FIRE ALARM SYSTEM IS A DEFERRED APPROVAL SUBMITTAL

MOUNTING
HEIGHT
1. CONTRACTOR SHALL VISIT JOB SITE AND THOROUGHLY EXAMINE ALL EXISTING CONDITIONS WHICH MAY AFFECT WORK PRIOR TO
SUBMITTING BID. NO ADDITIONAL COSTS WILL BE CONSIDERED FOR CONTRACTORS FAILURE TO DO SO. EXPOSED PARTS OF
SWITCHBOARDS, PANELS, TRANSFORMERS, BOXES, CONDUITS, ETC. WERE NOT OPENED DURING THE DESIGN PHASE OF THE
PROJECT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO IMMEDIATELY NOTIFY THE ENGINEER AND/OR OWNER IF INACCURACIES
OR OTHER DISCREPANCIES BETWEEN THE DRAWINGS AND ACTUAL FIELD CONDITIONS ARE FOUND.

FIXTURE TYPE
CEILING OUTLET
CIRCUIT NUMBER
SWITCH LEG
RECESSED FIXTURE

MOTOR, NUMBER INDICATES HORSEPOWER

AS NOTED

RECESSED FIXTURE FED FROM EMERGENCY CIRCUIT


WALL MOUNTED FIXTURE
2X4 FIXTURE
2X4 FIXTURE FED FROM EMERGENCY CIRCUIT ("EM")
1X4 FIXTURE
STRIP FIXTURE
EXIT LIGHT FIXTURE WITH MINIMUM 90 MINUTE BATTERY
BACKUP
DENOTES WALL MOUNTED
DENOTES ILLUMINATED FACE
DENOTES ARROW DIRECTION
EMERGENCY BATTERY UNIT WITH TWO HEADS AND
MINIMUM 90 MINUTE BATTERY

MS

CSFD

POLE MOUNTED LIGHT FIXTURE

48" UNO

STARTER

48" UNO

COMBINATION STARTER DISCONNECT SWITCH

48" UNO

VARIABLE FREQUENCY DRIVE

48" UNO

VARIABLE FREQUENCY DRIVE WITH INTEGRAL DISCONNECT


SWITCH

48" UNO

3. DETERMINE ROUTING OF CONCEALED FEEDERS AND HOMERUNS IN COOPERATION WITH OTHER TRADES TO SIMPLIFY
INSTALLATION WHEREVER POSSIBLE BUT SUBJECT TO APPROVAL OF ENGINEER FOR VISUAL AND STRUCTURAL REASONS.

THERMOSTAT (BY OTHERS). ELECTRICAL CONTRACTOR TO


PROVIDE 1/2"C.O. FROM DEVICE TO REQUIRED MECHANICAL
EQUIPMENT PER HVAC DRAWINGS. VERIFY FINAL LOCATION
PRIOR TO ROUGH-IN.

54" UNO

4. ALL CONDUCTORS SHALL BE COPPER, TYPE THWN-2/THHN 90 DEGREE INSULATION. ALL LUGS SHALL BE 75 DEGREE RATED,
MINIMUM.
5. USE OF FLEXIBLE CONDUIT IS NOT ALLOWED EXCEPT FOR LENGTHS UP TO 6 FEET FOR FINAL CONNECTION TO LIGHTING FIXTURES
OR VIBRATING EQUIPMENT. ALL CONDUITS SHALL INCLUDE A GROUND WIRE SIZED PER CODE. CONCEALED CONDUIT SHOULD BE
INSTALLED WHEREVER POSSIBLE. IF EXPOSED CONDUITS AND BOXES ARE INSTALLED, THEY SHALL BE PAINTED TO MATCH THE
SURFACES WHERE INSTALLED WHEN VISIBLE TO THE PUBLIC.

JUNCTION BOX IN CEILING. MAKE NECESSARY CONNECTION TO


VAV BOX. VERIFY FINAL LOCATION AND COORDINATE WITH
MECHANICAL CONTRACTOR.

