R2 Consolidated Geotech Report-12.03.15

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 73

GEOTECHNICAL INVESTIGATION REPORT

FOR
ALL BOREHOLE

Client

KITCO LIMITED
KERALA

Project

PROPOSED CONSTRUCTION OF GENX/GE90 ENGINE


OVERHAUL WORKSHOP AT AIR INDIA MRO, MIHAN SEZ,
NAGPUR

Recognized by Ministry of Environment & Forest (MoEF)


An ISO 9001:2008 & ISO 18001 :2007 Certified

At KM Stone 16.5km, Near Hotel Shahenshah,,


Amravati Road, Waddhamana, Nagpur-23
Ph-0712-2542261, Email-nilawarlabs@gmail.com

INDEX
Sr.
No.

Particulars

Page No.
From

To

1.

Geotechnical Investigation Report

01

21

2.

CBR Graphs

22

23

3.

Borelogs

24

30

4.

Laboratory Test Sheet

31

31

5.

Chemicals Test Sheet

32

32

6.

Pile calculations & observation sheet

33

37

7.

Grain Size Analysis Graphs

38

44

8.

Triaxial Test Graphs

45

51

9.

Direct Shear Graphs

52

59

10.

e-Log Graphs

60

66

11.

Borehole Photos

67

70

12.

Borehole Location Map

71

71

KITCO LIMITED

Nilawar Laboratories

Geo-Technical Investigation Report


1.0.0 Introduction
Extensive soil investigation is carried out for proposed construction of
GENX/GE90 Engine Overhaul Workshop at Air India MRO, MIHAN SEZ, Nagpur
for KITCO LIMITED to study the stratification and making classification of
physical properties of the soils. On the basis of this study, foundation can be
classified. The laboratory testing carried out by us, and deals with the
aspects relating to classification of soils and stratification.

2.0.0 General Discussion.


Nilawar Laboratories has carried out the entire scope of work of Geo-technical
investigations based on the investigation plan, specifications and data
requirements of KITCO LIMITED.

3.0.0 SCOPE OF GEO-TECHNICAL INVESTIGATION :


The geo-technical investigation programme is drawn by KITCO LIMITED. for
this project envisages obtaining sufficient data regarding the engineering
properties of soil for different soil strata. The relevant data regarding sub-soil
profile is to be generated for all kinds of strata at investigation location by
drilling boreholes up to relevant depths.

3.1.0 Scope of work as covered KITCO LIMITED includes the following;

To identify the soil stratification up to recommended depth by sinking


borehole at each location. All boreholes locations were approved by the
Engineer-in-Charge.

To conduct standard penetration tests (SPT) at various depths in boreholes,


generally at 1.5m intervals up to terminated depth and to collect
representative samples.

Collect disturbed samples from boreholes generally at 1.5m intervals or at


every change of stratum in cohesive and semi-cohesive soils.

Document Name: Geo Technical Investigation Report


Page-1

KITCO LIMITED

Nilawar Laboratories

Extract undisturbed samples from boreholes generally at 1.5m intervals or


at every change of stratum in cohesive and semi-cohesive soils.

To record standing ground water levels in boreholes.

To conduct laboratory tests on undisturbed, disturbed and SPT soil samples


to obtain strength, classification and other parameters as per Technical
Specifications.

To collect rock sample, record core recovery percentage and RQD if rock
encountered.

To carryout following tests on the DS & UDS samples at Laboratory.

i)

Natural moisture content Bulk and Dry Density

ii)

Void ratio

iii)

Liquid limit, plastic limit and plasticity index.

iv)

Specific gravity

v)

Bulk and Dry Density

vi)

Direct shear test

vii)

Swelling PressureTest

viii)

Sieve and hydrometer analysis

ix)

Test on core samples

x)

Chemical analysis of the soil & sub-soil water

4.0.0 METHODOLOGY OF INVESTIGATION AND FIELD WORK


4.1.0 BORING AND DRILLING:
All exploratory boreholes of 150 mm nominal diameter were sunk by deploying
boring rigs using the conventional rotary drilling Methodology followed for
boring conformed to IS: 1892. Boring was effected by the cutting action of
rotating bit with casing in the top layer to stabilize the side of the bore and to
prevent soil from absorbing water during drilling process.
* - Bore logs are attached with this report separately.

Document Name: Geo Technical Investigation Report


Page-2

KITCO LIMITED

Nilawar Laboratories

4.1.1 SAMPLING :
UDS samples were collected from the cohesive stratum wherever possible.
The recovered samples from SPT tests have also been collected wherever
possible.

4.2.0 STANDARD PENETRATION TEST:


Standard Penetration Test (SPT) to determine penetration resistance was
conducted in the boreholes at various depths following the procedure
described in IS: 2131. In this method, driving bit is replaced by split spoon
sampler (50.8mm OD and 35.0mm ID) and the sampler is driven by dropping
65 kg hammer on top of the driving collar with free fall of 75 cm. The length of
the sampler is 60 cm. The sampler is first driven through 15 cm as Seating
Drive. It is further driven through 30 cm. The number of blows required to
drive the sampler for 30 cm beyond seating drive is termed as Penetration
resistance, N. Test is terminated on recording a blow count of 100 blows for
30 cm or less penetration for consecutive two tests.

4.3.0 GROUND WATER LEVEL:


The standing ground water level in the borehole after stabilization of the water
level it was recorded wherever water table has been met.

4.4.0 Laboratory Testing


Brief procedure for conducting laboratory tests is described below;

4.5.0 Particle size analysis


Testing procedure generally conforms to IS : 2720 (Part 4)- 1985.
Both sieve analysis and hydrometer analysis has been carried out.

4.5.1 Sieve Analysis


Sieve analysis for coarser fractions has been done by dry sieving, while wet
sieving method has been followed for soil fractions with appreciable amount of

Document Name: Geo Technical Investigation Report


Page-3

KITCO LIMITED

Nilawar Laboratories

clay. Sieving has been done using a sieve shaker by passing through the
following IS sieves.
4.75 mm, 2.36 mm, 1.70 mm, 1.40 mm, 1.00 mm, 600 microns, 425 microns,
100 microns and 75 microns.

4.5.2 Hydrometer Analysis


Soil suspension prepared by adding sodium hexa metaphosphate and sodium
carbonate is transferred to 75 micron IS sieve placed on a receiver and the soil
washed on the sieve without any loss. The suspension that has passed through
the sieve is transferred to 1000 ml measuring cylinder and made upto exactly
1000 ml with distilled water and then shaken thoroughly. Hydrometer is
immersed to a depth slightly below its floating position and then allowed to flat
freely. Hydrometer readings are taken at 10, 20, 30, and 45 seconds and then
at 1, 2 ,4, 8, 15 and 30 minutes and 1, 2, 4, 8 and 24 hours.
The diameter of the particle in suspension at any sampling time t is calculated
using Stokes formula as shown below and the percentage finer is calculated.
D=(30)/[980(G-Gl)] x [(HR)/( t)]
Where,

D= diameter of particle in suspension, in mm.

U= Coefficient of viscosity of water at the temperature of suspension


at the time of taking the hydrometer reading, in poise.
G= Specific gravity of the soil friction used in the sedimentation analysis
G1= Specific gravity of water.
HR= Effective depth corresponding to Rh.
t= time elapsed between the beginning of sedimentation
and taking of hydrometer reading, in minutes.
Rh = hydrometer reading corrected for meniscus = Rh +
Cm
Rh= hydrometer reading at the upper rim of the
meniscus.
Cm= Meniscus correction.
Semi log graph is then plotted with grain size (mm) in x axis and percentage
passing in y axis in the standard graph sheet. The graph represents respective

Document Name: Geo Technical Investigation Report


Page-4

KITCO LIMITED

Nilawar Laboratories

percentage of coarse and fine fractions and is useful as a tool for visual
presentation.

4.6.0 Atterbergs Limits


Liquid limit and plastic limit tests on clayey samples were done as per
procedure in IS : 2720 (Part 5)- 1985.

