37-113

06-02-08 -R4

CERTIFIED
A
1470
203
406
152

1016

152

CONCRETE INSERTS

FOR 1/2" DIA. BOLT

PLAN

100

F.G.

F.G.

F.G.

PLUGGED
KNOCKOUT
HOLES

1219

50 DIA.
LIFTING HOLE

150

COMPACTED 20mm (3/4")

SECTION B-B

CLEAN CRUSHED STONE

SECTION A-A
NOTE :
1. ALL DIMENSIONS ARE SHOWN IN MILLIMETRES.
2. FOUNDATION TO BE PRECAST CONCRETE PAD. MANUFACTURER WILL DELIVER THE UNIT
TO THE SITE.
3. COMPLETE THE EXCAVATION AND PROVIDE BEDDING CONSISTING OF MIN. 150 mm LAYER
OF

THOROUGHLY

COMP

4. PLACE BACKFILL CONSISTING OF CLEAN EARTH, SAND, OR PEA GRAVEL IN THOROUGHLY


COMPACTED LAYERS.
5. PAD LOCATION TO BE KEPT CLEAR OF OBSTRUCTIONS FOR ACCESS BY HYDRO ONE
BRAMPTON PERSONNEL AND EQUIPMENT.
6. INSTALL 4-10 GROUND RODS AND MIN. 2/0 STRANDED COPPER GROUND WIRE.
REFER TO STD. 41-10.

CHECKED:

----------------------

APPROVED:

---------------------

ORIGINAL ISSUE:

SEPT. 23, 1991

INSTALLATION OF PRECAST
FOUNDATION FOR
1 PH PADMOUNT TRANSFORMER