Professional Documents
Culture Documents
Operation & Maintenance Instructions Manual: FI 3 0 3 ME
Operation & Maintenance Instructions Manual: FI 3 0 3 ME
Operation & Maintenance Instructions Manual: FI 3 0 3 ME
INSTRUCTIONS MANUAL
F I
3 0 3 M E
smar
www.smar.com
web: www.smar.com/contactus.asp
Introduction
INTRODUCTION
The FI303 is from the first generation of Profibus PA devices. It is a converter mainly intended for
interface of a Profibus PA system to control valve or other actuators. The FI303 produces a 4-20 mA
output proportional to input received over the Profibus PA network. The digital technology used in
the FI303 enables an easy interface between the field and the control room and several interesting
features that reduce considerably the installation, operation and maintenance costs.
The FI303 is part of Smar's complete 303 line of Profibus PA devices.
Profibus PA, is not only a replacement for 4-20 mA or intelligent/smart transmitter protocols, it
contains much more.
The digital technology used in the FI303 enables the choice of several types of transfer functions, an
easy interface between the field and the control room and several interesting features that
considerably reduce the installation, operation and maintenance costs.
Some of the advantages of bi-directional digital communications are known from existing smart
transmitter protocols: Higher accuracy, multi-variable access, remote configuration and diagnostics,
and multi-dropping of several devices on a single pair of wires.
The system controls variable sampling, algorithm execution and communication so as to optimize
the usage of the network, not loosing time. Thus, high closed loop performance is achieved.
Using Profibus technology, with its capability to interconnect several devices, very large control
schemes can be constructed. In order too be user friendly the function block concept was
introduced.
The FI303, like the rest of the 303 family, has some Function Blocks built in, like Analog Output and
Transducer and Display Blocks.
The need for implementation of Fieldbus in small as well as large systems was considered
when developing the entire 303 line of Profibus-PA devices. They have common features
and can configured locally using a magnetic tool, eliminating the need for a configuration
tool or console in many basic applications.
Get the best result of the FI303 by carefully reading these instructions.
NOTE
In case of using Simatic PDM as the configuration and parameterization tool, Smar
recommends that the user does not apply the option "Download to Device". This function
can improperly configure the field device. Smar recommends that user make the use of the
option "Download to PG / PC" and then selecting the Device Menu, use the menus of the
transducer, function and display blocks acting specifically, according to each menu and
method for reading and writing.
III
Waiver of responsibility
The contents of this manual abides by the hardware and software used on the current equipment
version. Eventually there may occur divergencies between this manual and the equipment. The
information from this document are periodically reviewed and the necessary or identified corrections
will be included in the following editions. Suggestions for their improvement are welcome.
Warning
For more objectivity and clarity, this manual does not contain all the detailed information on the
product and, in addition, it does not cover every possible mounting, operation or maintenance
cases.
Before installing and utilizing the equipment, check if the model of the acquired equipment complies
with the technical requirements for the application. This checking is the users responsibility.
If the user needs more information, or on the event of specific problems not specified or treated in
this manual, the information should be sought from Smar. Furthermore, the user recognizes that the
contents of this manual by no means modify past or present agreements, confirmation or judicial
relationship, in whole or in part.
All of Smars obligation result from the purchasing agreement signed between the parties, which
includes the complete and sole valid warranty term. Contractual clauses related to the warranty are
not limited nor extended by virtue of the technical information contained in this manual.
Only qualified personnel are allowed to participate in the activities of mounting, electrical connection,
startup and maintenance of the equipment. Qualified personnel are understood to be the persons
familiar with the mounting, electrical connection, startup and operation of the equipment or other
similar apparatus that are technically fit for their work. Smar provides specific training to instruct and
qualify such professionals. However, each country must comply with the local safety procedures,
legal provisions and regulations for the mounting and operation of electrical installations, as well as
with the laws and regulations on classified areas, such as intrinsic safety, explosion proof, increased
safety and instrumented safety systems, among others.
The user is responsible for the incorrect or inadequate handling of equipments run with pneumatic
or hydraulic pressure or, still, subject to corrosive, aggressive or combustible products, since their
utilization may cause severe bodily harm and/or material damages.
The field equipment referred to in this manual, when acquired for classified or hazardous areas, has
its certification void when having its parts replaced or interchanged without functional and approval
tests by Smar or any of Smar authorized dealers, which are the competent companies for certifying
that the equipment in its entirety meets the applicable standards and regulations. The same is true
when converting the equipment of a communication protocol to another. In this case, it is necessary
sending the equipment to Smar or any of its authorized dealer. Moreover, the certificates are
different and the user is responsible for their correct use.
Always respect the instructions provided in the Manual. Smar is not responsible for any losses
and/or damages resulting from the inadequate use of its equipments. It is the users responsibility to
know and apply the safety practices in his country.
IV
Table Of Contents
TABLE OF CONTENTS
SECTION 1 - INSTALLATION ..................................................................................................................... 1.1
GENERAL ............................................................................................................................................................................... 1.1
MOUNTING ............................................................................................................................................................................ 1.1
TOPOLOGY AND NETWORK CONFIGURATION ................................................................................................................. 1.4
INTRINSIC SAFETY BARRIER .............................................................................................................................................. 1.5
JUMPER CONFIGURATION .................................................................................................................................................. 1.5
POWER SUPPLY ................................................................................................................................................................... 1.5
INSTALLATION IN HAZARDOUS AREAS ............................................................................................................................. 1.6
EXPLOSION/FLAME PROOF ................................................................................................................................................. 1.6
INTRINSICALLY SAFE ........................................................................................................................................................... 1.6
VI
Installation Flowchart
Installation Flowchart
Start
Yes
No
Configure the engineering unit.
Yes
Is the indication correct?
No
See section 4 - Maintenance
OK
VII
VIII
Section 1
INSTALLATION
General
NOTE
The installation carried out in hazardous areas should follow the recommendations of the IEC60079-14
standard.
The overall accuracy of measurement and control depends on several variables. Although the
converter has an outstanding performance, proper installation is essential, in order to maximize its
performance.
Among all factors, which may affect converter accuracy, environmental conditions are the most
difficult to control. There are, however, ways of reducing the effects of temperature, humidity and
vibration.
Locating the converter in areas protected from extreme environmental changes can minimize
temperature fluctuation effects.
In warm environments, the converter should be installed to avoid, as much as possible, direct exposure to the sun. Installation close to lines and vessels subjected to high temperatures should also be
avoided.
Use of sunshades or heat shields to protect the converter from external heat sources should be
considered, if necessary.