4.6.1 Liquid Limit


Testing is done as per IS : 2720 (Part 5) 1985. About 200 gm of soil sample
passing through 425 micron IS sieve is mixed thoroughly with distilled water
on the flat glass to form a uniform paste. The paste generally has a
consistency that will require 30 to 35 drops of the cup to cause the required
closure of standard groove. The ready mix soil is placed in the Casagrande cup
in such a way to form a depth of 1 cm at the centre of the cup, and then
central groove of 12 mm is made using standard grooving tool. The cup is
fitted and dropped by turning the crank at the rate of 2 revolutions per second
until the two halves of the soil close. The number of drops required to make
the groove close for the length of 12 mm is recorded.
A portion of the sample is then taken out for water content determination and
the water content corresponding to 25 blows represents the liquid limit.

4.6.2 Plastic Limit


About 15 gms of oven dried soil passing through 425 microns sieve is mixed
with sufficient quantity of water such that the soil mass becomes plastic
enough to be easily shaped into a ball. A portion of this ball is rolled on a glass
plate with the palm of the hand into a thread of uniform dia of 3 mm. The
water content represents the plastic limit.

4.6.3 Plasticity Index


It is the difference between liquid limit and plastic limit.

Document Name: Geo Technical Investigation Report


Page-5

KITCO LIMITED

Nilawar Laboratories

4.7.0 Natural Moisture Content (NMC)


A moisture cup is loosely filled with soil and weighed with lid. It is then kept in
oven with lid removed and maintained at temperature of the oven at 110 0 C
for 24 hours. The lid of the container is replaced and the dry weight found out.
The percentage of water content is calculated using the formula.
W=

W2-W3 x 100
W3-W1

Where W2= weight of container with wet soil, in g.


W3= weight of container with dry soil, in g
W1= weight of container with lid, in g
W= moisture content (%)

4.8.0 Bulk and Dry Density


Test procedure shall be as per IS: 2720 (Part-7) 1987.
The unit weight of soil in g/cc is its weight per unit volume. Soil is filled in
container and its weight determined. Knowing the volume of container, the
ratio of weight to volume represents bulk density.
The soil is then oven dried and weighed and dry density d(g/cc) is computed
using formula.
d = b /(1+W)
Where, b = bulk density in g/cc
W= natural moisture content in %

4.9.0 Specific Gravity


Test procedure shall be as per IS: 2720 (Part 3/ Section 1) 1987 for finegrained soils. Specific gravity of soil solids can be defined as the weight of
given volume of soil particles to the weight of equal volume of distilled water.
This term is used in relating weight of soil to its volume.
Specific gravity is found out using standard specific gravity bottle of 50 ml
capacity by weighing empty bottle (w1), bottle+ dry soil (w2), bottle + dry soil
+ water (w3), bottle + water (w4)
Specific gravity of soil =

(w2-w1) / ((w2-w1) (w3 w4))

Document Name: Geo Technical Investigation Report


Page-6

KITCO LIMITED

Nilawar Laboratories

4.10.0 Direct Shear Test


Test procedure shall be as per IS : 2720 (Part 13). In this test the soil
specimen is confined in a square metal box split into two halves horizontally.
Perforated metal plates and porous stones are placed above and below the
specimen to allow free drainage. After applying vertical load the soil is
gradually sheared by applying horizontal force, which makes the two halves of
the box move relative to each other. The shear is applied at a constant strain
rate and measured in a proving ring. Vertical deformation is measured with dial
gauge. Minimum of three specimens are tested and the graph drawn with
normal stress in X axis and shear stress in Y axis. From the straight line plot,
values of C and are measured.

4.11.0 Chemical Test on Soil Sample


Procedure for pH, Chloride and Sulphate is as below.
Preparation of Aqueous extract
Calculated quantity of field soil sample is mixed with distilled water in the
ration of 1:1
The suspension is mixed thoroughly and allowed to stand for 24 hours and the
extract is obtained by filtering with the help of a vacuum pump.
Final extract is filtered again and used for chemical tests.

4.11.1 Measurements of pH
20 g of soil sample is mixed with 50ml of distilled water. The suspension is
stirred for few seconds and is allowed to stand for 1 hour with occasional
stirring. It is stirred again, immediately before testing.
The pH meter is calibrated with standard buffers and the pH of the soil
suspension is measured.

Document Name: Geo Technical Investigation Report


Page-7

KITCO LIMITED

Nilawar Laboratories

4.11.2 Chloride
5 to 6 drops of Potassium chromate indicator is added to 10 ml of filtrate to
get yellow colour and then titrated against Silver nitrate solution (0.02N)
End point

Yellow

Chloride content, % =

Brick Red colour.


0.071 x V1 x V
S

Wd

Where,
V1

Volume of Silver nitrate used during titration (ml)

Volume of filtrate taken for the test (ml)

Wd

Weight of dry soil taken for filtration (g)

Volume of filtrate obtained from Wd (ml)

4.11.1 Sulphate
10ml of Sodium Chloride- Hydrochloric acid mixture, 10ml of Glycerol-Ethanol
mixture and 0.15 g of Barium Chloride is added to 50 ml of soil filtrate.
This is stirred for about an hour and the absorbance is measured against
distilled water blank using a colorimeter.
The Sulphate content of the sample is deduced from the standard curve.

Document Name: Geo Technical Investigation Report


Page-8

KITCO LIMITED

Nilawar Laboratories

5.0.0 Location : MIHAN, Nagpur


Sr.

BH-NO.

R.L. (m)

1.

BH-01

2.

No.

GPS Coordinates

Terminated

G.W.T.Below

Easting

Northing

Depth (m)

G.L.(m)

307.727

0295801

2331612

10.00

1.40

BH-03

308.462

0295713

2331724

11.00

2.00

3.

BH-04

307.533

0295843

2331650

10.00

4.00

4.

BH-05

309.387

0295795

2331704

10.00

1.80

5.

BH-06

308.229

0295758

2331769

10.00

1.70

6.

BH-07

308.333

0295798

2331661

10.00

1.00

7.

BH-08

308.425

0295752

2331717

10.00

1.70

5.1.0 Scope of work


Above mentioned boreholes have been executed for the proposed construction
of GENX/GE90 Engine Overhaul Workshop at Air India MRO, MIHAN SEZ,
Nagpur. The terminated depth and ground water table at all the boreholes is
mentioned above.

5.2.0 Sub-soil Profile


Layer I Filling
The occurrence of Filling, depth and N is tabulated below:
BH-No.

Depth (m)

Thickness (m)

N values

BH 01

0.00 1.50

1.50

BH 03

0.00 0.50

0.50

BH 04

0.00 0.50

0.50

BH 05

0.00 1.50

1.50

BH 06

0.00 1.50

1.50

BH 07

0.00 3.00

3.00

BH 08

0.00 0.20

0.20

This formation is encountered at above mentioned locations. No Laboratory


test is possible on such type of sample.

Document Name: Geo Technical Investigation Report


Page-9

KITCO LIMITED

Nilawar Laboratories

Layer II Silty Clay with Sand


The occurrence of silty clay with sand, depth and N is tabulated below:
BH-No.

Depth (m)

Thickness (m)

N values

BH 01

1.50 4.95

3.45

39

BH 03

0.50 3.00

2.50

10

BH 04

0.50 6.00

5.50

23, 38

BH 05

1.50 3.45

1.95

20

BH 07

3.00 4.50

1.50

30

BH 08

0.20 3.00

2.80

16

This formation is observed at above mentioned locations. The representative


samples are collected and tested for the determination of index properties in
laboratory.

Layer III Silty Clay with Sand & Gravels


The occurrence of silty clay with sand & gravels, depth and N is tabulated
below:
BH-No.

Depth (m)

Thickness (m)

N values

BH 05

3.45 4.50

1.05

BH 06

1.50 3.45

1.95

16

BH 07

4.50 4.90

0.40

BH 08

3.00 3.40

0.40

This formation is observed at above mentioned locations. The representative


samples are collected and tested for the determination of index properties in
laboratory.

