Auto Fire Detection, Alarm and Suppression System

Sl
Item
1 Suppression Agent (Gas)
Brand
Origin of the Brand
Composition:
Purity (%)
Classification of Fire
Safe Human Expose Time
Discharge Time
Storage Pressure
Type
Molecular Weight
Boiling Point
Critical Temperature, C
Critical Pressure, kPa
Critical Density, kg/m3
Vapor Pressure @ 20 C, bar
Freezing Point, C
Viscosity of Liquid
Solubility of Water in Agent
Specific Heat of Liquid
Heat of Vaporization
Certification and Listing
2 Cylinder
Brand
Origin of the Brand
Specification

3 Accessories for Cylinder


(as required)

4 Nozzle
5 Control Panel
Brand
Origin of the Brand
Zone
Working Method

Indicators

Switch

Delay Discharge Timer


Power Supply Input
Operating / System
Charger
Cabinet
Test Class
6 Battery
7 Heat Detector
Brand
Origin of the Brand
Supply Voltage
Alarm Indication
Alarm Current
8 Smoke Detector
Brand
Origin of the Brand
Supply Voltage
Alarm Indication
Alarm Current
9 Flashing Light
10 Alarm Bell

11 Call Point
12 Gas Discharge Sign
13 Caution Sign

14 Accessories for suppression


Channel (as required)

15 Installation

arm and Suppression System


Description of Items
Suppression Agent
NAF S 125
Safety Hi-Tech
Italy
HFC-125 + 0.15% of Limonene
99.99
A, B, C and Electrical Fire.
5 min
10 sec
42 bar
Clean Agent Suppression System
00:02.0
@ 760 mm Hg, C : -48.5
: 66.0
: 3618
: 574
: 13.5
: -102.8
@ 25 C, centipoises: 0.140
@ 21 C, % by weight: 0.07
@ 25 C, kJ/kg C : 1.407
'@ Boiling Point at 25C, kJ/kg : 164.7
UL Recognized and US EPA SNAP Listed gaseous extinguishing agent
Cylinder for NAF S 125
Safety Hi-Tech
Italy
Seamless storage containers having a working pressure of 42 bar and
a test pressure from 150 bar to 300 bar
Each Cylinder Assembly includes storage container, valve, flange and
dip tube. Units combined with accessories (hoses, NRV, actuators and
pneumatic components) can be used as modular (one cylinder) or
centralized (multiple cylinders) system.

UL Listed
67.5 Liter Cylinder
Cylinder Back Rack
Cylinder Front Strap
Pressure Gauge
Cheek Valve
Manual Actuator

Aluminum Dip Tube


Actuator Block inch TEDEM +SOLENOID
Connection Hose/Pilot Hose
Steel Nozzle 360, Size "-1"
DETECTION SYSTEM (Fire suppression Zone)
Extinguishing Area Control Panel with Gas release
Program
Malaysia
2 Detection Zone, 1 Extingushing Area
The gas discharge can be automatic using double knock detections or
manual using electrical key switch.
Power Source, Power Failure, Zone Fire, Fault and Isolate, Bell Isolate,
Auxiliary Trip Isolate, Gas Isolate.
Bell Isolate, Auxiliary Trip Isolate, Gas Isolate, Fault Buzzer Mute,
Master Reset, Main on/off, Test Battery.
Built-in and Adjustable
240V AC 50Hz
24V DC
Auto / Trickle
The system is housed in a compact enclosure, finished with signal red
epoxy powder paint.
EN 54-2 or MS 1745-2
Rechargeable Seal Lead-Acid Battery for control panel, 12V each 7.2 ah
Conventional Heat Detector
Apollo
UK
9to 33V
Red LED
52mA, at 24V
Photo Electric Smoke Detector.
Apollo
UK
9to 33V
Red LED, Flashing LED
52mA, at 24V
Flashing light
Output: 1Meter@95dBA, 3Meter@92dBA, Current Consumption :
25mA, Dimensions: 6.
Manual Release or Break Glass
Gas Discharge Sign
Caution Sign

Mechanical and Electrical fittings


Schedule 40 pipe 1" Dia, Korea
Schedule 40 pipe 1" Dia, Korea
Schedule 40 pipe " Dia, Korea
Schedule 40 pipe " Dia, Korea
Fire resistance cable, BRB
Best Quality Local Painting, Berger or equivalent
PVC Pipe " conduit, fittings
Others
Installation
Installation, Detection Testing, Commissioning