Humidity is fatal to electronic circuits. In areas subjected to high relative humidity, the O-rings for the
electronics cover must be correctly placed. Removal of the electronics cover in the field should be
reduced to the minimum necessary, since each time it is removed the circuits are exposed to the
humidity. The electronic circuit is protected by a humidity proof coating, but frequent exposures to
humidity may affect the protection provided. It is also important to keep the covers tightened in
place. Every time they are removed, the threads are exposed to corrosion, since painting cannot
protect these parts. Code-approved sealing methods on conduit entering the converter should be
employed.
Mounting
Using the bracket, the mounting may be done in several positions, as shown on Figure 1.3 Dimensional Drawing and Mounting Positions.
For better visibility, the digital indicator may be rotated in steps of 90 (See the section Maintenance
Procedures).
Output Wiring
The output is in fact a current link. An external power source is therefore necessary. The FI303
controls the current in the loop. (See Figure 1.4 - Output Connections). The three channels have a
common ground for the external power supply.
The output load is limited by the voltage of the external power supply. Please refer to the load graph
to determine the maximum load.
On loss of power the output will be uncertain. If power is maintained, but communication is lost, the
output may be pre-configured to freeze or go to a safe value.
Electric Wiring
Access the wiring block by removing the Electrical Connection Cover. This cover can be locked
closed by the cover locking screw (See Figure 1.1 - Cover Locking). To release the cover, rotate the
locking screw clockwise.
1.1
H1 BUS
GROUND
TERMINAL
OUTPUT
GROUND
TERMINAL
OUTPUT
TERMINALS 3
COMUNICATION
TERMINALS
1.2
Installation
PLUG
CONDUIT
CONNECTION
COMMUNICATIONS
TERMINAL
PLUG
WALL OR
PANEL MOUNTING
MOUNTING BRACKET
PIPE 2"
1.3
1.4
Installation
Jumper Configuration
In order to work properly, the jumpers J1 and W1 located in the FI303 main board must be correctly
configured (See Table 1.1 - Description of the Jumpers).
J1
W1
Power Supply
The FI303 receives power from the bus via the signal wiring. The power supply may come from a
separate unit or from another device such as a controller or DCS.
The voltage should be between 9 to 32 Vdc for non-intrinsic safe applications.
A special requirement applies to the power supply used in an intrinsically safe bus and depends on
the type of barrier used.
Use of PS302 is recommended as power supply.
1.5
Explosion/Flame Proof
WARNING
In Explosion-Proof installations the cable entries must be connected or closed using metal cable
gland and metal blanking plug, both with at least IP66 and Ex-d certification.
The standard plugs provided by Smar are certified according to CEPEL certificate. If the plug
needs to be replaced, a certified plug must be used.
The electrical connection with NPT thread must use waterproofing sealant. A non-hardening
silicone sealant is recommended.
For NEMKO ATEX certificate please to follow the installation guidelines in hazardous locations
below: Group II Category 2G, Ex d, Group IIC, Temperature Class T6, EPL Gb U = 28VDC
Ambient Temperature: -20 to 60C for T6
Environmental Protection: IP66/687 or IP66W/687W
The electrical connection available are - 14NPT and M20x1,5.
Cable entries must be connected or closed using metal cable gland and metal blanking plug,
both with at least IP66 and Ex-d certification or any appropriate ATEX approved metal cable
gland and metal blanking plug. Do not remove the transmitter covers when power is ON.
Intrinsically Safe
WARNING
In hazardous zones with intrinsically safe or non-incendive requirements, the circuit entity
parameters and applicable installation procedures must be observed.
To protect the application the transmitter must be connected to a barrier. Match the parameters
between barrier and the equipment (Consider the cable parameters). Associated apparatus
ground bus shall be insulated from panels and mounting enclosures. Shield is optional. If used, be
sure to insulate the end not grounded. Cable capacitance and inductance plus Ci and Li must be
smaller than Co and Lo of the associated Apparatus.
It is not recommended to remove the transmitter cover when the power is ON.
1.6
Section 2
OPERATION
Functional Description - Electronics Refer to the block diagram
Receives the signal from the CPU and converts it to an analog voltage, used by the current
control.
Current Control
Controls the current of the channel according the data received from the CPU.
Signal Isolator
Its function is to isolate the data signal between the output and the CPU.
2.2
Section 3
CONFIGURATION
One of the many advantages of using Fieldbus technologies is that device configuration is
independent of the configuration software. The FI303 may be configured by a third party terminal or
operator console as Smars configurators ProfibusView or AssetView for FDT.
The FI303 contains three output transducer blocks, one physical block, one display transducer
block, three analog output function blocks.
Function Blocks are not covered in this manual. For further explanation and details of function
blocks, see the Function Blocks Instruction Manual.
The transducer block isolates the function block of the specific I/O hardware, like sensors and
actuators, for example. Transducer block controls access to I/O through manufacturer specific
implementation. This allows the transducer block to execute the algorithm, as frequently as
necessary to obtain good data from sensors without burdening the function blocks that use the data.
It also insulates the function blocks from the manufacturer specific characteristics of certain
hardware.
By accessing the hardware, the transducer block can get data from I/O or passing control data to it.
The connection between Transducer block and Input/Output Function blocks is called channel.
Normally, transducer blocks perform functions, such as linearization, characterization, temperature
compensation, control and exchange data to/from hardware.
In order to assure correct values in the offline configuration, when using download function of
Simatic PDM, please make sure you have done the upload firstly.
Offline Configuration
1. First run Download to PG/PC option to assure valid values.
2. Run after the Menu Device option to configure the required parameters using the related menus.
NOTE
It is not advisable to use the Download to Device option. This function can misconfigure the equipment.
3.1
Configuration
Terminal Number
It is the parameter, which makes reference to a channel value, which in its turn, is sent via internally
from the specified transducer output to function block.
It starts at channel one (1) for transducer number one until channel three (3) for transducer number
three.
The channel number of the AO block is related to the transducers terminal number. Channel
number 1, 2, 3 corresponds bi-univocally to the terminal block with the same number. Therefore, all
user has to do is choosing combinations: (1.1), (2.2), (3.3) for (CHANNEL, BLOCK) respectively.
CAL_MIN_SPAN
CONVERTER_SER_NUM
CONVERTER_MAN
CONVERTER_MAINT_DATE
FEEDBACK_VALUE
TERMINAL_NUMBER
TAB_ACTUAL_NUMBER
3.2
DESCRIPTION
The actual value variable for the final control element in units of OUT_SCALE. Status
BAD will indicate a hardware problem.