Document Name: Geo Technical Investigation Report


Page-10

KITCO LIMITED

Nilawar Laboratories

Layer IV Highly Weathered Rock


The occurrence of highly weathered rock, depth and N is tabulated below:
BH-No.

Depth (m)

Thickness (m)

N values

BH 03

3.00 3.12

0.12

>100

BH 06

3.45 4.50

1.05

54

BH 07

4.90 6.00

1.10

BH 08

3.40 4.00

0.60

This formation is observed at above mentioned locations. No Laboratory test is


possible on such type of sample.

Layer V Boulder (Basalt)


The boulder formation is perceived at following mentioned locations. The
representative samples are collected. The occurrence of boulder is tabulated
below:

Run (m)
BH-No.

BH-01
BH-03

BH-04
BH-05

BH-06

Thickness

Core
Recovery

RQD (%)

From

To

(m)

4.95

6.00

1.05

Nil

Nil

6.00

7.50

1.50

Nil

Nil

3.12

4.50

1.38

Nil

Nil

4.50

6.00

1.50

Nil

Nil

6.00

7.50

1.50

Nil

Nil

7.50

9.00

1.50

Nil

Nil

9.00

10.50

1.50

Nil

Nil

6.00

7.50

1.50

Nil

Nil

7.50

9.00

1.50

Nil

Nil

4.50

4.55

0.05

Nil

Nil

4.55

6.00

1.45

Nil

Nil

6.00

7.50

1.50

Nil

Nil

7.50

9.00

1.50

Nil

Nil

4.50

4.53

0.03

Nil

Nil

4.53

6.00

1.47

Nil

Nil

6.00

7.50

1.50

Nil

Nil

(%)

Document Name: Geo Technical Investigation Report


Page-11

KITCO LIMITED

Nilawar Laboratories
Run (m)

BH-No.

BH-07

BH-08

Thickness

Core
Recovery

RQD (%)

From

To

(m)

7.50

9.00

1.50

Nil

Nil

6.00

6.02

0.02

Nil

Nil

6.02

7.50

1.48

Nil

Nil

7.50

8.00

0.50

Nil

Nil

4.00

4.03

0.03

Nil

Nil

4.03

5.50

1.47

Nil

Nil

5.50

7.00

1.50

Nil

Nil

7.00

8.00

1.00

Nil

Nil

(%)

The boulder formation is encountered at above mentioned locations. The core


recovery percentages and RQD (Rock Quality Designation) observed in this layer
indicates poor rock formation.

Layer VI Fine Grained Basalt Rock (Fractured rock)


The hard rock formation is observed at following mentioned locations. The
representative samples are collected. The occurrence of hard rock is tabulated
below:
Run (m)
BH-No.

Thickness

Core
Recovery

RQD (%)

From

To

(m)

7.50

9.00

1.50

50

Nil

9.00

10.00

1.00

87

Nil

BH-03

10.50

11.00

0.50

22

Nil

BH-04

9.00

10.00

1.00

48

Nil

BH-05

9.00

10.00

1.00

33

Nil

BH-06

9.00

10.00

1.00

35

Nil

8.00

9.00

1.00

60

Nil

9.00

10.00

1.00

70

48

8.00

9.00

1.00

51

Nil

9.00

10.00

1.00

65

27

BH-01

BH-07
BH-08

(%)

Document Name: Geo Technical Investigation Report


Page-12

KITCO LIMITED

Nilawar Laboratories

The hard rock formation is encountered at above mentioned locations is black


coloured basalt rock. The core recovery percentages and RQD (Rock Quality
Designation) observed in this layer indicates poor rock formation.

5.3.0 Laboratory Test Results:


5.3.1 Index Properties of Soil Samples.
Depth
(m)

NMC
(%)

Gravels
(%)

Sand
(%)

Silt
(%)

Clay
(%)

L.L.
(%)

P.I.
(%)

1.50

22

02

17

54

27

54

29

4.50

22

02

11

59

28

60

33

0.50

22

05

24

46

25

48

24

3.45

22

02

17

57

24

47

24

4.95

19

03

15

57

25

46

23

BH-05

2.35

18

04

24

51

21

52

26

BH-06

3.00

20

08

21

46

25

54

29

BH-07

3.00

23

07

22

44

27

58

32

BH-08

1.00

20

03

17

54

26

55

30

BH-No.
BH-01
BH-03
BH-04

5.3.2 Strength Properties

Location

Depth
(m)

Bulk

Dry

Cohesion

Density

Density

(g/cc)

(g/cc)

(kg/cm2)

Angle of
Internal
Friction
(degrees)

BH-01

3.00

1.86

1.56

0.26

13

BH-03

1.95

1.85

1.57

0.24

12

BH-04

1.50

1.84

1.53

0.25

12

1.50

1.83

1.53

0.25

11

3.45

1.86

1.56

0.19

17

BH-06

2.50

1.88

1.54

0.25

13

BH-07

4.50

1.90

1.61

0.20

16

BH-08

3.00

1.88

1.61

0.22

14

BH-05

Document Name: Geo Technical Investigation Report


Page-13

KITCO LIMITED

Nilawar Laboratories

5.3.3 Physical Test on Rock Samples.


Water

Compressive

Absorption

Strength

(%)

(Kg/cm2)

2.83

0.12

810

10.50

2.84

0.18

787

BH-04

9.00

2.86

0.10

844

BH-05

9.00

2.82

0.16

765

BH-06

9.00

2.85

0.20

774

BH-07

9.00

2.85

0.15

872

BH-08

9.00

2.87

0.17

836

Depth

Bulk Density

(m)

(g/cc)

BH-01

7.50

BH-03

BH-No.

Note: At Borehole No 1, 4, 5 & 6 at depth 7.50 m RQD percentage is Nil, so


Point Load test is conducted for calculating compressive strength. The
observation sheet is attached with this report.

5.4.0 Engineering Analysis


At this location silty clay with sand formation is observed at upper layer and is
followed by boulder/basalt rock.
Following are the locations where the value of SPT is greater than 100 and the
value of penetration is mentioned in the below table.

Sr.No

Location

Depth
(m)

1.

BH-03

2.

No. of blows for


'N'-value
(SPT)

First
15 cm
(N1)

Next
15 cm
(N2)

Next
15 cm
(N3)

3.00

12

>100

BH-05

4.50

05

>100

3.

BH-06

4.50

03

>100

4.

BH-07

6.00

02

>100

5.

BH-08

4.00

03

>100

Note:- The value of penetration is also incorporated in respective depths in


respective borelogs attached with this report.

Document Name: Geo Technical Investigation Report

KITCO LIMITED

Nilawar Laboratories

5.5.0 Safe Bearing Capacity Calculations


5.5.1 Calculation of Safe Bearing Capacity: Shear Criteria
At BH-01 at depth 3.00 m, silty clay with sand formation is observed. The value
of c & is taken from laboratory test results i.e. c=0.26 kg/cm2 & =13 and
SBC calculated by considering local shear failure for 3.00m deep and 3.0m wide
square foundation with factor of safety as 3. The water table correction 0.5 is
taken.
0.26

Cohesion, c =
Angle of Internal friction,
Depth of footing (D) =
Width of footing (B) =
Depth of GWT (Dw) =
Factor of safety =
Where,

a) Cohesion, c =
b) Angle of Internal friction,

13

3.0
3.0
3.0
3

m
m
m

2.6

t/m
(Modified for local
shear)

8.93

Kg/cm

1.860

g/cc

7.90

Nq =

2.24

N =

1.02

e) Shape factor, sc=

1.3

sq =

1.2

s =

0.8

f) Depth Factor, dc=

1.18

dq =

1.00

d =

1.00

c) Bulk density,
d) Nc

g) Inclination Factor, ic= iq = i


h) Water table correction, W =
i) Overburden Pressure (q) = D x

qu

1.0
0.5

5.58

t/m

= 2/3 cNc sc dc ic + q(Nq - 1) sq dq iq + 0.5 B N s d i W'


= 30.48 t/m2

qs = qu/3
= 10.16

t/m2

Say 10.00 t/m2


5.5.2 Permissible Bearing value: Settlement Criteria
Net allowable bearing capacity is calculated by settlement criteria for 40mm
allowable settlement as per IS: 8009 (Part-I) 1976. For 3.0m wide footing.
i) Size of Footing: 3.0m x 3.0m
At BH-01 at 4.50 m depth the observed SPT Value is 39.

