Professional Documents
Culture Documents
660 MW Harbin Boiler FSSS Writeup
660 MW Harbin Boiler FSSS Writeup
QS3132003-000-FSSS-Wp-10001
CN-20308
QS3132003
I/A System
Write-up of FSSS Logic ( Included MFT)
R0
Rev
2015-1-22
Date
Qian Lin
Chk
Wei, Liu
Apr
Description
ISSUE
Purpose
Date
A0
First issue
2014.1.5
A1
A2
A3
A4
A5
FOXBORO
By
Checked
Approved
CLIENT
User
Manager
Systems
Manager
Validation
Co-ordinator
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 1 of 39
Revision History
Rev.
0
1
2
3
4
Purpose
First issue
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
Date
Jan. 05 2014
Authors
shiwq
SHANGHAI FOXBORO
:
Page 2 of 39
Table of Contents
Table of Contents .................................................................................................................................................. 3
FSSS ....................................................................................................................................................................... 6
FSSS Design Specification ..................................................................................................................................................... 6
1 Basic architecture ........................................................................................................................................... 6
1.1 Hardware architecture ............................................................................................................ 6
1.2 FSSS FSSS System ................................................................................................................. 7
2 Main functions ................................................................................................................................................ 7
2.1 Common logics ....................................................................................................................... 7
2.2 (MFT) Main fuel trip (MFT) ..................................................................................................... 7
MFTTrip conditions: ................................................................................................................ 7
MFT, Once MFT occurs, system execute the following operation: .......... 9
MFT, Once MFT occurs, hardwire execute the following operation: 10
2.3 Furnace ignition purge ................................................................................................... 11
: ................................................................................................................................................. 11
: ......................................................................................................................................... 12
2.4 (OFT) Oil fuel trip (OFT) ........................................................................................... 12
2.4.1 OFT: LDO OFT conditions .............................................................................................. 12
2.4.2 OFT: HDO OFT conditions ............................................................................................. 13
2.4.3 OFT: LDO reset conditions .................................................................................... 13
2.4.4 OFT:HFO reset conditions ..................................................................................... 13
2.5 Oil leakage test.................................................................................................................. 14
: Light oil leakage test conditions: .................................................................. 14
: Heavy oil leakage test conditions: ................................................................ 15
: Process of oil leakage test: ....................................................................................... 15
2.6
Ignition conditions ................................................................................................ 16
2.6.1 Furnace ignition permission conditions ........................................................ 16
2.6.2 Light oil system ignition permission conditions ............................................ 16
2.6.3 Heavy oil system ignition permission conditions .......................................... 17
2.6.4 Coal ignition permission conditions .............................................................. 17
2.6.5 A~H Coal layer A~H ignition permission ............................................................. 18
2.7 Main oil logic control .................................................................................................. 19
2.7.1 oil supply fast valve ................................................................................................. 19
2.7.2 (10EGB90AA500/10EGI90AA500) Oil return motor operated valve ....................... 20
3 Oil system logics .................................................................................................................................... 20
3.1 Oil burner control ........................................................................................... 20
3.1.1 A1 light oil burner ignition permission conditions............................... 20
3.1.2 A1 light oil ignition trip conditions .................................................................. 21
3.1.3 light oil start ignition sequence ............................................................... 21
3.1.4 light oil stop ignition sequence ................................................................ 22
3.1.5 A1 light oil burner purging ........................................................................... 22
3.2 heavy oil burner control ............................................................................. 23
3.2.1 heavy oil burner ignition permission conditions ................................. 23
3.2.2 heavy oil ignition trip conditions ..................................................................... 23
3.2.3 heavy oil start ignition sequence ............................................................. 24
3.2.4 heavy oil stop ignition sequence ............................................................. 24
3.2.5 heavy oil burner purging.............................................................................. 25
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 3 of 39
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 4 of 39
4.2.15.2
close permission conditions .......................................................................................... 37
4.2.16
burner cooling air damper ................................... Error! Bookmark not defined.
4.2.16.1
auto open conditions ...................................................... Error! Bookmark not defined.
5 Seal air fan .............................................................................................................................. 37
5.1 (A/B )1HFW11AN001/1HFW12AN001Sealing air fan ............................................ 37
6 Scanner air fan ................................................................................................................. 39
6.1 (1HXA01AN001/1HXA02AN001) Fire detection Scanner air fan ........................................ 39
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 5 of 39
NCC 2x660MW
FSSS
FSSS Design Specification
1
Basic architecture
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 6 of 39
Fuel Oil control logic includes oil burners are on-off control, layers are on-off control.
