification

UMT

User management tool

Underreach

A term used to describe how the relay behaves during a


fault condition. For example, a distance relay is
underreaching when the impedance presented to it is
greater than the apparent impedance to the fault applied to
the balance point, that is, the set reach. The relay does not
see the fault but perhaps it should have seen it. See also
Overreach.

UTC

Coordinated Universal Time. A coordinated time scale,


maintained by the Bureau International des Poids et
Mesures (BIPM), which forms the basis of a coordinated
dissemination of standard frequencies and time signals.
UTC is derived from International Atomic Time (TAI) by
the addition of a whole number of "leap seconds" to
synchronize it with Universal Time 1 (UT1), thus allowing
for the eccentricity of the Earth's orbit, the rotational axis
tilt (23.5 degrees), but still showing the Earth's irregular
rotation, on which UT1 is based. The Coordinated
Universal Time is expressed using a 24-hour clock, and
uses the Gregorian calendar. It is used for aeroplane and
ship navigation, where it is also sometimes known by the
military name, "Zulu time." "Zulu" in the phonetic
alphabet stands for "Z", which stands for longitude zero.

UV

Undervoltage

WEI

Weak end infeed logic

VT

Voltage transformer

X.21

A digital signalling interface primarily used for telecom


equipment

3IO

Three times zero-sequence current.Often referred to as the


residual or the earth-fault current

3UO

Three times the zero sequence voltage. Often referred to as


the residual voltage or the neutral point voltage

670 series 2.0 IEC


Communication Protocol Manual

363

ABB AB
Substation Automation Products
SE-721 59 Vsters, Sweden
Phone
+46 (0) 21 32 50 00
Fax
+46 (0) 21 14 69 18
www.abb.com/substationautomation

1MRK 511 302-UEN - Copyright 2014 ABB. All rights reserved.