Document Name: Geo Technical Investigation Report


Page-15

KITCO LIMITED

Nilawar Laboratories

Hence,
B = 3.00m, N = 39
Corrected N value for dialency

= 27

Settlement at a load of 1 kg/cm2 = 11.4 mm


Water table correction for the settlement

Load at 40mm settlement =

40 x 10
22.8

11.4
0.5
= 22.8 mm

= 17.54 t/m2 17.50 t/m2

5.6.0 Safe Load Carrying Capacity for Pile Foundation


The weathered rock formation is observed at 5.00 m depth for BH-01; hence
SPT value is taken 100. The safe load carrying capacity of Bored Cast In-situ
Piles founded on rocks with different diameter and length are computed as per
IS: 2911 (Part I/Sec 2).

5.6.1 Permissible Bearing value by Settlement Criteria:


Depth of
Location

Size of Footing

Safe Bearing

(m)

Pressure (t/m2)

3.00

3.0 x 3.0

10.00

4.50

3.0 x 3.0

17.50

5.00

3.0 x 3.0

44.00

1.50

3.0 x 3.0

8.00

3.00

3.0 x 3.0

44.00

4.50

3.0 x 3.0

44.00

1.50

3.0 x 3.0

8.00

3.00

3.0 x 3.0

11.50

4.50

3.0 x 3.0

17.00

6.00

3.0 x 3.0

44.00

1.50

3.0 x 3.0

7.50

Foundation
(m)

BH-01

BH-03

BH-04

BH-05

Document Name: Geo Technical Investigation Report


Page-16

KITCO LIMITED

Nilawar Laboratories
Depth of

Location

Size of Footing

Safe Bearing

(m)

Pressure (t/m2)

3.50

3.0 x 3.0

12.00

4.50

3.0 x 3.0

44.00

1.50

3.0 x 3.0

8.50

3.50

3.0 x 3.0

25.00

4.50

3.0 x 3.0

44.00

3.00

3.0 x 3.0

12.50

4.50

3.0 x 3.0

12.50

6.00

3.0 x 3.0

44.00

1.50

3.0 x 3.0

9.50

3.00

3.0 x 3.0

9.50

4.00

3.0 x 3.0

44.00

Foundation
(m)

BH-06

BH-07

BH-08

5.6.2 Safe

Load

Carrying

Capacity

for

Pile

foundation

boulder/weathered rock as per IS 2911 Part I Sec II - 2010:


Location

BH-01

BH-04

Diameter of

Length of

Pile (m)

Pile (m)

0.60

5.00

115.00

0.75

5.00

185.00

0.90

5.00

265.00

1.00

5.00

325.00

1.20

5.00

470.00

0.60

6.00

115.00

0.75

6.00

185.00

0.90

6.00

265.00

1.00

6.00

325.00

1.20

6.00

470.00

Safe Load (Ton)

Document Name: Geo Technical Investigation Report


Page-17

for

KITCO LIMITED

Location

BH-07

Nilawar Laboratories
Diameter of

Length of

Pile (m)

Pile (m)

0.60

5.00

115.00

0.75

5.00

185.00

0.90

5.00

265.00

1.00

5.00

325.00

1.20

5.00

470.00

Safe Load (Ton)

5.6.3 Safe Load Carrying Capacity for Pile foundation for Hard rock (Basalt)
as per IS: 14593 1998.
Location

BH-01

BH-03

Diameter of

Length of

Pile (m)

Pile (m)

0.60

7.50

180.00

0.75

7.50

285.00

0.90

7.50

410.00

1.00

7.50

505.00

1.20

7.50

730.00

0.60

10.50

175.00

0.75

10.50

275.00

0.90

10.50

400.00

1.00

10.50

490.00

1.20

10.50

710.00

0.60

9.00

190.00

0.75

9.00

295.00

0.90

9.00

430.00

1.00

9.00

530.00

Safe Load (Ton)

BH-04

Document Name: Geo Technical Investigation Report


Page-18

KITCO LIMITED

Location

BH-05

BH-06

BH-07

BH-08

Nilawar Laboratories
Diameter of

Length of

Pile (m)

Pile (m)

1.20

9.00

760.00

0.60

9.00

170.00

0.75

9.00

270.00

0.90

9.00

390.00

1.00

9.00

480.00

1.20

9.00

690.00

0.60

9.00

175.00

0.75

9.00

270.00

0.90

9.00

390.00

1.00

9.00

485.00

1.20

9.00

700.00

0.60

9.00

195.00

0.75

9.00

305.00

0.90

9.00

440.00

1.00

9.00

545.00

1.20

9.00

785.00

0.60

9.00

190.00

0.75

9.00

295.00

0.90

9.00

425.00

1.00

9.00

525.00

1.20

9.00

755.00

Safe Load (Ton)

5.7.0 Consolidation Settlement


The consolidation settlements that may occur due to loads likely to be imposed
by the structure on the strata below foundation. At this location silty clay with
sand is observed at upper layer and is followed by boulder/basalt rock. The

Document Name: Geo Technical Investigation Report


Page-19

KITCO LIMITED

Nilawar Laboratories

foundation kept below silty clay layer may not show settlement. It is suggested
that the soil at the suggested invert level shall be thoroughly examined for
Loose/soft soil pockets.

5.8.0 Discussion
The type of foundation depends on stratification, type of structure, loading,
allowable settlement etc. In present case the structure is Engine overhaul
workshop and load coming on foundation is considerable.
At Borehole no BH-08, 03, 05 & 06 below 4.0 m depth boulder formation is
observed, open foundation is suggested considering type of strata available.
For remaining location deep foundation i.e. pile foundation is suggested, which
may modified as per site restriction and other parameter.
a) There is a silty clay formation below filling material, hence, this soil needs
to be replaced with borrowed soil. The soil is showing swelling properties ,
as the water table is observed at a shallow depth of 2-4m below NGL.
b) The present filling material is a competent material followed by silty clay
strata which has swelling properties, hence, we recommend to replace this
silty clay strata with the competent filling / borrow material in order to bear
the heavy load of the grade slab.
c) At this location the strata below 5.0m to 9.0m depth is weathered rock/
boulder and it shows the value of SPT>100. As per common practice SPT is
terminated if the value is >100. This layer consists of boulder with smaller
size, hence, no core recovery / RQD is observed which shows the fractured/
scattered nature of strata. Thus pile capacity is evaluated on the basis of
SPT value. If you require higher capacity for pile then grouting is necessary.
The thickness of said layer is approx. 4m. Otherwise, pile may be rested at
9.0m depth where black basalt (hard rock) is observed and pile capacity are
evaluated on the basis of compressive strength of rock and detail
calculation sheet are attached with this report.

5.9.0 Chemical Analysis of soil and water samples

Document Name: Geo Technical Investigation Report


Page-20

KITCO LIMITED

Nilawar Laboratories

Soil and water samples tested for pH, chloride and Sulphate as SO4 and SO3
indicate that the result of water samples is within the permissible limits as per
IS: 456-2000, Table No.1, Clause 5.4. The chemical test result of sample is
attached with this report separately;

5.10.0 Conclusions

Foundation level and type of foundation should be decided by


designer considering the overall investigation and design parameter.

The pile capacities at site should be verified by pile load tests as per IS
specifications.