This is the output conversion of the linearisated value using the high and low scale. The
engineering unit is mA (1211).
This parameter contains the highest calibrated value. This parameter indicates where
the converter should be when the setpoint is 100%. The engineering unit used by this
calibration is mA.
This parameter contains the lowest calibrated value. This parameter indicates where
the converter should be when the setpoint is 0%. The engineering unit used by
calibration is mA.
This parameter contains the minimum calibration span value allowed. This minimum
span information is necessary to ensure that when calibration is done, the two
calibrated points (high and low) are not too close together. The engineering unit used
by calibration is mA.
This parameter contains the converter serial number.
Name of converter-manufacturer
The date of last maintenance.
The actual final value of the final control element in units of OUT_SCALE.
The terminal number, which references a channel value, which is sent via internal,
manufacturer-specific from AO function block to the specified transducer. It starts at
one (1) for transducer number one until three (3) for transducer number three.
Contains the actual numbers of entries in the table. It shall be calculated after the
transmission of the table is finished.
TAB_OP_CODE
TAB_STATUS
TAB_X_Y_VALUE
LIN_TYPE
FEEDBACK_CAL
CAL_CONTROL
ACTUATOR_ACTION
SP_RATE_INC
SP_RATE_DEC
SP_HI_LIM
SP_LO_LIM
DESCRIPTION
The index parameter identifies which element of the table is in the X_VALUE and
Y_VALUE parameter currently
TAB_MAX_NUMBER is the maximum size (number of X_VALUE and Y_VALUE
values) of the table in the device.
For device internal reasons (e.g. for calculation), sometimes it is necessary to use a
certain number of table values in minimum. This number is provided in the
TAB_MIN_NUMBER parameter.
The modification of a table in a device influences the measurement or actuation
algorithms of the device. Therefore an indication of a starting and an end point is
necessary. The TAP_OP_CODE controls the transaction of the table.
0: not initialised
1: new operation characteristic, first value (TAB_INDEX=1), old curve cleared
2: reserved
3: last value, end of transmission, check table, swaps the old curve with the new
curve, actualise ACTUAL_NUMBER.
4: delete point of table with actual index (optional), sort records with increasing
Charact-Input-Value, assign new indexes, decrement CHARACT_NUMBER.
5: insert point (Charact-Input-Value relevant) (optional), sort records with increasing
Charact-Input-Value, assign new indexes. Increment CHARACT_NUMBER.
6: replace point of table with actual index (optional).
It is possible to read a table or parts of the table without start an stop an interaction
(TAB_OP_CODE 1 and 3). The start is indicated by set TAB_ENTRY to 1.
It is common to provide a plausibility check in the device. The result of this check is
indicated in the TAB_STATUS parameter.
0: not initialised
1: good (new table is valid)
2: not monotonous increasing (old table is valid)
3: not monotonous decreasing (old table is valid)
4: not enough values transmitted (old table is valid)
5: too many values transmitted (old table is valid)
6: gradient of edge too high (old table is valid)
7: Values not excepted (old values are valid)
8: 127 reserved
> 128 manufacturer specific
The X_Y_VALUE parameter contains one value couple of the table
Type of linearisation.
0 = no linearisation (mandatory)
1 = linearisation table (optional)
240 = Manufacturer specific
249 = Manufacturer specific
250 = Not used
251 = None
252 = Unknown
253 = Special
This parameter should be set with the actual output current during the calibration
procedure.
This parameter controls when the calibration procedure ends. It is necessary since the
user should enter the "analog current" value that he sees at the multi-meter. The device
waits for a flag that tells it when to change from TRIM mode to normal one.
Fail-Safe position for power-loss of the actuator resp. the valve:
0 = not initialized
1 = opening (100%)
2 = closing (0%)
3 = none / remains in actual position
Ramp rate at which upward setpoint changes are acted on in Auto mode, in FV units
per second. If the ramp rate is set to zero or minus infinite then the setpoint will be used
immediately.
Ramp rate at which downward setpoint changes are acted on in Auto mode, in FV units
per second. If the ramp rate is set to zero or plus infinite then the setpoint will be used
immediately.
The setpoint high limit is the highest setpoint operator entry that can be used for the
transducer block.
The setpoint low limit is the lowhest setpoint operator entry that can be used for the
3.3
Configuration
PARAMETERS
BACKUP_RESTORE
XD_ERROR
DESCRIPTION
transducer block.
This parameter allows to save and to restore data according to factory and user
calibration procedures. It has the following options:
1, "Factory Cal Restore",
2, "Last Cal Restore",
3, "Default Data Restore",
4, "Shut-Down Data Restore",
11, "Factory Cal Backup",
12, "Last Cal Backup",
14, "Shut-Down Data Backup",
0, "None".
Indicates the condition of calibration process according to:
{16, "Default value set"},
{22, "Applied process out of range"},
{26, "Invalid configuration for request"},
{27, "Excess correction"},
{28, "Calibration failed"}
The electronic main board serial number.
This parameter is used to indicate EEPROM saving process.
{0, False}
{1, True}
This array of Unsigned 8 bytes contains information about which kind of materials and
mechanical parts have been used for the device. This is part of the Ordering Code
information necessary to buy a spare unit.
XD_ERROR
MAIN_BOARD_SN
EEPROM_FLAG
ORDERING_CODE
Parameter Name
Object
Type
Data Type
Store
Size
Access
Parameter
usage/Type
of Transport
Initial/Default
Value
Mandatory/
Optional
Class
Standard Parameters
13
3.4
VIEW
FINAL_VALUE
DS-33
R/w
C/a
FINAL_VALUE_SCALE
Array
Float
R/w
C/a
4 and 20 mA
10
CAL_POINT_HI
Float
R/w
C/a
20
11
CAL_POINT_LO
Float
R/w
C/a
12
CAL_MIN_SPAN
Float
C/a
13
CONVERTER_SER_NUM
Unsigned32
R/w
C/a
14
CONVERTER_MAN
Octet String
16
R/w
C/a
""
15
CONVERTER_MAINT_DATE
Octet String
16
R/w
C/a
""
16
FEEDBACK_VALUE
DS-33
R/w
C/a
Unsigned8
R/w
C/a
17
TERMINAL_NUMBER
18
TAB_ACTUAL_NUMBER
19
TAB_ENTRY
20
TAB_MAX_NUMBER
21
TAB_MIN_NUMBER
22
TAB_OP_CODE
23
TAB_STATUS
24
TAB_X_Y_VALUE
25
LIN_TYPE
Parameter Name
Object
Type
Data Type
Store
Size
Access
26
FEEDBACK_CAL
Float
R/w
Parameter
usage/Type
of Transport
C/a
CAL_CONTROL
Unsigned8
R/w
C/a
27
28-38
Mandatory/
Optional
Class
M
Initial/Default
Value
NOT USED
39
ACTUATOR_ACTION
Unsigned8
R/w
C/a
40
SP_RATE_INC
float
R/w
C/a
41
SP_RATE_DEC
float
R/w
C/a
42
SP_HI_LIM
float
R/w
C/a
43
SP_LO_LIM
float
R/w
C/a
44
BACKUP_RESTORE
Unsigned8
R/w
C/a
45
XD_ERROR
Unsigned8
C/a
0x10
46
MAIN_BOARD_SN
Unsigned32
R/w
C/a
47
EEPROM_FLAG
Unsigned8
R/w
C/a
Array of
Char
R/w
C/a
48
VIEW
ORDERING_CODE
CYCLIC CONFIGURATION
The profibus network master executes the equipment initialization process through the gsd file,
which has details for hardware and software revision, equipment bus timing and information on the
cyclic data exchange.
