Sepam Series 80 Undervoltage
Sepam Series 80 Undervoltage
Sepam Series 80 Undervoltage
Phase-to-phase voltage
Operation
DE50334
This function gives the RMS value of the fundamental 50 Hz or 60 Hz component of:
b the main phase-to-phase voltages:
v ( U21 = V1 V2 ) , voltage between phases 2 and 1
v ( U32 = V2 V3 ) , voltage between phases 3 and 2
v ( U13 = V3 V1 ) , voltage between phases 1 and 3.
DE50333
Readout
The measurements may be accessed via:
b the Sepam display via the
key
b the display of a PC with the SFT2841 software
b the communication link
b an analog converter with the MSA141 option.
1-3-2 network: phase-to-neutral and phase-to-phase voltages.
Characteristics
Measurement range
Units
Resolution
Accuracy
Display format
Refresh interval
(1) Un rated current set in the general settings.
(2) At Unp, under reference conditions (IEC 60255-6).
SEPED303001EN - 01/2013
31
Metering functions
Phase-to-neutral voltage
Operation
This function gives the RMS value of the fundamental 50 Hz or 60 Hz component of:
b the main phase-to-neutral voltages V1, V2, V3 measured on phases 1, 2 and 3
b the additional phase-to-neutral voltages V'1, V'2 and V'3 measured on phases 1,
2 and 3.
Readout
The measurements may be accessed via:
b the Sepam display via the
key
b the display of a PC with the SFT2841 software
b the communication link
b an analog converter with the MSA141 option.
Characteristics
0.05 to 1.2 Vnp (1)
V or kV
1V
0.5 % typical (2) main channels
1 % typical (2) additional channels
1 % from 0.5 to 1.2 Vnp
2 % from 0.06 to 0.5 Vnp
Display format
3 significant digits
Refresh interval
1 second (typical)
(1) Vnp: primary rated phase-to-neutral voltage (Vnp = Unp/3).
(2) At Vnp, under reference conditions (IEC 60255-6).
Measurement range
Units
Resolution
Accuracy
32
SEPED303001EN - 01/2013
Block diagram
DE51543
Protection functions
Operation
Protection against voltage dips or detection of
abnormally low voltage in order to:
b Trigger automatic load shedding
b Trigger a source transfer
b Disconnect a generator, in conformity with a "Grid
code".
It includes a time delay T with:
b definite time (DT)
b inverse definite minimum time (see the tripping curve
equation on page 226)
b definite time with a curve T(U/Un) that can be
customized point by point.
Whether operation is phase-to-neutral or phase-tophase voltage depends on the connection chosen for
the voltage inputs.
Characteristics
Settings
Measurement origin
Setting range
U/Un
DE81252
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
Accuracy (1)
2 % or 0,005 Unp
Resolution
1%
Drop-out/pick-up ratio
103 % 2 %
Time delay T (tripping time for zero voltage)
Setting range
50 ms to 300 s
Accuracy (1)
2 % or 25 ms
Resolution
10 ms or 1 digit
0.5
1.5
Tc in sec
Overshoot time
Reset time
Connection conditions
Connection type
Characteristic times
Operating time
YES
U21, U32
Designation
U21 (1)
NO
On U21
only
Syntax
Equations Logipam
NO
Reset protection
P27_x_101 b
YES
Inhibit protection
P27_x_113 b
Outputs
Designation
Connection type
Operation in phase-toneutral voltage
Operation in phase-tophase voltage
Inputs
Operation in
phase-to-neutral voltage
Operation in
YES
phase-to-phase voltage
96
V1 (1)
On V1
NO
only
Syntax
Equations Logipam
Matrix
P27_x_1
P27_x_3
b
b
b
b
Phase 1 fault
P27_x_7
b
Phase 2 fault (2)
P27_x_8
b
Phase 3 fault (2)
P27_x_9
b
Protection inhibited
P27_x_16 b
Instantaneous output V1 or U21
P27_x_23 b
Instantaneous output V2 or U32
P27_x_24 b
Instantaneous output V3 or U13
P27_x_25 b
Delayed output V1 or U21
P27_x_26 b
Delayed output V2 or U32
P27_x_27 b
Delayed output V3 or U13
P27_x_28 b
x: Unit number.
(1) Under reference conditions (IEC 60255-6).
(2) When the protection in used is phase-to-neutral voltage.
b
b
b
b
b
b
b
b
b
b
SEPED303001EN - 01/2013