Document Name: Geo Technical Investigation Report


Page-21

897:;
43296248 46264
29


 !"# 
$%""
&'()*+,-./012


1234546748964
962




 !"$ 
#%34
&'()*+,-.5067




9 
14  9 243
24
29 96


Page-22

45767
8888888888888888888888888888888888888888888888888888888888
 !"# 
$%&!#
'()#*+,-.#/#0123#

1234546748964
962




#


9 
14  9 243
24
29 96


Page-23

KITCO LIMITED.

Nilawar Laboratories

BORE LOG
PROJECT: GEO-TECHNICAL INVESTIGATION WORKS FOR CONSTRUCTION OF
GENX/GE90 ENGINE OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR
CLIENT: KITCO LIMITED.

TYPE OF BORING :

Rotary Drilling

BORE HOLE DIA. :

150 mm

BORE HOLE NO : BH-01

WATER TABLE
(Below GL) :
GPS Coordinates

1.40 m

LOCATION :- Mihan
Reduced Level (R.L) :- 307.727 m

N: 2331612
E: 0295801

STANDARD PENETRATION TEST

From

To

Run

0.00

1.50

1.50

1.50

3.00

1.50

3.00

3.40

0.40

ENGINEERING
CLASSIFICATION

LEGEND

ROCK DRILLING
DEPTH BELOW GL (m)

Filling

TYPE OF
SAMPLIN
G

NO. OF BLOWS FOR


FIRST NEXT
15 cm 15 cm
(N1)
(N2)

NEXT
'N'CORE
15 cm VALUE RECOVERY RQD (%)
(N3) (N2 + N3)
(%)

REMARKS

DS
DS
UDS

Silty Clay with Sand


3.40

4.50

1.10

DS

4.50

4.95

0.45

SPT-01

4.95

6.00

1.05
Weathered Rock

6.00

7.50

1.50

7.50

9.00

1.50

9.00

10.00

1.00

Fine Grained Hard


Rock (Black Basalt)

SPT = STANDARD PENETRATION TEST

####
####
####
####
++++
++++
++++

10

18

21

39
Nil

Nil

Nil

Nil

Core

50

Nil

Core

87

Nil

Small
Pieces

BH Terminated at 10.00 m

DS = DISTURBED SAMPLE
UDS = UNDISTURBED SAMPLE
Surveyor
Date: 30.12.2014

Document Name: Geo-Technical Investigation Report

Page-24

KITCO LIMITED.

Nilawar Laboratories

BORE LOG
PROJECT: GEO-TECHNICAL INVESTIGATION WORKS FOR CONSTRUCTION OF
GENX/GE90 ENGINE OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR
CLIENT: KITCO LIMITED.

TYPE OF BORING :

Rotary Drilling

BORE HOLE DIA. :

150 mm

BORE HOLE NO : BH-03

WATER TABLE
(Below GL) :
GPS Coordinates

2.00m

LOCATION :- Mihan
Reduced Level (R.L) : 308.462 m

N: 2331724
E: 0295713

STANDARD PENETRATION TEST

From

To

Run

0.00

0.50

0.50

0.50

1.50

1.00

1.50

1.95

0.45

ENGINEERING
CLASSIFICATION

LEGEND

ROCK DRILLING
DEPTH BELOW GL (m)

Filling

TYPE OF
SAMPLIN
G

NO. OF BLOWS FOR


FIRST NEXT
15 cm 15 cm
(N1)
(N2)

NEXT
'N'CORE
15 cm VALUE RECOVERY RQD (%)
(N3) (N2 + N3)
(%)

REMARKS

DS
DS
SPT-01

03

04

06

10

Silty Clay with Sand


1.95

2.35

0.40

2.35

3.00

0.65

3.00

3.12

0.12

3.12

4.50

1.38

4.50

6.00

1.50

6.00

7.50

1.50

7.50

9.00

1.50

9.00

10.50

1.50

10.50 11.00

0.50

UDS
DS
Highly Weathered
Rock

Boulder

Fine Grained Hard


Rock (Black Basalt)

SPT = STANDARD PENETRATION TEST

####
####
0000
0000
0000
0000
0000
0000
0000
0000
++++
++++
++++

SPT-02

>100

Small
Pieces

Core

Nil

Nil

Nil

Nil

Nil

Nil

Nil

Nil

Nil

Nil

22

Nil

BH Terminated at 11.00 m

DS = DISTURBED SAMPLE
UDS = UNDISTURBED SAMPLE
Surveyor
Date: 16.01.2015

Document Name: Geo-Technical Investigation Report

Page-25

KITCO LIMITED.

Nilawar Laboratories

BORE LOG
PROJECT: GEO-TECHNICAL INVESTIGATION WORKS FOR CONSTRUCTION OF
GENX/GE90 ENGINE OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR
CLIENT: KITCO LIMITED.

TYPE OF BORING :

Rotary Drilling

BORE HOLE DIA. :

150 mm

BORE HOLE NO : BH-04

WATER TABLE
(Below GL) :
GPS Coordinates

4.00 m

LOCATION :- Mihan
Reduced Level (R.L) :- 307.533 m

N: 2331650
E: 0295843

STANDARD PENETRATION TEST


ENGINEERING
CLASSIFICATION

LEGEND

ROCK DRILLING
DEPTH BELOW GL (m)

TYPE OF
SAMPLIN
G

From

To

Run

0.00

0.50

0.50

0.50

1.50

1.00

DS

1.50

1.90

0.40

UDS

1.90

3.00

1.10

3.00

3.45

0.45

3.45

4.50

1.05

DS

4.50

4.95

0.45

SPT-02

4.95

6.00

1.05

DS

6.00

7.50

1.50

7.50

9.00

1.50

9.00

10.00

1.00

Filling

NO. OF BLOWS FOR


FIRST NEXT
15 cm 15 cm
(N1)
(N2)

NEXT
'N'CORE
15 cm VALUE RECOVERY RQD (%)
(N3) (N2 + N3)
(%)

REMARKS

DS

DS
Silty Clay with Sand

SPT-01

Weathered Rock

####
####
####

Small
Pieces

Fine Grained Hard


Rock (Black Basalt)

++++
++++

Core

SPT = STANDARD PENETRATION TEST

06

10

13

23

11

17

21

38

48

Nil

BH Terminated at 10.00 m

DS = DISTURBED SAMPLE
UDS = UNDISTURBED SAMPLE
Surveyor
Date: 30.12.2014

Document Name: Geo-Technical Investigation Report

Page-26

KITCO LIMITED.

Nilawar Laboratories

BORE LOG
PROJECT: GEO-TECHNICAL INVESTIGATION W ORKS FOR CONSTRUCTION OF
GENX/GE90 ENGINE OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR
CLIENT: KITCO LIMITED.

TYPE OF BORING :

Rotary Drilling

BORE HOLE DIA. :

150 mm

BORE HOLE NO : BH-05

WATER TABLE
(Below GL) :
GPS Coordinates

1.80 m

LOCATION :- Mihan
Reduced Level (R.L) : 309.387 m

N: 2331704
E: 0295795

STANDARD PENETRATION TEST

From

To

Run

0.00

1.50

1.50

1.50

1.90

0.40

1.90

2.35

0.45

2.35

3.45

1.10

3.45

3.85

0.40

3.85

4.50

0.65

4.50

4.55

0.05

4.55

6.00

1.45

6.00

7.50

1.50

7.50

9.00

1.50

9.00

10.00

1.00

ENGINEERING
CLASSIFICATION

LEGEND

ROCK DRILLING
DEPTH BELOW GL (m)

Filling

TYPE OF
SAMPLIN
G

NO. OF BLOWS FOR


FIRST NEXT
15 cm 15 cm
(N1)
(N2)

NEXT
'N'CORE
15 cm VALUE RECOVERY RQD (%)
(N3) (N2 + N3)
(%)

REMARKS

DS
UDS

Silty Clay with Sand

SPT-01

04

09

11

20

DS
Silty Clay With Sand &
Gravels

00000
00000
00000
00000

Boulder (Basalt)

0000
0000
0000
0000
0000
0000

Fine Grained Hard


Rock (Black Basalt)

SPT = STANDARD PENETRATION TEST

++++
++++
++++

UDS
DS
SPT -02

>100

Small
Pieces

Core

Nil

Nil

Nil

Nil

Nil

Nil

Nil

Nil

33

Nil

BH Terminated at 10.00 m

DS = DISTURBED SAMPLE
UDS = UNDISTURBED SAMPLE
Surveyor
Date: 19.01.2014

Document Name: Geo-Technical Investigation Report

Page-27

KITCO LIMITED.