The FI303 has 3 function blocks with analog output (AOs) that the class 1 master uses to execute
the cyclic services. Users must choose what configuration best suits their application. If the AO
Block Mode is in AUTO, it will receive the value and the status of the class 1 master setpoint. In
addition, the user may alter this value via a class 2 master if the setpoint status is equal to 0x80
(good), and the following configurations can be chosen:
SP;
SP/CKECKBACK;
SP/READBACK/POSD;
SP/READBACK/POSD/CKECKBACK.
If the AO block is in RCAS, the equipment only receives the setpoint value and status through a
class 1 master, and the status will always be equal to 0xc4 (IA). The following configurations may
be chosen:
SP;
SP/CKECKBACK;
SP/READBACK/POSD;
SP/READBACK/POSD/ CKECKBACK;
RCASIN/RCASOUT;
RCASIN/RCASOUT/ CKECKBACK;
SP/READBACK/RCASIN/RCASOUT/POSD/CHECKBACK.
The example below shows the necessary steps to integrate the FI303 to a PA system. These steps
are applicable to all the equipments on Smar 303 line:
Copy the FI303 gsd file into the search directory of the PROFIBUS configurator, usually called
GSD;
3.5
Configuration
Copy the FI303 bitmap file on the search directory of the PROFIBUS configurator, usually called
BMP;
After choosing the master, define the communication rate. Do not forget that the couplers may
have the following fixed communication rates 45,45 kbits/s (Siemens) or 93,75 kbits/s (P+F) and
variable comm rates up to 12 Mbit/s as instance: SK2 and SK3 from P+F, link IM157 from
Siemns and Smars controllers with embedded couplers (DF95 or DF97);
Choose the configuration via parameterization with the gsd file, according to the application, as
seen previously. Notice that this choice must match the AO blocks operating mode. Under these
conditions mind the status value of the setpoint value, which should be 0x80 (Good) when in
Auto mode, and 0xc4(IA) when in Rcas. Three AO blocks may be operated in the following cyclic
order: AO_1, AO_2 e AO_3. If only 2 AOs are to be applied, there should be: configuration for
the AO_1, configuration for the AO_2 and EMPTY MODULE.
The watchdog condition may be activated, prompting the equipment to enter a fail-safe mode when
detecting a communication loss between the slave and the master equipment. As FI303 will be on a
final element, it is recommended that a fail-safe value be configured.
Using ProfibusView, AssetView FDT from Smar or Simatic PDM from Siemens, for instance, user
may configure parameters of the Transducer block. See Figure 3.2 - Function and Transducer
Blocks.
3.6
3.7
Configuration
3.8
Table handling
It is possible to load and re-load tables into the devices. This table is used for linearisation mostly.
For this procedure the following parameters are necessary:
TAB_INDEX
TAB_X_Y_VALUE
TAB_MIN_NUMBER
TAB_MAX_NUMBER
TAB_OP_CODE
TAB_STATUS
The TAB_X_Y_VALUE parameter contains the value couple of each table entries.
TAB_INDEX parameter identifies which element of the table is current in the TAB_X_ Y_VALUE
parameter (see the following figure).
y_Value
Index
x_Value
1
2
3
4
...
n
x1
x2
x3
x4
...
xn
y_Value
yn
yn-1
y4
y1
y2
y3
y4
...
yn
y3
y2
y1
...
x1
x1
x2
x3
x4
...
x2
x3
x4
xn-1
xn x_Value
xn
x_Value
Tab
y_Value
y1
y2
y3
y4
...
yn
Configuration
This eventual non-linearity may be corrected through the User Table.
User just needs to configure the input values and the correspondent output values in %. Configure a
minimum of two points. These points will define the characterization curve. The maximum number of
points is 8. It is recommended to select the points equally distributed over the desired range or over
a part of the range where more accuracy is required. User needs to set "user defined (table) in the
linearization type field.
3.10
3.11
Configuration
3.12
Output engeneering Unit and Scale will be the same for the transducer block. Note that the allowed
unit is mA.
Selecting Advanced Settings page, user can set the fail-safe conditions.
3.13
Configuration
3.14
In the screen Config Mode Block the user can adjust the operation of the block.
3.15
Configuration
Using Feedback page, the user can monitore and check all values related between the analog block
and the transducer block:
Information
about the
real condition
of transducer
and analog
output block.
3.16
Current Trim
The FI303 provides the capability of making a TRIM in the output channels, if necessary.
TRIM procedure is necessary if the indication of the transducer block output differs from the actual
physical output. The reason may be:
User can check the calibration of the transducer output by measuring the actual current in the output
and compare it with the indication of the device (an appropriate meter must be used). If a mismatch
is detected, a TRIM can be done.
TRIM can be done in two points:
LOWER TRIM: Is used to TRIM the output at the lower range.
UPPER TRIM: Is used to TRIM the output at the upper range.
These two points define the linear characteristic of the output. TRIM in one point is independent
from the other.
There are two ways of doing the TRIM: using local adjustment or using a Configuration Tool (For
example, ProfibusView). When doing the TRIM, make sure you are using an appropriate meter (with
the necessary accuracy).