Main functions
SHANGHAI FOXBORO
:
Page 7 of 39
8. <30BMCR2/35s(10TRI01DI010/10TRI01DI011/10TRI01DI012),
trident.
Boiler total air flow low (total air<30%, 2/3 5s delay), hard wired to trident.
9.
After boiler ignition memory, all oil system trip or pulverized mill system trip.
Oil system trip: All HFO and LDO angle valves closed or oil supply fast shutoff valve closed.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 8 of 39
10
In the situation of fuel quantity>20%, HP bypass valve closed and either one of the left side HP main
steam valve closed (including left side HP high steam valve and left side HP control steam valve) and either
right side HP main steam valve closed (including right side HP high steam valve and right side HP control
steam valve), or LP bypass valves closed and either left side LP main steam closed (including left side LP high
steam valve and left side LP control steam valve) and either right side of LP bypass main steam valve closed
(including right side LP high steam valve and right side LP control steam valve)
15. 2/315s (1LAB60CF001 / 1LAB60CF002/
1LAB60CF003)
After Boiler ignition memory, feed water flow low-low2/3, 15s delay.
16.
(1HAD50CT001/1HAD50CT002/1HAD50CT003/1HAD50CT011/1HAD50CT012/1HAD50CT013)
Arch inlet manifold inlet temperature HH (2/3)
17.
MFT trident
Loss of MFT TRICONEX cabinet power.
MFT delay 2 seconds, then Close light/heavy return oil fast valve
3.
Close all light/heavy oil angle valves, purging steam valves and atomization valve.
4.
SHANGHAI FOXBORO
:
Page 9 of 39
8.
10.
Close all attemperating water general valve and motor operated valves and control valve
11.
115
When MFT happened(not caused by FDF or IDF), the secondary air damper should be in manual mode,
maintain its current status percentage. Back into auto mode after 5 min, and set to purging status
percentage.
When MFT happened caused by FDF or IDF, the secondary air damper should maintain its current
percentage, and 100% opened after 1 min.
MFT, Once MFT occurs, hardwire execute the following operation:
1.
To ignition cabinet, igniter stop igniting, close all oil angle valves.
6. /
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 10 of 39
To ETS, to ECS.
9. ESP
To ESP
10.
To sootblow
MFT
MFT set or purge again request exist.
2.
MFT
No MFT conditions
3.
4.
5.
6.
7.
8.
9.
10.
All coal feeder stopped.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 11 of 39
11.
Light/heavy oil fuel fast valve are closed
12.
All light/heavy oil burner angle valves are closed
13.
No flame in furnace
14. 30%<<40%
Total air flow >30%BMCR and <40%BMCR
15. (>55%)
Set secondary air damper at purging position(>55%)
16. >50%
Set aux air damper > 50%
, , ,5.
MFT, , . , 5, ,
MFT
When all purging conditions are satisfied, Pushing start purging to order purging. It will start
5-minute purging. If it occurred MFT during this period, or purge conditions are not satisfied, the purge
would be interrupted and the time count would clear. Otherwise MFT reset automatically after
5-minute purge.
:
4MFT30
If first ignition failed 4 times or no oil gun in service 30 minutes after MFT reset, the furnace need to purge
again, interlock furnace ignition conditions, reset purging finished signal, and purging again request is on.
2.4
MFT
MFT set
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 12 of 39
2.
2
Any light oil angel valve not close, light oil main supply oil pipe pressure low low, 2s delay.
3.
2
Any light oil angel valve not close, light oil compressed air main pipe pressure low low, 2s delay.
4.
Any light oil angel valve not close, light oil supply fast valve is not open.
5.
Any light oil angel valve not close, light oil return fast valve is not open.
6.
CRTOFT
Manual LDO OFT in CRT.
MFT
MFT set
2.
2
Any heavy oil angel valve not close, heavy oil main supply oil pipe pressure low low, 2s delay.
3.
2
Any heavy oil angel valve not close, heavy oil compressed air main pipe pressure low low, 2s delay.
4.
Any heavy oil angel valve not close, heavy oil supply fast valve is not open.
5.
Any heavy oil angel valve not close, heavy oil return fast valve is not open.
6.
CRTOFT
Manual HFO OFT in CRT.
OFT
No light oil OFT conditions
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 13 of 39
OFT
No heavy oil OFT conditions
OFT, :
When light OFT occurs, below functions are executed automatically:
3s,
Delay 3s, close light oil return oil fast valve
OFT, :
When heavy OFT occurs, below functions are executed automatically:
3s,
as in Light oil
SHANGHAI FOXBORO
:
Page 14 of 39
Start 3-minute oil pressure monitoring process. If the main oil pipe pressure change less than the
setpoint value (0.3Mpa), it shows leakage test succeed in this step.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 15 of 39
4. 60s
Open oil return valve, releases the oil in the pipe, and close the oil return valve in 60s.