VAV

2. IT IS THE INTENT OF THESE PLANS AND SPECIFICATIONS THAT A COMPLETE AND WORKABLE ELECTRICAL INSTALLATION BE
PROVIDED FOR ALL THE EQUIPMENT DESCRIBED OR SHOWN AS BEING IN THIS CONTRACT. FURNISH ALL LABOR AND TOOLS
NECESSARY AND FURNISH AND INSTALL ALL APPARATUS, MATERIALS, EQUIPMENT AND COMPONENTS IN A MANNER COMPLYING
WITH ALL APPLICABLE CODES, INCLUDING ITEMS REQUIRED BUT NOT NORMALLY SHOWN, SUCH AS COUPLINGS, HANGERS,
BRACKETS, CLAMPS, JUNCTION BOXES, PULLBOXES, SMALL GUTTERS, CONNECTORS AND HARDWARE. ANY DISCREPANCIES
BETWEEN THE DRAWINGS AND THE CODE, OR RECOGNIZED STANDARDS SHALL BE BROUGHT TO THE ATTENTION OF THE
OWNER'S AUTHORIZED REPRESENTATIVE AND INSPECTOR OF RECORD PRIOR TO COMMENCING ANY WORK.

LOCKABLE DISCONNECT SWITCH

6. GREEN INSULATED COPPER GROUNDING CONDUCTOR SHALL BE INSTALLED AND CONNECTED TO EACH POWER OUTLET,
ENCLOSURE, POWER DEVICE, FIXTURE, ETC. THROUGHOUT THE SITE. THE RACEWAYS SHALL NOT BE RELIED UPON FOR
EQUIPMENT GROUNDING.

JUNCTION BOX IN CEILING WITH MOTOR RATED SWITCH WITH-IN


SIGHT OF DAMPER. MAKE NECESSARY CONNECTION TO
COMBINATION SMOKE FIRE DAMPER. VERIFY FINAL LOCATION
AND COORDINATE WITH MECHANICAL CONTRACTOR.

Project:

7. LABEL ALL RECEPTACLES, JUNCTION BOXES, PULLBOXES, DISCONNECT SWITCHES AND CONTROL DEVICES WITH THEIR SERVING
PANEL AND CIRCUIT NUMBER(S).

SLMC - 6TH. Floor


Remodel

8. PROVIDE FIRE STOPPING AT ALL CONDUIT PENETRATIONS OF CEILINGS AND WALLS AND BACK OF ELECTRICAL BOXES
COMPATIBLE WITH AND TO MAINTAIN THE FIRE RATING OF THE STRUCTURE.

SWITCH. SUBSCRIPT INDICATES CONTROLLING SWITCH


LEG. SUPERSCRIPT INDICATES THE FOLLOWING:
2
TWO POLE
3
THREE-WAY SWITCH
4
FOUR-WAY SWITCH
WP WEATHERPROOF
D
DIMMER
M
MANUAL MOTOR STARTER
K
KEY OPERATED
P
PILOT
OS OCCUPANCY SENSOR. "a,b" SUBSCRIPT
REPRESENTS DUAL RELAY SENSOR
VS
VACANCY SENSOR. "a,b" SUBSCRIPT
REPRESENTS DUAL RELAY SENSOR
LV
LOW VOLTAGE TYPE

48"

WALL MOUNTED PIR SENSOR, SINGLE RELAY


WALL MOUNTED PIR SENSOR, DUAL RELAY

PHONE OUTLET. PROVIDE DEEP 4S BOX WITH 1-GANG MUD RING


AND MINIMUM 3/4"C.O. WITH PULL CORD TO ABOVE CEILING IN
ACCESSIBLE SPACE.
COMBINATION PHONE/DATA OUTLET. PROVIDE DEEP 4S BOX
WITH 1-GANG MUD RING AND 1"C.O. WITH PULL CORD TO ABOVE
CEILING IN ACCESSIBLE SPACE.

18" UNO
9. COORDINATE THE ELECTRICAL WORK WITH THE WORK OF OTHER TRADES.

52" UNO

18" UNO

48"
48"

NURSE CALL STAFF EMERGENCY STATION

48" UNO

CEILING MOUNTED ULTRASONIC OCCUPANCY SENSOR

NURSE CALL CODE BLUE STATION

48" UNO

CEILING MOUNTED POWER PACK

NURSE CALL LIGHT - 1 WHITE LAMP

90" UNO

TV OUTLET

84" UNO

DUPLEX RECEPTACLE WITH GROUND FAULT


INTERRUPTER

18" UNO

CT

DUPLEX RECEPTACLE ABOVE COUNTER. COORDINATE


MOUNTING HEIGHT IN FIELD WITH CASEWORK.