3.17
Configuration
After entering the desired value, the generated current is corrected according to the desired value
and user can make the correction until the right current value is reached. For this purpose, user
needs to inform the generated current:
Pressing OK, we have. When pressing OK the following window comes up:
User can proceed until the generated current is equal to the desired value:
If the calibrated current is correct, press "No" and a new warning appears:
3.18
When user press "OK", a new window comes up allowing him to enter the desired value of the new
calibrated point and of the upper current. Write for instance 20.0 mA in new value:
After entering the desired value, the generated current is corrected according to this value and user
can make the correction until the right current is reached. For this purpose, the user needs to inform
the generated current:
3.19
Configuration
Pressing OK, it follows:
User can proceed until the generated current is equal to the desired value:
If the calibrated current is correct, press "No" and a new warning appears:
3.20
Lower
Upper
NOTE
Codes for XD_ERROR:
16: Default Value Set
22: Out of range
26: Invalid Calibration request
27: Excessive Correction
See Local Adjust Tree Quick Guide, page 3.29 for more information about Via Local Adjustment.
3.21
Configuration
3.23
Configuration
3.24
The Local Address Change window allows the user to enable/disable the access to change the
equipment address.
Configuration
Always on the LCD interface will be shown two parameters at the same time, switching between the
configured parameter at the LCD-II and the last monitoring parameter. If user does not want to show
two parameters at the same time, it is only needed to set "none" when configure the LCD-II:
Selecting
None, only
the last chosen
monitoring
parameter will
be shown
at LCD.
3.26
With this
option, the
Mode Block
parameter
is shown at
the LCD.
3.27
3.28
LOWER
UPPER
LOWER
OUT_1
26
FEED
BLOCK
24
ADDR
LCD6
ADDR
CONF
TRD1
TRD2
TRD3
AO1
AO2
LCD2
LCD3
LCD4
LCD5
LCD6
AO3
PHY
LCD1
PRMT
ITEM
Span Hole
TGGL
1
ADDR
Zero Hole
Magnetic Tool
UPDT
CONF: option where it is possible to select the LCD to configure. Six options are available: from LCD1 up to LCD6;
BLOCK: option where the user must select the function block that he desires to configure;
PRMT: number correspondent to the relative index of the desired parameter into the chosen function block;
ITEM: configure this option when a selected parameter has sub items to be configured, for example, the OUT_SCALE parameter is compounded by EU at 100%, EU at 0%,
Unit Index and Decimal Point;
TGGL (Toggle): switches from 1 up to 6 configured parameters on the display. If TGGL is equal to 2, for example, the display wil l switch between LCD1 and LCD2;
UPDT: refreshes the display when one of the LCDs are configured. Finalize display configuration by setting "UPDT", after choosing the configuration for the local adjustment.
10
LCD4
With TOGGLE 6
LCD1
LCD2
Follow Steps:
1) Browse until TGGL
2) Select 2
3) Configure LCD 2 with the desired parameter
FEED
LCD5
UPPER
OUT
Follow Steps:
1) Insert magnetic screw driver in zero hole
2) Wait 3 seconds
3) Insert magnetics screw driver in span hole
4) Wait 3 seconds, then MD will appear on display
Configuration
ACTION
Inicializes and rotates through the available functions.
Selects the function shown in the display.
Table 3.4 Purpose of the holes on the Housing
3.29
Configuration
J1 Jumper Connections
If J1 (see figure 3.32) is connected to ON, then simulation mode in the AO block is enabled.
W1 Jumper Connections
If W1 is connected to ON, the local adjustment programming tree is enabled and then important
block parameters can be adjusted and communication can be pre-configured via local adjustment.
OFF
ON
OFF
ON
LOC
ADJ
WR
J1
W1
MAIN BOARD
Place the
magnetic tool in
orifice S and wait
during 5
seconds.
3.30
In order to decrement
the lower value, place
the magnetic tool in
orifice Z to shift the
arrow to the downward
position and then, by
inserting and keeping
the tool in orifice S, it is
possible to decrement
the lower value.
3.31
Configuration
To decrease the upper
value, insert the
magnetic tool in orifice
Z to change the arrow
position downward ().
Remove it and insert it
in the orifice S to
decrease the upper
value.
To decrease the
address value, place
the magnetic tool on
orifice S to change the
arrow position
downward. Insert and
keep the tool to
decrease the address
value
3.32
Cyclical Diagnosis
Via cyclic communication is possible to verify diagnostics from the FI303 using the Profibus Master
Class 1 or even via acyclic communication via Master Class 2. The Profibus-PA devices provide up
to 4 standard diagnoses bytes via Physcial Block (See figure 3.40 and 3.41) and when the most
significant bit of the fourth Byte is "1", the diagnose will extend the information in more 6 bytes.
These Diagnosis bytes can also be monitored via cyclic tools.
= "Error appears"
= "Error disappears"
= "Hardware failure electronics"
= "Not used 25"
= "Not used 26"
= "Not used 27"
= "Memory error"
= "Measurement failure"
= "Device not initialized"
= "Device initialization failed"
;Byte 02
Unit_Diag_Bit(32)
Unit_Diag_Bit(33)
Unit_Diag_Bit(34)
Unit_Diag_Bit(35)
Configuration
Unit_Diag_Bit(36)
Unit_Diag_Bit(37)
Unit_Diag_Bit(38)
Unit_Diag_Bit(39)
= "Coldstart"
= "Maintenance required"
= "Characteristics invalid"
= "Ident_Number violation"
; Extended_Diag
3.34
Unit_Diag_Bit(56)
Unit_Diag_Bit(57)
Unit_Diag_Bit(58)
Unit_Diag_Bit(59)
Unit_Diag_Bit(60)
Unit_Diag_Bit(61)
Unit_Diag_Bit(62)
Unit_Diag_Bit(63)
Unit_Diag_Bit(64)
Unit_Diag_Bit(65)
Unit_Diag_Bit(66)
Unit_Diag_Bit(67)
Unit_Diag_Bit(68)
Unit_Diag_Bit(69)
Unit_Diag_Bit(70)
Unit_Diag_Bit(71)
Unit_Diag_Bit(72)
Unit_Diag_Bit(73)
Unit_Diag_Bit(74)
Unit_Diag_Bit(75)
Unit_Diag_Bit(76)
Unit_Diag_Bit(77)
Unit_Diag_Bit(78)
Unit_Diag_Bit(79)
Unit_Diag_Bit(80)
Unit_Diag_Bit(81)
Unit_Diag_Bit(82)
Unit_Diag_Bit(83)
Unit_Diag_Bit(84)
Unit_Diag_Bit(85)
Unit_Diag_Bit(86)
3.35
Configuration
3.36
Section 4
MAINTENANCE PROCEDURES
General
NOTE
Equipment installed in hazardous atmospheres must be inspected in compliance with the IEC60079-17
standard.