5. 30.3Mpa
Start 3-minute oil pressure monitoring process. If the main oil pipe pressure change less than the set
point value (0.3Mpa), it shows leakage test succeed in this step.
6.
The leakage test end.
,
In addition, the oil leakage test can be taken by bypass to come into being successful status forcibly.
SHANGHAI FOXBORO
:
Page 16 of 39
2.6.4
1.
Furnace ignition permission
2.
The secondary air temperature is normal.
3.
Either of seal air fan is running.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 17 of 39
2.6.5
1. A()
Coal layer A ignition permission(OR)
AB
LDO AB layer in service
B>50%BC
Coal layer B feeder load > 50%, and HFO layer BC in service
B>50%>??W
Coal layer B feeder load > 50%, and load > ??W
2. B()
Coal layer B ignition permission(OR)
AB
LDO AB layer in service
BC
HFO BC layer in service
A>50%>??W
Coal layer A feeder load > 50%, and load > ??W
C>50%>??W
Coal layer C feeder load > 50%, and load > ??W
3. C()
Coal layer C ignition permission(OR)
AB, B>50%
LDO AB layer in service, and coal layer B feeder load > 50%
BC
HFO AB layer in service
B>50%>??W
Coal layer B feeder load > 50%, and load > ??W
D>50%>??W
Coal layer D feeder load > 50%, and load > ??W
4. D()
Coal layer D ignition permission(OR)
BC, C>50%
HFO BC layer in service, and coal layer C feeder load > 50%
C>50%>??W
Coal layer C feeder load > 50%, and load > ??W
5. E()
Coal layer E ignition permission(OR)
EF
HFO EF layer in service
FGF>50%
HFO FG layer in service, and coal layer F feeder load > 50%
F>50%>??W
Coal layer F feeder load > 50%, and load > ??W
6. F()
Coal layer F ignition permission(OR)
EF
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 18 of 39
Open conditions:
MFT
No MFT
Interlock close:
MFT
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 19 of 39
MFT
OFT
OFT
2.7.2 (10EGB90AA500/10EGI90AA500)
Interlock close:
MFT2
MFT delay 2 seconds
OFT 2
OFT delay 2 seconds
CRT
There are three ways to control oil burner: single activation, layer activation, and in-site control.
In single control mode, we can start or stop the selected oil burner through sequence panel in CRT;
In layer control mode, we can automatically diagonally start or stop a certain layer of the oil burner
through CRT soft-hand control.
3.1 Oil burner control
SHANGHAI FOXBORO
:
Page 20 of 39
CRT
CRT
When these conditions are satisfied, CRT operator station in the CRT display the signal of "permit ignition".
When ignition condition of all oil guns is satisfied, the oil gun can be put into operation. its taken in account to
provide the staff with the flexibility of operating single or one-layer burner when designing the system.
When staff launches a designated group of ignition burners through CRT operation, the system can open
the fast valve and atomizing valve orderly. If in a set period of time, any oil gun has not been ignited,
corresponding fast valve, atomizing valves will automatically shut down, and "ignition failure" alarm triggers.
3.1.2 A1 light oil ignition trip conditions
1. MFT
MFT
2. OFT
Light oil OFT
3. 10s2s
inlet oil valve not close in 10s, no light oil flame detected, 2s delay.
4.
In normal startup, oil inlet valve not opened..
5.
Manual stop LDO ignition start sequence.
SHANGHAI FOXBORO
:
Page 21 of 39
When A1 light oil burner trip condition exist, then execute light oil burner stop sequence automatically. Stop
sequence also include purging step, when light oil gun purging request signal and purging permission
conditions are on, then execute purging step in stop sequence, otherwise when light oil purging interlock
signal or purging permission conditions are on, then bypass all the purging step.
1.
Close light oil inlet valve.
2.
Insert light oil gun. (purge step)
3.
Once A1 light oil inlet valve not closed, then light oil purge request signal is on, after 6 steps in A1 light
oil stop ignition sequence is finished, reset this signal.
2. light oil purge permission conditions
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 22 of 39
MFT
MFT
OFT
OFT
A1
A1
1. MFT
MFT
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 23 of 39
2. OFT
Heavy oil OFT
3. 10s2s
inlet heavy oil valve not close in 10s, no heavy oil fire detected, 2s delay.
4.
In normal startup, heavy oil inlet valve not opened.