TOP OF COUNTER

WP

GFI RECEPTACLE WITH WEATHERPROOF COVER

18" UNO

CEILING RECEPTACLE

18" UNO

RECEPTACLE ON EMERGENCY CIRCUIT

18" UNO

DEDICATED 20A. RECEPTACLE

18" UNO

FLOOR OUTLET
SPECIAL PURPOSE RECEPTACLE

18" UNO

DOUBLE DUPLEX RECEPTACLE

18" UNO

11. WHERE ANCHORAGE DETAILS ARE NOT SHOWN ON DRAWINGS, THE FIELD INSTALLATION SHALL BE SUBJECT TO THE APPROVAL
OF THE STRUCTURAL ENGINEER AND THE INSPECTOR.

Client:

Success Healthcare 1
LLC d/b/a Silver Lake
Medical Center

14. ALL NECESSARY CLEARANCES SHALL BE MAINTAINED AT NEW ELECTRICAL EQUIPMENT PER LATEST NEC (WITH STATE
AMENDMENTS).
72" UNO

18" UNO

1711 West Temple Street


Los Angeles, CA 90026

13.NEW RECEPTACLES WITHIN 6' OF SINK SHALL BE GFCI TYPE. WEATHERPROOF RECEPTACLES SHALL BE GFCI TYPE.

A/V OUTLET. PROVIDE DEEP 4S BOX WITH 1-GANG MUD RING


AND 1"C.O. WITH PULL CORD TO ABOVE CEILING IN ACCESSIBLE
SPACE.

AV

10.ELECTRICAL CONTRACTOR TO VERIFY MOUNTING HEIGHTS OF OUTLET BOXES NEAR, ON OR WITHIN CABINETWORK, SINKS,
MIRRORS, COUNTERS, ETC. OUTLETS SHOWN ON PLANS ARE APPROXIMATE ONLY AND ANY IN CONFLICT WITH OTHER
OBSTRUCTIONS SHALL BE RELOCATED AT NO EXPENSE TO THE OWNER.

12. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE WEATHERPROOF.

FLOOR BOX WITH COMBINATION PHONE/DATA OUTLET. PROVIDE


1"C.O. WITH PULL CORD TO ABOVE CEILING IN ACCESSIBLE
SPACE.

DUPLEX RECEPTACLE
GFI

DATA OUTLET. PROVIDE DEEP 4S BOX WITH 1-GANG MUD RING


AND MINIMUM 1"C.O. WITH PULL CORD TO ABOVE CEILING IN
ACCESSIBLE SPACE.

15. ALL METALLIC OBJECTS THAT ENCLOSE ELECTRICAL CONDUCTORS OR THAT MIGHT BE ENERGIZED BY ELECTRICAL CURRENTS
MUST BE EFFECTIVELY GROUNDED. BOND ALL METAL EQUIPMENT PARTS SUCH AS ENCLOSURES, RACEWAYS, BUILDING METAL
STRUCTURE, WATER PIPING, GAS PIPING AND ANY OTHER EQUIPMENT LIKELY TO BECOME ENERGIZED. SHORT SECTIONS OF
METAL ENCLOSURES OR RACEWAYS USED TO PROVIDE SUPPORT OR PROTECTION OF LOW VOLTAGE (LESS THAN 70V) CABLE
ASSEMBLIES FROM PHYSICAL DAMAGE SHALL NOT BE REQUIRED TO BE GROUNDED. PROVIDE GROUND CONTINUITY AS REQUIRED
BY CURRENT APPLICABLE CODES.

1711 West Temple Street


Los Angeles, CA 90026

16.PROPERLY MOUNT EQUIPMENT TO FLOOR WITH REQUIRED HARDWARE FOR SEISMICALLY RESTRAINING EQUIPMENT AGAINST
SEISMIC FORCES IN ANY DIRECTION.
17.MATERIALS, PRODUCTS, DEVICES, OR FIXTURES INCLUDED IN THESE CONSTRUCTION DOCUMENTS MUST BE NEW AND MUST MEET
OR EXCEED THE REQUIREMENTS OF CALIFORNIA ELECTRICAL CODE (CEC), AMERICAN NATIONAL STANDARD INSTITUTE (ANSI),
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE), NATIONAL ELECTRICAL MANUFACTURING ASSOCIATION (NEMA),
CALIFORNIA ADMINISTRATIVE CODE: TITLE 24, CITY OF ANAHEIM, ADOPTED ELECTRICAL ORDINANCE.