SMAR FI303 PROFIBUS PA to Current Converters are extensively tested and inspected before
delivery to the end user. Nevertheless, during their design and development, consideration was
given to the possibility of repairs by the end user, if necessary.
In general, it is recommended that the end-user do not try to repair printed circuit boards.
Instead, he should have spare circuit boards, which may be ordered from SMAR whenever
necessary.
TROUBLESHOOTING
SYMPTOM
NO QUIESCENT URRENT
Power Supply
Check power supply output. The voltage at the FI303 terminals must be between 9 and 32 VDC.
Electronics Circuit Failure
Check circuit boards for defect by replacing them with spare ones.
Network Connection
Check network connections: devices, power supply, couplers, links and terminators.
Converter Configuration
Check configuration of communication parameters of converter.
NO COMMUNICATION
Network Configuration
Check communication configuration of the network.
Electronics Circuit Failure
Try to replace the converter circuit with spare parts.
Output Terminals Connection
Check wiring polarity and continuity.
Power Supply
Check power supply output. The voltage at the output terminals of FI303 must be between 3 and 45 VDC.
INCORRECT OUTPUTS
Load Resistance
Load resistance must be between 0 and 2000. Note that the maximum value depends on output power
supply voltage.
Calibration
Check calibration of converter.
4.1
Disassembly Procedure
Refer to Figure 4.1 - FI303 Exploded View Make sure to disconnect power supply before
disassembling the converter.
12
11
10
9
8
7
15
6
5
14
4
2
16
13
Maintenance Procedures
To remove the electronic plates (5 and 7) and the display (4), release the lid lock (8) on the
carcass side not bearing the words Field Terminals and unscrew the lid (1).
WARNING
The plates have CMOS components that may be damaged by electrostatic discharges. Follow the right
procedure for handling the CMOS components. The plate should be stored in an electrostatic-proof case.
Loosen both screws (3) that anchors the display and the main circuit board. Gently pull out the
display, and then the main board (5). To remove the output board (7), first unscrew both screws
(6) that anchors it to the housing (9), and gently pull out the board.
Reassembly Procedure
Put output board (7) into housing (9).
Anchor output board with its screws (6).
Place the main plate (5) on the carcass and make sure the pins are connected.
Put display (4) into the housing, observing the four mounting positions. The "" symbol must
point upward.
Anchor the main board and display with their screws (3).
Fit the cover (1) and lock it using the locking screw (8).
Interchangeability
The calibration data on the Inlet plate are stored on the Principal plate EEPROM, reason why
they are said to be match pairs.
ADVERTNCIA
If, for some reason, you separate the input and the main boards, you must do a trim to guarantee
precision of the inputs. With mismatched boards, the factory trim will not be as good as it was.
DESCRIPTION
AssetView FDT
BC1
Fieldbus/RS232 Interface
BT302
Terminator
DF47-17
DF73
HSE/PROFIBUS-DP Controller
DF95/DF97
FDI302
PBI
ProfibusView
PS302/DF52
Power Supply
PSI302/DF53
SD1
4.3
Aluminum
316 SS
Aluminum
316 SS
Cover, Buna-N
Units with indicator
Units without indicator
Units With Indicator
Units Without Indicator
Digital Indicator
Main and Output Circuit Board Assembly
Input Board Screw
Housing in Aluminum
Housing in 316 Stainless Steel
- 14 NPT
M20 x 1.5
PG 13.5 DIN
- 14 NPT
M20 x 1.5
PG 13.5 DIN
Housing in Aluminum
Housing in 316 Stainless Steel
Bichromated Carbon Steel
Bichromated 304 Stainless Steel
Bichromated Carbon Steel
Bichromated 304 Stainless Steel
316 Stainless Steel
316 Stainless Steel
Carbon Steel
Stainless Steel 316
Carbon Steel bolts, nuts, washers
and U-clamp in Stainless Steel
POSITION
CODE
1 and 15
1 and 15
1
1
2
3
3
3
3
4
5 and 7
6
6
8
9
9
9
9
9
9
10
11
12
13
14
14
16
16
16
16
16
16
-
204-0102
204-0105
204-0103
204-0106
204-0122
304-0118
304-0117
204-0118
204-0117
214-0108
400-0318
314- 0125
214-0125
204-0120
400-0312
400-0313
400-0314
400-0315
400-0316
400-0317
204-0114
204-0116
314-0123
204-0124
304-0119
204-0119
400-0808
400-0809
400-0583-11
400-0583-12
400-0810
400-0811
214-0801
214-0802
214-0803
CATEGORY
(NOTE 1)
NOTE
1234-
4.4
For category A, it is recommended to keep, in stock, 25 parts installed for each set, and for category B, 50.
It includes terminal holder insulator, bolts (cover lock, grounding and terminal holder insulator) and identification plate without certification.
O-Rings are packaged in packs of 12 units.
Including U-clamp, nuts, bolts and washers. Spare Parts List.
Section 5
TECHNICAL CHARACTERISTICS
Functional Specifications
Output Signal
Input Signal
Output Load Limitation
Digital only, Fieldbus, 31.25 Kbit/s voltage mode with bus power.
External Output Supply Voltage 3-45 Vdc.
Bus power 9-32 Vdc.
Current consumption quiescent 12 mA.
Output impedance: non-intrinsic safety from 7.8 KHz - 39 KHz should be greater or equal to 3
KOhm.
Intrinsic safety output impedance (assuming an IS barrier in the power supply) from 7.8 KHz - 39
KHz should be greater or equal to 400 Ohm.
Optional 4 digit LCD indicator.
Power Supply
Indication
Hazardous Area Certification
Explosion-proof and intrinsically safe (ATEX (NEMKO and DEKRA EXAM), FM, CEPEL, CSA and
NEPSI).
Designed to comply with European Regulations (ATEX 94/9/EC and LVD 2006/95/EC).
Temperature Limits
Humidity Limits
Turn-on Time
Update Time
Configuration
Operation:
Storage:
Display:
-40
-40
-10
-40
to
to
to
to
85 C
120 C
60 C
85 C
(-40
(-40
( 14
(-40
to
to
to
to
185 F)
250 F)
140 F) operation
185 F) without damage.
0 to 100% RH.
Approximately 10 seconds.
Approximately 0.5 second.
Basic configuration may be done using local adjustment magnetic tool if device is fitted with
display. Complete configuration is possible using remote configurator (Ex.: ProfibusView,
AssetView for FDT or Simatic PDM).