Nilawar Laboratories

BORE LOG
PROJECT: GEO-TECHNICAL INVESTIGATION WORKS FOR CONSTRUCTION OF
GENX/GE90 ENGINE OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR
CLIENT: KITCO LIMITED.

TYPE OF BORING :

Rotary Drilling

BORE HOLE DIA. :

150 mm

BORE HOLE NO : BH-06

WATER TABLE
(Below GL) :
GPS Coordinates

1.70m

LOCATION :- Mihan
Reduced Level (R.L) : 308.229 m

N: 2331769
E: 0295758

STANDARD PENETRATION TEST

From

To

Run

0.00

1.50

1.50

1.50

1.95

0.45

1.95

2.50

0.55

2.50

2.90

0.40

2.90

3.45

0.55

3.45

3.90

0.45

3.90

4.50

0.60

4.50

4.53

0.03

4.53

6.00

1.47

6.00

7.50

1.50

7.50

9.00

1.50

9.00

10.00

1.00

ENGINEERING
CLASSIFICATION

LEGEND

ROCK DRILLING
DEPTH BELOW GL (m)

Filling

Silty Clay with Sand &


Gravels

00000
00000
00000
00000
00000
00000
00000

Highly Weathered
Rock

Boulder

0000
0000
0000
0000
0000
0000

SPT = STANDARD PENETRATION TEST

NO. OF BLOWS FOR


FIRST NEXT
15 cm 15 cm
(N1)
(N2)

NEXT
'N'CORE
15 cm VALUE RECOVERY RQD (%)
(N3) (N2 + N3)
(%)

REMARKS

DS

####
####
####
####

Fine Grained Hard


Rock (Black Basalt)

TYPE OF
SAMPLIN
G

SPT-01

03

07

09

16

08

23

31

54

DS
UDS
DS
SPT-02
DS
SPT-03

>100

Small
Pieces

Core

Nil

Nil

Nil

Nil

Nil

Nil

Nil

Nil

35

Nil

BH Terminated at 10.00 m

DS = DISTURBED SAMPLE
UDS = UNDISTURBED SAMPLE
Surveyor
Date: 22.01.2015

Document Name: Geo-Technical Investigation Report

Page-28

KITCO LIMITED.

Nilawar Laboratories

BORE LOG
PROJECT: GEO-TECHNICAL INVESTIGATION WORKS FOR CONSTRUCTION OF
GENX/GE90 ENGINE OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR
CLIENT: KITCO LIMITED.

TYPE OF BORING :

Rotary Drilling

BORE HOLE DIA. :

150 mm

BORE HOLE NO : BH-07

WATER TABLE
(Below GL) :

1.00 m

LOCATION :- Mihan

GPS Coordinates

N: 2331661

Reduced Level (R.L) :- 308.333 m

E: 0295798
STANDARD PENETRATION TEST

From

To

Run

0.00

1.50

1.50

ENGINEERING
CLASSIFICATION

LEGEND

ROCK DRILLING
DEPTH BELOW GL (m)

TYPE OF
SAMPLIN
G

NO. OF BLOWS FOR


FIRST NEXT
15 cm 15 cm
(N1)
(N2)

NEXT
'N'CORE
15 cm VALUE RECOVERY RQD (%)
(N3) (N2 + N3)
(%)

REMARKS

DS
Filling

1.50

3.00

1.50

3.00

3.45

0.45

3.45

4.50

1.05

4.50

4.90

0.40

4.90

6.00

1.10

6.00

6.02

0.02

6.02

7.50

1.48

7.50

8.00

0.50

8.00

9.00

1.00

9.00

10.00

1.00

DS
SPT-01

07

12

18

30

Silty Clay with Sand


DS
Silty Clay with Sand &
Gravels
Highly Weathered
Rock

Boulder (Basalt)

Fine Grained Hard


Rock (Black Basalt)

SPT = STANDARD PENETRATION TEST

0000
0000

####
####
#0 #0 #0 #0
0000
0000
0000
0000
++++
++++
++++

UDS
DS
SPT-02

>100

Small
Pieces

Nil

Nil

Nil

Nil

Core

60

Nil

Core

70

48

BH Terminated at 10.00 m

DS = DISTURBED SAMPLE
UDS = UNDISTURBED SAMPLE
Surveyor
Date: 06.01.2015

Document Name: Geo-Technical Investigation Report

Page-29

KITCO LIMITED.

Nilawar Laboratories

BORE LOG
PROJECT: GEO-TECHNICAL INVESTIGATION WORKS FOR CONSTRUCTION OF
GENX/GE90 ENGINE OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR
CLIENT: KITCO LIMITED.

TYPE OF BORING :

Rotary Drilling

BORE HOLE DIA. :

150 mm

BORE HOLE NO : BH-08

WATER TABLE
(Below GL) :
GPS Coordinates

1.70 m

LOCATION :- Mihan
Reduced Level (R.L) :- 308.425 m

N: 2331717
E: 0295752

STANDARD PENETRATION TEST

From

To

Run

0.00

0.20

0.20

0.20

1.50

1.30

1.50

1.95

0.45

1.95

3.00

1.05

3.00

3.40

0.40

3.40

4.00

0.60

4.00

4.03

0.03

4.03

5.50

1.47

ENGINEERING
CLASSIFICATION

Filling

7.00

1.50

7.00

8.00

1.00

8.00

9.00

1.00

9.00

10.00

1.00

TYPE OF
SAMPLIN
G

NO. OF BLOWS FOR


FIRST NEXT
15 cm 15 cm
(N1)
(N2)

NEXT
'N'CORE
15 cm VALUE RECOVERY RQD (%)
(N3) (N2 + N3)
(%)

REMARKS

DS
DS

Silty Clay with Sand

SPT-01

05

07

09

16

DS
Silty Clay with Sand &
Gravels
Highly Weathered
Rock

Boulder (Basalt)
5.50

LEGEND

ROCK DRILLING
DEPTH BELOW GL (m)

Fine Grained Hard


Rock (Black Basalt)

SPT = STANDARD PENETRATION TEST

oooo
oooo

####
####
####
0000
0000
0000
0000
0000
0000
++++
++++
++++

UDS
DS
SPT-02

>100
Nil

Nil

Nil

Nil

Nil

Nil

Core

51

Nil

Core

65

27

Small
Pieces

BH Terminated at 10.00 m

DS = DISTURBED SAMPLE
UDS = UNDISTURBED SAMPLE
Surveyor
Date: 11.01.2015

Document Name: Geo-Technical Investigation Report

Page-30

KITCO Ltd.

Nilawar Laboratories

BH-04

BH-05

BH-06

BH-07

BH-08

COHESION
(kg/cm2)

ANGLE f

WATER
ABSORPTION (%)

COMPRESSIVE
STRENGTH
(Kg/cm2)

1.50

DS

02

17

54

27

54

25

16

29

CH

22

34

2.644

3.00

UDS

04

24

45

27

52

25

17

27

CH

19

1.86

1.56

31

2.646

0.693

0.329

0.587

27

0.26

13

0.25

13

4.50

DS

02

11

59

28

60

27

16

33

CH

22

37

2.647

7.50

CORE

2.83

2.83

2.885

0.12

810

0.50

DS

05

24

46

25

48

24

15

24

CI

22

31

2.639

SWELLING
PRESSURE
(Kg/cm2)
Unconfined
Compressive Test
(KN/m2)

ANGLE f

TRIAXIAL
TEST

COHESION
(kg/cm2)

DIRECT
SHEAR
TEST

COMPRESSION
INDEX Cc

BH-03

NMC BULK DRY FREE


(%) DEN- DEN- SWELL
SITY SITY INDEX
(g/cc) (g/cc)
(%)

VOID RATIO

BH-01

DEPTH SAMPGRAIN SIZE ANALYSIS


LIQUID PLASTIC SHRINK PLASTISILT
CLAY LIMIT
(m)
LING GRAVEL SAND
LIMIT
AGE
CITY
(%)
(%)
(%)
(%)
(%)
(%)
LIMIT INDEX
(%)
(%)

SPECIFIC
GRAVITY

BORE
HOLE
NO.