CCTV CAMERA OUTLET. PROVIDE MINIMUM 1/2"C.O. WITH PULL


CORD TO CCTV MONITORING EQUIPMENT. COORDINATE WITH
SECURITY VENDOR.
CARD READER

18.NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE
DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT.
48"

19. ALL ELECTRICAL WORK SHALL COMPLY WITH CURRENTLY ADOPTED NATIONAL ELECTRICAL CODE (WITH STATE AMENDMENTS)
AND LOCAL JURISDICTION CODE.
20.OUTLET BOXES LOCATED ON OPPOSITE SIDES OF RATED WALLS SHALL BE SEPARATED PER DETAIL 2/E-002, REGARDLESS OF
LOCATIONS SHOWN ON DRAWING.

Stamp:

SEE NOTE INDICATED BY NUMBER


SEE EQUIPMENT SCHEDULE FOR MORE INFORMATION

21.THE INTENT OF THE CONSTRUCTION DOCUMENTS IS TO RECONSTRUCT THE HOSPITAL BUILDING IN ACCORDANCE WITH THE 2013
CBSC. SHOULD ANY CONDITION DEVELOP NOT COVERED BY THE APPROVED CONSTRUCTION DOCUMENTS, WHEREIN THE
FINISHED WORK WILL NOT COMPLY WITH THE 2013 CBSC, AMENDED CONSTRUCTION DOCUMENTS (ACDS) DETAILING AND
SPECIFYING THE REQUIRED WORK SHALL BE SUBMITTED TO AND APPROVED BY OSHPD BEFORE PROCEEDING WITH THE WORK.

CONDUIT IN CEILING, FLOOR OR WALL AS REQUIRED BY


FIELD CONDITIONS
CONDUIT IN FLOOR

22.SUPPORTS AND ATTACHMENTS OF ALL EQUIPMENT TO BE INSTALLED AS A PART OF THIS PROJECT SHALL BE DETAILED ON
CONSTRUCTION DOCUMENTS, EXCEPT THOSE EXEMPT BY THE 2013 CBC SECTION 1616A.1.18. EQUIPMENT SUPPORTS AND
ATTACHMENTS SHALL BE APPROVED BY THE APPROPRIATE DESIGN PROFESSIONAL OF RECORD (DPR) AND OSHPD AS A PART OF
FIELD REVIEWS /OBSERVATIONS. THE INSPECTOR OF RECORD (IOR) SHALL ASSUME THAT THE ABOVE REQUIREMENTS ARE
ENFORCED
23.PROVIDE QUANTITY OF #12 CONDUCTORS IN 1/2" CONDUIT MINIMUM TO OBTAIN SWITCHING AND POWER FEED CIRCUITING AS
SHOWN. ALL BRANCH CIRCUITS SHALL INCLUDE A GROUND CONDUCTOR.

2013 CALIFORNIA ADMINISTRATIVE CODE (CAC)


PART 1, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2013 CALIFORNIA BUILDING CODE (CBC)
PART 2, TITLE 24, CCR BASED ON THE 2012 INTERNATIONAL BUILDING CODE (IBC)
2013 CALIFORNIA ELECTRICAL CODE (CEC)
PART 3, TITLE 24, CCR BASED ON THE 2011 NATIONAL ELECTRICAL CODE (NEC)
2013 CALIFORNIA MECHANICAL CODE (CMC)
PART 4, TITLE 24, CCR BASED ON THE 2012 UNIFORM MECHANICAL CODE (UMC)

JUNCTION BOX

2013 CALIFORNIA PLUMBING CODE (CPC)


PART 5, TITLE 24, CCR BASED ON THE 2012 UNIFORM PLUMBING CODE (UPC)

TRANSFORMER (GROUND PER CEC)