Performance Specifications
Accuracy
Ambient Temperature
Effect
Output Power Supply
Effect
Vibration Effect
Electromagnetic
Interference Effect
0.1%.
For a 10 C variation: 0.05%.
0.005%/V
Complies with SAMA PMC 31.1 standard.
Designed to comply with European Directive EMC 2004/108/EC.
Physical Specifications
Hardware
Electrical Connection
Material of Construction
Mounting
Weight
Physical: according to IEC 61158-2 and conformity with the FISCO model.
1/2-14 NPT, PG 13.5 or M20 x 1.5.
Injected low copper aluminum with polyester painting or 316 Stainless Steel housing, with Buna
N O-rings on covers.
With an optional bracket can be installed on a 2" pipe or fixed on a wall or panel.
Without display and mounting bracket: 0.80 kg.
Add for digital display: 0.13 kg.
Add for mounting bracket: 0.60 kg.
5.1
Ordering Code
MODEL
FI303
Without Indicator
With Digital Indicator
COD. Mounting Bracket
0
Without Bracket
1/2 - 14 NPT
M20 X 1.5
PG 13.5 DIN
SPECIAL OPTIONS
COD. Housing
H0
Aluminum (IP/TYPE)
H1
H2
H3
I4
I5
I6
Without Certification
IE
NEPSI: Ex-ia
COD. Painting
P0
P3
Black Polyester
P4
White Epoxi
P5
Yellow Polyester
P8
Without Painting
P9
PC
PG
3 output - 4 to 20 mA
COD. Tag Plate
J0
With tag
J1
Blank
J2
FI303
5.2
See Notes
TYPICAL MODEL
Appendix A
CERTIFICATIONS INFORMATION
Manufacturing Location Approved
Smar Equipamentos Industriais Ltda Sertozinho, So Paulo, Brasil.
Use shielded, twisted-pair cable for powering the instrument and signal wiring.
Keep the shield insulated at the instrument side, connecting the other one to the ground.
The transmitter has a double protection. In this case the transmitter shall be fitted with appropriate certified cable entries
Ex-d and the electric circuit supplied by a certified diode safety barrier as specified for the protection Ex-ia.
Environmental Protection
Enclosure Types (Type X): Supplementary letter X meaning special condition defined as default by Smar the following:
Saline Environment approved - salt spray exposed for 200 hours at 35C. (Ref: NEMA 250)
Ingress protection (IP W): Supplementary letter W meaning special condition defined as default by Smar the following: Saline
Environment approved - salt spray exposed for 200 hours at 35C. (Ref: IEC60529)
Ingress protection (IP x8): Second numeral meaning continuous immersion in water under special condition defined as
default by Smar the following: 1 Bar pressure during 24hours. (Ref: IEC60529)
A.2
Certifications Information
Model FI303 Fieldbus Converter; supply 12-42V dc, 4-20mA; Enclosure Type 4/4X; Intrinsically safe with Fieldbus/FISCO Entity
parameters
@ Terminals + and -:
Vmax = 24 V, Imax = 380 mA, Pi = 5.32 W, Ci = 5 nF, Li = 12 uH;
@ Terminals 1 4:
Vmax = 30 V, Imax = 110 mA, Ci = 5nF, Li = 12 uH;
when connected through CSA Certified Safety Barriers as per Smar Installation Drawing 102A0559; Code T3C.
Note: Only models with stainless steel external fittings are Certified as Type 4X.
Special conditions for safe use:
Temperature Class T3C
Maximum Ambient Temperature: 40C (-20 to 40 C)
FM Approvals (Factory Mutual)
Intrinsic Safety (FM 3006959)
IS Class I, Division 1, Groups A, B, C and D
IS Class II, Division 1, Groups E, F and G
IS Class III, Division 1
Explosion Proof (FM 3006959)
XP Class I, Division 1, Groups A, B, C and D
Dust Ignition Proof (FM 3006959)
DIP Class II, Division 1, Groups E, F and G
DIP Class III, Division 1
Non Incendive (FM 3006959)
NI Class I, Division 2, Groups A, B, C and D
Environmental Protection (FM 3006959)
Option: Type 4X/6/6P or Type 4/6/6P
Special conditions for safe use:
Entity Parameters Fieldbus Power Supply Input (report 3015629):
Vmax = 24 Vdc, Imax = 250 mA, Pi = 1.2 W, Ci = 5 nF, Li = 12 uH
Vmax = 16 Vdc, Imax = 250 mA, Pi = 2 W, Ci = 5 nF, Li = 12 uH
4-20 mA Current Loop:
Vmax = 30 Vdc, Imax = 110 mA, Pi = 0,825 W, Ci = 5 nF, Li = 12 uH
Temperature Class T4
Maximum Ambient Temperature: 60C (-20 to 60 C)
NEMKO (Norges Elektriske MaterielKontroll)
Explosion Proof (Nemko 13 ATEX 1570)
Group II, Category 2 G, Ex d, Group IIC, Temperature Class T6, EPL Gb
Ambient Temperature: -20 to 60 C
Environmental Protection (Nemko 13 ATEX 1570)
Options: IP66W/68W
The Essential Health and Safety Requirements are assured by compliance with:
EN 60079-0:2012 General Requirements
EN 60079-1:2007 Flameproof Enclosures d
EXAM (BBG Prf - und Zertifizier GmbH)
Intrinsic Safety (DMT 00 ATEX E 065) - In Progress
Group I, Category M2, Ex ia, Group I, EPL Mb
Group II, Category 2 G, Ex ia, Group IIC, Temperature Class T4/T5/T6, EPL Ga
FISCO Field Device
Supply circuit for the connection to an intrinsically safe fieldbus-circuit:
Ui = 24Vdc, Ii = 380 mA, Pi = 5.32 W, Ci 5 nF, Li = neg
Parameter of the supply circuit complies with FISCO model according to EN 60079-27: 2008.
A.3
Output-signal-circuits; three 4-20 mA current sinks with common ground for external intrinsically safe supply
Effective internal capacitance Ci negligible
Effective internal inductance Ci negligible
Safety-relevant maximum values for certified intrinsically safe 4-20 mA current loop circuits as a function of ambient temperature
and temperature class;
Max. Ambient
temperature Ta
60C
50C
40C
Temperature
Class
T4
T5
T6
Voltage DC
Ui
28 V
28 V
28 V
Current
Ii
93 mA
93 mA
93 mA
Power
Pi
750 mW
750 mW
570 mW
The signal outputs are safely galvanically separated from the fieldbus circuit.