IS
CLASSIFICATION

LAB TEST RESULTS

1.95

UDS

03

20

51

26

51

25

17

26

CH

18

1.85

1.57

36

2.642

0.685

0.326

0.617

34

0.24

12

0.24

13

10.50

CORE

2.84

2.83

2.912

0.18

787

1.50

UDS

03

16

55

26

51

25

15

26

CH

20

1.84

1.53

32

2.644

0.724

0.331

0.572

25

0.25

12

0.23

11

3.45

DS

02

17

57

24

47

23

13

24

CI

22

30

2.642

4.95

DS

03

15

57

25

46

23

13

23

CI

19

29

2.644

9.00

CORE

2.86

2.86

2.920

0.10

844

1.50

UDS

02

18

53

27

55

26

19

29

CH

20

1.83

1.53

35

2.644

0.734

0.358

0.634

36

0.25

11

2.35

DS

04

24

51

21

52

25

18

27

CH

18

32

2.643

3.45

UDS

37

22

24

17

49

23

16

26

CI

19

1.86

1.56

18

2.638

0.688

62

0.19

17

0.17

16

9.00

CORE

2.82

2.82

2.885

0.16

765

2.50

UDS

12

24

36

28

60

27

20

33

CH

22

1.88

1.54

37

2.643

0.715

0.337

0.589

51

0.25

13

0.24

13

3.00

DS

08

21

46

25

54

25

18

29

CH

20

32

2.645

9.00

CORE

2.85

2.84

2.901

0.20

774

3.00

DS

07

22

44

27

58

26

18

32

CH

23

34

2.646

4.50

UDS

16

32

33

19

44

21

14

23

CI

18

1.90

1.61

24

2.642

0.641

0.266

0.534

58

0.20

16

0.22

15

9.00

CORE

2.85

2.85

2.915

0.15

872

1.00

DS

03

17

54

26

55

25

17

30

CH

20

36

2.645

3.00

UDS

13

34

32

21

46

22

13

24

CI

17

1.88

1.61

23

2.641

0.644

0.274

0.546

53

0.22

14

0.23

13

9.00

CORE

2.87

2.87

2.894

0.17

836

Document Name: Geo-Technical Investigation Report

Page-31

KITCO LIMITED.

Nilawar Laboratories

CHEMICAL ANALYSIS OF SOIL SAMPLES

Sr.No

Location

Depth
(m)

pH

Sulphate

Chloride

(%)

(%)

1.

BH-01

3.00

8.87

0.0036

0.0026

2.

BH-03

1.50

8.84

0.0080

0.0044

3.

BH-04

1.50

8.34

0.0048

0.0044

4.

BH-05

1.50

8.93

0.0128

0.0058

5.

BH-06

2.50

8.90

0.0092

0.0054

6.

BH-07

4.50

8.79

0.0616

0.0496

7.

BH-08

3.00

8.86

0.0348

0.0139

Document Name: Geo Technical Investigation Report


Page-32

KITCO LIMITED.

Nilawar laboratories

TYPICAL CALCULATION FOR SAFE LOAD CARRING CAPACITY FOR


BORED CAST IN-SITU PILE.
(AS PER IS: 2911 Part I Sec II 2010)
LOCATION: BH-01 (For 0.60 m dia Pile)
1
2
3
4

Dia of Pile (D)


15 D (Effective length of pile)
Length of Pile
Shear Strength of Rock (Cu1)

=
=
=
=

0.60 m
9.0 m
5.00 m
700 kN/m2

Average shear strength of rock (Cu2)

= 700 kN/m2

Bearing Capacity Factor (Nc)

= 9.0

Socket Length into the Rock (ls)

= 1.50 m

Factor of Safety (Fs)

= 3

() recommended value

= 0.90

Safe Load Carring Capacity of bored cast in-situ Pile


Qs = Cu1Nc . *B2 + Cu2 . *B*L
4*Fs
Fs
Where,
Qs = Safe Load capacity of pile in tonnes.
Ap = Cross sectional area of pile in m2
D = diameter of pile in m.
Nc = Bearing Capacity factor.
Fs= Factor of safety.
Cu1 = Shear strength of rock below the base of the pile kN/m2.
Cu2 = Average Shear strength of rock in the socketed length of pile kN/m2.
Ls = Socket Length of pile in m.

Document Name: Geo Technical Investigation Report

Page-33

KITCO LIMITED.

Nilawar laboratories

By solving above equation,


Ultimate Bearing Capacity (Qs)

= 1186.92 kN
= 118.69 Tons

Say = 115.00 Ton

Document Name: Geo Technical Investigation Report

Page-34

Page-35

Page-36

Page-37

Page-38

Page-39

Page-40

Page-41

Page-42

Page-43

Page-44

Page-45

Page-46

Page-47

Page-48

Page-49

Page-50

Page-51

KITCO LIMITED

Nilawar Laboratories

Direct Shear Graph


PROJECT : GEO-TECHNICAL INVESTIGATION WORKS FOR

BOREHOLE NO : BH-01

Shear Stress (Kg/cm2)

CONSTRUCTION OF GENX/GE90 ENGINE


OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR

3
2.9
2.8
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0

DEPTH : 3.00 m

Cohesion (Kg/cm2)
= 0.26
Angle of Internal Friction = 13e
A

Normal Stress (Kg/cm2)

Document Name: Geo-Technical Investigation Report

Page-52

KITCO LIMITED

Nilawar Laboratories

Direct Shear Graph


PROJECT : GEO-TECHNICAL INVESTIGATION WORKS FOR

BOREHOLE NO : BH-03

Shear Stress (Kg/cm2)

CONSTRUCTION OF GENX/GE90 ENGINE


OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR

3
2.9
2.8
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0

DEPTH : 1.95 m

Cohesion (Kg/cm2)
= 0.24
Angle of Internal Friction = 12e
A

Normal Stress (Kg/cm2)

Document Name: Geo-Technical Investigation Report

Page-53

KITCO LIMITED

Nilawar Laboratories

Direct Shear Graph


PROJECT : GEO-TECHNICAL INVESTIGATION WORKS FOR

BOREHOLE NO : BH-04

Shear Stress (Kg/cm2)

CONSTRUCTION OF GENX/GE90 ENGINE


OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR

3
2.9
2.8
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0

DEPTH : 1.50 m

Cohesion (Kg/cm2)
= 0.25
Angle of Internal Friction = 12e
A

Normal Stress (Kg/cm2)

Document Name: Geo-Technical Investigation Report

Page-54

KITCO LIMITED

Nilawar Laboratories

Direct Shear Graph


PROJECT : GEO-TECHNICAL INVESTIGATION WORKS FOR

BOREHOLE NO : BH-05

Shear Stress (Kg/cm2)

CONSTRUCTION OF GENX/GE90 ENGINE


OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR

3
2.9
2.8
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0

DEPTH : 1.50 m

Cohesion (Kg/cm2)
= 0.25
Angle of Internal Friction = 11e
A

Normal Stress (Kg/cm2)

Document Name: Geo-Technical Investigation Report

Page-55

KITCO LIMITED

Nilawar Laboratories

Direct Shear Graph


PROJECT : GEO-TECHNICAL INVESTIGATION WORKS FOR

BOREHOLE NO : BH-05

Shear Stress (Kg/cm2)