1. SUPPORT AND BRACING FOR NEW CONDUIT SHALL BE PROVIDED PER OPM-0043-13 MASON SEISMIC RESTRAINT COMPONENTS
FOR SUSPENDED UTILITIES OR OTHER APPROVED OSHPD OPM. THE EXISTING ROOF STRUCTURE CONSISTS OF 2X WOOD
FRAMING SPANNING TO WOOD OR STEEL BEAMS PER STRUCTURAL PLANS. SUPPORT AND BRACING DETAILS PROVIDED NEED TO
INCLUDE CONNECTION TO WOOD FRAMING AND ANY SUPPLEMENTAL FRAMING REQUIRED.
2. PRE-APPROVED PIPES, DUCTS, AND CONDUITS SEISMIC BRACING
A. LAYOUT DRAWINGS OF THE SUPPORTS, ATTACHMENTS, AND BRACING SYSTEMS IN ACCORDANCE WITH THE PRE-APPROVAL
SHALL BE SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL (RDP) IN RESPONSIBLE CHANGE OF THE PROJECT FOR
REVIEW TO VERIFY THAT THE DETAILS ARE IN CONFORMANCE WITH THE CODE REQUIREMENTS. THE LAYOUT DRAWINGS SHALL
AS A MINIMUM SATISFY THE REQUIREMENTS OF ASCE 7 SECTION 13.6 AS MODIFIED BY THE CBC 2013 SECTION 1616A.
a.) THE STRUCTURAL ENGINEER OF RECORD (SEOR) SHALL VERIFY THAT THE SUPPORTING STRUCTURE IS ADEQUATE FOR
THE FORCES IMPOSED ON IT BY THE SUPPORTS, ATTACHMENTS, AND BRACES INSTALLED IN ACCORDANCE WITH THE
PRE-APPROVAL IN ADDITION TO ALL OTHER LOADS.
b.) THE SEOR SHALL FORWARD THE SUPPORTS, ATTACHMENTS, AND BRACING DRAWINGS (INCLUDING APPROVED AMENDED
CONSTRUCTION DOCUMENTS FOR SUPPLEMENTARY FRAMING WHERE REQUIRED) TO THE DISCIPLINE IN RESPONSIBLE
CHARGE WITH A NOTATION INDICATING THAT THE DRAWINGS HAVE BEEN REVIEWED AND ARE IN GENERAL
CONFORMANCE WITH THE PRE-APPROVAL AND THE DESIGN OF THE PROJECT.
c.)
d.) THE REGISTERED DESIGN PROFESSIONAL (RDP), OTHER THAN SEOR, MAY PROVIDE THE SHOP DRAWING STAMP FOR
SMALL PROJECTS AT THE DISCRETION OF THE OSHPD DISTRICT STRUCTURAL ENGINEER.
B.

C.

THE SEOR SHALL DESIGN ANY SUPPLEMENTARY FRAMING THAT IS NEEDED TO RESIST THE LOADS, MAINTAIN STABILITY AND/OR
IS REQUIRED FOR INSTALLATION OF PRE-APPROVED SYSTEM.
THE SUPPLEMENTARY FRAMING SHALL BE SUBMITTED TO OSHPD AS AN AMENDED CONSTRUCTION DOCUMENTS (ACD).
THE LAYOUT DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE SUBMITTED TO THE OSHPD TO REVIEW:
1) STRUCTURE SUPPORTING THE DISTRIBUTION SYSTEM HAS ADEQUATE CAPACITY;
2) SEISMIC DESIGN FORGES (FP) ARE IN ACCORDANCE WITH THE CBC 2013; AND
3)
a. SIZE OF DISTRIBUTION SYSTEM COMPONENTS,
b. SPACING OF BRACING AND FLEX JOINTS, AND
c. SUBSTRATE FOR ATTACHMENTS

D.

THE LAYOUT DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE KEPT ON THE JOBSITE AND CAN THEN BE USED FOR
INSTALLATION OF THE SUPPORT AND BRACING.
OSHPD FIELD STAFF WILL REVIEW THE INSTALLATION.

E.

A COPY OF THE CHOSEN BRACING SYSTEM(S) INSTALLATION GUIDE/OPM MANUAL SHALL BE ON THE JOBSITE PRIOR TO
STARTING THE INSTALLATION OF HANGER AND/OR BRACES.

F.

COMPONENTS OF TWO OR MORE PRE-APPROVED BRACING SYSTEMS SHALL NOT BE MIXED.


ONLY ONE PRE-APPROVED BRACING SYSTEM MAY BE USED FOR A RUN OF PIPE, DUCT, OR CONDUIT.
ANY SUBSTITUTION OF COMPONENTS OF AN OPM SYSTEM SHALL REQUIRE OSHPD REVIEW AND APPROVAL.

2013 CALIFORNIA FIRE CODE (CFC)


PART 9, TITLE 24, CCR BASED ON THE 2012 INTERNATIONAL FIRE CODE (IFC)

Drawing Title:

ELECTRICAL TITLE
SHEET

SINGLE LINE DIAGRAM & OVERALL FLOOR PLAN

PDA Project No.:


Date:
Phase:
Checked By:
Drawn By:
Plan Check No.:
Revisions:

1
2

398-15-200
11/02/2015
CD
JJB
ALH, JJS
S153113-19-00

DATE
12/1/2015
3/1/2016

DESCRIPTION
OSHPD SUBMITTAL
OSHPD BACKCHECK 1
5/27/2016 OSHPD BACKCHECK 2

Agency Approval:

Drawing No.:

E-001