Ambient Temperature: -40C Ta 60C
The Essential Health and Safety Requirements are assured by compliance with:
EN 60079-0:2009 General Requirements
EN 60079-11:2007 Intrinsic Safety i
EN 60079-26:2007 Equipment with equipment protection level (EPL) Ga
EN 60079-27:2008 Fieldbus intrinsically safe concept (FISCO)
CEPEL (Centro de Pesquisa de Energia Eltrica)
Intrinsic Safety (CEPEL 97.0019X)
Ex ia, Group IIC, Temperature Class T4/T5, EPL Ga
FISCO Field Device
Entity Parameters:
Pi = 5.32 W, Ui = 30V, Ii = 380 mA, Ci = 5.0 nF, Li = Neg
Ambient Temperature:
-20 to 65C for T4
-20 to 50C for T5
Explosion Proof (CEPEL 97.0091)
Ex d, Group IIC, Temperature Class T6, EPL Gb
Maximum Ambient Temperature: 40C (-20 to 40 C)
Environmental Protection (CEPEL 97.0019X and CEPEL 97.0091)
Options: IP66/68W or IP66/68
Special conditions for safe use:
The certificate number ends with the letter "X" to indicate that for the version of FIELDBUS to current Converter model FI303
equipped with housing made of aluminum alloy, only can be installed in "Zone 0" if is excluded the risk of occurs impact or friction
between the housing and iron/steel itens.
The Essential Health and Safety Requirements are assured by compliance with:
ABNT NBR IEC 60079-0:2008 General Requirements
ABNT NBR IEC 60079-1:2009 Flameproof Enclosures d
ABNT NBR IEC 60079-11:2009 Intrinsic Safety i
ABNT NBR IEC 60079-26:2008 Equipment with equipment protection level (EPL) Ga
IEC 60079-27:2008 Fieldbus intrinsically safe concept (FISCO)
ABNT NBR IEC 60529:2005 Classification of degrees of protection provided by enclosures (IP Code)
NEPSI (National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation)
Intrinsic Safety (NEPSI GYJ071324)
Ex ia, Group IIC, Temperature Class T4/T5/T6
Supply terminals entity parameters:
Ui = 16 V, Ii = 250 mA, Pi = 2.0 W, Ci = 5 nF, Li = 0
A.4
Certifications Information
Terminals 1-4:
Pi = 0.75 W, Ui = 28 V, Ii = 93 mA, Ci = 0 nF, Li = 0
Ambient Temperature:
T4 40 C for Pi = 2.0W,
Pi = 750 mW
T4 60 C for Pi = 865 mW, Pi = 750 mW
T5 40 C for Pi = 990 mW, Pi = 750 mW
T6 40 C for Pi = 630 mW, Pi = 570 mW
A.5
NEPSI (National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation)
A.6
Certifications Information
Canadian Standards Association (CSA)
A.7
A.8
MARCIAL
MISSAWA
20 10 08 20 10 08
MARCIAL
MISSAWA
6
16 07 07 16 07 07
MOACIR
CASSIOLATO
5
07 05 03 07 05 03
MOACIR
CASSIOLATO
4
08 02 00 08 02 00
REV. DESIGN
APPROVED
ALT DE
0049/08
AREA
ALT DE
0004/07 28 03 95
ALT DE CUSTOMER:
0043/03
EQUIPMENT:
ALT DE
0015/00
MELONI
+
DRAWING
DESIGN
28
03
95
28
M.MISSAWA SINASTRE
VERIFIED
03
95
FI302/303
CONTROL DRAWING
28
03
FIELDBUS
GROUND BUS
4 to 20mA
I.S.
BARRIER
FIELDBUS
I.S.
BARRIER
OPTIONAL
SHIELDING
APPROVED
PELUSO
95
DRAWING N.
Voc
Isc
Po
24V
250mA
1,2W
Voc
Isc
Po
La
FIELDBUS
Ca
16V
250mA
2W
4-20mA
30V
Voc
110mA
Isc
POWER SUPPLY
POWER SUPPLY
ASSOCIATED APPARATUS
2-
56-
4-20mA
Ci=5nF Li=12uH
Vmax
30V
Imax
110mA
FIELDBUS
Ci=5nF Li=12uH
Vmax
24V
Imax
250mA
ENTITY VALUES:
FIELDBUS
APPROVAL.
PREVIOUS MANUFACTURER
BE SUBSTITUTED WITHOUT
4-
7-
3-
FM
HAZARDOUS AREA
1-
REQUIREMENTS:
Certifications Information
FM
APPROVED
smar
O.S.
102A0080
REV
SH.01/01
07
A.9
A.10
Appendix B
SRF Service Request Form
Converter from Fieldbus to 4-20mA
GENERAL DATA
Model:
Serial Number:
TAG:
FI302 ( )
FI303 ( )
_____________________________________________________________________________________________________
_____________________________________________________________________________________________________
How many
channels are
used in IF?
1( )
Configuration:
Magnetic Tool ( )
2( )
PC ( )
3( )
Software: _____________
INSTALLATION DATA
Type/Model/Manufacturer of device
connected to the channel 1:
______________________________________________________________________________________
Type/Model/Manufacturer of device
connected to the channel 2:
______________________________________________________________________________________
Type/Model/Manufacturer of device
connected to the channel 3:
______________________________________________________________________________________
PROCESS DATA
Hazardous Area
Classification:
Types of Interference
Without interference ( )
presents in the area:
Ambient
Temperature:
Temperature ( )
Vibration ( )
Others: ____________________________________
OCCURRENCE DESCRIPTION
_____________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________
SERVICE SUGGESTION
Adjustment ( )
Cleaning ( )
Preventive Maintenance ( )
Update / Up-grade ( )
Other: _______________________________________________________________________________________________________________
USER INFORMATION
Company: ___________________________________________________________________________________________________________
Contact: _____________________________________________________________________________________________________________
Title: ________________________________________________________________________________________________________________
Section: _____________________________________________________________________________________________________________
Phone: _________ _________________________
_________ _________________________
E-mail: ________________________________________________________________________
Extension: __________________________
Date: ______/ ______/ _________________
B.1
Returning Materials
Should it be necessary to return the converter to Smar, simply contact your local Smar office
informing the defective equipment serial number and dispatch it to our factory.
For easier analysis and faster solution of the problem, the returned material should include the
documentation with a description of the failure observed in the field and the circumstances that
caused it. Other information, such as the installation site, type of measure taken and the process
conditions are also important for a prompt evaluation.
B.2