Professional Documents
Culture Documents
NGR CALCULATION Paper-24-10022010 PDF
NGR CALCULATION Paper-24-10022010 PDF
D. Braun
ABB Switzerland
dieter.braun@ch.abb.com
Introduction:
The vast majority of all electric failures are arcing faults. In
the theoretical treatment and for protection considerations
they are mostly seen as steady state faults in combination
with a fault resistance. This is justified in case of 3- and 2phase faults and also for single-phase faults in systems with
low impedance grounded neutral where there is practically no
chance of fault arc extinction. In the case of single-phase
faults in a system with isolated or high impedance grounded
neutral however the electric arc may be extinguished at a
current zero and the system voltage recovers then until to a
certain magnitude when a re-strike occurs followed again by
an arc extinction. This series of events may recur several and
even many times; it is called an intermittent fault.
FIG. 1:
i t1 =
2 20000
If
Rneutral
or
Petersen Coil
fo =
C
Rfault
1
2 1.5L"d 2C g
i t2 = U
LG
2C g
"
d
1.5L
sin 2f o t
2.1
(ignoring R f ),
K1
Cl-g
Rd1
20
G1
Cl-g
Q1 Ra1
M1
L1
K2
10
Rd1
Cl-g
G2
M2
10
Q2
L 1 = Ld" /10
(K1, M1 - K0, M0 grounded,
part of the distributed
voltage sources G1 - G0)
Ra1 = Ra/10
Rd1 = 1530* L 1
Q9
Ra1
L1
K0
M0
Rd1
G0
Cl-g
GN
20
FIG. 3:
GN
GKC
LA
LB
LC
FAULT
GRD
Petersen
Coil
FIG. 4:
FIG. 2:
2.
Intermittent Single Phase Faults in Stator
Windings
In [1] tests with single phase intermittent faults in an urban
8kV cable system with isolated neutral have been described.
Those tests have clearly shown that the arc channel in the
cable insulation between core and sheath behaves like a restriking switch: The transient current is interrupted at current
zero and then the voltage recovers with 50Hz and a re-strike
occurs if the voltage has reached a certain level. Surprising at
these tests has been, that the arc current was interrupted
already after the first half-cycle of the recharge current it2.
This process of arc extinction and re-strike showed to be
repeated almost regularly.
Therefore it seems reasonable to suppose that a stator
winding behaves similarly and that intermittent faults occur
also in generators.
It is the aim of the following analyses to simulate such
phenomena in generator windings and to assess the
consequences on methods of grounding and fault protection
of synchronous generators.
CGENERATOR
CSURGE + DUCTS
CSURGE + XFORMER
(DISTRIBUTED)
3
inserted between generator neutral and ground a HV
resistance or a Petersen coil tuned to the total capacitance to
ground of FIG. 4.
2.3
3.1
Case 1
This is the classical textbook case, i.e. a persistent singlephase-to-ground fault at the generator terminals.
3. Analysis
Discussion
of
Various
Cases,
Results,
Case
No
Neutral
high resist.
time
t2
max.
Re-strikes
Energy in
healthy ph.
per
fault resist.
[%]
[ms]
[A]
[kHz]
[p.u.]
cycle
[J]
100
440
4.7
2.18
140 + 9.4/cycle
2)
2)
"
100
5.0
440
4.7
2.18
140 + 220/cycle
"
100
0.4
440
4.7
2.18
1402) + 210/cycle
"
100
0.2
440
4.7
2.18
140 + 160/cycle
"
20
5.0
80
5.3
1.23
5 + 8/cycle
resonant
100
440
4.7
2.18
140 + 1/cycle
resonant
100
5.0
440
4.7
2.18
1/10
1402) + 11/cycle 3)
1)
3)
2)
Table I
Results
Fault at Arcing
grounding winding
FIG. 5:
2)
2)
2)
4
transients are produced in the healthy phases jeopardizing the
stator insulation.
FIG. 6:
FIG. 7:
FIG. 8:
3.2
Case 6
A persistent fault with neutral grounding via Petersen coil
results in the same transient part of the fault current as for
Case 1. The steady state fault current however is now close to
zero, depending on the degree of compensation and the
resistive part of the Petersen coil. The shapes of phase
5
voltages L-G and zero sequence voltage are identical to those
of Case 1 (no plot).
Case 7, same as Case 6, but with arc extinctions and restrikes
Now a quite different picture shows compared to resistive
grounding (Case 2). After arc extinction the voltage in the
affected phase recovers extremely slowly due to exact tuning
of the resonant circuit (FIG. 9).
4.
FIG. 9:
Conclusions
From tests in an MV cable system with isolated neutral it
can be concluded that single phase faults in the stator
insulation of a synchronous generator are in the vast
majority arcing faults which are characterised by a
sequence of arc extinctions and re-strikes.
An analysis of the transient single phase fault current in
a generator step-up transformer system with high
impedance grounded neutral which is normal for
synchronous generators shows that after an extremely
high and short discharge current of the capacitance of the
faulted phase an oscillatory damped recharge current
follows, the first amplitude of which is about 6080
times higher than the final steady state capacitive fault
current.
Simulations with arc-extinctions and re-strikes of the
single phase fault current in a typical generator step-up
transformer system (modelled with distributed sources
and generator elements) demonstrate quite clearly that
for a high resistance grounded neutral intermittent faults
may occur with a high cadence (2 extinctions / re-strikes
per cycle). The energy absorbed in the fault resistance
and caused by the damped transient recharge current is
by a factor of 20 higher than that caused by the small
steady state fault current. It is the intermittent high
transient current which is responsible for heavy iron
burning (welding) and insulation damages.
The interval between arc extinction and re-strike in the
faulted insulation is substantially prolonged by using a
Petersen coil instead of a high resistance for grounding
of the generator neutral. This way the energy absorption
in the fault resistance and consequently the damage may
be reduced by a factor of 20.
From this point of view neutral grounding of
synchronous generators via Petersen coil is far superior
to high resistance grounding.
For fault detection the signal of the zero sequence
voltage is sufficient for a high percentage of the stator
winding. Protection of 100% of the stator winding
requires
different
methods
(third
harmonic
measurement).
5. References
[1]
[2]
[3]
[4]