5. 1HHA11CU103XB01
heavy oil scanner fault.
6.
Manual stop HFO ignition start sequence.
When heavy oil burner trip condition exist, then execute light oil burner stop sequence automatically. Stop
sequence also include purging step, when heavy oil gun purging request signal and purging permission
conditions are on, then execute purging step in stop sequence, otherwise when heavy oil purging interlock
signal or purging permission conditions are on, then bypass all the purging step.
1.
Close heavy oil inlet valve.
2.
Insert heavy oil gun. (purge step)
3.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 24 of 39
When start igniting, open heavy oil purging valve, open heavy oil atomization valve. (purge step)
4. 3,
3 minutes later, close heavy oil purging valve and heavy atomization valve. (purge step)
5.
Retract heavy oil gun. End of sequence.
3.2.5 heavy oil burner purging
1. heavy oil purging request
Once heavy oil inlet valve not closed, then heavy oil purge request signal is on, after 3 steps in heavy oil
stop ignition sequence is finished, reset this signal.
2. heavy oil purge permission conditions
MFT
MFT
OFT
OFT
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 25 of 39
CRT
The control ways of pulverized coal burner are the remote control, sequence-program control, and also
flame detector monitoring systems. Remote operation means that the operator can start or stop the coal by CRT
operation station respectively; Program-controlled operation is to start or stop coal chain gates, coal feeder, coal
mill, dampers and other equipments in accordance with unit control sequence, the logic program provisions and
interlock conditions.
The controlled objects in the process of start/stop are the coal feeder, the mill, valve, etc.
SHANGHAI FOXBORO
:
Page 26 of 39
gate open
gate open
7 ,
Commandopen coal feeder outlet damper, coal feeder inlet damper, lift grinding roller
Feedback:coal feeder outlet&inlet damper opened, grinding roller lifted in position.
8
60
Commandstart mill main motor.
Feedback:mill main motor started and 60s delay.
9
, 30s
Commandstart coal feeder.
Feedback:coal feeder started with minimum quantity, 30s delay.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 27 of 39
10
SHANGHAI FOXBORO
:
Page 28 of 39
SHANGHAI FOXBORO
:
Page 29 of 39
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 30 of 39
include PA hdr
pressure low
MFT
2.
Both PA fan stopped.
3. 4/4,5
Mill outlet damper closed (4/4) while mill motor is running5 sec delay.
4. >120
Mill separator outlet temperature >120.
5.
Mill PA air flow low low.
6. >120
Mill grinding roller lube oil temperature>120.
7. 4/4,2
Loss of flame (4/4)2 sec delay.
8. <2.0Mpa
Hydraulic oil pump stopped or outlet oil pressure low <2.0Mpa
9. >130
Mill motor stator winding temperature >130
10. >85
Mill motor bearing temperature >85.
11. >85
Mill motor winding iron core temperature >85.
12.
Differential pressure between seal air and PA air is low
13. RB
Runback.
4.2.1.3 interlock device as below after mill trip condition
satisfied:
1.
Trip mill motor.
2.
Trip coal feeder.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 31 of 39
3.
Close coal feeder outlet valve.
4.
Close cold&hot PA air damper&valve.
5.
Close mill outlet damper.
6.
Close mill seal air inlet valve.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 32 of 39
SHANGHAI FOXBORO
:
Page 33 of 39
(,60s)
Mill grinding roller fallen in position.
4.2.8
4.2.9
coal feeder
2.
Coal feeder outlet damper opened.
3.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 34 of 39
feeder fault to be
included
SHANGHAI FOXBORO
:
Page 35 of 39
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 36 of 39
Start permissive:
No trip conditions
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 37 of 39
Stop permissive:
All mills are stopped.
or
AB
SAF A and SAF B running and header pipe pressure normal
Interlock start:
<=6Kpa
When FAN A standby button is on , and start condition for seal Fan is satisfied, the differential pressure
between seal air main pipe and heat primary air main pipe is low and the other seal air fan is running;
When FAN A standby button is on, and start condition for seal Fan is satisfied, another seal fan tripped
Protect stop:
PA fan all stopped
1302s
Motor stator winding temperature > 130 (2/3), 2s delay.
85
Motor bearing temperature > 85.
85
Bearing temperature >85.
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 38 of 39
Start permissive:
Interlock start:
FAN A standby button is on and outlet pressure of Flame check cooling fan is low low
Stop permissive:
MFT12
MFT delay 12 hours
or
Issue: A1
Revision Date:2013-09-04
Revision Status: As comment
SHANGHAI FOXBORO
:
Page 39 of 39