CONSTRUCTION OF GENX/GE90 ENGINE


OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR

3
2.9
2.8
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0

DEPTH : 3.45 m

Cohesion (Kg/cm2)
= 0.19
Angle of Internal Friction = 17e
A

Normal Stress (Kg/cm2)

Document Name: Geo-Technical Investigation Report

Page-56

KITCO LIMITED

Nilawar Laboratories

Direct Shear Graph


PROJECT : GEO-TECHNICAL INVESTIGATION WORKS FOR

BOREHOLE NO : BH-06

Shear Stress (Kg/cm2)

CONSTRUCTION OF GENX/GE90 ENGINE


OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR

3
2.9
2.8
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0

DEPTH : 1.50 m

Cohesion (Kg/cm2)
= 0.25
Angle of Internal Friction = 13e
A

Normal Stress (Kg/cm2)

Document Name: Geo-Technical Investigation Report

Page-57

KITCO LIMITED

Nilawar Laboratories

Direct Shear Graph


PROJECT : GEO-TECHNICAL INVESTIGATION WORKS FOR

BOREHOLE NO : BH-07

Shear Stress (Kg/cm2)

CONSTRUCTION OF GENX/GE90 ENGINE


OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR

3
2.9
2.8
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0

DEPTH : 4.50 m

Cohesion (Kg/cm2)
= 0.22
Angle of Internal Friction = 15e
A

Normal Stress (Kg/cm2)

Document Name: Geo-Technical Investigation Report

Page-58

KITCO LIMITED

Nilawar Laboratories

Direct Shear Graph


PROJECT : GEO-TECHNICAL INVESTIGATION WORKS FOR

BOREHOLE NO : BH-08

Shear Stress (Kg/cm2)

CONSTRUCTION OF GENX/GE90 ENGINE


OVERHAUL WORKSHOP AT AIR INDIA MRO,
MIHAN SEZ, NAGPUR

3
2.9
2.8
2.7
2.6
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0

DEPTH : 3.00 m

Cohesion (Kg/cm2)
= 0.23
Angle of Internal Friction = 13e
A

Normal Stress (Kg/cm2)

Document Name: Geo-Technical Investigation Report

Page-59

KITCO LIMITED

Nilawar Laboratories

e log p CURVE
PROJECT :

Soil Investigation for proposed construction of


GENX/GE90 Engine Overhaul Workshop at Air India
MRO, Mihan SEZ

BOREHOLE NO : BH-01
DEPTH : 3.00 m

0.690

0.670

0.650

0.630

VOID RATIO (e)

0.610

0.590

0.570

0.550

0.530

0.510

0.490

0.470
0.1

Pc = 2.00 Kg/cm2

10

Pressure in Kg/cm2

Document Name: Geo Technical Report

Page-60

KITCO LIMITED

Nilawar Laboratories

e log p CURVE
PROJECT :

Soil Investigation for proposed construction of


GENX/GE90 Engine Overhaul Workshop at Air India
MRO, Mihan SEZ

BOREHOLE NO : BH-03
DEPTH : 1.95 m

0.680

0.660

0.640

0.620

VOID RATIO (e)

0.600

0.580

0.560

0.540

0.520

0.500

0.480

0.460
0.1

Pc = 2.05 Kg/cm2

10

Pressure in Kg/cm2

Document Name: Geo Technical Report

Page-61

KITCO LIMITED

Nilawar Laboratories

e log p CURVE
PROJECT :

Soil Investigation for proposed construction of


GENX/GE90 Engine Overhaul Workshop at Air India
MRO, Mihan SEZ

BOREHOLE NO : BH-04
DEPTH : 1.50 m

0.705

0.685

0.665

0.645

VOID RATIO (e)

0.625

0.605

0.585

0.565

0.545

0.525

0.505
0.1

Pc = 2.15 Kg/cm2

10

Pressure in Kg/cm2

Document Name: Geo Technical Report

Page-62

KITCO LIMITED

Nilawar Laboratories

e log p CURVE
PROJECT :

Soil Investigation for proposed construction of


GENX/GE90 Engine Overhaul Workshop at Air India
MRO, Mihan SEZ

BOREHOLE NO : BH-05
DEPTH : 1.50 m

0.720

0.700

0.680

0.660

VOID RATIO (e)

0.640

0.620

0.600

0.580

0.560

0.540

0.520

0.500
0.1

Pc = 2.00 Kg/cm2

10

Pressure in Kg/cm2

Document Name: Geo Technical Report

Page-63

KITCO LIMITED

Nilawar Laboratories

e log p CURVE
PROJECT :

Soil Investigation for proposed construction of


GENX/GE90 Engine Overhaul Workshop at Air India
MRO, Mihan SEZ

BOREHOLE NO : BH-06
DEPTH : 1.50 m

0.710

0.690

0.670

0.650

VOID RATIO (e)

0.630

0.610

0.590

0.570

0.550

0.530

0.510

0.490
0.1

Pc = 2.10 Kg/cm2

10

Pressure in Kg/cm2

Document Name: Geo Technical Report

Page-64

KITCO LIMITED

Nilawar Laboratories

e log p CURVE
PROJECT :

Soil Investigation for proposed construction of


GENX/GE90 Engine Overhaul Workshop at Air India
MRO, Mihan SEZ

BOREHOLE NO : BH-07
DEPTH : 4.50 m

0.630

0.610

0.590

VOID RATIO (e)

0.570

0.550

0.530

0.510

0.490

0.470

0.450
0.1

Pc = 1.90 Kg/cm2

10

Pressure in Kg/cm2

Document Name: Geo Technical Report

Page-65

KITCO LIMITED

Nilawar Laboratories

e log p CURVE
PROJECT :

Soil Investigation for proposed construction of


GENX/GE90 Engine Overhaul Workshop at Air India
MRO, Mihan SEZ

BOREHOLE NO : BH-08
DEPTH : 3.00 m

0.630

0.610

0.590

VOID RATIO (e)

0.570

0.550

0.530

0.510

0.490

0.470

0.450
0.1

Pc = 1.95 Kg/cm2

10

Pressure in Kg/cm2

Document Name: Geo Technical Report

Page-66

CORE BOX OF BH-1

CORE BOX OF BH-3

Page-67

CORE BOX OF BH-4

CORE BOX OF BH-5

Page-68

CORE BOX OF BH-6

CORE BOX OF BH-7

Page-69

CORE BOX OF BH-8

Page-70

10

11

12

G
25

00

BH2

BH3

G
00
25
1
R

7100

GAS BANK

10000
6700

37064

37064

37064

29764

2000

29264

10000

16500

10m WIDE ROAD

72670

87670

BH7

BH8

54270

ENGINE WORK SHOP


AREA = 11667.288 SQ.M

29264

7300

10m WIDE ROAD

16571

8300

18400

BH1

9100

16071

R1

9000

155100

10000

1500

10m WIDE ROAD

7300

23571

29764

1500

1070

BH6

BH5

16071

BH4

9000

1500

162400

0
50

2
R1

9500

185830

MRO FACILITY BLOCK

10m WIDE ROAD

10m WIDE ROAD

10m WIDE ROAD

10m WIDE ROAD

ENERGY BLOCK

NOTE:
1. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS ARE IN METERS
2. ONLY WRITTEN DIMENSIONS SHOULD BE FOLLOWED

BORE HOLE LOCATION

DESIGNED

KITCO Ltd.

CHECKED
DRAWN

- DIMENSION MAY VARY AS PER SITE MEASUREMENT

(Estd. in 1972 by IDBI & Govt. of Kerala)

Neethu

PUTHIYA ROAD - NH BYPASS, KOCHI - 28

CLIENT:

CHECKED

AIR INDIA LTD.

APPROVED

PROJECT:PMC
SCALE

UNIT
SL.No.

PARTICULARS

INITIAL

SERVICES FOR CONSTRUCTION OF GEnx. / GE90

1 : 500
mm.

TITLE:

BORE HOLE LOCATION

DATE

DATE

04.12.2014
DRG NO:

REV.

DP 757 DRG CL 01 004

SHEET NO:

1 OF 1
Page-71

You might also like